Eco Dial Eng

59
Division - Name - Date - Language 1

Transcript of Eco Dial Eng

Division - Name - Date - Language 1

Division - Name - Date - Language 2

1. INTRODUCTION

From Ecodial2 to Ecodial3 :

Windows 3.11, 95, 98 and NT

New products : Contactors , Circuit breakers (Telemecanique), Thermal relays, Soft starters, Variable speed drives,

Capacitors

A new calculation standard : CENELEC (R0064-003) Installation standards : IEC364, C15-100

Division - Name - Date - Language 3

General characteristics Drawing Definition of circuit characteristics Power sum Calculation Results Output

The main steps of a study

Division - Name - Date - Language 4

Un Ph-Ph (415V) : sets the LV network voltage. This value corresponds to a phase-phase voltage

Earthing arangement (TNC) : sets the earthing arrangement at the transformer. This value can only be changed in a network after an LV/LV transformer, or from TNC to TNS.

Cascading (YES) : authorises Ecodial to use reinforced breaking capacity to choose downstream breakers. This can help reduce the cost of an installation.

Discrimination (YES) : displays the discrimination results and chooses breakers giving better discrimination results.

Smax (240mm²) : sets the maximum cable CSA that Ecodial can use when sizing cables (multiple cables in parallel can always be used though)

General characteristicsCalculation / General characteristics

Division - Name - Date - Language 5

CSA N / CSA Ph (1) : sets the minimum ratio between phase and neutral conductors. This is used to allow half neutrals (1/2) or require full neutrals (1).

Tolerance (5%) : Ecodial calculates the theoretical Phase CSA. Tolerance can be included to allow the choice of cable slightly smaller than the theoretical value.

Standard (IEC947-2) : Allows the user to choose a default product standard (IEC947-2 or IEC898) according to which the breaking capacity of the circuit breakers are given. If the standard is set to IEC898, Ecodial automatically chooses IEC947-2 if no IEC898 are available

Target power factor (0.96) : this is the value Ecodial will use to size the required capacitor bank. It corresponds to the power factor downstream of the transformer.

System frequency (50Hz) : enables users to choose products that are suitable for 60hz applications (capacitors, …).

General characteristicsCalculation / General characteristics

Division - Name - Date - Language 6

Sources : Transformer, Generator, Undefined, (Bus coupler) Busbar : Busbar, (interlock) Outgoing circuits Loads : receiver, motor, lighting, variable speed drive LV transformer (isolating, step-up, step-down) graphic links - project links Standard diagrams

Drawing the network - the symbol toolboxDisplay / Symbol Toolbox

Division - Name - Date - Language 7

B2

Switchboard

Q1

Source

C1

T1

Q5

Main lighting

C5

D5 Main lighting

E5

Q4

K4

Main motor

C4

M4

Q3

Main Load

C3

L3

The first study

Division - Name - Date - Language 8

select circuit and F4, or double-click on circuit

• Name all the circuits :

– Supply, Switchboard, Main Load, Main Motor, Main Lighting

• Enter circuit parameters:

– Main Load : 35m, 238A

– Main motor : 39m, 110kW (mechanical),

– Main Lighting :15m cable, 30m busbar, 20x150W Incandescent lights, 10 identical circuits

Useful tools

• Network / Item lists …

– faster input of circuit characteristics once the circuits are named.

• Display / Network tree (F2)

• Network / Logical check (F3)

Definition of circuit characteristicsNetwork / Circuit description

Division - Name - Date - Language 9

Automatically calculates the theoretical power of transformer and generator. (400kVA)

Automatically calculates the currents in the different branches of the circuits. (ex Total Switchboard feeders = 436.36A)

Ku and Ks coefficients can be used to optimise design.

Ecodial will recommend a transformer size.

Power sum should be run after every modification !

The Power SumCalculation / Power Sum

Division - Name - Date - Language 10

The Power Sum is not compulsory.

But then the user must manually define the currents in every circuits.

