49
NYC Department of Education Building Condition Assessment Survey 2007-2008 M477 Architectural Inspection Inspection Type Last Edited Time In InspectionId STUYVESANT HS (NEW) - MANHATTAN, 345 CHAMBERS STREET, MANHATTAN, NY, 10282 School: 998032 2007-10-10 09:38AM 2008-06-11 03:37PM ARCHITECTURAL - SENIOR 1107825 2007-10-10 09:21AM 2008-01-31 04:33PM ARCHITECTURAL - JUNIOR Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principle(s) Information Principal Name Stanley Teitel Principal Organization Stuyvesant HS Meeting with Principal? Yes Principal Feedback The principal had the following comments: 1. His primary concern is the constant break down of classroom incremental units. Currently about 10% are not working. 2. Lack of adequate service contracts prevents properly servicing of some building equipment. 3. The electronic system controlling clock time is not working everywhere. Currently over 156 clocks are not working properly. 4.The Gyms lack any air conditioning and have few operable windows for natural ventilation. The extensive glass block areas on the east wall allows too much solar heat gain producing unbearable heat year round. Solar screening is needed for glass block walls plus the installation of more operable windows. 5. Protective screens are needed at electric heat units in Gym and other areas for protection from ball throwing and vandalism. Custodian Edward Mallicoat Fireman Tom Bulger Comments on the Area (Square Feet) 420,000 Comments on the Stories (Floors) plus Basements 10+Penthouse+Partial Basement Comments on the Year Built 1992 Comments on the Student Population 3128 Comments on the Staff Population 266 Comments on the Number of Classrooms 60 Facade Photo View of main facade of building along Chambers Street. Page 1 of 49 Print Date: 7/17/2008 Mobile Validity Version 2.0 (P)

description

Building inspection of 345 Chambers Street.

Transcript of NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

Page 1: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Inspection Type Last EditedTime InInspectionId

STUYVESANT HS (NEW) - MANHATTAN, 345 CHAMBERS STREET, MANHATTAN, NY, 10282School:

998032 2007-10-10 09:38AM 2008-06-11 03:37PMARCHITECTURAL - SENIOR

1107825 2007-10-10 09:21AM 2008-01-31 04:33PMARCHITECTURAL - JUNIOR

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principle(s) Information

Principal Name Stanley Teitel

Principal Organization Stuyvesant HS

Meeting with Principal? Yes

Principal Feedback The principal had the following comments: 1. His primary

concern is the constant break down of classroom incremental

units. Currently about 10% are not working. 2. Lack of adequate

service contracts prevents properly servicing of some building

equipment. 3. The electronic system controlling clock time is not

working everywhere. Currently over 156 clocks are not working

properly. 4.The Gyms lack any air conditioning and have few

operable windows for natural ventilation. The extensive glass

block areas on the east wall allows too much solar heat gain

producing unbearable heat year round. Solar screening is needed

for glass block walls plus the installation of more operable

windows. 5. Protective screens are needed at electric heat units in

Gym and other areas for protection from ball throwing and

vandalism.

Custodian Edward Mallicoat

Fireman Tom Bulger

Comments on the Area (Square Feet) 420,000

Comments on the Stories (Floors) plus Basements 10+Penthouse+Partial Basement

Comments on the Year Built 1992

Comments on the Student Population 3128

Comments on the Staff Population 266

Comments on the Number of Classrooms 60

Facade Photo

View of main facade of building along Chambers Street.

Page 1 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 2: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural InspectionElevation Photo

View of main entrance at Chambers Street.

Roof Photo

View of main pedestrian roof deck at 5th floor.

Elevator overhaul at passenger car #2Have any Systems/Major Building Components been upgraded? Systems:

2006Years:

Elevator overhaul of #5 car from lobby to pool deck

area.

