EDVN041323 - FTXS-GVMV

download EDVN041323 - FTXS-GVMV

of 160

Transcript of EDVN041323 - FTXS-GVMV

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    1/160

    EDVN041323

    FTXS-G Series

    - Heat Pump -

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    2/160

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    3/160

    EDVN041323

    Split Type Air Conditioners FTXS-G Series 1

    Split Type

    Air Conditioners

    FTXS G Series

    1. Power Supply ..........................................................................................32. Functions.................................................................................................4

    3. Specifications..........................................................................................5

    4. Dimensions .............................................................................................84.1 Indoor Unit................................................................................................8

    4.2 Outdoor Unit ...........................................................................................10

    5. Wiring Diagrams....................................................................................125.1 Indoor Unit..............................................................................................12

    5.2 Outdoor Unit ...........................................................................................13

    6. Piping Diagrams....................................................................................15

    6.1 Indoor Unit..............................................................................................156.2 Outdoor Unit ...........................................................................................16

    7. Capacity Tables ....................................................................................187.1 Heat Pump .............................................................................................18

    7.2 Capacity Correction Factor by the Length of Refrigerant Piping

    (Reference) ............................................................................................23

    8. Operation Limit......................................................................................24

    9. Sound Level ..........................................................................................259.1 Measuring Location................................................................................25

    9.2 Indoor Unit..............................................................................................26

    9.3 Outdoor Unit ...........................................................................................2810.Electric Characteristics..........................................................................30

    11.Installation Manual ................................................................................3111.1 Safety Precautions .................................................................................31

    11.2 25/35 Class ............................................................................................32

    11.3 50/60 Class ............................................................................................46

    11.4 71 Class .................................................................................................60

    12.Operation Manual..................................................................................7412.1 Safety Precautions .................................................................................74

    12.2 25/35 Class ............................................................................................77

    12.3 50/60 Class ..........................................................................................101

    12.4 71 Class ...............................................................................................125

    13.Optional Accessories ..........................................................................15113.1 Option List ............................................................................................151

    13.2 Air Direction Adjustment Grille......................................152

    Heat Pump

    FTXS25GVMV

    FTXS35GVMV

    FTXS50GVMV

    FTXS60GVMV

    FTXS71GVMV

    RXS25GVMV

    RXS35GVMV

    RXS50GVMV

    RXS60GVMV

    RXS71GVMV

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    4/160

    EDVN041323

    2 Split Type Air Conditioners FTXS-G Series

    13.3 Air Direction Adjustment Grille......................................153

    13.4 Drain Plug......................................................................154

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    5/160

    EDVN041323 Power Supply

    Split Type Air Conditioners FTXS-G Series 3

    1. Power Supply

    Note: Power Supply Intake ; Outdoor Unit

    Indoor Unit Outdoor Unit Power Supply

    FTXS25GVMV RXS25GVMV

    1 , 220 ~ 240 V, 50 Hz

    1 , 220 ~ 230 V, 60 Hz

    FTXS35GVMV RXS35GVMV

    FTXS50GVMV RXS50GVMV

    FTXS60GVMV RXS60GVMV

    FTXS71GVMV RXS71GVMV

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    6/160

    Functions EDVN041323

    4 Split Type Air Conditioners FTXS-G Series

    2. Functions

    Category Functions

    FTXS25/3

    5GVMV

    RXS25/35

    GVMV

    FTXS50/6

    0/71GVMV

    RXS50/60

    /71GVMV

    Category Functions

    FTXS25/3

    5GVMV

    RXS25/35

    GVMV

    FTXS50/6

    0/71GVMV

    RXS50/60

    /71GVMV

    BasicFunction

    Inverter(with inverter power control)

    Health &Clean

    Air-purifying filter

    Operation limit for cooling (CDB)10

    ~ 4610

    ~ 46Photocatalytic deodorising filter

    Operation limit for heating (CWB)15~ 20

    15~ 18 Air-purifying filter with photocatalytic

    deodorising function (option)

    PAM control

    Standby electricity saving Titanium apatite photocatalyticair-purifying filter

    Compressor Oval scroll compressor

    Swing compressor Air filter (prefilter)

    Rotary compressor Wipe-clean flat panel

    Reluctance DC motor Washable grille

    ComfortableAirflow

    Power-airflow flap MOULD PROOF operation

    Power-airflow dual flaps Heating dry operation

    Power-airflow diffuser Good-sleep cooling operation

    Wide-angle louvres Timer 24-hour ON/OFF TIMER

    Vertical auto-swing (up and down) NIGHT SET mode

    Horizontal auto-swing (right and left) Worry FreeReliability &Durability

    Auto-restart (after power failure)

    3-D airflow Self-diagnosis (digital, LED) display

    COMFORT AIRFLOW operation Wiring error check function

    ComfortControl

    Auto fan speed Anti-corrosion treatment of outdoorheat exchanger

    Indoor unit quiet operation

    NIGHT QUIET mode (automatic) Flexibility Multi-split / split type compatible indoor

    unit

    OUTDOOR UNIT QUIET operation(manual)

    Flexible power supply correspondence

    INTELLIGENT EYE operation Chargeless 10 m 10 m

    Quick warming function Either side drain (right or left)

    Hot-start function Power selection

    Automatic defrosting RemoteControl

    5-room centralised controller (option)

    OperationAutomatic operation

    Remote control adaptor(normal open pulse contact) (option)

    Programme dry operation Remote control adaptor(normal open contact) (option)

    Fan only DIII-NET compatible

    (adaptor) (option)

    LifestyleConvenience

    New POWERFUL operation(non-Inverter)

    RemoteController

    Wireless

    Inverter POWERFUL operation Wired

    Priority-room setting

    COOL / HEAT mode lock

    HOME LEAVE operation

    ECONO operation

    Indoor unit [ON/OFF] button

    Signal receiving sign

    Temperature display

    Note: : Available

    : Not available

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    7/160

    EDVN041323 Specifications

    Split Type Air Conditioners FTXS-G Series 5

    3. Specifications50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V

    Note: The data are based on the conditions shown in the table below.

    Model

    Indoor Unit FTXS25GVMV FTXS35GVMV

    Outdoor UnitRXS25GVMV RXS35GVMV

    Cooling Heating Cooling Heating

    Capacity Rated (Min. ~ Max.)

    kW 2.5 (1.2 ~ 3.0) 3.4 (1.2 ~ 4.5) 3.5 (1.2 ~ 3.8) 4.0 (1.2 ~ 5.0)

    Btu/h 8,500 (4,100 ~ 10,200) 11,600 (4,100 ~ 15,350) 11,900 (4,100 ~ 12,950) 13,600 (4,100 ~ 17,050)

    kcal/h 2,150 (1,030 ~ 2,580) 2,920 (1,030 ~ 3,870) 3,010 (1,030 ~ 3,260) 3,440 (1,030 ~ 4,300)Moisture Removal L/h 1.2 1.9

    Running Current (Rated) A 3.5 - 3.3 - 3.2 / 3.5 - 3.3 4.3 - 4.1 - 3.9 / 4.3 - 4.1 4.9 - 4.7 - 4.5 / 4.9 - 4.7 5.1 - 4.9 - 4.7 / 5.1 - 4.9

    Power Consumption Rated(Min. ~ Max.) W 600 (300 ~ 800) 830 (290 ~ 1,340) 1,020 (300 ~ 1,200) 1,080 (290 ~ 1,550)

    Power Factor (Rated) % 77.9 - 79.1 - 78.1 /77.9 - 79.187.7 - 88.0 - 88.7 /

    87.7 - 88.094.6 - 94.4 - 94.4 /

    94.6 - 94.496.3 - 95.8 - 95.7 /

    96.3 - 95.8

    COP Rated (Min. ~ Max.) W/W 4.17 (4.00 ~ 3.75) 4.10 (4.14 ~ 3.36) 3.43 (4.00 ~ 3.17) 3.70 (4.14 ~ 3.23)

    Piping Connections

    Liquid mm 6.4 6.4

    Gas mm 9.5 9.5

    Drain mm 18.0 18.0

    Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes

    Max. Interunit Piping Length m 20 20

    Max. Interunit Height Difference m 15 15

    Chargeless m 10 10

    Amount of Additional Charge ofRefrigerant g/m 20 20

    Indoor Unit FTXS25GVMV FTXS35GVMVFront Panel Colour White White

    Airflow Rate

    H

    m/min(cfm)

    8.7 (307) 9.4 (332) 8.9 (314) 9.7 (342)

    M 6.7 (237) 7.6 (268) 6.9 (244) 7.9 (279)

    L 4.7 (166) 5.8 (205) 4.8 (169) 6.0 (212)

    SL 3.9 (138) 5.0 (177) 4.0 (141) 5.2 (184)

    Fan

    Type Cross Flow Fan Cross Flow Fan

    Motor Output W 40 40

    Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto

    Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards

    Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof

    Running Current (Rated) A 0.17 - 0.16 - 0.15 /0.17 - 0.160.17 - 0.16 - 0.15 /

    0.17 - 0.160.19 - 0.18 - 0.17 /

    0.19 - 0.180.19 - 0.18 - 0.17 /

    0.19 - 0.18

    Power Consumption (Rated) W 35 - 35 - 35 / 35 - 35 35 - 35 - 35 / 35 - 35 40 - 40 - 40 / 40 - 40 40 - 40 - 40 / 40 - 40

