technical dataair conditioning systemsFTKS/FTXS-C FTKS/FTXS-B Wall Mounted, Inverter Controlled Unit
Split Sky Air
Split - Sky Air
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.
Specifications are subject to change without prior notice.
Zandvoordestraat 300 B - 8400 Ostend Belgium www.daikineurope.com
EEDE04-1/3 10/2004 Prepared in Belgium by Goekint Graphics
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
TABLE OF CONTENTS FTKS/FTXS-C/B1 2 Features 2 3
.................................................................................
Specifications
.......................................................................
Nominal capacity, capacity steps and nominal input
Technical specifications
3 4 5 6
Dimensional drawings Piping diagrams Wiring diagrams Sound level
.....................................................
13 15 17 19
..................................................................
.................................................................
..........................................................................
Sound level data Sound pressure spectrum
7
Accessories
..........................................................................
24
Standard accessories Optional accessories
8 9 10
Control systems Center of gravity Installation
..................................................................
25 27 28
................................................................
............................................................................
For capacity tables, please refer to part II: outdoor units
Split - Sky Air Indoor units
1
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
1
Features+ Up to 4 indoor units can be connected to 1 Multi outdoor unit. All indoor units are individually controllable with remote control and do not need to be installed in the same room. They operate simultaneously within the same cooling or heating mode. + The outdoor unit can easily be mounted on a roof, a terrace or placed against an outside wall. + Outdoor units are fitted with a swing compressor, renowned for its low noise and energy efficiency. + The remote control has a 24 hour timer + The indoor model also has a start/stop button mounted on the front panel + Up to 5 indoor units can be operated from a single centralised control + Purpose designed holder provided for your remote control
11
+ Flat front panel: its stylish appearance fits easily within any interior dcor and is more easy to clean. + Lightweight and compact + The movement sensor saves power consumption in unoccupied rooms. + The home leave operation saves energy during absence. + Automatic horizontal and vertical auto-swing ensures uniform air flow and temperature distribution. + 3D-air flow (50,60,71 class only) + Powerful mode can be selected for rapid cooling or heating. + Air purification filter with photocatalytic deodorising function - deodorises the air - powerful decomposes cigarette and pet odours - removes house dust and pollen - deactivates bacteria and viruses + Indoor / outdoor unit silent operation Silent buttons on the remote control lower the operating sound of the indoor and/or outdoor unit by 3dB(A) each. + Night quiet mode automatically reduces the operating sound of the outdoor unit by 3dB(A) at night. multi outdoors in cooling mode only
2 3 r 0Standard Optional 5 steps
q 7 x 8 6 0 6 4MKS/MXS (cooling appl. only)
FTXS
FTKS
z ! Split - Sky Air Indoor units
2
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
1NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only: INDOOR UNITS NOMINAL INPUT Cooling nominal kW FTKS20CVMB 0.04 FTKS25CVMB 0.04 FTKS35CVMB 0.04
2
For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION
kW kW
kWh kW kW
FTKS20CVMB RKS20CVMB 1.32.03.0 0.300.500.98 4.00 A 250 RKH20CVMB 1.32.02.6 0.430.620.945 3.23 A 310
FTKS25CVMB RKS25CVMB 1.32.53.0 0.300.6950.98 3.60 A 347.5 RKH25CVMB 1.32.253.0 0.430.701.20 3.21 A 350
