OSM15/25_Al_2/4 MULTI-CONTROL SERIES Application Guide MAN5002253 Revision 1 Outdoor Circuit Breaker / Recloser 15 kV, ...16 kA, ...630 A 27 kV, ...12.5 kA, ...630 A

Transcript of OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit...

Page 1: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

OSM15/25_Al_2/4MULTI-CONTROL SERIES

Application Guide MAN5002253

Revision 1

Outdoor Circuit Breaker / Recloser15 kV, ...16 kA, ...630 A27 kV, ...12.5 kA, ...630 A

Page 2: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly
Page 3: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

This application guide contains information necessary for installation, commissioning

and operation. It is absolutely necessary for the proper and safe use of the OSM to

read this application guide carefully before starting and to adhere to the instructions

as well as relevant regulations.

Safety First

· Installation, operation and maintenance shall only be carried out by trained and

experienced personnel who are familiar with the equipment and the electrical

safety requirements.

· During installation, commissioning, operation and maintenance of the equipment

the relevant legal regulations (such as NFPA 70E, CEC, ANSI), accident prevention

regulations and the connecting conditions of the electric utilities shall be followed.

· Take note that during operation of the OSM certain parts are subject to

dangerous voltage. Mechanical parts, also remote-controlled, can move quickly.

Failure to comply may result in death, severe personal injury or damage to

equipment.

· Pay attention to the hazard statements located throughout this manual.

· The operating conditions of the OSM shall comply with the technical data specified

in this manual.

· Personnel installing, operating and maintaining the equipment shall be familiar

with this manual and its contents.

For special configurations please contact Tavrida Electric North America.

Page 4: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

4

1

5

6

2

3

4

Table of Contents

1. Introduction• Applicability ....................................................................................................................................................................................................7• Hazard Statements .......................................................................................................................................................................................8• Safety Instructions ........................................................................................................................................................................................8• Definitions .........................................................................................................................................................................................................9• General .............................................................................................................................................................................................................9

2. OSM Recloser• Overview ........................................................................................................................................................................................................ 11• Vacuum Circuit Breaker - VCB .............................................................................................................................................................. 12• Protective Tank ............................................................................................................................................................................................ 14• Main Circuit Bushings .............................................................................................................................................................................. 15• Bushing extensions ................................................................................................................................................................................... 15• Cable Clamps ................................................................................................................................................................................................ 16• Current Transformers ............................................................................................................................................................................... 17• Mechanical Trip ........................................................................................................................................................................................... 18• Mechanical Position Indicator ............................................................................................................................................................ 18

3. Installation: Primary Part• General, Preparation ................................................................................................................................................................................ 20• Bracket Mounting ...................................................................................................................................................................................... 20• Main Terminal Connection ................................................................................................................................................................... 21

4. Installation: Secondary Part• Secondary Connections of the OSM ............................................................................................................................................... 23• Auxiliary Circuit Terminations ............................................................................................................................................................. 23• Protective Earthing ................................................................................................................................................................................... 25• Installation of the Manual Trip Hook ............................................................................................................................................... 25

5. Commissioning, Maintenance• General ............................................................................................................................................................................................................. 27• Commis s ioning Primary Part ............................................................................................................................................................... 27• Commis s ioning S econdary Part ........................................................................................................................................................ 27• Maintenance ................................................................................................................................................................................................. 27• Non-conformity .......................................................................................................................................................................................... 27

6. Receiving and Inspection• Packing ........................................................................................................................................................................................................... 29

• Trans port ....................................................................................................................................................................................................... 30• Unpacking, Goods Received Control .............................................................................................................................................. 30• Rating Plate, Seal ........................................................................................................................................................................................ 31• Storage ............................................................................................................................................................................................................. 31

Page 5: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

5

8

9

10

11

7

7. Product Line• Outdoor Circuit Breaker (OSM) ........................................................................................................................................................... 33• Accessories .................................................................................................................................................................................................... 33

8. Dimensions and Weights• Dimens ions and Weights of the OSM ............................................................................................................................................. 35• Dimens ions of the OSM Earthing Provisions .............................................................................................................................. 35• Dimens ions of the Mounting Provisions ...................................................................................................................................... 35• Standard ANSI Mounting Hardware ............................................................................................................................................... 36

9. Circuit Diagrams

10. Technical Data• Outdoor Circuit Breaker (OSM) ........................................................................................................................................................... 41• Ambient Conditions ................................................................................................................................................................................. 43

11. Legal Information• Warranty .......................................................................................................................................................................................................... 45• Quality Regulations .................................................................................................................................................................................. 45• Complaints and .......................................................................................................................................................................................... 45• Trans port Damage ..................................................................................................................................................................................... 45• Environmental Friendliness .................................................................................................................................................................. 46• Non-conformity Report .......................................................................................................................................................................... 46• Liability ............................................................................................................................................................................................................. 46• Copyright ........................................................................................................................................................................................................ 46

Page 6: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

6

1 Introduction

Page 7: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

7

1

Applicability

This application guide applies to a range of Outdoor Switching Modules (OSM) manufactured by Tavrida Electric that work with a variety of Tavrida and third-party controls:

The model number is shown on the equipment rating plates. If your equipment does not correspond to the numbers in the table above then this manual is not applicable. Please contact your nearest Tavrida Electric office or distributor for the correct documents.