    Power Factor (Rated) % 93.6 - 95.1 - 97.2 /93.6 - 95.193.6 - 95.1 - 97.2 /

    93.6 - 95.195.7 - 96.6 - 98.0 /

    95.7 - 96.695.7 - 96.6 - 98.0 /

    95.7 - 96.6

    Temperature Control Microcomputer Control Microcomputer Control

    Dimensions (H W D) mm 283 800 195 283 800 195Packaged Dimensions (H W D) mm 265 855 340 265 855 340

    Weight (Mass) kg 9 9

    Gross Weight (Gross Mass) kg 12 12

    Sound Pressure Level H / M / L / SL dB(A) 37 / 31 / 25 / 22 37 / 33 / 28 / 25 38 / 32 / 26 / 23 38 / 34 / 29 / 26

    Sound Power Level H dB

    Outdoor Unit RXS25GVMV RXS35GVMV

    Casing Colour Ivory White Ivory White

    Compressor

    Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type

    Model 1YC23NXD 1YC23NXD

    Motor Output W 600 600

    Refrigerant OilType FVC50K FVC50K

    Charge L 0.375 0.375

    RefrigerantType R-410A R-410A

    Charge kg 1.0 1.0

    Airflow RateH m/min

    (cfm)33.5 (1,183) 30.2 (1,066) 33.5 (1,183) 30.2 (1,066)

    SL 23.4 (826) 28.3 (999) 23.4 (826) 28.3 (999)

    FanType Propeller Propeller

    Motor Output W 50 50

    Running Current (Rated) A 3.33 - 3.14 - 3.05 /3.33 - 3.144.13 - 3.94 - 3.75 /

    4.13 - 3.944.71 - 4.52 - 4.33 /

    4.71 - 4.524.91 - 4.72 - 4.53 /

    4.91 - 4.72

    Power Consumption (Rated) W 565 - 565 - 565 / 565 - 565 795 - 795 - 795 / 795 - 795 980 - 980 - 980 / 980 - 980 1,040 - 1,040 - 1,040 /1,040 - 1,040

    Power Factor (Rated) % 77.1 - 78.2 - 77.2 /77.1 - 78.287.5 - 87.7 - 88.3 /

    87.5 - 87.794.6 - 94.3 - 94.3 /

    94.6 - 94.396.3 - 95.8 - 95.7 /

    96.3 - 95.8

    Starting Current A 4.3 5.1

    Dimensions (H W D) mm 550 765 285 550 765 285

    Packaged Dimensions (H W D) mm 589 882 363 589 882 363

    Weight (Mass) kg 34 34

    Gross Weight (Gross Mass) kg 40 40

    Sound Pressure Level H / SL dB(A) 46 / 43 47 / 44 47 / 44 48 / 45

    Sound Power Level H dB 61 62 62 63

    Drawing No. C: 3D086402 C: 3D086398

    Conversion Formulae

    kcal/h = kW 860Btu/h = kW 3412

    cfm = m/min 35.3

    Cooling Heating Piping Length

    Indoor ; 27CDB / 19CWBOutdoor ; 35CDB / 24CWB

    Indoor ; 20CDBOutdoor ; 7CDB / 6CWB 7.5 m

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    8/160

    Specifications EDVN041323

    6 Split Type Air Conditioners FTXS-G Series

    50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V

    Note: The data are based on the conditions shown in the table below.

    Model

    Indoor Unit FTXS50GVMV FTXS60GVMV

    Outdoor UnitRXS50GVMV RXS60GVMV

    Cooling Heating Cooling Heating

    Capacity Rated (Min. ~ Max.)

    kW 5.0 (1.7 ~ 6.0) 5.8 (1.7 ~ 7.7) 6.0 (1.7 ~ 6.7) 7.0 (1.7 ~ 8.0)

    Btu/h 17,100 (5,800 ~ 20,500) 19,800 (5,800 ~ 26,300) 20,500 (5,800 ~ 22,900) 23,900 (5,800 ~ 27,300)

    kcal/h 4,300 (1,460 ~ 5,160) 4,990 (1,460 ~ 6,620) 5,160 (1,460 ~ 5,760) 6,020 (1,460 ~ 6,880)

    Moisture Removal L/h

    Running Current (Rated) A 7.2 - 6.9 - 6.6 / 7.2 - 6.9 7.4 - 7.1 - 6.8 / 7.4 - 7.19.2 - 8.8 - 8.4 /

    9.2 - 8.89.4 - 9.0 - 8.6 /

    9.4 - 9.0Power Consumption Rated(Min. ~ Max.) W 1,550 (440 ~ 2,080) 1,600 (400 ~ 2,530) 1,980 (440 ~ 2,390) 2,040 (400 ~ 2,810)

    Power Factor (Rated) % 97.9 - 97.7 - 97.9 /97.9 - 97.798.3 - 98.0 - 98.0 /

    98.3 - 98.097.8 - 97.8 - 98.2 /

    97.8 - 97.898.6 - 98.6 - 98.8 /

    98.6 - 98.6

    COP Rated (Min. ~ Max.) W/W 3.23 (3.86 ~ 2.88) 3.63 (4.25 ~ 3.04) 3.03 (3.86 ~ 2.80) 3.43 (4.25 ~ 2.85)

    Piping Connections

    Liquid mm 6.4 6.4

    Gas mm 12.7 12.7

    Drain mm 18.0 18.0

    Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes

    Max. Interunit Piping Length m 30 30

    Max. Interunit Height Difference m 20 20

    Chargeless m 10 10

    Amount of Additional Charge ofRefrigerant g/m 20 20

    Indoor Unit FTXS50GVMV FTXS60GVMV

    Front Panel Colour White White

    Airflow Rate

    Hm/min(cfm)

    14.7 (519) 16.2 (572) 16.2 (572) 17.4 (614)M 12.6 (445) 13.8 (487) 13.9 (491) 15.3 (540)

    L 10.2 (360) 11.5 (406) 11.5 (406) 12.8 (452)

    SL 9.2 (325) 10.2 (360) 10.0 (353) 10.5 (371)

    Fan

    Type Cross Flow Fan Cross Flow Fan

    Motor Output W 43 43

    Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto

    Air Direction Control Right, Left, Horizontal, Downwards Right, Left, Horizontal, Downwards

    Air Filter Removable, Washable, Mildew Proof Removable, Washable, Mildew Proof

    Running Current (Rated) A 0.16 - 0.15 - 0.15 /0.16 - 0.150.17 - 0.16 - 0.16 /

    0.17 - 0.160.19 - 0.18 - 0.17 /

    0.19 - 0.180.21 - 0.20 - 0.19 /

    0.21 - 0.20

    Power Consumption (Rated) W 34 36 40 45

    Power Factor (Rated) % 96.6 - 98.6 - 94.4 /96.6 - 98.696.3 - 97.8 - 93.8 /

    96.3 - 97.895.7 - 96.6 - 98.0 /

    95.7 - 96.697.4 - 97.8 - 98.7 /

    97.4 - 97.8

    Temperature Control Microcomputer Control Microcomputer Control

    Dimensions (H W D) mm 290 1,050 238 290 1,050 238

    Packaged Dimensions (H W D) mm 337 1,147 366 337 1,147 366

    Weight (Mass) kg 12 12Gross Weight (Gross Mass) kg 17 17

    Sound Pressure Level H / M / L / SL dB(A) 44 / 40 / 35 / 32 42 / 38 / 33 / 30 45 / 41 / 36 / 33 44 / 40 / 35 / 32

    Sound Power Level H dB 60 58 61 60

    Outdoor Unit RXS50GVMV RXS60GVMV

    Casing Colour Ivory White Ivory White

    Compressor

    Type Hermetically Sealed Swing Type Hermetically Sealed Swing Type

    Model 2YC36BXD 2YC36BXD

    Motor Output W 1,100 1,100

    Refrigerant OilType FVC50K FVC50K

    Charge L 0.65 0.65

    RefrigerantType R-410A R-410A

    Charge kg 1.5 1.5

    Airflow RateH m/min

    (cfm)48.9 (1,727) 45.0 (1,589) 50.9 (1,797) 46.3 (1,635)

    SL 41.7 (1,472) 45.0 (1,589) 45.0 (1,589) 46.3 (1,635)

    FanType Propeller Propeller

    Motor Output W 53 53

    Running Current (Rated) A 7.04 - 6.75 - 6.45 /7.04 - 6.757.23 - 6.94 - 6.64 /

    7.23 - 6.949.01 - 8.62 - 8.23 /

    9.01 - 8.629.19 - 8.80 - 8.41 /

    9.19 - 8.80

    Power Consumption (Rated) W 1,516 1,564 1,940 1,995

    Power Factor (Rated) % 97.9 - 97.6 - 97.9 /97.9 - 97.698.3 - 98.0 - 98.1 /

    98.3 - 98.097.9 - 97.9 - 98.2 /

    97.9 - 97.998.7 - 98.6 - 98.8 /

    98.7 - 98.6

    Starting Current A 7.4 9.4

    Dimensions (H W D) mm 735 825 300 735 825 300

    Packaged Dimensions (H W D) mm 792 960 390 792 960 390

    Weight (Mass) kg 48 48

    Gross Weight (Gross Mass) kg 53 53

    Sound Pressure Level H / SL dB(A) 47 / 44 48 / 45 49 / 46 49 / 46

    Sound Power Level H dB 61 62 63 63

    Drawing No. C: 3D086399 C: 3D086400

    Conversion Formulae

    kcal/h = kW 860

    Btu/h = kW 3412cfm = m/min 35.3

    Cooling Heating Piping Length

    Indoor ; 27CDB / 19CWBOutdoor ; 35CDB / 24CWB

    Indoor ; 20CDBOutdoor ; 7CDB / 6CWB 7.5 m

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    9/160

    EDVN041323 Specifications

    Split Type Air Conditioners FTXS-G Series 7

    50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V

    Note: The data are based on the conditions shown in the table below.

