  • LGE Internal Use Only

    HVAC & Energy Solution

    25,May, 2011

    BMS Gateway Introduction

    AE Control Lab. AC Control 2Gr.Haejin Kim([email protected])

    Contents

    1. Network Structure2. V-Net Line Up3. What is BMS?4. BMS Biz Process5. Lon Work Gateway

    - Function- Installation method- Intro. to xif File & JMT List

    6. BAC Net Gateway- Function- Installation method- Intro. to JMT List

    7. Regarding AHU8. Other BMS GW9. Practice

  • LGE Internal Use Only

    HVAC & Energy Solution

    VENTRAC

    CACPAC

    1. Network Structure

    Manage-

    ment

    (Integration)

    & Control

    Device

    AC Manager

    ACP

    AC Smart AC Ez.(ing)

    TMSBMS

    485 Gateway

    BACnet

    LonWork/BACnet

    Multi-V

    LGAP

    AC Station

    (FCS)

    DDC

    HVAC

    Facility

    Lighting

    Web

    Gateway

    (?)

    Ethernet, TCP/IP

    AC Smart

    (?)

    Ethernet, TCP/IP Ethernet, TCP/IP

    LonWork

    IO Module

    (AI/AO/DI/DO)

    Modbus

    (ing)

  • LGE Internal Use Only

    HVAC & Energy Solution

    2. V-net Product Line Up

    Central

    Controller

    Simple Central

    Controller

    ACP

    Aircon Base

    Controller

    PQCSB101S0

    PDI(Power

    DistributionIndicator)

    PQCPA11A0E (Version 4)PQCPB11A0E(With IO)

    PQCSC101S0

    PQCSS520A0EPQCSSA20A0

    PQCSW320A0EPQCSW320A1E

    AC Manager

    AC Smart

    Others

    BMS GatewayBACnet

    PQNFB17B0LonWorks

    PQNUD1S00

    PQCSA001T0

    128

    Exp. Kit

    On/Off Signal Thermostat

    PI485

    3rd

    Link

    PQCSD130A0

    PHNFP14A0 PSNFP14A0PMNFP14A0

    PQCSE440U0

    Do Kit

    PQNFP00T0

    Dry Contact

    PMNFP14A1

    PQNFB16A1

    Web Based Controller

    PC Software Program, Max 16 ACP Communication

    Function

    ControllerScheduler

    PQDSA/PQDSB (AC220V) PQDSBC

    PQDSBNGCM1

    PQDSB1(AC24V)

    Option

    PQCSE342A0

    AC-EZ

    (AC-EZ)

    PQCSE341A0

    Web Web +PDI

    KNX(Under Testing)

    Modbus(UnderDeveloping)

    ODU DC

    PQDSBCDVM0

    RCU(Room Control Unit)PQDSBCGCD0

  • LGE Internal Use Only

    HVAC & Energy Solution

    3. What is BMS ?

    Building management system (BMS) means a system designed to control, monitor and optimize various building services, including lighting, heating, ventilation, cooling,

    swimming pool pumps and water use in cooling towers.

    /BNU-BN

  • LGE Internal Use Only

    HVAC & Energy Solution

    1. Test & Commissioning of Multi-V2. Test & Commissioning of the LonWorks Gateway

    1. Creation of control address table 2. Making Multi-V Lon Works Point list on project and pass it to BMS

    1. Check BMS maker and confirm interoperability (JMT List on Global Web Site)2. Check and list models of Multi-V3. Prepare document: Point List of Lon Works Gateway (installation manual)

    .xif File for Lon Work Gateway (Global Web Site)

    Test & Commissioning

    1. Technical meeting and JMT if necessary

    Inquiry

    Hand in estimate

    Receive order

    InstallationRefer to installation manual

    BMS Maker Engineering Option :