Systems:

2007Years:

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Priority Condition

No condition recorded

Structural Engineer Required

Condition Description Location DescriptionComponent Affected PhotoImage

No condition recorded

Accessibility

Status

F

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesNoExterior Entrances & Exits

NoNoExterior H/C Lifts

YesNoExterior Ramps and Railings

Interior Routes

YesNoInterior Corridor Doors And Hardware

Page 2 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 3: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

YesNoInterior Corridors & Lobbies

YesNoInterior Elevators

NoNoInterior H/C Lifts

YesNoInterior Lobby Doors And Hardware

YesNoInterior Ramps

Room & Spaces

Art Rooms

Rooms #1006, #1010, #1024 & #1024A Yes Yes

Auditorium

1st Floor Yes Yes

Cafeteria

5th Floor Yes Yes

Class Rooms

1st to 10th Floors Yes Yes

Computer Rooms

Rooms #307, #325, #411, #413, #436 &

#451

Yes Yes

Gymnasium

3rd Floor Yes Yes

6th Floor Yes Yes

Library

6th Floor, Room #615 Yes Yes

NoMulti-purpose Room

Science Lab

Rooms #703, #709, #727, #731, #803,

#807, #811, #815, #827, #903, #911,

#913 & #927.

Yes Yes

Toilet Rooms (boys)

All Floors Yes Yes

Toilet Rooms (girls)

All Floors Yes Yes

Toilet Rooms (staff)

All Floors Yes Yes

Building Template

Page 3 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 4: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Inspection

Question Response

ARCHITECTURAL

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

Does not existAreaway

InspectedAwnings And Canopies

Condition 3- Fair

METAL:DETERIORATION/DAMAGED/MISSING PIECESDeficiency

5th floor roof trellis has rusting beams and supports.Deficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of rusting steel trellis support from 5th floor roof.

Deficiency Photo 2

5th floor roof trellis has rusting beams and supports. View from

above.

Violations No violations recorded

InspectedChimney

Condition 3- Fair

METAL:DENTS, RUSTDeficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 4 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 5: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Chimney

Roof #2 has 2 metal chimney stacks that are rusted.

Violations No violations recorded

InspectedCoping

Condition 3- Fair

CAST STONE:OPEN BED JOINTDeficiency

Deficiency Location/Instance

400Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North facade copings outside cafeteria at roofs #7 & #8 have

deteriorated bed joints.

Deficiency Photo 2

Copings at skylights on roof #8 have lifting copings with

defective bed joints and water infiltration.

Violations No violations recorded

CAST STONE:CRACKED/BROKEN PIECESDeficiency

Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 5 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 6: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Coping

Deficiency Photo 1

Several coping sections cracked at facade E & F at roof #8 fenced

off from 5th floor roof deck.

Deficiency Photo 2

Several coping sections cracked at facade E & F at roof #8 fenced

off from 5th floor roof deck.

Violations No violations recorded

Does not existCornice

InspectedDoors

InspectedDoors and Frames

Condition 2- Between Good and Fair

METAL:DETERIORATED DOOR AND/OR FRAMEDeficiency

1st Floor Hudson River facade at NW Exit doors and service

doors at east facade under pedestrian bridge.

Deficiency Location/Instance

4Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

1st Floor Hudson River facade at NW Exit doors.

Deficiency Photo 2

Service doors at east facade under pedestrian bridge are rusting.

Violations No violations recorded

METAL:DETERIORATED/MISSING HARDWAREDeficiency

North Exit stairs from Stage.Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Page 6 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 7: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Doors

Doors and Frames

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 3Purpose of Action

Deficiency Photo 1

North Exit stairs doors have defective hardware.

Violations No violations recorded

InspectedLintels

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTransom/side Light

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedExterior Soffits

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedExterior Walls

65,000Replacement Quantity

Replacement Uom S.F.