    Model

    Indoor Unit FTXS71GVMV

    Outdoor UnitRXS71GVMV

    Cooling Heating

    Capacity Rated (Min. ~ Max.)

    kW 7.1 (2.3 ~ 8.5) 8.2 (2.3 ~ 10.0)

    Btu/h 24,200 (7,800 ~ 29,000) 28,000 (7,900 ~ 34,100)

    kcal/h 6,110 (1,980 ~ 7,310) 7,050 (1,980 ~ 8600)

    Moisture Removal L/h

    Running Current (Rated) A 10.8 - 10.4 - 9.9 / 10.8 - 10.4 11.6 - 11.1 - 10.6 / 11.6 - 11.1Power Consumption Rated(Min. ~ Max.) W 2,360 (570 ~ 3,200) 2,520 (520 ~ 3,730)

    Power Factor (Rated) % 99.3 - 98.7 - 99.3 / 99.3 - 98.7 98.7 - 98.7 - 99.1 / 98.7 - 98.7

    COP Rated (Min. ~ Max.) W/W 3.01 (4.04 ~ 2.66) 3.25 (4.42 ~ 2.68)

    Piping Connections

    Liquid mm 6.4

    Gas mm 15.9

    Drain mm 18.0

    Heat Insulation Both Liquid and Gas Pipes

    Max. Interunit Piping Length m 30

    Max. Interunit Height Difference m 20

    Chargeless m 10

    Amount of Additional Charge ofRefrigerant g/m 20

    Indoor Unit FTXS71GVMV

    Front Panel Colour White

    Airflow Rate

    H

    m/min(cfm)

    17.4 (614) 21.5 (759)

    M 14.6 (516) 18.0 (636)L 11.9 (420) 14.4 (508)

    SL 11.2 (395) 13.3 (470)

    Fan

    Type Cross Flow Fan

    Motor Output W 43

    Speed Steps 5 Steps, Quiet, Auto

    Air Direction Control Right, Left, Horizontal, Downwards

    Air Filter Removable, Washable, Mildew Proof

    Running Current (Rated) A 0.21 - 0.20 - 0.19 / 0.21 - 0.20 0.28 - 0.27 - 0.26 / 0.28 - 0.27

    Power Consumption (Rated) W 45 60

    Power Factor (Rated) % 97.4 - 97.8 - 98.7 / 97.4 - 97.8 97.4 - 96.6 - 96.2 / 97.4 - 96.6

    Temperature Control Microcomputer Control

    Dimensions (H W D) mm 290 1,050 238

    Packaged Dimensions (H W D) mm 337 1,147 366

    Weight (Mass) kg 12

    Gross Weight (Gross Mass) kg 17

    Sound Pressure Level H / M / L / SL dB(A) 46 / 42 / 37 / 34 46 / 42 / 37 / 34

    Sound Power Level H dB 62 62Outdoor Unit RXS71GVMV

    Casing Colour Ivory White

    Compressor

    Type Hermetically Sealed Swing Type

    Model 2YC63BXD

    Motor Output W 1,920

    Refrigerant OilType FVC50K

    Charge L 0.75

    RefrigerantType R-410A

    Charge kg 2.3

    Airflow RateH m/min

    (cfm)54.5 (1,924) 52.5 (1,854)

    SL 46.0 (1,624) 52.5 (1,854)

    FanType Propeller

    Motor Output W 66

    Running Current (Rated) A 10.59 - 10.20 - 9.71 / 10.59 - 10.20 11.32 - 10.83 - 10.34 / 11.32 - 10.83

    Power Consumption (Rated) W 2,315 2,460

    Power Factor (Rated) % 99.4 - 98.7 - 99.3 / 99.4 - 98.7 98.8 - 98.8 - 99.1 / 98.8 - 98.8Starting Current A 11.6

    Dimensions (H W D) mm 770 900 320

    Packaged Dimensions (H W D) mm 900 925 390

    Weight (Mass) kg 71

    Gross Weight (Gross Mass) kg 79

    Sound Pressure Level H / SL dB(A) 52 / 49 52 / 49

    Sound Power Level H dB 66 66

    Drawing No. C: 3D086401

    Conversion Formulae

    kcal/h = kW 860Btu/h = kW 3412

    cfm = m/min 35.3

    Cooling Heating Piping LengthIndoor ; 27CDB / 19CWB

    Outdoor ; 35CDB / 24CWBIndoor ; 20CDB

    Outdoor ; 7CDB / 6CWB 7.5 m

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    10/160

    Dimensions EDVN041323

    8 Split Type Air Conditioners FTXS-G Series

    4. Dimensions

    4.1 Indoor Unit

    FTXS25/35GVMV

    FTXS50/60GVMV

    WIRELESS REMOTE CONTROLLER

    (ARC433B46)

    THE MARK () SHOWS PIPING DIRECTIONAIR FLOW

    (INDOOR

    )

    REAR

    30MIN.

    800

    RIGHTLEFT

    ( )50 MIN.50 MIN.

    197REQUIRED SPACE

    195

    SIGNAL RECEIVERNAME PLATE

    OPERATION LAMP283

    TIMER LAMP

    INTELLIGENT EYE LAMP

    INTELLIGENT EYE SENSOR

    BOTTOM INDOOR UNIT ON/OFF SWITCH

    ROOM TEMP. THERMISTOR (INSIDE)FLAPS

    SIGNAL TRANSMITTER800

    711 49 13

    17

    BLADE ANGLE1858

    UP/DOWN (AUTOMATIC)DAIKIN

    180

    COOLING, DRY .HEATING FAN283

    44.5

    163

    510

    1106044.5

    305070

    65

    STANDARD LOCATIONS OF WALL HOLESRIGHT/LEFT (MANUAL)

    45 45

    WALL HOLE FOR EMBEDDED PIPING

    65 HOLE WALL HOLE65 HOLE

    GAS PIPE 9.5 Cut(THE LENGTH OF PIPE OUTSIDE

    THE UNIT : ABOUT 390)

    LIQUID PIPE 6.4 CuT(THE LENGTH OF PIPE OUTSIDETHE UNIT : ABOUT 340)

    DRAIN HOSE(CONNECTING PART

    I.D. 14

    O.D.18THE HOSE LENGTH OF OUTSIDE

    THE UNIT IS APPROX. 440)

    (SPACE FORMAINTENANCE)

    (SPACE FORMAINTENANCE)

    (SPACEFOR

    PERFORMAN

    CE)

    INCLUDINGMOUNTING PLATE

    FRONT PANEL FIXED SCREWS(INSIDE)

    TERMINAL BLOCKWITH EARTH

    TERMINAL

    3D084049A

    THE MARK () SHOWS PIPING DIRECTION

    REARREAR1050LEFT RIGHT

    REQUIRED SPACE)(240

    238

    OPERATION LAMP

    SIGNAL RECEIVER

    290

    INTELLIGENT EYE SENSOR

    TIMER LAMP

    HOME LEAVE LAMP

    FLAPS

    18 105058BLADE ANGLES

    893.5 52.530

    HEATING DRY14.5

    163

    155.5

    10 290

    552

    151040 5

    15 3540 55

    3555

    FAN

    60VERTICAL BLADE (AUTOMATIC) 99.552

    5 STANDARD LOCATIONS OF WALL HOLES

    505 5055

    55

    SIGNAL

    TRANSMITTER

    INDOOR UNIT ON/OFFSWITCH

    ROOM TEMP. THERMISTOR(INSIDE)

    FRONT GRILLE FIXING SCREWS(INSIDE)

    HORIZONTAL BLADE(AUTOMATIC)

    COOLING

    INCLUDING

    INSTALLATION PLATE

    (SPACE FORMAINTENANCE)

    MODEL NAMEPLATE

    TERMINAL BLOCK WITH

    EARTH TERMINAL(INSIDE)

    WIRELESS REMOTE

    CONTROLLER(ARC433B70)

    AIR FLOW (INDOOR)

    (FOR PERFORMANCE AND MAINTENANCE)

    WALL HOLE FOR

    EMBEDDED PIPING

    80 HOLE

    WALL HOLE

    80 HOLE

    (SPACE FORMAINTENANCE)

    (SPACEFOR

    PERFORMANCE)

    GAS PIPE 12.7 CuT(THE LENGTH OF PIPE OUTSIDE

    THE UNIT: ABOUT 430)

    LIQUID PIPE 6.4 CuT(THE LENGTH OF PIPE OUTSIDE

    THE UNIT: ABOUT 480)

    (THE HOSE LENGTH OF

    OUTSIDE THE UNIT:ABOUT 530)

    DRAIN HOSE FOR VP13(CONNECTING PART

    I. D. 14. 0, O. D. 18. 0)

    MIN. 50MIN. 50

    MIN

    .30

    3D077945A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    11/160

    EDVN041323 Dimensions

    Split Type Air Conditioners FTXS-G Series 9

    FTXS71GVMV

    WIRELESS REMOTE

    CONTROLLER

    REAR REAR1050LEFT RIGHT

    240

    238

    OPERATION LAMP

    SIGNAL RECEIVER

    290

    INTELLIGENT EYE SENSOR

    TIMER LAMP

    HOME LEAVE LAMP

    FLAPS

    18 105058BLADE ANGLES

    893.5 52.5

    3

    0

    COOLING HEATING14.5

    163

    155.5

    10 290

    5 52

    151040 5

    15 3540 55

    3555

    FAN 60 99.5 52

    5

    505 50

    5555

    THE MARK () SHOWS PIPING DIRECTION

    (SPACE FOR

    MAINTENANCE)MIN.50

    AIR FLOW (INDOOR)

