NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 44 - BRONX, 1825 PROSPECT AVENUE, BRONX, NY, 10457School:
4970 2019-05-22 08:52AM 2019-05-28 08:45AMARCHITECTURAL - SENIOR
5004 2019-05-22 08:38AM 2019-05-28 10:13AMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? No
The building is surrounded by scaffolding, Sidewalk Shed and
netting for the ongoing work at the Security Lights, Roof,
Parapet and Exterior Walls, so these components weren’t
accessible for inspection .
Comments on Inaccessible Inspection
Principal(s) Information
Principal Name Melissa Harrow
Principal Organization C.S. 44 David C. Farragut - Bronx
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments:
1.The PA System is deficient and need replacement.
2. The Auditorium Seating is deteriorated and requires
renovations.
3. The Corridor Floors are deteriorated and need refinishing .
Principal Name Lariely Sanchez
Principal Organization 84X598 - Kipp Freedom Middle School
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments:
1. The Interior Plumbing fixtures are deficient and need repairs or
replacement.
2. The Heating and Cooling in the building is inconsistent from
room to room and requires control adjustments or upgrades.
3. The Ceiling on 4th Floor and Auditorium are deteriorated and
need refinishing.
Custodian Was not present
Fireman Toni Cubi
Building Square Footage 72,000
Comments on the Area (Square Feet) N/A
Comments on the Stories (Floors) plus Basements 4+B+PH
Comments on the Year Built 1911
Comments on the Student Population 385
Comments on the Staff Population 61
Comments on the Number of Classrooms 49
Weather Fair
Facade Photo
Corner of Prospect Avenue and E 176th Street - West View
Page 1 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural InspectionMain Entrance Photo
Facade A - Prospect Avenue
Roof Photo
Roof 1 - North View
Have any Systems/Major Building Components been upgraded? Systems: Foundation Wall/ Slab waterproofing (Electrical Panel
Room), Exterior Stair repairs (partial), Schoolyard
repaying (partial )
Years: 2013
Systems: Exterior Stair repairs (partial )
Years: 2009
Systems: HC Student Toilet Room upgrades
Years: 2008
Systems: Parapet, Exterior Masonry repairs (partial )
Years: 2004
Systems: Roofing,Windows/Guards replacement (full)
Years: 1999
Have there been any New Building Additions? No New Construction
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Missing Interior Fire
DoorsMissing door poses a
potential safety hazard
Classrooms/C
orridors/Admi
n Space
Door(s)
Corridor near
Room 105
Toni CubiYes Fireman
Page 2 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Physical Breakdown Structure Exists Complies Required Deficiency
FUNCTIONAL ACCESSIBILITY
Exterior Routes
NoExterior Entrances & Exits
DOOR WIDTH < 36"
NoNoExterior H/C Lifts
NoNoExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
NoYesInterior Corridor Doors And Hardware
YesInterior Corridors & Lobbies
NoInterior Elevators
YesInterior Lobby Doors And Hardware
NoInterior Ramps
Rooms & Spaces
Art Rooms
Yes NoRoom 312 (C.S. 44), 404 (Kipp Freedom
M.S.)
NOT ON ACCESSIBLE ROUTE
Auditorium
Yes No1st Floor
NOT ON ACCESSIBLE ROUTE
Cafeteria
Yes YesBasement
Classrooms
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Computer Rooms
Yes NoRoom 308
NOT ON ACCESSIBLE ROUTE
Gymnasium
Yes No4th Floor
NOT ON ACCESSIBLE ROUTE
NoLibrary
Main Office
Yes NoRoom 155(C.S. 44), 402(Kipp Freedom
M.S.)
