MCS Total Solution for all your Control Needs 5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: 239-694-0089 Fax: 239-694-0031 www.mcscontrols.com MCS-BMS-GATEWAY STARTUP GUIDE Covers Model No. FPC-C35 For Interfacing MCS-MAGNUM To Building Automation Systems Protocols BACnet MS/TP, Metasys N2 Open, LonWorks Version 4.2 - Rev. 2017-11-30 File No: 916 CE & RoHS

Transcript of Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY...

Page 1: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS TotalSolutionfor all yourControlNeeds

5580 Enterprise Pkwy.Fort Myers, FL 33905

Office: 239-694-0089Fax: 239-694-0031

www.mcscontrols.com

MCS-BMS-GATEWAY STARTUP GUIDE

Covers Model No. FPC-C35

For Interfacing MCS-MAGNUM To Building Automation Systems Protocols

BACnet MS/TP, Metasys N2 Open, LonWorks

Version 4.2 - Rev. 2017-11-30

File No: 916 CE & RoHS

Page 2: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

2

The MCS Commitment is to provide practical solutions for the industries needs and to be both a leader and partner in the effective use of

microprocessor controls.

Micro Control Systems, Inc.5580 Enterprise ParkwayFort Myers, Florida 33905

PH:(239) 694-0089 FAX:(239) 694-0031www.mcscontrols.com

All information contained within this document is considered to be proprietary information of Micro Control Systems, Inc. No information or data from this document shall be published, used, reproduced, transmitted, or disclosed to others outside your organization without the prior expressed written consent of Micro Control Systems, Inc. This document and the information contained herein shall be treated as proprietary. Reasonable provisions shall be provided to ensure that this information remains proprietary by your employees, agents, and other personnel that may have access to this document. Copyright ©2016

Date Author Description of Changes11-06-09-15 DEW Restructured manual

07-05-16 DEW New files from SMC

07-06-16 DEW Edits from Carlos

10-03-16 DEW Change Drawings from Ian - pg 13

12-27-16 DEW Add new chapter 9

11-30-17 DEW Remove Address 0 on dip switch settings

Revision/Disclaimer Page

Page 3: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

3

Table of ContentsChapter - 1. Introduction ..........................................................................................................................5

1.1. BTL Mark – BACnet Testing Laboratory .........................................................................................................51.2. LonMark Certification ......................................................................................................................................51.3. UL and RoHS Cerfication ...............................................................................................................................5

Chapter - 2. Quick Start Guide ..............................................................................................................6

Chapter - 3. Setup for MCS-BMS-GATEWAY ....................................................................................73.1. Record Identification Data ...............................................................................................................................73.2. Configuring Device Communications ..............................................................................................................7

3.2.1 Set COM settings on all Devices Connected to the MCS-BMS-GATEWAY ............................................73.2.2 Set IP Address for each MCS-MAGNUM connected to the MCS-BMS-GATEWAY ................................7

3.3. BMS Network Settings: Selecting Stored Configurations, Setting the MAC ........................................ Address, Device Instance, and Baud Rate ...............................................................................................................8

3.3.1 Selecting Configuration Files for Devices: “S” Bank DIP Switches S0 – S3 ...........................................83.3.2 LonWorks, BACnet MS/TP and N2 .........................................................................................................8Figure 5 Protocol Selection Switch Tables ..........................................................................................................83.3.3 BACnet MS/TP: Setting the MAC Address for BMS Network .................................................................93.3.4 BACnet MS/TP and BACnet/IP: Setting the Device Instance ..............................................................103.3.5 Metasys N2: Setting the Node-ID ..........................................................................................................103.3.6 BACnet MS/TP: Setting the Serial Baud Rate for BMS Network ..........................................................11

3.3.6.1. Baud Rate DIP Switch Selection ..........................................................................................11

Chapter - 4. Interfacing MCS-BMS-GATEWAY to Devices ......................................................124.1. MCS-BMS-GATEWAY Connection Ports ......................................................................................................124.2. Wiring diagram for connecting the MCS-Magnum ........................................................................................134.3. Device Connections to MCS-BMS-GATEWAY ..............................................................................................144.4. MCS-MAGNUM Address Settings .................................................................................................................154.5. Biasing the RS-485 Device Network .............................................................................................................174.6. End of Line Termination Switch for the Modbus RS-485 Device Network ....................................................184.8. Power-Up MCS-BMS-GATEWAY .................................................................................................................194.7. Wiring Field Port to LonWorks Network ........................................................................................................20

Chapter - 5. LonWorks (FPC-C35) ......................................................................................................215.1. Commissioning the MCS-BMS-GATEWAY on a LonWorks network ............................................................21Field Port to LonWorks ............................................................................................................................................21

5.1.1 Instructions to Download XIF File (external interface file) ....................................................................22 from MCS-BMS-GATEWAY FPC-C35 Using Web Browser ..................................................................22

Chapter - 6. BACnet/IP SETUP .............................................................................................................246.1. Connecting A PC to the MCS-BMS-GATEWAY ...........................................................................................246.3. Connect the PC to MCS-BMS-GATEWAY via the Ethernet Port ..................................................................256.2. BACnet/IP: Setting IP Address for Field Network ..........................................................................................26

Chapter - 7. Appendix - Troubleshooting .....................................................................................28

Chapter - 8. CREATING CSV FILES USING MCS-CONFIG .......................................................44

Chapter - 9. Reference and Specifications ....................................................................................549.1. Compliance with UL Regulations ..................................................................................................................54

Page 4: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

4

PAGE LEFT BLANK

Page 5: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

5

Chapter - 1. IntroductionMCS-BMS-GATEWAY is an external, high performance Building Automation multi-protocol gateway that has been preprogrammed to support BACnet®1 MS/TP, Metasys®2 N2 by JCI, and LonWorks®3. Configurations for the various protocols are stored within the MCS-BMS-GATEWAY and are selectable via DIP switches for fast and easy installation. It is not necessary to download any configuration files to support the required applications.

This document provides the necessary information to facilitate installation of the MCS-BMS-GATEWAY.

1.1. BTL Mark – BACnet Testing Laboratory

The BTL Mark on the MCS-BMS-GATEWAY is a symbol that indicates to a consumer that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. Go to http://www.bacnetinternational.net/btl/ for more information about the BACnet Testing Laboratory.

1.2. LonMark Certification

LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices work together. Micro Control Systems has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, MCS-BMS-GATEWAY and MCS-BMS-GATEWAY for OEM applications and the full featured, configurable gateways.

1.3. UL and RoHS Cerfication

The MCS-BMS GATEWAY is approved across a variety of standards, including the UL 916, CE, and RoHS.