    1. In Real Site data transition

    2. Pre_Engineering by using .xif File

    4. BMS Biz Process / Lon Works 2. BMS Biz Process

  • LGE Internal Use Only

    HVAC & Energy Solution

    1. Test & Commissioning of Multi-V2. Test & Commissioning of the BAC Net Gateway

    1. Creation of control address table 2. Making Multi-V BAC Net object list on project and pass it to BMS

    1. Check BMS maker and confirm interoperability (JMT List on Global Web Site)

    2. Check and list models of Multi-V

    3. Prepare document: PICS of BAC Net Gateway (Refer to installation manual)

    Test & Commissioning

    1. Technical meeting and JMT if necessary

    Inquiry

    Hand in estimate

    Receive order

    InstallationRefer to installation manual

    PICS : BAC Net Protocol Implementation Conformance Statement

    4. BMS Biz Process / BAC Net 2. BMS Biz Process

  • LGE Internal Use Only

    HVAC & Energy Solution

    4. BMS Biz Process

    JMT(Joint Matching Test) has to be done at BMS maker side

    Why :

    - BAC Net has many choices of transmission flexibility.

    - So, to minimize working procedure at local site

    - Necessary for every independent BMS

    - In the case that the BMS has updated, JMT will be required

  • LGE Internal Use Only

    HVAC & Energy Solution

    BNU-LW (LonWorks)

    5. LonWorks Gateway

    Model : PQNFB16A1

    1. Function2. Installation method3. Intro. to xif File & JMT List

  • LGE Internal Use Only

    HVAC & Energy Solution

    5. LonWorks Gateway

    Function(BMS Control/Monitoring Point)

    Air conditioner Ventilation

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.1 Function (Point List For BMS Engineering)

    Air conditioner

    SNVT : Standard Network Variable Typenvi : network variable input (command), nvo : network variable output (monitoring)

  • LGE Internal Use Only

    HVAC & Energy Solution

    Ventilation

    5.1 Function (Point List For BMS Engineering)

    Point

    No.Name

    Object Name

    (nn : Air conditioner and

    ventilation group/indoor

    unit address

    Object

    Type

    Unit

    Code 0 Code 1 code2 Code3Code

    5Code 9

    1ON/OFF

    (setting)SNVT_switch nviOnOff_nn Input Stop Operation

    2 ON/OFF (status) SNVT_switch nvoOnOff_nn Output Stop Operation

    3 Lock (setting) SNVT_switch nviLock_nn input Cancel Setting

    4 Lock( status) SNVT_switch nvLock_nn Input Cancel Setting

    5Operation Mode

    (setting)

    SNVT_hvac_modenviHeatCo

    ol_nnoutput Auto

    Heat

    exchangeNormal

    6Operation Mode

    (status)

    SNVT_hvac_mode

    nviHeatCool_nnOutput Auto

    Heat

    exchangeNormal

    7Fan speed

    (setting)

    SNVT_switch

    nviFanSpeedCmd_nnInput

    LowHigh

    Very

    high

    8Fan speed

    (status)

    SNVT_switch

    nvoFanSpeed_nnoutput Low High

    Very

    high

    9 Error CodeSNVhvac_status

    nvoUnitStatus_nnoutput Refer to the LG Air Conditioner Error Code.

    10User Mode

    (setting)SNVT_count nviUser_nn Output Quick

    Power

    saveHeat

    11User Mode

    (status)SNVT_count nvoUser_nn output Quick

    Power

    saveheat

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.2 LonWorks Gateway / Self Checking

    Function (Web Access Commissioning )

    Internet

    Internet Explorer

  • LGE Internal Use Only

    HVAC & Energy Solution

    STEP 1. Set unit address Assign a unique address to the unit being connected address must be 00~3F

    STEP 2. Set PI485 Install one PI485 for each outdoor unit, and set the DIP switch.In Multi V Plus II system(Outdoor & Indoor series 2, Remocon : New Type),PI485 Installation does not need.

    STEP 3. Connect PI485 and Lon Works Gateway through the RS485 line.