• Advantage : quicker calculations :

– Do not have to draw/enter all the circuits.

– Enter only the circuits one wants to calculate, and expected current.

• Disadvantage : results can be sometimes surprising !

POWER SUM IS RECOMMENDED IN BIG PROJECTS !

The Power SumCalculation / Power Sum

Division - Name - Date - Language 11

Division - Name - Date - Language 12

When single phases are connected to a three phase board, Ecodial can automatically suggest a phase distribution solution

The automatic distribution can be modified. The logic applied is the following

• Ecodial sorts the loads by decreasing intensity.

• Starting from the highest load, Ecodial will place the loads onto the first phase until the sum of these loads is equal to 33% of the total load

• Ecodial then tries to load the second phase until the sum of these loads reaches 50 of the remaining loads.

• All the loads that remain are then allocated to the third phase. This systems gives the best possible distribution in most cases. It is always

possible to modify the result. The upstream circuit is sized on the highest phase loading.

The Power SumLoad distribution

Division - Name - Date - Language 13

Automatic mode

– equipment is selected automatically.

– No additional entry is required, Ecodial uses default values (installation method, cable type, …)

Manual mode

– parameters can be defined by user, and then theyare checked to see if they verify all the safety criteria.

– An unsafe choice will not be allowed to be validated.

Equipment calculated

– Circuit breakers (and fuses) and isolators

– Contactors and relays

– Cable, BTS, and busbar

The CalculationCalculation / Calculate

Division - Name - Date - Language 14

Division - Name - Date - Language 15

Load current and breaking capacity identifies circuit breaker

Choice of circuit breaker sets thermal setting

Thermal setting defines minimum theoretical cable CSA

Verification of cable (Sp, Sn, Spe theoretic)

• voltage drop

• protection against indirect contact

• short circuit currents

Sizing constraint (overload, voltage drop, user, …)

The CalculationCalculation / Calculate

Division - Name - Date - Language 16

Busbar sizing :

• For main busbar, size is defined by the circuit breaker protection which is defined by the nominal current of transformer (and not the sum of the load currents !)

• For other busbar (sub DB) : sizing according to circuit breaker protection, which is defined by the load current.

Short circuit currents

• Ik max : cold short circuit (copper is cold-low resistivity)

• Ik min : warm short circuit (copper is warm - high resistivity)

• Ik3 : three phase ‘bolted’ fault

• Ik2 : phase - phase fault

• Ik1 : phase - neutral fault

• Earth fault : phase-earth fault

The CalculationCalculation / Calculate

Division - Name - Date - Language 17

The CalculationResistivity values

o : resitivity at 20 degrees Celcius (IEC909)

• copper : 18,51• aluminium : 29,41

At different temperatures :• PVC

1= 1,2x o at 70 degrees

2= 1,38x o at 115 degrees (if S <= 300 mm²)

2= 1,34x o at 105 degrees (if S > 300 mm²

3= 1,30x o at 95 degrees (if S <= 300 mm²)

3= 1,26x o at 85 degrees (if S > 300 mm²)

• PR 1= 1,28x o at 90 degrees

2= 1,60x o at 170 degrees

3= 1,48x o at 140 degrees

Linear reactance (non armoured cables)• multi core or single core in trefoil : = 0,08• single core, flat touching : = 0,09• single core, spaced : = 0,13

Division - Name - Date - Language 18

The CalculationShort circuit currents (values of resistivity to be used)

Ik3max, Ik2max and Ik1max : o

Ik2min and Ik1min

• for circuit protected by fuses : 2

• for circuits protected by circuit breakers : 1

If (earth fault current)• TNC :

– for circuit protected by fuses : 2

– for circuits protected by circuit breakers : 1

• Multicore, PE included

– for circuit protected by fuses : 2

– for circuits protected by circuit breakers : 1

• PE separate

– for circuit protected by fuses : 2

– for circuits protected by circuit breakers : 1

Voltage drop :

• 1

Division - Name - Date - Language 19

B7

Emergency DB

B2

Switchboard

C6

Emergency DB feeder

Q6

Q8

C8

Emergency supply

G8

L9

C9

Vital Load

Q9

M10

C10

Vital Motor

K10

Q10

Q5

Main lighting

C5

D5

Main lighting

E5

Q4

K4

Main motor

C4

M4

Q3

Main Load

C3

L3

Q1

Source

C1

T1

The second study

Division - Name - Date - Language 20

Define new circuits :

• Emergency DB feeder : 45 m , (I = ???)

