AE09400
-
Upload
unjourdeprintemps -
Category
Documents
-
view
221 -
download
0
Transcript of AE09400
-
7/29/2019 AE09400
1/8
BUL265
Field Evaluation of Microirrigation Water Application
Uniformity 1
A.G. Smajstrla, B.J. Boman, D.Z. Haman, D.J. Pitts, and F.S. Zazueta2
1. This document is BUL265, one o a series o the Agricultural and Biological Engineering Department, Florida Cooperative Extension Service, Institute
o Food and Agricultural Sciences, University o Florida. Original publication date March 1990. Revised February 1997. Reviewed January 2012. Visit the
EDIS website at http://edis.ias.u.edu.
2. A.G. Smajstrla, Water Management Specialist, Agricultural and Biological Engineering Department; D.J. Boman, Citrus Irrigation Specialist, IRREC Ft.
Pierce, FL; D.Z. Haman, Water Management Specialist, Agricultural and Biological Engineering Department; D.J. Pitts, Water Management Specialist,
SWFREC Immokalee, FL; and F.S. Zazueta, Water Management Specialist, Agricultural and Biological Engineering Department; Cooperative Extension
Service, Institute o Food and Agricultural Sciences, University o Florida, Gainesville, 32611.
The Institute o Food and Agricultural Sciences (IFAS) is an Equal Opportunity Institution authorized to provide research, educational inormation and other services only toindividuals and institutions that unction with non-discrimination with respect to race, creed, color, religion, age, disability, sex, sexual orientation, marital status, national
origin, political opinions or aliations. U.S. Department o Agriculture, Cooperative Extension Service, University o Florida, IFAS, Florida A&M University CooperativeExtension Program, and Boards o County Commissioners Cooperating. Millie Ferrer-Chancy, Interim Dean
A microirrigation system has the potential to be a very
ecient way to irrigate. However, to be eciently applied,
irrigation water must be uniormly applied. Tat is, with
each irrigation, approximately the same amount o water
must be applied to all o the plants irrigated. I irrigation is
not uniormly applied, some areas will get too much water
and others will get too little. As a result, plant growth willalso be nonuniorm, and water will be wasted where too
much is applied. Uniormity is especially important when
the irrigation system is used to apply chemicals along with
the irrigation water because the chemicals will only be
applied as uniormly as the irrigation water.
Te uniormity o water application rom a microirrigation
system is aected both by the water pressure distribution
in the pipe network and by the hydraulic properties o the
emitters used. Te emitter hydraulic properties include the
eects o emitter design, water quality, water temperature,and other actors on emitter ow rate. Factors such as
emitter plugging and wear o emitter components will aect
water distribution as emitters age.
Tis publication presents procedures to separately evaluate
the eects o pressure variations in the pipe network
(hydraulic uniormity) and variations due to the emitter
characteristics (emitter perormance variation) on unior-
mity o water application. Knowing both o these actors
will help an irrigation system manager identiy the causes o
low application uniormities and the corrections that may
be required to improve the uniormity o water application.
Tese procedures should be used on newly installed
microirrigation systems to veriy that they were properly
designed and installed, and to provide a reerence or utureevaluations. Also, evaluations should be done each year
to determine the eects o emitter plugging or changes in
other components on system perormance. More requent
evaluations may be required to diagnose and treat emitter
plugging problems.
Flow Rate Variation and
UniformityTe uniormity o water application can be calculated rom
the statistical distribution o emitter ow rates that aremeasured in the eld.
where US
= statistical uniormity o the emitter discharge
rates, and Vqs
= statistical coecient o variation o emitter
discharge rates.
In Equation (1) , the coecient o variation is the standard
statistical denition o the sample standard deviation
divided by the mean. Tus, when emitter ow rates are
http://edis.ifas.ufl.edu/http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://edis.ifas.ufl.edu/ -
7/29/2019 AE09400
2/8
2
measured in the eld, Vqs
includes the eects o variability
in emitter ow rate rom all causes, including both water
pressure distributions and emitter hydraulic properties,
emitter plugging.
From Equation (1), when the variation in emitter ow rates
increases, the uniormity o water application decreases.
able 1 lists ve microirrigation uniormity classications,
ranging rom excellent to unacceptable, recognized by the
American Society o Agricultural Engineers (ASAE, 1996a;
1996b).
