Edition: September 2012 EB 3967 EN Mounting and Operating Instructions Solenoid Valve Type 3967 Fig. 1

Transcript of Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type...

Page 1: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

Edition: September 2012 EB 3967 EN

Mounting and Operating Instructions

Solenoid Valve Type 3967

Fig. 1

Page 2: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 2 –

Contents

General notes 3

Attachment 3Rail mounting 4Panel and wall mounting 4Attachment to connection block with positioner for SAMSON Type 3277 Linear Actuators 5Attachment to linear actuators with NAMUR rib according to IEC 60534-6-1 5Attachment to rotary actuators with NAMUR interface according to VDI/VDE 3845 6

Air connection 7Air supply pipes 7Quality of compressed air according to ISO 8573-1 7Air supply and operating medium 7Connections for air supply, operating medium and exhaust air 8Venting 8Connection of air supply 9External connection of air supply 9Internal connection of air supply 9Restrictor plate for supply air or exhaust air 10

Electrical connection 11Connection cable 11Degree of protection 12Manual override 12

Servicing explosion-protected devices 13

Certifications 14EC Type Examination Certificate PTB 06 ATEX 2027 14Statement of Conformity PTB 06 ATEX 2028 X 18

Page 3: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 3 – EB 3967 EN

General notes

The devices may only be mounted,started up and operated by experi-enced personnel familiar with this

product.

According to these mounting and operating in-structions, trained personnel is referred to asindividuals who are able to judge the workthey are assigned to and recognize possibledangers due to their specialized training, theirknowledge and experience as well as theirknowledge of the applicable standards.Explosion-protected versions of this device areto be operated only by personnel who has un-dergone special training or instructions or whois authorized to work on explosion-protecteddevices in hazardous areas.Any hazards that could be caused in the valveby the process medium, the signal pressure orby moving parts are to be prevented by meansof the appropriate measures.If inadmissible motions or forces are producedin the pneumatic actuator as a result of the sup-ply pressure level, it must be restricted using asuitable supply pressure reducing station.Proper shipping and appropriate storage of thedevice are assumed.For technical data, ordering data, accessoriesand spare parts see Data Sheet T 3967 EN.

Model number and device index

The model number and the device index areshown on the nameplate:

3967-XXXXXXXXXXXXXXXX XX

�Attachment

Before mounting, all relevant partsof the plant must be depressurized.Due to the high surface resistance,

the device must be mounted and serviced inhazardous areas in such a way that no elec-trostatic charging is to be expected.

The devices can be mounted in any desired po-sition.The cable gland must be installed verticallydownwards or, if this is not possible, horizon-tally (see “Connection cable“, page 11).On mounting, make sure that a minimum clear-ance of 200 mm above the enclosure cover iskept.When the devices are to be used in hazardousareas of zone 21 according to EN 50281-1-1:1998, the equipment must be mounted in anadditional enclosure made of steel, stainlesssteel or plastic. The enclosure including its con-nection parts and bushings must be proven tocomply with degree of protection IP 54 accord-ing to IEC 60529:1989.In locations where there is a risk of mechanicaldamage to the enclosure, the enclosure must befitted with additional protection to fullfill the requirements in paragraph 6 of EN 61241-0:2006 Electrical apparatus for use in the pres-ence of combustible dust.

Device indexModel number

Page 4: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 4 –

Rail mounting

Devices with adapter plate can be attachedwith two mounting bases to rails with G-profileG 32 or top hat rails TH 35 according toEN 60715 (see Fig. 2).

Panel and wall mounting

Fig. 3

Rail mounting

Fig. 2

� Mounting plate for wall mounting Order no.1400-6726

� 2 � Hexagon socket head screwISO 4762 – M 3 � 8

Panel and wall mounting

Devices with adapter plate can be attached onpanels. For wall mounting an additionalmounting plate is required (see Fig. 3).