    STEP 4. Login to LonWorks Gateway through the Internet Explorer,Check if all Indoor units are connected

    Installation process

    Refer to the Simple Central Controller Installation Method

    Refer to the Simple Central Controller Installation Method

    5.3. LonWorks Gateway /

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.3. LonWorks Gateway

    5.3.1 Installation method(system connection)

    [ Indoor Address : 00~3F ]

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.3. LonWorks Gateway

    5.3.2 Wiring LonWorks Gateway to RS485 Line

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.3. LonWorks Gateway

    5.3.3 Check the connection through Web Access

    192.168.1.101

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.3. LonWorks Gateway

    5.3.4 Check the connection through Web Access

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.3. LonWorks Gateway

    5.3.5 Check the connection through Web Access

  • LGE Internal Use Only

    HVAC & Energy Solution

    Commissioning Test

    LGAP

    Using web browser

    LonWorks

    BMS

    BMS Engineering SideLG Engineering Side

    1. Creating the A/C points.2. Test of all units and operations.

    1. Confirm A/C connection2. Test of operations

    IP : 192.168.1.200

    Subnet : 255.255.255.0

    IP : 192.168.1.101

    Subnet : 255.255.255.0

    LonWorksRouter

    5.3 Installation process

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.4 .xif File & JMT List

    - .xif File is for pre_engineering of BMS Company

    - If this file is send to BMS company, BMS company can make BMS Graphic &

    control windows (we call it pre-engineering)

    - Can download on the Global Web site

    ( www.lgeaircon.com > Customer support > Download > Software )

    - It include LG Air_conditioner Point List(control/monitoring property & data)

    .xif File

    JMT(Joint Matching Test) List of PQNFB16A1

    No BMS Maker Model Version Date of JMT Location of JMT

    1 T.A.C Vista 2005/09 Netherland

    2 Andover 2006/12 Korea(Seoul)

    3 SIEMENS RX Tool 2007/07 France

    4 TRANE NL Util Node utility 4.5.8 2008/07 Munchen,German

    5

    List will be upgraded without inform, can refer on the Global Web site

    ( www.lgeaircon.com > Customer support > Download > Software )

  • LGE Internal Use Only

    HVAC & Energy Solution

    5.4 Lonwork Commissioning Methods

    LGAPLonWorks

    BMS

    1) Using Upload from device

    2) Using XIF File for pre-engineering

    Commissioning is to get device information of LonGW.There are 2 commissioning methods in LonGW.- One is upload from device, the other is using XIF

    Deviceinformation

    LGAPLonWorks

    BMS

    Deviceinformation

    XIF(Dev Info)

  • LGE Internal Use Only

    HVAC & Energy Solution

    BNU-BAC(BAC Net)

    Model : PQNFB17B0

    6. BAC Net Gateway 4. BAC Net Gateway

    1. Concept2. Basic theory

    1) Object2) Device Instance No3) Instance No of indoor4) Service5) BMS Communication sequence

    3. Web access test4. Installation Process5. Wireshark HOWTO6. VTS

  • LGE Internal Use Only

    HVAC & Energy Solution

    6. BAC Net Gateway / Concept

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.1 BAC Net Gateway / Concept

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 BAC Net Gateway/Basic Theory/1.Object

    propertyTemperature sensor

    Object example Important Property (need do remember..)

    - object name, object type, present value

    Q1

  • LGE Internal Use Only

    HVAC & Energy Solution

    Point

    NoName Object Name Object Type Indoor Vent

    1 ON/OFF (setting) StartStopCommand_XX Binary Output 0 0

    2 ON/OFF (status) StartStopStatus_XX Binary Input 0 0

    3 Lock (setting) LockCommand_XX Binary Output 0 0

    4 Lock (status) LockStatus_XX Binary Input 0 0

    5 Filter Sign FilterSign_XX Binary Input X 0

    6 Filter Sign reset FilterSignReset_XX Binary Value X 0

    7 Operation Mode (setting) ModeCommand_XX Multistate Output 0 0

    8 Operation Mode (status) ModeStatus_XX Multistate Input 0 0

    9 Swing (setting) SwingCommand_XX Binary Output 0 X

    10 Swing (status) SwingStatus_XX Binary Input 0 X

    11 Fan speed (setting) FanSpeedCommand_XX Multistate Output 0 0

    12 Fan speed (status) FanSpeedStatus_XX Multistate Input 0 0

    13 Set Room Temperature SetRoomTemp_XX Analog Value 0 X

    14 Room Temperature RoomTemp_XX Analog Input 0 X

    15 Alarm Alarm_XX Binary Input 0 0

    16 Error Code MalfunctionCode_XX Analog Input 0 0

    17 User Mode (setting) UserModeCommand_XX Multistate Output X 0

    18 User Mode (status) UserModeStatus_XX Multistate Input X 0

    6.2 Function(BMS Control/Monitoring Point)

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 Function(Object List)