Emitter Hydraulic CharacteristicsEmitter Flow EquationMicroirrigation emitter ow rates have dierent
responses to pressure variations. Te response o a specic
emitter depends on its design and construction. Te
relationship between emitter operating pressure and ow
rate is given by:
where
q= emitter ow rate (gal/hr),
Kd= emitter discharge coecient,
P= operating pressure (psi), and
x= emitter discharge exponent.
Te coecient and exponent or this equation will
normally be given by the emitter manuacturer or rom an
independent testing laboratory such as the Caliornia State
University Center or Irrigation echnology (CI).
Te emitter discharge exponent, x, is a measure o the sensi-
tivity o the emitter ow rate to changes in pressure. Tis
exponent is dimensionless and it is independent o the units
used to measure ow rate and pressure. Values o x rangerom 0 to 1, with values around 0.5 being very common or
turbulent ow emitters. Low values o x (below 0.5) indicate
emitters that are relatively insensitive to changes in pressure
(pressure compensating emitters), while large values o x
indicate emitters that have larger changes in ow rate as
pressures change (laminar ow emitters).
Emitter Manufacturing VariationIn addition to ow variations due to pressure, variations
between emitters o the same type also occur due to
manuacturing variations in the tiny plastic components.
Because their orice diameters are very small, microir-
rigation emitters are easily plugged or partially plugged
rom particulate matter, chemical precipitates, and organic
growths. For these reasons, water application uniormity
may be greatly aected by the emitter perormance.
Te manuacturing coecient o variation (Vm
) is dened
as the statistical coecient o variation (standard deviation
divided by the mean discharge rate) in emitter discharge
rates when new emitters o the same type are operated at
identical pressures and water temperatures. Under these
identical operating conditions, dierences in ow rates
observed are assumed to be due to variations in emitter
components. able 2 classies point source (drip emitters
and microsprinkiers) and line source (drip tubing) emitters
based on manuacturing variation.
Because manuacturing variation reduces uniormity o
water application, choose emitters with low values o Vm
. When comparing emitters with similar ow properties
(i.e., similar values o Kd
and x in Equation 1 ), the highest
uniormity will be obtained by selecting the emitter with
the smallest manuacturing variation.
Pressure Variation and UniformityWhen water ows through a pipe network, pressure losses
occur because o riction losses in the pipes and ttings.Pressure changes also occur as water ows uphill (pressure
loss) or downhill (pressure gain) in a pipe network. I a
microirrigation system is poorly designed or improperly
installed, pressure losses may be excessive because compo-
nents are too small or design ow rates or slopes are too
steep or the components selected. For these reasons, water
application uniormity may be greatly aected by the design
o the pipe network.
Hydraulic uniormity reers to the eects o pressure
variations on the uniormity o water application rom
a microirrigation system. Hydraulic uniormity, Ush
, isdened similar to water application uniormity in Equation
(1) , except that the emitter discharge exponent, x, must
also be considered. Tis exponent shows the relationship
between emitter operating pressure and ow rate. Because
x is dierent or dierent types o emitters, the allowable
pressure variation is also dierent or each emitter type.
Figure 1.
http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_1_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_2_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E1http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_2_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_1_DOCUMENT_AE094 -
7/29/2019 AE09400
3/8
3
where
Ush
= hydraulic uniormity based on pressure
distributions,
x= emitter discharge exponent, and
Vh= hydraulic variation, which is the statistical coecient
o variation o pressures.
A low value o Ush
is most ofen due to improper design.
However, improper installation o components or the
installation o the wrong components can also reduce Ush
. Low values o Ush
may be due to pipe sizes that are too
small, laterals that are too long, laterals that are incorrectly
oriented with respect to slope, improper emitter selec-
tion, or other causes. All o these items must be properly
designed and installed in order to obtain an acceptable
uniormity o water application.
