Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation...

93
Advanced Thermal Response Testing and Its Relevance to Complex UTES Arrays Göran Hellström NeoEnergy Sweden Ltd

Transcript of Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation...

Page 1: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Advanced Thermal Response Testing and Its Relevance to Complex UTES Arrays

Göran HellströmNeoEnergy Sweden Ltd

Page 2: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Energy load

Borehole heat exchanger

Ground

Borehole heat exchanger

Page 3: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

CLOSED LOOPBOREHOLE HEAT EXCHANGERS

Page 4: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Closed Loop Vertical BHE Insertion

4

Page 5: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Single U-pipe BHE

Page 6: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Multipipe coaxial type

Page 7: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

U-tube Coaxial

Basic types of borehole heat exchangers

Page 8: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-3 0

+2,5

Undisturbed ground

+8,5

Heat extraction rate

40 W/m

Borehole wall

Ground-source heat pump operating conditions

Typical operating conditions in central Sweden

Page 9: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-3 0

+2,5

Undisturbed ground

+8,5

Borehole wall

Ground-source heat pump operating conditions

40 % of temperature difference between heat carrier fluid and surrounding ground within the borehole

Page 10: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-3 0

+2,5

Undisturbed ground

+8,5

Borehole wall

Ground-source heat pump operating conditions

40 % of temperature difference between heat carrier fluid and surrounding ground within the borehole

TRT used to measure performance of borehole heat exchangers

Page 11: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-3 0

+2,5

Undisturbed ground

+8,5

Borehole wall

Ground-source heat pump operating conditions

40 % of temperature difference between heat carrier fluid and surrounding ground within the borehole

TRT used to measure performance of borehole heat exchangers Thermal conductivity of ground

Page 12: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-3 0

+2,5

Undisturbed ground

+8,5

Borehole wall

Ground-source heat pump operating conditions

40 % of temperature difference between heat carrier fluid and surrounding ground within the borehole

TRT used to measure performance of borehole heat exchangers Thermal conductivity of ground

Page 13: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Single U-pipe BHE

Germany, several bentonite 0,10-0,13Germany, several thermal grout 0,06-0,08USA, several bentonite 0,13-0,15USA, several thermal grout 0,09-0,10Sweden, several water, heating 0,06-0,08Studsvik ice 0,09

Field measurements of borehole thermal resistance

Page 14: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

UNDERGROUND THERMAL ENERGY STORAGE

Page 15: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

BTES - Luleå

Borehole heat store: 120 boreholes depth 65 m

Page 16: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Measured temperature in center of store

BTES - Luleå

Page 17: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Measured and simulated energy balance 1983-1988

-1500

-1000

-500

0

500

1000

1500

2000

2500

3000

3500

4000

4500

Ener

gy (M

Wh)

Simulated heat injectionMeasured heat injectionSimulated heat extractionMeasured heat extraction

1983-84 1985-861984-85 1987-881986-87

BTES - Luleå

Page 18: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Estimated ground temperature after charging

BTES - Luleå

Heat losses proportional to to thermal conductivity of ground

Page 19: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Estimated ground temperature after charging

BTES - Luleå

Heat losses proportional to to thermal conductivity of ground

(Influence of groundwater flow)

Page 20: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL PROCESSES

Page 21: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

What is the relation between fluid temperatures and heat transfer rates for a specific borehole exhanger design?

0

5

10

15

20

25

30

35

40

0 50 100 150 200 250 300 350

Days

Tem

pera

ture

(C)

Outlet temperature

Inlet temperature

Mean store temperature

Energy load variation

Page 22: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Common approach: Determine a thermal response function!

Two basic parts: Response of the thermal process in the borehole Response of the thermal process in the ground

surrounding borehole

Method of analysis

Page 23: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

0

1

2

3

4

5

0 5 10 15 20 25 30 35 40Tid

Tem

pera

turä

ndrin

g

Rg

Rb

Borrhålsvägg

Fluid

Ostörd mark

Temperature change when constant heat injection rate is supplied

Borehole wall

Undisturbed ground

Time (hours)

Thermal response

(Similar to thermal response test)

Page 24: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Superpositioning of response functions

Thermal response

0

1

2

3

4

5

6

7

8

0 2000 4000 6000 8000 10000

Flui

d te

mpe

ratu

re

Time

Page 25: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Superpositioning of response functions

