Schedule-2A (Sub-Station) Page 1 of89 Package:17/2012-13(ATRI) ORISSA POWER TRANSMISSION CORPORATION LIMITED CONSTRUCTION OF  220/132/33KV SUB-STATION  ALONG WITH 220KV AND 132KV TRANSMISSION LINES AND ASSOCIATED SYSTEM AT ATRI BID DOCUMENT No.: SR. G.M-CPC-TENDER-ATRI PACKAGE-17/2012-13 (Equipment/Materials Price Break-up of Ex-works Prices against Package- ATRI) PART-I, SCHEDULE-2A (FOR SUBSTATION) TO BE QUOTED IN INR SL NO  Unit Unit Ex-works Price Total Ex-works Price Excise Duty Sales Tax 1 2 3 4 5 6= 4X5 7 8 9 10 1  NOS 33 2 245 KV,2000A,40KA,ISOLATORS 2.1 WITH OUT EARTH SWITCH  NOS 11 2.2 WITH SINGLE EARTH SWITCH  NOS 11 2.3 TANDEM WITHOUT EARTH SWITCH  NOS 17 3  NOS 18 4  NOS 10 5 216 KV, METAL OXIDE SURGE ARRESTOR,10 KA, class III  NOS 24 6 245 KV ,2 CORE,SINGLE PHASE,IVT  NOS 6 7 220 KV Bus Post Insulators  NOS 93 8  NOS 33 9 145 KV,1200A,40 KA,ISOLATORS 9.1  NOS 14 9.2 D/I WITH SINGLE EARTH SWITCH  NOS 6 9.3 D/I WITHOUT EARTH SWITCH  NOS 4 10 145 KV,6600pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER  NOS 18 11 120 KV METAL OXIDE SURGE  ARRESTOR, 10 KA, Class III  NOS 30 12 145 KV ,2 CORE,SINGLE PHASE,IVT  NOS 3 SUPPLY OF FOLLOWING EQUIPMENT  (As per Technical Specification) Quantity for 220/132/33kV Substation at ATRI [10 Nos (6Fdr+2AT+1BT+1B/)220 KV Bays, 11Nos (6Fdr+2AT+2T+1B/C) 132 KV Bays & 07 Nos (4Fdr+2T+1B/C) 33 KV Bays] Mode of Transaction (Direct or Bought-out item) Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For bought-out items, taxes & duties excluding Octroi/Entry Tax are invariably included in the price quoted at column(6)] Other Levies(if any) 245 KV,1200-600-300/1-1-1-1-1 A,40KA,5CORE SINGLE PHASE CURRENT TRANSFORMER 245 KV,4400pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER 245KV,3150A,40KA,SF6,CIRCUIT BREAKER WITH SUPPORTING STRUCTURE 145 KV,(800-400-200/1-1-1-1),40 KA,4CORE SINGLE PHASE CURRENT TRANSFORMER S/I WITH OUT EARTH SWITCH (Includes sectional switches at the main bus near B/C )

Transcript of ORISSA POWER TRANSMISSION CORPORATION LIMITED …old.optcl.co.in/ten/BPS_IB_ATRI .pdf · 2012. 5....

  • Schedule-2A (Sub-Station) Page 1 of89 Package:17/2012-13(ATRI)

    ORISSA POWER TRANSMISSION CORPORATION LIMITEDCONSTRUCTION OF  220/132/33KV SUBSTATION  ALONG WITH 220KV AND 132KV TRANSMISSION LINES AND ASSOCIATED SYSTEM AT ATRI

    BID DOCUMENT No.: SR. G.MCPCTENDERATRI PACKAGE17/201213(Equipment/Materials Price Breakup of Exworks Prices against Package ATRI)

    PARTI, SCHEDULE2A (FOR SUBSTATION) TO BE QUOTED IN INR

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 101  NOS  332 245 KV,2000A,40KA,ISOLATORS

    2.1 WITH OUT EARTH SWITCH  NOS  112.2 WITH SINGLE EARTH SWITCH  NOS  112.3 TANDEM WITHOUT EARTH SWITCH  NOS  173  NOS  18

    4  NOS  105 216 KV, METAL OXIDE SURGE ARRESTOR,10 KA, class III  NOS  246 245 KV ,2 CORE,SINGLE PHASE,IVT  NOS  67 220 KV Bus Post Insulators  NOS  938  NOS  339 145 KV,1200A,40 KA,ISOLATORS

    9.1  NOS  149.2 D/I WITH SINGLE EARTH SWITCH  NOS  69.3 D/I WITHOUT EARTH SWITCH  NOS  410 145 KV,6600pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER  NOS  1811 120 KV METAL OXIDE SURGE  ARRESTOR, 10 KA, Class III  NOS  3012 145 KV ,2 CORE,SINGLE PHASE,IVT  NOS  3

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    245  KV,1200600300/11111  A,40KA,5CORE  SINGLE  PHASE CURRENT TRANSFORMER

    245  KV,4400pF,3CORE,SINGLE  PHASE  CAPACITOR  VOLTAGE TRANSFORMER245KV,3150A,40KA,SF6,CIRCUIT  BREAKER  WITH  SUPPORTING STRUCTURE

    145  KV,(800400200/1111),40  KA,4CORE  SINGLE  PHASE CURRENT TRANSFORMER

    S/I WITH OUT EARTH SWITCH (Includes sectional switches at the main bus near B/C )

  • Schedule-2A (Sub-Station) Page 2 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    13 132 KV Bus Post Insulators  NOS  3014  NOS  11

    15  NOS  15

    16.1  NOS  6

    16.2  NOS  2

    16.3  NOS  2

    16.4  NOS  2

    17 36 KV,800A,25KA,ISOLATORS

    17.1 S/I WITH OUT EARTH SWITCH  NOS  817.2 D/I WITH SINGLE EARTH SWITCH  NOS  417.3 D/I WITHOUT EARTH SWITCH  NOS  217.4 S/I WITH BEAM MOUNTED  NOS  218 30 KV, METAL OXIDE SURGE  ARRESTOR, 10KA, class II  NOS  2419 36 KV ,2 CORE,SINGLE PHASE,IVT  NOS  320  NOS  721 33 KV Bus Post Insulators  NOS  1622 BUS BAR & CIRCUIT MATERIALS

    22.1  SET  48

    145KV,3150A,40KA,SF6,CIRCUIT  BREAKER  WITH  SUPPORTING STRUCTURE36KV(800400200/111A),  25KA,  3CORE  SINGLE  PHASE CURRENT TRANSFORMER36  KV,(800400200/1111  A,(3  PS  CL  &  1  0.2),25KA,3CORE SINGLE PHASE CURRENT TRANSFORMERNCT FOR TRANSFORMER PROTECTION RATING 36 KV,(1200600300/11  A,    HAVING  TWO  PS  CLCORE  (IN  EACH  AUTO TRANSFORMER 1 No. NCT )NCT FOR TRANSFORMER PROTECTION RATING 36 KV,(800400200/11  A,    HAVING  TWO  PS  CLCORE  (  IN  EACH  POWER TRANSFORMER 132 KV SIDE1 NO)NCT FOR TRANSFORMER PROTECTION RATING 36 KV,(800400200/11  A,    HAVING  TWO  PS  CLCORE  (IN  EACH    POWER TRANSFORMER 33 KV SIDE1 NO.)

    36KV,1250A,25KA,VACUUM  CIRCUIT  BREAKER  WITH SUPPORTING STRUCTURE

    160 KN ANTIFOG    INSULATOR STRINGS  for double  tension  twin Moose conductor ( TENSION)220 KV

  • Schedule-2A (Sub-Station) Page 3 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    22.2  SET  132

    22.3  SET  30

    22.4  SET  94

    22.5  SET  18

    22.6  SET  42

    22.7  SET  81

    22.8  SET  66

    22.9  SET  3323 ACSR MOOSE CONDUCTOR 18

    24  LOT  1

    25HARDWARES & FITTINGS/SPACERS/CLAMP  & CONNECTORS

     LOT  1

    26  LOT  127 SUBSTATION EARTHING SYSTEMS

    27.1  LOT  1

    27.2  LOT  1

    160 KN ANTIFOG  INSULATOR STRINGS  for  single  tension single Moose conductor (TENSION)220 KV120  KN  INSULATOR  STRINGS  for  Double  tension  Twin  Moose conductor (TENSION)132 KV120  KN  INSULATOR  STRINGS  for  single  tension  Single  Moose conductor (TENSION)132 KV120  KN  INSULATOR  STRINGS  for  Double  Tension  Twin  Moose conductor ( TENSION)33 KV120  KN  INSULATOR  STRINGS    for  Single  tension  Single  Moose conductor (TENSION)33 KV90  KN  INSULATOR  STRINGS   for  Single  Suspension  Double/ Single Moose cond ( SUSPENSION)220 KV90KN  INSULATOR  STRINGS   for   Single  Suspension  Double/ Single Moose cond ( SUSPENSION)132 KV90  KN  INSULATOR  STRINGS   for  Single  Suspension   Double/ Single Moose cond (SUSPENSION)33 KV

    Kms

    IPS  4"  ALUMINIUM  TUBES(114.2  mm  OD,  &  8.51mm  Thickness)( Required for Equipment to equipment connection in 220 KV side only)

    EARTH WIRES & IT'S HARDWARES & FITTING, with copper earth bond

    EARTHING CONDUCTOR FOR BURRIAL : 75X10 mm GI Flat for laying (spacing maximum 5m both way) EARTHING CONDUCTOR: 50X6 mm GI  Flat for  Raiser from the burial earth mat to equipment,structure etc)

  • Schedule-2A (Sub-Station) Page 4 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    27.3  LOT  1