• Emergency DB

• Emergency supply

• Vital Load (36m, 135A)

• Vital Motor (75m, 18,5 kW mechanical)

Run Power Sum

• Transformer : 400 to 630 kVA

• Generator : 160 kVA (only supplies Emergency board !)

Run Calculation

Modify the circuit

Division - Name - Date - Language 21

Zoom : drag a box around the area to zoom into

Grid

Alf F3 = search for a particular circuit based on its name or ID

Circuit selection (multiple) : keep SHIFT button pressed while selecting multiple circuits, or draw a box around the circuits to select.

Moving circuits : drag and drop the selection

Copying circuits (including the characteristics)

• select circuit to be copied

• CTRL+C and then CTRL+V

• Edit / Copy and then Edit / Paste

Enlarge busbars : select busbar, click on , enlarge bars.

Advanced editing

Division - Name - Date - Language 22

Power (kVA) : the nominal rating of the transformer. It is usually calculated and set in the power sum, nonetheless it can be manually set by the user here.

Earthing arrangement : a reminder of the earthing arrangement set in the general characteristics. Modifying the earthing arrangement here does not modify the earthing arrangement of all the downstream circuits.

Distributed neutral : identifies networks that have or have no neutral conductor.

Un Ph-Ph : a reminder of the system voltage. As for the earthing system, changing the voltage here does not automatically change the voltage of all the other circuits.

Short circuit voltage : parameter which is used to calculate the impedance of the transformer (Z). The resistance and reactance are estimated using the CENELEC guide lines.

Circuit descriptionTransformer

Division - Name - Date - Language 23

Circuit descriptionTransformer (2)

HV Psc : short circuit level on the medium voltage side of the transformer. Enables Ecodial to calculate the impedance (Z) of the medium voltage network

Connection : the different windings of the MV/LV transformer

Power factor : a result of the Power Sum. The power factor at the downstream terminals of the transformer.

System frequency

HV operating time : time used to size the transformer to circuit breaker connection (refers to Electrical Installation Guide table H1-63)

Division - Name - Date - Language 24

Circuit descriptionTransformer (3)

Results :

• R and X of MV network (using CENELEC R064-003 formulas)

– XQ= 0,995 x ZQ RQ=0,1 x XQ

• R and X of transformer (using CENELEC R064-003 formulas)

– RT=0,31 x ZT XT = 0,95 x ZT

• Ib : rated current of the transformer (In)

• Isc max (maximum short circuit current at the terminals of the transformer)

• Copper losses (heat loss)

kQQ S

UnZ

2)05,1(

100

)05,1( 2kr

rTT

u

S

UnZ

TRInPcu 23

Un

SIn rT

3

upstream

kZ

UncIIsc

3

05,1maxmax3

Division - Name - Date - Language 25

Circuit descriptionGenerators

Power (kVA) : see previous

Earthing arrangement : see previous

Distributed neutral : see previous

Un Ph-Ph : see previous

Power factor : see previous.

System frequency : see previous

X’o : Zero phase impedance

X’’ : Transient impedance, used to calculate the short circuit current

Division - Name - Date - Language 26

Circuit descriptionSource

Un Ph-Ph : see previous

Isc max (kA) : maximum short circuit current (Ik3max) at the point of the LV connection from which the study will start.

Power factor : see previous.

System frequency : see previous

Energy supplier : Private substation is the only value.