    (FOR PERFORMANCE AND MAINTENANCE)

    MIN.30

    MIN.50

    (SPACEFOR

    PERFORMANCE)

    (SPACE FORMAINTENANCE)REQUIRED SPACEINCLUDING

    INSTALLATION PLATE( )

    MODEL NAMEPLATE

    TERMINAL BLOCK WITH

    EARTH TERMINAL(INSIDE)

    GAS PIPE 15.9 CuT(THE LENGTH OF PIPE OUTSIDE

    THE UNIT: ABOUT 430)

    LIQUID PIPE 6.4 CuT(THE LENGTH OF PIPE OUTSIDE

    THE UNIT: ABOUT 480)

    (THE HOSE LENGTH OFOUTSIDE THE UNIT:

    ABOUT 530)

    WALL HOLE80 HOLE

    STANDARD LOCATIONS OF WALL HOLESWALL HOLE FOREMBEDDED PIPING

    80 HOLE

    VERTICAL BLADE (AUTOMATIC)

    DRY

    HORIZONTAL BLADE

    (AUTOMATIC)

    (ARC433B70)

    SIGNALTRANSMITTER

    FRONT GRILLE FIXING SCREWS(INSIDE)

    INDOOR UNIT ON/OFF

    SWITCH

    ROOM TEMP. THERMISTOR(INSIDE)

    DRAIN HOSE FOR VP13(CONNECTING PART

    I.D. 14.0, O.D. 18.0)

    3D077942A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    12/160

    Dimensions EDVN041323

    10 Split Type Air Conditioners FTXS-G Series

    4.2 Outdoor Unit

    RXS25/35GVMV

    RXS50/60GVMV

    MINIMUM SPACE FOR AIR PASSAGE

    150

    574 105.5

    49013

    100

    150

    50 50 50300

    311

    29.5

    50

    100

    HANDLE BRAND NAME LABEL

    6312285 7658OUTDOOR AIR THERMISTOR

    550

    165

    10

    5

    22196

    DRAIN OUTLET(I.D15.9 HOSE FOR CONNECTION)

    4-HOLES FOR ANCHOR BOLTS(M8 OR M10)

    WALL HEIGHT ON AIR OUTLET SIDE

    = LESS THAN 1200

    IN CASE OF REMOVINGSTOP VALVE COVER GAS STOP VALVE

    (9.5 CuT)

    SERVICEPORT

    WIRING

    INLET

    MANUFACTURER' S

    LABELLIQUIDSTOP VALVE(6.4 CuT)

    3D077982A

    MINIMUM SPACE FOR AIR PASSAGE

    100

    825 78

    325

    580124100

    350

    250 503

    6

    50

    350

    300

    350

    330

    100

    350

    10

    25

    NAME PLATE

    BRAND NAME LABEL WIRING INLET

    735

    64

    89

    155 18

    160 30

    SERVICE PORT

    LIQUID STOP VALVE(6.4 CuT)

    GAS STOP VALVE(12.7 CuT)

    OUTDOOR AIR TEMPERATURE

    THERMISTOR

    IN CASE OF REMOVING

    STOP VALVE COVER

    TERMINAL STRIPWITH EARTH TERMINAL

    WALL HEIGHT ON AIR OUTLET SIDE= LESS THAN 1200

    4-HOLES FOR ANCHOR BOLTS(M8 OR M10)

    DRAIN OUTLET(I.D.15.9 HOSE FOR CONNECTION)

    3D077994A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    13/160

    EDVN041323 Dimensions

    Split Type Air Conditioners FTXS-G Series 11

    RXS71GVMV

    MINIMUM SPACE FOR AIR PASSAGE

    900

    WALL HEIGHT ON AIR OUTLET SIDE = LESS THAN 1200620 140

    100

    350

    71

    102

    320350

    380

    100

    50 50(345~355)

    117

    100

    30

    30

    376 19145 350

    350

    50

    GAS STOP VALVE

    NAME PLATE

    LIQUID STOP VALVE

    770

    410

    126

    90

    50

    104 3078

    67108

    OUTDOOR AIRTHERMISTOR

    TERMINAL STRIP

    WITH EARTH TERMINAL

    INTERCONNECTING PIPINGAND WIRING INLET

    GAS PIPE(15.9 SINGLE UNION)

    LIQUID PIPE(6.4 SINGLE UNION)

    4-CUTS FOR ANCHOR BOLTS(M12)

    DRAIN OUTLETI.D.25 HOSE FOR CONNECTION.

    3D078005A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    14/160

    Wiring Diagrams EDVN041323

    12 Split Type Air Conditioners FTXS-G Series

    5. Wiring Diagrams

    5.1 Indoor Unit

    FTXS25/35GVMV

    FTXS50/60/71GVMV

    3D078575B

    3D078576B

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    15/160

    EDVN041323 Wiring Diagrams

    Split Type Air Conditioners FTXS-G Series 13

    5.2 Outdoor Unit

    RXS25/35GVMV

    RXS50/60GVMV

    3D078579B

    3D078580A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    16/160

    Wiring Diagrams EDVN041323

    14 Split Type Air Conditioners FTXS-G Series

    RXS71GVMV

    3D078581C

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    17/160

    EDVN041323 Piping Diagrams

    Split Type Air Conditioners FTXS-G Series 15

    6. Piping Diagrams

    6.1 Indoor UnitFTXS25/35GVMV FTXS50/60GVMV

    INDOOR UNIT

    MUFFLER ASSY HEAT EXCHANGER7.0 CuT

    6.4 CuT

    6.4 CuT

    6.4 CuT7.9CuT

    CROSS FLOW FAN

    MFAN MOTOR

    9.5 CuT

    REFRIGERANT FLOWCOOLINGHEATING

    FIELD PIPING

    (6.4 CuT)

    FIELD PIPING

    (9.5 CuT)

    THERMISTORON HEAT EXCH.

    4D078439A

    INDOOR UNIT

    (7.9 CuT)

    HEAT EXCHANGER

    CROSS FLOW FAN

    MFAN MOTOR

    (12.7 CuT)

    REFRIGERANT FLOW

    COOLING

    HEATING

    THERMISTORON HEAT EXCH.

    FIELD PIPING

    (6.4 CuT)

    FIELD PIPING

    (12.7 CuT)

    4D077898A

    FTXS71GVMV

    INDOOR UNIT

    (7.9 CuT)

    HEAT EXCHANGER

    CROSS FLOW FAN

    MFAN MOTOR

    (12.7 CuT)

    REFRIGERANT FLOW

    COOLING

    HEATING

    THERMISTORON HEAT EXCH.

    FIELD PIPING

    (6.4 CuT)

    FIELD PIPING

    (15.9 CuT)

    4D077941A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    18/160

    Piping Diagrams EDVN041323

    16 Split Type Air Conditioners FTXS-G Series

    6.2 Outdoor Unit

    RXS25/35GVMV

    RXS50/60GVMV

    OUTDOOR UNIT

    HEAT EXCHANGER7.0 CuT

    7.0 CuT

    9.5Cu

    T

    4.8 CuT6.4 CuT6.4 CuT

    4.8 CuT

    M

    PROPELLER FAN

    9.5 CuT9.5CuT

    6.4CuT

    7.9

    CuT

    9.5C

    uT

    MUFFLER

    9.5 CuT 9.5 CuTCOMPRESSOR

    MUFFLER7.9CuT

    ACCUMULATORREFRIGERANT FLOW

    COOLING

    HEATING

    FOUR WAY

    VALVEON:HEATING

    GAS STOPVALVE

    FIELD PIPING(9.5 CuT)

    FIELD PIPING

    (6.4 CuT)LIQUID STOPVALVE

    .4.0xID.2.0CuT

    MUFFLERWITH

    FILTER

    MUFFLERWITH

    FILTER

    MUFFLERWITH

    FILTER

    MOTOR OPERATEDVALVE

    OUTDOOR TEMPERATURETHERMISTOR

    HEAT EXCHANGERTHERMISTOR

    DISCHARGE PIPETHERMISTOR

    3D078991A

    FIELD PIPING(6.4 CuT)

    FIELD PIPING(12.7 CuT)

    OUTDOOR UNIT

    HEAT EXCHANGER7.9 CuT

    7.9 CuT

    7.9 CuT

    7.9 CuT

    7.9 CuT12.7 CuT CAPILLARY TUBE14.0 CuT7.9 CuT7.9 CuT4.0 CuT7.9 CuT7.9 CuT REFRIGERANT FLOW

    6.4 CuTCAPILLARY TUBE2 COOLING7.9 CuTCAPILLARY TUBE3

    4.0 CuT HEATING6.4

    CuT

    4.0 CuT

    CAPILLARY TUBE4

    6.4

    CuT

    M

    PROPELLER FANEV

    FILTER12.7 CuT

    6.4

    CuT

    9.5 CuT12.7 CuT

    RECEIVER7.9 CuT

    12.7CuT

    MUFFLER MUFFLER6.4 CuT7.9 CuT

    9.5

    CuT

    MUFFLER7.9 CuT

    12.7 CuT

    COMPRESSOR

    OUTDOOR TEMPERATURETHERMISTOR

    HEAT

    EXCHANGER

    THERMISTOR

    FOUR WAYVALVEON:HEATING

    DISCHARGE PIPETHERMISTOR

    MUFFLERWITH

    FILTER

    ELECTRONICEXPANSION

    VALVE

    GAS STOP VALVEWITH SERVICE PORT

    LIQUIDSTOP VALVE

    3D078127A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    19/160

    EDVN041323 Piping Diagrams

    Split Type Air Conditioners FTXS-G Series 17

    RXS71GVMV

    FIELD PIPINGGAS (15.9 CuT)