    27.4  LOT  1

    28  LOT  1

    29

    29.1  NOS  18

    29.2  NOS  4

    29.3  NOS  2

    29.4  NOS  5

    29.5 CT, PT, CVT OUT DOOR CONSOLE BOXES LOT 1

    30

    30.1

    30.1.1 P1S220 KV (NOMINAL UNIT WT 4.5 MT)  NOS  4930.1.2 T1S  132 KV(NOMINAL UNIT WT 1.2 MT)  NOS  2830.1.3 T4S  132KV  (NOMINAL UNIT WT 0.95 MT)  NOS  730.1.4 T8S  33KV(NOMINAL UNIT WT 0.8 MT)  NOS  8

    EARTHING DEVICE & ASSOCIATED ACCESSORIES (50 mm heavy  duty  GI  PERFORATED  PIPE  3  mtrs  long  for    treated earth pit)

    EARTHING DEVICE & ASSOCIATED ACCESSORIES  40mm MS rod 3 mtrs long for non treated earth pit)G.I Cable Trays including support GI angle suitable for different sections i.e. Section:11,22,33 & 44 along with its accessories as per TS.SUB  STATION  SWITCYARD  BMK,AC  CONSOLE  &  OTHER MARSHALLING BOXESBAY MARSHALLING KIOSK  (10 nos on 220 kV bay, 06 Nos 132 kv bay & 02 Nos 33 kv Bay )SWITCH YARD AC CONSOLE FOR LIGHTING  (02 nos on 220 kV bay, 01 Nos 132 kv bay & 01 Nos 33 kv Bay )SWITCH  YARD  RECEPTACLE  BOARD  FOR  TFR  OIL FILTERATION    (01  no.  near  220/132  KV  Auto  Tfr  ,  01  No.  near 132/33 KV Tfr)

    SWITCH  YARD  RECEPTACLE  BOARD  FOR  WELDING  & OTHER EMERGENCY  (02 nos on 220 kV bay, 02 Nos 132 kv bay & 01 Nos 33 kv Bay )

    SWITCH YARD STRUCTURES ( INCLUDING FOUNDATION BOLTS) FOR 220/132/33 KV CLASSDIFFERENT TYPES OF COLUMNS(LATTICE TYPE) WITH DETAILS

  • Schedule-2A (Sub-Station) Page 5 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    30.1.5 T9S  33KV(NOMINAL UNIT WT 0.6 MT)  NOS  1130.2 DIFFERENT TYPE OF BEAMS WITH DETAILS

    30.2.1 Q1S220KV (NOMINAL UNIT WT 1.5 MT)  NOS  4430.2.2 G1   132 KV(NOMINAL UNIT WT 0.62 MT)  NOS  1930.2.3 G1X  132 KV (NOMINAL UNIT WT 1.4 MT)  NOS  430.2.4 G2   132 KV(NOMINAL UNIT WT 0.91 MT)  NOS  830.2.5  NOS  430.2.6 G6  33KV (NOMINAL UNIT WT 0.53 MT)  NOS  330.2.7 G4   33KV(NOMINAL UNIT WT 0.4 MT)  NOS  630.2.8 G4X   33KV (NOMINAL UNIT WT 0.4 MT)  NOS  430.2.9 TOTAL WEIGHT OF COLUMN & BEAM  MT  375.0030.3

    30.3.1 ISOLATORS220KV  SET  3930.3.2 ISOLATORS132KV  SET  2430.3.3 ISOLATORS33 KV  SET  1630.3.4 CTS220 KV  SET  3330.3.5 CTS132 KV  SET  3330.3.6 CTS33 KV  SET  2130.3.7 CVTS220 KV  SET  1830.3.8 CVTS132 KV  SET  1830.3.9 IVTS220 KV  SET  6

    30.3.10 IVTS132 KV  SET  330.3.11 IVTS33 KV  SET  330.3.12 Surge Arrester220 Kv  SET  24

    G1,2    132  KV(Each  two  beams  of  G1  type)    (NOMINAL  UNIT  WT 1.25 MT)

    SUPPORT STRUCTURES (PIPE TYPE) FOR ALL 220KV, 132 KV & 33KV EQUIPMENTS

  • Schedule-2A (Sub-Station) Page 6 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    30.3.13 Surge Arrester132 kV  SET  3030.3.14 Surge Arrester33 kV  SET  630.3.15 Wave Trap220 KV  SET  1230.3.16 Wave Trap132 KV  SET  1230.3.17 BPI220 KV  SET  9330.3.18 BPI132 KV  SET  3030.3.19 BPI33 KV  SET  1630.3.20 NCTS  SET  630.3.21  MT  150.00

    30.4 Total weight of GI Nuts and bolts for the above structures  MT  7231 GENERAL EQUIPMENT & SUBSTATION ACCESSORIES

    31.1

    31.1.1  LOT  131.1.2  LOT  131.1.3  LOT  131.1.4  LOT  131.1.5  LOT  131.1.6  LOT  131.1.7  LOT  131.1.8  LOT  131.2

    31.2.1  LOT  131.2.2  LOT  1

    TOTAL  WEIGHT  OF  SUPPORT  STRUCTURE  FOR  ABOVE EQUIPMENT

    POWER  CABLES,1.1KV,XLPE,ARMOURED,  ALUMINIUM CONDUCTOR (As per Specification)3.5 CX300 mm2

    3.5 CX185 mm2

    3.5 CX120 mm2

    3.5 CX70 mm2

    3.5 CX35 mm2

    4 CX 16 mm2

    4 CX 6 mm2

    2CX 6 mm2

    CONTROL  CABLES,1.1  KV,  PVC,STRANDED  COPPER(As  per specification)4 CX 2.5 mm2

    5 CX 2.5 mm2

  • Schedule-2A (Sub-Station) Page 7 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    31.2.3  LOT  131.2.4  LOT  131.2.5  LOT  131.2.6  LOT  131.2.7  LOT  131.2.8  LOT  1

    32

    32.1  NOS  12

    32.2  NOS  10

    32.3 LINE MATCHING UNIT & LINE MATCHING DISTRIBUTION UNIT  SET  10

    32.4  MTRS  5000

    32.5  NO  1

    32.6 25 PAIR ARMOURED JELLY FILLED CABLE  MTRS  150032.7 10 PAIR ARMOURED TELEPHONE CABLES  MTRS  150032.8 4 PAIR NON ARMOURED TELEPHONE CABLES  MTRS  60032.9 4 WIRE TELEPHONE SET  NO  2032.10 2 WIRE TELEPHONE SET  NO  2032.11 FAX MACHINE  NO  1

    7CX 2.5 mm2

    10 CX 2.5 mm2

    12 CX 2.5 mm2

    16 CX 2.5 mm2

    19 CX 2.5 mm2

    1CX 120 mm2 BAT TO BAT CHARGER & CHARGER TO DCDB

    ACCESSORIES  FOR  PLCC  SYSTEM  AS  PER  TECHNICAL SPECIFICATION220 kV Line Trap  for Pedestal mounting with  complete  accessories :1600A,1mH,  (90500kHZ),Isc=40kA  compatible  to  IEC  353 specifications132 kV Line Trap  for Pedestal mounting with  complete  accessories :800A,  0.5  mH,  (90500kHZ),Isc=40kA  compatible  to  IEC  353 specifications

    12.5 mm OD armoured Co-axial Cable; Impedance: 75 ohms, Insulation Resistance: 100 Meg Ohms Dielectric strengh: 5 kV, Signal attenuation: 6 dB/KM (Max) at 500 kHz

    EPABX(Telephone  Exchange)  standard  complied  to  ITUTG711,G712,Q507,  Q517  capacity  16  lines  /Trunks (2W,4W,RSU),Universal  Numbering  scheme,Operating console,Desktop PCMenue driven.

  • Schedule-2A (Sub-Station) Page 8 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    32.12  SET  232.13 BATTERY CHARGER FOR 48 V, 75 A Float cum Boost  SET  232.14 48 V DCDB  SET  1

    33

    33.1  NOS  2

    33.2  SETS  2

    34

    34.1  LOT  1

    PLANTE TYPE BATTERY 350 AH(FOR 48 V)

    SUPPLY  OF  STATION  TRANSFORMER  &  OTHER  MATERIALS FOR  MEETING  THE  AUXILIARY  SUPPLY  OF  THE  SUBSTATION AS PER TECHNICAL SPECIFICATIONSTATION TRANSFORMER 33KV/433V,315 KVA (AS PER SPECIFICATION)33  KV  AB  SWITCH  IN  33  KV  SIDE(600AMP),HG  FUSE,  DP STRUCTURE(preferably by using 200X100 mm RS Joist),ANGLE FOR BRACING  OF  DP  STRUCTURE,POWER  CABLES,  CHANEL,  FOR ERECTION  OF  TRANSFORMER  INCLUDING    INSULATORS, CONDUCTOR, CLAMPS & CONNECTOR, JUMPERING AND OTHER ACCESSORIES  FOR  COMMISSIONING  OF  THE  STN TRANSFORMER.IT  INCLUDES  LT  OUT  DOOR  KIOSK  MADE  OUT OF 14 SWG GI MARSHALLING BOX OR BETTER , HAVING CABLE TERMINATING  FACILITY  FOR  INCOMING  &  OUT  GOING  TO  THE BOX. THE RATING OF THE BUS BAR, TERMINAL BOX & STUDS TO BE  USED  SHALL  HAVE  CONTINEOUS  RATING  OF  1000  AMP. MARSHALLING  BOXES  ARE  TO  BE  INSTALLED  NEAR  TO  THE AUXILIARY STATION TRANSFORMERS.

    SUB  STATION  LIGHTING  (AS  PER  SPECIFICATION  AND APPROVED  DRAWINGS)(includes  Switch  yard,Colony  street  and other street area)SUBSTATION  SWITCH  YARD    LIGHTING,IT  INCLUDES  SUPPLY OF FIXTURES & LAMPS  (LED) of  reputed make (Philips/CGL/Bajaj) with switch gear,GI Conduit etc.(Lighting  fixtures are  to be  fixed rigidly on the Column at a suitable height so that the required lux can be maintained).