1 BACnet is a registered trademark of ASHRAE2 Metasys is a registered trademark of Johnson Controls Inc.3 LonMark is a registered trademark of LonMark International4 LonWorks is a registered trademark of Echelon Corporation

File No: 916 CE & RoHS

Page 6: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

6

Chapter - 2. Quick Start Guide1. Record the information about the unit. (Section 3.1)

2. Set the device’s BACnet MSTP serial settings (protocol address, baud rate) (Section 3.2)

3. Select a stored configuration and set field protocol MAC address/Node-ID/Device Instance, and baud rate. (Section 3.3)

4. Connect MCS-BMS-GATEWAY’s 6 pin RS-485 connector to the RS-485 network that is connected to each of the devices. (Section 4.2)

5. Connect MCS-BMS-GATEWAY FPC-C35’s 2 pin LonWorks port to the Field Protocol cabling if connecting by LonWorks (Section 4.7)

6. Connect Power to MCS-BMS-GATEWAY’s 6 pin connector. (Section 4.8)

7. Use the MCS-BMS-GATEWAY’s embedded tool which is accessed with a browser, referred to in this manual as the Web Configurator, to change the IP Address. No changes to the configuration file are necessary. (Section 5)

8. LonWorks (FPC-C35): If LonWorks is selected the MCS-BMS-GATEWAY must be commissioned on the LonWorks Network. This needs to be done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 7)

9. DOWNLOAD FieldServer-Toolbox.zip at www.mcscontrols.com: http://www.mcscontrols.com/Software/BMS%20Tools/FieldServer%20Toolbox%20Setup.zip

Part Number ...............................................................................................

Serial No. ....................................................................................................

PROTOCOL USED BACnet MS/TP LONTALK JOHNSON N2

I/P ADDRESS MCS-BMS-GATEWAY .........................................................

IP ADDRESS MCS-CONTROLLER ...........................................................

SUBNET ADDRESS ...................................................................................

MAGNUM BACnet PORT ...........................................................................

BAUD RATE ...............................................................................................

BACNET ADDRESS USED ........................................................................

FPC-C35

192-168-18- (range 201-250)

192-168-18- (see label on MCS-BMS-GATEWAY)

255-255-255-0 47808 19,200 Default 181, (18100 plus Node setting ‘A’ Bank DIP Switches)

TERMS USED:BACnet - communications protocol for BUILDING AUTOMATION AND CONTROL NETWORKSMAC ADDRESS - MEDIA ACCESS CONTROL ADDRESS (MAC address)LonWorks - PROTOCOL FOR NETWORKING DEVICESBACnet MSTP - COMMUNICATION PROTOCOL FOR BUILDING AUTOMATION TRANSPORTED BY ETHERNETMetasys® N2 - COMMUNICATION PROTOCOL FOR BUILDING AUTOMATION WITH JOHNSON CONTROLS

Page 7: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

7

Chapter - 3. Setup for MCS-BMS-GATEWAY3.1. Record Identification DataEach MCS-BMS-GATEWAY has a unique part number located on the side or the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows:

Model Part NumberMCS-BMS-GATEWAY FPC-C35 FPC-C35

Figure 1: MCS-BMS-GATEWAY Part Numbers

• FPC-C35 units have the following 3 ports: LonWorks + Ethernet + RS-485.

3.2. Configuring Device Communications3.2.1 Set COM settings on all Devices Connected to the MCS-BMS-GATEWAY

• Set up all devices on the same subnet as the MCS-BMS-GATEWAY and the configuration PC.�� All of the connected serial devices MUST have the same Baud Rate, Data Bits, Stop Bits, and Parity settings as the MCS-BMS-GATEWAY.

3.2.2 Set IP Address for each MCS-MAGNUM connected to the MCS-BMS-GATEWAY• The device needs to be on the same IP subnet as the MCS-BMS-GATEWAY and the configuration PC.• Record the following MCS-MAGNUM information to start the setup:

�� IP Address�� MCS-MAGNUM BacNet Device ID�� Set MCS-MAGNUM BacNet port to 47808 in MCS-CONFIG

.

Page 8: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

8

3.3. BMS Network Settings: Selecting Stored Configurations, Setting the MAC Address, Device Instance, and Baud Rate

3.3.1 Selecting Configuration Files for Devices: “S” Bank DIP Switches S0 – S3The S bank of DIP switches (S0 - S3) are used to select and load a configuration file from a group of pretested/preloaded configuration files which are stored in the MCS-BMS-GATEWAY FPC-C35.

NOTE: S0 - S3 DIP Switches sets the Protocol: BACnet MS/TP, LONTALK, OR JOHNSON N2

NOTE: When setting DIP Switches, please ensure that power to the board is OFF.

3.3.2 LonWorks, BACnet MS/TP and N2The following chart describes S0 - S3 DIP Switch configuration settings for MCS-BMS-GATEWAY to support LonWorks, BACnet® MS/TP and Metasys® N2 by JCI

Figure 5 Protocol Selection Switch Tables

S0 – S3 DIP Switches S Bank DIP Switch Location

S0

S1

S2

S3

Off On

Figure 3: S Bank DIP Switches

Fig 3Shows setting for

BACNet MS/TPDip switch S0 ‘ON’ as per the Figure 5

chart below

MCS-BMS-GATEWAY MCS-BMS-GATEWAY Bank DIP SwitchesProfile – MCS-BMS-GATEWAY RER S0 S1 S2 S3Lonworks Off Off Off OffBacnet MS/TP On Off Off OffN2 Off On Off Off

Page 9: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

9

3.3.3 BACnet MS/TP: Setting the MAC Address for BMS Network• Only 1 MAC address is set for MCS-BMS-GATEWAY regardless of how many devices are connected

to MCS-BMS-GATEWAY.• Set the BACnet MS/TP MAC addresses of the MCS-BMS-GATEWAY to a value between 1 to 127

(MAC Master Addresses); this is so that the BMS Front End can find the MCS-BMS-GATEWAY via BACnet auto discovery.

NOTE: Never set a BACnet MS/TP MAC Address from 128 to 255. Addresses from 128 to 255 are Slave Addresses and can not be discovered by BMS Front Ends that support auto discovery of BACnet MS/TP devices.

• Set DIP switches A0 – A7 to assign MAC Address for BACnet MS/TP for the MCS-BMS-GATEWAY FPC-C35.

• Please refer to Appendix A.10 for the complete range of MAC Addresses and DIP switch settings.

NOTE: When using Metasys N2 and Modbus TCP/IP, the ‘A’ Bank of DIP switches are disabled and not used. They should be set to OFF.

NOTE: When setting DIP Switches, please ensure that power to the board is OFF.