Every care has been taken in the preparation of this manual. However please note that not all the details or variations in the equipment or process being described can be covered. Neither is it expected to address all contingencies associated with the installation and operation of this equipment. For any further information please contact your nearest Tavrida Electric office or distributor.

Model Types Description

OSM15_Al_2(630_150_2) 15.5 kV, three-phase gang operated outdoor fault interrupter / recloser

OSM15_Al_4(2) 15.5 kV, independent pole operated outdoor fault interrupter / recloser

OSM25_Al_2(630_150_2) 27 kV, three-phase gang operated outdoor fault interrupter / recloser

OSM25_Al_4(2) 27 kV, independent pole operated outdoor fault interrupter / recloser

The OSM_Al_2/4 series are compatible with several third party controls, as well as customized Tavrida options. Chapters in this manual refering to mounting, primary connection and operation of the OSM; for all information relating to the operation, mounting and functionality of the supplied control please consult the applicable control manual.

Page 8: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

8

1

Hazard StatementsThis manual contains three types of hazard statements, as follows:

DANGER: Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.

WARNING: Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION: Indicates a potentially hazardous situation that, if not avoided, could result in personal injury or equipment damage.

Safety InstructionsGeneral hazard statements applying to this equipment are described in this section. Statements relating to specific tasks or procedures are located throughout this manual.

DANGER: Contact with hazardous voltage will cause death or severe personal injury. Contact with Recloser or Control Cubicle terminals should only be undertaken when equipment is isolated from applicable sources of voltage.

WARNING: This equipment is not intended to protect human life. Follow all locally approved safety procedures when installing or operating this equipment. Failure to comply may result in death or severe personal injury.

WARNING: Before working with equipment described in this manual carefully read and understand the contents of this manual. Improper handling, installation, operation or maintenance can result in death, severe personal injury or damage to equipment.

WARNING: Power distribution equipment must be properly selected for the intended operation. It must be installed and used in conjunction with all relevant safety procedures. Failure to comply can result in death, personal injury or equipment damage.

Page 9: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

9

1

DefinitionsThe following abbreviations are used in this operating manual:

AR Automatic reclosing CM Control moduleCO Close open cycle SM Switching module LED Light emitting diodeMCB Miniature circuit breaker

Make time The make time is the time period from the energising of the closing circuit to the time when the current begins to flow in the first pole.

Closing timeThe closing time is the time period from the energising of the closing circuit to the time when all three poles have contact.

Pre-arcing timeInterval of time between the initiation of current flow in the first pole during a closing operation and the moment when the contacts touch in all poles for three-phase conditions and the instant when the contacts touch in the arcing pole for single-phase conditions.

Opening timeThe opening time is the time period from energising of the closing circuit up to the time when all the switching poles are separated.

Break time The break time is the time period from the energising of the closing circuit up to the time when the arcs of all the poles are extinguished.

Open-close time (during AR)Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the contacts touch in the first pole during a reclosing cycle.

Dead time (during AR)Interval of time between final arc extinction in all poles in the opening operation and the first reestablishment of current in any pole in the subsequent closing operation.

NC Normally closed contact NO Normally open contactOSM Outdoor Circuit Breaker PCD Pole center distance SCADA Supervisory control and data aquisition VCB Vacuum circuit breaker VI Vacuum interrupter

General The Outdoor Switching Module (OSM) is designed for use as an automatic circuit recloser or sectionalizer on overhead distribution lines and as an outdoor circuit breaker in distribution substation applications for voltages up to 27 kV.

Figure 1

Page 10: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

10

2 OSM Recloser

Page 11: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

11

2

Overview

Tavrida Electric’s OSM provides the following advantages:

Environmentally friendlyThe OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly option - no oil or SF6 despite its compact size.The reliability of the design is proven by the worlds‘ most severe climate and pollution conditions test at the Koeberg Insulator Pollution Test Station (KIPTS) in South Africa.

Smallest Dimensions and lowest WeightTavrida Electric‘s innovative vacuum circuit breaker and the robust aluminium tank contribute to the light weight of the OSM - not more than 76kg - making it the most light weight outdoor circuit breaker in its class, greatly simplifying shipping, handling and installation.

Highest Availability30,000 C-O operations at rated current and up to 100 operations with full short circuit breaking current without any maintenance.

Optimized MeasurementBuilt-in voltage sensors on all six poles and three current transformers guarantee high accuracy over a wide measurement range.

Figure 2 General arrangement of the OSM

1. Terminal

2. Six HV bushings

3. Current transformers built into the bushings

4. Vacuum circuit breaker

5. Protective tank

6. Mechanical position indicator

7. Manual trip operation mechanism

8. Support rail

2

1

3

4

5

6

7

8

Page 12: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

12

Vacuum Circuit Breaker - VCBEach OSM is equipped with Tavrida Electric’s innovative vacuum circuit breaker (VCB). Tavrida Electric has simplified the mechanical structure of the vacuum circuit breaker to the greatest possible degree. It uses three single-coil magnetic actuators, one per pole. All switching elements are assembled along a single axis - all mechanical movements are therefore direct and linear. The three actuators are mounted in a steel frame and mechanically linked by a synchronizing shaft. Optimal selection of all components makes these the most compact vacuum circuit breakers in the world.

Failure of critical components, such as· mechanical latches· gears, chains, bearings and levers· tripping and closing coils· spring charging motors...are completely avoided.