  • Schedule-2A (Sub-Station) Page 9 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    34.2  LOT  1

    34.3  LOT  1

    STREET LIGHTING, IT INCLUDES SUPPLY OF GI TUBULAR POLE,  WITH  LED  LIGHTING  FIXTURES  WITH  LAMPS  of  reputed  make (Philips/CGL/Bajaj)(TO  BE  PROVIDED  IN  THE  SWITCH  YARD, ALONG  THE  ROADS  (APPROACH  INSIDE  YARD  AND    OTHER ROADS).ELECTRICAL SUPPLY TO STREET LIGHTING, COLONY QUARTERS;>  1 NO. OUTDOOR KIOSK FOR STREET LIGHTING PURPOSE HAVING 2 NOS 200 AMP SWITCH FUSE UNITS  AND ,  6 NOS.OUT LETS OF  32 AMP MCB FOR STREET  LIGHTING.  (XLPE  CABLES(3.5  CORE  120  SQMM)  FROM  MAIN  ACDB FROM CONTROL ROOM TO THE OUT DOOR KIOSK. XLPE CABLE OF 4C X 16 SQMM  FROM  OUTDOOR  KIOSK  TO  THE  STREET  LIGHT  POLES  AND  4CX6 SQMM  FROM  POLE  TO  POLE  AND  2CX6  SQMM  FROM  POLE  TO  LIGHTING FIXTURES.)                                                        >  1  NO.  OUTDOOR  KIOSK  FOR  COLONY  SUPPLY  PURPOSE  HAVING  2  NOS. 200 A SWITCH FUSE UNITS, 6 NOS.OUT LETS OF  32 AMP MCB FOR COLONY QUARTES.(  XLPE  CABLES(3.5  CORE  120  SQM)  FROM  MAIN  ACDB  FROM CONTROL  ROOM  TO  THE  OUT  DOOR  KIOSK.  4CX16  SQMM  FROM  KIOSK  TO EACH QUARTER. PROVISION OF CABLE(2C/4C6 SQM) FROM THE OUT DOOR KIOSK INSTALLED NEAR THE QUARTER TO THE RESPECTIVE QUARTERS UP TO  THE  SWITCH  FUSE  UNIT  PROVIDED  INSIDE  THE  QUARTERS.  INDIVIDUAL CABLES FOR INDIVIDUAL QUARTERS. IT ALSO INCLUDES PROPER EARTHING OF THE QUARTER AS PER THE STANDARD PRACTICE AND SPECIFICATION.)>    ALL  THE  STREET  LIGHT  POLE    SHALL  BE  OF  GI  TUBULAR  POLE  AND PROVISION OF A GI JUNCTION BOX WITH SUITABLE COVERS AT A HEIGHT OF 1  METRE  FROM  THE  GROUND.  (LT  UNDER  GROUND  POWER  CABLES  OF 4CX6/16  SQMM  SHALL  BE  CONNECTED  TO  THE  JUNCTION  BOX.)  THE JUNCTION  BOX  SHALL  HAVE  PROVISION  OF  FUSES,  BUSES,  CONNECTORS FOR  CABLE  IN  AND  OUT.  THIS  INCLUDES  SUPPLY  OF  ALL MATERIALS(EXCEPT  CABLES)  AS  PER  APPROVED  DRAWING  AND SPECIFICATION  TO  COMPLETE  THE  STREET  LIGHTING  SYSTEM.  PROPER EARTHING  AS  PER  STANDARD  PRACTICE  FOR  STRRET  LIGHT  POLES  AND OUTDOOR  KIOSKS  ARE  ALSO  INCLUDED  IN  THE  SCOPE  OF  WORKS.  THE STREET LIGHT SHALL BE OF LED LAMP FITTINGS INCLUDING LAMPS.                   (*  REMARKS  :  FOR  SUPPLY  OF  ALL  THE  CABLES  AS  INDICATED  ARE COVERED IN THE CABLE ITEMS AS INDICATED ABOVE AT 31.1)

  • Schedule-2A (Sub-Station) Page 10 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    35  LOT  1

    36

    36.1 FOAM TYPE9 LTRS  NOS  436.2 DRY CHEMICAL POWDER(TROLLEY MOUNTED) 22.5 KGS  NOS  436.3 DRY POWDER TYPE  5 KGS  NOS  436.4  NOS  1036.5  NOS  1036.6  NOS  436.7 FIRE BUCKET (6 NOS IN EACH STAND) WITH STAND  SET  5

    37

    37.1 220 KV SIDE

    37.1.1 FEEDER CONTROL PANEL(CPF2D)  NOS  637.1.2 TRANSFORMER CONTROL PANEL(CPL2D)  NOS  237.1.3 BUS TRANSFER CONTROL PANEL(CPT2D)  NOS  137.1.4 BUSCOUPLER CONTROL PANEL (CPB2D)  NOS  137.1.5 FEEDER RELAY PANEL(RPF2D)  NOS  637.1.6 TRANSFORMER RELAY PANEL(RPL2D)  NOS  237.1.7 BUS TRANSFER RELAY PANEL(RPT2D)  NOS  1

    2  TR  CAPACITY  SPLIT  AIR  CONDITIONING  UNITS  WITH  REMOTE  CONTROL FACILITY:  INCLUDING  SUPPLY  OF  AIR  CONDITIONERS,VOLTAGE STABILISER,CONTROL BOXES  ETC  FOR  COMPLETING THE A.C SCHEME.(AS PER  SPECIFICATION  )    FOR  CONTROL  ROOM,  CARRIER  ROOM  & CONFERENCE ROOM.(*SUPPLY OF CABLES ARE COVERED  IN CABLE  ITEMS AS INDICATED ABOVE AT31.1)

    FIRE  FIGHTING  SYSTEM(PORTABLE  AND  WHEEL  MOUNTED SETS  FOR  CONTROL  ROOM,EQUIPMENT  LIKE  TRANSFORMER AND  OTHER  AREAS  AS  PER  TECH  SPEC(REFER  TSVOLIIASCOPE OF WORKAT SL NO. 16ANNEXURE  I)

    CO2  4.5 KGS

    CO2  9 KGS

    CO2 (TROLLY MOUNTED) 22.5 KGS 

    PROTECTION,CONTROL  METERING,  EVENT  LOGGER,BUS  BAR PROTN PAN,COMM PAN, RELAY TOOL KITS AS PER  TECH SPEC 

  • Schedule-2A (Sub-Station) Page 11 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    37.1.8 BUSCOUPLER RELAY PANEL (RPB2D)  NOS  137.1.9 COMMON PANEL (KP2)  NOS  1

    37.1.10 SYNCHRONOUS TROLLY  NOS  137.1.11 BUSBAR RELAY PANEL(RBB2D)  NOS  137.1.12 TIME SYNCH EQUIPMENT  NOS  137.1.13 EVENT LOGGER PANEL  NOS  1

    37.2 132 KV SIDE

    37.2.1 FEEDER CONTROL PANEL(CPF1M)  NOS  6

    37.2.2  NOS  4

    37.2.3 BUSCOUPLER CONTROL PANEL (CPB1M)  NOS  137.2.4 FEEDER RELAY PANEL(RPF1M)  NOS  6

    37.2.5  NOS  4

    37.2.6 BUSCOUPLER RELAY PANEL (RPB1M)  NOS  137.2.7 COMMON PANEL (KP1)  NOS  137.3 33 KV SIDE

    37.3.1 FEEDER CONTROL & RELAY PANEL(CPF/RPF0M)  NOS  437.3.2 TRANSFORMER CONTROL & RELAY PANEL(CPL/RPL0M)  NOS  237.3.3 BUSCOUPLER CONTROL & RELAY PANEL (CPB/RPB0M)  NOS  1

    38 AC & DC SYSTEM

    38.1 AC SYSTEM

    38.1.1  SET  1

    TRANSFORMER  CONTROL  PANEL(CPL1M)(2  for  132  KV  Side  of 220/132/33 KV Auto Tfr + 2 for 132 KV side of 132/33 KV Power Tfr)

    TRANSFORMER RELAY PANEL(RPL1M), 02 NOS FOR 220/132 KV AUTO TRANSFORMERS ON 132 KV SIDE AND 02 NOS FOR 132/33 KV OTHER TRANSFORMERS

    MAIN  AC  DB,(HAVING  800  A,50KA,DRAWOUT  TYPE  ACB  WITH  3 O/C,E/F,U/V  RELAYING  FACILITY  INDOOR  TYPE  AS  PER SPECIFICATION.(MAIN DB1,MAIN DB2 WITH B/C)

  • Schedule-2A (Sub-Station) Page 12 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    38.1.2  SET  1

    38.1.3  SET  1

    38.1.4  SET  138.1.5 EMERGENCY LIGHTING DISTRIBUTION BOARD  SET  138.1.6 INDOOR RECEPTACLE BOARD  SET  138.2 DC SYSTEM

    38.2.1  SET  1

    38.2.2 220 V DC EMERGENCY DISTRIBUTION BOARD  SET  139 BATTERY (350 AH PLANTE TYPE) FOR 220 V DC  SET  240  SET  241 DISTLED WATER PLANT OF 10 LTR/HR FOR BATTERY BANKS  SET  142

    WALKIE TALKIE SET 2

    43  NOS  2

    44  SET  1

    45  SET  1

    46  NOS  1

    ACDB (HAVING 400A MCCB) AS PER SPECIFICATION (AC DB1,AC DB2 WITH B/C)MAIN LIGHTING DISTRIBUTION BOARD (HAVING  250A MCCB AS INCOMER)AS PER SPECIFICATION (WITH DB1,DB2 & B/C)

    INDOOR  LIGHTING  DISTRIBUTION  BOARD  AS  PER SPECIFICATION. (WITH DB1,DB2 & B/C)

    220  V  DC  BOARD  (HAVING  100A  DC  MCCB  AS  INCOMER,  E/F (EARTH  LEAKAGE),  UNDER  &  OVER  VOLTAGE    AS  PER SPECIFICATION (DC DB1,DC DB2 & B/C)