FTKS35CVMB RKS35CVMB 1.43.43.8 0.301.061.30 3.21 A 530 RKH35CVMB 1.43.153.8 0.461.0451.425 3.01 B 522.5 4MKS58,75,90B
kWh
2MKS40/3MKS50/4MKS58,75,90B For more information, see chapter MKS-B
TECHNICAL SPECIFICATIONSFor indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTKS20CVMB FTKS25CVMB 273 784 195 7.5 White 38 25 22 56 7.7 4.2 3.6 5 steps, silent and auto 1,340 1,090 840 Cross flow fan 18 ML fin - J7Hi - XA tube 2 x 12 x 1.4 Removable/washable/mildew proof Microcomputer control J 6.4 J 9.5 J 18.0 Both liquid and gas pipes See chapter RKS-C/RKH-C See chapter MKS-B3D044242B 3D044243B 3D044244B
FTKS35CVMB
WEIGHT COLOUR SOUND LEVEL
Unit Unit Sound pressure (cooling) (4)
FAN
Sound power (cooling) (5) Air flow rate (cooling)
high low super low high low super low steps high medium low
Speed
38 25 22 56 7.7 4.2 3.6 1,340 1,090 840 18 2 x 12 x 1.4
39 26 23 57 7.7 4.4 3.8 1,340 1,100 870 18 2 x 12 x 1.4
HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS
Type Motor output Type Rows x stages x fin pitch
INSULATION MATERIAL For outdoor units
Heat insulation tape Pair application Multi application
liquid gas drain
mm mm mm
Split - Sky Air Indoor units
3
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
12NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only: INDOOR UNITS NOMINAL INPUT Cooling nominal kW FTKS50BVMB 0.04 FTKS60BVMB 0.04 FTKS71BVMB 0.045
For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (2-3) Cooling (1) min.nom.max. NOMINAL INPUT Cooling min.nom.max. EER ENERGY LABEL Cooling ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION
kW kW
kWh
FTKS50BVMB RKS50BVMB9 0.905.005.80 0.451.662.30 3.01 B 830 4MKS58,75,90B
FTKS60BVMB RKS60BVMB9 0.906.006.70 0.452.122.45 2.83 C 1,060 4MKS75,90B For more information, see chapter MKS-B
FTKS71BVMB RKS71BVMB9 0.907.108.00 0.452.533.07 2.81 C 1,265 4MKS90B
TECHNICAL SPECIFICATIONSFor indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTKS50BVMB 290 795 238 9 44 35 32 63 11.4 8.0 7.1 1,340 1,180 1,010 40 2 x 16 x 1.4 FTKS60BVMB 290 1,050 238 12 FTKS71BVMB
WEIGHT COLOUR SOUND LEVEL
Unit Unit Sound pressure (cooling) (4)
FAN
Sound power (cooling) (5) Air flow rate (cooling)
high low super low high low super low steps high medium low
Speed
HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS
Type Motor output Type Rows x stages x fin pitch
White 45 36 33 63 16.2 11.4 10.2 5 steps, silent and auto 1,330 1,170 1,010 Cross flow fan ML fin - J8Hi - XA tube 2 x 16 x 1.4 Removable/washable/mildew proof Microcomputer control J 6.4 J 18.0 Both liquid and gas pipes See chapter RKS-B See chapter MKS-B
46 37 34 63 16.7 11.6 10.6 1,370 1,210 1,040 43 2 x 16 x 1.4
INSULATION MATERIAL For outdoor units
Heat insulation tape Pair application Multi application
liquid gas drain
mm mm mm
J 12.7
J 15.9
3D040781A 3D040782A 3D040783A
4
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
1ELECTRICAL SPECIFICATIONS
2
For indoor units only: CURRENT Nominal running current Maximum running current For combination indoor units + outdoor units:
cooling cooling
A A
FTKS20CVMB 0.18
FTKS25CVMB 0.18 See chapter RKS-C: electrical data FTKS25CVMB RKS25CVMB 3.9 See chapter RKS-C: electrical data
FTKS35CVMB 0.18
Nominal running current cooling cooling Maximum running current Starting current cooling For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling
CURRENT
A A A
FTKS20CVMB RKS20CVMB 2.8
FTKS35CVMB RKS35CVMB 4.9
A A A
FTKS20CVMB RKH20CVMB 3.3
FTKS25CVMB RKH25CVMB 3.7 See chapter RKH-C: electrical data
FTKS35CVMB RKH35CVMB 4.9
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A
FTKS20CVMB
FTKS25CVMB 2MKS40/3MKS50/4MKS58,75,90B See chapter MKS-B: electrical data
FTKS35CVMB
For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage
Hz V
FTKS20CVMB VM 1 50 230
FTKS25CVMB VM 1 50 230
FTKS35CVMB VM 1 50 2303D044242B 3D044243B 3D044244B
NOTES1 2 3 4 5 6 7 8 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)
Split - Sky Air Indoor units