NOT ON ACCESSIBLE ROUTE
Multi-purpose Room
Yes YesBasement
Nurse's Office
Yes NoRoom 158
NOT ON ACCESSIBLE ROUTE
NoPool
NoScience Lab
Page 3 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Physical Breakdown Structure Exists Complies Required Deficiency
Toilet Rooms (boys)
Yes YesRoom B18
Toilet Rooms (girls)
Yes YesRoom B4
Toilet Rooms (staff)
Yes NoNone on Accessible Route
NOT ON ACCESSIBLE ROUTE
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
Does not existAREAWAY
Does not existAWNINGS AND CANOPIES
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Under constructionCOPING
Under constructionCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL CLAD:DETERIORATED DOOR AND FRAME -
MINOR DETERIORATION
Deficiency
Page 4 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - Main Entrance
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existEXTERIOR SOFFITS
Under constructionEXTERIOR WALLS
Does not existLOADING DOCK
InaccessibleLOUVER
Under constructionPARAPETS
Does not existPLAZA DECK
Under constructionROOF
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 5- Poor
STONE:CRACKS/SPALLING - MAJORDeficiency
Deficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 5 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo 1
Facade A - Main Entrance
Violations No violations recorded
InspectedRAILINGS
Condition 3- Fair
RUST - MINORDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 2Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - Main Entrance
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 4- Between Fair and Poor
STONE:DETERIORATED SUBSTRATEDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE SUBSTRATE AND RESET
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 6 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo 1
Facade F
Violations No violations recorded
STONE:WORN-OUT TREAD/RISER/NOSINGDeficiency
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
STONE:OPEN JOINTSDeficiency
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 7 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo 1
Facade F
Violations No violations recorded
InspectedWINDOWS
11,000Replacement Quantity
Replacement Uom S.F.
InaccessibleEXTERIOR GUARDS
InaccessibleLINTELS
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:All Facades Inspected
3- FairInstance Condition
Instance Quantity 11,000
Instance Quantity Uom S.F.
Installation Year 1999
Source of Installation Year Documented
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (409 Seats) Inspected
Ceiling
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (409 Seats) Does not exist
Fixed Seating
Instance on 1st Floor (409 Seats) Inspected
3- FairInstance Condition
DAMAGED/BROKEN/INOPERABLEDeficiency
Seats A/101, B/214, F/202, H/111, J/106 and other locationsDeficiency Location/Instance
24Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 8 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Fixed Seating
Deficiency Photo 1
Seat F/202
Violations No violations recorded
Floor Finish
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Near Stage, Near Entrance, Center AisleDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Stage
Violations No violations recorded
Sliding-folding Partition
Instance on 1st Floor (409 Seats) Does not exist
Stage
Instance on 1st Floor (409 Seats) Inspected
Stage
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (409 Seats) Does not exist
Stage Curtains
Instance on 1st Floor (409 Seats) Does not exist
Walls
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (409 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
CAFETERIA
Page 9 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Does not exist
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Near Stair A, Exit, KitchenDeficiency Location/Instance
100Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Stair A
Violations No violations recorded
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 4- Between Fair and Poor
WOOD:DETERIORATED DOORDeficiency
Room 301, 312Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
Page 10 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 301
Violations No violations recorded
METAL:DETERIORATED DOORDeficiency
Room 108Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 105
Deficiency Photo 2
Room 108
Violations No violations recorded
METAL:MISSING DOORDeficiency
Corridor near Room 105Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Corridor near Room 106
Page 11 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Main Entrance Lobby, Corridor near Room 106, 212, 317, 406
and other locations
Deficiency Location/Instance
500Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Lobby
Violations No violations recorded
VINYL TILES:DETERIORATED SUBSTRATEDeficiency
Room 305, Corridor near Stair E/3, Corridor near Auditorium,
Corridor near Room 305
Deficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Stair E/3
Violations No violations recorded
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
GYMNASIUM
Instance on 4th Floor Inspected
Ceiling
Instance on 4th Floor Under construction
Door(s)
Instance on 4th Floor Inspected
3- FairInstance Condition
WOOD:DETERIORATED DOORDeficiency
EntranceDeficiency Location/Instance
Page 12 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Door(s)
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Entrance
Violations No violations recorded
Fixed Equipment
Instance on 4th Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 4th Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on 4th Floor Does not exist
Sliding-folding Partition
Instance on 4th Floor Does not exist
Stage
Instance on 4th Floor Does not exist
Walls
Instance on 4th Floor Inspected
2- Between Good and FairInstance Condition
WALL PADDING:DETERIORATEDDeficiency
Southwest, Northeast of RoomDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Southwest of Room
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 4th Floor Does not exist
InspectedINTERIOR DOOR HARDWARE
Page 13 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
INTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
METAL PAN:DAMAGED/MISSINGDeficiency
Prep, Near SinkDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Prepare
Violations No violations recorded
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLIBRARY
Does not existLOCKER ROOM
MULTI-PURPOSE ROOM
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Page 14 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
MULTI-PURPOSE ROOM
Fixed Equipment
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Near ExitDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Exit
Violations No violations recorded