Maximizing the benefits of the drive mechanism requires vacuum interrupters that combine small dimensions with an extraordinarily long mechanical and electrical lifespan. The use of a predefined axial magnetic field shape provides even distribution of current density and consequently substantial improvement of vacuum interrupting performance.Carefully selected contact material and expert contact design as well as optimized movement and switching speed result in bounce-free closing.

Substantial increase in mechanical lifespan as well as size reduction of Tavrida Electric vacuum interrupters was achieved by utilizing metal bellows consisting of welded single discs as opposed to the conventional use of folded steel.

The result is 30,000 C-O cycles at rated current or up to 100 operations at full short-circuit breaking current without the need to replace or adjust any parts of the vacuum circuit breaker.

Tavrida Electric´s vacuum circuit breaker are entirely maintenance free over a total life expectancy of at least 30 years.

1. Upper terminal

2. VI

3. Lower terminal

4. Movable contact with bellows

5. Flexible junction shunt

6. Drive insulator

7. Opening and contact pressure springs

8. Magnetic actuator (complete module)

9. Armature

10. Synchronizing shaft

11. Actuator coil

12. Interlocking pins

13. Auxiliary contacts

14. Frame

15. Support insulator

Figure 3 View into the VCB

Vacuum Circuit Breaker (VCB)

2

1

34

5

6

7

8910111213

14

15

2

Page 13: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

13

Closing Closing operation is possible only if the manual trip hook is in the upper position. In the open position the contacts are kept open by the force of the opening springs. To close the contacts the coils of the magnetic actuators are excited by a current impulse of the close capacitors of the CM. As a result the contacts close, while at the same time the opening springs are compressed. In the closed position the contacts are kept closed by means of the magnetic force only. The VCB maintains the closed position without mechanical latching also in case of a failure of the auxiliary power supply (Figure 4).

Opening To open the contacts a current impulse in the reverse polarity derived from the opening capacitors of the CM is injected in the coils of the magnetic actuators releasing the magnetic holding force. The compressed opening springs and contact pressure springs open the contacts (Figure 4).

Manual Closing The VCB can only be closed electrically via the CM. In the case of a failure of auxiliary power supply the contacts can be closed using an alternative auxiliary power supply such as a battery. Mechanical closing is not possible and leads to the destruction of the VCB.

Manual Trip When the manual trip hook is pulled down the synchronizing shaft is rotated. A force exceeding the magnetic attraction forces of the ring magnet is applied to the armature, which subsequently starts to move. As the air gap increases, the opening springs and the contact pressure springs overcome the magnetic holding force, and the vacuum interrupter opens.

Position main contacts

Actuator coil current

Anchor travel

Anchor velocity

Open

Closed

Open

Closed

0

0

0

Clos

e co

mm

and

CM (d

ry c

onta

ct)

Clos

e im

puls

to V

CB-c

oils

Star

t anc

hor m

ovem

ent

VCB

mai

n co

ntac

ts c

lose

dSt

op a

ncho

r mov

emen

t

Switc

h off

act

uato

r cu

rren

t for

clo

se o

pera

tion

Trip

com

man

d CM

(d

ry c

onta

ct)

Trip

impu

ls to

VCB

-coi

ls

VCB

mai

n co

ntac

ts o

pen

Ope

n po

sitio

n ke

pt b

y op

enin

g sp

rings

0 20 40 60 80 100 120 140 160

Time (ms)

Figure 4 Typical oscillogram of VCB operation

Warning

2

Page 14: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

14

2

Each OSM has the following rating plates:· Serial number plate · Rating plate

The tank supports provide a firm, stable support. The supports are protection against chipping of the powder coating during transportation. These supports shall be removed after installation on the pole.

The protective tank is equipped with a ceramic breather on the bottom. The breather ensures that no dust or pollution ingress occurs.

Protective Tank

The OSM are constructed from an aluminium tank incorporating the vacuum circuit breaker with single coil magnetic actuators. The protective tank consists of two main parts: The housing and the bottom protective cover riveted to the housing. The OSM housing and the cover are made of a corrosion resistant aluminium alloy. Water-tight aluminium rivets are used to secure the cover. The tank is powder coated in light grey (RAL 7038). The tank including the control cable cover provides IP65 degree of protection.

Four threaded holes (M12x30) on each side of the tank allow mounting equipment for pole or substation installation to be fitted. Two of these threaded holes are used to install the set of lifting lugs on the tank. The earthing provision (M12x30 threaded hole) is labelled for easy identification.

Serial number plate

Rating plate

Mounting Provisions

Provisions for Lifting lugs

Tank supports

Ceramic Breather

Figure 5

Figure 6

Figure 7

Earthing Provision

Page 15: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

15

2

Main Circuit BushingsThe main circuit bushings are manufactured from UV stable polymer. They are covered by light grey silicon rubber bushing boots which provide a creepage distance of 500 mm (19.7“) for the 15.5 kV version and 860 mm (33.8“) for the 27 kV version.

The bushings are indelibly marked by stickers with the terminal designation X1, X2, X3 for the normal incoming side and X4, X5 and X6 for the normal outgoing side.

Allowable wire pull at the connection point is 300 N.

Bushing extensions

Bushing extensions of the OSM end with cylindrical rods with a milled surface profile for connection of cables. This surface is necessary for placing of cable conductors. All parts are tin plated, which allows the connection of both aluminum and copper conductors. A special clamp is used for connection of the cables.