    BATTERY  CHARGER  FOR  220  V,  350  AH  BATTERY  (FLOAT  AND FLOAT CUM BOOST)

    SET/PAIR

    PORTABLE  ALUMINIUM  LADDER  EXTENDABLE  TYPE  OF ADEQUATE  HEIGHT  TO  BE  USED  FOR  MAINTENANCE  OF EQUIPMENT  INSIDE  SWITCH  YARD.(REFER  TSVOLIIASCOPE OF WORKAT SL NO. 19)

    PEDESTAL  MOUNTED  WHEEL  FITTED  DERRICK  FOR  LIFTING/ LOWERING OF MATERIALS UP TO 1.5 TON CAPACITY.(REFER TSVOLIIASCOPE OF WORKAT SL NO. 20)POWER WINCH NEAR STORE SHED FOR HANDLING  MATERIALS UPTO 5 TON CAPACITY.WATER COOLER WITH WATER PURIFIER(purification system of ISI mark) SYSTEM

  • Schedule-2A (Sub-Station) Page 13 of89 Package:17/2012-13(ATRI)

    SL NO  Unit 

    Unit 

    Exw

    orks

     Pric

    e

    Tota

    l Ex

    wor

    ks P

    rice

    Excise Duty  Sales Tax

    1 2 3 4 5 6= 4X5 7 8 9 10

    SUPPLY OF FOLLOWING EQUIPMENT (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Mode of Transaction 

    (Direct or Boughtout 

    item)

    Total Taxes & Duties applicable for transaction between bidder and OPTCL and not included in the price at Column(6) [For boughtout items, taxes & duties excluding Octroi/Entry Tax are invariably 

    included in the price quoted at column(6)]

    Other Levies(if any)

    47  LOT  1

    48  LOT  1

    49  LOT  1

    50  LOT  1

    TOTAL OF SUBSTATION (PARTI)2A (SUPPLY)Note:

    1 Before filling up rate/amount etc. in the schedules bidders are requested to read carefully the instruction given in VolI of Bidding Document.2 Bidders are required to fill up amount in all column except shaded portion.

    3

    4 Kindly enclose soft copy of the duly filled schedule in a CD with the priced copy of Bid.5 In mode of transaction column please indicate Direct/BoughtOut. For Taxes & Duties on Direct/Boughtout items ref clause 6.0 of SCC (VolIA)

    Date   : (Signature) ……………………………………………Place : ( Name)  ………………………………………………

    ( Designation ) ………………………………………. (Common Seal) …………………………………… 

    MAINTENANCE  TESTING  EQUIPMENT    (REFER  TSVOLIIASCOPE  OF  WORKAT  SL  NO.  17  ANNEXURE    II  ,INDICATED  IN SCHEDULE OF REQUIREMENTS OF MAINTENANCE EQUIPMENT)

    OTHER TOOLS AND PLANTS (T&P's) REQUIREMENT  (REFER TSVOLIIASCOPE  OF  WORKAT  SL  NO.  18  ANNEXURE    III ,INDICATED IN SCHEDULE OF REQUIREMENTS OTHER T&P's)

    OFFICE FURNITURE  (REFER TSVOLIIASCOPE OF WORKAT SL NO.  18  ANNEXURE    IV  ,INDICATED  IN  SCHEDULE  OF REQUIREMENTS  OFFICE  FURNITURE)  &  PLACING  IN  CONTROL ROOM,CONFERENCE  ROOM,OFFICE  ROOMS,LIBRARY,TESTING LAB,etc.

    BEST QUALITY & APPROVED MAKE   RUBBER MAT TO BE KEPT INFRONT & BACK SIDE (where doors of the panels are provided) OF ALL PANELS,BOARDS ETC.

    Bidders are requested not to leave any column blank. If any column is left blank it shall be considered that amount against those items are included in any other item and the total amount for that item shall be calculated as free of cost (Zero value). No rate shall be furnished/obtained after bid opening (Ref clause no 33.4.1 of INB volI) 

  • Schedule-2B (Sub-Station) Page 14 of89 Package:17/2012-13 (ATRI)

    ORISSA POWER TRANSMISSION CORPORATION LIMITED

    BID DOCUMENT No.: SR. G.MCPCTENDERATRI PACKAGE17/201213(Equipment/Materials Price Breakup of Exworks Prices F&I against Package ATRI)

    PARTI, SCHEDULE2B (FOR SUBSTATION) TO BE QUOTED IN INR

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    1  NOS  332 245 KV,2000A,40KA,ISOLATORS

    2.1 WITH OUT EARTH SWITCH  NOS  112.2 WITH SINGLE EARTH SWITCH  NOS  112.3 TANDEM WITHOUT EARTH SWITCH  NOS  173

    245 KV,4400pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER NOS  18

    CONSTRUCTION OF  220/132/33KV SUBSTATION  ALONG WITH 220KV AND 132KV TRANSMISSION LINES AND ASSOCIATED SYSTEM AT ATRI

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    245  KV,1200600300/11111  A,40KA,5CORE  SINGLE  PHASE  CURRENT TRANSFORMER

  • Schedule-2B (Sub-Station) Page 15 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    4245KV,3150A,40KA,SF6,CIRCUIT BREAKER WITH SUPPORTING STRUCTURE

     NOS  105 216 KV, METAL OXIDE SURGE ARRESTOR,10 KA, class III  NOS  246 245 KV ,2 CORE,SINGLE PHASE,IVT  NOS  67 220 KV Bus Post Insulators  NOS  938  NOS  339 145 KV,1200A,40 KA,ISOLATORS

    9.1  NOS  149.2 D/I WITH SINGLE EARTH SWITCH  NOS  69.3 D/I WITHOUT EARTH SWITCH  NOS  410 145 KV,6600pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER  NOS  1811 120 KV METAL OXIDE SURGE  ARRESTOR, 10 KA, Class III  NOS  3012 145 KV ,2 CORE,SINGLE PHASE,IVT  NOS  3

    145  KV,(800400200/1111),40  KA,4CORE  SINGLE  PHASE  CURRENT TRANSFORMER

    S/I  WITH  OUT  EARTH  SWITCH  (Includes  sectional  switches  at  the  main  bus near B/C )

  • Schedule-2B (Sub-Station) Page 16 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    13 132 KV Bus Post Insulators  NOS  3014

    145KV,3150A,40KA,SF6,CIRCUIT BREAKER WITH SUPPORTING STRUCTURE NOS  11

    15  NOS  15

    16.1  NOS  6

    16.2  NOS  2

    16.3  NOS  2

    16.4  NOS  2

    17 36 KV,800A,25KA,ISOLATORS

    17.1 S/I WITH OUT EARTH SWITCH  NOS  8

    36KV(800400200/111A),  25KA,  3CORE  SINGLE  PHASE  CURRENT TRANSFORMER36  KV,(800400200/1111  A,(3  PS  CL  &  1  0.2),25KA,3CORE  SINGLE  PHASE CURRENT TRANSFORMERNCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(1200600300/11  A,   HAVING TWO PS CLCORE (IN EACH AUTO TRANSFORMER 1 No. NCT )NCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(800400200/11  A,   HAVING TWO PS CLCORE (  IN EACH POWER TRANSFORMER 132 KV SIDE1 NO)NCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(800400200/11  A,   HAVING  TWO  PS  CLCORE  (IN  EACH    POWER  TRANSFORMER  33  KV  SIDE1 NO.)

  • Schedule-2B (Sub-Station) Page 17 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    17.2 D/I WITH SINGLE EARTH SWITCH  NOS  417.3 D/I WITHOUT EARTH SWITCH  NOS  217.4 S/I WITH BEAM MOUNTED  NOS  218 30 KV, METAL OXIDE SURGE  ARRESTOR, 10KA, class II  NOS  2419 36 KV ,2 CORE,SINGLE PHASE,IVT  NOS  320  NOS  721 33 KV Bus Post Insulators  NOS  1622 BUS BAR & CIRCUIT MATERIALS

    22.1  SET  48

    22.2  SET  132

    22.3  SET  30

    36KV,1250A,25KA,VACUUM  CIRCUIT  BREAKER  WITH  SUPPORTING STRUCTURE

    160  KN  ANTIFOG    INSULATOR  STRINGS  for  double  tension  twin  Moose conductor ( TENSION)220 KV160  KN  ANTIFOG  INSULATOR  STRINGS  for  single  tension  single  Moose conductor (TENSION)220 KV120  KN  INSULATOR  STRINGS  for  Double  tension  Twin  Moose  conductor (TENSION)132 KV

  • Schedule-2B (Sub-Station) Page 18 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    22.4  SET  94

    22.5  SET  18

    22.6  SET  42

    22.7  SET  81

    22.8  SET  66

    22.9  SET  3323 ACSR MOOSE CONDUCTOR  Kms  1824  LOT  125 HARDWARES & FITTINGS/SPACERS/CLAMP  & CONNECTORS  LOT  126  LOT  1

    120  KN  INSULATOR  STRINGS  for  single  tension  Single  Moose  conductor (TENSION)132 KV120  KN  INSULATOR  STRINGS  for  Double  Tension  Twin  Moose  conductor ( TENSION)33 KV120  KN  INSULATOR  STRINGS    for  Single  tension  Single  Moose  conductor (TENSION)33 KV90 KN INSULATOR STRINGS  for Single Suspension Double/ Single Moose cond ( SUSPENSION)220 KV90KN INSULATOR STRINGS  for  Single Suspension Double/ Single Moose cond ( SUSPENSION)132 KV90  KN  INSULATOR  STRINGS   for  Single  Suspension   Double/  Single  Moose cond (SUSPENSION)33 KV

    IPS  4"  ALUMINIUM  TUBES(114.2  mm  OD,  &  8.51mm  Thickness)(  Required  for Equipment to equipment connection in 220 KV side only)