Distributed neutral : see previous

I service connection (A) : Intensity of the connection, in other words the current rating of the upstream protection device (not drawn on the diagram).

Division - Name - Date - Language 27

Circuit descriptionSource (2)

Isc min upstream (kA) : value of the Ik1min short circuit at the point of connection. This value is used to calculate the ‘warm’ impedance of the Phase/Neutral loop.

Earthing arrangement : see previous.

dU initial (%) : The voltage drop from the transformer to the LV connection from which the study starts. This used to calculate the cumulative voltage drop downstream of the LV connection.

Division - Name - Date - Language 28

Circuit descriptionCapacitor

Power factor before compensation : value of the power factor calculated in the Power Sum (the Power Sum must be run to calculate a Capacitor bank)

Power of the Harmonic sources : In order to take into account the effect of harmonics on the capacitors, Ecodial needs the power of all the harmonic generating (non-linear) loads on the network. This value is used in conjunction with the transformer size to identify the type (Standard, H or SAH) of capacitor used by Ecodial.

Power (kvar) : Total power of the capacitor bank needed to attain the target power factor.

Type of compensation

Step : resolution of the automatic capacitor bank : ex 5x50kvar means the capacitor bank can go from 0 to 250kvar in steps of 50 kvar (controlled by the regulator)

Ib : current drawn by the capacitor bank (inclusive of possible harmonic currents and manufacturing tolerances)

Division - Name - Date - Language 29

Circuit descriptionCapacitor

Ih L, C,

Transformer(PT)

Capacitor(Q)

Harmonic current injection

Equivalent impedance of L-C circuit (resistances ignored)• Z= j.L./ (1-L.C.²)

Resonance when ²=(2f)²=LC (Zmax induces to Voltage max)• order of resonance :

• if order of resonance is close to harmonic current injection, filtering devices could be required.

Harmonic voltage created across the equivalent impedance of the transformer and capacitor, which causes circulating currents in the L-C loop, which can be a cause of nuisance tripping in transformer or capacitor protection devices.

c

T

Qucc

Pn

(%)

Circuit descriptionCapacitor

Circuit descriptionCapacitor

Vh

Division - Name - Date - Language 30

Circuit descriptionCircuit breaker (distribution)

Range : Product range from which the circuit breaker is to be chosen. If Ecodial cannot find a breaker in that range it will look for a breaker in a predefined range (function of the demand current)

Designation : name of circuit breaker Trip unit / curve : name of the trip unit or curve of the circuit breaker Nb of poles protected : polarity of the circuit breaker that is required. Earth leakage protection : if earth leakage protection (RCD) is required (by user,

or for a particular application, switch this characteristic to YES). Fire protection : this is a characteristic that will force an earth leakage device,

and set it to ensure that a leakage current will not be able to cause a fire (threshold < 300mA)

• Integrated with the protection device : certain RCDs are integrated (NS Vigi, …) and certain are separated (RH***). The user can choose the type of RCD required. By default, Ecodial looks for integrated RCDs, and then separated RCDs if unsuccessful.

• Class : (A / AC ) defines the sensitivity of the RCD to continuous and pulsed DC signals.

• Earth leakage protection device : name of the device ensuring the function of RCD.

Division - Name - Date - Language 31

• Sensitivity (mA) : pickup current of the RCD device

• Delay (ms) : time delay before disconnection under earth fault conditions I thermal setting (A) : Thermal setting of the circuit breaker. This value is set to

be greater or equal to the demand current, and is used to size the cable. I magnetic setting (A) : magnetic setting of the circuit breaker. This setting s

made to ensure protection against indirect contact in TN, and to ensure correct motor starting based on start-up currents.

