Update on NY State & NY City Energy Codes by Lee Brandt

19
3/29/2017 1 Update on NY State & NY City Energy Codes Lee Brandt, LC, IALD, LEED AP BD+C Principal HLB Lighting Design LEDucation Provider Number Update on NY State & NY City Energy Codes Course Number Lee E Brandt March 29, 2017 Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request. This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. _______________________________________ ____ Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Transcript of Update on NY State & NY City Energy Codes by Lee Brandt

Page 1: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

1

Update on NY State & NY City Energy Codes

Lee Brandt, LC, IALD, LEED AP BD+CPrincipal

HLB Lighting Design

LEDucationProvider Number

Update on NY State & NY City Energy CodesCourse Number

Lee E BrandtMarch 29, 2017

Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.

This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner ofhandling, using, distributing, or dealing in any material or product.___________________________________________

Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Page 2: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

2

This presentation is protected by US and International Copyright laws. Reproduction, distribution, display and use of the presentation without written

permission of the speaker is prohibited.

© HLB Lighting Design Inc. 2017

Copyright Materials

Course Description• NY state and thus NY city 

have recently adopted new energy codes.  This seminar will update the audience on lighting related items for the newly adopted codes.  A summary of changes will be provided.

Learning Objectives• Codes in use as of 10/3/2016

• Changes from IECC 2012 to 2015 

• Changes from Std. 90.1 2010 to 2013

• NY State amendments to the base codes

• NY City amendments to State items and base codes

Page 3: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

3

Where can you find the codes?• NYS

– https://www.dos.ny.gov/dcea/noticadopt.html

• NYC– http://www1.nyc.gov/site/buildings/codes/2016‐energy‐conservation‐code.page

– For purchase ($112)• https://a856‐citystore.nyc.gov/2/Municipal‐Publications/11/Rules‐Regulations/2290/2016‐New‐York‐City‐Energy‐Conservation‐Code

When?

• Effective Date 10/3/16

Page 4: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

4

Items of Note• Changes in IECC 2015 & Standard 90.1 2013

– Both are “re‐written” 

– LPD’s – Whole Building/Building Area and Space by Space

– IECC – Decorative allowance back

– 90.1 – many more spaces require bi‐level lighting

– IECC’s Mandatory Additional Efficiency Package Options• 6 options, pick 1

– 10% under either Building or Space by Space (New Construction only)

– Enhanced Digital Lighting Controls

Items of Note• Power requirements

– 90.1 – NYS Amendment changed voltage drop language (Section 8.4.1) to match National Electric Code language – combined voltage drop of 5%

– 90.1 – 50% Automatic Receptacle control is still there (8.4.2) – AND more spaces!

Items of Note• NYC Amendments

– Historic Buildings – Must be on National or State list. – No change, but a reminder:

• 90.1 – Dwelling Units within commercial buildings STILL have to comply• IECC and 90.1 – incorporated LL48 language on occupancy and vacancy 

sensors like before.• Occupancy Sensors OFF within 20 minutes

– OPEN OFFICES now require occupancy sensor control– Reduced LPD for Open and Enclosed office and Retail Sales Area– Alterations

• IECC = 20% threshold [NYC]• Standard 90.1 = 20% threshold [NYC]

Page 5: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

5

Compliance Path Options• NYS and NYC ‐ IECC 2015 Prescriptive 

– Efficiency Options for new construction only

• NYS ‐ IECC 2015 Performance– Building energy cost < 85% of reference building

• NYS and NYC ‐ Std. 90.1 2013 Prescriptive

• NYS and NYC ‐ Std. 90.1 2013 Performance (2 paths)

New York CityIECC Performance Path removed

Envelope and Power Requirements

Envelope – Window to Wall Ratio(no change)

IECC 2015 – C402.4.1• Prescriptive:

– 30% Max OR

– 40% Max when

• >25% conditioned floor area in daylight zone 

• Automatic daylighting controls installed

• Certain VT requirements

STD. 90.1 – Tables 5.5.1‐8• Prescriptive

– 40% (No change)

– Allowance for Street Level vertical fenestration (5.5.4.4.1 Exception 3.)

– Limits fenestration on East & West facing walls (5.5.4.5) (no change)

Page 6: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

6

Envelope – Window to Wall Ratio

• Prescriptive Path

• Benefits of daylighting = 0

• Use Performance Paths!