A0

A1

A2

A3

A4

A5

A6

A7

Off On

Figure 4: MAC Address DIP Switches

Fig 4Shows setting for 03 BMS Address

as found in A.10 appendixin the rear of this manual

Page 10: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

10

3.3.4 BACnet MS/TP and BACnet/IP: Setting the Device Instance • The ‘A’ Bank of DIP switches are used for two purposes:

�� For BACnet MS/TP, they are used to set the BACnet MS/TP MAC address (Section 3.3.2)�� For both BACnet MS/TP and BACnet/IP, they are also used to determine the BACnet Device Instance values

• The BACnet Device Instance can range from 1 to 4,194,303.• The BACnet device instances will be calculated by taking the Node Offset (default is 18100) found in

Web Configurator and adding it to the value of the ‘A’ Bank DIP switches.

When more than one device is connected to the MCS-BMS-GATEWAY, the subsequent BACnet Device Instance values will be sequential from the first/previous device.

For example: Given that Device Instance = Node_Offset + A Bank DIP switch value

�� Default Node_Offset value = 18100�� ‘A’ Bank DIP switch value = 03 (as per Appendix A.10 DIP Switch Setting)

Then the Device Instance values for the devices are:�� Device 1 Instance = 18103�� Device 2 Instance = 18104

3.3.5 Metasys N2: Setting the Node-ID• Set DIP switches A0 – A7 to assign a Node-ID for Metasys N2 to the MCS-BMS-GATEWAY.• Node-ID’s range from 1-255. • Refer to Appendix A.10 for the full range of addresses for setting Node ID.

Page 11: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

11

3.3.6 BACnet MS/TP: Setting the Serial Baud Rate for BMS Network• DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate required by the

Building Management System for BACnet MS/TP. • The baud rate on MCS-BMS-GATEWAY for Metasys N2 is set for 19,200. DIP Switches B0 – B3 are

disabled for Metasys N2.

NOTE: When setting DIP Switches, please ensure that power to the board is OFF.

3.3.6.1. Baud Rate DIP Switch Selection

B0

B1

B2

B3

Off On

Figure 5: Baud Rate DIP Switches

Fig 5Shows setting for 19200 Baud Rate

Baud B0 B1 B2 B3

Auto Off Off Off Off

110 On Off Off Off300 Off On Off Off600 On On Off Off

1200 Off Off On Off2400 On Off On Off4800 Off On On Off9600 On On On Off

19200 Off Off Off On20833 On Off Off On28800 Off On Off On38400 On On Off On57600 Off Off On On76800 On Off On On

115200 Off On On On

Page 12: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

12

Chapter - 4. Interfacing MCS-BMS-GATEWAY to Devices4.1. MCS-BMS-GATEWAY Connection Ports

Figure 7: MCS-BMS-GATEWAY

Page 13: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

13

4.2. Wiring diagram for connecting the MCS-Magnum

Figure 7 - Gateway to RS-485 wiring

Page 14: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

14

4.3. Device Connections to MCS-BMS-GATEWAY MCS-BMS-GATEWAY 6 Pin Phoenix connector for RS-485 Devices.

• Pins 1 through 3 are for RS-485 devices.�� The RS-485 GND (Pin 3) is not typically connected

• Pins 4 through 6 are for power. Do not connect power (wait until Section 3.4).

Figure 8: Power and RS-485 Connections

Device Pins MCS-BMS-GATEWAY Pin # Pin Assignment

Pin RS-485 + Pin 1 RS-485 +Pin RS-485 - Pin 2 RS-485 -Pin GND Pin 3 RS-485 GNDPower In (+) Pin 4 V +Power In (-) Pin 5 V -Frame Ground Pin 6 FRAME GND

Page 15: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

15

4.4. MCS-MAGNUM Address SettingsThe MCS-BMS-GATEWAY is connected to the MCS-MAGNUM via Ethernet . The Bacnet Device ID and the IP address of the MCS-MAGNUM must be setup properly to enable successful communications between the MCS-BMS-GATEWAY and the MCS-MAGNUM.The MCS-MAGNUM BACNET DEVICE ID must be set to the address specified on the MCS-BMS-Gateway’s label (Example - 18103).

The MCS-MAGNUM BACNET DEVICE ID can be verified and changed (with the proper authorization code) from MCS-Magnum’s keypad the keypad/LCD of a live unit. To get authorized on Magnum do the following:1. Press ‘Menu’2. Using , , , or position curser to ‘Passwords’3. Press key.4. Enter 4 digit password & press .5. Press ‘Menu’ to make next selection.

The following steps will display the Bacnet Device ID:

(to change the address you first must be authorized)

1. Press the MENU key and then Using , , , or position curser to Serv Tools then press the ENTER key.2. then Using , , , or position curser to Bacnet Setting then press Enter.3. Use , , curser to change the Bacnet Device ID.4. Set your desired address then press Enter. 5. Reset or cycle power to the magnum for the change to take effect.

NOTE: This BACNet Device ID will change depending on the address that will be set on the ‘A’ DIP Switches.

Page 16: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

16

The MCS-MAGNUM IP must be set to the address specified on the MCS-BMS-Gateway’s label(Example - 192.168.18.101). Range of default settings: 101-150

The MCS-MAGNUM IP address can be verified and changed (with the proper authorization code) from the MCS-Magnum’s Keypad/LCD of a live unit. The following steps will display the IP Address settings:(to change the address you first must be authorized)

1. Press the MENU key and then Using , , , or position curser to Serv Tools then press the ENTER key.

2. Then Using, , or position curser to Serv Tools then press Enter.3. Then Using,, , or position curser to Ethernet Network then press Enter.4. Then Using, , , or position curser to IP address then press Enter.5. Using , to increase and decrease the first set of values then use the to select the next set of numbers

and use , to increase and decrease the second value and repeat the previous steps for rest of the ip address.

6. Once you have set the desired address press the Enter key.7. Reset or cycle power to the magnum for the change to take effect.

The MCS-MAGNUM IP address can be verified and changed (with the proper authorization code) from MCS-CONNECT of a live unit. The following steps will display the IP Address settings:(to change the address you first must be authorized)

1. Connect to your MCS-Controller thru MCS-CONNECT2. Click on the ‘SERVICE’ tab3. Click on the ‘ETHERNET’ tab4. Make changes to the IP address and any other changes as shown on the MCS-BMS-GATEWAY label.5. Save your changes

Page 17: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

17

4.5. Biasing the RS-485 Device Network• An RS-485 network with more than one device needs to have biasing to ensure proper communication.

The biasing only needs to be done on one device.• The MCS-BMS-GATEWAY has 510 Ohm resistors that can be used to set the biasing.

The MCS-BMS-GATEWAY’s default positions from the factory for the Biasing jumpers are OFF.• The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the outside of the

board of the MCS-BMS-GATEWAY. (Figure 9) • Only turn biasing ON:

�� IF the BMS cannot see more than one device connected to the MCS-BMS-GATEWAY AND all the settings (wiring, and DIP switches) have been checked.

• To turn biasing ON, move the 2 RED biasing jumpers to straddle the 4 pins closest to the inside of the board of the MCS-BMS-GATEWAY.