All facadesInstance

Instance Condition 4- Between Fair and Poor

150Instance Quantity

Instance Quantity Uom SF

STONE:CHIPPED/SPALLED/BROKEN PIECESDeficiency

Roof Plan Reference

Elevation

Facades A, H and J primarily with cracks and chipped stone.

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 7 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 8: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Deficiency Photo 1

Uneven settlement has caused numerous granite stone base panels

to crack. Photo taken at facade A.

Deficiency Photo 2

Uneven settlement has caused numerous granite stone base panels

to crack. Photo taken at facade A.

Violations No violations recorded

CAST IN PLACE / PRE-CAST CONCRETE:MINOR CRACKS,

SPALLED, DETERIORATED REBAR

Deficiency

Roof Plan Reference

Elevation

Various locations

150Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A at 2nd & 3rd floors with chipped panels. Composite

panels have too many joints where water is infiltrating and

freezing causing failures.

Violations No violations recorded

BRICK:MINOR CRACKS AND SPALLINGDeficiency

Page 8 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 9: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Roof Plan Reference

Elevation

Facades J, H, F, E & G

500Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Bricks beginning to spall with hairline cracks mainly at dark

maroon bricks at insets along facade F.

Violations No violations recorded

BRICK:OPEN/BAD JOINTSDeficiency

Roof Plan Reference

Elevation

Various locations mainly at walls of upper floor setbacks.

1,000Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 9 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 10: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Deficiency Photo 1

Facade J at 5th floor has missing and/or defective horizontal

sealant which is typical at other locations.

Deficiency Photo 2

Facade H at 1st floor has missing and/or defective horizontal

sealant which is typical at other locations.

Violations No violations recorded

STONE:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Various locations throughout.

600Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Failed joint sealant at stone base panels at Facade A is typical of

other locations.

Page 10 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 11: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Deficiency Photo 2

NE exit vestibule with water damaged drywall ceilings due to bad

sealant at joints in 2nd exterior composite stone panels.

Violations No violations recorded

GLASS BLOCK:CHIPPED/ BROKEN PIECESDeficiency

Roof Plan Reference

Elevation

Facades G & H

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of several glass blocks broken at 5th Boys locker room

along east facade H. Also defective head and sill joints allowing

water infiltration.

Deficiency Photo 2

Overview of east facade H where glass block wall sections have

broken elements and bad jointing at heads and sills.

Violations No violations recorded

METAL PANEL:WATER INFILTRATIONDeficiency

Page 11 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 12: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Roof Plan Reference

Elevation

Facade E at 1st floor NW exit.

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Exterior view of 1st floor Stair Exit H at northwest facade E,

where metal louvers above the doors are leaking water into

building and causing damages to drywall /plaster walls and

ceilings inside.

Deficiency Photo 2

Interior view of water damaged ceiling at 1st floor Stair Exit H

where metal louvers above exit doors are leaking water into

building.

Violations No violations recorded

BRICK:OPEN/BAD JOINTSDeficiency

Roof Plan Reference

Page 12 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 13: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Exterior Walls

Elevation

Facade J.

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade J brick window heads have defective mortar joints and

minor leaks are occurring.

Deficiency Photo 2

Close-up of window heads sealed with temporary spot caulking.

Violations No violations recorded

InspectedLoading Dock

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLouver

Condition 3- Fair

RUSTDeficiency

Cooling Tower equipmentDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Louvers at cooling tower are badly corroded.

Violations No violations recorded

Page 13 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 14: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

InspectedParapets

6,000Replacement Quantity

Replacement Uom C.F.

All FacadesInstance

Instance Condition 3- Fair

6,000Instance Quantity

Instance Quantity Uom CF

BRICK:MINOR CRACKS, SPALLINGDeficiency

Deficiency Location/Instance

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of 5th floor parapet at roof #7 outside Cafeteria. This is

typical of other locations were parapet brick is developing cracks

and spalling from water infiltration.

Deficiency Photo 2

View of south parapet at roof #3 where reinforced concrete

back-up has cracks and missing sections requiring repairs.