    FIELD PIPINGLIQUID (6.4 CuT)

    OUTDOOR UNIT

    HEAT EXCHANGER

    7.9 CuT7.9 CuTHEADER7.9 CuT

    7.9 CuT7.9 CuT7.9 CuT7.9 CuT

    12.7CuT

    7.9 CuTRECEIVER

    4.0 CuT

    7.9 CuT EV9.5 CuT9.5 CuT9.5 CuT 9.5 CuT9.5 CuT

    FILTERFILTERDISTRIBUTORDC FAN MOTOR M

    9.5CuT

    CAPILLARY TUBEPROPELLER FAN

    15.9 CuT15.9 CuT

    7.9 CuT9.5CuT

    7.9 CuT

    MUFFLER9.5 CuT

    15.9 CuT

    15.9CuT

    15.9

    CuT

    7.9

    CuT

    REFRIGERANT FLOW

    COMPRESSOR ACCUMULATOR ACCUMULATORCOOLINGHEATING 15.9 CuT 15.9 CuT

    OUTDOOR TEMPERATURETHERMISTOR

    HEAT EXCHANGER (CONDENSER)THERMISTOR ELECTRONIC

    EXPANSIONVALVE

    LIQUIDLINE

    STOPVALVE

    GAS LINESTOP VALVE

    4-WAYVALVEON : HEATING

    DISCHARGE PIPETHERMISTOR

    3D078128A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    20/160

    Capacity Tables EDVN041323

    18 Split Type Air Conditioners FTXS-G Series

    7. Capacity Tables

    7.1 Heat Pump

    FTXS25GVMV + RXS25GVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D086268

    AFR 8.7

    BF 0.24

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 2.56 1.93 0.46 2.44 1.87 0.50 2.33 1.82 0.55 2.28 1.79 0.57 2.21 1.76 0.59 2.10 1.70 0.64

    16.0 22 2.68 1.90 0.46 2.56 1.84 0.51 2.44 1.79 0.55 2.40 1.77 0.57 2.33 1.74 0.60 2.21 1.69 0.64

    18.0 25 2.79 1.99 0.47 2.68 1.94 0.51 2.56 1.89 0.55 2.51 1.87 0.57 2.44 1.84 0.60 2.33 1.80 0.64

    19.0 27 2.85 2.11 0.47 2.73 2.06 0.51 2.62 2.01 0.56 2.57 1.99 0.57 2.50 1.96 0.60 2.38 1.92 0.64

    22.0 30 3.02 2.03 0.47 2.91 1.99 0.52 2.79 1.95 0.56 2.74 1.93 0.58 2.67 1.91 0.60 2.56 1.86 0.65

    24.0 32 3.14 1.98 0.47 3.02 1.94 0.52 2.90 1.90 0.56 2.86 1.89 0.58 2.79 1.86 0.61 2.67 1.83 0.65

    AFR 9.4

    INDOOR OUTDOOR TEMPERATURE (CWB)

    EDB 10 5 0 6 10

    C TC PI TC PI TC PI TC PI TC PI

    15.0 2.29 0.70 2.67 0.74 3.06 0.77 3.52 0.81 3.82 0.84

    20.0 2.17 0.72 2.56 0.75 2.94 0.79 3.40 0.83 3.71 0.86

    22.0 2.12 0.73 2.51 0.76 2.89 0.80 3.35 0.84 3.66 0.86

    24.0 2.08 0.74 2.46 0.77 2.85 0.80 3.31 0.84 3.61 0.87

    25.0 2.05 0.74 2.44 0.77 2.82 0.81 3.28 0.85 3.59 0.88

    27.0 2.01 0.75 2.39 0.78 2.77 0.82 3.24 0.86 3.54 0.88

    Symbols: Notes:1. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    2. shows nominal (rated) capacities and power input.

    AFR : Airflow rate (m/min.)

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    21/160

    EDVN041323 Capacity Tables

    Split Type Air Conditioners FTXS-G Series 19

    FTXS35GVMV + RXS35GVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D086269

    AFR 8.9

    BF 0.24

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 3.31 2.33 0.78 3.31 2.33 0.86 3.26 2.31 0.93 3.19 2.27 0.96 3.10 2.22 1.01 2.93 2.13 1.08

    16.0 22 3.75 2.44 0.79 3.58 2.35 0.86 3.42 2.27 0.94 3.36 2.24 0.97 3.26 2.19 1.01 3.10 2.11 1.09

    18.0 25 3.91 2.52 0.79 3.75 2.44 0.87 3.58 2.37 0.94 3.52 2.34 0.97 3.42 2.29 1.02 3.26 2.22 1.09

    19.0 27 3.99 2.63 0.79 3.83 2.55 0.87 3.66 2.48 0.94 3.60 2.45 0.97 3.50 2.41 1.02 3.34 2.33 1.10

    22.0 30 4.23 2.53 0.80 4.07 2.46 0.88 3.90 2.39 0.95 3.84 2.37 0.98 3.74 2.33 1.03 3.58 2.26 1.10

    24.0 32 4.39 2.45 0.81 4.23 2.39 0.88 4.07 2.33 0.96 4.00 2.30 0.99 3.90 2.27 1.03 3.74 2.21 1.11

    AFR 9.7

    INDOOR OUTDOOR TEMPERATURE (CWB)

    EDB 10 5 0 6 10

    C TC PI TC PI TC PI TC PI TC PI

    15.0 2.69 0.91 3.14 0.96 3.60 1.00 4.14 1.06 4.50 1.09

    20.0 2.55 0.94 3.01 0.98 3.46 1.03 4.00 1.08 4.36 1.12

    22.0 2.50 0.95 2.95 0.99 3.40 1.04 3.94 1.09 4.31 1.13

    24.0 2.44 0.96 2.90 1.00 3.35 1.05 3.89 1.10 4.25 1.14

    25.0 2.42 0.96 2.87 1.01 3.32 1.05 3.86 1.10 4.22 1.14

    27.0 2.36 0.97 2.81 1.02 3.26 1.06 3.81 1.11 4.17 1.15

    Symbols: Notes:1. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    2. shows nominal (rated) capacities and power input.

    AFR : Airflow rate (m/min.)

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    22/160

    Capacity Tables EDVN041323

    20 Split Type Air Conditioners FTXS-G Series

    FTXS50GVMV + RXS50GVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D086271

    AFR 14.7

    BF 0.18

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 5.12 3.74 1.19 4.89 3.62 1.30 4.66 3.51 1.42 4.56 3.46 1.46 4.42 3.39 1.53 4.19 3.28 1.65

    16.0 22 5.35 3.68 1.20 5.12 3.57 1.31 4.89 3.46 1.43 4.79 3.41 1.47 4.65 3.35 1.54 4.42 3.24 1.65

    18.0 25 5.58 3.84 1.20 5.35 3.74 1.32 5.12 3.64 1.43 5.02 3.60 1.48 4.88 3.53 1.55 4.65 3.44 1.66

    19.0 27 5.70 4.04 1.21 5.47 3.94 1.32 5.23 3.84 1.44 5.14 3.81 1.48 5.00 3.75 1.55 4.77 3.65 1.66

    22.0 30 6.04 3.90 1.22 5.81 3.81 1.33 5.58 3.72 1.45 5.49 3.69 1.49 5.35 3.63 1.56 5.11 3.55 1.67

    24.0 32 6.27 3.79 1.22 6.04 3.71 1.34 5.81 3.63 1.45 5.72 3.60 1.50 5.58 3.55 1.57 5.34 3.47 1.68

    AFR 16.2

    INDOOR OUTDOOR TEMPERATURE (CWB)

    EDB 10 5 0 6 10

    C TC PI TC PI TC PI TC PI TC PI

    15.0 3.90 1.35 4.56 1.42 5.21 1.48 6.00 1.56 6.52 1.62

    20.0 3.70 1.39 4.36 1.46 5.01 1.52 5.80 1.60 6.32 1.65

    22.0 3.62 1.40 4.28 1.47 4.93 1.54 5.72 1.61 6.24 1.67

    24.0 3.54 1.42 4.20 1.48 4.85 1.55 5.64 1.63 6.16 1.68

    25.0 3.50 1.43 4.16 1.49 4.81 1.56 5.60 1.64 6.12 1.69

    27.0 3.42 1.44 4.08 1.51 4.73 1.57 5.52 1.65 6.04 1.70

    Symbols: Notes:1. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    2. shows nominal (rated) capacities and power input.

    AFR : Airflow rate (m/min.)