    EARTH WIRES & IT'S HARDWARES & FITTING, with copper earth bond

  • Schedule-2B (Sub-Station) Page 19 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    27 SUBSTATION EARTHING SYSTEMS

    27.1  LOT  1

    27.2  LOT  1

    27.3  LOT  1

    27.4  LOT  1

    28  LOT  1

    29

    29.1  NOS  18

    EARTHING  CONDUCTOR  FOR  BURRIAL  :  75X10  mm  GI  Flat  for  laying (spacing maximum 5m both way) EARTHING CONDUCTOR: 50X6 mm  GI    Flat  for    Raiser  from  the  burial  earth  mat  to equipment,structure etc)

    EARTHING DEVICE & ASSOCIATED ACCESSORIES  (50 mm heavy duty GI PERFORATED PIPE 3 mtrs long for  treated earth pit)EARTHING DEVICE & ASSOCIATED ACCESSORIES  40mm MS rod 3 mtrs long for non treated earth pit)G.I Cable Trays including support GI angle suitable for different sections i.e. Section:11,22,33 & 44 along with its accessories as per TS.SUB  STATION  SWITCYARD  BMK,AC  CONSOLE  &  OTHER MARSHALLING BOXESBAY MARSHALLING KIOSK  (10 nos on 220 kV bay, 06 Nos 132 kv bay & 02 Nos 33 kv Bay )

  • Schedule-2B (Sub-Station) Page 20 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    29.2  NOS  4

    29.3  NOS  2

    29.4  NOS  5

    29.5 CT, PT, CVT OUT DOOR CONSOLE BOXES LOT 1

    30

    30.1 DIFFERENT TYPES OF COLUMNS(LATTICE TYPE) WITH DETAILS

    30.1.1 P1S220 KV (NOMINAL UNIT WT 4.5 MT)  NOS  4930.1.2 T1S  132 KV(NOMINAL UNIT WT 1.2 MT)  NOS  2830.1.3 T4S  132KV  (NOMINAL UNIT WT 0.95 MT)  NOS  730.1.4 T8S  33KV(NOMINAL UNIT WT 0.8 MT)  NOS  8

    SWITCH  YARD  AC  CONSOLE  FOR  LIGHTING  (02  nos  on  220  kV  bay,  01 Nos 132 kv bay & 01 Nos 33 kv Bay )SWITCH  YARD  RECEPTACLE  BOARD  FOR TFR  OIL  FILTERATION    (01 no. near 220/132 KV Auto Tfr , 01 No. near 132/33 KV Tfr)SWITCH  YARD  RECEPTACLE  BOARD  FOR  WELDING  &  OTHER EMERGENCY  (02 nos on 220 kV bay, 02 Nos 132 kv bay & 01 Nos 33 kv Bay )

    SWITCH  YARD  STRUCTURES  (  INCLUDING  FOUNDATION  BOLTS)  FOR 220/132/33 KV CLASS

  • Schedule-2B (Sub-Station) Page 21 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    30.1.5 T9S  33KV(NOMINAL UNIT WT 0.6 MT)  NOS  1130.2 DIFFERENT TYPE OF BEAMS WITH DETAILS

    30.2.1 Q1S220KV (NOMINAL UNIT WT 1.5 MT)  NOS  4430.2.2 G1   132 KV(NOMINAL UNIT WT 0.62 MT)  NOS  1930.2.3 G1X  132 KV (NOMINAL UNIT WT 1.4 MT)  NOS  430.2.4 G2   132 KV(NOMINAL UNIT WT 0.91 MT)  NOS  830.2.5 G1,2  132 KV(Each two beams of G1 type)  (NOMINAL UNIT WT 1.25 MT)  NOS  430.2.6 G6  33KV (NOMINAL UNIT WT 0.53 MT)  NOS  330.2.7 G4   33KV(NOMINAL UNIT WT 0.4 MT)  NOS  630.2.8 G4X   33KV (NOMINAL UNIT WT 0.4 MT)  NOS  430.2.9 TOTAL WEIGHT OF COLUMN & BEAM  MT  375.0030.3

    30.3.1 ISOLATORS220KV  SET  39

    SUPPORT  STRUCTURES  (PIPE  TYPE)  FOR  ALL  220KV,  132  KV  &  33KV EQUIPMENTS

  • Schedule-2B (Sub-Station) Page 22 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    30.3.2 ISOLATORS132KV  SET  2430.3.3 ISOLATORS33 KV  SET  1630.3.4 CTS220 KV  SET  3330.3.5 CTS132 KV  SET  3330.3.6 CTS33 KV  SET  2130.3.7 CVTS220 KV  SET  1830.3.8 CVTS132 KV  SET  1830.3.9 IVTS220 KV  SET  6

    30.3.10 IVTS132 KV  SET  330.3.11 IVTS33 KV  SET  330.3.12 Surge Arrester220 Kv  SET  2430.3.13 Surge Arrester132 kV  SET  3030.3.14 Surge Arrester33 kV  SET  630.3.15 Wave Trap220 KV  SET  12

  • Schedule-2B (Sub-Station) Page 23 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    30.3.16 Wave Trap132 KV  SET  1230.3.17 BPI220 KV  SET  9330.3.18 BPI132 KV  SET  3030.3.19 BPI33 KV  SET  1630.3.20 NCTS  SET  630.3.21 TOTAL WEIGHT OF SUPPORT STRUCTURE FOR ABOVE EQUIPMENT  MT  150.00

    30.4 Total weight of GI Nuts and bolts for the above structures  MT  7231 GENERAL EQUIPMENT & SUBSTATION ACCESSORIES

    31.1

    31.1.1  LOT  131.1.2  LOT  131.1.3  LOT  131.1.4  LOT  1

    POWER  CABLES,1.1KV,XLPE,ARMOURED,  ALUMINIUM  CONDUCTOR  (As  per Specification)3.5 CX300 mm2

    3.5 CX185 mm2

    3.5 CX120 mm2

    3.5 CX70 mm2

  • Schedule-2B (Sub-Station) Page 24 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    31.1.5  LOT  131.1.6  LOT  131.1.7  LOT  131.1.8  LOT  131.2

    CONTROL CABLES,1.1 KV, PVC,STRANDED COPPER(As per specification)

    31.2.1  LOT  131.2.2  LOT  131.2.3  LOT  131.2.4  LOT  131.2.5  LOT  131.2.6  LOT  131.2.7  LOT  131.2.8  LOT  1

    3.5 CX35 mm2

    4 CX 16 mm2

    4 CX 6 mm2

    2CX 6 mm2

    4 CX 2.5 mm2

    5 CX 2.5 mm2

    7CX 2.5 mm2

    10 CX 2.5 mm2

    12 CX 2.5 mm2

    16 CX 2.5 mm2

    19 CX 2.5 mm2

    1CX 120 mm2 BAT TO BAT CHARGER & CHARGER TO DCDB

  • Schedule-2B (Sub-Station) Page 25 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    32 ACCESSORIES FOR PLCC SYSTEM AS PER TECHNICAL SPECIFICATION

    32.1  NOS  12

    32.2  NOS  1032.3 LINE MATCHING UNIT & LINE MATCHING DISTRIBUTION UNIT  SET  10

    32.4  MTRS  5000

    32.5  NO  1

    32.6 25 PAIR ARMOURED JELLY FILLED CABLE  MTRS  150032.7 10 PAIR ARMOURED TELEPHONE CABLES  MTRS  150032.8 4 PAIR NON ARMOURED TELEPHONE CABLES  MTRS  60032.9 4 WIRE TELEPHONE SET  NO  20

    220 kV Line Trap    for Pedestal mounting with   complete   accessories :1600A,1mH, (90500kHZ),Isc=40kA compatible to IEC 353 specifications132 kV Line Trap  for Pedestal mounting with  complete  accessories :800A, 0.5 mH, (90500kHZ),Isc=40kA compatible to IEC 353 specifications

    12.5 mm OD armoured Co-axial Cable; Impedance: 75 ohms, Insulation Resistance: 100 Meg Ohms Dielectric strengh: 5 kV, Signal attenuation: 6 dB/KM (Max) at 500 kHzEPABX(Telephone  Exchange)  standard  complied  to  ITUTG711,G712,Q507, Q517  capacity  16  lines  /Trunks  (2W,4W,RSU),Universal  Numbering scheme,Operating console,Desktop PCMenue driven.

  • Schedule-2B (Sub-Station) Page 26 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    32.10 2 WIRE TELEPHONE SET  NO  2032.11 FAX MACHINE  NO  132.12  SET  232.13 BATTERY CHARGER FOR 48 V, 75 A Float cum Boost  SET  232.14 48 V DCDB  SET  1

    33

    33.1 STATION TRANSFORMER 33KV/433V,315 KVA (AS PER SPECIFICATION)  NOS  2

    PLANTE TYPE BATTERY 350 AH(FOR 48 V)

    SUPPLY  OF  STATION  TRANSFORMER  &  OTHER  MATERIALS  FOR  MEETING THE  AUXILIARY  SUPPLY  OF  THE  SUBSTATION  AS  PER  TECHNICAL SPECIFICATION

  • Schedule-2B (Sub-Station) Page 27 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    33.2  SETS  2

    34

    34.1  LOT  1

    33 KV AB SWITCH IN 33 KV SIDE(600AMP),HG FUSE, DP STRUCTURE(preferably by  using  200X100  mm  RS  Joist),ANGLE  FOR  BRACING  OF  DP STRUCTURE,POWER  CABLES,  CHANEL,  FOR  ERECTION  OF  TRANSFORMER INCLUDING    INSULATORS,  CONDUCTOR,  CLAMPS  &  CONNECTOR, JUMPERING  AND  OTHER  ACCESSORIES  FOR  COMMISSIONING  OF  THE  STN TRANSFORMER.IT INCLUDES LT OUT DOOR KIOSK MADE OUT OF 14 SWG GI MARSHALLING  BOX  OR  BETTER  ,  HAVING  CABLE  TERMINATING  FACILITY FOR  INCOMING & OUT GOING TO THE BOX. THE RATING OF THE BUS BAR, TERMINAL BOX & STUDS TO BE USED SHALL HAVE CONTINEOUS RATING OF 1000  AMP.  MARSHALLING  BOXES  ARE  TO  BE  INSTALLED  NEAR  TO  THE AUXILIARY STATION TRANSFORMERS.