Uniformity TestsTis publication presents procedures or making threeseparate tests that are useul to evaluate the perormance
o a microirrigation system: (1) overall water application
uniormity, (2) hydraulic uniormity or pressure variation,
and (3) emitter perormance variation. Tese tests should
be perormed in the order indicated because, i the overall
water application uniormity is high, there is no need to
perorm urther tests. I the water application uniormity
is low, then hydraulic uniormity tests should be conducted
in order to determine the cause o the low uniormity. Te
hydraulic uniormity test will indicate whether the cause o
the low water application uniormity is excessive pressure
variation in the system or emitter perormance problems
such as plugging.
o simpliy computations, the statistical uniormity
nomograph shown in Figure 1 was developed. Tis graph is
used to determine both water application uniormity rom
emitter ow rate data and hydraulic variation rom pressure
distribution data.
1. Water Application Uniformity TestTe water application uniormity is a measure o how
evenly the volumes o water are applied rom each emitter.
Tis uniormity can be determined by measuring emitter
ow rates or the times required to ll a container o known
volume. I some emitters tested are completely plugged,
then ow rates must be measured since a container will
never be lled. o measure emitter ow rates, use a gradu-
ated cylinder to measure the volume collected or a given
time, such as one or two minutes. A stop watch or wrist
watch with a second hand can be used to measure times.
o accurately determine uniormity, measurements shouldbe made at a minimum o 18 points located throughout
each irrigated zone. More may be required or greater
accuracy. Computations will be simplied i the number o
points measured is a multiple o 6. Te statistical coecient
o variation is then calculated rom these data points.
Care should be taken to distribute the measurement points
throughout the irrigated zone. Some points should be
located near the inlet, some near the center, and some at the
distant end. Also, some should be located at points o high
elevation and some at points o low elevation. However, the
specic emitters to be tested should be randomly selected ateach location. Do not visually inspect the emitters to select
those with certain ow characteristics
beore making measurements. In act, to avoid being
inuenced by the appearance o an emitter as it operates,
emitters could be selected and agged beore the irrigation
system is turned on. Te water application uniormity can
be read rom Figure 1. Te ollowing 6 steps are required:
1. Calculate 1/6 o the number o data points measured.
Tat is, divide the number o data points by 6. For
example, i 18 points were measured, this number will be
3.
2. Look at the set o data measured to locate and then add
the lowest 1/6 o the ow rates (or times or volumes)
measured. For 18 data points this will be the sum o the 3
lowest ow rates, times or volumes measured.
Figure 2.
http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1 -
7/29/2019 AE09400
4/8
4
3. Look at the data set again to locate and then add the
highest 1/6 o the ow rates, times, or volumes measured.
For 18 data points this will be the sum o the 3 highest
values.
4. Locate the sum o the high ow rates, times, or volumes
on the vertical axis in Figure 1. Draw a horizontal line
across the graph rom that point. I this sum does not t
on the scale, or i the value is very small so that the scale
is dicult to read, the sums calculated in Steps 2 and 3
can both be multiplied or divided by a common actor.
Tis can be done because their absolute values are not
important, but only the relative dierences between the
high and low values are critical.
5. Locate the sum o the low ow rates, times or volumes
on the horizontal axis in Figure 1. Draw a vertical line up
the graph rom that point. Again, i necessary, modiy the
values rom Steps 2 and 3 as discussed in Step 4. However,
i changes are made, be sure to change the sums o both
the lowest and highest values by multiplying or dividingboth by the same actor.
6. Read the water application uniormity at the intersection
o the two lines drawn.
As an example o the use o Figure 1 , assume that water
rom 18 emitters was collected at random locations
throughout an irrigated zone. Assume that the method used
was to record the times required to ll a small container,
and that the times were recorded in seconds. An example
set o data is shown in able 3.
From the above 6-step procedure:
Step 1.1/6 o l8 data points = 3
Step 2.62 + 64 + 64 = l90 sec (lowest 3 values)
Step 3.90 + 88 + 86 = 264 sec (highest 3 values)
Step 4.locate 264 sec on the vertical axis in Figure l and
draw a horizontal line across the graph rom that point.
Step 5.Locate 190 sec on the horizontal axis in Figure 1 and
draw a vertical line rom that point.Step 6.Te intersection o these two lines occurs between
the 80% and 90% lines. Tis indicates a Very Good water
application uniormity coecient o about 88%.