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    23/160

    EDVN041323 Capacity Tables

    Split Type Air Conditioners FTXS-G Series 21

    FTXS60GVMV + RXS60GVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D086272

    AFR 16.2

    BF 0.28

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 5.68 4.00 1.49 5.68 4.00 1.66 5.59 3.95 1.81 5.48 3.89 1.87 5.31 3.80 1.96 5.03 3.66 2.10

    16.0 22 6.42 4.18 1.53 6.14 4.03 1.67 5.86 3.89 1.82 5.75 3.84 1.88 5.59 3.75 1.97 5.31 3.62 2.11

    18.0 25 6.70 4.32 1.54 6.42 4.19 1.68 6.14 4.06 1.83 6.03 4.00 1.89 5.86 3.93 1.98 5.58 3.80 2.12

    19.0 27 6.84 4.51 1.54 6.56 4.38 1.69 6.28 4.25 1.83 6.17 4.20 1.89 6.00 4.12 1.98 5.72 4.00 2.13

    22.0 30 7.25 4.33 1.55 6.97 4.21 1.70 6.69 4.10 1.85 6.58 4.06 1.91 6.41 3.99 1.99 6.14 3.88 2.14

    24.0 32 7.53 4.20 1.56 7.25 4.09 1.71 6.97 3.99 1.86 6.86 3.95 1.91 6.69 3.89 2.00 6.41 3.79 2.15

    AFR 17.4

    INDOOR OUTDOOR TEMPERATURE (CWB)

    EDB 10 5 0 6 10

    C TC PI TC PI TC PI TC PI TC PI

    15.0 4.71 1.73 5.50 1.81 6.29 1.89 7.24 1.99 7.87 2.06

    20.0 4.47 1.77 5.26 1.86 6.05 1.94 7.00 2.04 7.63 2.11

    22.0 4.37 1.79 5.16 1.87 5.95 1.96 6.90 2.06 7.54 2.13

    24.0 4.28 1.81 5.07 1.89 5.86 1.98 6.81 2.08 7.44 2.14

    25.0 4.23 1.82 5.02 1.90 5.81 1.99 6.76 2.09 7.39 2.15

    27.0 4.13 1.84 4.92 1.92 5.71 2.00 6.66 2.10 7.29 2.17

    Symbols: Notes:1. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    2. shows nominal (rated) capacities and power input.

    AFR : Airflow rate (m/min.)

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    24/160

    Capacity Tables EDVN041323

    22 Split Type Air Conditioners FTXS-G Series

    FTXS71GVMV + RXS71GVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V)

    Cooling

    Heating

    3D086273

    AFR 17.4

    BF 0.27

    INDOOR OUTDOOR TEMPERATURE (CDB)

    EWB EDB 20 25 30 32 35 40

    C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

    14.0 20 6.18 4.36 1.68 6.18 4.36 1.90 6.18 4.36 2.11 6.18 4.36 2.20 6.18 4.36 2.32 5.95 4.23 2.51

    16.0 22 7.60 4.87 1.82 7.27 4.69 2.00 6.94 4.52 2.17 6.81 4.45 2.24 6.61 4.35 2.34 6.28 4.19 2.52

    18.0 25 7.93 5.02 1.83 7.60 4.85 2.01 7.27 4.69 2.18 7.13 4.63 2.25 6.94 4.53 2.35 6.61 4.38 2.53

    19.0 27 8.09 5.21 1.84 7.76 5.06 2.01 7.43 4.90 2.19 7.30 4.84 2.26 7.10 4.75 2.36 6.77 4.60 2.53

    22.0 30 8.58 5.00 1.85 8.25 4.86 2.03 7.92 4.72 2.20 7.79 4.67 2.27 7.59 4.59 2.38 7.26 4.45 2.55

    24.0 32 8.91 4.85 1.86 8.58 4.72 2.04 8.25 4.59 2.21 8.12 4.54 2.28 7.92 4.46 2.39 7.59 4.34 2.56

    AFR 21.5

    INDOOR OUTDOOR TEMPERATURE (CWB)

    EDB 10 5 0 6 10

    C TC PI TC PI TC PI TC PI TC PI

    15.0 5.52 2.13 6.45 2.23 7.37 2.34 8.48 2.46 9.22 2.55

    20.0 5.24 2.19 6.16 2.29 7.09 2.40 8.20 2.52 8.94 2.60

    22.0 5.12 2.21 6.05 2.31 6.98 2.42 8.09 2.54 8.83 2.63

    24.0 5.01 2.23 5.94 2.34 6.86 2.44 7.97 2.57 8.71 2.65

    25.0 4.95 2.24 5.88 2.35 6.81 2.45 7.92 2.58 8.66 2.66

    27.0 4.84 2.27 5.77 2.37 6.69 2.47 7.80 2.60 8.39 2.67

    Symbols: Notes:1. Capacities are based on the following conditions.

    Corresponding refrigerant piping length : 7.5 mLevel difference : 0 m

    2. shows nominal (rated) capacities and power input.

    AFR : Airflow rate (m/min.)

    BF : Bypass factor

    EWB : Entering wet bulb temp. (C)

    EDB : Entering dry bulb temp. (C)

    TC : Total capacity (kW)

    SHC : Sensible heat capacity (kW)

    PI : Power input (kW)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    25/160

    EDVN041323 Capacity Tables

    Split Type Air Conditioners FTXS-G Series 23

    7.2 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length

    of refrigerant piping the distance between the indoor unit and the outdoor unit.

    < line : cooling capacity>

    < --- line : heating capacity>

    7.2.1 25/35 Class

    7.2.2 50 Class

    7.2.3 60/71 Class

    Note: The graphs show the factor when additional refrigerant of the proper quantity is charged.

    Capacitycorrectionfactor

    1

    5 10 15 20

    0.9

    0.8

    R-410A (25/35 Class)

    Piping length (m)(R19651)

    Range of the RefrigerantAdditional Charge

    Capacitycorrectionfactor

    1

    5 10 15 20 3025

    0.9

    0.8

    R-410A (50 Class)

    Piping length (m)(R19652)

    Range of the Refrigerant Additional Charge

    Capacitycorrectionfactor

    1

    5 10 15 20 3025

    0.9

    0.8

    R-410A (60/71 Class)

    Piping length (m)(R19653)

    Range of the Refrigerant Additional Charge

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    26/160

    Operation Limit EDVN041323

    24 Split Type Air Conditioners FTXS-G Series

    8. Operation Limit

    RXS25/35GVMV

    RXS50/60/71GVMV

    O

    utdoortemp.(CDB)

    Outdoortemp.(CWB)

    HeatingCooling

    20

    15

    50

    1046

    40

    5

    30

    0

    20

    -5

    10

    -10

    283010 14 2320-15

    (-15CDB)

    10 20 30

    Continuousoperation

    C

    ontinuousoperation

    Pull-downperiod

    Indoor temp. (CWB)

    Indoor temp. (CDB)

    Notes:

    The graphs are based

    on the following conditions.Equivalent piping length 7.5mLevel difference 0mAir flow rate High 3D078142A

    Cooling Heating20

    5018

    46

    1540

    1030

    5

    20

    010

    -5

    0

    -10

    -10

    -15

    (-15CDB)20 2310 14 3028

    2010 30

    Outdoortemp.(CDB)

    Indoor temp. (CWB)

    Co

    ntinuousoperation

    Pull-downperiod

    Notes:

    The graphs are based

    on the following conditions.Equivalent piping length 7.5m

    Level difference 0m

    Air flow rate High

    Outdoortemp.(CWB)

    Continuousope

    ration

    Indoor temp. (CDB)

    3D078146A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    27/160

    EDVN041323 Sound Level

    Split Type Air Conditioners FTXS-G Series 25

    9. Sound Level

    9.1 Measuring Location

    Notes: 1. Operation sound is measured in an anechoic chamber.

    2. The data are based on the conditions shown in the table below.

    Indoor Unit Outdoor Unit

    Cooling Heating Piping Length

    Indoor ; 27CDB / 19CWBOutdoor ; 35CDB / 24CWB Indoor ; 20CDBOutdoor ; 7CDB / 6CWB 5 m

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    28/160

    Sound Level EDVN041323

    26 Split Type Air Conditioners FTXS-G Series

    9.2 Indoor Unit

    FTXS25GVMV

    FTXS35GVMV

    FTXS50GVMV

    COOLING HEATING70 70

    NC-70OVER ALL (dB)

    NC-70

    NC-60 NC-60

    60 60SCALE

    A 37

    NC-50 NC-50

    50 50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    NC-40 NC-40

    4040

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    NC-30

    STANDARD EXTERNAL STATIC PRESSURE

    NC-30

    30 30

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    NC-20NC-20

    Cooling

    20 20

    500 500250 250125125 631000 10002000 20004000 8000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    63

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    50/60Hz

    220-240/220-230v(H)

    50/60Hz

    220-240/220-230v(L)

    25

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OVER ALL (dB)

    SCALE

    A 37

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Heating

    50/60Hz

    220-240/220-230v(H)

    50/60Hz

    220-240/220-230v(L)

    28

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    3D077896A

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE50025012563 1000 2000 80004000

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    OVER ALL (dB)

    SCALE

    A 38

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Cooling

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    26

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    OVER ALL (dB)

    SCALE

    A 38

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v50/60Hz

    JIS STANDARD

    STANDARD EXTERNAL STATIC PRESSURE

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Heating

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    29

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    70

    60

    50

    40

    30

    20

    70

    60

    50

    40

    30

    20

    COOLING HEATING

    OCTAVE BAND CENTER FREQUENCY (Hz)

    500250125 1000 2000 4000 800063 3D077897A

    COOLING HEATING70 70

    NC-70 NC-70OVER ALL (dB)

    NC-60 NC-60

    60 60SCALE

    NC-50 NC-50

    A 44 35

    50 50

    (B.G.N IS ALREADY RECTIFIED)

    NC-40 NC-40

    OPERATING CONDITIONS

    4040

    NC-30NC-30

    3030

    NC-20NC-20

    OCTAVEBAND

    SOUNDPRESSURELEVEL

    dB

    (0dB=0.0002

    bar)

    OCTAVEBAND

    SOUNDPRESSURELEVEL

    dB

    (0dB=0.0002

    bar)

    OVER ALL (dB)