Frame rating (A) : maximum rating of the circuit breaker frame Trip unit rating (A) : maximum setting of the trip unit. Ir : position of the thermal adjustment on the trip unit Io : position of the thermal adjustment on the trip unit Im/Isd : position of the magnetic adjustment on the trip unit Motor mechanism : breakers must be able to be fixed with a motor mechanism

Circuit descriptionCircuit breaker (distribution) (2)

Division - Name - Date - Language 32

Cascading requested :

• YES : circuit breaker is chosen using cascading with the upstream device (only the device directly upstream)

• NO : circuit breaker is chosen based on its stand-alone breaking capacity.

Discrimination requested :

• YES : circuit breakers that have better discrimination potential are selected instead of normal circuit breakers

Installation : Fixed breakers or withdrawable breakers

Circuit descriptionCircuit breaker (distribution) (3)

Division - Name - Date - Language 33

Circuit descriptionCircuit breaker (motor)

Range : see previous Designation : see previous Trip unit / curve : see previous Contactor : name of contactor to be used according to the co-ordination tables Thermal protection : name of thermal overload (if needed) according to co-

ordination tables. Soft starter : name of soft starter (if needed) according to co-ordination tables. Earth leakage protection : see previous. Fire protection :see previous with the added safety that the tripping time is

delayed by at least 60ms to ensure there is no nuisance tripping on start-up. Number of poles protected : always 3P3T, as Ecodial does not cover single

phase motors I thermal setting (A) : Thermal setting of the circuit breaker. This value is set to

be greater or equal to the demand current, and is used to size the cable. I magnetic setting (A) : magnetic setting of the circuit breaker. This setting s

made to ensure protection against indirect contact in TN, and to ensure correct motor starting based on start-up currents.

Division - Name - Date - Language 34

Frame rating (A) : maximum rating of the circuit breaker frame Trip unit rating (A) : maximum setting of the trip unit. Ir : position of the thermal adjustment on the trip unit Io : position of the thermal adjustment on the trip unit Im/Isd : position of the magnetic adjustment on the trip unit Motor mechanism : breakers must be able to be fixed with a motor mechanism Cascading requested :

• YES : circuit breaker is chosen using cascading with the upstream device (only the device directly upstream)

• NO : circuit breaker is chosen based on its stand-alone breaking capacity. Discrimination requested :

• YES : circuit breakers that have better discrimination potential are selected instead of normal circuit breakers

Installation : Fixed breakers or withdrawable breakers

Circuit descriptionCircuit breaker (motor) (2)

Division - Name - Date - Language 35

Circuit descriptionLoad

Number of identical circuits : instead of drawing multiple feeders having EXACTLY the same characteristic, just draw one !

Ib : demand current of the load (calculated from the power and polarity)

Circuit polarity : polarity of the load

Earthing arrangement : see previous

Power (kVA) : demand power (calculated from the current and the polarity)

Power factor : power factor of the load (.8 is default value)

Fixed / Mobile :

• Fixed : permanent connection from installation to load.

• Mobile : terminal load is fed through a power socket (special earth leakage conditions are then applicable : 30mA and Instanataneous protection is required)

Division - Name - Date - Language 36

Circuit descriptionMotor

Number of identical circuits : see previous Mechanical power (kW) : rated mechanical power of motor Type of starting : for Direct on Line or Soft Starting applications Motor efficiency : ratio between mechanical and electrical power (in kW) Ib (A) : full load current of motor Power factor : full load power factor of the motor Circuit polarity (always 3P) Earthing arrangement : see previous Power (kW) : demand power (calculated from the efficiency) Type of co-ordination : Type 1 or Type 2 Starting class : Standard / Long Start-up current : sets the magnetic setting of the breaker

Division - Name - Date - Language 37

Circuit descriptionLighting

Number of identical circuits Lighting Source : type of lamp Individual lamp power : Number of lamps per light : for each lighting point there can be several lamps Nb of lights (A) : total number of lamps on the Canalis lighting line Ib : full load current at the origin of the Canalis lighting distribution Ballast power : for lamps using ballasts (fluo tubes, …) Circuit polarity Earthing arrangement Power (kW) : total demand power (calculated) Power factor

