Asset: P.S. 361 (OLD 89) - BROOKLYN, 3109 NEWKIRK AVENUE, New York, 11226 Inspection Id Inspection Type Time In Last Edited SA : K864 Architectural - Senior 2019-01-03 8:59 AM 2019-01-14 11:12 AM AA : K864 Architectural - Associate 2019-01-03 8:32 AM 2019-01-03 6:55 PM Asset Data Question Answer Was the building fully accessible for inspection Yes Principal(s) Information Principal Name Mary Magruder Organization Success Academy - Brooklyn Did you meet with this Principal? No Did this Principal provide feedback? No Custodian Matty Turturici Fireman Gilbert Rosario Building Square Footage 57000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B+Attic Comments on the Number of Classrooms 27 Comments on the Year Built 1897 Student Population 285 Staff Population 67 Weather Fair Facade Photo Corner of Newkirk Avenue and E 32nd Street-Northwest View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 K864 PB/A&W Print Date: 6/21/2019 Page 1 of 45

Transcript of NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of...

Page 1: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Asset: P.S. 361 (OLD 89) - BROOKLYN, 3109 NEWKIRK AVENUE, New York, 11226

Inspection Id Inspection Type Time In Last Edited

SA : K864 Architectural - Senior 2019-01-03 8:59 AM 2019-01-14 11:12 AM

AA : K864 Architectural - Associate 2019-01-03 8:32 AM 2019-01-03 6:55 PM

Asset Data

Question Answer

Was the building fully accessible for inspection Yes

Principal(s) Information

Principal Name Mary Magruder

Organization Success Academy - Brooklyn

Did you meet with this Principal? No

Did this Principal provide feedback? No

Custodian Matty Turturici

Fireman Gilbert Rosario

Building Square Footage 57000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B+Attic

Comments on the Number of Classrooms 27

Comments on the Year Built 1897

Student Population 285

Staff Population 67

Weather Fair

Facade Photo

Corner of Newkirk Avenue and E 32ndStreet-Northwest View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 1 of 45

Page 2: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Main Entrance Photo

Facade A-Newkirk Avenue

Roof Photo

Roof 5-Northeast View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Exterior Entrance Doors upgraded (3); MultipurposeRoom (Room 111), Upgrades to Multipurpose Room (3rdFloor-Cafeteria), Multipurpose Room (3rdFloor-Gymnasium)

Year: 2018

Systems: Waterproofing Exterior Walls

Year: 2015

Systems: Partial Exterior Walls repointed, Partial Shingle Roofingrepairs

Year: 2013

Systems: Exterior Face Brick replacement at rear Walls

Year: 2006

Systems: Roofs, Windows, Exterior Guards replacement;Swimming Pool repairs

Year: 1998

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 2 of 45

Page 3: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No Missing InteriorFire Doors

Missing FireDoor is apotential safetyhazard

INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Door(s)

Corridor nearRoom 104

Gilbert Rosario Fireman

No Missing InteriorFire Doors

Missing FireDoor is apotential safetyhazard

INTERIOR |STAIRS/RAMPS: INTERIOR |Door(s)

StairG/Basement

Gilbert Rosario Fireman

No Potential FallingDebris

Damaged andloose ceilingtiles are apotential safetyhazard.

INTERIOR |CLASSROOMS/CORRIDORS/ADMINSPACES |Ceiling

Room 211 Gilbert Rosario Fireman

Yes Tripping Hazard Large gaps (3")in safety mats isa potentialsafety hazard.

SITE |PLAYGROUNDS | SafetySurfacing

West side ofwest Playground

Gilbert Rosario Fireman

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No Yes

Interior Routes

Corridor and Lobby H/C Lifts No Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 3 of 45

Page 4: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Interior Routes

Interior Ramps No

Rooms & Spaces

Art Rooms Room 104 Yes No Not on Accessible Route

Auditorium No

Cafeteria No

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms No

Gymnasium No

Library No

Main Office Room 109 Yes No Not on Accessible Route

Multi-purpose Room Room 111, 3rd Floor-Gymnasium, 3rdFloor-Cafeteria

Yes No Not on Accessible Route No Yes

Nurse's Room Room 107A Yes No Not on Accessible Route

Pool Basement Yes No Not on Accessible Route

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1

Instance Condition 3 - Fair

Instance Quantity 1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 4 of 45

Page 5: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

AREAWAY

Instance Quantity Uom EACH

Deficiency AREAWAY STAIRS: DETERIORATEDTREADS/RISERS/NOSINGS

Roof Plan reference

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

AW1

Violations No violations recorded.