    SCALE

    A 42 33

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    20 20

    500 500250250125 12563 63 10001000 2000 2000 4000 800080004000

    OCTAVE BAND CENTER FREQUENCY (Hz)OCTAVE BAND CENTER FREQUENCY (Hz)

    POWER SOURCE 220-240/220-230V 50/60Hz

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Heating

    50/60Hz

    220-240/220-230v(H)

    50/60Hz

    220-240/220-230v

    (L)

    50/60Hz

    220-240/220-230v

    (H)

    50/60Hz

    220-240/220-230v

    (L)

    POWER SOURCE 220-240/220-230V 50/60Hz

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Cooling

    JIS STANDARD JIS STANDARD

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    APPROXIMATETHRESHOLD HEARINGFOR CONTINUOUSNOISE

    3D077900A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    29/160

    EDVN041323 Sound Level

    Split Type Air Conditioners FTXS-G Series 27

    FTXS60GVMV

    FTXS71GVMV

    COOLING70

    NC-70

    NC-60

    60

    NC-50

    50

    NC-40

    40

    NC-30

    30

    NC-20

    20

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    63

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    70OVER ALL (dB)

    60SCALE

    A 45

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    40

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    30

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Cooling

    20

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    36

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    HEATING

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    50025012563 1000 2000 80004000

    OVER ALL (dB)

    SCALE

    A 44

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Heating

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    35

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    3D077939A

    OVER ALL (dB)

    SCALE

    A 46

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Heating

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    37

    70

    NC-70

    NC-60

    60

    NC-50

    50

    NC-40

    40

    NC-30

    30

    NC-20

    20

    8000

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    50025012563 1000 2000 4000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    HEATINGOVER ALL (dB)

    SCALE

    A 46

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    JIS STANDARD JIS STANDARD

    POWER SOURCE 220-240/220-230v 50/60Hz

    50/60Hz 220-240/220-230v (H)

    50/60Hz 220-240/220-230v (L)

    Cooling

    50/60Hz220-240/220-230v

    (H)

    50/60Hz220-240/220-230v

    (L)

    37

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    63

    COOLING70

    60

    50

    40

    30

    20OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    3D077904A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    30/160

    Sound Level EDVN041323

    28 Split Type Air Conditioners FTXS-G Series

    9.3 Outdoor Unit

    RXS25GVMV

    RXS35GVMV

    RXS50GVMV

    OVER ALL (dB)

    SCALE

    A

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    50/60Hz 220-240/220-230v

    Heating

    50/60Hz220-240/220-230v

    47

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    COOLING70

    60

    50

    40

    30

    20

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    63

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    70OVER ALL (dB)

    60SCALE

    A

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    40

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    30

    50/60Hz 220-240/220-230v

    Cooling

    20

    50/60Hz220-240/220-230v

    46

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    HEATING

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    50025012563 1000 2000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    3D078008A

    OVER ALL (dB)

    SCALE

    A

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    50/60Hz 220-240/220-230v

    Heating

    50/60Hz220-240/220-230v

    48

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    COOLING70

    60

    50

    40

    30

    20

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    63

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    70OVER ALL (dB)

    60SCALE

    A

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    40

    POWER SOURCE 220-240/220-230v 50/60Hz

    JIS STANDARD

    30

    50/60Hz 220-240/220-230v

    Cooling

    20

    50/60Hz220-240/220-230v

    47

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    HEATING

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    50025012563 1000 2000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE3D078009A

    OVER ALL (dB)

    SCALE

    A

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    50/60Hz 220-240/220-230v

    Heating

    50/60Hz220-240/220-230v

    48

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    COOLING70

    60

    50

    40

    30

    20

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    OCTAVEBAND

    SOUNDPRESSURELEVEL

    dB(

    0dB=0.0002

    bar)

    63

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    70OVER ALL (dB)

    60SCALE

    A

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    JIS STANDARD JIS STANDARD40

    POWER SOURCE 220-240/220-230v 50/60Hz

    30

    50/60Hz 220-240/220-230v

    Cooling

    20

    50/60Hz220-240/220-230v

    47

    OCTAVEBAND

    SOUNDPRESSURELEVEL

    dB(

    0dB=0.0002

    bar)

    HEATING

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    50025012563 1000 2000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    3D078015A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    31/160

    EDVN041323 Sound Level

    Split Type Air Conditioners FTXS-G Series 29

    RXS60GVMV

    RXS71GVMV

    COOLING70

    60

    50

    40

    30

    20OCTAVEBANDSOUNDPRE

    SSURELEVEL

    dB(0dB=0.0002

    bar)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    63

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    70OVER ALL (dB)

    60SCALE

    A

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    JIS STANDARD JIS STANDARD40

    POWER SOURCE 220-240/220-230v 50/60Hz

    30

    50/60Hz 220-240/220-230v

    Cooling

    20

    50/60Hz220-240/220-230v

    49

    OCTAVEBANDSOUNDPRE

    SSURELEVEL

    dB(0dB=0.0002

    bar)

    HEATING

    50025012563 1000 2000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    OVER ALL (dB)

    SCALE

    A

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    50/60Hz 220-240/220-230v

    Heating

    50/60Hz220-240/220-230v

    49

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    3D078016A

    70OVER ALL (dB)

    60SCALE

    A

    50(B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    40

    POWER SOURCE 220-240/220-230v 50/60Hz

    30Cooling

    20

    50/60Hz220-240/220-230v

    52

    OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    70

    60

    50

    40

    30

    20OCTAVEBANDSOUNDPRESSURELEVEL

    dB(0dB=0.0002

    bar)

    COOLING

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    500250125 1000 2000 4000 8000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    63

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    HEATING

    50025012563 1000 2000 80004000

    OCTAVE BAND CENTER FREQUENCY (Hz)

    APPROXIMATE

    THRESHOLD HEARING

    FOR CONTINUOUS

    NOISE

    NC-70

    NC-60

    NC-50

    NC-40

    NC-30

    NC-20

    OVER ALL (dB)

    SCALE

    A

    (B.G.N IS ALREADY RECTIFIED)

    OPERATING CONDITIONS

    POWER SOURCE 220-240/220-230v 50/60Hz

    Heating

    50/60Hz220-240/220-230v

    52

    JIS STANDARDJIS STANDARD

    3D078017A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    32/160

    Electric Characteristics EDVN041323

    30 Split Type Air Conditioners FTXS-G Series

    10.Electric Characteristics

    3D0860713D086072

    3D086073

    3D086074

    Indoor Unit Outdoor UnitPower Supply Compressor OFM IFM

    Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA

    FTXS25GVMV RXS25GVMV

    50 - 220Max. 50 Hz, 264 VMin. 50 Hz, 198 V

    9.75 10 48.5

    3.5

    50 0.22 40 0.1450 - 230 3.350 - 240 3.2

    60 - 220 Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    3.5

    60 - 230 3.3

    FTXS35GVMV RXS35GVMV

    50 - 220Max. 50 Hz, 264 VMin. 50 Hz, 198 V

    9.75 10 75

    4.4

    50 0.22 40 0.14

    50 - 230 4.2

    50 - 240 4.0

    60 - 220 Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    4.4

    60 - 230 4.2

    FTXS50GVMV RXS50GVMV

    50 - 220Max. 50 Hz, 264 VMin. 50 Hz, 198 V

    19.75 20 67

    6.7

    53 0.32 43 0.17

    50 - 230 6.4

    50 - 240 6.1

    60 - 220 Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    6.760 - 230 6.4

    FTXS60GVMV RXS60GVMV

    50 - 220Max. 50 Hz, 264 VMin. 50 Hz, 198 V

    19.75 20 84

    8.7

    53 0.39 43 0.18

    50 - 230 8.3

    50 - 240 7.9

    60 - 220 Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    8.7

    60 - 230 8.3

    FTXS71GVMV RXS71GVMV

    50 - 220Max. 50 Hz, 264 VMin. 50 Hz, 198 V

    19.75 20 56

    10.3

    66 0.40 43 0.19

    50 - 230 9.9

    50 - 240 9.4

    60 - 220 Max. 60 Hz, 253 VMin. 60 Hz, 198 V

    10.3

    60 - 230 9.9

    Symbols: Notes:

    MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.Indoor temp. 27CDB / 19CWBOutdoor temp. 35CDB.

    2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. Be sure to install an earth leak detector. (One that can handle

    higher harmonics.)(This unit uses an inverter, which means that an earth leakdetector capable handling high harmonics must be used in orderto prevent malfunctioning of the earth leak detector.)