RS-485 Bias Switch

(off)

Figure 9: RS-485 Biasing Switch on the MCS-BMS-GATEWAY

Page 18: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

18

4.6. End of Line Termination Switch for the Modbus RS-485 Device Network• On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each end.• The MCS-BMS-GATEWAY has an End of Line (EOL) blue jumper. The default setting for this Blue

EOL switch is OFF with the jumper straddling the pins closest to the inside of the board of the MCS-BMS-GATEWAY.

�� On short cabling runs the EOL switch does not to need to be turned ON• If the MCS-BMS-GATEWAY is placed at one of the ends of the trunk, set the blue EOL jumper to the

ON position straddling the pins closest to the outside of the board of the MCS-BMS-GATEWAY.• Always leave the single Red Jumper in the A position (default factory setting).

RS-485 EOL Switch

(off)

Leave in Position A

Figure 10: Rs-485 End-Of-Line Termination Switch on the MCS-BMS-GATEWAY

Page 19: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

19

4.8. Power-Up MCS-BMS-GATEWAY Apply power to MCS-BMS-GATEWAY as show below in Figure 13. Ensure that the power supply used complies with the specifications provided in chapter 9.

• MCS-BMS-GATEWAY accepts either 9-30VDC or 12-24 VAC on pins 4 and 5.• Frame GND should be connected.

Power Requirement for MCS-BMS-GATEWAY External Gateway Current Draw TypeMCS-BMS-GATEWAY Family 12VDC/VAC 24VDC/VAC 30VDCFPC – C35 (Typical) 210mA 130mA 90mAFPC – C35 (Maximum) 250mA 170mA 110mANOTE: These values are ‘nominal’ and a safety margin should be added to the power supply of the host system. A safety margin of 25% is recommended.

Figure 12: Required current draw for the MCS-BMS-GATEWAY

Power to MCS-BMS-GATEWAY

MCS-BMS-GATEWAYPin #

PinAssignment

Power In (+) Pin 4 V +Power In (-) Pin 5 V -Frame Ground Pin 6 FRAME GND

Figure 13: Power Connections

Page 20: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

20

4.7. Wiring Field Port to LonWorks Network• Connect the LonWorks network wires to the 2-pin LonWorks connector on MCS-BMS-GATEWAY

FPC-C35 as shown below in Figure 11.• Connect MCS-BMS-GATEWAY to the field network with the LonWorks terminal using approved

cable per the FT-10 installation guidelines. LonWorks has no polarity.

BMS LonWorks Wiring

MCS-BMS-GATEWAY Pin #

Pin Assignment

LonWorks Pin 1 LonWorksLonWorks Pin 2 LonWorks

Figure 11: Connection from ProtoCarrier to LonWorks Field Network

Page 21: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

21

Chapter - 5. LonWorks (FPC-C35) 5.1. Commissioning the MCS-BMS-GATEWAY on a LonWorks network

Commissioning may only be performed by the LonWorks administrator.

1. To commission the MCS-BMS-GATEWAY LonWorks port, press ‘BLUE’ Service Pin 2. This pin is located on the MCS-BMS-GATEWAY top base board. See the illustration below on the MCS-BMS-GATEWAY where the button is located.

NOTE:Inherent to the design of LonWorks is the intention that all nodes residing on a LonWorks network possess a profile which accurately describes the network variables available to the LonWorks network. This profile is declared to the LonWorks network by means of an External Interface File (XIF). This XIF remains unchanged for any particular profile. In other words, a change in the XIF is by definition a new profile.3. If an XIF file is required, see steps in next section to generate XIF.

LonWorks ‘BLUE’ Service Pin

Field Port to LonWorks

1

Page 22: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

22

5.1.1 Instructions to Download XIF File (external interface file) from MCS-BMS-GATEWAY FPC-C35 Using Web Browser

Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and MCS-BMS-GATEWAY.The Default IP Address of MCS-BMS-GATEWAY is 192.168.18.201, Subnet Mask is 255.255.255.0. If the PC and MCS-BMS-GATEWAY are on different IP Networks, assign a static IP Address to the PC on the 192.168.18.XXX network.

• For Windows XP:

• For Windows XP and Windows 7, select: Use the following IP Address

• Open a web browser and go to the following address: [IP Address of MCS-BMS-GATEWAY]/fserver.xif�� Example: 192.168.10.201/fserver.xif

• If the web browser prompts to save the file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file onto the local PC as fserver.xif

*Customer ProtoCarrier Startup Guide

Page 23 of 38

6 LONWORKS (FPC-C35): COMMISSIONING PROTOCARRIER ON A LONWORKS NETWORK

Commissioning may only be performed by the LonWorks administrator.

6.1 Commissioning ProtoCarrier FPC-C35 on a LonWorks Network

The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoCarrier FPC-C35 at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool.

If an XIF file is required, see steps in Section 6.1.1 to generate XIF.

6.1.1 Instructions to Download XIF File from ProtoCarrier FPC-C35 Using Browser

Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and ProtoCarrier.

The Default IP Address of ProtoCarrier is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoCarrier are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network.

For Windows XP:

Go to > >

Right-click on Local Area Connection > Properties

Highlight >

For Windows 7 or later:

Go to > >

> >

Right-click on Local Area Connection > Properties

Highlight >

Figure 17: LonWorks Service Pin Location

192 . 168 . 18 . 201

255 . 255 . 255 . 0

192 . 168 . 18 . 1

*Customer ProtoCarrier Startup Guide

Page 24 of 38

For Windows XP and Windows 7, select: Use the following IP Address

Click twice

Open a web browser and go to the following address: [IP Address of ProtoCarrier]/fserver.xif

o Example: 192.168.1.24/fserver.xif

If the web browser prompts to save the file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file onto the local PC as fserver.xif

Figure 18: Sample of Fserver.XIF File Being Generated

Page 23: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

23

Figure 18: Sample of Fserver.XIF File Being Generated

NOTE:The external interface file (.XIF) for the FieldServer can be uploaded from the FieldServer for the particular application. The FieldServer differs from most other LonWorks devices in that its XIF file is not fixed due to varying applications. The list of points available to the network will vary depending on the other networks connected to the FieldServer, and the requirements of the particular application.

Page 24: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

24

Chapter - 6. BACnet/IP SETUP6.1. Connecting A PC to the MCS-BMS-GATEWAY

• Confirm that the network cabling is correct• Confirm that the computer network card is operational and correctly configured• Confirm that there is an Ethernet adapter installed in the PC’s Device Manager List, and that it is

configured to run the TCP/IP protocol• Check that the IP netmask of the PC matches the MCS-BMS-GATEWAY. The Default IP Address of

the MCS-BMS-GATEWAY is 192.168.18.201, Subnet Mask is 255.255.255.0, Default Gateway is 192.168.18.1.