5
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
12ELECTRICAL SPECIFICATIONSFor indoor units only: CURRENT Nominal running current Maximum running current For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A cooling cooling A A FTKS50BVMB 0.18 FTKS60BVMB 0.18 See chapter RKS-B: electrical data FTKS60BVMB RKS60BVMB9 9.3 See chapter RKS-B: electrical data FTKS50BVMB 4MKS58,75,90B FTKS60BVMB 4MKS75,90B See chapter MKS-B: electrical data FTKS71BVMB 4MKS90B FTKS71BVMB 0.20
FTKS50BVMB RKS50BVMB9 7.3
FTKS71BVMB RKS71BVMB9 11.1
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling cooling cooling A A A
For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage
Hz V
FTKS50BVMB VM 1 50 230
FTKS60BVMB VM 1 50 230
FTKS71BVMB VM 1 50 2303D040781A 3D040782A 3D040783A
NOTES1 2 3 4 5 6 7 8 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)
6
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
1NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only: INDOOR UNITS NOMINAL INPUT Cooling Heating nominal nominal kW kW FTXS20CVMB 0.04 0.04 FTXS25CVMB 0.04 0.04 FTXS35CVMB 0.04 0.04
2
For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION
kW kW kW kW
kWh
FTXS20CVMB RXS20CVMB 1.32.02.6 1.32.74.5 0.300.500.98 0.290.6751.46 4.00 4.00 A A 250 FTXS20CVMB RXH20CVMB 1.32.02.6 1.32.64.0 0.430.620.945 0.350.761.31 3.23 3.42 A B 310
FTXS25CVMB RXS25CVMB 1.32.53.0 1.33.44.5 0.300.6950.98 0.290.9351.46 3.60 3.64 A A 347.5 FTXS25CVMB RXH25CVMB 1.32.53.0 1.32.854.5 0.430.701.20 0.350.8351.61 3.21 3.41 A B 350 2MXS40/3MXS52/4MXS68/80B For more information, see chapter MXS-B
FTXS35CVMB RXS35CVMB 1.43.43.8 1.44.05.0 0.301.061.30 0.311.171.59 3.21 3.42 A B 530 FTXS35CVMB RXH35CVMB 1.43.153.8 1.43.65.0 0.461.0451.425 0.4051.0551.90 3.01 3.41 B B 522.5
kW kW kW kW
kWh
3D044245B 3D044246B 3D044247B
Split - Sky Air Indoor units
7
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
12NOMINAL CAPACITY and NOMINAL INPUTFor indoor units only: INDOOR UNITS NOMINAL INPUT Cooling Heating nominal nominal kW kW FTXS50BVMB 0.04 0.045 FTXS60BVMB 0.04 0.045 FTXS71BVMB 0.045 0.050
For combination indoor + outdoor units (air cooled): INDOOR UNITS OUTDOOR UNITS - PAIR APPLICATION NOMINAL CAPACITY (3-4) Cooling (1) min.nom.max. Heating (2) min.nom.max. NOMINAL INPUT Cooling min.nom.max. Heating min.nom.max. EER Cooling COP Heating ENERGY LABEL Cooling Heating ANNUAL ENERGY Cooling CONSUMPTION OUTDOOR UNITS - MULTI APPLICATION
kW kW kW kW
kWh
FTXS50BVMB RXS50BVMB 0.905.005.80 0.905.807.50 0.451.662.30 0.451.702.58 3.01 3.41 B B 830 3MXS52/ 4MXS68,80B
FTXS60BVMB RXS60BVMB 0.906.006.70 0.907.008.00 0.452.122.45 0.452.093.10 2.83 3.35 C C 1,060 4MXS68,80B For more information, see chapter MXS-B
FTXS71BVMB RXS71BVMB 0.907.108.00 0.908.509.50 0.452.533.07 0.452.633.80 2.81 3.23 C C 1,265 4MXS80B
3D040778A 3D040779 3D040780A
8
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
1TECHNICAL SPECIFICATIONSFor indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTXS20CVMB FTXS25CVMB 273 784 195 7.5 White 38/38 25/28 22/25 56/56 7.7/7.8 4.2/5.3 3.6/4.6 5 steps, silent and auto 1,340/1,300 1,090/1,130 840/960 Cross flow fan 18 ML fin - J7Hi - XA tube 2 x 12 x 1.4 Removable/washable/mildew proof Microcomputer control 6.4 9.5 18.0 Both liquid and gas pipes See chapter RXS-C/RXH-C See chapter MXS-B3D044245B 3D044246B 3D044247B
2
FTXS35CVMB
WEIGHT COLOUR SOUND LEVEL
FAN
HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS
high low super low Sound power (cooling/heating) high (6) Air flow rate high (cooling/heating) low super low Speed (cooling/heating) steps high medium low Type Motor output Type Rows x stages x fin pitch
Unit Unit Sound pressure (cooling/heating) (5)
38/38 25/28 22/25 56/56 7.7/7.8 4.2/5.3 3.6/4.6 1,340/1,300 1,090/1,130 840/960 18 2 x 12 x 1.4
39/39 26/29 23/26 57/57 7.7/8.1 4.4/5.3 3.8/4.6 1,340/1,340 1,100/1,150 870/960 18 2 x 12 x 1.4
INSULATION MATERIAL For outdoor units