    SUB  STATION  LIGHTING  (AS  PER  SPECIFICATION  AND  APPROVED DRAWINGS)(includes Switch yard,Colony street and other street area)SUBSTATION SWITCH YARD  LIGHTING,IT INCLUDES SUPPLY OF FIXTURES & LAMPS (LED) of reputed make (Philips/CGL/Bajaj) with switch gear,GI Conduit etc.(Lighting fixtures are to be fixed rigidly on the Column at a suitable height so that the required lux can be maintained).

  • Schedule-2B (Sub-Station) Page 28 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    34.2  LOT  1STREET  LIGHTING,  IT  INCLUDES  SUPPLY OF GI TUBULAR  POLE,    WITH  LED LIGHTING  FIXTURES  WITH  LAMPS  of  reputed  make  (Philips/CGL/Bajaj)(TO  BE PROVIDED  IN  THE  SWITCH  YARD,  ALONG  THE  ROADS  (APPROACH  INSIDE YARD AND  OTHER ROADS).

  • Schedule-2B (Sub-Station) Page 29 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    34.3  LOT  1

    ELECTRICAL SUPPLY TO STREET LIGHTING, COLONY QUARTERS;> 1 NO. OUTDOOR KIOSK FOR STREET LIGHTING PURPOSE HAVING 2 NOS 200 AMP SWITCH FUSE  UNITS    AND  ,    6  NOS.OUT  LETS  OF    32  AMP  MCB  FOR  STREET  LIGHTING.  (XLPE CABLES(3.5 CORE 120 SQMM) FROM MAIN ACDB FROM CONTROL ROOM TO THE OUT DOOR KIOSK. XLPE CABLE OF 4C X 16 SQMM FROM OUTDOOR KIOSK TO THE STREET LIGHT POLES AND  4CX6  SQMM  FROM  POLE  TO  POLE  AND  2CX6  SQMM  FROM  POLE  TO  LIGHTING FIXTURES.)                                                        >  1  NO.  OUTDOOR  KIOSK  FOR  COLONY  SUPPLY  PURPOSE  HAVING  2  NOS.  200  A  SWITCH FUSE UNITS, 6 NOS.OUT LETS OF  32 AMP MCB FOR COLONY QUARTES.( XLPE CABLES(3.5 CORE 120 SQM) FROM MAIN ACDB FROM CONTROL ROOM TO THE OUT DOOR KIOSK. 4CX16 SQMM FROM KIOSK TO EACH QUARTER. PROVISION OF CABLE(2C/4C6 SQM) FROM THE OUT DOOR KIOSK INSTALLED NEAR THE QUARTER TO THE RESPECTIVE QUARTERS UP TO THE SWITCH FUSE UNIT PROVIDED INSIDE THE QUARTERS. INDIVIDUAL CABLES FOR INDIVIDUAL QUARTERS.  IT  ALSO  INCLUDES  PROPER  EARTHING  OF  THE  QUARTER  AS  PER  THE STANDARD PRACTICE AND SPECIFICATION.)>  ALL THE STREET LIGHT POLE  SHALL BE OF GI TUBULAR POLE AND PROVISION OF A GI JUNCTION BOX WITH SUITABLE COVERS AT A HEIGHT OF 1 METRE FROM THE GROUND. (LT UNDER  GROUND  POWER  CABLES  OF  4CX6/16  SQMM  SHALL  BE  CONNECTED  TO  THE JUNCTION  BOX.)  THE  JUNCTION  BOX  SHALL  HAVE  PROVISION  OF  FUSES,  BUSES, CONNECTORS FOR CABLE IN AND OUT. THIS INCLUDES SUPPLY OF ALL MATERIALS(EXCEPT CABLES)  AS  PER  APPROVED  DRAWING  AND  SPECIFICATION  TO  COMPLETE  THE  STREET LIGHTING SYSTEM. PROPER EARTHING AS PER STANDARD PRACTICE FOR STRRET LIGHT POLES  AND  OUTDOOR  KIOSKS  ARE  ALSO  INCLUDED  IN  THE  SCOPE  OF  WORKS.  THE STREET LIGHT SHALL BE OF LED LAMP FITTINGS INCLUDING LAMPS.                  (* REMARKS : FOR SUPPLY  OF ALL THE  CABLES  AS  INDICATED ARE COVERED  IN THE CABLE  ITEMS AS INDICATED ABOVE AT 31.1)

  • Schedule-2B (Sub-Station) Page 30 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    35  LOT  1

    36

    36.1 FOAM TYPE9 LTRS  NOS  436.2 DRY CHEMICAL POWDER(TROLLEY MOUNTED) 22.5 KGS  NOS  436.3 DRY POWDER TYPE  5 KGS  NOS  436.4  NOS  1036.5  NOS  1036.6  NOS  436.7 FIRE BUCKET (6 NOS IN EACH STAND) WITH STAND  SET  5

    2  TR  CAPACITY  SPLIT  AIR  CONDITIONING  UNITS  WITH  REMOTE  CONTROL  FACILITY: INCLUDING  SUPPLY  OF  AIR  CONDITIONERS,VOLTAGE  STABILISER,CONTROL  BOXES  ETC FOR  COMPLETING  THE  A.C  SCHEME.(AS  PER  SPECIFICATION  )    FOR  CONTROL  ROOM, CARRIER  ROOM  &  CONFERENCE  ROOM.(*SUPPLY  OF  CABLES  ARE  COVERED  IN  CABLE ITEMS AS INDICATED ABOVE AT31.1)

    FIRE  FIGHTING  SYSTEM(PORTABLE  AND  WHEEL  MOUNTED  SETS  FOR CONTROL  ROOM,EQUIPMENT  LIKE  TRANSFORMER  AND  OTHER  AREAS  AS PER  TECH  SPEC(REFER  TSVOLIIASCOPE  OF  WORKAT  SL  NO.  16ANNEXURE  I)

    CO2  4.5 KGS

    CO2  9 KGS

    CO2 (TROLLY MOUNTED) 22.5 KGS 

  • Schedule-2B (Sub-Station) Page 31 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    37

    37.1 220 KV SIDE

    37.1.1 FEEDER CONTROL PANEL(CPF2D)  NOS  637.1.2 TRANSFORMER CONTROL PANEL(CPL2D)  NOS  237.1.3 BUS TRANSFER CONTROL PANEL(CPT2D)  NOS  137.1.4 BUSCOUPLER CONTROL PANEL (CPB2D)  NOS  137.1.5 FEEDER RELAY PANEL(RPF2D)  NOS  637.1.6 TRANSFORMER RELAY PANEL(RPL2D)  NOS  237.1.7 BUS TRANSFER RELAY PANEL(RPT2D)  NOS  137.1.8 BUSCOUPLER RELAY PANEL (RPB2D)  NOS  137.1.9 COMMON PANEL (KP2)  NOS  1

    37.1.10 SYNCHRONOUS TROLLY  NOS  137.1.11 BUSBAR RELAY PANEL(RBB2D)  NOS  1

    PROTECTION,CONTROL  METERING,  EVENT  LOGGER,BUS  BAR  PROTN PAN,COMM PAN, RELAY TOOL KITS AS PER  TECH SPEC 

  • Schedule-2B (Sub-Station) Page 32 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    37.1.12 TIME SYNCH EQUIPMENT  NOS  137.1.13 EVENT LOGGER PANEL  NOS  1

    37.2 132 KV SIDE

    37.2.1 FEEDER CONTROL PANEL(CPF1M)  NOS  637.2.2  NOS  437.2.3 BUSCOUPLER CONTROL PANEL (CPB1M)  NOS  137.2.4 FEEDER RELAY PANEL(RPF1M)  NOS  6

    37.2.5  NOS  4

    37.2.6 BUSCOUPLER RELAY PANEL (RPB1M)  NOS  137.2.7 COMMON PANEL (KP1)  NOS  137.3 33 KV SIDE

    37.3.1 FEEDER CONTROL & RELAY PANEL(CPF/RPF0M)  NOS  4

    TRANSFORMER CONTROL PANEL(CPL1M)(2  for 132 KV Side of 220/132/33 KV Auto Tfr + 2 for 132 KV side of 132/33 KV Power Tfr)

    TRANSFORMER  RELAY  PANEL(RPL1M),  02  NOS  FOR  220/132  KV  AUTO TRANSFORMERS  ON  132  KV  SIDE  AND  02  NOS  FOR  132/33  KV  OTHER TRANSFORMERS

  • Schedule-2B (Sub-Station) Page 33 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    37.3.2 TRANSFORMER CONTROL & RELAY PANEL(CPL/RPL0M)  NOS  237.3.3 BUSCOUPLER CONTROL & RELAY PANEL (CPB/RPB0M)  NOS  1

    38 AC & DC SYSTEM

    38.1 AC SYSTEM

    38.1.1  SET  1

    38.1.2  SET  1

    38.1.3  SET  1

    38.1.4  SET  138.1.5 EMERGENCY LIGHTING DISTRIBUTION BOARD  SET  138.1.6 INDOOR RECEPTACLE BOARD  SET  138.2 DC SYSTEM

    MAIN  AC  DB,(HAVING  800  A,50KA,DRAWOUT  TYPE  ACB  WITH  3  O/C,E/F,U/V RELAYING FACILITY INDOOR TYPE AS PER SPECIFICATION.(MAIN DB1,MAIN DB2 WITH B/C)ACDB (HAVING 400A MCCB) AS PER SPECIFICATION (AC DB1,AC DB2 WITH B/C)MAIN LIGHTING DISTRIBUTION BOARD (HAVING  250A MCCB AS INCOMER)AS PER SPECIFICATION (WITH DB1,DB2 & B/C)INDOOR LIGHTING DISTRIBUTION BOARD AS PER SPECIFICATION. (WITH DB1,DB2 & B/C)