• Go to Start > Run• Type in “ipconfig”• The account settings should be displayed• Ensure that the IP address is 192.168.18.xxx, the Subnet mask is 255.255.255.0 and the Default Gateway is 192.168.18.1• Ensure that the PC and MCS-BMS-GATEWAY are on the same IP Network, or assign a Static IP Address

to the PC on the 192.168.18.XXX network• If Using Windows XP, ensure that the firewall is disabled• Ensure that all other Ethernet cards active on the PC, especially wireless adapters are disabled

Page 25: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

25

6.3. Connect the PC to MCS-BMS-GATEWAY via the Ethernet Port• Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC and

MCS-BMS-GATEWAY.• The Default IP Address of MCS-BMS-GATEWAY is 192.168.18.201 (range 201-250), Subnet Mask

is 255.255.255.0. If the PC and MCS-BMS-GATEWAY are on different IP Networks, assign a static IP Address to the PC on the 192.168.18.XXX network.

• For Windows XP:

Go to > >

Right-click on Local Area Connection > Properties

> thgilhgiH

For Windows 7 or later:

> > ot oG

> >

Right-click on Local Area Connection > Properties

> thgilhgiH

For Windows XP and Windows 7, use the following IP Address:

Click twice.

192 . 168 . 18 . XXX

255 . 255 . 255 . 0

NetworkConnections

192 . 168 . 18 . 1

MCS-BMS-GATEWAY RANGE201-250

use an address that will not conflict with

these numbers

Page 26: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

26

6.2. BACnet/IP: Setting IP Address for Field Network• After setting a local PC on the same subnet as the MCS-BMS-GATEWAY (Section 4.1), open a web

browser on the PC and enter the IP Address of the MCS-BMS-GATEWAY; the address is shown on the label affixed to your MCS-BMS-GATWAY 192.168.10.XXX (range 201-250)

NOTE: If the IP Address of the MCS-BMS-GATEWAY has been changed by previous configuration, the assigned IP Address can be discovered using the FieldServer Toolbox utility. See Section Appendix A.1 for instructions.

• The Web Configurator will be displayed as the landing page. (Figure 14)

Figure 14: Web Configuration Screen

Page 27: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

27

• From the Web GUI landing page, click on “Setup” to expand the navigation tree and then select “Network Settings” to access the IP Settings menu. (Figure 15)

Figure 15: Changing IP Address via Web GUI

• Enter the new IP Address for the MCS-BMS-GATEWAY’s Ethernet port in the “N1 IP Address” field.• If necessary, change the Subnet Mask setting in the “N1 Netmask” field.• If necessary, change the IP Gateway setting in the “Default Gateway” field.

NOTE: If the MCS-BMS-GATEWAY is connected to a router, the IP Gateway of the MCS-BMS-GATEWAY should be set to the IP Address of that router.

• Click the “System Restart” button at the bottom of the page to apply changes and restart the MCS-BMS-GATEWAY.• Unplug Ethernet cable from PC and connect the MCS-BMS-GATEWAY to the network hub or

router.• Record the IP Address assigned to the MCS-BMS-GATEWAY for future reference.

Page 28: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

28

Chapter - 7. Appendix - Troubleshooting Appendix A. 1. Lost or Incorrect IP Address

• Ensure that FieldServer Toolbox is loaded on the local PC. If not, download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care-Resource Center, Software Downloads:

http://www.mcscontrols.com/Software/BMS%20Tools/FieldServer%20Toolbox%20Setup.zip• Extract the executable file and complete the installation.

• Disable any wireless Ethernet adapters on the PC/Laptop.• Disable firewall and virus protection software if possible.• Connect a standard CAT5 Ethernet cable between the PC and MCS-BMS-GATEWAY. • Double click on the FS Toolbox Utility.• Check IP Addresses from the Device listings.

• Correct IP Address(es) by right clicking the settings icon and changing the IP Address.

*Customer ProtoCarrier Startup Guide

Page 25 of 38

Appendix A. Troubleshooting

Appendix A.1. Lost or Incorrect IP Address

Ensure that FieldServer Toolbox is loaded on the local PC. If not, download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care-Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable any wireless Ethernet adapters on the PC/Laptop.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoCarrier.

Double click on the FS Toolbox Utility.

Check IP Addresses from the Device listings.

Correct IP Address(es) by right clicking the settings icon and changing the IP Address.

Figure 19: Ethernet Port Location

Ethernet Port

*Customer ProtoCarrier Startup Guide

Page 25 of 38

Appendix A. Troubleshooting

Appendix A.1. Lost or Incorrect IP Address

Ensure that FieldServer Toolbox is loaded on the local PC. If not, download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care-Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable any wireless Ethernet adapters on the PC/Laptop.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoCarrier.

Double click on the FS Toolbox Utility.

Check IP Addresses from the Device listings.

Correct IP Address(es) by right clicking the settings icon and changing the IP Address.

Figure 19: Ethernet Port Location

Ethernet Port

Page 29: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

29

Appendix A. 2. Viewing Diagnostic information• Type the IP Address of the MCS-BMS-GATEWAY into the web browser or use the FieldServer

Toolbox to connect to the MCS-BMS-GATEWAY.• Click on Diagnostics and Debugging Button , then click on view, and then on connections.• If there are any errors showing on the Connection page, please refer to section for the relevant

wiring and settings.

Figure 20: Error messages screen

Appendix A. 3. Check Wiring and Settings• No COMS on N2. If the Tx/Rx LEDs are not flashing rapidly then there is a COM issue. To fix this

problem, check the following:�� Visual observations of LEDs on MCS-BMS-GATEWAY (Appendix A.5)�� Check baud rate, parity, data bits, stop bits�� Check BacNet MSTP device address�� Verify wiring�� Verify BacNet MSTP device is connected to the same subnet as the MCS-BMS-GATEWAY�� Verify BacNet MSTP device was discovered in Web Configurator

• No COMS on TCP/IP side to the MCS-MAGNUM. To fix this problem check the following:�� Device IP setting�� Verify wiring�� Verify MCS-MAGNUM is connected to the same subnet as the MCS-BMS-GATEWAY

NOTE: If the problem still exists, a Diagnostic Capture needs to be taken and sent to support. (Appendix A.6)

Page 30: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

30

Appendix A. 4. No communication between the MCS-Magnum and the MCS-BMS-GATEWAY

• Confirm that the network cabling is correct• Check that the IP address, subnet mask, and the default gateway of the MCS-Magnum match what the

label on the MCS-BMS-GATEWAY says it should be set to. • Check the LED’s on the Ethernet port. The yellow LED should be solid yellow the green LED should

continuously flash.

• LED Diagnostics for Lonworks Communications between the MCS-BMS-GATEWAY and device Note: Please see the diagram below for LED Locations

Yellow LED Green LED

Ethernet Port

Page 31: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

31

Appendix A. 5. LED Diagnostics for Communications Between MCS-BMS-GATEWAY and Devices

Please see the diagram below for LED locations to MCS-BMS-GATEWAY FPC-C35.