Bushing extension of 15.5 kV OSMs Bushing extension of 27 kV OSMs

Each type of bushing extension has special inserts in the bull-end.Inserts are initially fitted with plastic plugs that must be removed before connection of lugs.

Insert

Plastic plugs

Figure 8 Phase Marking

Figure 9 Figure 10

Figure 11 Figure 12

NOTE: Bushing extensions shown for illustrative purposes only. Bushings on the OSM are not removable.

Page 16: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

16

2

Cable ClampsThe clamps allow reliable connection of cable conductors from 35 to 240 mm2.

One clamp is enough for connection of cables up to 90 mm2. Two clamps shall be used for connection of cables 120 mm2 and more.

For protection of connections against environmental conditions protective covers are used.

If the diameter of connected cable is more than 10 mm the end of covers shall be cut off by acorresponding length to provide tight stretching of cover to cable.

Clamp

Nut

Cleat

Plain washerSpring lock washer

Nuts should be torqued to 20±1 Nm.

Figure 13

Figure 14

Figure 15

Figure 16

Figure 17

Figure 18

Page 17: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

17

2

Current TransformersThe OSM15/25_Al_4 are equipped with protection transformers in the bushings X1, X2, X3. The parameters of the current transformers are specified in the Chapter “Technical Data” on page 42.

In case of connection of cables with lugs the lugs shall have 10.5 mm holes.

The range of connected cables with lugs is from 16 to 240 mm2. Bolts M10±25 at torque 30±2 Nm are used. In this case protective covers are not placed. Figure 19

NEMA two-hole and four-hole pads are available for installation onto the OSM.

For both variants, align the pads with the bolt connections as shown in Figure 20. Tighten the bolts to 25±2Nm.

Figure 20 NEMA pads installed

Figure 21 Current transformer

Page 18: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

18

Mechanical TripThe mechanical trip hook is made of zinc anodised steel and coated with powder polymer paint RAL1023 (Figure 22). When pulled down, the OSM is mechanically locked in the OPEN position and electrically interlocked against closing. Until the hook stick lever is pushed back in the closedposition, the OSM remains locked and cannot be electrically operated.

Mechanical Position IndicatorThe position indicators are located under a protective cover underneath the tank and are clearly visible from the ground. The indicator colour is red when the OSM is closed and green when it is opened.Three phase (Al_2) models have a single position indicator.

2

Figure 22 Manual Trip Hook

Figure 23 Open / Close Marking

Page 19: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

19

3Installation: Primary Part

Page 20: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

20

3

Figure 24 Mounting kit TNA_RecUnit_MountFrame_2

General, PreparationAll local and national electrical codes, standards and practices must be adhered to during installation and comissioning of this device. Only licensed and qualified personnel shall perform installation, commissioning and operation.

Bracket MountingThere are different mounting bracket sets available on request. They can be complimented with surge arrestor and PT brackets. After mounting of the OSM its support rails should be removed, as shown in Figures 24 and Figure 25.

Application sample for round wooden pole (Hardware type with two 1kVA transformers for loop schemes shown).

Page 21: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

21

3

Main Terminal ConnectionTools and lubricant required:· Torque wrench· 8mm hex socket head· CG60 contact lubricant (Electrolube, http://www.electrolube.co.uk).

Procedure:· If an existing cable shall be reconnected the old lubricant shall be removed from the contact surfaces.· If an insulated cable is used the insulation of the connecting tip should be stripped by 70 mm (Figure 26).

Figure 26 End of connected tail

· Contact surfaces shall be first smoothed out with a card file or metallic brush and the abrasive dust shall be removed with rags. Then a thin layer of the lubricant, with a thickness of not more than 1 mm, shall be applied onto the connection tip.· Connect stripped portion to the OSM terminal according to Figures 14 and 15.· Tighten the nuts to 20 ± 1 Nm or bolt to 30 ± 2 Nm.· For protection of connections against environments use protective covers according to Figures 16, 17 and 18.

Application sample for trapezoidal concrete pole

Figure 25 Mounting kit 2TES.029.002-01

Page 22: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

22

4 Installation: Secondary Part

Page 23: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

23

4

Secondary Connections of the OSM

The secondary connection of the OSM is realized with a Harting terminal type Han-42DD installed underneath the OSM next to the position indicators.

The protective lid is intended for protection of the auxiliary circuit connections from water and dust. It is made from aluminum and has a finish similar to the protective tank. They are supplied with a rectangular rubber seal to provide the same IP65 degree of protection of the module.

