Bluebox Overview

16
7/15/2019 Bluebox Overview http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 1/16 www.swegon.com OVERVIEW Blue Box TM Top Energy Class Selection Highly energy efcent chillers and heat pumps or air conditioning

description

heat pumps details

Transcript of Bluebox Overview

Page 1: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 1/16

www.swegon.com

OVERVIEW

Blue Box

TM

Top Energy Class Selection

Highly energy efcent

chillers and heat pumps

or air conditioning

Page 2: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 2/162

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Dedicated to taking care o your needs

A Swegon companyBlue Box, a company in the Swegon Group, is one o the leadingmanuacturers o chillers and heat pumps. The actory has modernproduction acilities situated in Cantarana di Cona, near Venice inItaly.

In 2010 Blue Box became a member o the Swegon Group.Swegon is one o the leading suppliers o air handling units, water-borne and airborne climate systems, ow control plus products oracoustic and residential ventilation. With the addition o Blue Boxwe are now also a leading supplier o chillers and heat pumps.

Swegon has a unique position as a supplier o comprehensive solu-tions ocused on energy efcient systems that also oer the clientadded value – a better indoor climate, lower operating costs andlower installation costs.

Our primary goal is to solve all customer require-ments in all our areas o operation.

This approach allows us to deliver not just dierent

products or dierent needs, but truly comprehen-sive solutions throughout all our operations in thefelds o industrial, commercial and residential airconditioning and rerigeration.

In line with this philosophy, a dedicated team atBlue Box is constantly at work seeking the mostadvanced technical and design solutions to providethe most ftting answer to all types o cooling andheat pump requirements.

We were frst to design and build chillers with screwcompressors, an innovation that brought signifcantbenefts to the product in terms o reliability andnoise reduction. Packaged air conditioners, brazed-

plate exchangers on large capacity units, patentor derosting, chillers with R410A rerigerant andmodular, customizable chillers delivered in 7 daysare other innovations rom us.

The result o our eorts is a very wide and com-plete range o products and proessional equipmentat the highest quality level.

Constant drive towards innovation and progress arethe key eatures o the company’s corporate ethos.

We continue to research and develop towards themost advanced technical solutions with the mini-mum energy consumption and with highest care orthe environment.

within

Page 3: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 3/163

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Outstanding benefts – or you

Ever more stringentrequirements are madeon the power consump-tion o buildings. Mosto the Blue Box productsare available in energyconsumption class A or inother high efcency tech-nologies like ree cooling.

This means a minimumenergy consumption,saving both operationcosts and the environ-ment.

Top Class energy efciency

Our respect o the environment is based not only in developingenvironmently riendly products and using recycled materials,

but also in the manuacturing process.

• R407C, R410A and R134a rerigerant gas

• Minimum noise levels and vibrations

• Minimum energy consumption

• Using recycled and biodegradable products

• ISO 14001 certifcation

Sustainable development

Blue Box are included in the worldwide certifcation programmeo Eurovent. The Eurovent certifcate guarantees high standardsand that data rom our sotware also is valid in the reality.

Reliable perormance

Quality comes frstAll our manuacturing processes are under continuously moni-toring and are in strict accordance with the procedures required

by our ISO 9001 certifcation. All products must pass anadvanced running test beore delivery.

Leading the developmentWe do not ollow the market, we lead. Our Test Lab is state othe art or the testing o units and prototypes. The climate con-trolled acility, completely autonomous and independent, canaccommodate any unit and test its capacity and perormancerom -15°C to +50°C.

Blue Box participates in the ECC programme or Liquid Chilling Packages.Check ongoing validity o certifcate online: www.eurovent-certifcation.

com or using: www.certiash.com

Page 4: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 4/164

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Installation examples

Blue Box chillerEx.: EPSILON ECHOS A Air handling unit Cooling coil

Chiller

Blue Box reversible chillerEx.: TETRIS A

Air handling unit Change over coil

Reversible chiller

RadiatorsAir diusers

Heating coil Boiler ordistrict heating

The air handling unit provides ree cooling when temperature conditions allow.When more cooling is needed, the Blue Box chiller provides the cooling coil with chilled water.When heating is needed, a boiler or district heating provides the heating coil with warm water.