    Point

    NO.Product Name

    Object Name

    (XXX : Unit address_

    Object

    Type

    Unit

    Inactive Active

    Text-0 Text-1 Text-2 Text-3 Text-4 Text-5

    1

    Indoor

    & Vent

    ON/OFF (setting) StartStopCommand_XXX BO Stop Start

    2 ON/OFF (status) StartStopStatus_XXX BI Stop Run

    3 Lock (setting) LockCommand_XXX BO Permit Prohibit

    4 Lock (status) LockStatus_XXX BI Permit Prohibit

    5

    Vent

    Filter Sign FilterSign_XXX BI Off On

    6 Filter Sign reset FilterSignReset_XXX BV Reset (OFF) Vold (On)

    7 Operation Mode (setting) ModeCommand_XXX MO Heat Exchange Auto Normal

    8 Operation Mode (status) ModeStatus_XXX MI Heat Exchange Auto Normal

    7

    Indoor

    Operation Mode (setting) ModeCommand_XXX MO Cool Dry Fan Auto Heat

    8 Operation Mode (status) ModeStatus_XXX MI Cool Dry Fan Auto Heat

    9 Swing (setting) SwingCommand_XXX BO Stop Run

    10 Swing (status) SwingStatus_XXX BI Stop Run

    11 Fan speed (setting)FanSpeedCommand_XX

    XMO Low Middle High Auto

    12 Fan speed (status) FanSpeedStatus_XXX MI Low Middle High Auto

    11Vent

    Fan speed (setting)FanSpeedCommand_XX

    XMO Low High Super High Auto

    12 Fan speed (status) FanSpeedStatus_XXX MI Low High Super High Auto

    13Indoor

    Set Room Temperature SetRoomTemp_XXX AV

    14 Room Temperature RoomTemp_XXX AI

    15 Indoor

    & Vent

    Alarm Alarm_XXX BI Normal Abnormal

    16 Error Code MalfunctionCode_XXX AI Reference LG original Error Code

    17

    Vent

    User Mode (setting)UserModeCommand_XX

    XMO

    Quick operation

    Energy saving

    Heat

    18 User Mode (status) UserModeStatus_XXX MIQuick

    operationEnergy saving

    Heat

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 BAC Net Gateway/Basic Theory/ 2.Device Instance & Network Number

    Device is processing unit of BACnet protocol.- One group is one device.

    Device instance No Indoor unit address range

    9000 00~0F

    9001 10~1F

    ; ;

    9015 F0~FF

    Device instance number must be unique.

    - Default first device instance number is 9000- Change device instance number to be unique if necessary

    (By using web page of BACnet GW)

    Starting device Instance No.

    (default no is 9000) Network(VNet) number must be unique

    - Default value is 10

    - Change Network number to be unique if necessary

    (by using web page of BACnet GW)

    network number setting (default = 10)

    Device instance number setting

    (default = 9000)

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 BAC Net Gateway/Basic Theory/ 2.Device Instance & Network Number example

    Device Instance Number & Network Number must be unique

    HUB

    BACnet/IP

    192.168.0.100

    Metasys ver4.1.5 192.168.0.106NAE Controller

    (Database, JAVA GUI)

    192.168.0.107

    BACnet GW#1

    10(Network Number)

    10

    DevNo:1000 DevNo:1001 DevNo:1015

    DevNo:2000 DevNo:2001DevNo:2015192.168.0.108

    BACnet GW#1

    (00-0F) (10-1F) (F0-FF)11

    (01)

    (00)

    (0F)

    (11)

    (10)

    (1F)

    (F1)

    (F0)

    (FF)

    Device (Group 0)

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 BAC Net Gateway/Basic Theory/3.Instance Number of Indoor

    2) Instance Number about Control & Monitoring Point of indoor unit Instance Numbering Rule

    type Indoor unit address Point no

    07815

    Type = 0(indoor), 1(vent)

    EX1) INDOOR UNIT = 0x01, startstop command (Point No = 1),instance number = 0x0101 = 257

    EX2) INDOOR UNIT = 0x01, lock status (Point No= 4),instance number = 0x0104 = 260

    16

    Point No. example

    16 bit

    17 bit

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.2 BAC Net Gateway/Basic Theory/4.Service

    Service Contents

    Who-Is Service used to determine the device object identifier and network addresses of all devices on the network

    I-Am Service used to respond to Who-Is service requests (device number)

    ReadProperty Request the value of one property of one BACnet Object

    ReadPropertyMultiple Request the values of one or more specified properties of one or more BACnet objects.