Auxiliary Circuit Terminations

Pin arrangement of Harting terminal Han-42DD is as follows:

Figure 27

Figure 28

Page 24: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

24

OSM Internal Designation Note Associated Harting Pin Number

Common Auxiliary contacts common point 29

AS1.1 NC1(A) auxiliary common point 22

AS2.1 NC2(B) auxiliary common point 17

AS3.1 NC3(C) auxiliary common point 16

YH1.1 Yellow handle contact 15

SC1.1 Phase A-1 actuator coil 2

SC2.1 Phase B-1 actuator coil 4

SC3.1 Phase C-1 actuator coil 6

SC3.2 Phase C-2 actuator coil 7

SC2.2 Phase B-2 actuator coil 5

SC1.2 Phase A-2 actuator coil 3

CT1.1 Phase A CT 21

CT2.1 Phase B CT 28

CT3.1 Phase C CT 35

CT3.2...1.2 CTs common point 27

VS1.1 X1-1 voltage sensor 36

GND X1-2 voltage sensor 30

VS2.1 X2-1 voltage sensor 37

GND X2-2 voltage sensor 31

VS3.1 X3-1 voltage sensor 38

GND X3-2 voltage sensor 32

VS4.1 X4-1 voltage sensor 40

GND X4-2 voltage sensor 39

VS5.1 X5-1 voltage sensor 41

GND X5-2 voltage sensor 33

VS6.1 X6-1 voltage sensor 42

GND X6-2 voltage sensor 34

GND Ground 19

GND Ground 20

GND Ground 25

GND Ground 26

- Not used 12

- Not used 13

- Not used 14

- Not used 18

- Not used 23

- Not used 24

- Not used 1

- Not used 8

- Not used 9

- Not used 10

- Not used 11

Termination of Harting terminals for OSM15/25_Al_4(2), OSM15/25_Al_2(630_150_2)

4

Page 25: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

25

4

Installation of the Manual Trip HookInstallation procedure:· Install the hook after final OSM installation· The M8 nut should be screwed on the threaded end of the hook· The hook with the nut to be drawn up at the mounting seat checking comfortable orientation of the hook· Holding the hook in this position, tighten the M8 nut to 10 Nm as shown in Figure 30.

Protective EarthingFor personnel protection the metal housing of the OSM must be connected according to the applicable regulations, such as DIN VDE 0141, via the marked earth screw of the OSM to the earth arrangement of the pole earth bus or substation. The earth connections can be carried out with cables or flat bar (zinccoated steel or copper). The cross section must be dimensioned such that a worst-case fault current (short circuit) does not cause a weakening of the earth connection (Figure 29).Tighten the earthing bolt to 30 ± 2 Nm of torque.

Reference values for cross sections of earth connection (copper):

Duration of fault current (1 s)

Max. temperature of earth connection

Cross section earth connection

<10 kA/10 kA 300 °C 35-70 mm² (1...3/0 AWG)

16 kA 300 °C 70-95 mm² (3/0...4/0 AWG)

The area around the earth screws shall be cleaned before providing the earth connections. After the occurrence of a short circuit, the proper condition of the protective earthing must be checked.

Figure 29

OSMVoltagetransformer

Umbilical cable

Power supply cable

Control cubicleEarth bus

Control cubicle earthing

OSM earthing

The OSM must be connected to earth ground via the stainless steel grounding bolt at the rear of the OSM tank. All metal objects including mounting hardware should also be suitably grounded. Failure to properly ground the OSM could lead to damage, mis-operation or high voltage potential on metal components.

Caution

Figure 30 Installation of manual trip hook

Page 26: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

26

Commissioning, Maintenance

5

Page 27: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

27

5

GeneralCommissioning, operation and maintenance is only permitted for qualified and trained personnel.

Insofar as installation, commissioning or retrofit is carried out on energized equipment, the relevant safety regulations, including all national and local standards must be adhered to. Failure to comply could result in death or severe injury.

The OSM must always be tested and operated together with the appropriate recloser control. Individual testing is not possible and may lead to the destruction of the OSM.

Danger

Commis s ioning S econdary PartPlease consult the appropriate control manual for commissioning procedures of the secondary part

MaintenanceUnder normal operating conditions (see chapter ”Ambient conditions”, page 43) the OSM is maintenance free for a period of at least 30 years or until it has reached the permissible number of operating cycles.

Non-conformityIf during installation, commissioning, operation or maintenance any non-conformity occurs, action shall be taken in accordance with the non-conformity report on pages 47, 48.

Commis s ioning Primary PartTests at the end of the installation shall include at least: · Operating conditions of OSM comply with requirements of the rating plate.· Check for damage, remove dirt.· Check bolted connections for fixing points and main terminals (also torques) according to page 16.· Protective earthing according to page 25.· Check the manual trip mechanism as follows:

Pull down the manual trip hook when the module is in the closed position. Manual trip hook shall remain in the lowered position and the module shall open. Initiate ”Close“ instruction. It shall be ignored, as in this position of the manual trip hook the actuator coils are isolated. Push the hook upward. It shall remain in the upper position. Initiate ”Close“ instruction again. This time it shall be executed.

Caution

Page 28: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

28

6

Receiving and Inspection

Page 29: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

29

Packing

The OSM/TEL is delivered in a corrugated box with dimensions 810 (L) x 810 (b) x 890 (h) and a weight of not more than 76 kg*. The following information are provided on the OSM packing cartons (Figure 33): · Handling symbols for transport and storage of the delivery unit (Figure 31) · Label 1 for manufacturers‘ product information (Figure 32) · Label 2 for logistics data (Figure 34)

100

Figure 31 Handling symbols

Figure 32 Label 1 for manufacturers‘

and product information

Figure 33 Packing carton

Figure 34 Label 2 Logistics data

3 421 1. This side up

2. Fragile

3. Protect from rain

4. Max. weight on

the delivery unit

5. Serial number

5

Mark: TEG-C-000111Place of delivery:

Consignee: AddressAddressAddressAddressAddressPhone:Contact person

P/O Number: Customer referenceArticle: Article descriptionSerial Number:

TAVRIDA ELECTRIC AG, Wetterkreuz 3, 91058 Erlangen, Germany, Phone: 0049-9131-972079-0

Consignee:

150218

6

* In some cases the OSM will be delivered in a wooden crate, or packaged as a ‘single lift’ device with mounting hardware, OSM and accessories pre-assembled. In these cases please check with the Tavrida shipping department for weights and dimensions of the packaging.