The air handling unit provides ree cooling when temperature conditions allow.During hot weather and when more cooling is needed, the Blue Box reversible chiller provides the change

over coil with chilled water.During cold weather and when heating is needed, the Blue Box reversible chiller provides the change over

coil and the radiator panels with warm water.

Page 5: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 5/165

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Installation examples

Blue Box heat pumpEx.: TAU MAX Air handling unit Heating coil

Heat pump

The air handling unit provides ree cooling when temperature conditions allow.When heating is needed, the Blue Box heat pump provides the heating coil with warm water.

Blue Box multiunctional unitEx.: OMICRON S EVO LT

Air handling unit Cooling coilHeating coil

Multiunctional unit

Climate beamsand

Comort modules

The air handling unit provides ree cooling when temperature conditions allow.Whenever cooling or heating is needed, the Blue Box multiunctional unit simultaneously provides the

cooling coil and the heating coil as well as the climate beams with chilled or warm water.

Page 6: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 6/166

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Air/Water chillers

Blue Box EPSILON ECHOS A

Blue Box ZETA ECHOS A (R)

Blue Box TETRIS A (R)

Air/Water heat pumps

Blue Box TAU (R)

Blue Box TAU MAX (R)

Blue Box GEYSER (R)

Blue Box GEYSER MAX (R)

Air/Water ree-cooling chillers

Blue Box ZETA ECHOS FC H

Blue Box TETRIS FC H

Air/Water multiunctional units

Blue Box OMICRON S EVO LT H

Water/Water chillers

Blue Box MU ECHOS A (R)

Water/Water heat pumps

Blue Box CORE (R)

Blue Box CORE MAX (R)

0 50 100 200 500 1000

Nominal cooling or heating capacity, kW

Capacity range o the Blue Box Top Energy Class Selection

Important inormation!All technical data specifed in this brochure is meant or use as an overview. Several o the units are avail-

able in a wide range o confgurations and with a wide range o accessories that can have an eect on thecapacities, dimensions, weights etc.

The energy class A model is specifed when available and the reversible model when applicable.

Stated cooling capacity and EER in this brochure is valid or an ambient air temperature o 35°C, andevaporator inlet/outlet water temperatures o 12/7°C, unless otherwise specifed.

Stated heating capacity and COP in this brochure is valid or an ambient air temperature o 7°C and evapo-rator inlet/outlet water temperatures o 40/45°C, unless otherwise specifed.

Total power input includes compressors and ans.

Catalogue documentation is available at www.swegon.com. Exact sizing is carried out by calculationsotware. Contact your nearest Swegon representative or more inormation and/or computer-generatedestimate.

Quickguide

6–33

45–145

123–523

33–227

44–135

114–684

7–32

46–60

11–37

32–64

6–46

6–28

34–87

Energy consumption class A

H Other high energy efciency technology 

Can produce hot water up to specifed temperature

(R) Reversible model is standard or optional 

Page 7: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 7/167

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Blue Box EPSILON ECHOS A

Air/Water chiller, cooling capacity 6–33 kW, energy class A 

• High perormance at any outdoor temperature.

• Limited space requirements

• Fast and easy installation and maintenance.

EPSILON ECHOS A 6 8 10 14 16 18 21 25 28 31 37

Nominal cooling capacity* kW 6,2 7,5 10,0 13,4 14,4 17,3 19,4 21,2 25,1 29,8 33,4

Total power input or cooling kW 2,1 2,5 3,2 4,1 4,6 5,2 5,9 6,5 7,3 9,0 9,8

EER 2,92 2,95 3,15 3,24 3,12 3,33 3,28 3,25 3,46 3,30 3,41Length mm 925 925 925 925 925 925 1105 1105 1105 1305 1305

Width mm 375 375 375 375 375 375 505 505 505 505 505

Height mm 700 700 700 1350 1350 1350 1385 1385 1385 1585 1585

Operating weight kg 88 93 102 135 151 166 212 233 233 367 367

Power supply 1x230V 3x400 V + N

Blue Box ZETA ECHOS AReversible Air/Water chiller, cooling capacity 44–135 kW, energy class A

• Wide range o capacities and confgurations or all installation requirements.