Mounting base according to EN 60715 Order no.� for rail with G-profile G 32 1400-5930� for top hat rail TH 35 1400-5931� 1� Slotted cheese head screw

ISO 1207 – M 3 � 8

��

� ��

� �

Page 5: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 5 – EB 3967 EN

Attachment to connection block with positioner for SAMSON Type 3277 Linear Actuators

Devices with NAMUR interface can be attachedto a connection block with SAMSON Type3730-X, 3731-X, 3766, 3767 or 378XPositioners for SAMSON Type 3277 LinearActuators (see Fig. 4).Before attaching, make sure that the moldedgasket is positioned correctly at the NAMUR in-terface.The devices are attached to the connectionblock using two hexagon socket head screwsISO 4762 – M 5 �35 and two split washersDIN 127 – B 5 underneath.

Attachment to connection block with positioner for SAMSON Type 3277 Linear Actuators

Fig. 4

Attachment to linear actuators with NAMUR rib according to IEC 60531-6-1

Fig. 5

Adapter plate for NAMUR rib according to IEC 60531-6-1, panel, wall or rail mountingConnection Material Order no.G 1/4 AlMgSiPb, powder-coated 1400-95981/4 NPT AlMgSiPb, powder-coated 1400-9599G 1/4 Stainless steel 1.4404 1400-96001/4 NPT Stainless steel 1.4404 1400-96011� Hexagon socket head screw

ISO 4762 – M 8 � 351� Split washer DIN 127 – B 8

Attachment to linear actuators with NAMUR rib according to IEC 60534-6-1

Devices with adapter plate can be attached tolinear actuators with NAMUR rib (see Fig. 5).The adapter plate is attached to the linear ac-tuator using a hexagon socket head screwISO 4762 – M 8 �35 and a split washerDIN 127 – B 8 underneath.

Page 6: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 6 –

Attachment to rotary actuators with NAMUR interface according to VDI/VDE 3845

Devices with NAMUR interface can be attachedto rotary actuators (see Fig. 6).The operation direction is determined by athreaded coding pin ISO 4029 – M 5 �10 onthe mounting flange of the rotary actuator.Before attaching, make sure that the moldedgasket is positioned correctly at the NAMUR in-terface.The devices are attached to the rotary actuatorusing two captive hexagon socket head screws ISO 4762 – M 5 �35 and two split washersDIN 127 – B 5 underneath.

Attachment to rotary actuators with NAMUR interface according to VDI/VDE 3845

Fig. 6

NAMUR interface according to VDI/VDE 3845

32

12

3

9 24

Page 7: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 7 – EB 3967 EN

Air connection

The air supply pipes and screwjoints must only be laid and mount-ed by experienced personnel. They

must be regularly checked for leaks and dam-age, and if necessary, repaired. Before start-ing any repair work, all supply pipes whichare to be opened must be depressurized.

The air connections are tapped holes or the airis connected over the NAMUR interface ac-cording to VDI/VDE 3845.

Air supply pipesConnection Air supply 9 Operating medium 1

Output 2Thread G (NPT) 1/4 G (NPT) 1/4

Pipe � 6 �1 mm � 12 �1 mmHose � 4 �1 mm � 9 �3 mm

Air supply Operating mediumMedium Connection Pressure Medium Connection PressureInstrument air, 9 1.4 … 6.0 bar Instrument air, 1 0 … 6.0 barfree of external or free of orcorrosive air supply 1.9 … 10.0 bar corrosive 0 … 10.0 barparticles, particles, oilor nitrogen containing air

or noncorrosivegases

Instrument air, 1 1.4 … 10.0 bar Instrument air, 1 1.4 … 10.0 barfree of internal free ofcorrosive air supply corrosiveparticles, (connection 9 particles,or nitrogen is closed) or nitrogen

3

1

2

9

Fig. 7

Symbol

When nitrogen is used as the medi-um, the devices must only bemounted in ventilated rooms or out-doors.

Air supply and operating mediummust not exceed the maximum per-missible pressure (see table below).