Thermal response

0

1

2

3

4

5

6

7

8

0 2000 4000 6000 8000 10000

Flui

d te

mpe

ratu

re

Time

Page 26: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Superpositioning of response functions

Thermal response

0

1

2

3

4

5

6

7

8

0 2000 4000 6000 8000 10000

Flui

d te

mpe

ratu

re

Time

Page 27: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Superpositioning of response functions

Thermal response

0

1

2

3

4

5

6

7

8

0 2000 4000 6000 8000 10000

Flui

d te

mpe

ratu

re

Time

Page 28: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Superpositioning of response functions

Thermal response

0

1

2

3

4

5

6

7

8

0 2000 4000 6000 8000 10000

Flui

d te

mpe

ratu

re

Time

Page 29: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Transient radial heat conduction

Steady-state heat conduction

Character of heat transfer process

Short term Long term

Page 30: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Example of numeric grid (Chiasson)

Numerical methods

Page 31: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

SBM – Superposition Borehole Model

homogeneous ground properties

borehole heat exchanger (depth, material, filling material)

arbitrary placement of boreholes (vertical or graded)

Validated against field experiments

Results:

fluid temperature variation

temperature in the ground

energy balance

Simulation models

Page 32: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Design tool

EED – Earth Energy Designer

easy and fast to use (GUI)

ground properties

borehole heat exchanger (type, depth, material, filling material)

800 predefined borehole configurations

heat carrier fluid

The model provides databases for the input data and also relies on a

database of pre-calculated response functions

Results: fluid temperature variation and required borehole length

Page 33: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Non-dimensional response functions

Non-dimensional thermal response function – so-called g-functions

Page 34: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL RESPONSE TEST

Page 35: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal Response Testing (TRT)

35

Page 36: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

1975, Gothenburg: GSHP in clay 1981, Luleå: 19 borehole pilot trial BTES installation 1983, Stockholm: GSHP in rock 1984, Luleå: 120 borehole high-temperature BTES installation 1986, Stockholm: 25 borehole low-temperature BTES 1992, Linköping: 100 U-pipes high-temperature heat storage in clay

These TRT tests were performed after the installations were already completed to verify ground loop performance

In order to influence the ground loop sizing it would be desirable to make an in-situ TRT before the detailed design

Brief history of Thermal Response Testing

Page 37: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

First mobile TRT rig (1996)

Mobile thermal response test equipment

Page 38: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

1996, Sweden: First mobile TRT in operation 1998, USA, Independent development

1997, Netherlands: Mobile TRT with heat pump 2008, Sweden: TRT with optic fibres

Brief history

Page 39: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal Response Testing (TRT) - Procedure

39

Test Procedure Minimum 3Hrs circulation without heating Minimum 50hrs circulation with constant heat input Optional 24hrs recovery with heater switched off

Data Logger Flow rate of carrier fluid (m3/s) Heat input (kW) Inflow temperature ( C) to BHE Return temperature ( C) from BHE Ambient air temperature ( C)

Page 40: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal Response Testing (TRT)

40

11121314151617181920212223242526272829303132

0 10 20 30 40 50 60 70 80 90 100

Tem

per

atu

re (C

)

Hours

Fluid temperature from boreholeFluid temperature to boreholeAmbient air temperature

0

1000

2000

3000

4000

5000

6000

7000

0 10 20 30 40 50 60 70 80 90 100

Hea

t inj

ectio

n ra

te (W

)

Hours

Measured injection rate, heat carrier fluid temperatures and ambient temperature

Page 41: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal response test (TRT) Estimates the effective thermal conductivity along the borehole Estimates the thermal resistance between heat carrier fluid and

borehole wall Logging of vertical temperature profile in the borehole Geohydrological conditions

Groundwater level Permeable layers

Sampling of cuttings Analysis of mineral composition gives further information on

thermal properties of the ground Drilling conditions

Soil depth, geological stratification, production capability

Site investigation of heat transfer properties

Page 42: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Planning of drilling and TRT test Allow 3-5 days between end of drilling and start of TRT test Allow for initial period with only circulation (no heat input) Test duration at least 50 hours Avoid drilling activities in the vicinity Measure vertical temperature profile before and after test