• Patented derosting system reduces power consumption.

• Two dierent sound confgurations.

ModelsHP: Reversible

Blue Box ZETA ECHOS A, reversible model 3.2 4.2 5.2 6.2 7.2 8.2 9.2 10.2 12.2

Nominal cooling capacity* kW 44,04 52,85 58,52 67,48 78,1 83,61 101,31 118,14 134,7

Total power input or cooling kW 14,17 17 18,22 21,64 22,8 25,87 32,55 36,63 43,28

EER 3,11 3,11 3,21 3,12 3,43 3,23 3,11 3,23 3,11

Nominal heating capacity* kW 51,8 59,54 66,44 74,37 89,32 99,23 114,4 135,52 151,16

Total power input or heating kW 13,78 15,98 17,78 20,38 23,77 27,07 33,5 38,1 42,1

COP 3,71 3,73 3,74 3,65 3,76 3,67 3,41 3,56 3,59

Length mm 1750 1750 2233 2233 3234 3234 3233 3233 3233

Width mm 1003 1003 1020 1020 1144 1144 1120 1120 1120

Height mm 1400 1400 1738 1738 1740 1740 1822 2382 2382

Operating weight kg 467 486 673 695 883 953 1018 1192 1250

Power supply 3x400 V + N

Quickguide

Air/Water chillers

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

Page 8: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 8/168

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Blue Box TETRIS AReversible Air/Water chiller, cooling capacity 114–684 kW, energy class A

Wide range o capacities and confgurations or all installation requirements.• Patented derosting system reduces power consumption.

ModelsHP: ReversibleA+: Very high energy efciencySLN: Super low noiseA SLN: Very high energy efciency and super low noise

Blue Box TETRIS A, reversible model 11.2 16.3 23.4 29.5 34.6 40.7 46.8 52.0 57.10 63.11 68.12

Nominal cooling capacity* kW 114 168 229 289 342 397 458 518 571 631 684

Total power input or cooling kW 35,8 53,9 72,2 90,4 108,2 126,1 144,4 162,6 180,4 198,6 216,4

EER 3,18 3,12 3,17 3,20 3,16 3,15 3,17 3,18 3,17 3,18 3,16Nominal heating capacity* kW 134 194 259 335 389 454 519 595 649 724 778

Total power input or heating kW 39,4 57,4 75,6 90,4 113,3 133,0 151,2 170,7 188,9 203,7 226,6

COP 3,40 3,39 3,43 3,71 3,44 3,41 3,43 3,48 3,43 3,56 3,44

Length mm 1158 2302 2302 3447 3447 4604 4604 5749 5749 6894 6894

Width mm 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302

Height mm 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397

Operating weight kg 848 998 1636 2004 2429 2556 2790 3569 3866 4120 4297

Power supply 3x400 V

Quickguide

Air/Water chillers

Blue Box TETRIS A+, reversible model 8.2 13.3 18.4 23.5 27.6 32.7 37.8 41.9 47.10 50.11 54.12

Nominal cooling capacity* kW 84 128 179 224 261 308 358 402 443 485 522

Total power input or cooling kW 25,8 38,8 51,8 64,8 77,7 90,5 103,6 116,6 129,4 142,5 155,3

EER 3,26 3,31 3,46 3,46 3,36 3,41 3,46 3,45 3,43 3,41 3,36

Nominal heating capacity* kW 100 150 206 256 301 357 413 460 511 558 602

Total power input or heating kW 29,2 42,7 56,4 69,9 84,5 99,1 112,8 127,3 140,9 154,4 169,1

COP 3,42 3,52 3,66 3,66 3,56 3,61 3,66 3,62 3,63 3,61 3,56

Length mm 1158 2302 2302 3447 3447 4604 4604 5749 5749 6894 6894

Width mm 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302

Height mm 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397

Operating weight kg 848 998 1636 2004 2429 2556 2790 3569 3866 4120 4297

Power supply 3x400 V

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

Page 9: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 9/169

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Quickguide

Blue Box TAU

Reversible Air/Water heat pump, heating capacity 7–32 kW, energy class A• Designed to be used with radiating panels, an ideal combination between comortable

temperatures and low energy consumption.

• High perormance at any outdoor temperature.

• Fast and easy installation and maintenance.

ModelsHWS: Multiunctional including hot water production up to 60°C

Blue Box TAU, reversible as standard 8 10 12 16 18 20 23 25 29 34

Nominal heating capacity* kW 6,9 8,8 10,9 14,7 15,9 18,8 21,5 23,4 26,9 31,5

Total power input or heating kW 2,1 2,7 3,1 4,4 4,8 5,3 6,2 6,8 8,0 9,2COP 3,23 3,20 3,46 3,37 3,34 3,57 3,48 3,45 3,38 3,43

Nominal cooling capacity* kW 6,2 7,5 9,6 12,7 14,2 16,7 19,0 20,8 24,0 29,5

Total power input or cooling kW 2,1 2,5 2,9 4,1 4,4 5,0 5,9 6,4 7,6 8,7

EER 2,88 2,99 3,32 3,13 3,20 3,36 3,22 3,24 3,15 3,39

Length mm 925 925 925 925 925 925 1105 1105 1305 1305

Width mm 375 375 375 375 375 375 505 505 505 505

Height mm 700 700 700 1350 1350 1350 1385 1385 1585 1585

Operating weight kg 88 93 102 135 151 166 212 233 358 367

Power supply 1x230V 3x400 V + N

Blue Box TAU MAXReversible Air/Water heat pump, heating capacity 46–60 kW, energy class A

• Designed to be used with radiating panels, an ideal combination between comortabletemperatures and low energy consumption.

• High perormance at any outdoor temperature.

• Fast and easy installation and maintenance.

• COP values among the highest in its category.

Hot water production up to 60°C

Blue Box TAU MAX, reversible as standard 50 60 70

Nominal heating capacity* kW 46,2 52,9 60,0

Total power input or heating kW 13,9 15,1 17,6

COP 3,32 3,50 3,40

Nominal cooling capacity* kW 46,2 52,9 60,0

Total power input or cooling kW 13,9 15,1 17,6

EER 3,32 3,50 3,40

Length mm 1078 1078 1078

Width mm 1078 1078 1078Height mm 2263 2263 2263

Operating weight kg 550 578 589

Power supply 3x400 V

Air/Water heat pumps

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

Page 10: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 10/1610

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Quickguide

Blue Box GEYSERReversible Air/Water heat pump, heating capacity 11–37 kW, energy class A

• Wide application use; Heating, hot water and cooling in various combinations.

• High perormance at any outdoor temperature.

• Fast and easy installation and maintenance.

• Hot water production up to 65°C

Blue Box GEYSER, reversible as standard 12M 16M 12 16 23 29 34

Nominal heating capacity* kW 11,2 14,7 10,6 14,7 20,9 28,5 37,1

Total power input or heating kW 3,1 4,1 2,9 3,9 5,8 8,1 10,5

COP 3,57 3,57 3,59 3,74 3,63 3,52 3,54

Nominal cooling capacity* kW 3,3 4,4 3,1 4,1 6,1 7,4 10,5

Total power input or cooling kW 3,01 3,17 3,32 3,24 3,35 3,34 3,28

EER 2,88 2,99 3,32 3,13 3,20 3,36 3,22

Length mm 925 925 925 925 1105 1305 1305

Width mm 375 375 375 375 505 505 505

Height mm 1350 1350 1350 1350 1385 1585 1585

Operating weight kg 139 170 139 170 221 397 397

Power supply 1x230V 3x400 V + N

Blue Box GEYSER MAXReversible Air/Water heat pump, heating capacity 32–64 kW, energy class A

• Wide application use; Heating, hot water and cooling in various combinations.

• High perormance at any outdoor temperature.

• Fast and easy installation and maintenance.

• Hot water production up to 65°C

Blue Box GEYSER MAX, reversible as standard 30 40 50 60

Nominal heating capacity* kW 31,8 43,3 55,0 64,3

Total power input or heating kW 8,8 12,2 15,5 17,7

COP 3,62 3,54 3,55 3,64

Nominal cooling capacity* kW 27,2 35,6 46,6 54,9

Total power input or cooling kW 8,5 12,6 16,2 18,9

EER 3,21 2,83 2,88 2,90

Length mm 1078 1078 1078 1078

Width mm 1078 1078 1078 1078Height mm 2263 2263 2263 2263

Operating weight kg 550 578 589 589

Power supply 3x400 V

Air/Water heat pumps

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

Page 11: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 11/1611

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Quickguide

Air/Water ree-cooling chillers

Blue Box ZETA ECHOS FCAir/Water chiller with integrated ree-cooling, cooling capacity 45–145 kW

• Wide range o capacities and confgurations or all installation requirements.• Patented ree-cooling system with one single an section only.• High EER and considerable energy saving when using ree-cooling.

ModelsLN: Low noise unit

Blue Box ZETA ECHOS FC, standard model 3.2 4.2 5.2 6.2 7.2 8.2 9.2 10.2 12.2 13.2

Nominal cooling capacity(ambient 30°C, water in/out 15/10°C, 30% glycol)

kW 45,1 50,7 58,0 68,2 75,3 89,7 102,6 113,9 132,3 144,4

Total power input or cooling kW 13,0 15,0 17,8 19,3 23,4 24,8 30,3 36,3 41,6 47,9

EER 3,48 3,37 3,27 3,54 3,23 3,62 3,39 3,14 3,18 3,01

Free-cooling nominal capacity(ambient 5°C, water 15/10°C, 30% glycol) kW 31,0 32,9 34,5 44,9 46,0 65,0 66,7 67,8 81,7 82,8

Length mm 2590 2590 2590 3250 3250 4200 4200 4200 4200 4200

Width mm 1337 1337 1337 1334 1334 1434 1434 1434 1434 1434

Height mm 1400 1400 1400 1740 1740 1740 1740 1740 1880 1880

Operating weight kg 921 927 959 1168 1182 1524 1538 1546 1650 1690

Power supply 3x400 V + N

Blue Box TETRIS FCAir/Water chiller with integrated ree-cooling, cooling capacity 123–523 kW

• Wide range o capacities and confgurations or all installation requirements.• Available in energy class A, but already the standard model is high energy efciency when

using ree-cooling.

ModelsA: Energy class A

A+: Very high energy efciencySLN: Super low noiseA SLN: Very high energy efciency and super low noise

Blue Box TETRIS FC, standard model(12 o 15 sizes specifed)

10.2 11.2 13.2 15.2 16.2 20.3 24.3 27.4 29.4 32.4 40.6 47.6

Nominal cooling capacity(ambient 30°C, water in/out 15/10°C, 30% glycol)

kW 123 134 143 159 182 223 262 299 322 349 453 523

Total power input or cooling kW 33,9 39,8 46,1 49,7 55,2 72,6 82,6 92,8 103,1 111,3 146,0 167,0

EER 3,63 3,36 3,10 3,20 3,29 3,07 3,17 3,22 3,12 3,13 3,10 3,13

Free-cooling nominal capacity(ambient 5°C, water in/out 15/10°C, 30% glycol)

kW 52,8 54,0 55,0 55,7 56,1 139,7 148,2 151,2 153,4 155,8 222,7 236,1

Length mm 2316 2316 2316 2316 2316 4604 4604 4604 4604 4604 5749 5749Width mm 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302 2302

Height mm 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397 2397

Operating weight kg 1337 1376 1416 1467 1476 2506 2640 2900 2860 3029 3794 4034

Power supply 3x400 V

Page 12: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 12/1612

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Quickguide

Air/Water multiunctional units

Blue Box OMICRON S EVO LTAir/Water multiunctional unit, cooling capacity 33–227 kW

• Wide range o capacities and combinations or cooling, heating and hot water.

• Cooling and heating simultaneously and independently rom each other.

• High energy efcient technology

• Hot water production up to 55°C

Blue Box OMICRON S EVO LT (12 o 16 sizes specifed) 3.2 4.2 5.2 6.2 7.2 9.2 11.2 12.4 14.4 16.4 19.4 21.4

Chiller mode

Nominal cooling capacity* kW 33 43 56 64 73 104 115 131 148 163 206 227

Total power input kW 11 14 18 22 25 36 40 45 53 59 72 79

EER 3,07 3,01 3,07 2,91 2,89 2,85 2,90 2,90 2,80 2,76 2,88 2,89

Heat pump mode

Nominal heating capacity* kW 38 50 61 71 85 112 126 143 159 188 228 245

Total power input kW 11 14 19 22 25 35 39 45 49 58 70 75

COP 3,38 3,52 3,28 3,27 3,44 3,21 3,27 3,21 3,23 3,26 3,25 3,25

Total recovery mode

Nominal cooling capacity* kW 33 43 55 64 73 100 114 130 149 162 202 226

EER 3,31 3,33 3,24 3,18 3,14 3,05 3,24 3,25 3,21 3,03 3,09 3,20

Nominal heating capacity* kW 42 56 72 84 97 133 149 170 195 215 267 296

COP 4,31 4,33 4,24 4,18 4,14 4,05 4,24 4,25 4,21 4,03 4,09 4,20

Length mm 2205 2205 2205 3210 3210 3210 3210 4204 4204 4204 4204 4204

Width mm 1740 1740 1740 1740 1740 1740 2380 2380 2380 2380 2380 2380

Height mm 1003 1003 1003 1104 1104 1104 1104 1104 1104 1104 1104 1104Operating weight kg 668 708 763 1073 1158 1272 1452 1873 2046 2220 2360 2403

Power supply 3x400 V + N 3x400 V

Water/Water chillers

Blue Box MU ECHOS AWater/water chiller, cooling capacity 6–46 kW, energy class A

• Very high EER• Low noise level•

Compact and space-saving design.• Fast and easy installation and maintenance.

ModelsHP: Reversible

MU ECHOS A, reversible model 6 8 11 16 19 22 24 28 32 35 42 48

Nominal cooling capacity (water in/out 12/7°C,cooling agent in/out 30/35°C, 30% glycol)

kW 5,9 8,3 10,4 15,5 17,9 20,9 23,4 26,6 32,4 35,1 41,7 46,4

Total power input kW 1,4 1,8 2,3 3,4 4,1 4,9 5,4 6,3 7,1 7,8 8,8 10,0

EER 4,20 4,57 4,47 4,52 4,33 4,30 4,38 4,25 4,60 4,52 4,76 4,66

Nominal heating capacity (water in/out 40/45°C,cooling agent in/out 0/-3°C, 30% glycol)

kW 5,4 7,5 9,2 13,0 15,7 18,3 21,2 24,8 27,8 30,4 34,5 38,6

Total power input kW 1,8 2,6 3,2 4,3 5,2 6,1 6,6 7,7 8,6 9,6 10,5 12,1

COP 3,04 2,90 2,93 3,01 3,01 3,00 3,21 3,23 3,23 3,18 3,29 3,20Length mm 456 456 456 456 507 507 861 861 862 862 862 862

Width mm 398 398 498 537 537 537 543 543 537 537 537 537

Height mm 671 671 671 671 671 671 671 671 1020 1020 1020 1020

Operating weight kg 158 164 169 102 106 112 164 168 200 203 204 252

Power supply 1x230 V 3x400 V + N

*) Water without glycol. With glycol solution the capacity is reduced approx. 10%.

Page 13: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 13/1613

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Water/Water heat pumps

Blue Box COREWater/water heat pump, heating capacity 6–28 kW, energy class A

• Wide range o capacities and combinations or heating, cooling and hot water,

• Ideal or use with geothermal probes,

ModelsHP: ReversibleHWS: Multiunctional including hot water production up to 60°CM: Monophase 1x230 V available or sizes 5-18,