    MFA : Max. fuse amps (A)

    RHz : Rated operating frequency (Hz)

    RLA : Rated load amps (A)

    OFM : Outdoor fan motor

    IFM : Indoor fan motor

    W : Fan motor rated output (W)

    FLA : Full load amps (A)

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    33/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 31

    11.Installation Manual

    11.1 Safety Precautions

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    34/160

    Installation Manual EDVN041323

    32 Split Type Air Conditioners FTXS-G Series

    11.2 25/35 Class

    11.2.1 Indoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    35/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 33

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    36/160

    Installation Manual EDVN041323

    34 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    37/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 35

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    38/160

    Installation Manual EDVN041323

    36 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    39/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 37

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    40/160

    Installation Manual EDVN041323

    38 Split Type Air Conditioners FTXS-G Series

    3PN14832-8E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    41/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 39

    11.2.2 Outdoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    42/160

    Installation Manual EDVN041323

    40 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    43/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 41

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    44/160

    Installation Manual EDVN041323

    42 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    45/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 43

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    46/160

    Installation Manual EDVN041323

    44 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    47/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 45

    3PN14832-9E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    48/160

    Installation Manual EDVN041323

    46 Split Type Air Conditioners FTXS-G Series

    11.3 50/60 Class

    11.3.1 Indoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    49/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 47

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    50/160

    Installation Manual EDVN041323

    48 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    51/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 49

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    52/160

    Installation Manual EDVN041323

    50 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    53/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 51

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    54/160

    Installation Manual EDVN041323

    52 Split Type Air Conditioners FTXS-G Series

    3PN14832-10E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    55/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 53

    11.3.2 Outdoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    56/160

    Installation Manual EDVN041323

    54 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    57/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 55

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    58/160

    Installation Manual EDVN041323

    56 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    59/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 57

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    60/160

    Installation Manual EDVN041323

    58 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    61/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 59

    3PN14832-11E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    62/160

    Installation Manual EDVN041323

    60 Split Type Air Conditioners FTXS-G Series

    11.4 71 Class

    11.4.1 Indoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    63/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 61

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    64/160

    Installation Manual EDVN041323

    62 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    65/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 63

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    66/160

    Installation Manual EDVN041323

    64 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    67/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 65

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    68/160

    Installation Manual EDVN041323

    66 Split Type Air Conditioners FTXS-G Series

    3PN14832-12E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    69/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 67

    11.4.2 Outdoor Unit

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    70/160

    Installation Manual EDVN041323

    68 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    71/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 69

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    72/160

    Installation Manual EDVN041323

    70 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    73/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 71

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    74/160

    Installation Manual EDVN041323

    72 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    75/160

    EDVN041323 Installation Manual

    Split Type Air Conditioners FTXS-G Series 73

    3PN14832-13E

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    76/160

    Operation Manual EDVN041323

    74 Split Type Air Conditioners FTXS-G Series

    12.Operation Manual

    12.1 Safety Precautions

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    77/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 75

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    78/160

    Operation Manual EDVN041323

    76 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    79/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 77

    12.2 25/35 Class

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    80/160

    Operation Manual EDVN041323

    78 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    81/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 79

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    82/160

    Operation Manual EDVN041323

    80 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    83/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 81

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    84/160

    Operation Manual EDVN041323

    82 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    85/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 83

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    86/160

    Operation Manual EDVN041323

    84 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    87/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 85

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    88/160

    Operation Manual EDVN041323

    86 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    89/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 87

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    90/160

    Operation Manual EDVN041323

    88 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    91/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 89

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    92/160

    Operation Manual EDVN041323

    90 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    93/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 91

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    94/160

    Operation Manual EDVN041323

    92 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    95/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 93

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    96/160

    Operation Manual EDVN041323

    94 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    97/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 95

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    98/160

    Operation Manual EDVN041323

    96 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    99/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 97

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    100/160

    Operation Manual EDVN041323

    98 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    101/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 99

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    102/160

    Operation Manual EDVN041323

    100 Split Type Air Conditioners FTXS-G Series

    3PN14831-3G

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    103/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 101

    12.3 50/60 Class

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    104/160

    Operation Manual EDVN041323

    102 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    105/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 103

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    106/160

    Operation Manual EDVN041323

    104 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    107/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 105

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    108/160

    Operation Manual EDVN041323

    106 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    109/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 107

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    110/160

    Operation Manual EDVN041323

    108 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    111/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 109

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    112/160

    Operation Manual EDVN041323

    110 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    113/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 111

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    114/160

    Operation Manual EDVN041323

    112 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    115/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 113

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    116/160

    Operation Manual EDVN041323

    114 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    117/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 115

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    118/160

    Operation Manual EDVN041323

    116 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    119/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 117

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    120/160

    Operation Manual EDVN041323

    118 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    121/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 119

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    122/160

    Operation Manual EDVN041323

    120 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    123/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 121

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    124/160

    Operation Manual EDVN041323

    122 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    125/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 123

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    126/160

    Operation Manual EDVN041323

    124 Split Type Air Conditioners FTXS-G Series

    3PN14831-4G

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    127/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 125

    12.4 71 Class

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    128/160

    Operation Manual EDVN041323

    126 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    129/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 127

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    130/160

    Operation Manual EDVN041323

    128 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    131/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 129

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    132/160

    Operation Manual EDVN041323

    130 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    133/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 131

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    134/160

    Operation Manual EDVN041323

    132 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    135/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 133

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    136/160

    Operation Manual EDVN041323

    134 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    137/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 135

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    138/160

    Operation Manual EDVN041323

    136 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    139/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 137

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    140/160

    Operation Manual EDVN041323

    138 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    141/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 139

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    142/160

    Operation Manual EDVN041323

    140 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    143/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 141

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    144/160

    Operation Manual EDVN041323

    142 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    145/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 143

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    146/160

    Operation Manual EDVN041323

    144 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    147/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 145

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    148/160

    Operation Manual EDVN041323

    146 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    149/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 147

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    150/160

    Operation Manual EDVN041323

    148 Split Type Air Conditioners FTXS-G Series

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    151/160

    EDVN041323 Operation Manual

    Split Type Air Conditioners FTXS-G Series 149

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    152/160

    Operation Manual EDVN041323

    150 Split Type Air Conditioners FTXS-G Series

    3PN14831-5G

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    153/160

    EDVN041323 Optional Accessories

    Split Type Air Conditioners FTXS-G Series 151

    13.Optional Accessories

    13.1 Option List

    13.1.1 Indoor Unit

    Note: Standard accessory

    13.1.2 Outdoor Unit

    Option Name 25/35 Class 50/60/71 Class

    1 Air-Purifying Filter with Photocatalytic Deodorising Function(without Frame)

    KAF970A46 KAF971B42

    2 Remote Controller Loss Prevention with Chain KKF917A4

    Option Name 25/35 Class 50/60 Class 71 Class

    1 Air Direction Adjustment Grille KPW937A4 KPW945A4

    2 Drain Plug KKP937A4 KKP945A4

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    154/160

    Optional Accessories EDVN041323

    152 Split Type Air Conditioners FTXS-G Series

    13.2 Air Direction Adjustment Grille

    b)

    Checking the parts

    Installation of Louver

    CAUTION

    Louver

    1piece1piece

    Shape

    Quantity

    Selection of Installation Location

    Check the following parts

    a)

    Before Installation

    Installation Procedure

    Use when installing in a location that meets the following conditions.When installing near the border to a neighbor's house

    If exhaust blows directly on passers-by because outdoor unit is installed facing a road.Changing the fan direction of the outdoor unit to prevent it blowing directly on shrubbery, etc.

    Installation is possible in the four directions:upward, downward, rightward, and leftward.The installation screws are attached to the louver.First temporarily attach the louver with 4 screws,

    then check that the angle is correct, and finallytighten the screws fully.

    1.Install so that a short circuit is prevented.2.For the use in snowy regions, avoid installation

    with the air outlet facing upward. Install so thatthe air outlet faces leftward, rightward, or down-ward.Snow accumulates in the air outlet of the outdoorunit, causing malfunction of the main body of theoutdoor unit.

    3.Be advised that if the fan direction is up,dead leaves and other foreign mattereasily accumulates in the exhaust vent.

    Name

    With 4 screws

    Installation manual

    Prepared holepitch 435mmFan partition

    Prepared holepitch 435mmFan partition

    Part A(see figure below)

    The prepared hole is in between the gratingof the grille. Part A (prepared hole) crosssection (the shape of either a or b)

    Grille grating

    Prepared hole Prepared hole

    Grille grating

    4P104499-1A

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    155/160

    EDVN041323 Optional Accessories

    Split Type Air Conditioners FTXS-G Series 153

    13.3 Air Direction Adjustment Grille

    Check the following parts

    Installation Procedure

    Before installation

    Name

    Quantity

    Louver

    1piece

    Truss tapping screw

    M44screws(max.7.5kW class)M54screws(8.0/9.0kW class)

    Installation manual

    1piece

    Shape

    Selection of Installation Location

    Installation of Louvers

    Space Needed for Installation

    Use when installing in a location that meets the following conditions.

    When installing near the border to a neighbor's house

    If exhaust blows directly on passers-by because outdoor unit is instal-

    led facing a road.

    If exhaust blows directly on vegetation

    A minimum of 100mm is neededbetween the back of the outdoorunit and any obstructions(walls, etc.)

    more

    than1

    00

    Attach the louvers overlapping the standard grille.

    Installing the louvers without the grille would allow hands to enter the fan area,

    which is dangerous, so be sure to install the standard grille.

    Caution

    When pointing up When pointing down

    (1) Remove the 4 attachment screws fromthe standard grille.

    Remove the 4 attachment screws fromthe standard grille.

    (2) Install the louver pointed up.

    Overlap the standard grille andscrew both in together.

    The attachment screwsare in the louvers.

    Install the louver pointed down.

    Overlap the standard grille andscrew both in together.

    The attachment screwsare in the louvers.

    (3)

    (1)

    (2)

    (3)Installation complete Installation complete

    3P089958-2C

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    156/160

    Optional Accessories EDVN041323

    154 Split Type Air Conditioners FTXS-G Series

    13.4 Drain Plug

    3P089958-1B

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    157/160

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    158/160

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    159/160

  • 7/26/2019 EDVN041323 - FTXS-GVMV

    160/160

    1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

    Cautions on product corrosion

    Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.

    Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or

    contractor to install those parts and accessories. Use of unauthorised parts and accessories or

    improper installation of parts and accessories can result in water or refrigerant leakage, electrical

    shock, fire or explosion.

    Read the User's Manual carefully before using this product. The User's Manual provides important

    safety instructions and warnings. Be sure to follow these instructions and warnings.

    If you have any enquiries, please contact your local importer, distributor and/or retailer.