��

1 Operating medium and internal air supply2 Output3 Exhaust air9 External air supply

Quality of compressed air according toISO 8573-1Particle size Oil contents Pressureand density dew pointClass 4 Class 3 Class 3� 5 µm � 1 mg/m3 �20 °C or atand least 10 K1 000/m3 below the

lowest ambienttemperature tobe expected

Page 8: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 8 –

Connections for air supply, operating mediumand exhaust air

The connections are protected against dirt par-ticles with sieves, mesh size 100 µm.The sieves must be cleaned or replaced whencontaminated as follows (see Fig. 8):

1 Screw sieve � out of the connection using ascrew driver (screw driver blade 7 to 9 mm).

2 Clean or replace sieve � and screw it com-pletely into connection.

Venting

The device is protected against water and dirtentering with a venting plug at the enclosurecover.In case of leakage, the diaphragm in the vent-ing plug must be replaced as follows (seeFig. 9):

1 Unscrew four screws and remove enclosurecover from the enclosure.

2 Unscrew cross head screw � and removeventing plug � from the enclosure cover.

3 Replace diaphragm �.Note: The seating surface of the diaphragmmust be lightly lubricated with silicone oil(Baysilone M 60000).

4 Attach venting plug � to the enclosure cov-er using cross head screw �.

5 Attach the enclosure cover to the enclosureusing four screws.Before attaching, make sure that the gasket� is positioned correctly at the enclosure.

Fig. 8

Connections for air supply, operating medium and exhaust air

Fig. 9

Venting

Spare part Order no.� Sieve 1/4" 0550-0213

Spare parts Order no.� Cross head screw 8336-0769

ISO 3506 – 3 �10� Gasket 0430-1941� Diaphragm 0520-1370� Venting plug 0070-0808

Connection plate Adapter plate

Page 9: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 9 – EB 3967 EN

Connection of air supply

The air supply can be connected externally overconnection 9 or internally over connection 1(see Fig. 10).

External connection of air supply(for attachment to actuators for modulatingservice or connection block with positioner)

1 Unscrew blanking plug � and O-ring �underneath from connection 9 at the con-nection plate or adapter plate.

2 Unscrew three screws � and removeadapter plate from the enclosure.Note: For this purpose, a screwdriver typeT 25 (manufacturer Torx) is required.

3 Take reversible gasket � out of the grooveand turn it so that the tab points to the right(connection 9).

4 Place the reversible gasket � into thegroove.

5 Refasten adapter plate to the enclosure us-ing three screws �.

Internal connection of air supply(for attachment to on-off actuators)

1 Seal connection 9 at the connection plate oradapter plate with a blanking plug � andan O-ring � underneath.

2 Unscrew three screws � and remove theadapter plate from the enclosure.

3 Take reversible gasket � out of the grooveand turn it so that the tab points to the left(connection 1).

4 Place the reversible gasket � into thegroove.

5 Refasten adapter plate to the enclosure us-ing three screws �.

Connection of air supply

Fig. 10

Spare parts Order no.� Screw DIN 7964 – 5 �20 8336-1108� Blanking plug G 1/4 0070-0799� O-ring 14 �1.5 8421-0070� Reversible gasket 0430-1884

��

1 9

External air supply

Internal air supply

Connection plate Adapter plate

Page 10: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 10 –

Restrictor plate for supply air or exhaust air

Fig. 12

Restrictor plate KVS value Order no.with exhaust air restrictor 0.01 … 0.24 1400-9603with supply air restrictor 0.01 … 0.24 1400-96022�Threaded bolt M 5

Symbols

Fig. 11

Restrictor plate for supply air or exhaust air

The devices can be provided with a restrictorplate for supply air or exhaust air (see Fig. 11and 12).The flow rate can be adjusted by turning the re-strictor screw clockwise or counterclockwise,using a screwdriver (screwdriver blade 5 to7 mm).The restrictor plate can be attached with twothreaded bolts M 5 to the rotary actuator or tothe adapter plate. Then make sure that the O-rings are positioned correctly at the NAMURinterface.The device can be attached with two hexagonsocket head screws to the restrictor plate.Before attaching, make sure that the moldedgasket is positioned correctly at the NAMUR in-terface.