Tag DescriptionSPL The SPL LED will light if the unit is not getting a response from one or more of the configured devices.

For LonWorks units, LED will light until the unit is commissioned on the LonWorks network.RUN The RUN LED will start flashing 20 seconds after power indicating normal operation. ERR The SYS ERR LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light

will indicate there is a system error on unit. If this occurs, immediately report the related “system error” shown in the error screen of the GUI interface to support for evaluation.

RX If socket protocol is serial, the RX LED will flash when a message is received on the host port. If socket protocol is Ethernet, this LED is not used.

TX If socket protocol is serial, the TX LED will flash when a message is sent on the host port. If socket protocol is Ethernet, this LED is not used.

PWR This is the power light and should show steady green at all times when the unit is powered.Figure 21: Diagnostic LEDs

Page 32: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

32

Appendix A. 6. Take Diagnostic Capture With the FieldServer Toolbox• Once the Diagnostic Capture is complete, email it to [email protected]. The Diagnostic

Capture will accelerate diagnosis of the problem.• Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download

http://www.mcscontrols.com/Software/BMS%20Tools/FieldServer%20Toolbox%20Setup.zip• Extract the executable file and complete the installation.

• Disable any wireless Ethernet adapters on the PC/Laptop.• Disable firewall and virus protection software if possible.• Connect a standard CAT5 Ethernet cable between the PC and MCS-BMS-GATEWAY.• Double click on the FS Toolbox Utility.• Step 1: Take a Log

�� Click on the diagnose icon of the desired device.

*Customer ProtoCarrier Startup Guide

Page 29 of 38

Appendix A.5. Take Diagnostic Capture With the FieldServer Toolbox

Once the Diagnostic Capture is complete, email it to [email protected]. The Diagnostic Capture will accelerate diagnosis of the problem.

Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor Corporation webpage, under Customer Care- Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable any wireless Ethernet adapters on the PC/Laptop.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoCarrier.

Double click on the FS Toolbox Utility.

Step 1: Take a Log

o Click on the diagnose icon of the desired device.

Figure 22: Ethernet Port Location

Ethernet Port

*Customer ProtoCarrier Startup Guide

Page 29 of 38

Appendix A.5. Take Diagnostic Capture With the FieldServer Toolbox

Once the Diagnostic Capture is complete, email it to [email protected]. The Diagnostic Capture will accelerate diagnosis of the problem.

Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor Corporation webpage, under Customer Care- Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

Extract the executable file and complete the installation.

Disable any wireless Ethernet adapters on the PC/Laptop.

Disable firewall and virus protection software if possible.

Connect a standard CAT5 Ethernet cable between the PC and ProtoCarrier.

Double click on the FS Toolbox Utility.

Step 1: Take a Log

o Click on the diagnose icon of the desired device.

Figure 22: Ethernet Port Location

Ethernet Port

Page 33: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

33

Select full Diagnostic.

NOTE: If desired, the default capture period can be changed. �� Click on “Start Diagnostic”.

�� Wait for Capture period to finish. Diagnostic Test Complete window will appear.

Page 34: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

34

• Step 2: Send Log�� Once the Diagnostic test is complete, a .zip file will be saved on the PC.

�� Choose “Open” to launch explorer and have it point directly at the correct folder�� Send the Diagnostic zip file to [email protected]

Page 35: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

35

Appendix A. 7. Fire Transfer - Load New CSV file1. To load a new configuration, follow these instructions:2. Follow instructions in Chapter 8 to create a new CSV file3. Open a web browser and type the IP Address of the FieldServer in the address bar.4. NOTE: Default IP Address is 192.168.18.201 (range 201-250)5. NOTE: Use the FS Toolbox utility if the IP Address is unknown (Appendix A.1).6. Locate your device, click on ‘CONNECT’.7. In the Navigation Tree on the left hand side, do the following:8. Click on “Setup”9. Click on “File Transfer”10. Click on the “Configuration” tab11. In the configuration tab, click on “Choose Files” and select the CSV file extracted in step 2.12. Click on the orange “Submit” button.13. When the download is complete, click on the “System Restart” button.

Page 36: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

36

Appendix A. 8. Retrieve a CSV File from MCS-BMS-GATEWAY1. To retrieve the config.csv from the device, follow these instructions:2. Open a web browser and type the IP Address of the FieldServer in the address bar.3. NOTE: Default IP Address is 192.168.18.201 (range 201-250)4. NOTE: Use the FS Toolbox utility if the IP Address is unknown (Appendix A.1).5. Locate your device, click on ‘CONNECT’.6. In the Navigation Tree on the left hand side, do the following:7. Click on “Setup”8. Click on “File Transfer”9. Click on the “Configuration” tab10. In the configuration tab, click on ‘CONFIG.CSV’ under ‘RETRIEVE’

11. The config.csv will print to your screen

12. Click on ‘DOWNLOAD’ in the upper right hand corner to save the file, click on ‘SAVE’

Page 37: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

37

Appendix A. 9. Update Firmware

• To load a new version of the firmware, follow these instructions:• Extract and save the new file onto the local PC.• Open a web browser and type the IP Address of the FieldServer in the address bar.• NOTE: Default IP Address is 192.168.18.201. )range 201-250)• NOTE: Use the FS Toolbox utility if the IP Address is unknown (Appendix A.1).• Locate your device, click on ‘CONNECT’.• In the Navigation Tree on the left hand side, do the following:• Click on “Setup”• Click on “File Transfer”• Click on the “Firmware” tab• In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step 1.• Click on the orange “Submit” button.• When the download is complete, click on the “System Restart” button.

Page 38: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

38

Appendix A. 10. BMS Address DIP Switch Settings

A7 A6 A5 A4 A3 A2 A1 A0 AddressOff Off Off Off Off Off Off On 1Off Off Off Off Off Off On Off 2Off Off Off Off Off Off On On 3Off Off Off Off Off On Off Off 4Off Off Off Off Off On Off On 5Off Off Off Off Off On On Off 6Off Off Off Off Off On On On 7Off Off Off Off On Off Off Off 8Off Off Off Off On Off Off On 9Off Off Off Off On Off On Off 10Off Off Off Off On Off On On 11Off Off Off Off On On Off Off 12Off Off Off Off On On Off On 13Off Off Off Off On On On Off 14Off Off Off Off On On On On 15Off Off Off On Off Off Off Off 16Off Off Off On Off Off Off On 17Off Off Off On Off Off On Off 18Off Off Off On Off Off On On 19Off Off Off On Off On Off Off 20Off Off Off On Off On Off On 21Off Off Off On Off On On Off 22Off Off Off On Off On On On 23Off Off Off On On Off Off Off 24Off Off Off On On Off Off On 25Off Off Off On On Off On Off 26Off Off Off On On Off On On 27Off Off Off On On On Off Off 28Off Off Off On On On Off On 29Off Off Off On On On On Off 30Off Off Off On On On On On 31Off Off On Off Off Off Off Off 32Off Off On Off Off Off Off On 33Off Off On Off Off Off On Off 34Off Off On Off Off Off On On 35Off Off On Off Off On Off Off 36Off Off On Off Off On Off On 37Off Off On Off Off On On Off 38Off Off On Off Off On On On 39Off Off On Off On Off Off Off 40Off Off On Off On Off Off On 41