Heat insulation tape Pair application Multi application
liquid gas drain
mm mm mm
Split - Sky Air Indoor units
9
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
12TECHNICAL SPECIFICATIONSFor indoor units only: INDOOR UNITS DIMENSIONS Unit H W D mm mm mm kg dB(A) dB(A) dB(A) dB(A) m3/min m3/min m3/min rpm rpm rpm W mm FTXS50BVMB 290 795 238 9 44/42 35/33 32/30 63/60 11.4/12.6 8.0/8.9 7.1/7.7 1,340/1,370 1,180/1,200 1,010/1,030 40 2 x 16 x 1.4 FTXS60BVMB 290 1,050 238 12 FTXS71BVMB
WEIGHT COLOUR SOUND LEVEL
FAN
HEAT EXCHANGER AIR FILTER TEMPERATURE CONTROL PIPING CONNECTIONS
high low super low Sound power (cooling/heating) high (6) Air flow rate high (cooling/heating) low super low Speed (cooling/heating) steps high medium low Type Motor output Type Rows x stages x fin pitch
Unit Unit Sound pressure (cooling/heating) (5)
White 45/44 36/35 33/32 63/62 16.2/17.4 11.4/12.7 10.2/11.4 5 steps, silent and auto 1,330/1,360 1,170/1,200 1,010/1,040 Cross flow fan ML fin - J8Hi - XA tube 2 x 16 x 1.4 Removable/washable/mildew proof Microcomputer control 6.4 12.7 18.0 Both liquid and gas pipes See chapter RXS-B See chapter MXS-B
46/46 37/37 34/34 63/63 16.7/18.5 11.6/13.5 10.6/12.1 1,370/1,440 1,210/1,270 1,040/1,100 43 2 x 16 x 1.4
INSULATION MATERIAL For outdoor units
Heat insulation tape Pair application Multi application
liquid gas drain
mm mm mm
15.9
3D040778A 3D040779 3D040780A
10
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
1ELECTRICAL SPECIFICATIONS
2
For indoor units only: CURRENT Nominal running current Maximum running current
cooling heating cooling heating
A A A A
FTXS20CVMB 0.18 0.18
FTXS25CVMB 0.18 0.18 See chapter RXS-C: electrical data
FTXS35CVMB 0.18 0.18
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A cooling heating cooling heating cooling heating A A A A A A
FTXS20CVMB RXS20CVMB 2.8 3.5
FTXS25CVMB RXS25CVMB 3.9 4.4 See chapter RXS-C: electrical data
FTXS35CVMB RXS35CVMB 4.9 5.4
FTXS20CVMB RXH20CVMB 3.3 4.0
FTXS25CVMB RXH25CVMB 3.7 4.4 See chapter RXH-C: electrical data
FTXS35CVMB RXH35CVMB 4.9 4.9
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A
FTXS20CVMB
FTXS25CVMB 2MXS40/3MXS52/4MXS68,80B
FTXS35CVMB
See chapter MXS-B: electrical data
For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage
Hz V
FTXS20CVMB VM 1 50 230
FTXS25CVMB VM 1 50 230
FTXS35CVMB VM 1 50 2303D044245B 3D044246B 3D044247B
NOTES1 2 3 4 5 6 7 8 9 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Nominal heating capacities are based on: indoor temperature 20CDB * outdoor temperature 7CDB/6CWB * refrigerant piping length 7.5m (horizontal) * level difference 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)
Split - Sky Air Indoor units
11
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
2
Specifications
12ELECTRICAL SPECIFICATIONSFor indoor units only: CURRENT Nominal running current Maximum running current cooling heating cooling heating A A A A FTXS50BVMB 0.18 0.20 FTXS60BVMB 0.18 0.20 See chapter RXS-B: electrical data FTXS50BVMB RXS50BVMB 7.3 7.5 FTXS60BVMB RXS60BVMB 9.3 9.2 See chapter RXS-B: electrical data FTXS71BVMB RXS71BVMB 11.1 11.6 FTXS71BVMB 0.20 0.22
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A
For combination indoor units + outdoor units: CURRENT Nominal running current Maximum running current Starting current cooling heating cooling heating cooling heating A A A A A A
FTXS50BVMB 3MXS52/ 4MXS68,80B
FTXS60BVMB 4MXS68,80B
FTXS71BVMB 4MXS80B
See chapter MXS-B: electrical data
For indoor units only: POWER SUPPLY NOMINAL DISTRIBUTION SYSTEM Phase VOLTAGE Frequency Voltage
Hz V
FTXS50BVMB VM 1 50 230
FTXS60BVMB VM 1 50 230
FTXS71BVMB VM 1 50 2303D040778A 3D040779 3D040780A