Deficiency AREAWAY SLAB: CRACKS AND SPALLING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 5 of 45

Page 6: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW1

Violations No violations recorded.

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 3 - Fair

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

CH1

Violations No violations recorded.

COPING Inspected

Condition 3 - Fair

Deficiency CAST STONE: CRACKED/BROKEN PIECES

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 6 of 45

Page 7: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

COPING

Roof Plan reference

Deficiency Quantity 55

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 6

Violations No violations recorded.

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 7 of 45

Page 8: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade E-Door I, H

Violations No violations recorded.

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 4

Deficiency Photo1

Facade H-Exit C3

Violations 35290250Z

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 8 of 45

Page 9: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

Deficiency Photo1

Facade B-Exit B2

Violations 35290250Z

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 4 - Between Fair and Poor

Deficiency WOOD: EXCESSIVELY WEATHERED

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 9 of 45

Page 10: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

DOORS

TRANSOM/SIDE LIGHT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A-Main Entrance

Violations No violations recorded.

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 23,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 23,000

Instance Quantity Uom S.F.

Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 10 of 45

Page 11: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade C

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 11 of 45

Page 12: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 12 of 45

Page 13: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade H

Violations No violations recorded.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 4,000

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 3 - Fair

Instance Quantity 4,000

Instance Quantity Uom C.F.

Deficiency BRICK: MINOR CRACKS, SPALLING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 13 of 45

Page 14: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

PARAPETS

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 5

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 13,700

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Does not Exist

ROOF CAGE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Asphalt Shingle: Roofs 1, 7

Instance Condition 4 - Between Fair and Poor

Instance Quantity 4,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 14 of 45

Page 15: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Dunnage Steel less than 18" above the Roofing?

Installation Year 1998

Source of Installation Custodial Staff

Deficiency ASPHALT SHINGLE: ROOFING: DAMAGED, WORN-OUT ORMISSING SHINGLES CURLING UP

Roof Plan reference

Deficiency Quantity 35

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 7

Violations No violations recorded.

Deficiency ASPHALT SHINGLE: ROOFING: MAJOR ACTIVE ROOF LEAKSIN INSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE ROOFING

Urgency of Action PRIORITY 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 15 of 45

Page 16: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Purpose of Action LEVEL 2

Deficiency Photo1

Room 308 (Roof 7)

Violations No violations recorded.

Deficiency ASPHALT SHINGLE: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Asphalt Shingle: Roofs 1, 7

Deficiency Quantity 4,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

InspectedInstance on Built-Up: Roofs 2-6, 8, 11-15

Instance Condition 4 - Between Fair and Poor

Instance Quantity 8,700

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1998

Source of Installation Custodial Staff

Deficiency BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 16 of 45

Page 17: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Deficiency Photo1

3rd Floor Multipurpose Room / Cafeteria (Roof 4)

Violations No violations recorded.

Deficiency BUILT-UP: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Built-Up: Roofs 2-6, 8, 11-15

Deficiency Quantity 8,700

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

InspectedInstance on Modified Bitumen: Roofs 9, 10, 16

Instance Condition 3 - Fair

Instance Quantity 1,000

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 1998

Source of Installation Custodial Staff

Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE

Deficiency Location/Instance Modified Bitumen: Roofs 9, 10, 16

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 3 - Fair

Deficiency DETERIORATED

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 17 of 45

Page 18: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

ROOF

Roofing

ROOFING DRAINS

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 5

Violations No violations recorded.

Specialties Inspected

BULKHEAD/PENTHOUSE Does not Exist

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inspected

Material Type(s) Plastic

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLING - MINOR

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 18 of 45

Page 19: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Roof Plan reference

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A- Main Entrance

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 6,700

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 3 - Fair

Deficiency RUST - MINOR

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 19 of 45

Page 20: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

WINDOWS

EXTERIOR GUARDS

Elevation

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades except Facades C and G

Instance Condition 3 - Fair

Instance Quantity 6,700

Instance Quantity Uom S.F.