Page 39: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

39

A7 A6 A5 A4 A3 A2 A1 A0 AddressOff Off On Off On Off On Off 42Off Off On Off On Off On On 43Off Off On Off On On Off Off 44Off Off On Off On On Off On 45Off Off On Off On On On Off 46Off Off On Off On On On On 47Off Off On On Off Off Off Off 48Off Off On On Off Off Off On 49Off Off On On Off Off On Off 50Off Off On On Off Off On On 51Off Off On On Off On Off Off 52Off Off On On Off On Off On 53Off Off On On Off On On Off 54Off Off On On Off On On On 55Off Off On On On Off Off Off 56Off Off On On On Off Off On 57Off Off On On On Off On Off 58Off Off On On On Off On On 59Off Off On On On On Off Off 60Off Off On On On On Off On 61Off Off On On On On On Off 62Off Off On On On On On On 63Off On Off Off Off Off Off Off 64Off On Off Off Off Off Off On 65Off On Off Off Off Off On Off 66Off On Off Off Off Off On On 67Off On Off Off Off On Off Off 68Off On Off Off Off On Off On 69Off On Off Off Off On On Off 70Off On Off Off Off On On On 71Off On Off Off On Off Off Off 72Off On Off Off On Off Off On 73Off On Off Off On Off On Off 74Off On Off Off On Off On On 75Off On Off Off On On Off Off 76Off On Off Off On On Off On 77Off On Off Off On On On Off 78Off On Off Off On On On On 79Off On Off On Off Off Off Off 80Off On Off On Off Off Off On 81Off On Off On Off Off On Off 82Off On Off On Off Off On On 83Off On Off On Off On Off Off 84

Page 40: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

40

A7 A6 A5 A4 A3 A2 A1 A0 AddressOff On Off On Off On On Off 86Off On Off On Off On On On 87Off On Off On On Off Off Off 88Off On Off On On Off Off On 89Off On Off On On Off On Off 90Off On Off On On Off On On 91Off On Off On On On Off Off 92Off On Off On On On Off On 93Off On Off On On On On Off 94Off On Off On On On On On 95Off On On Off Off Off Off Off 96Off On On Off Off Off Off On 97Off On On Off Off Off On Off 98Off On On Off Off Off On On 99Off On On Off Off On Off Off 100Off On On Off Off On Off On 101Off On On Off Off On On Off 102Off On On Off Off On On On 103Off On On Off On Off Off Off 104Off On On Off On Off Off On 105Off On On Off On Off On Off 106Off On On Off On Off On On 107Off On On Off On On Off Off 108Off On On Off On On Off On 109Off On On Off On On On Off 110Off On On Off On On On On 111Off On On On Off Off Off Off 112Off On On On Off Off Off On 113Off On On On Off Off On Off 114Off On On On Off Off On On 115Off On On On Off On Off Off 116Off On On On Off On Off On 117Off On On On Off On On Off 118Off On On On Off On On On 119Off On On On On Off Off Off 120Off On On On On Off Off On 121Off On On On On Off On Off 122Off On On On On Off On On 123Off On On On On On Off Off 124Off On On On On On Off On 125Off On On On On On On Off 126Off On On On On On On On 127On Off Off Off Off Off Off Off 128

Page 41: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

41

A7 A6 A5 A4 A3 A2 A1 A0 AddressOn Off Off Off Off Off Off On 129On Off Off Off Off Off On Off 130On Off Off Off Off Off On On 131On Off Off Off Off On Off Off 132On Off Off Off Off On Off On 133On Off Off Off Off On On Off 134On Off Off Off Off On On On 135On Off Off Off On Off Off Off 136On Off Off Off On Off Off On 137On Off Off Off On Off On Off 138On Off Off Off On Off On On 139On Off Off Off On On Off Off 140On Off Off Off On On Off On 141On Off Off Off On On On Off 142On Off Off Off On On On On 143On Off Off On Off Off Off Off 144On Off Off On Off Off Off On 145On Off Off On Off Off On Off 146On Off Off On Off Off On On 147On Off Off On Off On Off Off 148On Off Off On Off On Off On 149On Off Off On Off On On Off 150On Off Off On Off On On On 151On Off Off On On Off Off Off 152On Off Off On On Off Off On 153On Off Off On On Off On Off 154On Off Off On On Off On On 155On Off Off On On On Off Off 156On Off Off On On On Off On 157On Off Off On On On On Off 158On Off Off On On On On On 159On Off On Off Off Off Off Off 160On Off On Off Off Off Off On 161On Off On Off Off Off On Off 162On Off On Off Off Off On On 163On Off On Off Off On Off Off 164On Off On Off Off On Off On 165On Off On Off Off On On Off 166On Off On Off Off On On On 167On Off On Off On Off Off Off 168On Off On Off On Off Off On 169On Off On Off On Off On Off 170On Off On Off On Off On On 171

Page 42: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

42

A7 A6 A5 A4 A3 A2 A1 A0 AddressOn Off On Off On On Off Off 172On Off On Off On On Off On 173On Off On Off On On On Off 174On Off On Off On On On On 175On Off On On Off Off Off Off 176On Off On On Off Off Off On 177On Off On On Off Off On Off 178On Off On On Off Off On On 179On Off On On Off On Off Off 180On Off On On Off On Off On 181On Off On On Off On On Off 182On Off On On Off On On On 183On Off On On On Off Off Off 184On Off On On On Off Off On 185On Off On On On Off On Off 186On Off On On On Off On On 187On Off On On On On Off Off 188On Off On On On On Off On 189On Off On On On On On Off 190On Off On On On On On On 191On On Off Off Off Off Off Off 192On On Off Off Off Off Off On 193On On Off Off Off Off On Off 194On On Off Off Off Off On On 195On On Off Off Off On Off Off 196On On Off Off Off On Off On 197On On Off Off Off On On Off 198On On Off Off Off On On On 199On On Off Off On Off Off Off 200On On Off Off On Off Off On 201On On Off Off On Off On Off 202On On Off Off On Off On On 203On On Off Off On On Off Off 204On On Off Off On On Off On 205On On Off Off On On On Off 206On On Off Off On On On On 207On On Off On Off Off Off Off 208On On Off On Off Off Off On 209On On Off On Off Off On Off 210On On Off On Off Off On On 211On On Off On Off On Off Off 212On On Off On Off On Off On 213On On Off On Off On On Off 214