NOTES1 2 3 4 5 6 7 8 9 Nominal cooling capacities are based on: indoor temperature 27CDB/19CWB * outdoor temperature 35CDB * refrigerant piping length: 7.5m * level difference: 0m. Nominal heating capacities are based on: indoor temperature 20CDB * outdoor temperature 7CDB/6CWB * refrigerant piping length 7.5m (horizontal) * level difference 0m. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Units should be selected on nominal capacity. Maximum capacity is limited to peak periods. The sound pressure level is measured via a microphone at a certain distance from the unit. For measuring conditions: please refer to item 6 of this chapter. The sound power level is an absolute value indicating the power which a sound source generates. Energy label: scale from A (most efficient) to G (less efficient). The Energy Label Directive 2002/31/EC will enter into force once the relevant measurement standard will be published in the European Official Standard. Annual energy consumption: based on average use of 500 running hours per year at full load (= nominal conditions)
12
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
3
Dimensional drawings
1FTK/XS20-25-35CThe mark (Y) shows piping directionRear Left Right Air flow (indoor) required space (for performance and maintenance)(including installation plate)
unit (mm)
3
(space for maintenance)Home leave lamp
(space for maintenance)
Name plateSignal receiver Room temp. thermistor
Terminal block with earth terminal Gas pipe 9.5Cut (The length of pipe outside the unit: about 300) Liquid pipe J6.4 CuT (the length of pipe outside the unit: about 350) Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the outside of the unit is approx. 410)
Bottom Flaps Front grille fixing screws (Inside)
Intelligent movement sensor Timer lamp Operation lamp Indoor unit ON/OFF switch
Signal transmitter
Blade angleUp/down (automatic) Cooling, dry Heating
Infrared remote controlFTXS--: (ARC433A1) FTKS--: (ARC433A2)
Right/left (manual)
Wall hole for embedded piping J 65 hole
Standard locations of wall holes
Wall hole J 65 hole
3D044026
FTK/XS50BThe mark (Y) shows piping directionLeft Right (including installation plate)50 MIN
Air flow (indoor) required space (for performance and maintenance)
50 MIN
(space for maintenance) Name plateOperation lamp Signal receiver Indoor unit ON/OFF switch Intelligent movement sensor Room temp. thermistor Timer lamp Home leave lamp
Required space
(space for maintenance)
Terminal block with earth terminal (Inside) Gas pipe 12.7Cut (The length of pipe outside the unit: about 340) Liquid pipe J6.4 CuT (the length of pipe outside the unit: about 350) Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the outside of the unit is approx. 440)
Bottom
Front grille fixing screws (Inside) Flaps Signal transmitter
Blade anglesHorizontal blade (Automatic) Cooling
Heating (FTX -- only)
Dry
Fan only Vertical blade (Automatic) Wall hole J 65 hole
Infrared remote controlFTX---: (ARC433A21) FTK---: (ARC433A22)
Wall hole for embedded piping J 65 hole
Standard locations of wall holes
3D040071
(space for performance)
Rear
Rear
30 MIN
(space for performance)
unit (mm)
Split - Sky Air Indoor units
13
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
3
Dimensional drawings
13FTK/XS60-71BThe mark (Y) shows piping directionLeft Right (space for maintenance)50 MIN (including installation plate) 30 MIN 50 MIN
Air flow (indoor) required space (for performance and maintenance)
unit (mm)(space for performance)
Rear
Rear
Required spaceName plate Terminal block with earth terminal Gas pipe J B Cut (The length of pipe outside the unit: about 340)
(space for maintenance)
Operation lamp Signal receiver Indoor unit ON/OFF switch Room temp. thermistor
Bottom Flaps Front grille fixing screws (Inside)
Intelligent movement sensor Timer lamp Home leave lamp
FTX(K)S6071--
A 6.4
FTX(K)S60-FTX(K)S71--
B 12.7
Drain hose (connecting part I.D. J 14.0, O.D. J 18.0) (The hose length on the Liquid pipe J A Cut (The length of pipe outside of the unit is outside the unit: about 390) approx. 440)
Signal transmitter Horizontal blade (Automatic) Cooling
Blade angleHeating (FTX -- only) Dry