OSM15_Al_4(630_150)

Page 30: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

30

6

Trans port

The OSM shall be transported in the original packing only. The packed goods shall be handled in accordance with the handling symbols. Loading procedures for OSM packing units shall be carried out only with fork lifts or cranes. Lifting gear must not be attached to the bushings, use only lifting lugs attached to the side mounts with suitable clearance of straps or chains. During transportation the OSM must not be exposed to impacts or dropped.

Unpacking, Goods Received Control

Before unpacking, please check the carton for damage and dampness. Removal of the products from the original packing must be carried out with due care. Every OSM shall be inspected for shipping damage or missing components.

Unpacking procedure:· Remove corrugated box· Install lifting lugs· Fit lifting slings (polyester) to the lifting lugs and lift the OSM· Do not attach the lifting slings to the HV-bushings

Scope of delivery for the OSM:

OSM Screwdriver Operating manual Routine test certificate

The following parts are included into corresponding installation kit:Hook 1Bolt DIN933 M12x25 8Nut DIN934 M8 1Washer DIN 125A 13 8Washer DIN 7980 12 8Protective cover AXCA.754529.001 6 Protective cover

The OSM must NEVER be lifted or moved by the bushings. Failure to use approved lifting points could cause damange to the bushing assemblies and compromise the safety of the device. Always use appropriate lifting and mounting points per the information in this manual. Danger

Num

ber

of c

losi

ng-o

peni

ng c

ycle

s

Life cycle of OSM

Page 31: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

31

6

OSM1. Rating plate

2. Serial number

3. Seal

Please check that the rating plates of the delivered devices correspond to the data of the order and technical data given on page 41. Tavrida Electric accepts no warranty for a device if the seal is broken or has been removed.

StorageShould immediate installation not be possible, the OSM shall be stored in the original packing under the following conditions: · The OSM is switched off. · Dessicants must be placed in the packing. · Storage must be closed dry, well ventilated and the room temperature should be between - 40°C and + 40°C (IEC62271-1/ DIN VDE 0670 Part 1000). · If several OSM are stacked a maximum of two layers is permitted.

Rating Plate, Seal

Figure 35 Labelling of the OSM

Figure 36 Seal of the OSM

3

1 2

2

Page 32: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

32

7

Product Line

Page 33: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

33

7

Outdoor Circuit Breaker (OSM)

Accessories

Item number Description Quantity Note

AXCA754529.001 Protective Cover 1

Rubber cover for protection of connection places from environmental effects.A set of these covers (6 pcs) is included in the OSM package, however can be ordered separately if required.

2TES.029.002-01 IEC Mounting Kit for concrete pole 1 For installation of OSM on a concrete pole

TNA_RecUnit_MountFrame_2 ANSI Mounting Kit for wooden pole 1 For installation of OSM on a wooden pole

TNA_RecUnit_Umbilical_4(8) Umbilical Cable, 8 meter length 1 For connection of OSM to control

TNA_RecUnit_Umbilical_4(11) Umbilical Cable, 11 meter length 1 For connection of OSM to control

TNA_RecUnit_Umbilical_4(12) Umbilical Cable, 12 meter length 1 For connection of OSM to control

TNA_RecUnit_Umbilical_4(14) Umbilical Cable, 14 meter length 1 For connection of OSM to control

Model Types - 15 kV Model Types - 27 kV

OSM15_Al_2(630_150_2) OSM25_Al_2(630_150_2)

OSM15_Al_4(2) OSM25_Al_4(2)

Page 34: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

34

8 Dimensions and Weights

Page 35: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

35

8

Dimens ions and Weights of the OSM

Rated voltage, kVDimensions, mm

Weight, kgA B C D Creepage

distanceMinimum taut string distance

15.5 216 260 652 637 500 203 65

27 296 294 731 703 860 203 72

Dimens ions of the OSM Earthing Provisions

Dimens ions of the Mounting Provisions

D

Page 36: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

36

8

Standard ANSI Mounting Hardware

Figure 37 Pole mounting hardware with provision for up to x6

surge arrestors and x2 1kVA transformers for loop

scheme control power

Figure 38 Substation frame mounting hardware with provision

for up to x3 external CT‘s

Page 37: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

37

9Circuit Diagrams

Page 38: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

38

9

09

160

42

30

01

09

15

00

06

10

3

09

30

010

05

42

Co

de

pin

s

09

30

00

09

90

1

Co

de

pin

s

09

30

00

09

90

1

Page 39: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

39

9

09 1

6 04

2 30

01

09 1

5 00

0 61

03

09 3

0 01

0 05

42

Code

pin

s09

30

000

9901

Code

pin

s09

30

000

9901

Page 40: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

40

10

Technical Data

Page 41: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

41

10

Basic Operating Parameters OSM15_Al_2(630_150_2)OSM15_Al_4(2)

OSM25_Al_2(630_150_2)OSM25_Al_4(2)