3

1

2

9

3

1

2

9

3/2-way function with supply air restrictor

3/2-way function with exhaust air restrictor

NAMUR interface according to VDI/VDE 3845

32

12

3

9 24

Page 11: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 11 – EB 3967 EN

Electrical connection

For electrical installation, observe the relevantregulations and the accident preventation reg-ulations that apply in the country of use. InGermany, these are the VDE regulations andthe accident preventation regulations of theemployers´ liability insurance.The following regulations apply to installationin hazardous areas: EN 60079-14:1998 (VDE0165-1:1999) Electrical Apparatus forExplosive Gas Atmospheres and EN 50281-1-2(VDE 0165 Part 2/1999) Electrical Apparatusfor Use in the Presence of Combustible Dust.For instrinsically safe electrical equipment ap-proved in accordance with Directive 94/9/EC,the data specified in the EC type examinationcertificate and the statement of conformity ap-ply to the connection of intrinsically safe cir-cuits (see “Certifications“, pages 14 to 22).

Do not loosen enameled screws inor on the enclosure.

Connecting cable

The power supply is connected through a cablegland � to screw terminals � underneath theenclosure cover (see Fig. 13 and 14).

When connected to DC voltage sig-nals, correct polarity must be en-sured.

The cable gland � with an O-ring � under-neath can be installed according to the mount-ing position hanging vertically downwards orhorizontally. The unused cable entry must besealed by a plug � and an O-ring � under-neath.Devices which are used for ambient tempera-tures to �45 °C must be provided with a metalcable gland.It is recommended to use connecting cableswith a conductor cross-section of 0.5 to2.5 mm2 and an external diameter of 5 to8 mm. The diameter of an individual wire in afine-stranded conductor must not be smallerthan 0.1 mm.Protect the conductor ends against splicing,e. g. by using wire-end ferrules.

� �

6/12/24 V DC

Fig. 13

Connection diagram

���

��

Fig. 14

Electrical connection

� Cable gland M 16 �1.5� Plug M 16 �1,5� O-ring 14 �1.5

(not for cable gland manufactured by CEAG)� Screw terminals

Page 12: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 12 –

Manual override

The devices are optionally provided with amanual override (see Fig.15).When an electric nominal signal is not avail-able, the device can be operated manually.

For safety circuits, only deviceswithout manual override must beused.�

Fig. 15

Manual override

Manual override at the enclosure cover� Pushbutton – Press pushbutton with a pin� Pushbutton switch – Press pushbutton switch using a

screwdriver (screwdriver blade4.5 mm) and turn 90° clockwise. To unlock, turn in opposite direction.

Manual override underneath the enclosure cover� Pushbutton – Press pushbutton

� � �

Degree of protection

The devices are protected against water anddust by a venting plug at the enclosure cover(see “Venting“, page 8).

The required degree of protection IP 65 according to IEC 60529:1989can be only guaranteed with in-

stalled enclosure cover, integrated ventingplug, closed cable entries and proper installa-tion of the connections.

Page 13: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 13 – EB 3967 EN

Servicing explosion-protecteddevices

If a part of the device on which the explosionprotection is based needs to be serviced, thedevice must not be put back into operation untila qualified inspector has assessed it accordingto explosion requirements, has issued aninspection certificate or given the device amark of conformity.Inspection by a qualified inspector is not re-quired if the manufacturer performs a routinetest on the device prior to putting it back intooperation. The passing of the routine test mustbe documented by attaching a mark of confor-mity o the device.Replace explosion-protected components onlyby original, routine tested components from themanufacturer.Devices that have already been used outsidehazardous areas and are intended for futureuse inside hazardous areas must comply withthe safety requirements placed on serviced de-vices.The devices must be inspected before being putback into operation as specified in para-graph (6) in Article 14 of the GermanOrdinance concerning the protection of safetyand health at work (BetrSichV).

Page 14: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 14 –

Certifications

Page 15: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 15 – EB 3967 EN

Page 16: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 16 –

Page 17: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 17 – EB 3967 EN

Page 18: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 18 –

Page 19: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 19 – EB 3967 EN

Page 20: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 20 –

Page 21: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 21 – EB 3967 EN

Page 22: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

EB 3967 EN – 22 –

Page 23: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

– 23 – EB 3967 EN

Page 24: Solenoid Valve Type 3967 - AC Controls Solenoid Valves/6.27.1 Samson Solenoid...Solenoid Valve Type 3967 Fig. 1. ... 1 Split washer DIN 127 – B 8 Attachment to linear actuators with

(Specifications subject to change without notice.)

SAMSOMATIC GMBH

A member of the SAMSON GROUP 2012

-09

· EB

396

7 EN