Installation Year 1998

Source of Installation Custodial Staff

Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 20 of 45

Page 21: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

EXTERIOR

WINDOWS

WINDOWS

Elevation

Deficiency Quantity 134

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

INTERIOR Inspected

POOLS Inspected

Instance Basement

CEILING

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency PLASTER/CONCRETE: CRACKS, SPALLING

Deficiency Location/Instance Basement Pool

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Basement Pool

Violations No violations recorded.

DECK/FLOOR

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILES: BROKEN/MISSING/WORN TILES

Deficiency Location/Instance Basement Pool

Deficiency Quantity 15

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 21 of 45

Page 22: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

POOLS

DECK/FLOOR

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Pool

Violations No violations recorded.

DIVING BOARD

Does not ExistInstance on Basement

POOL LINING

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF STRUCTURE

Does not ExistInstance on Basement

SEATING

Does not ExistInstance on Basement

WALLS

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement -Pool Equipment Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 22 of 45

Page 23: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Deficiency Photo1

Basement-Pool Equipment Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement-Boiler Room

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Masonry

Condition 3 - Fair

Deficiency BRICK: OPEN JOINTS

Deficiency Location/Instance Basement - Boiler Room

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPOINT

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 23 of 45

Page 24: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency BRICK: CRACKED/SPALLED

Deficiency Location/Instance Basement-Pool Equipment Room, Electrical Roomqq

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Pool Equipment Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Does not Exist

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Room 211

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 24 of 45

Page 25: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo1

Room 211

Violations No violations recorded.

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Rooms 207A, 212

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 207A

Violations No violations recorded.

Deficiency METAL PAN: DAMAGED/MISSING

Deficiency Location/Instance Room 307

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 307

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 25 of 45

Page 26: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency METAL PAN: DAMAGED/MISSING - ACTIVE LEAK

Deficiency Location/Instance Room 308

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Room 308

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 308A

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 308A

Violations No violations recorded.

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: MISSING DOOR

Deficiency Location/Instance Vestibules in Rooms 102, 202

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 26 of 45

Page 27: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency Photo1

Room 202 Vestibule

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Room 302

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 302

Violations No violations recorded.

Deficiency WOOD: MISSING DOOR

Deficiency Location/Instance Corridor near Room 104

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Corridor near Room 104

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 27 of 45

Page 28: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Main Entrance Vestibule, Rooms 201, 210, 212, 306, 307, and others

Deficiency Quantity 10

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 307

Violations No violations recorded.

Floor Finish Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED SUBSTRATE

Deficiency Location/Instance Rooms 200, 207, 302, 305

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 305

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Rooms 205, 307, 308, Corridor near Rooms 200, 206, and others

Deficiency Quantity 1,900

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 28 of 45

Page 29: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 307

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 207A, 308A

Deficiency Quantity 120

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 308A

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

Deficiency Location/Instance Room 308

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 29 of 45

Page 30: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Walls Inspected

Room 308

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Does not Exist

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on Basement

Ceiling

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Basement

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Does not Exist

LOCKER ROOM Inspected

InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)

Alternative use Yes

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Alternative use Yes

Ceiling

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Condition 4 - Between Fair and Poor

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Vestibule

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 30 of 45

Page 31: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

LOCKER ROOM

Ceiling

Deficiency Photo1

Vestibule

Violations No violations recorded.

Door(s)

InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Locker Room Lockers

InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Basement - Room 09 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Basement - Room 08 (400SF, 28 Lockers)

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

MULTI-PURPOSE ROOM Inspected

InspectedInstance on Room 111

InspectedInstance on 3rd Floor - Cafeteria

InspectedInstance on 3rd Floor - Gymnasium

Ceiling

InspectedInstance on 3rd Floor - Cafeteria

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 31 of 45

Page 32: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Ceiling

Deficiency Location/Instance Left side near windows

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Left side near windows

Violations No violations recorded.

Door(s)

InspectedInstance on 3rd Floor - Cafeteria

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Storage Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Storage Room

Violations No violations recorded.