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
Does not existPOOLS
SCIENCE DEMO ROOM
Instance on Room 313 Inspected
NoAlternative Use
Fixed Equipment
Instance on Room 313 Inspected
2- Between Good and FairInstance Condition
CABINETRY:MISSING/DAMAGEDDeficiency
Room 313Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 15 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
SCIENCE DEMO ROOM
Fixed Equipment
Deficiency Photo 1
Near Room 313
Violations No violations recorded
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? 1
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 3- Fair
METAL:DETERIORATED DOORDeficiency
Stair C/BasementDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/Basement
Violations No violations recorded
InspectedPartition
Condition 2- Between Good and Fair
GLASS PANEL:DAMAGED/DETERIORATEDDeficiency
Stair A/BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 16 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Partition
Deficiency Photo 1
Stair A/Basement
Violations No violations recorded
METAL FRAME:DAMAGED/DETERIORATEDDeficiency
Stair A/Basement, C/4Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/Basement
Violations No violations recorded
METAL PANEL:DAMAGED/DETERIORATEDDeficiency
Stair C/3Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/3
Violations No violations recorded
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
ROLLED ASPHALT:CRACKSDeficiency
Stair B/3, C/4, Main Entrance Vestibule, F/Basement and other
locations
Deficiency Location/Instance
Page 17 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair B/3
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Stair C/1, 4, E/1, 4Deficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair C/1
Violations No violations recorded
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Stair A/Basement, B/2, E/1, 3, F/Basement and other locationsDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair E/3
Violations No violations recorded
InspectedSTRUCTURAL
Page 18 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 3- Fair
STEEL COLUMNS/BEAMS:DETERIORATED MASONRY
FIREPROOFING
Deficiency
Basement - Storage AreaDeficiency Location/Instance
30Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Basement- Storage Area
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 3- Fair
CINDER CONCRETE ARCH:METAL PAN DETERIORATED,
SPALLED
Deficiency
Basement - Storage Area, Boiler RoomDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Basement - Storage Area
Violations No violations recorded
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
Gas Meter Room, Boiler RoomDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Page 19 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo 1
Gas Meter Room
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 4- Between Fair and Poor
CONCRETE:WATER INFILTRATION IN ELECTRICAL
PANEL ROOM
Deficiency
Electrical Meter RoomDeficiency Location/Instance
150Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Electrical Meter Room
Violations 35213756R
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 20 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
INTERIOR
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 2- Between Good and Fair
METAL:DETERIORATED DOORDeficiency
3rd Floor BoysDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
InspectedCONTAINERIZATION
Condition 4- Between Fair and Poor
CONTAINER DAMAGEDDeficiency
Parking LotDeficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Parking Lot
Violations No violations recorded
CONCRETE PAD MISSINGDeficiency
Parking LotDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL NEW
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Violations No violations recorded
Page 21 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
SITE
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
Does not existDRAINAGE SYSTEM FOR SOIL
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 4- Between Fair and Poor
WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency
Along Prospect Avenue, East 176 StreetDeficiency Location/Instance
360Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Prospect Avenue
Violations No violations recorded
WROUGHT IRON:RUST - MAJORDeficiency
Along Prospect Avenue, East 176 StreetDeficiency Location/Instance
560Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along East 176 Street
Violations No violations recorded
CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency
Along Prospect Avenue, East 176 Street, Southwest of BuildingDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
Page 22 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
SITE
FENCES
LEVEL 2Purpose of Action
Deficiency Photo 1
Southwest of Building
Violations No violations recorded
CHAIN LINK:DAMAGED POST/RAILDeficiency
Southwest of BuildingDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Southwest of Building
Violations No violations recorded
CHAIN LINK:DAMAGED/DETERIORATEDDeficiency
Southwest of BuildingDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Southwest of Building
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED CURBSDeficiency
Along Prospect Avenue, East 176 StreetDeficiency Location/Instance
Page 23 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
25Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Prospect Avenue
Violations No violations recorded
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Prospect Avenue, East 176 StreetDeficiency Location/Instance
225Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along East 176 Street
Violations No violations recorded
HEAVINGDeficiency
Along East 176 StreetDeficiency Location/Instance
50Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along East 176 Street
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Page 24 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2018-2019
X044Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
InaccessibleAsphalt
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
InspectedAsphalt
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedConcrete
3- FairCondition
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along Prospect Avenue, East 176 StreetDeficiency Location/Instance
150Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Prospect Avenue, East 176 Street
Violations No violations recorded
Does not existPavers
Does not existStudent Use
Does not existPLAYGROUNDS
Does not existPLAYING SURFACE
InaccessibleRETAINING WALLS
Does not existSEATING
Does not existSITE WALLS (NOT RETAINING WALLS)
Does not existSTAIRS/RAMPS: EXTERIOR
Page 25 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)