Envelope – Skylight RequirementsIECC 2015 – C402.3.2• Prescriptive:

– Directly under roof w/ ceiling >15’

– Spaces > 2,500 sq ft

– Certain space types

– Daylight zone / area requirements associated with Skylights

• Multi‐level lighting controls (C405.2.3.3)

STD. 90.1 ‐ 5.5.4.2.3 • Prescriptive:

– Directly under roof w/ ceiling >15’

– Spaces > 2,500 sq ft

– Certain space types

– Daylight zone / area requirements associated with Skylights

• Multi‐level lighting controls (9.4.1.1.f)

Power – Voltage DropIECC 2015

• No requirements

STD. 90.1 – 8.4.1

• Mandatory– 2% for feeders

– 3% for branch circuits

New York State & New York CityCHANGED THE LANGUAGE TO MATCH NATIONAL ELECTRIC CODE (NEC)

Page 7: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

7

PowerAutomatic Receptacle Control

IECC 2015

• No requirements

STD. 90.1 – 8.4.2

• Mandatory– Private offices, conference 

rooms AND

– Print/Copy rooms, break rooms, classrooms, and individual work stations

– 25% of modular furniture circuits

Lighting

Lighting – Scope – Dwelling Units(no change)

IECC 2015 – C405.1/R404.1

• > 75% of lamps in permanently installed light fixtures shall use high efficacy lamps 

– Does not include low voltage lighting!

– High Efficacy = 

• CFL

• <T8 linear fluorescent

• >60 lumens / watt for > 40 watt lamp

STD. 90.1 – 9.1.1• ExceptedNew York City 

DWELLING UNITS ARE NOT EXCEPTED!! They do not have to apply with Lighting Section if they meet IECC language 

Page 8: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

8

Lighting – Scope ‐ AlterationsIECC 2015 – C101.4.3

• Exception for <10% replacement of luminaires in a space as long as power is not increased

• Replacement of lamps + ballasts ok (need not comply with code) if LPD not increased

STD. 90.1 – 9.1.2

• Exception for <10% of connected lighting load such that LPD is not increased

• All other alterations must comply with LPD and auto shutoff (9.4.1.1)– Including lamps + ballasts 

replacement

– Including exterior alterations

New York CityMADE THRESHOLD 20%

New York CityAlterations to comply with all control requirements

Controls

Automatic ControlIECC 2015 – C405.2.2.1

– Automatic Time Switch controls shall be installed

– Exception for areas with occupancy sensors.  

STD. 90.1 – 9.4.1.1

– Automatic Controls to shut off interior lighting shall be installed

• Time of day

• Occupant sensor

• Signal from other system indicating unoccupied space

Page 9: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

9

Occupancy SensorsIECC 2015 – C405.2.1• Required in:

– Classrooms/Lecture/Training– Conference / Meeting Rooms– Copy/Print Rooms– Employee lunch and break rooms– Private offices– Restrooms– Storage Rooms– Janitorial Closets– Spaces< 300 sq. ft– Warehouses

• Auto‐off within 30 min

STD. 90.1 – 9.4.1.1.b.c.g.h• Auto‐off within 20 min

New York City amendmentsAuto‐off within 20 min!

Occupancy Sensors – Open Offices

• Open Offices require occupancy sensors (full on ok)

• Auto‐off within 20 min

New York CityAffects both IECC and Std. 90.1

Automatic Control ‐ FunctionsIECC 2015 – C405.2.1.1 • Manual or Auto ON

– Auto ON only if <50% power• OK for 100% on in corridors, 

stairwells, restrooms, entrance areas, and lobbies, or areas requiring 100% on for safety

• NYC – OK for 100% on in open offices

• Warehouses – separate for each aisle

• Auto OFF (full) required

STD. 90.1 – 9.4.1.1.b.c.g.h

• Manual or Auto ON– Auto ON only if <50%  power

• OK for 100% on in some spaces including open offices – see table 9.6.1

• Auto OFF (partial) 9.4.1.1.g– Spaces that used to be exempt 

from auto‐off (corridors, stairs, lobbies, warehouses)

• Auto OFF (full) 9.4.1.1.h– Most spaces

Page 10: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

10

Manual/Local ControlsIECC 2015 – C405.2.2.3

– Manual lighting controls required in almost all areas (some exceptions)

STD. 90.1 – 9.4.1.1.a

– Manual lighting controls required in almost all spaces (some exceptions)

Light Reduction ControlsIECC 2015 – C405.2.2.2

– 50% reduction in each area where time‐switch controls are installed. 