Fixed Equipment

Does not ExistInstance on Room 111

Does not ExistInstance on 3rd Floor - Cafeteria

Does not ExistInstance on 3rd Floor - Gymnasium

Floor Finish

InspectedInstance on 3rd Floor - Cafeteria

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on 3rd Floor - Gymnasium

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 32 of 45

Page 33: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Floor Finish

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Room 111

Condition 1 - Good

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on Room 111

Does not ExistInstance on 3rd Floor - Cafeteria

Does not ExistInstance on 3rd Floor - Gymnasium

Stage

Does not ExistInstance on 3rd Floor - Cafeteria

Does not ExistInstance on 3rd Floor - Gymnasium

Does not ExistInstance on Room 111

Walls

InspectedInstance on 3rd Floor - Gymnasium

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Opposition of windows

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Opposite of windows

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on Room 111

Does not ExistInstance on 3rd Floor - Cafeteria

Does not ExistInstance on 3rd Floor - Gymnasium

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Inspected

InspectedInstance on Basement

Alternative use Yes

Ceiling

Not RequiredInstance on Basement

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 33 of 45

Page 34: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

SHOWER ROOM

Door(s)

Does not ExistInstance on Basement

Floor Finish

Not RequiredInstance on Basement

Walls

Not RequiredInstance on Basement

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Partially

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 4 - Between Fair and Poor

Deficiency METAL CLAD WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stair BD/Basement

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BD/Basement

Violations No violations recorded.

Deficiency WOOD: MISSING DOOR

Deficiency Location/Instance Stair G/Basement

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Stair G/Basement

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 34 of 45

Page 35: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s) Inspected

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency GLASS PANEL: DAMAGED/DETERIORATED

Deficiency Location/Instance Stair BD/1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BD/1

Violations No violations recorded.

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance Stair G/Basement

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair G/Basement

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 35 of 45

Page 36: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Location/Instance Stairs AC/1, BD/3, G/Basement, 1

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair BD/3

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stairs AC/3, F/3

Deficiency Quantity 35

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair F/3

Violations No violations recorded.

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Inside Room 207A

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 36 of 45

Page 37: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

TOILET ROOMS - STAFF

Door(s)

Purpose of Action LEVEL 2

Deficiency Photo1

Inside Room 207A

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Inside Room 308A

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Inside Room 308A

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 37 of 45

Page 38: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room B1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room B1

Violations No violations recorded.

Stalls Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency CONCRETE PAD DAMAGED

Deficiency Location/Instance North side of Building

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 38 of 45

Page 39: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

CONTAINERIZATION

Violations No violations recorded.

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance North side of Building

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED COVER

Deficiency Location/Instance Mini Building - Exit C, Mini Building - Old Main Entrance from East32nd Street

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Mini Building - Exit C

Violations No violations recorded.

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 39 of 45

Page 40: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

Drainage System for Soil

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East 32nd Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance East 32nd Street, Newkirk Avenue

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East 32nd Street

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 40 of 45

Page 41: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

PAVING

Student Non-Use

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Newkirk Avenue, North side of Building

Deficiency Quantity 125

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

North side of Building

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency CRACKS - MINOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 41 of 45

Page 42: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

PAVING

Student Use

Asphalt

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Does not Exist

Pavers Does not Exist

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Main Entrance, East 32nd Street

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

East 32nd Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency DAMAGED CURBS

Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue

Deficiency Quantity 90

Quantity Uom L.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 42 of 45

Page 43: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Newkirk Avenue

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance East 32nd Street, East 31st Street, Avenue D, Newkirk Avenue

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Avenue D

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard - East

InspectedInstance on Schoolyard - West

Benches

InspectedInstance on Schoolyard - West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Does not ExistInstance on Schoolyard - East

Fence

InspectedInstance on Schoolyard - West

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance Entrance from Schoolyard

Deficiency Quantity 50

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 43 of 45

Page 44: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

PLAYGROUNDS

Fence

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Entrance from Schoolyard

Violations No violations recorded.

Pavement

InspectedInstance on Schoolyard - West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard - East

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Play Equipment

InspectedInstance on Schoolyard - East

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

InspectedInstance on Schoolyard - West

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard - West

Condition 3 - Fair

Deficiency DETERIORATED/MISSING

Deficiency Location/Instance West side of west Playground

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 44 of 45

Page 45: NYC Department of Education - NYCSCAPotential Action REPLACE Urgency of Action PRIORITY 4 Purpose of Action LEVEL 2 NYC Department of Education Architectural Inspection Building Condition

Question Response

SITE

PLAYGROUNDS

Safety Surfacing

Deficiency Photo1

West side

Violations No violations recorded.

Unpaved Area

Does not ExistInstance on Schoolyard - East

Does not ExistInstance on Schoolyard - West

PLAYING SURFACE Does not Exist

RETAINING WALLS Does not Exist

SEATING Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

K864

PB/A&W Print Date: 6/21/2019Page 45 of 45