Division - Name - Date - Language 38

Circuit descriptionVariable Speed Drive

Reference : name of VSD Nominal power of the VSD (kW) : characteristic of VSD Ib : current drawn by VSD (including harmonics) Absorbed power : total power drawn by VSD (motor power and heat loss) Torque (A) : starting torque : High or standard Form factor : ratio between total RMS and 50Hz signal (characteristic of VSD) Is permanent : output current Is max permanent : maximum permanent output current (characteristic of VSD) Is max 60s : maximum 60s output current (characteristic of VSD) Earthing arrangement Circuit polarity

Division - Name - Date - Language 39

Circuit descriptionCable

Length : length of the cable (Short circuit and voltage drop calculations) Installation method : code for the type of installation. Defines the standard

derating factors and the type of conductors used. Insulation : sets the insulation material of the cable (impedance calculation) Type of conductor : output from the Installation method, not an input ! Neutral loaded : source of derating on 3P+N networks Conductor arrangement : calculation of the linear reactance of the cable Type of PE : influences the type of cables selected by Ecodial Number of additional circuits : cable derating Number of layers : cable derating K user : additional cable derating (over and above the standards) Ambient temperature : cable derating Delta U max on circuit (%) : maximum voltage drop allowed on the cable Reference : name of cable

Division - Name - Date - Language 40

Circuit descriptionCable (2)

Nb Ph conductor : calculation result CSA Ph conductor : calculation result Nb N conductor : calculation result CSA N conductor : calculation result Nb PE conductor : calculation result CSA PE conductor : calculation result Phase metal : cable characteristic (input) Neutral metal : cable characteristic (input) PE metal : cable characteristic (input) Safety voltage : 50V or 25V

Division - Name - Date - Language 41

Ecodial and the earthing schemesImplementing protection against indirect contact

TT

• Earth fault current (leakage) calculated using the impedance of the source and earth electrodes, and the Phase-Earth conductor impedance

• Standards require an RCD device on the main incomer

the earth and source electrodes must not be interconnected ! TN

• Earth fault current calculated using the Phase-Earth conductor impedance

• Protection against indirect contact insured by setting the magnetic under the Earth fault current

• Trip units can be changed to ensure accurate magnetic threshold is used

• RCDs can be implemented IT (2nd fault)

• identical calculations as for the TN system

• Earth fault current is calculated assuming both fault occur at the same point. This ensures ‘worse case scenario’ as if the second fault appears further away, the real fault current on the 2nd fault would be greater than the calculated fault current corresponding to the 2nd fault location, and ensuring tripping by the 2nd fault location protection device.

Division - Name - Date - Language 42

Calculation rulesPhase CSA

a

m

Irth

KSth

11

Theoretical Phase CSA : calculated by a formula, where (IEC 60364-5-523-B):

• K is the total derating (temperature laying method, cables in parallel, …)

• Irth : is the thermal setting of the upstream breaker

• m and a : parameters defined by the laying method and the type of cable (metal, insulator) andthe number of loaded conductors in the circuit)

Choice of Phase conductor

• based on cable database supplied

• based on theoretical phase CSA and tolerance

• based on installation rules (ex TNC Smini = 10mm²)

• based on limits implied in the standards (ex Smini for multicore conductors on perforated tray = 25mm²)

• based on maximum phase CSA allowed

Voltage drop is calculated on this cable using demand current

• CSA could be increased

Division - Name - Date - Language 43

Calculation rulesNeutral CSA

Theoretical calculation made by Ecodial

• minimum theoretical CSA equal Ph or Ph/2

Warning : the Neutral as any cable should be sized according to the upstream protection setting (this is to ensure safety, not continuity !).