Number of boreholes to test For large projects sometimes several test boreholes drilled

and number of TRT chosen depending on variability of geology

Borehole heat exchanger depth and design Should be similar to chosen design

Heat injection rate and heat carrier flow rate Should be similar to expected load conditions

Thermal response test considerations

Page 43: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Measured heat input Measured average fluid temperature Measured ambient air temperature

Radial heat conduction in rock Line-source model Two node borehole model

Borehole heat capacity included Heat carrier fluid capacity included

Parameter fitting using Nelder-Mead minimization of quadratic error

Results: Effective thermal conductivity and borehole thermal resistance

Evaluation method

Page 44: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Electric power from grid Easy to use Sometimes unreliable (power cuts, vandalism, etc) Some diurnal fluctuation

Electric power from generator Independent of grid (required at undeveloped sites) Stable power Needs refueling

Heavy rigs difficult to handle outside paved areas Thermal insulation of flow path very important Full remote control practical

Experiences – equipment

Page 45: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Evaluation methods used: Line-source method Numerical parameter fitting method with radial heat conduction and heat capacity

of fluid and grout

Important to use the same model and parameters when applying the results to the design case

Borehole thermal resistance may have to be modified from measured conditions due to changes in flow rate and temperature

Experiences – evaluation

Page 46: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Fitting procedure of measured and calculated fluid temperatures gives effective ground thermal conductivity and borehole thermal resistance

8

9

10

11

12

13

14

15

16

17

0 10 20 30 40 50 60 70 80 90

Hours

Ave

rage

flui

d te

mpe

ratu

re

Measured fluid temperature

Fitted simulated fluid temperature

Thermal response test evaluation

Page 47: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Long-term test (35 days) in Sweden (1996)

5

10

15

20

25

30

0 100 200 300 400 500 600 700 800 900

Hours

Tem

pera

ture

Measured fluid temperature

Air temperature

Calculated fluid temperature

Oskarshamn, Sweden1996-07-05 --- 1996-08-10870 hours

Borehole depth 161 mBorehole diameter 135 mmUndisturbed ground temperature 10,5 CSingle U-pipe

40 W/m

40 W/m

69 W/m

69 W/m

40 W/m

11 W/m 11 W/m11 W/m

11 W/

Long-term thermal response test evaluation

Page 48: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Short-term response (residence time)

8

9

10

11

12

13

14

0 500 1000 1500 2000 2500

Time (seconds)

Flui

d te

mpe

ratu

re (C

)

Borehole outlet temperature

Borehole inlet temperature

Start of heating

Residence time (400 seconds)

Initial thermal response

Page 49: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal response test

Fluid capacity

Page 50: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal response test

Fluid and grout thermal capacity

Page 51: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Temperature as function of borehole depth

Brf. Mandolinen, LundTemperaturloggning med kabellod i U-rör 040415-16

8,0

8,5

9,0

9,5

10,0

10,5

11,0

11,5

12,0

0 20 40 60 80 100 120 140 160 180 200

Djup (m)

Tem

per

atu

r (C

)

B6B14B13B12B11B10B8B9

Undisturbed ground temperature

Depth

Page 52: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Temperature as function of borehole depth

Undisturbed ground temperature

8,0

8,5

9,0

9,5

10,0

10,5

11,0

0 50 100 150 200

Tem

pera

ture

(C)

Depth (m)

Borehole1 - close to old building

Borehole 2 - middle of park

Borehole 3 - close to new building

Page 53: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Temperature as function of borehole depthThe boreholes are located in the centre of Stockholm

Undisturbed ground temperature

8

9

10

11

12

13

14

15

16

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190

Tem

pera

ture

(C)

Depth (m)

Boreholel 1

Borrhole 2

Page 54: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

5,0

5,5

6,0

6,5

7,0

7,5

8,0

8,5

9,0

9,5

10,0

0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300

Tem

pera

tur

(C)

Djup (m)

Borrhål 1

Borrhål 2

Extrapolerad temperatur

Borehole 1 disturbed by groundwater flow

Undisturbed ground temperature

Page 55: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Temperature as function of borehole depthThe evolution of the profiles indicate a zone with groundwater flow around 25 m depth

Temperature profile at different times

8

9

10

11

12

13

14

15

16

17

18

0 25 50 75 100 125 150 175 200

Tem

pera

ture

(C)

Depth (m)

45 minutes before TRT

4,5 hours after TRT

3 days after TRT

Page 56: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

About 150 measurements performed in Sweden About eight of those strongly affected by groundwater flow

Values influenced by vertical groundwater flow through borehole At one location the system was changed from borehole heat extraction

to groundwater-source heat pump after the TRT result Warning – flow conditions may change with more boreholes in the

vicinity Nearby drilling activities disturbs the groundwater flow

Effective thermal conductivities in the range 2,5-6,8 W/m,K Values influenced by vertical groundwater through borehole

Experiences – effective thermal conductivity

Page 57: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Estimation of borehole thermal resistance requires good estimate of undisturbed ground temperature

Groundwater-filled boreholes Borehole thermal resistance depends on heat injection rate

and temperature level Method to estimate borehole heat exchanger performance

Site-specific conditions may influence values (base reference values on measurements on several boreholes)

Experiences – borehole thermal resistance

Page 58: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Measure undisturbed vertical temperature profile Estimate undisturbed ground temperature based on initial

period with only circulation of heat carrier fluid “Undisturbed” ground temperature profile may be disturbed by

heat flow from buildings, paved areas and tunnels (and changes in local climate) Interpreting vertical variations in thermal conductivity by

using the profile may be difficult Measuring vertical temperature profile before and after the TRT

may indicate zones of groundwater flow and/or layers with differing thermal conductivity

Experiences – undisturbed ground temperature

Page 59: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL RESPONSE TESTGroundwater-filled boreholes

Page 60: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Better heat transfer than grouted or sand-filled boreholes

Water movement Natural convection between pipes and borehole wall Vertical flow in borehole

Freezing of borehole water

Groundwater-filled boreholes

Page 61: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

ActiveBorehole depth

Groundwater-filled part of the borehole

Active borehole depth

Page 62: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Case Power [kW] Dur [h] λe [W/m,K] Rb [Km/W]

M1 6 70 3.4 0.065

M2 Circulation pump36Circulation pump

26989971

3.23.23.2

0.0690.0590.104

M3 Circulation pump63

237296

3.53.5

0.0670.077

M4 Circulation pump6Circulation pump3Circulation pump3

271165312023307

3.33.33.3

3.3

0.0650.0960.073

0.073

0,04

0,05

0,06

0,07

0,08

0,09

0,1

0,11

8 13 18 23 28

Fluidtemperatur [oC]

Term

iskt

bor

rhål

smot

stån

d [K

m/W

]

TRT measurements at Luleå

High injection rates and high temperatures give lower borehole thermal resistance due to natural convection within the borehole

996996,5

997997,5

998998,5

999999,51000

1000,5

2 7 12 17 22 27

Temperatur [oC]

Den

site

t [kg

/m3 ]

TRT with varying heat injection rates

Ground-water filled boreholes

Page 63: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

-0,006

-0,004

-0,002

0

0,0020,004

0,006

0,008

0,01

0,012

-0,06 -0,04 -0,02 0 0,02 0,04 0,06

Cartesian coordinater (x,y,z) = (0, 1.5, ]-0.0518, 0.0518[) [m]

Has

tighe

t [m

/s]

12 24 38

The water close to the pipes will rise during heatinjection

Water velocity depends on temperature (viscosity).

Heat injection rate 75 W/m

12 C results in maximum velocity of 0,006 m/s

24 C results in maximum velocity of 0,009 m/s

38 C results in maximum velocity of 0,011 m/s

Simulations of natural convection in borehole

Single U-pipe in groundwater-filled borehole

Page 64: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermosiphon effect

Vertical groundwater flow through borehole due to natural convection

Page 65: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermosiphon – heat injection

Page 66: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermosiphon – heat extraction

Page 67: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Ground water levels

Groundwater flow between permeable layers with different hydrostatic pressure

Page 68: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal response test and artesian flow

Thermal response influenced by groundwater flow

Page 69: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL RESPONSE TESTGroundwater flow

Page 70: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Simulation of thermal process in low permeable layer(Dähne and Kaiser, 2004)

Regional groundwater flow

Page 71: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Simulation of thermal process in high permeable layer(Dähne and Kaiser, 2004)

Regional groundwater flow

Page 72: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Influence of groundwater flow (Witte, 2001)