    WriteProperty Modify the value of a single specified property of a BACnet object

    WritePropertyMultiple Modify the value of one or more specified properties of a BACnet object.

    Basic BACnet Service

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.3 BAC Net Gateway/Basic Theory/Service/4.WHO-IS and I-AM

    AC Smart II

    9000

    DeviceNumber

    (00) (01) (02)

    (12)(11)(10)

    (A0) (A1) (AF)

    9001

    9010

    9016(07)

    Who-Is

    I-Am(9000)I-Am(9001)I-Am(9010)I-Am(9016)

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.3 BAC Net Gateway/Basic Theory/Service/4.WHO-IS and I-AM

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.3 BAC Net Gateway/Basic Theory/Service/4.RPM

    Q2

  • LGE Internal Use Only

    HVAC & Energy Solution

    6.3 BAC Net Gateway/Basic Theory/5.BMS Communication Sequence

    BMS BACnet GW

    WHOIS (Unconfirmed req)WHOIS (Unconfirmed req)

    IAM ACK (9000, Segmented_transmit)

    ReadP(vendor id, system status, object_name, 9000)

    ReadP ACK(vendor id = 432, system-status:operational, obj_name: LG HVAC Device 9000)

    ReadMP(objid, max_apdu_length_accepted, seg_supported, vendor_id)

    ReadMP ACK(objid:9000, max_apdu_leng_accepted:1496, seg_supported:segmented-transmit,Vendor_id : 432)

    ReadP(obj-list)

    ReadP ACK(object 9000, BO 1, BI 2, . 787)

    ReadP(1, object name)

    ReadP ACK(1, obj_name : ac_startstopCmd_0

    ReadMP(1, Inactive-text, active-text)

    ReadMP ACK(1, Inactive text : stop, active text : start)

    DeviceInformation

    InformationOf indoor unit 00

    Network Info(broadcast)

  • LGE Internal Use Only

    HVAC & Energy Solution

    6. BAC Net Gateway

    Function(Web Access Commissioning )

    Internet

    Internet Explorer

  • LGE Internal Use Only

    HVAC & Energy Solution

    Installation process

    6. BAC Net Gateway

    STEP 1. Set unit address Assign a unique address to the unit being connected

    STEP 2. Set PI485 Install one PI485 for each outdoor unit, and set the DIP switch.In Multi V Plus II system, PI485 Installation does not need.

    STEP 3. Connect PI485 and BAC Net Gateway through the RS485 line.

    STEP 6. Login to BAC Net Gateway through the Internet Explorer,Check if the all Indoor unit connected

    STEP 4. Connect LAN Cable to BAC Net Gateway

    STEP 5. Set the IP & Function of BAC Net Gateway by use of key & LCD

    Refer to the ACP Installation Method, all same Method

  • LGE Internal Use Only

    HVAC & Energy Solution

    IP Address of BNU-BAC

    1

    2 Click that

    6. BAC Net Gateway

    Check the connection through Web Access

  • LGE Internal Use Only

    HVAC & Energy Solution

    Display windows for products

    You can find the connected product status

    If you cant , you must check the follows

    - Communication line between each others

    - Duplicated address of indoor

    - Confirm the communication between BNU-BAC and indoor or ventilation

    Check the connection through Web Access

    6. Installation process

  • LGE Internal Use Only

    HVAC & Energy Solution

    Commissioning Test

    LGAP

    Using web browser

    BAC Net

    BMS

    BMS Engineering SideLG Engineering Side

    HUB

    1. Creating of the A/C points.2. Test of all units and operations.

    1. Confirm A/C connection2. Test of operations

    IP : 192.168.1.100

    Subnet : 255.255.255.0IP : 192.168.1.200

    Subnet : 255.255.255.0

    IP : 192.168.1.101

    Subnet : 255.255.255.0

    6. Installation process

  • LGE Internal Use Only

    HVAC & Energy Solution

    BNU-BAC(PQNFB17B0) JMT(Joint Matching Test) List

    Check your BAC Net gateway Version in LCD , If not compatible to your site vendor,

    Upgrade to the last version software, If need contact H.Q.