• Important exceptions – Spaces with one luminaire < 

100 watts– Spaces that use less than 0.6 

w/sf– Corridors, equipment rooms, 

public lobbies, electrical/mechanical rooms

– Above exceptions must have a manual control

– Daylight zones with controls per  C405.2.3

STD. 90.1 – 9.4.1.1.d

– Each area with manual control (many space types) shall have one control step between 30 and 70% in addition to off.

• Can be accomplished  with dimming, step ballast, zoning

Daylighting ControlsIECC 2012 – C405.2.3• Daylight‐responsive controls are required for 

lights in daylight zones– >150 watts of general lighting

• Calibration required• Offices, classrooms, labs, library reading rooms 

– continuous dim from full to 15%• Appears other areas can be controlled on/off 

or steps• Shall be capable of complete shut off• Sidelight zones facing different orientations 

shall be controlled separately• Toplight and sidelight daylight zones shall be 

controlled separately• Not required for retail and other exceptions

STD. 90.1 – 9.4.1.1.e and f.• Photocontrols shall control lights in 

primary sidelighted and toplighted areas– >150 watts of general lighting

– >300 watts of general lighting for primary and secondary sidelighted areas (separate zones)

• Calibration required

• Continuous dim or at least one control point between 50% and 70%, a second at between 20% and 40%, a third at full off.

• General lighting overlapping toplightedand sidelighted areas shall be controlled together

• Not required for retail and other exceptions

Page 11: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

11

Sidelighting DefinitionSTD. 90.1 – 3.2 DefinitionsIECC ‐ C405.2.3.2

• Sidelight Daylight Zone– Floor area next to vertical 

fenestration (window, roof monitor, clerestory)

– >24 sq. ft of window

– If existing buildings, Tvis >0.20

• Primary sidelighted areas

• Secondary sidelighted areas

Sidelighting DefinitionIECC 

Sidelighting DefinitionSTD. 90.1

Page 12: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

12

Toplighting /Skylight Zone DefinitionSTD. 90.1 – 3.2 DefinitionsIECC – C405.2.3.3 

• Toplight Daylight Zone– Floor area underneath a roof 

fenestration assembly (skylight, roof monitor)

• Daylight Area Under Skylights (including roof monitor)

Toplighting /Skylight DefinitionIECC 

Toplighting /Skylight DefinitionIECC 

Page 13: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

13

Toplighting /Skylight DefinitionIECC 

Toplighting /Skylight DefinitionSTD. 90.1

Interior Lighting Control Requirements (summary)

• Each space is required to have or is limited by:– Local on/off control– Manual on restrictions– Partial automatic‐on (via occupancy or time control)– Partial automatic‐off (via occupancy or time control) (full off complies) 

[not IECC/NYC path]– Automatic full off (via occupancy or time control)– Bi‐level control available to occupant– Scheduled automatic off– Daylight control – continuous dimming or step [no more manual 

control in IECC/NYC path]

Page 14: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

14

• Space by Space Method 

• Controls required for each space are listed with LPD

– REQ = mandatory

– ADD1 = at least one of these must be implemented

– ADD2 = at least one of these must be implemented

– Some helpful footnotes – especially for electrical and mechanical rooms (note #7) – add’l LPD

Standard 90.1 Table 9.6.1

Standard 90.1 Table 9.6.1

Additional Interior Controls(no change)

STD. 90.1‐ 9.4.1.3IECC ‐ C405.2.4

• Mandatory –Dedicated/separate control for Display/Accent, Case, Non‐visual and Demonstration 

• Task Lights – sensor on the luminaire or on the wall

Page 15: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

15

Additional Interior Controls Guest Rooms

STD. 90.1 ‐ 9.4.1.3.bIECC ‐ C405.2.4.3

• Auto‐off (lighting and switched receptacles) within 20 min OR keycard activation

• Bathrooms shall have separate device to turn off all bathroom lighting within 30 min

– 5 watt night light exempt

• Auto‐off (lighting and switched receptacles) within 20 min OR keycard activation