Fan Vertical blade (Automatic) Infrared remote control FTX---: (ARC433A2133) FTK---: (ARC433A22) Wall hole for embedded piping J 80 hole Wall hole J 80 hole
Standard locations of wall holes
3D040073A
14
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
4
Piping diagrams
1FTK/XS20-25-35CIndoor unitHeat exchanger
4
Thermistor on heat exchanger
Field piping
Cross flow fan
Fan motor Field piping
Refrigerant flow Cooling Heating 4D033698B
FTK/XS50-60BIndoor unit
Heat exchanger
Thermistor on heat exchanger Cross flow fan
Field piping
Field piping
Fan motor
Refrigerant flow Cooling Heating 4D040081
Split - Sky Air Indoor units
15
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
4
Piping diagrams
14FTK/XS71BIndoor unit
Heat exchanger
Thermistor on heat exchanger Cross flow fan
Field piping
Field piping
Fan motor
Refrigerant flow Cooling Heating 4D040082
16
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
5
Wiring diagrams
1FTK/XS20-25-35C
5
Intelligent movement sensor
(Terminal for centralised control) Transmission circuit
Outdoor
g Field wiringCAUTION
Signal receiver
Note that operation will restart automatically if the main power supply is turned off and then back on again.
RInfrared remote control
Indoor
C70 FU H1PH3P M1F M1S PCB1PCB3 R1T, R2T S1S36 S1W X1M
: Protective earth : Running capacitor : Fuse : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip
3D033599C
FTK/XS50B
g Field wiringRectifier
Outdoor
Transmission circuit
CAUTIONNote that operation will restart automatically if the main power supply is turned off and then back on again.
RFG FU H1H3 H1PH3P M1F M1S, M2S PCB1PCB5 R1T, R2T S1S38 S1W X1M
Intelligent movement sensor
Signal receiver Infrared remote control
Indoor
: Protective earth : Frame ground : Fuse : Harness : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip
3D038065A
Split - Sky Air Indoor units
17
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
5
Wiring diagrams
15FTK/XS60-71Bg Field wiringRectifier
Outdoor
Transmission circuit
CAUTIONNote that operation will restart automatically if the main power supply is turned off and then back on again.
RFG FU H1H3 H1PH3P M1F M1S, M2S PCB1PCB5 R1T, R2T S1S38 S1W X1M
Intelligent movement sensor
Signal receiver Infrared remote control
Indoor
: Protective earth : Frame ground : Fuse : Harness : Pilot lamp : Fan motor : Swing motor : Printed circuit board : Thermistor : Connector : Operation switch : Terminal strip
3D038530B
18
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
6 6-1Cooling only
Sound levelSound level dataSound pressure level
16230V, 50Hz Cooling Measuring location SL 22 22 23 32 33 34Location of microphone
Model H FTKS20C FTKS25C FTKS35C FTKS50B FTKS60B FTKS71B 38 38 39 44 45 46
Sound power level (Cooling) 56 56 57 63 63 63
6-1
L 25 25 26 35 36 37
Heat pumpSound pressure level Model H FTXS20C FTXS25C FTXS35C FTXS50B FTXS60B FTXS71B 38/38 38/38 39/39 44/42 45/44 46/46 230V, 50Hz Cooling/Heating L 25/28 25/28 26/29 35/33 36/35 37/37 SL 22/25 22/25 23/26 32/30 33/32 34/34Location of microphone
Measuring location
Sound power level (Cooling/Heating) 56/56 56/56 57/57 63/60 63/62 63/63
6-2Cooling only
Sound pressure spectrum
FTKS20-25C
FTKS35C
Octave band sound pressure level dB:(0dB = 0.0002 bar)
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
approximate threshold hearing for continuous noise
4D035255B Octave band center frequency (Hz)
4D035256B Octave band center frequency (Hz)
Split - Sky Air Indoor units
19
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
166-2
6 6-2FTKS50B
Sound levelSound pressure spectrum
FTKS60B
Octave band sound pressure level dB:(0dB = 0.0002 bar)
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise
4D040303 Octave band center frequency (Hz)
4D040304 Octave band center frequency (Hz)
FTKS71B
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise
4D040305 Octave band center frequency (Hz)
NOTE1 Operation noise differs with operation and ambient conditions.
Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)
20
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
6 6-2Heat pump
Sound levelSound pressure spectrum
16FTXS20-25C (Heating)
FTXS20-25C (Cooling)
6-2
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise
3D035240B Octave band center frequency (Hz)
3D035240B Octave band center frequency (Hz)
FTXS35C (Cooling)
FTXS35C (Heating)
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise
3D035241B Octave band center frequency (Hz)
3D035241B Octave band center frequency (Hz)
NOTE1 Operation noise differs with operation and ambient conditions.
Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)
Split - Sky Air Indoor units
21
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
166-2
6 6-2
Sound levelSound pressure spectrum
FTXS50B (Cooling)
FTXS50B (Heating)
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise
3D040299 Octave band center frequency (Hz)
3D040299 Octave band center frequency (Hz)
FTXS60B (Cooling)
FTXS60B (Heating)
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
Octave band sound pressure level dB:(0dB = 0.0002 bar)approximate threshold hearing for continuous noise
3D040300 Octave band center frequency (Hz)
3D040300 Octave band center frequency (Hz)
NOTE1 Operation noise differs with operation and ambient conditions.
Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)
22
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
6 6-2
Sound levelSound pressure spectrum
16FTXS71B (Heating)
FTXS71B (Cooling)
6-2
Octave band sound pressure level dB:(0dB = 0.0002 bar)
Octave band sound pressure level dB:(0dB = 0.0002 bar)
approximate threshold hearing for continuous noise
approximate threshold hearing for continuous noise
3D040301 Octave band center frequency (Hz)
3D040301 Octave band center frequency (Hz)
NOTE1 Operation noise differs with operation and ambient conditions.
Legend 50/60Hz 220-240/220-230V(H) 50/60Hz 220-240/220-230V(L)
Split - Sky Air Indoor units
23
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
177-1
7 7-1j Mounting plate A
AccessoriesStandard accessories1 2 1 j Remote control holder E j AAA dry-cell G batteries j Indoor unit fixing screws M4x12L H 1 2 2 j Operation manual K j Installation manual L 1 1
FTK/XS20-25-35C
j Air purification filter with photocatalytic deodorising B function j Infrared remote control D
FTK/XS50-60-71B
j Mounting plate A j Air purification filter with photocatalytic deodorising B function j Infrared remote control D
1 2 1
j Remote control holder E j AAA dry-cell G batteries j Indoor unit fixing screws M4x12L H
1 1 2
j Operation manual K j Installation manual L
2 1
7-2FTK/XS-C/B
Optional accessories20 Normal open contact Normal open pulse contact 1 up to 5 rooms (2) 25 35 KRP413A1S KRP413A1S KRC72 DCS302C51 DCS301B51 DST301B51 KRP928A2S KAF918A43 KAF918A44 KKF917A4 50 60 71
Option name Wiring adapter for time clock / remote control (1) Centralised control board Central remote control Unified ON/OFF control Schedule timer Interface adapter (3) Air purification filter with photocatalytic deodorising function (with frame) Air purification filter with photocatalytic deodorising function (without frame) Anti-theft protection for remote control
(1) Wiring adapter is also required for each indoor unit. (2) Wiring adapter supplied by Daikin. Time clock and other devices: field supply. (3) Interface adapter for room air conditioners (DIII-NET)
24
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
8 8-1
Control systemsInfrared remote control
188-1
FTK/XS20-25-35C
1 2
3 4 5 6 7
Signal transmitter: It sends signals to the indoor unit. Display: It displays the current settings. (In this illustration, each section is shown with all its displays ON for the purpose of explanation.) HOME LEAVE button: for HOME LEAVE operation POWERFUL button: for POWERFUL operation TEMPERATURE adjustment buttons: It changes the temperature setting ON/OFF button: Press this button once to start operation. Press once again to stop it. MODE selector button: It selects the operation mode (Auto , / Dry I / Cool u / Heat w / Fan B)
8 9 10 11 12 13 14 15 16
OUTDOOR UNIT SILENT button: SILENT operation FAN setting button: It selects the air flow rate setting. SWING button SENSOR button: for INTELLIGENT EYE Operation ON TIMER button OFF TIMER button TIMER setting button: It changes the time setting TIMER CANCEL button: It cancels the timer setting. CLOCK button
Split - Sky Air Indoor units