    BMS Company LG BAC Net G/W

    Ver.

    Date of

    JMTLocation of JMT

    Vendor Name S/W & Controller

    Nao DigitalVersion 1.0.0

    2006/11 Seoul in Korea

    A.L.C. - SW : Web CTRL 4.1 2007/04 Seoul in Korea

    Siemens - S/W : Design insight 2.0 Version 1.0.2 2008/03 Seoul in Korea

    Andover - S/W : Continuum 1.73

    Version 1.1.3

    2008/08 Melbourne in Australia

    Delta Controls

    - SW : ORCA View 3.33

    - Controller : DCS-1212E2008/08 Melbourne in Australia

    - SW : ORCA View 3.33

    - Controller : DAC-11462008/08 Melbourne in Australia

    ALERTON- S/W : Envision 2.0

    - Controller : BCM-ETH2008/08

    Warramble in

    Australia

    Johnsons Controls

    - Controller : Metasys

    NCE v3.12008/08 Perth in Australia

    - Controller : Metasys

    NAE v2.2.02008/10 Columbia

    - S/W : M3 Workstation

    v5.42008/11

    Seoul in

    Korea,Greece

    KDT - Cimon SCADA Ver. 2.5 Version 1.2.3 2008/11 Kwangju in Korea

    6. Installation process

  • LGE Internal Use Only

    HVAC & Energy Solution

    0. Positioning to wire shark

    Ref. How to use the wire shark program _ BAC Net test program

    HUB

    Case 1. BMS S/W is installed on PC

    - Wire shark Program is executed on BMS PC

    - It is best to capture the data through this program

    HUB

    Case 2. BMS S/W is installed on own controller

    - Wire shark Program is executed on another PC

    - It has got some restrictions to capture the data

    it is not bad. We are helpful

    PC BNU-GW

    BMS System

    Controller BNU-GW

    PC

    Wire shark Program

    BMS System

  • LGE Internal Use Only

    HVAC & Energy Solution

    1. Execute the wire shark program and click the menu Capture->Interface

    Ref. How to use the wire shark program _ BAC Net test program

  • LGE Internal Use Only

    HVAC & Energy Solution

    2. Click on the menu Capture Interface and confirm the network interface card

    1

    2

    Ref. How to use the wire shark program _ BAC Net test program

  • LGE Internal Use Only

    HVAC & Energy Solution

    3. Enter bacnet at the Filter. Then you can see the BACnet data as below

    Ref. How to use the wire shark program _ BAC Net test program

    Display the BACnet Data

  • LGE Internal Use Only

    HVAC & Energy Solution

    4. Click the button Capture Stop for stopping capturing

    Ref. How to use the wire shark program _ BAC Net test program

  • LGE Internal Use Only

    HVAC & Energy Solution

    5. Click on the menu File Save As for making the log file

    1

    3

    2

    4

    Created file name BAC Net-log.pcap

    Ref. How to use the wire shark program _ BAC Net test program

  • LGE Internal Use Only

    HVAC & Energy Solution

    7. AHU /

    NO AHU Type AHU Model Contents Dry Contact PI485 Central Controller etc

    1Comm Kit

    (Simple Control)

    PUCKA0 Product:Universal PQDSBC PMNFP14A0ACSmart, ACP,

    BACnet, Lonwork2 PRCKA0 Product : MultiV PQDSBNGCM0 PMNFP14A0/1

    EEV KIT(PRLK048A0)

    3 Control Kit(Simple Control

    + DamperControl)

    PRCKD20E Product : MultiV * 4 NoNo need

    (Embedded)-

    4 PRCKD40E Product : MultiV * 8 No

  • LGE Internal Use Only

    HVAC & Energy Solution

    7. AHU / Comm Kit /

    BACnet/IPLAN

    LGNet0

    Honeywell SymmetrE V310.1( : WellTech)

    BACnet GW

    MV Plus II 4EA

    Artcool Mirror

    (ARNU09GSER2)Artcool Gallery

    (ARNU09GSF12)Artcool Gallery

    (ARNU07GSF12)

    System Structure

    TCP/IP

    BNA-1C

    CPU1

    DI

    Lonworks(FT-10)

    C-BUS

    MV SyncII

    RS485

    LGNet2LGNet1

    Control Panel

    Room Controller

    AHU Comm Kit (PUCKA0, PRCKA0) operates as one of indoor unit.