Exterior Lighting ControlsIECC 2012 – C405.2.5 STD. 90.1 – 9.4.1.4

• Automatic control to keep lights off when sufficient daylight available

– Façade and landscape lighting

• Auto shut‐off b/t midnight or business closing and 6am or business opening

– All other exterior lighting including signage shall be controlled automatically to reduce connected load by minimum of 30%

• From midnight to 6am (or within one hour of business close / open) OR

• Any period of inactivity > 15 min

STD90.1 only – 9.4.1.2 

9.4.1.3

Daylight Transition Zone

• Garage must have automatic shut off controls (9.4.1.1.i)

• Occupancy sensor to decrease power of each luminaire by 30%

• <3600 sq ft zone

• Daylight transition zone, separate control – 50% reduction from sunset to sunrise

• Daylight responsive lighting zone within 20’ of perimeter wall 

Daylight Transition Zone

20’ Daylight Control Zone

3,600 sq ft max control zone

Exterior Lighting ControlsParking Garage

Page 16: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

16

Lighting Power Density

Interior Lighting Power

• Building Area about the same as 2012

• Reduced LPD’s from 2012 for Space by Space

– Decorative allowance is back! (C405.4.2.2.1.2.)

STD. 90.1 – 9.5.1 AND 9.6.1IECC 2015 ‐ C405.4.2 (1) AND (2)

• Building Area about the same as 2010

• A few changes on Space by Space

• New allowance for spaces for the visually impaired

Interior Lighting PowerOffice Areas

STD. 90.1 Z–9.6.1IECC 2015 ‐ C405.4.2 (2)

New York CitySpace by Space Reductions‐ Office/Enclosed – 1.0 w/sf  [from 1.11]‐ Office/Open Plan – 0.9 w/sf  [from 0.98]

Page 17: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

17

Interior Lighting PowerRetail Sales Areas

STD. 90.1 –9.6.2.bIECC 2015 ‐ C405.4.2 .2.1.1

• Base allowance – 1000 watts

• 1.44 w/sf (base code)• Base allowance – 500 watts

• 1.59 w/sf (base code)

+ Base Allowance

+ Retail Area 1 * 0.6 w/sf

+ Retail Area 2 * 0.6 w/sf

+ Retail Area 3 * 1.4 w/sf

+ Retail Area 4 * 2.5 w/sf

New York CitySpace by Space Reduction‐ Retail Sales Area – 1.3 w/sf

Interior Lighting PowerAdditional Allowances (90.1)

STD. 90.1 – TABLE 9.6.1IECC – N/A

• Room Cavity Ratio additional allowance for tall and unique shaped rooms and corridors less than 8’ wide

– 20% increase on LPD!

Interior Lighting PowerAdditional Allowances (90.1)

STD. 90.1 – TABLE 9.6.3IECC – N/A

• Additional  control methods – in addition to Mandatory controls = extra wattage

– Specific conditions and applications

Page 18: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

18

Exterior Lighting Power

• No major changes

– Tradable / Non‐tradable

– Matches Std. 90.1 except Building Façade which is lower 

– Area calculation is above grade wall area

STD. 90.1 – 9.4.2.2IECC ‐ C405.5.2(2)• No major changes

– Tradable / Non‐tradable

– Lighting Zones ‐ Has LZ0

– Matches IECC/NYC path except Building Façade

– Area calculation is wall area or length

– Also has categories for Landscaping and Loading Docks

Functional TestingSTD. 90.1 – 9.4.4 IECC – C408.3 

• Controls have to be tested

• Daylighting controls actually reduce electric lighting

• Placement and sensitivity of sensors

• Documentation required

• Third party – they produce report

Additional Efficiency Package Requirements

IECC 2012 – C406• Mandatory for New Construction  only

– Additional Efficiency Package Options!  Project must chose 1

• Efficient HVAC equipment 

• Reduced LPD C406.3

• Enhanced Lighting Controls C406.4

• On‐site renewable energy

• Dedicated outdoor air system

• High Efficiency service water heating

– Lighting may be the common choice• Building Area OR Space by Space tables 

with 10% reduction

• Enhanced Controls

STD. 90.1 • No requirement

Page 19: Update on NY State & NY City Energy Codes by Lee Brandt

3/29/2017

19

What you learned• Codes in use as of 10/3/2016

• Changes from IECC 2012 to 2015 

• Changes from Std. 90.1 2010 to 2013

• NY State amendments to the base codes

• NY City amendments to State items and base codes