Rated data

Rated voltage (Ur) 15.5 kV 27 kV

Rated current (Ir) up to 630 A (800 A) 1) depending on CT rated primary current

Rated power frequency withstand voltage (Ud), 1 min dry 50 kV 60 kV (70 kV) 1)

Rated power frequency withstand voltage (Ud), 10s wet 45 kV 50 kV (60 kV) 1)

Rated lightning impulse withstand voltage (peak) (Up) 110 kV 150 kV

Partial discharge decay level, not less than 10 pC @ 13.2 kV 10 pC @ 17.2 kV

Rated short-circuit breaking current (Isc) 16 kA 12.5 kA

Rated short-circuit making current, peak 41.6 kA 32.5 kA

Rated short-time withstand current, 4s (Ik) 16 kA 12.5 kA

Rated frequency (fr) 50/60Hz

Cable charging current 25 A 31.5 A

Line charging current 3.33 A 5 A

Switching performance

Mechanical life (CO-cycles) 30 000

Operating cycles, rated current (CO-cycles) 30 000

Maximum number of CO-cycles per hour Refer to control manual

Operating cycles, rated–short circuit breaking current 100

Closing time, not more than 2) 35 ms

Opening time, not more than 2) 15 ms

Break time, not more than 2) 23 ms

Rated operating sequence Refer to control manual

Standards

International StandardAmerican StandardRussian StandardChinese Standard

IEC 62271-100, IEC 62271-111IEEE C37.60

GOST R 52565-2006GB 1984-2003

Other data

Current sensing 3 current transformers

Voltage sensing 6 voltage sensors

Main contact resistance, not more than 85 µOhm 95 µOhm

Solar radiation ≤ 1.1 kW/m²

Degree of protection IP65

Weight 65 kg 72 kg

Outdoor Circuit Breaker (OSM)

1) 800 A continuous current and 70 kV dielectric products available by special order. Please contact Tavrida Electric North America for further information.2) OSM closing, opening and break times based on Tavrida CM_15 series controls without processing acceptance time. Please see control manual for more information on additional time to calculate a complete fault interruption cycle.

Page 42: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

42

10

Basic Operating Parameters OSM15_Al_2(630_150_2)OSM15_Al_4(2)

OSM25_Al_2(630_150_2)OSM25_Al_4(2)

Design, switching capacity of auxiliary contacts OSM

Number of available auxiliary contacts for OSM 3 NC + 1 NO

Minimum current for (12-30) V AC / DC, ohmic load 100 mA

Minimum current for 12 V AC / DC, inductive load (t=20 ms, cosj =0.3) 100 mA

Maximum current for 30 V DC, ohmic load 5 A

Maximum current for 30 V DC, inductive load (t=20 ms) 3 A

Maximum current for 50 V DC, ohmic load 1 A

Maximum current for 50 V DC, inductive load (t=20 ms) 1 A

Maximum current for 75 V DC, ohmic load 0.75 A

Maximum current for 75 V DC, inductive load (t=20 ms) 0.75 A

Maximum current for 125 V DC, ohmic load 0.5 A

Maximum current for 125 V DC, inductive load (t=20 ms) 0.03 A

Maximum current for 250 V DC, ohmic load 0.25 A

Maximum current for 250 V DC, inductive load (t=20 ms) 0.03 A

Maximum current for 125 V AC, ohmic load 5 A

Maximum current for 125 V AC, inductive load (cosj =0.3) 5 A

Maximum current for 250 V AC, ohmic load 5 A

Maximum current for 250 V AC, inductive load (cosj =0.3) 5 A

Parameter of Current Transformers and Voltage Sensors

OSM15/OSM25_Al_2(630_150_2)OSM15/25_Al_4(2)

Current transformers

Rated primary current A 600

Rated secondary current A 1

Rated output, VA at PF=0.8...1 2.5

Accuracy limit factor for protective current transformers 25

Accuracy class of protective transformers acc. to IEC 60044 at the rated output, PF=0.8...1 C25

Rated continuous thermal current, A 630

Voltage Sensors

Output voltage 0.11 - 0.13 V per kV

Temperature coefficient of capacitance -770 ppm/oC

Continuous reverse voltage of shunted varistor of low arm 22 - 40V real dispersion

Page 43: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

43

Num

ber o

f clo

sing

-ope

ning

cyc

les

Life cycle of OSM

Figure 39

Ambient Conditions The OSM is designed for the following ambient and operating conditions for outdoor installations:

Maximum ambient temperature + 55 °C

Minimum ambient temperature - 50 °C

Humidity 100% condensing

Altidude to 3000 m

Above 1000 m derating according to ANSI C37.6010

Page 44: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

44

11

Legal Information

Page 45: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

45

11

WarrantyUnless otherwise stated in the contract, the warranty period is 3 years from date of invoice. If agreed to otherwise, the contract conditions apply. No warranty is given in the case of …a) … the warranty period having run out during the period of storage with the customer.b) … the operating conditions, ambient conditions, transport and storage conditions have not been adhered to according to the application description or the application guide.c) … an unauthorized manipulation of the device has been carried out, such as opening the housing or damaging the seal.d) … the device has not been properly installed, such as incorrect connection voltages.

Quality RegulationsAll manufacturing facilities of the company have been certified by KEMA in the Netherlands and comply with (DIN EN) ISO 9001:2000.