  • Schedule-2B (Sub-Station) Page 34 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    38.2.1  SET  1

    38.2.2 220 V DC EMERGENCY DISTRIBUTION BOARD  SET  139 BATTERY (350 AH PLANTE TYPE) FOR 220 V DC  SET  240  SET  241 DISTLED WATER PLANT OF 10 LTR/HR FOR BATTERY BANKS  SET  142

    WALKIE TALKIE SET 2

    43  NOS  2

    44  SET  1

    220  V  DC  BOARD  (HAVING  100A  DC  MCCB  AS  INCOMER,  E/F  (EARTH LEAKAGE), UNDER & OVER VOLTAGE   AS PER SPECIFICATION (DC DB1,DC DB2 & B/C)

    BATTERY  CHARGER  FOR  220  V,  350  AH  BATTERY  (FLOAT  AND  FLOAT  CUM BOOST)

    SET/PAIR

    PORTABLE  ALUMINIUM  LADDER  EXTENDABLE  TYPE  OF  ADEQUATE  HEIGHT TO  BE  USED  FOR  MAINTENANCE  OF  EQUIPMENT  INSIDE  SWITCH  YARD.(REFER TSVOLIIASCOPE OF WORKAT SL NO. 19)PEDESTAL MOUNTED WHEEL FITTED DERRICK FOR LIFTING/ LOWERING OF MATERIALS UP TO 1.5 TON CAPACITY.(REFER TSVOLIIASCOPE OF WORKAT SL NO. 20)

  • Schedule-2B (Sub-Station) Page 35 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    45  SET  1

    46WATER COOLER WITH WATER PURIFIER(purification system of ISI mark) SYSTEM

     NOS  1

    47  LOT  1

    48  LOT  1

    49  LOT  1

    50  LOT  1

    TOTAL OF SUBSTATION (PARTI)2B (F&I)

    POWER WINCH NEAR STORE SHED FOR HANDLING  MATERIALS UPTO 5 TON CAPACITY.

    MAINTENANCE  TESTING  EQUIPMENT    (REFER  TSVOLIIASCOPE  OF WORKAT  SL  NO.  17  ANNEXURE    II  ,INDICATED  IN  SCHEDULE  OF REQUIREMENTS OF MAINTENANCE EQUIPMENT)OTHER  TOOLS  AND  PLANTS  (T&P's)  REQUIREMENT    (REFER  TSVOLIIASCOPE OF WORKAT SL NO. 18 ANNEXURE  III ,INDICATED IN SCHEDULE OF REQUIREMENTS OTHER T&P's)OFFICE  FURNITURE    (REFER  TSVOLIIASCOPE  OF  WORKAT  SL  NO.  18 ANNEXURE    IV  ,INDICATED  IN  SCHEDULE  OF  REQUIREMENTS  OFFICE FURNITURE)  &  PLACING  IN  CONTROL  ROOM,CONFERENCE  ROOM,OFFICE ROOMS,LIBRARY,TESTING LAB,etc.

    BEST  QUALITY  &  APPROVED  MAKE    RUBBER  MAT  TO  BE  KEPT  INFRONT  & BACK  SIDE  (where  doors  of  the  panels  are  provided)  OF  ALL  PANELS,BOARDS ETC.

  • Schedule-2B (Sub-Station) Page 36 of89 Package:17/2012-13 (ATRI)

    SL NO  Unit 

    Unit 

    F&I C

    harg

    es

    Tota

    l  F&

    I Cha

    rges

    1 2 3  4 5 6= 4X5

    F&I FOR SUPPLY OF FOLLOWING EQUIPMENTS (As per Technical Specification)

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     AT

    RI [1

    0 No

    s (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 1

    1Nos

     (6Fd

    r+2A

    T+2T

    +1B/

    C) 1

    32 K

    V Ba

    ys &

     07 

    Nos 

    (4Fd

    r+2T

    +1B/

    C) 3

    3 KV

     Ba

    ys]

    Note:1 Before filling up rate/amount etc. in the schedules bidders are requested to read carefully the instruction given in VolI of Bidding Document.2 Bidders are required to fill up amount in all column except shaded portion.3

    4 Kindly enclose soft copy of the duly filled schedule in a CD with the priced copy of Bid.5

    Date   : (Signature) ……………………………………………Place : ( Name)  ………………………………………………

    ( Designation ) ……………………………………….(Common Seal) …………………………………… 

    Bidders are requested not to leave any column blank.  If any column is left blank it shall be considered that amount against those items are included in any other item and the total amount for that item shall be calculated as free of cost (Zero value). No rate shall be furnished/obtained after bid opening (Ref clause no 33.4.1 of INB volI) 

    Bidder should be quoted including service tax, no service tax shall be paid/reimbursed.

  • Schedule-2C (Sub-Station) Page 37 of 89 Package:17/2012-13 (ATRI)

    ORISSA POWER TRANSMISSION CORPORATION LIMITEDCONSTRUCTION OF  220/132/33KV SUBSTATION  ALONG WITH 220KV AND 132KV TRANSMISSION LINES AND ASSOCIATED SYSTEM AT ATRI

    BID DOCUMENT No.: SR. G.MCPCTENDERATRI PACKAGE17/201213(Equipment/Materials Price Breakup of Erection Prices against Package ATRI)

    PARTI, SCHEDULE2C (FOR SUBSTATION) TO BE QUOTED IN INR

    SL NO

    DESCRIPTION OF ITEMS

    Unit

    Erection charges

    Unit Rate Total Price

    1 2 3 4 5 6=4X5A ELECTRICAL WORKS (PART-I)

    1245 KV,1200600300/11111 A,40KA,5CORE SINGLE PHASE CURRENT TRANSFORMER

     NOS  332 245 KV,2000A,40KA,ISOLATORS

    2.1 WITH OUT EARTH SWITCH  NOS  112.2 WITH SINGLE EARTH SWITCH  NOS  112.3 TANDEM WITHOUT EARTH SWITCH  NOS  173 245 KV,4400pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER  NOS  184 245KV,3150A,40KA,SF6,CIRCUIT BREAKER WITH SUPPORTING STRUCTURE  NOS  105 216 KV, METAL OXIDE SURGE ARRESTOR,10 KA, class III  NOS  246 245 KV ,2 CORE,SINGLE PHASE,IVT  NOS  67 220 KV Bus Post Insulators  NOS  938

    145 KV,(800400200/1111),40 KA,4CORE SINGLE PHASE CURRENT TRANSFORMER NOS  33

    9 145 KV,1200A,40 KA,ISOLATORS

    9.1  NOS  149.2 D/I WITH SINGLE EARTH SWITCH  NOS  69.3 D/I WITHOUT EARTH SWITCH  NOS  410 145 KV,6600pF,3CORE,SINGLE PHASE CAPACITOR VOLTAGE TRANSFORMER  NOS  1811 120 KV METAL OXIDE SURGE  ARRESTOR, 10 KA, Class III  NOS  3012 145 KV ,2 CORE,SINGLE PHASE,IVT  NOS  3

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     ATR

    I [10

     Nos

     (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 

    11No

    s (6

    Fdr+

    2AT+

    2T+1

    B/C)

     132

     KV 

    Bays

     & 0

    7 No

    s (4

    Fdr+

    2T+1

    B/C)

     33 

    KV 

    Bays

    ]

    ERECTION,TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS ALONG WITH CIVIL WORKS (As per Technical Specification)

    S/I WITH OUT EARTH SWITCH (Includes sectional switches at the main bus near B/C )

  • Schedule-2C (Sub-Station) Page 38 of 89 Package:17/2012-13 (ATRI)

    SL NO

    DESCRIPTION OF ITEMS

    Unit

    Erection charges

    Unit Rate Total Price

    1 2 3 4 5 6=4X5

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     ATR

    I [10

     Nos

     (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 

    11No

    s (6

    Fdr+

    2AT+

    2T+1

    B/C)

     132

     KV 

    Bays

     & 0

    7 No

    s (4

    Fdr+

    2T+1

    B/C)

     33 

    KV 

    Bays

    ]

    ERECTION,TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS ALONG WITH CIVIL WORKS (As per Technical Specification)

    13 132 KV Bus Post Insulators  NOS  3014 145KV,3150A,40KA,SF6,CIRCUIT BREAKER WITH SUPPORTING STRUCTURE  NOS  1115

    36KV(800400200/111A), 25KA, 3CORE SINGLE PHASE CURRENT TRANSFORMER NOS  15

    16.1  NOS  6

    16.2  NOS  2

    16.3  NOS  2

    16.4  NOS  217 36 KV,800A,25KA,ISOLATORS

    17.1 S/I WITH OUT EARTH SWITCH  NOS  817.2 D/I WITH SINGLE EARTH SWITCH  NOS  417.3 D/I WITHOUT EARTH SWITCH  NOS  217.4 S/I WITH BEAM MOUNTED  NOS  218 30 KV, METAL OXIDE SURGE  ARRESTOR, 10KA, class II  NOS  2419 36 KV ,2 CORE,SINGLE PHASE,IVT  NOS  320 36KV,1250A,25KA,VACUUM CIRCUIT BREAKER WITH SUPPORTING STRUCTURE  NOS  721 33 KV Bus Post Insulators  NOS  1622 BUS BAR & CIRCUIT MATERIALS

    22.1  SET  48

    22.2  SET  132

    22.3  SET  30

    22.4  SET  94

    36 KV,(800400200/1111 A,(3 PS CL & 1 0.2),25KA,3CORE SINGLE PHASE CURRENT TRANSFORMERNCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(1200600300/11  A,    HAVING TWO PS CLCORE (IN EACH AUTO TRANSFORMER 1 No. NCT )NCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(800400200/11  A,    HAVING TWO PS CLCORE ( IN EACH POWER TRANSFORMER 132 KV SIDE1 NO)NCT  FOR  TRANSFORMER  PROTECTION  RATING  36  KV,(800400200/11  A,    HAVING TWO PS CLCORE (IN EACH  POWER TRANSFORMER 33 KV SIDE1 NO.)