• With 4p4t CB, the neutral can be of the same CSA of the Phase

• With 4p3t 1/2N, the neutral can be half

• With 3p devices (Neutral not protected), there is an unknown, as there is no direct protection on the neutral…

Phase unbalance can lead (worse case scenario) to a phase current equal to neutral current, so Neutral should be at least equal to Phase

Triplen Harmonics (3rd, 9th, …) add up on the neutral. Therefore, if the phase is ONLY 3rd harmonics, neutral current = 3x phase current. In reality, the neutral current will usually be less than 1.7-1.8 times the phase current, example ;

• Irms (phase) = (I1, I3 (80%), I5(45%), I7(12%)) = 1.36x I1

• Irms (neutral) = 3x I3 = 2.4x I1 = 1.76 Irms (phase)

Division - Name - Date - Language 44

Calculation rulesNeutral CSA

Recommended actions :

• use half neutrals

– when there is a 4p3t N/2 circuit breaker protecting the circuit,

– and if there is no possibility of excessive phase unbalance and/or triplen harmonic loading on the circuit.

– Note : 3p3t are acceptable solutions, but 4p3t N/2 offer more safety under unexpected conditions

• use full neutrals

– when there is a 4p4t circuit breaker protecting the circuit

– and if there is a possibility of excessive phase unbalance, or limited triplen harmonic (max allowed = 33% triplen in the RMS)

– Note : 3p3t are acceptable solutions, but 4p4t offer more safety under unexpected conditions

• use double neutrals

– with 3p3t circuit breakers

– when there is a high risk of excessive triplen harmonic

Division - Name - Date - Language 45

Calculation rulesPE CSA

Automatic minimum PE :

• if Ph 16mm², PE = Ph x kph/kpe

• if Ph 35 mm², PE = 16mm² x kph/kpe

• if Ph > 35 mm², PE = Ph/2 x kph/kpe

• where kph and kpe function of the type of phase and earth conductor (metal, insulation, single/multi core, …)

• in TT, max PE = 35mm²

Theoretical minimum PE : the theoretical minimum PE cross section should only verify the I²t < k²S² condition, as no current is ever expected to flow on the PE (as it is an equipotential link). This condition usually implies small PE cross sections (+/- 4mm² in TN and 1mm² in TT). Using such small cables has two bad consequences :

• reducing Earth fault current (due to higher impedance), which could require the use of earth fault protection devices or lowering the magnetic thresholds to non efficient levels (motor starting and discrimination problems)

• creating a higher voltage differential on the PE due to natural leakage currents

Ecodial chooses automatically the CSA given above, but allows smaller cables to be selected by the user.

Division - Name - Date - Language 46

Network

• General characteristics

– TNC

– 400V

• Transformer

– 800kVA transformer

– Incomer cable length = 0

• Load

– 3P+N

– 100A

– Installation method EJ(1)

Calculate the network with :

• Load cable length =30m, 100m, 140m, 170m

• Info needed : Irm, If, Sph, Spe, DeltaU, CB, Sizing criteria

Tableau

B2

T1

C1

Circuit

Q1

Q3

Circuit

C3

L3

Calculation examplesthe effect of long cables

Division - Name - Date - Language 47

Calculation examplesthe effect of long cables

Cable sized on load current

Cable sized on voltage drop

Setting of trip unit to cater for low earth fault current

(protection against indirect contact)

• To ensure disconnection in sufficient time, Ecodial verifies that the earth fault current is higher than the magnetic setting of the breaker (including tolerance).

• Trip units can be changed to ensure this :

– C curve to B curve

– TM to STR

• cable size can be increased

• If no solution is found Ecodial interrupts the calculation requesting the user to manually place an RCD on the circuit breaker to ensure disconnection, and therefore protection against indirect contact.

Division - Name - Date - Language 48

Non-uniformly distributed load

• the Icc and DeltaU can be calculated at each tap-off point, or for worst case scenario (Icc at source)

• Calculation method to be used for distribution systems having loads that vary substantially in power and location.

Uniformly distributed load

• the Icc is calculated at the beginning of BTS.

• The voltage drop is estimated as a function of the number of tap-offs

• Calculation adapted for distribution systems having evenly distributed loads (in power and location)

Calculation examplesPrefabricated busbar trunking

Division - Name - Date - Language 49

Uniformly and Non-uniformly distributed load.