Blue Box CORE, reversible model 7 9 10 11 14 18 19 22 25 27 32 37

Nominal heating capacity (water in/out 40/45°C,cooling agent in/out 0/-3°C, 30% glycol)

kW 5,8 6,9 7,5 8,7 10,1 13,1 14,7 17,1 19,5 21,9 25,1 28,4

Total power input kW 1,8 2,2 2,3 2,6 3,0 3,8 4,4 4,9 5,6 6,0 6,8 7,9

COP 3,23 3,19 3,26 3,33 3,38 3,45 3,36 3,48 3,50 3,68 3,68 3,61

Nominal cooling capacity (water in/out 12/7°C,cooling agent in/out 30/35°C, 30% glycol)

kW 6,0 7,2 8,0 9,0 10,6 13,5 15,1 17,2 19,5 22,0 25,1 30,0

Total power input kW 1,4 1,7 1,8 2,1 2,4 3,0 3,5 4,0 4,5 4,9 5,6 6,3

EER 4,29 4,28 4,44 4,38 4,50 4,56 4,36 4,29 4,32 4,47 4,49 4,7

Length mm 640 640 640 640 640 640 640 640 640 890 890 890

Width mm 640 640 640 640 640 640 640 640 640 760 760 760

Height mm 1235 1235 1235 1235 1235 1235 1235 1235 1235 1235 1235 1235

Operating weight kg 179 - 230 251 - 259

Power supply 3x400 V + N

Quickguide

Blue Box CORE MAXWater/water heat pump, heating capacity 34–87 kW, energy class A

• Wide range o capacities and combinations or heating, cooling and hot water.

• Ideal or use with geothermal probes.

ModelsHP: Reversible

HWS: Multiunctional including hot water production up to 60°C

Blue Box CORE MAX, reversible model 43 50 55 63 74 84 95 111

Nominal heating capacity (water in/out 40/45°C,cooling agent in/out 0/-3°C, 30% glycol)

kW 34,1 39,1 43,3 49,8 58,3 63,7 72,8 87,1

Total power input kW 9,8 11,1 12,0 13,7 16,0 18,0 19,8 23,2

COP 3,48 3,53 3,59 3,63 3,64 3,54 3,68 3,75

Nominal cooling capacity (water in/out 12/7°C,cooling agent in/out 30/35°C, 30% glycol)

kW 32,6 37,6 41,8 48,4 57,1 65,4 72,8 84,5

Total power input kW 8,0 9,0 9,9 11,3 12,9 14,6 16,3 19,8

EER 4,06 4,16 4,20 4,29 4,42 4,48 4,46 4,27

Length mm 1200 1200 1200 1200 1200 1200 1200 1200Width mm 1040 1040 1040 1040 1040 1040 1040 1040

Height mm 1305 1305 1305 1305 1305 1305 1305 1305

Operating weight kg 280 - 410

Power supply 3x400 V + N

Page 14: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 14/1614

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Quickguide

Dry cooler

Blue Box RDCDry cooler or Water/Water units

(or cooling agent only)• Rejected heat capacity 10–120 kW

Other Blue Box products

Blue Box DATATECHPrecision air conditioner or technologicalenvironmentsCooling capacity 6–170 kWDirect expansion or Water/Air

Blue Box KAPPA V EVO AReversible Air/Water chillerCooling capacity 249–1566 kW

Blue Box KAPPA V EVO FCAir/Water chiller with integrated ree-coolingCooling capacity 327–1186 kW

Blue Box OMICRON V EVO LTAir/Water multiunctional unitCooling capacity 236–672 kW

Blue Box SIGMA 2002Reversible Water/Water chillerCooling capacity 42–297 kW

Blue Box OMEGA V ECHOS AReversible Water/Water chillerCooling capacity 185–1555 kW

Beside the selections shown in this brochure, we can oer awide range o other chillers and heat pumps, such as units ordata rooms and or applications with large cooling require-

ments.Some examples:

Page 15: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 15/1615

Blue Box Top Energy Class Selection

The company reserves the right to make design changes without prior notice.

Reerences

Munich Airport, Germany

Stade de France, Paris, France

ONU Centre, Vienna, Austria

Porsche Centre, Reading, Great Britain

Scrovegni Chapel, Padua, Italy

Det Norske Veritas, Stavanger, Norway

Page 16: Bluebox Overview

7/15/2019 Bluebox Overview

http://slidepdf.com/reader/full/bluebox-overview-56328066478f9 16/16

   E   N  -   B   l  u  e   B  o  x  o  v  e  r  v   i  e  w    2

   0   1   1  -   0   1  -   2   5