    160  KN  ANTIFOG    INSULATOR  STRINGS  for  double  tension  twin  Moose  conductor ( TENSION)220 KV160  KN  ANTIFOG  INSULATOR  STRINGS  for  single  tension  single  Moose  conductor (TENSION)220 KV120 KN INSULATOR STRINGS for Double tension Twin Moose conductor (TENSION)132 KV120  KN  INSULATOR  STRINGS  for  single  tension  Single  Moose  conductor  (TENSION)132 KV

  • Schedule-2C (Sub-Station) Page 39 of 89 Package:17/2012-13 (ATRI)

    SL NO

    DESCRIPTION OF ITEMS

    Unit

    Erection charges

    Unit Rate Total Price

    1 2 3 4 5 6=4X5

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     ATR

    I [10

     Nos

     (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 

    11No

    s (6

    Fdr+

    2AT+

    2T+1

    B/C)

     132

     KV 

    Bays

     & 0

    7 No

    s (4

    Fdr+

    2T+1

    B/C)

     33 

    KV 

    Bays

    ]

    ERECTION,TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS ALONG WITH CIVIL WORKS (As per Technical Specification)

    22.5120 KN INSULATOR STRINGS for Double Tension Twin Moose conductor ( TENSION)33 KV

     SET  18

    22.6  SET  42

    22.7  SET  81

    22.8  SET  66

    22.9  SET  3323 ACSR MOOSE CONDUCTOR  Kms  1824  LOT  125 HARDWARES & FITTINGS/SPACERS/CLAMP  & CONNECTORS  LOT  126  LOT  127 SUBSTATION EARTHING SYSTEMS

    27.1  LOT  1

    27.2  LOT  1

    27.3  LOT  1

    27.4  LOT  1

    120 KN INSULATOR STRINGS  for Single tension Single Moose conductor (TENSION)33 KV90  KN  INSULATOR  STRINGS   for  Single  Suspension  Double/  Single  Moose  cond ( SUSPENSION)220 KV90KN  INSULATOR  STRINGS   for   Single  Suspension  Double/  Single  Moose  cond ( SUSPENSION)132 KV90  KN  INSULATOR  STRINGS   for  Single  Suspension   Double/  Single  Moose  cond (SUSPENSION)33 KV

    IPS 4" ALUMINIUM TUBES(114.2 mm OD, & 8.51mm Thickness)( Required for Equipment to equipment connection in 220 KV side only)

    EARTH WIRES & IT'S HARDWARES & FITTING, with copper earth bond

    EARTHING  CONDUCTOR  FOR  BURRIAL  :  75X10  mm  GI  Earth  Flat  for  laying  (spacing maximum 5m) (Substation earth mat): Design, engineering, supply (except the 75X10 mm GI Earth Flat, only erection)  inclusive of corrosion protection measures if any,laying of   earth mat  conductors   of   size 75X10  mm GI Flat  as per  the  approval  of   Engineer  in  charge,  excavation, welding/jointing of ground conductors along with risers (a) up to Finished level from the mat  size 75X10 mm GI Flat with back  filling  and  good  compaction,The  spacing  between  the  earth  conductor  not  more  than  5  mtrs (both way) and to be buried at depth of 700 mm from the finished ground level as per the practice and as per specification.EARTHING CONDUCTOR: 50x6 mm GI  Flat for  Raiser from the burial earth mat to equipment,structure including proper welding, bending and anti corrosive painting etc from the finished ground level to the top of the  structure  and  equipment  shall  be  with  50X6  mm  GI  Flats,    as  per  approved  drawing  and specification.EARTHING DEVICE & ASSOCIATED ACCESSORIES (50 mm heavy duty GI PERFORATED PIPE 3 mtrs long for  treated earth pit): perforated 50 mm Heavy duty GI pipes for treated earth pits (with  details  of  treatment  as  per  IS)  including,  excavation,supply  of  Bentonate  powder  and  other materials for the treated earth pit as per standard practice and as per specification.

    EARTHING DEVICE & ASSOCIATED ACCESSORIES  40mm MS rod 3 mtrs long for non treated earth pit) to be inserted directly inside the soil.

  • Schedule-2C (Sub-Station) Page 40 of 89 Package:17/2012-13 (ATRI)

    SL NO

    DESCRIPTION OF ITEMS

    Unit

    Erection charges

    Unit Rate Total Price

    1 2 3 4 5 6=4X5

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     ATR

    I [10

     Nos

     (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 

    11No

    s (6

    Fdr+

    2AT+

    2T+1

    B/C)

     132

     KV 

    Bays

     & 0

    7 No

    s (4

    Fdr+

    2T+1

    B/C)

     33 

    KV 

    Bays

    ]

    ERECTION,TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS ALONG WITH CIVIL WORKS (As per Technical Specification)

    28  LOT  1

    29SUB STATION SWITCYARD BMK,AC CONSOLE & OTHER MARSHALLING BOXES

    29.1  NOS  18

    29.2  NOS  4

    29.3  NOS  2

    29.4  NOS  529.5 CT, PT, CVT OUT DOOR CONSOLE BOXES LOT 1

    30

    30.1 DIFFERENT TYPES OF COLUMNS(LATTICE TYPE) WITH DETAILS

    30.1.1 P1S220 KV (NOMINAL UNIT WT 4.5 MT)  NOS  4930.1.2 T1S  132 KV(NOMINAL UNIT WT 1.2 MT)  NOS  2830.1.3 T4S  132KV  (NOMINAL UNIT WT 0.95 MT)  NOS  730.1.4 T8S  33KV(NOMINAL UNIT WT 0.8 MT)  NOS  830.1.5 T9S  33KV(NOMINAL UNIT WT 0.6 MT)  NOS  1130.2 DIFFERENT TYPE OF BEAMS WITH DETAILS

    30.2.1 Q1S220KV (NOMINAL UNIT WT 1.5 MT)  NOS  4430.2.2 G1   132 KV(NOMINAL UNIT WT 0.62 MT)  NOS  1930.2.3 G1X  132 KV (NOMINAL UNIT WT 1.4 MT)  NOS  430.2.4 G2   132 KV(NOMINAL UNIT WT 0.91 MT)  NOS  830.2.5 G1,2  132 KV(Each two beams of G1 type)  (NOMINAL UNIT WT 1.25 MT)  NOS  430.2.6 G6  33KV (NOMINAL UNIT WT 0.53 MT)  NOS  3

    G.I  Cable  Trays  including  support  GI  angle  suitable  for  different  sections  i.e. Section:11,22,33 & 44 along with its accessories as per TS.

    BAY MARSHALLING KIOSK (10 nos on 220 kV bay, 06 Nos 132 kv bay & 02 Nos 33 kv Bay )SWITCH YARD AC CONSOLE FOR LIGHTING (02 nos on 220 kV bay, 01 Nos 132 kv bay & 01 Nos 33 kv Bay )SWITCH YARD RECEPTACLE BOARD FOR TFR OIL FILTERATION   (01 no. near 220/132 KV Auto Tfr , 01 No. near 132/33 KV Tfr)SWITCH YARD RECEPTACLE BOARD FOR WELDING & OTHER EMERGENCY  (02 nos on 220 kV bay, 02 Nos 132 kv bay & 01 Nos 33 kv Bay )

    SWITCH YARD STRUCTURES (  INCLUDING FOUNDATION BOLTS) FOR 220/132/33 KV CLASS

  • Schedule-2C (Sub-Station) Page 41 of 89 Package:17/2012-13 (ATRI)

    SL NO

    DESCRIPTION OF ITEMS

    Unit

    Erection charges

    Unit Rate Total Price

    1 2 3 4 5 6=4X5

    Qua

    ntity

     for 2

    20/1

    32/3

    3kV 

    Subs

    tatio

    n at

     ATR

    I [10

     Nos

     (6

    Fdr+

    2AT+

    1BT+

    1B/)2

    20 K

    V Ba

    ys, 

    11No

    s (6

    Fdr+

    2AT+

    2T+1

    B/C)

     132

     KV 

    Bays

     & 0

    7 No

    s (4

    Fdr+

    2T+1

    B/C)

     33 

    KV 

    Bays

    ]

    ERECTION,TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS ALONG WITH CIVIL WORKS (As per Technical Specification)

    30.2.7 G4   33KV(NOMINAL UNIT WT 0.4 MT)  NOS  630.2.8 G4X   33KV (NOMINAL UNIT WT 0.4 MT)  NOS  430.2.9 TOTAL WEIGHT OF COLUMN & BEAM  MT  375.0030.3

    SUPPORT STRUCTURES (PIPE TYPE) FOR ALL 220KV, 132 KV & 33KV EQUIPMENTS

    30.3.1 ISOLATORS220KV  SET  3930.3.2 ISOLATORS132KV  SET  2430.3.3 ISOLATORS33 KV  SET  1630.3.4 CTS220 KV  SET  3330.3.5 CTS132 KV  SET  3330.3.6 CTS33 KV  SET  2130.3.7 CVTS220 KV  SET  1830.3.8 CVTS132 KV  SET  1830.3.9 IVTS220 KV  SET  6

    30.3.10 IVTS132 KV  SET  330.3.11 IVTS33 KV  SET  330.3.12 Surge Arrester220 Kv  SET  2430.3.13 Surge Arrester132 kV  SET  3030.3.14 Surge Arrester33 kV  SET  630.3.15 Wave Trap220 KV  SET  1230.3.16 Wave Trap132 KV  SET  1230.3.17 BPI220 KV  SET  9330.3.18 BPI132 KV  SET  3030.3.19 BPI33 KV  SET  1630.3.20 NCTS  SET  630.3.21 TOTAL WEIGHT OF SUPPORT STRUCTURE