Procedure Flowsheet Elaboration

download Procedure Flowsheet Elaboration

of 31

description

pfe

Transcript of Procedure Flowsheet Elaboration

PROYECTO: CLEANING SYSTEM

Div. Cartones Nacionales

Div. Cartones Nacionales

PROCEDURE: FLOWSHEET ELABORATION

IN-PRC-001REV. 0

FLOWSHEET ELABORATION

Rev.DateDescriptionByCheck.Apr.

0

CMKAOFMA

CONTENT

1. OBJECTIVE

2. DEFINITIONS

2.1 General Instructions

2.2 Standard Format

2.3 Symbols

2.3.1 Equipment, Piping and Valves

2.3.2 Instruments and Control Valves

2.4 Information Register

2.4.1 Text Standard

2.4.2 Balance Data

2.4.3 Units

2.4.4 Pipe Identification

2.4.5 Main Equipment Identification

2.4.6 Pump Identification

2.4.7 Hand Valves Identification

2.4.8 Instrument and Control Valve Identification

2.5 Plotting

ANNEX

IStandard Format for Flowsheets

IISymbols for Equipment, Piping and Hand Valves

IIISymbols for Instruments and Control Valves

IVInformation Register - Text Standard

VMill Area and Equipment Codification

VIPlotting Instructions

1 OBJECTIVE

The purpose of this document is to establish standards for flowsheet elaboration, from the content and drawing point of view

2 DEFINITIONS

2.1General Instructions

The flowsheets will be drawn in AUTOCAD, in the sheet format A1 or A1 multiple, according to the process sequence, from the left to the right whenever this is possible. The text height defined in the annex IV allow reduced plotting to A4 format height for easier handling when necessary.

The origin and destine of the flow lines will be indicated in the flowsheet ends by a standard block for each line, in which it will be indicated the number of the corresponding drawing.

In the flowsheet extremities, the complete media denomination will be written. For any other part, the standard media code shall be used.

The texts will be in Spanish or English, according to project definition, written in capital letters, except for units, that will be written in the usual form (e.g. gpm, l/min, etc.).

The progressive revisions shall be indicated by letters until approval for erection, when revision 0 (zero) will be established. From that on, revisions shall be indicated by numbers.

2.2Standard FormatAccording to annex I.

2.3Symbols2.3.1Equipment, Piping and Hand ValvesAccording to annex II.

2.3.2Instruments and Control ValvesAccording to annex III.

2.4Information Register2.4.1Text StandardAccording to annex IV.

2.4.2Balance DataThe balance data indicate in the flowsheet shall correspond to the normal operating conditions, with indication of maximum volumetric flow inside parenthesis.

In general, balance data will not be followed by the respective units, which will be indicated in a legend in the flowsheet right end. Only the atypical units will be indicated together with the data, for example:

Pulp line, fiber flow of 250 kgBD/min, 10 % consistency, design flow 2500 l/min, and maximum flow 2750 l/min:

Indication:250 10 2500 (2750)

Water line, design flow 800 l/min, maximum flow 1000 l/min:

Indication:800 (1000)

Steam line, design flow 5 t/h, and maximum flow 7 t/h:

Indication:5 (7) t/h

In the battery limits, additional process conditions as pressure, concentration and temperature, shall be indicated with the respective units.

2.4.3Units

According to International System, unless there is a different definition for an specific project.

2.4.4Pipe Identification

The code to be used is as follows:

DD MM EEEE NNN II

Dnominal pipe diameter (in inches)

Mmedia code according to Piping Material and Hand Valve Selection Guide

Epipe specification code, according to Piping Material and Hand Valve Selection Guide

Nsequential number

Iinsulation code (thickness)

Example of pipe identification:

In the right end of the flowsheet, a legend for pipe identification will be indicated (see annex I).

2.4.5Main Equipment Identification

The number and the equipment denomination will be according to equipment list and will be indicated inside the representative figure, whenever it is possible.

Additional information depends on what is relevant for each the type of equipment, for instance, screen perforations, tank diameter, pulp consistency, etc.). The additional information will be indicated with smaller characters, bellow the equipment number and denominations, always in the same sequence.

The area and equipment code are according to annex V.

Example of equipment identification:

2.4.6Pump Identification

The pump number will be according to pump list. The nominal flow and manometric height will be also indicated.

The area code is according to annex V.

Example of pump identification:

2.4.7Hand Valves Identification

The area code is according to annex V.

Example of hand valve identification:

2.4.8Instrument and Control Valve Identification

The instrument loop will be represented by the function code and sequential number. The codification will be according to annex III.

Example of instrument loop and control valve identification:

2.5Plotting

According to annex VI.

ANNEX I

Standard Format for Flowsheets

ANNEX II

Symbols for Equipment, Piping and Hand Valves

ANNEX III

Symbols for Instruments and Control Valves

INSTRUMENTATION SYMBOLOGYannex III

(Table and notes extracted from ISA standard)

FUNCTIONAL IDENTIFICATION FOR FLOWSHEETS

FIRST LETTER (4)SUCCEEDING LETTERS (3)

Measured or initiating VariableModifierReadout or Passive FunctionOutput FunctionModifier

AAnalysis (5,19)

Alarm

BBurner,Combustion

Users Choice (1)Users Choice (1)Users Choice (1)

CUsers Choice (1)

Control (13)

DUsers Choice (1)Differential (4)

EVoltage

Sensor (Primary Element)

FFlow RateRatio (Fraction) (4)

GUsers Choice (1)

Glass, Viewing Device (9)

HHand

High (7,15,16)

ICurrent (Electrical)

Indicate (10)

JPowerScan (7)

KTime, Time Schedule Time rate of change (4, 21)

Control Station (22)

LLevel

Light (11)

Low (7,15,16)

MUsers Choice (1)Momentary (4)

Middle Intermediate (7,15)

NUsers Choice (1)

Users Choice (1)Users Choice (1)Users Choice (1)

OUsers Choice (1)

Orifice, Restriction

PPressure, Vacuum

Point (Test) Connection

QQuantityIntegrate, Totalize (4)

RRadiation

Record (17)

SSpeed, FrequencySafety (8)

Switch (13)

TTemperature

Transmit (18)

UMultivariable (6)

Multifunction (12)Multifunction (12)Multifunction (12)

INSTRUMENTATION SYMBOLOGY (CONT.)annex III

FUNCTIONAL IDENTIFICATION FOR FLOWSHEETS

FIRST LETTER (4)SUCCEEDING LETTERS (3)

Measured or initiating VariableModifierReadout or Passive FunctionOutput FunctionModifier

VVibration, Mechanical Analysis (19)

Valve, Damper Louver (13)

WWeight, Force

Well

XUnclassified (2)X AxisUnclassified (2)Unclassified (2)Unclassified (2)

YEvent, State or Presence (20)Y Axis

Relay, Compute Convert (13,14,18)

ZPosition, Dimension Z Axis

Driver, Actuator, Unclassified Final Control Element

NOTES FOR TABLE1. A users choice letter is intended to cover unlisted meanings that will be used repetitively in a particular project. If used, the letter may have one meaning as a first-letter and another meaning as a succeeding-letter. The meanings need to be defined only once in a legend, or other place, for that project. For example, the letter N may be defined as modulus of elasticity as a first-letter and oscilloscope as a succeeding-letter.

2. The unclassified letter X is intended to cover unlisted meanings that will be used only once or used to a limited extent. If used, the letter may have any number of meanings as a first-letter and any number of meanings as a succeeding-letter. Except for its use with distinctive symbols, it is expected that the meaning will be defined outside a tagging bubble on a flow diagram. For example, XR-2 may be a stress recorder and XX-4 may be a stress oscilloscope.

3. The grammatical form of the succeeding-letter meanings may be modified as required. For example, indicate may be applied as indicator or indicating, transmit as transmitter or transmitting, etc.

4. Any first-letter, if used in combination with modifying letters D (differential), F (ratio), M (momentary), K (time rate of change, Q (integrate or totalize), or any combination of these is intended to represent a new and separate measured variable, and the combination is treated as a first-letter entity. Thus, instruments TDI and TI indicate two different variables, namely, differential-temperature and temperature. Modifying letters are used when applicable.

5. First letter A (analysis) covers all analysis not described by a users choice letter. It is expected that the type of analysis will be defined outside a tagging bubble.

6. Use of first-letter U for multivariable in lieu of a combination of first-letter is optional. It is recommended that nonspecific variable designators such as U be used sparingly.

7. The use of modifying terms high, low, middle or intermediate, and scan is optional.

8. The term safety applies to emergency protective final control elements only. Thus, a self-actuated valve that prevents operation of a fluid system at a higher-than-desired pressure by bleeding fluid from the system is a back-pressure-type PCV, even if the valve is not intended to be used normally. However, this valve is designated as a PSV if it is intended to protect against emergency conditions, i.e., conditions that are not expected to arise normally.

The designation PSV applies to all valves intended to protect against emergency pressure conditions regardless of whether the valve construction and mode of operation place them in the category of the safety valve, relief valve, or safety relief valve. A rupture disc is designated PSE.

9. The passive function G applies to instruments or devices that provide an uncalibrated view, such as sight glasses and television monitors.

10. Indicate normally applies to the readout analog or digital of an actual measurement. In the case of a manual loader, it may be used for the dial or setting indication, i.e., for the value of the initiating variable.

11. A pilot light that is part of an instrument loop should be designated by a first-letter followed by the succeeding-letter L. For example, a pilot light that indicates an expired time period should be tagged KQL. If it is desired to tag a pilot light that is not part of an instrument loop, the light is designated in the same way. For example, a running light for an electric motor may be tagged EL, assuming voltage to be the appropriate measured variable, or YL, assuming the operating status is being monitored. The unclassified variable X should be used only for applications, which are limited in extent.

The designation XL should not be used for motor running lights, as these are commonly numerous. It is permissible to use the users choice letter M, N or O for a motor running light when the meaning is previously defined. If M is used, it must be clear that the letter does not stand for the word motor, but for a monitored state.

12. Use of a succeeding-letter U for multifunction instead of a combination of other functional letters is optional. This nonspecific function designator should be used sparingly.

13. A device that connects, disconnects, or transfers one or more circuits may be either a switch, a relay, an ON-OFF controller, or a control valve, depending on the application.

If the device manipulates a fluid process stream and is not a hand-actuated ON-OFF block valve, it is designated as a control valve. It is incorrect to use the succeeding-letter CV for anything other than a self-actuated control valve. For all applications other than fluid process streams, the device is designated as follows:

A switch, if it is actuated by hand.

A switch, or an ON-OFF controller, if it is automatic and is the first such device in a loop. The term switch is generally used if the device is used for alarm, pilot light, selection, interlock, or safety.

The term controller is generally used if the device is used for normal operating control.

A relay, if it is automatic and is not the first such device in a loop, i.e., it is actuated by a switch or an ON-OFF controller.

14. It is expected that the functions associated with the use of succeeding-letter Y will be defined outside a bubble on a diagram when further definition is considered necessary. This definition need not be made when the function is self-evident, as for a solenoid valve in a fluid signal line.

15. The modifying terms high, and low, and middle or intermediate correspond to values of the measured variable, not to values of the signal, unless otherwise noted. For example, a high-level alarm derived from a reverse-acting level transmitter signal should be an LAH, even though the alarm is actuated when the signal falls to a low value. The terms, may be used in combination as appropriate. (See Section 6.9 of ISA standard).

16. The terms high and low, when applied to positions of valves and other open-close devices, are defined as follows: high denotes that the valve is in or approaching the fully open position, and low denotes that it is in or approaching the fully closed position.

17. The word record applies to any form of permanent storage of information that permits retrieval by any means.

18- For use of the term transmitter versus converter, see the definitions in Section 3.

19- First-letter V, vibration or mechanical analysis is intended to perform the duties in machinery monitoring that the letter A performs in more general analysis. Excepts for vibration, it is expected that the variable of interest will be defined outside the tagging bubble.

20- First-letter Y is intended for use when control or monitoring responses are event-driven as opposed to time-or time schedule-driven. The letter Y, in this position, can also signify presence or state.

21- Modifying-letter K, in combination with a first-letter such as L, T or W, signifies a time rate of change of the measured or initiating variable. The variable WKIC, for instance, may represent a rate-of-weight-loss controller.

22- Succeeding-letter K is a users option for designating a control station, while the succeeding-letter C is used for describing automatic or manual controllers. (See Section 3, Definitions of ISA standard).

EXAMPLES OF LOOP DENOMINATION IN FLOWSHEETSannex III

FRC flow control and register

PICpressure control and indication

PRCAH/Lpressure control and register with alarm high or low

FFRCflow control and register with a proportional ratio

LICASlevel control and indication, with alarm and interlocking

TICAH/Ltemperature control and indication, with alarm high or low

ARCanalytic control and register

HICmanual control station with indication

HSmanual switch

FYflow calculations

KSOcommand for on-off valves actuation by an automatic temporized sequence with open/close indication

ANNEX IV

Information Register Text Standard

ANNEX V

Mill Area and Equipment Codification

MILL AREA CODIFICATIONannex V

SpanishEnglishArea Code

BatidoresBeater RoomBAT

T & BTop & Back Cleaning SystemLRS

FillerFiller Cleaning SystemLRE

PolyPoly Cleaning SystemPLY

Parte HmedaWet EndPHU

Parte SecaDry endPSE

Acabado y despachoFinishingACA

Sala ArcillaCoating KitchenARC

SatinadoraCoaterSAT

Casa de FuerzaPower HouseCDF

Tratamiento de EfluenteEffluent TreatmentPTE

Sistema contra incendioFire extinguishing SystemSCI

GalponesWarehouseGAL

Taller MecnicoMechanical workshopTAL

CarpinteraCarpentryCRP

VehculosVehiclesVEH

AlmacnWarehouseALM

Edificio de mquinaMachine BuildingEDI

EQUIPMENT IDENTIFICATION CODESannex V

SpanishEnglishEquipment Code

AcopleCouplingAO

AcumuladorAcumulatorAU

AfiladoraGrinderAF

AgitadorAgitatorAG

Aire acondicionadoConditioning airAC

Alimentador rotativoRotative feederAR

Aplicador de revestimientoCoating aplicatorAP

Astillador de discoChipper, discAD

Balanceador dinmico universalUniversal dynamic balancingBU

BalanzaScaleBL

BobinadoraWinderBB

Bomba centrifugaCentrifugal pumpBO

Bomba de desplazamiento positivoPositive displacement pumpBP

Bomba de diafragmaDiaphragm pumpBD

Bomba de tornilloScrew pumpBT

Bomba de vacoVacuum pumpBV

Bomba engrenagenGear pumpBE

Bomba sumergidaSubmerged pumpBS

Caja de entradaHead boxCE

Caja de nivelLevel boxCN

Caja de succinSuction boxSU

Caja sopladoraBlowing boxCJ

CalandriaCalanderLD

CalderaBoilerCB

Caldera de recup. de vaporReboilerCR

CalentadorHeaterCT

CanalChannelCA

Canal de captacinCaption channelCC

CapotaHoodPO

ChimeneaChimneyHN

CicloneCycloneLN

Cilindro enfriadorCooling cylinderCF

Cilindro secadorDryer cylinderCS

Cilindro, generalCylinder, generalCG

ClarificadorClarifierCI

EQUIPMENT IDENTIFICATION CODES (cont.)annex V

SpanishEnglishEquipment Code

CloradorChlorinatorCL

ColaderaScreenCO

CompresorCompressorCP

CompuertaGateCM

CondensadorCondenserCD

ContracloneContracloneCC

CortaderaCutterTA

CristalizadorCristalizerCZ

CuchilloKnifeCH

DampersDampersDA

DecantadorSettlerDC

Decantador de arenaSand settling boxDR

DeculatorDeculatorDU

DeflakerDeflakerDK

DeflectorDeflectorDT

DepuradorScreenDE

Depurador centrifugoPressure screenDP

Depurador de astillasChip screenDL

DesaereadordeaeratorSD

descargadorUnloaderDD

descortezadorDebarkerDZ

DesfibradorPressure fibrilizerDF

Desupercalentador DesuperheaterDN

Detector de metalesMetals detectorDM

DifusorDifuserDI

DigestorDigesterDG

DispersorDisperger DS

DistribuidorDistributerDB

DosificadorPin feederDO

EconomizadorEconomizerEC

ElevadorElevatorEL

EmbaladoraBalerEB

EmpacadoraWrapping machineEP

EnfriadorCoolerEF

Equipos neumticosPneumatic equipmentEN

EQUIPMENT IDENTIFICATION CODES (cont.)annex V

SpanishEnglishEquipment Code

EspesadorThickenerES

EstabilizadorStabilizerET

EvaporadorEvaporatorEV

ExtractorExhausterEX

EyectorEjectorEY

Eyector de bobinasRoll kickerEI

Filtro de aceiteFilter, oil FC

Filtro de aguaFilter, water FG

Filtro de aireFilter, airFA

Filtro lavadorWashing filterFL

Filtros, generalFilter, generalFI

FloculadorFloculatorFU

FlotadorFlotatorFT

FormadoraFormerFO

GeneradorGeneratorGN

Grua estacionariaStationary trolleyGE

Horno de calLime kilnHC

Instrumento de laboratorioLaboratory instrumentIL

Intercambiador de calorHeat exchangerIC

Junta de expansinExpansion jointJE

Junta flexibleFlexible jointJF

Lavador de astillasChip washerLV

Lavador de gasesScrubberLG

Limpiador de Alta DensidadHigh Density CleanerLA

Limpiador de Baja DensidadLow Density CleanerLB

Limpiador de Media DensidadMedium Density CleanerLM

Maquina de papelPaper machineMP

Mesa formadoraForming tableMF

MezcladorMixerME

Motor bombaMotor, pumpMB

Motor de aire comprimidoMotor, compressed airMC

Motor DieselMotor, DieselMD

Motor gasolinaMotor, gasolineMG

Motor hidrulicoMotor, hydraulicMH

Motor neumticoMotor, pneumaticMN

EQUIPMENT IDENTIFICATION CODES (cont.)annex V

SpanishEnglishEquipment Code

Motor reductorMotor, reducerMR

Pre-calentadorPre-heaterPL

PrecipitadorPrecipitatorPP

Pre-condensadorPre-condenserPC

Pre-desaguadorPre-dewaterPD

PrensaPressPR

Prensa de rechazosPress, rejectPZ

Prensa hmedaPress, wetPH

Puente gruaCranePT

PulperPulperPU

PurgadorPurgerPG

Purificador de aceiteOil purifierPF

QuemadorBurnerQM

RaggerRaggerRG

RaspadorDoctorRA

ReactorReactorRT

RebobinaderRewinderRB

Recipiente de presinVesselsRP

Reductor de velocidadGear boxRV

Refinador cnicoRefiner, conicRC

Refinador de discoRefiner, discRE

RegaderaShowerRG

ReglaRulerRL

RodilloRollIR

Rodillo mount hopeRoll, mount hopeRM

Rollo guaRoll, guideRO

ScavengerScavengerSV

Secador de aireDryer, airSA

Separador centrifugoCentrifugal separatorSE

Separador de condensadoCondensate separatorSC

Separador de metalesMetal separatorSM

Separador de polvillo/sopladorDust separator/blowerSP

SilenciadorSilencerSL

SiloSiloSI

Sistema de lubricacin centralLubrication system, centralLU

EQUIPMENT IDENTIFICATION CODES (cont.)annex V

SpanishEnglishEquipment Code

Sistema de lubricacin por aceiteLubrication system, oilLA

Sistema de lubricacin por grasaLubrication system, greaseLS

Super calandriaSuper calanderSR

TanqueTankTQ

TermocompresorTermocompressorTM

Tornillo DenverDenver ScrewTD

TolvaContainerTO

Torre de alta densidadHigh density towerTD

Torre de blanqueoBleaching towerTB

Torre de EnfriamientoCooling TowerTE

Transportador de cadenaConveyor, chainTN

Transportador de correaConveyor, beltTC

Transportador, generalConveyor, generalTR

Transportadora de rolasLog conveyorTL

Triturador de cortezaBark .....TT

Tumbador de bobina

TU

TurbinaTurbineTI

Unidad de enfriamientoCooling unitUE

Unidad de LubrificacinLubrication unitUL

Unidad hidrulicaHydraulic unitUH

Vlvula de cuchilloKnife valveVC

Vlvula, generalValveVG

Variador de velocidadFrequency converterVV

VentiladorFanVE

VertederoWeirVT

VibradorVibratorVI

ELECTRICAL EQUIPMENT IDENTIFICATION CODESannex V

SpanishEnglishEquipment Code

AlimentadorFeederAL

Aparato de iluminacinLighting deviceAI

Auto transformadorAutotransformerAT

Banco de baterasBattery bankBB

BaterasBatteriesBA

Conversor elctricoElectric converterCE

Conversor inversor de frecuenciaFrequency converterCI

Centro de control de motoresMotor control centerCM

Cabina de seccionamientoSwitchgearCS

CapacitorCapacitorCP

Caja de comando localConsoleCL

Caja auxiliar (pasaje)Junction boxC

Ducto de barrasBus bar ductDB

DisjuntorBreakerDJ

ExcitatrizExciterE

FusiblesFusesFU

Generador elctricoElectrical generatorGE

Motor elctricoElectrical motorM(*)

Panel de medicinMeasuring panelPM

Panel de comandoCommand panelPC

Panel del CLPCLP panelPL

Panel de proteccinProtection panelPP

Para rayosLightning arresterPR

Cuadro de distribucin de iluminacinIlluminating panelCD

RetificadorRectifierRF

Resistor de calentamientoHeating resistorRA

Resistor de aterramientoGrounding resistorRT

Sub estacin unitariaUnit substationSU

Transformador de corrienteCurrent transformer TC

Transformador de distribucinDistribution transformerTD

Transformador de fuerzaPower transformerTF

Transformador de iluminacinIlluminating transformerTI

Transformador de PotencialPotential transformerTP

Vareador electromagntico

VM

(*) the electrical motors will be identified by the equipment tag number followed by the letter M. For example:

- the motor for the pump BAT-BO-101 will be BAT-BO-101M

ANNEX VI

Plotting Instructions

PLOTTING INSTRUCTIONSannex VI

LINE COLORS AND THICKENESS FOR FLOWSHEETS DRAWING AND PLOTTING

DESCRIPTIONCOLORPen1 : 2 (sulfite)Thickness1 : 1 (vegetal)REMARK

EQUIPMENTCYAN0.450.55Equipment number and name also en cyan. Other text in green

STOCK FLOWCYAN

Shall be a polyline with width = 3

GENERAL PROCESS FLOWGREEN OR YELLOW0.250.35Green is to be used preferentially. Use yellow only if it is necessary

WATER FLOWBLUE0.250.35

STEAM FLOWRED0.250.35

INSTRUMENTATION AND SINAL LINESMAGENTA0.10.15Text in green

CALL LINES

MAGENTA0.10.15

DASHMAGENTA0.10.15

LINE END BLOCKGREEN0.250.35

SUPPLY LIMITSMAGENTA0.10.15texts in green

DESCRIPTIONCOLORPen1 : 2 (sulfite)Thickness1 : 1 (vegetal)REMARK

TEXTSGREEN0.250.35FONT to be ROMANS. The heights are indicated in annex IV

SHEET STANDARD FORMAT

Internal margin

External margin

Numbers and letters

DivisionsFLOOR, SEWERS

WHITE

MAGENTA

GREEN

WHITE

YELLOW0.45

0.10

0.25

0.45

0.250.55

0.15

0.35

0.55

0.35

LEGENDSAME COLOR OF WHAT IT REFERS

STAMPSEE ANNEX I

INCRUSTAR Excel.Sheet.8

INCRUSTAR Excel.Sheet.8

INCRUSTAR Excel.Sheet.8

INCRUSTAR Excel.Sheet.8

INCRUSTAR Excel.Sheet.8

IN PRC001doc

1_______________________________________________________________________________________

INGENIERIA DE PROCESOS C.A.

e-mail: [email protected] Tel. 0241 823 2928 Valencia Venezuela

INPROC001.doc

2________ ______________________________________________________________________________

INGENIERIA DE PROCESOS C.A.

e-mail: [email protected] Tel. 0241 823 2928 Valencia Venezuela

_965552111.xlsHoja1

8 WH C3F- 107 B11 (2)

insulation code (thickness)BAT - TQ - 204number

sequential numberPULP TANKdenominationBAT - 345

pipe specification code4000 x 6000 mmdimensionsBAT - BO - 125numbersequential number

media code75 m3 - 10 min.volume - retention time10500 l/minnominal flowarea code

nominal diameter3.5%consistencyH = 45 mwgmanometric height

50 Ctemperature

FV - 134

function code

FE - 134sequential number

FC 134

Hoja2

Hoja3

_968392091.xlsHoja1

8 WH C3F- 107 B11 (2)

insulation code (thickness)BAT - 204number

sequential numberPULP TANKdenominationBAT - 345

pipe specification code4000 x 6000 mmdimensionsBAT - BO - 125numbersequential number

media code75 m3 - 10 min.volume - retention time10500 l/minnominal flowarea code

nominal diameter3.5%consistencyH = 45 mwgmanometric height

50 Ctemperature

FV - 134

function code

FE - 134sequential number

FC 134

Hoja2

Hoja3

_1077615021.xlsHoja1

8 WH C3F- 107 B11 (2)

insulation code (thickness)BAT - 204number

sequential numberPULP TANKdenominationBAT - 345

pipe specification code4000 x 6000 mmdimensionsBAT - BO - 125numbersequential number

media code75 m3 - 10 min.volume - retention time10500 l/minnominal flowarea code

nominal diameter3.5%consistencyH = 45 mwgmanometric height

50 Ctemperature

FV - 134

function code

FE - 134sequential number

FC 134

Hoja2

Hoja3

_960974931.xlsHoja1

8 WH C3F- 107 B11 (2)

insulation code (thickness)BAT - 204number

sequential numberPULP TANKdenominationBAT - 345

pipe specification code4000 x 6000 mmdimensionsBAT - BO - 125numbersequential number

media code75 m3 - 10 min.volume - retention time10500 l/minnominal flowarea code

nominal diameter3.5%consistencyH = 45 mwgmanometric height

50 Ctemperature

FV - 134

function code

FE - 134sequential number

FC 134

Hoja2

Hoja3

_960974970.xlsHoja1

8 WH C3F- 107 B11 (2)

insulation code (thickness)BAT - 204number

sequential numberPULP TANKdenominationBAT - 345

pipe specification code4000 x 6000 mmdimensionsBAT - BO - 125numbersequential number

media code75 m3 - 10 min.volume - retention time10500 l/minnominal flowarea code

nominal diameter3.5%consistencyH = 45 mwgmanometric height

50 Ctemperature

FV - 134

function code

FE - 134sequential number

FC 134

Hoja2

Hoja3

_956432301.doc