From this analysis, it can be concluded that the irrigation
system represented by the ow rate data in able 3 was
designed and constructed to achieve a high degree o
uniormity o water application throughout the zone that
was analyzed. Also, because o the high water application
uniormity, it can be concluded that the variability among
emitters used in this irrigation system is low. No signicant
emitter plugging is indicated.
2. Hydraulic Uniformity (Pressure
Variation)TestTe hydraulic uniormity o a microirrigation system is
estimated by measuring pressures at points distributedthroughout each irrigated zone. Measure pressures to the
nearest pound per square inch (psi). Although it is not
necessary to measure pressures at the same emitters where
ows were measured, it is normally convenient to do so
while ow rates are being measured.
Pressures can easily be measured using a portable pressure
gauge connected with a exible tube. Gauges are com-
mercially available with a needle on a exible tube or direct
insertion into the lateral pipe. Alternatively, some emitters
are constructed so that a exible tube can be slipped overthe emitter, allowing the pressure to be measured with the
emitter in place.
Some microsprinkler emitters are connected to the lateral
using small diameter exible tubing with a barbed insertion
tting. Because o pressure losses in these connecting tubes,
pressure should be measured at the end o the tube near the
emitter while the emitter is operating. Tis can be done by
installing a small barbed tee in the connecting tube.
Te pressure distribution data are analyzed in the same way
that the previously discussed ow rate data were analyzed.Te only dierence is that the hydraulic coecient o varia-
tion due to pressure, Vh, is read rom Figure 1 rather than
directly reading the statistical uniormity. Ten, in Step 7,
the hydraulic uniormity must be calculated rom Vh
and
the emitter discharge exponent, x, as shown in Equation
(3). Te hydraulic uniormity can be determined using the
ollowing 7-step procedure:
1.Calculate 1/6 o the number o data points measured. I
18 pressures were measured, this number is 3.
2.Look at the data measured to locate and then add
the lowest 1/6 o the pressures measured. For 18
pressure measurements, this is the sum o the 3
lowest pressures.
3.Look at the data again to locate and then add the
http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1 -
7/29/2019 AE09400
5/8
5
highest 1/6 o the pressures measured. For 18
pressure measurements, this is the sum o the 3
highest pressures.
4.Locate the sum o the high pressures on the vertical axis
in Figure 1 . Draw a horizontal line across the graph rom
that point. I this sum does not t on the scale, or i the
value is very small so that the scale is dicult to read, thesums in Steps 2 and 3 can both be multiplied or divided by
a common actor.
5.Locate the sum o the low pressures on the horizontal axis
in Figure 1 . Draw a vertical line up the graph rom that
point. Again, i necessary, modiy the values rom Steps 2
and 3 as discussed in Step 4. However, i modications are
made, be sure to modiy the sums o both the lowest and
highest values by multiplying or dividing both by the same
actor.
6.Read the hydraulic variation, V h , at the intersection othe two lines drawn.
7.Calculate the hydraulic uniormity, Ush
, rom Equation
(3).
As an example o the use o Figure 1 to calculate the
hydraulic uniormity, consider the pressure data set in able
3. Assume that the 18 pressures shown in able 3 were read
at random locations throughout the irrigated zone. It will
normally be easiest to measure these pressures at the same
time and location while the ow rates were being measured,
but this is not necessary. For example, they could bemeasured later at 18 dierent locations, afer the ow rate
data indicated that there was a problem with water applica-
tion uniormity, and it is now important to determine the
cause o that low uniormity.
For this analysis, the emitter discharge exponent, x, must
be obtained rom the emitter manuacturer or the emitter
being used. For this example assume that a typical turbulent
ow emitter was used with x = 0.5. Ten, ollowing the
above 7-step procedure:
Step 1. 1/6 o 18 = 3
Step 2. 21 + 21 + 22 = 64 psi (1owest 3 values)
Step 3. 28 + 27 + 27 = 82 psi (highest 3 values)
Step 4. Because the data rom Steps 2 and 3 would be
located in the lower lef-hand corner o Figure 1, and the
graph would be dicult to read, multiply both values by 5
to expand the scale:
(5)(82 psi) = 410 psi
(5)(64 psi) = 320 psi.