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 14 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 15: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Parapets

Deficiency Photo 1

View at 5th floor roof with open gaps at joints and water

infiltration causing spalling of cement stucco finish and rusting of

reinforcement.

Violations No violations recorded

InspectedRoofing

InspectedRoofing

Replacement Quantity 50,300

Replacement Uom S.F.

InspectedFlashing

4- Between Fair and PoorCondition

DAMAGED CAP FLASHINGDeficiency

Deficiency Location/Instance

150Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of exposed ductwork of Pool Pak air handler located at Roof

#9 above 6th floor Gym. Cap flashing appears defective around

roof penetrations and may be contributing to leaks occurring in

the Gym below.

Deficiency Photo 2

At roof #11 above 6th floor Dance Studio the cap flashing is

missing at surrounding walls. Persistent leaks occur in Studio

room below. This may be a contributing factor.

Violations No violations recorded

InspectedHatch

2- Between Good and FairCondition

Page 15 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 16: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Roofing

Hatch

No deficiencies recordedDeficiency

InspectedLadder

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedLeaders, Gutters, Downspouts

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedRoof Barrier

4- Between Fair and PoorCondition

RAILINGS/PANELS:DETERIORATEDDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Damaged and missing railing sections at several roof areas,

including roofs #3, #5, #6, and #11. Photo of broken railing

barrier at roof #4.

Deficiency Photo 2

Missing and damaged railing sections at several roof areas,

including roofs #3, #5, #6, and #11. Photo of missing railing

barrier at roof #1, next to bulkhead door.

Violations No violations recorded

Does not existRoof Cage

InspectedRoof Fence

2- Between Good and FairCondition

CHAIN LINK:RUSTEDDeficiency

Page 16 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 17: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Roofing

Roof Fence

Deficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Outdoor fenced in shop area at 10th floor energy shop has rusting

fence sections.

Deficiency Photo 2

Close-up of outdoor fenced in shop area at 10th floor energy shop

has rusting fence sections.

Violations No violations recorded

InspectedRoofing

All roofs (15 years old)Instance

Instance Condition 4- Between Fair and Poor

50,300Instance Quantity

Instance Quantity Uom SF

PLAZA DECK:PAVERS IN POOR CONDITIONDeficiency

Deficiency Location/Instance

5,000Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 17 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 18: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Roofing

Roofing

Deficiency Photo 1

Damaged deck pavers at roof#3 over 10th floor Energy Shop and

Mechanical Drafting classroom.

Deficiency Photo 2

Damaged deck pavers at roof #11 over Dance Studio.

Violations No violations recorded

BUILT-UP:VEGETATION GROWTHDeficiency

Deficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Vegetation at multiple locations at roofs #6, #10, #11, #14, #16

,etc. Photo of vegetation at roof #11.

Deficiency Photo 2

Heavy vegetation at roof deck pavers at small setback of roof #15

over 1st floor stage exit at facade E. Also, roof is leaking here.

Violations No violations recorded

Page 18 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 19: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Roofing

Roofing

PLAZA DECK:LOCAL LEAKSDeficiency

Deficiency Location/Instance

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of displaced roof pavers at roof #11 where leaks are

occurring into Dance Studio below.

Deficiency Photo 2

View of roof #9 over 6th floor Gym where leaks are occurring at

center section where air handlers are located.

Violations No violations recorded

InspectedRoofing Drains

4- Between Fair and PoorCondition

CLOGGEDDeficiency

Deficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Page 19 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 20: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Roofing

Roofing Drains

Deficiency Photo 1

Partially clogged drains with vegetation at roofs #6, #14 and #16.

Photo of drain at roof #4.

Deficiency Photo 2

View of small setback roof #16 where roof is leaking at drain

location.

Violations No violations recorded

InspectedSpecialties

InspectedBulkhead/Penthouse

InspectedRoof

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedWalls/