Today most of the equipments used in offices, Industries and at home are highlysophisticated and high-end equipments. Every workplace has mission critical areas that needto be protected from fire hazard not only to save life and property but also to ensure that theenterprise does not come to a stand still.
The most common fuels in fire and explosion incidents are petroleum products, cellulosematerials (wood, paper, cloth) and polymers.
Overview of Fire Protection
Restricted © Siemens AG 20XXJanuary 2018Page 3 I BT SSP-OP
Type of Fire Protection Systems
Fire
Protection System
Water
Based System
Gas
Based Systems
Restricted © Siemens AG 20XXJanuary 2018Page 4 I BT SSP-OP
Water based Systems
Water Based
Systems
Yard Hydrant
System
Wet Riser System
SprinklerSystem
Spray System
Foam System
Restricted © Siemens AG 20XXJanuary 2018Page 5 I BT SSP-OP
Standards/Codes for Fire Fighting System
Restricted © Siemens AG 20XXJanuary 2018Page 6 I BT SSP-OP
SPRINKLER SYSTEM
• It is the first self detecting and second acting fire protectionsystem.
• It is basically a fire water network provided inside the occupancyduly provided with fire sensitive fusible elements.
• It can work in absence of man power and at any time. It providesdetection & protection in otherwise unapproachable area also.
Restricted © Siemens AG 20XXJanuary 2018Page 7 I BT SSP-OP
SPRINKLER PUMP AS REQUIRED
HEAVY GRADE GI/MS PIPES
ALARM VALVE & GONG BELL
Components of Sprinkler System
Restricted © Siemens AG 20XXJanuary 2018Page 8 I BT SSP-OP
FLOW SWITCH
ISOLATION VALVES
SPRINKLER AIR RELEASE VALVE
Components of Sprinkler System
Restricted © Siemens AG 20XXJanuary 2018Page 9 I BT SSP-OP
SPRINKLERSFLEXIBLE HOSESFITTINGSSUPPORTING CLAMPS
Components of Sprinkler System
Restricted © Siemens AG 20XXJanuary 2018Page 10 I BT SSP-OP
TYPE OF SPRINKLERSUpright and pendent sprinklers
Flush and Recessed sprinklers
Concealed sprinklers
Intermediate sprinklers
Extra and very extra large orifice sprinklers
High temperature sprinklers
Large drop sprinklers
Fast response sprinklers
Restricted © Siemens AG 20XXJanuary 2018Page 11 I BT SSP-OP
How a sprinkler system worksA sprinkler system consists of a network of pipes connected to a watersupply, carrying sprinkler heads which are activated in the event offire. Each sprinkler acts as an individual heat sensing device, andduring a fire only those affected by the heat activates.
The sprinkler bulb contains a liquid which has a high co-efficient ofexpansion. A small quantity of vapour is trapped when the bulb ishermetically sealed. When the liquid expands under the influence ofheat from a fire, pressure in the bulb rises until all the vapour isabsorbed. Further rises of temperature cause a rapid pressure risesufficient to shatter the bulb into small pieces, releasing the seal andallowing water to be distributed evenly over the fire area.
Restricted © Siemens AG 20XXJanuary 2018Page 12 I BT SSP-OP
In a fire, few deaths result from direct contact with flames; thegreatest threat comes from inhalation of the products ofcombustion such as carbon dioxide, hydrogen cyanide,hydrogen chloride and other toxic gases, and the heat of thegases.
The response time of a fast response sprinkler ensures thatthe life-threatening levels of toxic gases and temperature arenever reached.
Sprinklers provide valuable time for those in charge to assisttheir escape.
Fast response sprinklers for life safety
Restricted © Siemens AG 20XXJanuary 2018Page 13 I BT SSP-OP
Components of Sprinkler
Restricted © Siemens AG 20XXJanuary 2018Page 14 I BT SSP-OP
Two functions to perform i.e firstdetect a fire and then provide anadequate distribution of water to controlthe fire spread
Hence an early detection andadequate discharge of water at requiredpressure over the affected area are themain criteria for design of sprinklers.
SPRINKLER DESIGN
Restricted © Siemens AG 20XXJanuary 2018Page 15 I BT SSP-OP
Conventional sprinklers
These can be mounted in either the upright or pendentposition and the deflector is designed to spray a proportion ofthe water discharge onto the surface of the ceilings.
Upright and pendent spray sprinklers
Spray sprinklers are used for applications where all the waterneeds to be discharged downwards.
Matching the sprinkler to the hazard
Restricted © Siemens AG 20XXJanuary 2018Page 16 I BT SSP-OP
Sidewall sprinklers
These are primarily used to keep ceilings clear of pipe work for aestheticreasons or to avoid having to disturb existing ceilings when installing pipework. Each sprinkler protects up to 17 m2 in light hazards and 9m2 inordinary hazards. Application Hotel guest rooms.
Horizontal sidewall sprinklers with extended coverage
These are specifically designed to give an extended coverage of waterdistribution. This type of sprinkler must have a fast response bulb. Onesprinkler can protect an area of up to 21m2
Matching the sprinkler to the hazard
Restricted © Siemens AG 20XXJanuary 2018Page 17 I BT SSP-OP
•Nominal release•Temperature in o C
•57•68•79•93•141•182•227•260
Liquid color code
OrangeRed
YellowGreenBlue
MauveBlackBlack
Nominal Release Temperature & Color Coding Glass bulbs
Selected temperature rating shall be at least 30 o above highest ambient temperature at the site of installation.
Restricted © Siemens AG 20XXJanuary 2018Page 18 I BT SSP-OP
• Actual operating temperature of the sprinkler.
• Ease of transfer of heat from the surrounding air to the affected parts of the sprinkler.
• Height of the ceiling below which the sprinkler is mounted.
• Shape of ceiling – Inverted V type, paneled, flat, curved, north light.
• Thermal characteristics of the ceiling assembly.
• Distance between the sprinkler and the ceiling.
• Horizontal distance of sprinkler from the fire.
Factors controlling the performance of Sprinklers
Restricted © Siemens AG 20XXJanuary 2018Page 19 I BT SSP-OP
Restricted © Siemens AG 20XXJanuary 2018Page 20 I BT SSP-OP
Important considerations
Coverage area per sprinkler
Location and spacing of sprinklers
Selection of type and temperature rating
Hydraulics of the system
Pumping and water requirements
Compliance to the code
SPRINKLER SYSTEM
Restricted © Siemens AG 20XXJanuary 2018Page 21 I BT SSP-OP
SPRINKLER COVERAGE
Light Hazard : 21 M2
Ordinary Hazard : 12 M2
High Hazard : 9 M2
Restricted © Siemens AG 20XXJanuary 2018Page 22 I BT SSP-OP
SPRINKLER SPACING
Area coverage per sprinkler is
12M2 for all sprinklers
Sprinkler
SprayPattern
Area covered = 12M2
(ORDINARY HAZARD)
Restricted © Siemens AG 20XXJanuary 2018Page 24 I BT SSP-OP
All the sprinkler patterns are overlapped toensure that there are no dry spots.
Hence spacing of sprinklers isvery important
Hence for a floor area of 1200 M2, requirement of roof sprinklers is > 100, (as a thumb rule 8 to 10% more)
Restricted © Siemens AG 20XXJanuary 2018Page 25 I BT SSP-OP
FALSE CEILING SPRINKLER SECTION
Restricted © Siemens AG 20XXJanuary 2018Page 27 I BT SSP-OP
Hazard Density inLPM/M2
Assumed Maximum Area of Operation in M2 (AMAO)
Light 2.5 84
Ordinary 5 360
High (Process)
10 260
High (Storage)
12.5 to 22.5 260 to 300
DESIGN DENSITY AS PER IS CODE
Restricted © Siemens AG 20XXJanuary 2018Page 28 I BT SSP-OP
DESIGN DENSITY (Illustration)
5 LPM/M2 over an AMAO of 360M2
One Sprinkler covers a floor area of 12M2
Each M2 of the floor area below should receivewater from the sprinkler at a rate of at least of 5LPM
Means sprinkler discharge should be at least 60 LPM
Restricted © Siemens AG 20XXJanuary 2018Page 30 I BT SSP-OP
LIGHT HAZARD :- NOT LESS THAN 20 MINUTES RUN FOR THE INSTALLEDPUMPING CAPACITY OR 35M3 WHICHEVER IS GREATER
ORDINARY HAZARD :- NOT LESS THAN 1 HOUR RUN FOR THE AGGREGATEPUMPING CAPACITY OR 200M3 WHICHEVER IS GREATER
HIGH HAZARD :- NOT LESS THAN 2 HOUR RUN FOR THE AGGREGATE PUMPINGCAPACITY
WATER REQUIREMENT AS PER IS CODE
Restricted © Siemens AG 20XXJanuary 2018Page 31 I BT SSP-OP
ROOF SPRINKLER SYSTEM
Restricted © Siemens AG 20XXJanuary 2018Page 32 I BT SSP-OP
ROOF SPRINKLER SYSTEM
Restricted © Siemens AG 20XXJanuary 2018Page 33 I BT SSP-OP
ROOF SPRINKLER SYSTEM
Restricted © Siemens AG 20XXJanuary 2018Page 35 I BT SSP-OP
WET RISER AND SPRINKLER SYSTEM
Restricted © Siemens AG 20XXJanuary 2018Page 37 I BT SSP-OP