Ten locate 410 psi on the vertical axis in Figure 1 and draw
a horizontal line across the graph rom that point
Step 5. Locate 320 psi on the horizontal axis in Figure 1 and
draw a vertical line rom that point.
Step 6. Te two lines drawn intersect at Vh = 0.1, indicating
a hydraulic uniormity that alls between the Very Good
and Excellent categories.
Step 7. From Equation (3) , calculate Ush
:
Ush
= 100% (1.0 - (0.5)(0.1)) = 95%
From Figure 1, this hydraulic uniormity would be classied
in the Excellent category.
From the above analysis, it can be concluded that the
irrigation system represented by the pressure data in able3 was designed and constructed to achieve a high degree
o uniormity in pressures throughout the zone that was
analyzed. Tus, i a low water application uniormity was
previously indicated, the cause o that low uniormity is
not poor hydraulic uniormity. Rather, the cause is emitter
perormance, probably emitter plugging.
3. Emitter Performance Variation
EvaluationEmitter perormance variation, V
p, reers to non-unior-
mity in water application that is caused by the emitters. I
the emitter perormance variation is high, this is normally
due to emitter plugging or to manuacturing variation
among emitters. It may also be due to other actors which
aect emitter ow rates, such as temperature.
Emitter perormance variation can be evaluated by
measuring emitter ow rates at known pressures. Tis can
be done by removing the emitters and testing them in a
laboratory. Alternatively, both pressures and ow rates can
be measured at individual emitters, but then ow rates must
be corrected to a common pressure by using the manuac-
turers data or that emitter. Neither o these procedures are
Figure 4.
http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E3http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_3_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094E3http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F1 -
7/29/2019 AE09400
6/8
6
recommended because o the amount o labor involved or
each.
Te nomograph in Figure 2 simplies the procedure or
determining the emitter perormance variation rom the
hydraulic and water application uniormities. Te emitter
perormance variation can be estimated in the ollowing
three steps:
1.Locate the previously calculated hydraulic (pressure)
uniormity coecient, USh
, on the upper bar o the
nomograph.
2.Locate the previously calculated water application unior-
mity coecient, Us, on the center bar o the nomograph.
3.Draw a straight line om the measured hydraulic unior-
mity (upper bar), through the water application uniormity
(center bar), and extend it down to the lower bar. Read the
emitter perormance variation Vp
on the lower bar.
As an example, assume that the uniormity o a new
microirrigation system was measured immediately afer
installation, and that the hydraulic uniormity determined
rom pressure measurements was 95%. Also, assume that
the statistical uniormity o water application rom emitter
ow rate measurements was 93%. From Figure 2, a straight
line drawn through Ush
=95% and US
=93% intersects the
lower bar at an emitter perormance variation o 5%. Tis
value would be expected to be approximately the coecient
o manuacturing variation or the emitter because this
system is newly installed, and it is assumed that no emitter
plugging has yet occurred. For this example, both the
hydraulic and water application uniormities are above 90%
and would be classied as excellent, indicating that the
system was well-designed and properly installed.
As a second example, assume that the same irrigation
system was again evaluated afer operating or 6 months,
and that the hydraulic uniormity was again ound to
be 95%, but the water application uniormity was now
88%. From Figure 2, a straight line drawn through these
two pomts shows that the emitter perormance variation
increased to 11%. Tese results demonstrate that the cause
o the lower water application uniormity measured is a
change in emitter perormance, probably emitter plugging.
Tis suggests that chemical water treatment or ushing o
lines may be required to restore the system to its original
high uniormity.
Because the Ush
remained unchanged, this demonstrates
that a change in the hydraulics o the system was not the
cause o the lower application uniormity measured. Tus,these tests not only indicate whether a problem with water
application uniormity has occurred, but also whether the
changes were due to changes in the system hydraulics or
changes in the emitter perormance.
Accuracy of EstimatesTe estimates o uniormities and perormance variations
made using the methods presented in this publication are
based on statistical samples o pressures and ow rates
measured in the eld. As with any statistical estimate, the
results will not be completely accurate unless all emittersare sampled. Tus, it is necessary to consider condence
limits on the estimates made when only a ew emitters are
sampled. Tis is a method o estimating how accurate the
measured result is, and whether it is necessary to make
additional measurements to improve the accuracy. able 4
gives condence limits on the uniormities or variabilities
measured.