Page 43: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

43

A7 A6 A5 A4 A3 A2 A1 A0 AddressOn On Off On Off On On On 215On On Off On On Off Off Off 216On On Off On On Off Off On 217On On Off On On Off On Off 218On On Off On On Off On On 219On On Off On On On Off Off 220On On Off On On On Off On 221On On Off On On On On Off 222On On Off On On On On On 223On On On Off Off Off Off Off 224On On On Off Off Off Off On 225On On On Off Off Off On Off 226On On On Off Off Off On On 227On On On Off Off On Off Off 228On On On Off Off On Off On 229On On On Off Off On On Off 230On On On Off Off On On On 231On On On Off On Off Off Off 232On On On Off On Off Off On 233On On On Off On Off On Off 234On On On Off On Off On On 235On On On Off On On Off Off 236On On On Off On On Off On 237On On On Off On On On Off 238On On On Off On On On On 239On On On On Off Off Off Off 240On On On On Off Off Off On 241On On On On Off Off On Off 242On On On On Off Off On On 243On On On On Off On Off Off 244On On On On Off On Off On 245On On On On Off On On Off 246On On On On Off On On On 247On On On On On Off Off Off 248On On On On On Off Off On 249On On On On On Off On Off 250On On On On On Off On On 251On On On On On On Off Off 252On On On On On On Off On 253On On On On On On On Off 254On On On On On On On On 255

Page 44: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

44

Chapter - 8. CREATING CSV FILES USING MCS-CONFIG

Go to our website and download the Fieldserver Toolbox by clicking here:MCS-BMS-GATEWAY Install Tools.zipThis will be needed to program the MCS BMS-Gateway.

Creating CSV Files

1. Open MCS-Config program and load the config you are working on.2. Click on Setup.

3. Be sure to set IP Address, Subnet Mask, Default Gateway, MCS IP Port and Bacnet Device ID, then save config file. DO NOT CHANGE BACNET DEVICE ID ONCE CSV FILES ARE CREATED!!

4. Click on BMS POINTS.

5. Click on Create MCS-BMS-Gateway CSV Files.

Page 45: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

45

6. When popup window comes up click ok.

Page 46: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

46

7. When prompted, select the file location where you want to save the csv files. This would be the time to name the CSV files, there is a 15 character maximum not including the file extension. If you do not name the file it will default to the first 15 characters of the config name. Then click save

Page 47: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

47

Programming the MCS-BMS-Gateway

1. Wire the MCS-BMS-Gateway to the 12Vdc output on the magnum controller.Connect a crossover Ethernet cable from your laptop to the Ethernet port on the MCS-BMS-Gateway.

2. Open the Fieldserver Toolbox.3. Click on discover now4. The toolbox should show the MCS-BMS-Gateway

5. Click on the settings icon

6. Click on Network Settings.

Page 48: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

48

7. Set IP Address, Subnet Mask, Default Gateway. Be sure the last set of numbers of the IP address is different than what the MCS-Magnum are set to. Click Update IP Settings

8. Click change and restart. This will restart the MCS-BMS-Gateway Card.

9. Once the gateway card has restarted, click on the setting icon.

Page 49: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

49

10. Click on File Transfer.

11. Select the Update Config tab at the top (A) Click Browse (B).

A.

B.

Page 50: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

50

12. Locate where you saved the CSV files and select the file that is named config.csv and click open.

13. Click update config when you see the file you have chosen says Ready.

Page 51: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

51

14. You will be prompted to restart the device, click restart.

15. Once device has restarted click on the settings icon once again.16. Click file transfer17. Click on the general files tab (C) and then click Browse (D)

C.

D.

Page 52: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

52

18. Locate where you saved the CSV files you created above. Select all three files listed. Click Open

19. Click Send Files when you see the files you have chosen say, Ready

Page 53: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

53

20. Once all files are sent, close the file transfer box by clicking on the X at the top of the screen.

21. Once closed you should be brought back to the Configure Device window, you will need to click restart device. Once that is completed your device has been programmed and is ready for use.

Page 54: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

54

Chapter - 9. Reference and Specifications

*Customer ProtoCarrier Startup Guide

Page 37 of 38

Appendix D. Reference

Appendix D.1. Specifications

ProtoCarrier FPC-C35

Electrical Connections

One 6-pin Phoenix connector with: RS-485 port (+ / - / gnd) Power port (+ / - / Frame-gnd)

One 2-pin Phoenix connector with: One Ethernet 10/100 BaseT port One FTT-10 LonWorks port

Approvals

CE Certified; TUV approved to UL 916, EN 60950-1, EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15; DNP3 Conformance Tested; RoHS Compliant; CSA 205 Approved BTL Marked LonMark Certified

Power Requirements Multi-mode power adapter: 9-30VDC or 12 - 24VAC Physical Dimensions 11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.) Weight 0.2 kg (0.4 lbs) Operating Temperature -40°C to 75°C (-40°F to167°F) Surge Suppression EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT Humidity 5 - 90% RH (non-condensing) (Specifications subject to change without notice)

Figure 23: Specifications

Appendix D.1.1. Compliance with UL Regulations

For UL compliance, the following instructions must be met when operating ProtoCarrier.

The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.

The interconnecting power connector and power cable shall: o Comply with local electrical code o Be suited to the expected operating temperature range o Meet the current and voltage rating for ProtoCarrier

Furthermore, the interconnecting power cable shall: o Be of length not exceeding 3.05m (118.3”) o Be constructed of materials rated VW-1, FT-1 or better

If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access.

This device must not be connected to a LAN segment with outdoor wiring.

9.1. Compliance with UL Regulations• For UL compliance, the following instructions must be met when operating MCS-BMS-GATEWAY.• The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating

temperature range.• The interconnecting power connector and power cable shall:

�� Comply with local electrical code�� Be suited to the expected operating temperature range�� Meet the current and voltage rating for MCS-BMS-GATEWAY

• Furthermore, the interconnecting power cable shall:�� Be of length not exceeding 3.05m (118.3”)�� Be constructed of materials rated VW-1, FT-1 or better

• If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access.

• This device must not be connected to a LAN segment with outdoor wiring.

Page 55: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

MCS-BMS-GATEWAY Startup Guide REVISION 4.2

55

Page 56: Version 4.2 - Rev. 2017-11-30 MCS-BMS-GATEWAY …mcscontrols.com/Documents/MCS/Manuals/MCS-BMS... · MCS-BMS-GATEWAY Startup Guide REVISION 4.2 5 Chapter - 1. Introduction MCS-BMS-GATEWAY

Providing HVAC/R Control Solutions Worldwide

5580 Enterprise Pkwy. Fort Myers, FL 33905Office: (239) 694-0089Fax: (239) 694-0031

www.mcscontrols.com