    So it can communicate with Central Controller through Outdoor unit(PI485).

    It can be working with dry contact like indoor unit

    AHU Comm

    Kit

  • LGE Internal Use Only

    HVAC & Energy Solution

    7. AHU / Control Kit /

    AHU Control Kit (PRCKD20E, PRCKD40E) communicate with Central Controller by itself

    It doesnt work with dry contact at this moment

    BACnet/IPLAN

    LGNet0

    Honeywell SymmetrE V310.1( : WellTech)

    BACnet GW

    MV Plus II 4EA

    Artcool Mirror

    (ARNU09GSER2)Artcool Gallery

    (ARNU09GSF12)Artcool Gallery

    (ARNU07GSF12)

    System Structure

    TCP/IP

    BNA-1C

    CPU1

    DI

    Lonworks(FT-10)

    C-BUSRS485

    FDD

    LGNet1

    Control Panel

    Room Controller

    (ACP_A/B)

    AHU Control

    Kit

  • LGE Internal Use Only

    HVAC & Energy Solution

    8. Other BMS Protocol / Modbus

    Modbus GW

    Management

    Control

    Device

    BMS

    485 Gateway

    Multi-V

    Ethernet

    RS-485

    PDI

    Modbus

    LGAP

    Multi-V

    Function Name Code Description

    Read Coil Status 01h On/Off(status),Lock(status),

    Swing(status), Alarm,

    Read Holding

    Registers

    03h Mode(status),

    Fan Speed(status),

    Room Temp, Error Code,

    Set Temp(status),

    Force Single Coil 05h On/Off(setting),

    Lock(setting),Swing(setting),

    Preset Single

    Registers

    06h Mode(setting),

    FanSpeed(setting),

    Set Temp(setting),

    Control & Monitoring Points

    Changes (BACnet GW)

    Contents AS-IS TO-BE

    Protocol BACnet BACnet + Modbus

    Compatible Unit AC, Vent, AHU

    AC, Vent, AHU

    PDI

    - Preparing new function around 30, May (Plan)

  • LGE Internal Use Only

    HVAC & Energy Solution

    9. Practice (Team Project)

    BACnet/IPLAN

    LGNet0

    BMS(PC)

    BACnet GW or Lonworks GW

    MV Plus II

    System Structure 1) Prepare : Make connection as below (BNU(Lonwork & BACnet), ACSmart, 1 ODU, 2 Indoor Units)

    - Only one BMS GW can be powered ON.

    2) BNU-LW

    A) Set indoor unit address as 01, 02

    and set ACSmart as slave

    B) Connect PC to Lonworks GW by LanCable

    C) Set PC IP to 192.168.1.30

    D) Access PC via internet explorer

    E) Check whether Indoor units are monitored or not

    F) Check control and monitoring function.

    (01) (02)

    3) BNU-LW

    3.1) Web Page Function

    A) Set indoor unit address as 01, 02 and Set ACSmart as slave

    B) Connect PC to BACnet GW by LanCable

    C) Set PC IP to 192.168.1.30

    D) Access PC via internet explorer

    E) Check whether Indoor units are monitored or not

    F) Check control and monitoring function.

    3.2) BMS Function

    A) Run VTS (Visual Test Shell for BACnet) Program

    (download it from internet first)

    B) Set up Wireshark Program

    C) Turn ON or OFF by VTS Program (INDOOR UNIT 01)

    - Check the result by VTS Program

    - Check the command by Remote controller or Web Page

    - Analyze BACnet Protocol by wireshark Prog for ON/OFF command

    AC-Smart

    25%

    50%

    25%

  • LGE Internal Use Only

    HVAC & Energy Solution

    The End

    2011 EU (Poland) BMS Gateway Seminar

    Thank You