From able 4, the condence limits are smaller when the
uniormity is greater. For example, or 18 samples, the
condence limit is 3.5% i the uniormity measured was
90%, while the condence limit is 16.2% i the uniormity
measured was 60%. Tis means that the actual uniormity
would be expected to be in the range o 86.5% to 93.5%
(90% 3.5%) i the estimated value was 90%, while it could
be expected to range as much as 43.8% to 76.2% (60%
16.2%) i the estimated value was
60%. Te smaller condence limits occur at the higher
uniormities because it is not likely that samples would be
randomly selected that would indicate a high uniormity i
the uniormity was actually low.
From able 4, the condence limits decrease as more
samples are taken. Tis indicates that we are more condent
in the results i more measurements are made. In act, the
condence limits decrease by a actor o two when the
number o samples is multiplied by our. I the uniormity
estimates are low when only 18 samples are
Figure 3.
http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F2http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_4_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/TABLE_4_DOCUMENT_AE094http://localhost/var/www/apps/conversion/tmp/scratch_5/IMAGE_AE_AE094F2 -
7/29/2019 AE09400
7/8
7
taken, then more samples must be taken in order to
improve the condence in the estimate. Tus, able 4 can
be used to determine the number o samples that must be
taken in order to estimate the actual uniormity with the
desired accuracy.
SummaryA method was presented to evaluate microirrigation
uniormity o water application under eld conditions.As a minimum, emitter ow rate data are required or
these evaluations. Pressure data are also needed in order
to determine whether the cause o any low uniormity
observed is system hydraulic (pressure) problems or
emitter characteristics, including plugging. I both tests are
made, the results not only indicate whether a problem with
water application uniormity exists, but also demonstrate
whether the problem is due to system hydraulics or to
emitter perormance, so that appropriate corrective actions
can be taken.
ReferencesASAE. 1996a. Field evaluation o microirrigation systems.
EP405.1. ASAE Standards. Amer. Soc. Agric. Engr., St.
Joseph, MI. Pp. 756-759.
ASAE. 1996b. Design and installation o microirrigation
systems. EP409. ASAE Standards. Amer. Soc. Agric. Engr.
St. Joseph, MI. Pp.792-797.
-
7/29/2019 AE09400
8/8
8
Table 1. Microirrigation system uniormity classifcations based
on emitter discharge rates1.
Classifcation Uniormity, U (%)
Excellent above 90%
Good 90%-80%
Fair 80%-70%
Poor 70% -60%
Unacceptable below 60%lAdopted rom ASAE (1996a).
Table 2. Classifcations o manuacturers coecient o
variation, Vm
, or emitters2.
Emitter Type Vm
Range (%) Classifcation
below 5% Excellent
Point Source 5% to 7% Average
(drip emitters 7% to 11% Marginal
and 11% to 15% Poor
microsprinklers) above 15% Unacceptable
Line Source below 10% Good
(drip tubes) 10% to 20% Average
above 20% Unacceptable
2Adopted rom ASAE (1996b).
Table 4. Confdence limits (90% level) on statistical uniormity
estimates3.
Uniormity Us
(%) Number o Samples Variability Vqs
(%)
18 36 72 144
90% 3.5% 2.4% 1.7% 1.2% 10%
80% 7.3% 5.0% 3.4% 2.4% 20%
70% 11.5% 7.8% 5.4% 3.8% 30%
60% 16.2% 10.9% 7.6% 5.4% 40%3Adopted rom ASAE (1996a).
Table 3. Data set or Figure 1 example.
Data Point Pressure (psi) Measured Time (sec)1 26 65
2 27 (high #2) 62 (low #1)
3 22 (low #3) 80
4 25 74
5 21 (low #1) 90 (high #1)
6 26 68
7 26 64 (low #2)
8 24 76
9 25 72
10 28 (high #1) 64 (low #3)
11 25 67
12 24 81
13 23 86 (high #3)
14 24 77
15 21 (low #2) 88 (high #2)
16 25 72
17 24 78
18 27 (high #3) 66