15

17

19

21

23

25

27

29

31

33

35

0 20 40 60 80 100 120

Time (hours)

Tem

pera

ture

(oC

)

Reference

GW extraction

Thermal response test and groundwater flow

Separation point where influence of groundwater flow can be seen

Page 73: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

14

16

18

20

22

24

26

28

0 20 40 60 80 100 120 140Time (hrs)

Tem

pera

ture

(ºC

)

24 Pa/m (0.5*48 Pa/m)

48 Pa/m

96 Pa/m (2*48 Pa/m)

Influence of groundwater flow - simulation (Witte, 2001)

Thermal response test and groundwater flow

Separation at later time with lower groundwater flow

Page 74: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL RESPONSE TESTFreezing boreholes

Page 75: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

In 2004 a new TRT equipment was built at LuleåTechnical University. It contains both an electricheater and a heat pump

Övertorneå

162 m groundwater-filled borehole, single U-pipe

5 days heat injection 12 kW7 days rest,6 days heat extraction 7,3 kW

Results

λe = 4,2 W/m,K

Rb1 = 0,066 Km/W (heat injection)

Rb2 = 0,094 Km/W (heat extraction, unfrozen)

Rb3 = 0,075 Km/W (heat extraction, frozen)

New TRT equipment

Page 76: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thermal response test with freezing

Temperature decrease in heat carrier fluidwith freezing borehole water

Page 77: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Stockholm, 1983

Thermal response test with freezing

unfrozen

freezing

Page 78: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Danger of squeezing the pipeA survey in Sweden showed that incidence of pipe damage is very small

(estimated to 1 in 5,000-10,000)

Freezing of borehole water

Page 79: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

THERMAL RESPONSE TESTOptic Fibre

Page 80: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

TRT with optical fibre (DTRT)Acuna, Hill, Mogensen, Palm (Royal Institute of Technology, Stockholm)

TRT with optic fibre

Page 81: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Temperature profile and flow log

TRT with optic fibre

Borehole depth 260 mDiameter 140 mmSingle U-pipe PE80 40 mmEthanol/water mixture (16%)Flow rate 1,87 m3/h

Page 82: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Vertical temperature profile before and during initial circulation of fluid

TRT with optic fibre

Average fluid temperatures during heating phase

Page 83: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Measurement of heat balance in sections

Distributed Thermal Response Test - DTRT

Page 84: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Power supplied in each section of the borehole

Distributed Thermal Response Test - DTRT

Page 85: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Fluid temperatures in each section during injection(Borehole thermal resistance evaluated from this curve)

Distributed Thermal Response Test - DTRT

Page 86: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Fluid temperatures in each section during recovery(Ground thermal conductivity evaluated from this curve)

Distributed Thermal Response Test - DTRT

Page 87: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Evaluated thermal conductivity and borehole thermal resistance in each section

Distributed Thermal Response Test - DTRT

DTRT results (average values)-Ground thermal conductivity 3,10 W/m,K-Borehole thermal resistance 0,063 K/(W/m)

TRT results -Ground thermal conductivity 3,08 W/m,K-Borehole thermal resistance 0,079 K/(W/m)

Undisturbed ground temperature-Based on vertical profile 9,10 C-Based on initial circulation 9,19 C(Difference attributed to circulation pump work)

Page 88: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Four different designs tested(3-pipe, U-pipe with and without spacer, U-pipe with internal turbulence promoter (fins))

Borehole heat exchanger comparison

Page 89: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Single U-pipe: Vertical temperature profile in fluid(Acuna et al, 2008)

Vertical temperature profile

Page 90: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Single U-pipe: Vertical temperature profile in fluid(Acuna et al, 2008)

Vertical temperature profile

Thermal short-circuiting

Page 91: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Current activities

Chalmers Technical University, Gothenburg Analytical and numerical modelling of short-term respons

Royal Institute of Technology, Stockholm Borehole heat exchangers – field measurements using optic

fibre

Luleå Technical University Numerical simulations of groundwater filled borehole heat

exchangers

Page 92: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

The thermal response test is an establishedstandard procedure for large projects

Thermal response test

Page 93: Advanced Thermal Response Testing and Its Relevance to ......Thermal response test evaluation Long-term test (35 days) in Sweden (1996) 5 10 15 20 25 30 0 100 200 300 400 500 600 700

Thank you!