All technical data of the vacuum circuit breaker are stored in an electronic database for each step of the manufacturing process. Testing of the circuit breakers is carried out in accordance with the relevant standards and beyond that the following test are carried out:

· 1000 C-O cycles · Insulation strength of the primary and auxiliary circuits at operating frequency · Measurement of the resistance of the main circuit · All test results are automatically stored

Complaints and Trans port DamageAll products are shipped exclusively with original packing to ensure safe transport and avoid transport damage (see Packing, Goods Received).

Tavrida Electric will not accept any claims for damages caused by improper transport, storage as well as unpacking. Transport damage must be reported in writing to the supplier as soon as it is discovered. A period of maximum 3 weeks after receipt is allowed for this.

For legitimate claims Tavrida Electric will supply replacement equipment free of charge according to our warrantyregulations. Tavrida Electric reserves the right to verify any claim.

Page 46: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

46

11

Environmental FriendlinessThe modules are manufactured from environmentally friendly material. Therefore, special disposal is not required.

Non-conformity ReportIn order to be able to exchange or repair the device, we kindly ask you to fill the accompanied “Non-conformity report” and send it to our regional representative or directly to us.

Please note:Your request can only be handled if the accompanying report is properly filled including the name and address as well as a copy of the invoice. For queries please contact your Tavrida Electric partner.

LiabilityDamages and demands for reimbursement of expenses incurred by the customer (in the following: compensation) for what-ever legal reasons, especially due to non-compliance of obligations of the contractual obligations and for unauthorized actions, are excluded. This does not apply, insofar as there is a compulsory liability such as according to the product liability law in cases of malice, gross negligence, because of damage to life, the body or health, because of damage to important contractual obligations.

Compensation for damage to important contractual obligations, however, is limited to the damage which can be predicted as typical of the contract insofar as there is no malice or gross negligence, because of damage to life, the body or health. A change of the obligation to provide proof to the disadvantage of the customer is not connected with these regulations.

CopyrightWithout our written permission, this documentation may not be used, also not in extract form, for own general publications, printouts, handbooks, training, lectures, etc. nor copied and further processed. This includes also the duplicating or re-copying in any form of data carriers and microfilms. A one-time written permission is not automatically to be taken as a part or complete surrender of the copyright provisions. We reserve the right to changes. The issue of a new version of these operating instructions renders all other older versions obsolete. Tavrida Electric and its associated companies make every effort to adapt the contents of their documentation to the latest and most current state of development of the products.

The present documentation was produced with the greatest care. However, we are not liable for possible errors in this information text, user-side incorrect interpretation and/or for consequences arising therefrom.

© Copyright 2011; Tavrida Electric reserves the right to make changes to the design and data of their products. Tavrida Electric accepts no responsibility or liability for losses or damage caused by improper actions based on this publication.

TAVRIDA ELECTRIC NA

Service Department1105 Cliveden AvenueDelta, BC, CanadaV3M 6G9

Phone: 604-540-6600Fax: 604-540-6604

E-Mail: [email protected]: www.tavrida-na.com

Page 47: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

47

11

NON-CONFORMITY REPORT

From: To: TAVRIDA ELECTRIC NAService Department

Address: Address: 1105 Cliveden Avenue

Delta, BC, Canada

Name:

Phone: Phone: 604-540-6600

Fax: Fax: 604-540-6604

E-Mail: E-Mail: [email protected]

Type designation OSM Serial No.:

Type designation CM Serial No.:

Date when non-conformity was noticed: Date of commissioning:

When did the non-conformity occur: Incoming inspection Installation/Commissioning Service

Place of installation of control: Pole / substation frame mounted Mounted in control room

Does your installation comply with the requirements of the Technical Manual, OSM?

Primary Part (OSM): Operating conditions of OSM comply with technical data specified in Technical Manual (pages 41-43) Fixing points (page 14) Protective earthing (page 25)

Description of non-conformity:

Non-conformity report issued by:

Date: Name: Signature:

Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.

Page 48: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

48

11

Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.

NON-CONFORMITY REPORT

From: To: TAVRIDA ELECTRIC NAService Department

Address: Address: 1105 Cliveden Ave

Delta, BC, Canada

Name:

Phone: Phone: 604-540-6600

Fax: Fax: 604-540-6604

E-Mail: E-Mail: [email protected]

Type designation OSM Serial No.:

Type designation CM Serial No.:

Date when non-conformity was noticed: Date of commissioning:

When did the non-conformity occur: Incoming inspection Installation/Commissioning Service

Place of installation of the control: Pole / substation frame mounted Mounted in control room

Does your installation comply with the requirements of the Technical Manual, OSM?

Primary Part (OSM): Operating conditions of OSM comply with technical data specified in Technical Manual (pages 41-43) Fixing points (page 14) Protective earthing (page 25)

Description of non-conformity:

Non-conformity report issued by:

Date: Name: Signature:

Page 49: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

49

Date:

11

Page 50: OSM15/25 Al 2/4 - Tavrida Electric - OSM-Al2... · The OSM is an air insulated outdoor circuit breaker with a patented combined insulation that makes it the environmentally friendly

This document is copyright and is intended for users and distributors of Tavrida Electric product. It contains information that is the intellectual property of Tavrida Electric and the document, or any part thereof, should not be copied or reproduced in any form without written permission from Tavrida Electric.