1-Bms Design

22
8/13/2019 1-Bms Design http://slidepdf.com/reader/full/1-bms-design 1/22 Introduction to BAS Systems

Transcript of 1-Bms Design

Page 1: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 1/22

Introduction to BASSystems

Page 2: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 2/22

Specifying / Design of BMS• Define hardware point types:

 – Analogue - within a specified range – Digital - On / Off or Open / Closed

 – Metering - Water, Electricity via a Contact

• Define Control Strategy – Plant Control Strategy

 – Software Interlocks – Set Values

 – Time Parameters

 – Alarm Limits

Page 3: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 3/22

Analogue Input• Analogue Input

 – 0-10Vdc – 0-10 000 Ohms

 – 0-20mA

• Examples of A.I.

 – Temperature Sensor

 – Humidity Sensor – Pressure Transducer

 – Light Level

 – Solar Level

Page 4: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 4/22

Analogue Output

• Analogue Output – 0 to 10Vdc

• Examples of A.O.

 – Electronic Actuators Valves / Dampers

 – Speed Control

 – Remote Setting Signal

Page 5: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 5/22

Digital Input

• Digital Input (Status or Binary Input) – Clean Contact (Volt Free)

• Examples of D.I.

 – Air Flow Switch

 – Door Contact

 – Water Level Switch

Page 6: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 6/22

Digital Output

• Digital Output (Binary Output) – A Switch

 – 240Vac Rated

 – Override Switches

• Examples of D.O.

 – Start / Stop Fan – Start / Stop Chiller

 – Switch On / Off Lights

Page 7: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 7/22

Meter

• Metered Input (Pulse Input) – A High Speed Pulse

 – Up to 600 Pulses per Minute

• Examples of Metering

 – Water Consumption

 – Electricity Consumption

 – Number of Persons Passing a Turnstile

Page 8: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 8/22

Software Points• Used to define the Control Strategy

• Typical Software Point Types – TIM - Time Schedules

 – SPA - Set Point – CTL - PID Control Algorithms

 – ROT - Rotation of Plant

 – CAL - Calculation

 – PRG - Programmable Freely Defined

 – MD - Maximum Demand

Page 9: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 9/22

Typical AHU Plant

Page 10: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 10/22

Typical AHU PlantD.I. D.I.

D.I.

Page 11: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 11/22

Typical AHU PlantD.I. D.I.

D.I.

D.O.

D.O.

Page 12: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 12/22

Typical AHU PlantD.I. D.I.

D.I.

D.O.

D.O.

A.O. A.O.A.O.

A.O.

A.O. A.O.

Page 13: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 13/22

Typical AHU PlantD.I. D.I.

D.I.

D.O.

D.O.

A.O. A.O.A.O.

A.O.

A.O. A.O.

A.I.

A.I.

Page 14: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 14/22

Select Outstation

• Based on Hardware count

• Match to appropriate Outstation

• Fixed hardware or Modular

• Allow spare capacity for future

expansion

Page 15: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 15/22

UNC 132• Fixed Configuration

• 8 A.I.• 10 D.I.

• (2 Meter)

• 6 A.O.

• 8 D.O.

• Total 32 H/W

• 50 Software points

• EEPROM Backup

Page 16: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 16/22

Modules

Page 17: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 17/22

UNC 196 Outstation• 6 Card Slots

• 16 Channel A.I. Card• 16 Channel D.I. Card

• 16 Channel A.O. Card

• 16 Channel D.O. Card• 6 Channel Meter Card

• Door Status Included

• Power status Included

• Total = 6 X 16 + 2 = 98

• Up to 250 points = 152S/W

Page 18: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 18/22

Page 19: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 19/22

Network Interface Unit

• Terminals

• Modems

• Bridges

• 3 X RS232

• 1 X LAN

Page 20: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 20/22

Keypad• Local Interrogation

• Parameter Changes

Page 21: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 21/22

BAS2800+ SystemsArchitecture

PSTN

X2 5

ISDN

Copper

802.3

Fibre

Field*

Automation*

Management*

* As per CEN TC247 standards

Page 22: 1-Bms Design

8/13/2019 1-Bms Design

http://slidepdf.com/reader/full/1-bms-design 22/22

Building IntegrationSolutions