• 800kVA

• 100A tapoffs

• D=5,10,15,20,25

• Total length 30m

• Info needed :

– Icc, deltaU per tap/off.B2

Tableau

D4

CEP

Q8

Circuit

C8

L8 L9

C9

Circuit

Q9

Q7

Circuit

C7

L7L6

C6

Circuit

Q6

Q5

Circuit

C5

L5

Q3

Circuit

C3

Q1

Circuit

C1

T1

Calculation examplesPrefabricated busbar trunking (2)

Division - Name - Date - Language 50

Ku : usage coefficient

• applicable to a CIRCUIT

• % full load current when load is running

• example :

– motor +/- 80%

– Light 100%

Ks : diversity coefficient

• applicable to a DISTRIBUTION BOARD

• chance of all feeders drawing maximum load at any given time

• relative to the number of feeders on DB.

• See Electrical Installation Guide

Calculation parametersDiversity and usage coefficients

Division - Name - Date - Language 51

Lathe 1 5.5 kWLathe 2 5.5 kW

Distribution box Lathe 3 5.5 kWLathe 4 5.5 kW

Workshop A Drill 1 2.2 kWDrill 2 2.2 kW

3x socket outlet circuit (1P+N) 20 A each6x lighting lines (1P+N) 10x 100W each

Compressor 15 kWIncomer Workshop B 5x socket outlet circuit (1P+N) 20 A each

4x lighting lines (1P+N) 4x 100W each

Ventilation Fan 1 2.2 kWDistribution box Ventilation Fan 2 2.2 kW

Oven 1 15 kWWorkshop C Oven 2 15 kW

10x socket outlet circuit (1P+N) 20 A each2x lighting lines (1P+N) 2x 100W each

Calculation parametersDiversity and usage coefficients - example

Division - Name - Date - Language 52

Apartment blocks :

Consumers 4 9 14 19 24 29 34 39 49

Ks 1 .78 .63 .53 .49 .46 .44 .42 .41

Distribution Boards (IEC439) :

Circuits 3 5 9 10+

Ks .9 .8 .7 .6

Circuits (Ks or Ku ?):• Lighting 1• Heating, air conditioning 1• Socket outlet circuit .1 to .2 (higher in industry)• Lifts/hoists 1 / .75 / .6

Calculation parametersDiversity and usage coefficients - example

Division - Name - Date - Language 53

Problem with Ku and Ks

• Responsibility of the user

• Personal experience

• Knowledge of installation

• Database of existing installations

Advantage of Ku and Ks

• more cost effective installation

• not oversized

• Example

– total installed power : 144kVA

– maximum expected demand : 80 kVA

Calculation parametersDiversity and usage coefficients - example

Division - Name - Date - Language 54

The algorithms used by Ecodial

Formulas, constants

• impedance

• Icc, voltage drop, ..

Reference to standards

Calculation guidesSpecial help file

Division - Name - Date - Language 55

Different types of information : The front page Header and footer The device lists Equipment display Calculation notes The single-line diagram

Printing : Customise the setup Choice of language

Output

Division - Name - Date - Language 56

Open and save a project How to make a link between projects ? Choice of interface language The summary Different kinds of exports :

DXF RTF ECD

Special

Division - Name - Date - Language 57

Circuit breaker and busbar selection Discrimation and cascading tables Tripping curves

Guides and tools

Division - Name - Date - Language 58

Maximum number of circuits in a project : 70 Maximum number of copied circuits : 20 Maximum number of transformers : 4

Limitations

Division - Name - Date - Language 59

Normal and emergency sources

• Ecodial uses the worst case scenario to select equipment :

– max short circuit level from Transformers

– min earth fault current from Generators

Complex networks It is not always possible to draw the exact network. It can be necessary

to draw a simplified network, and define the final network based on these calculations.

Special applications