25
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
188-1
8 8-1
Control systemsInfrared remote control
FTK/XS50-60-71B
1 2
3 4 5 6 7
Signal transmitter: It sends signals to the indoor unit. Display: It displays the current settings. (In this illustration, each section is shown with all its displays ON for the purpose of explanation.) HOME LEAVE button: for HOME LEAVE operation POWERFUL button: for POWERFUL operation TEMPERATURE adjustment buttons: It changes the temperature setting ON/OFF button: Press this button once to start operation. Press once again to stop it. MODE selector button: It selects the operation mode (Auto , / Dry I / Cool u / Heat w / Fan B)
8 9 10 11 12 13 14 15 16 17
OUTDOOR UNIT SILENT button: SILENT operation FAN setting button: It selects the air flow rate setting. SENSOR button: for INTELLIGENT EYE Operation SWING button Flap (horizontal blade) SWING button Louver (Vertical blades) ON TIMER button OFF TIMER button TIMER setting button: It changes the time setting TIMER CANCEL button: It cancels the timer setting. CLOCK button
26
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
9
Center of gravity
FTK/XS20-25-35C
19
4D020686H
FTK/XS50B
4D040311
FTK/XS60-71B
4D040313
Split - Sky Air Indoor units
27
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
1010
Installation
1
FTK/XS20-25-35C
Indoor unit installation drawings
How to attach the indoor unit. Hook the claws of the bottom frame to the mounting plate. If the claws are difficult to hook, remove the front panel. How to remove the indoor unit. Push up the marked area (at the lower part of the front panel) to release the claws. If it is difficult to release, remove the front panel. Front panel
j Mounting A plate Clip
j Mounting plate A
Bottom frame Mark (rear side)
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
30mm or more from ceiling
Caulk pipe hole gap with putty.
Front grille Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipes cut line.
50 mm or more from walls (on both side) (on both side) Air filters Appearance of the indoor unit may differ from some models.
Service lid This service lid is an open/close type.
j Air purification filter with photocatalytic B deodorising function Tabs (upper 3 locations)
+ Remove the screws on the service lid. + Slide the service lid leftward. + Rotate the service lid upward.
Tabs (lower 2 locations)B Insert the upper side of the j Air purification filter with photocatalytic deodorising function into the tabs (upper 3 locations), push the lower side of the filters up a little and into the tabs (lower 2 locations).
Before screwing the remote control holder to the wall, make sure that control signals are properly received by indoor unit. j Infrared remote control D
j Remote control E holder
28
Split - Sky Air Indoor units
Wall Mounted, Inverter Controlled Unit R-410A FTK/XS20,25,35CVMB FTK/XS50,60,71BVMB
10
Installation10Indoor unit installation drawingsj Mounting plate A
1
FTK/XS50-60-71B
The mounting plate should be installed on a wall which can support the weight of the indoor unit. The figure shows a 50 class unit. (See Indoor Unit Installation 1. Installing the mounting plate for details regarding 60 and 71 class units.)Cut thermal insulation pipe to an appropriate length and wrap it with tape, making sure that no gap is left in the insulation pipes cut line.
30mm or more from ceiling Front grille
Caulk pipe hole gap with putty.
50 mm or more from walls (on both side) (on both side) Air filters Intelligent movement sensor Only for 60 and 70 class units.
Wrap the installation pipe with the finishing tape from bottom to top
Service lid Opening service lid Service lid is opening/closing type. Opening method 1) Remove the service lid screws. 2) Lift the service lid upward.
j Air purifying filter with photocatalytic B deodorizing function. 50 class Tabs (upper 3 locations)
Tabs (lower 2 locations) 60, 71 class Tabs (upper 3 locations)
Tabs (lower 3 locations)B Insert the upper side of the j Air purification filter with photocatalytic deodorising function into the tabs (upper 3 locations), push the lower side of the filters up a little and into the tabs (lower 2 locations).
Movement sensorCaution1) Do not hit or violently push the movement sensor. This can lead to damage and malfunction. 2) Do not place large objects near the sensor. Also keep heating units or humidifiers outside the sensors detection area.
Split - Sky Air Indoor units
29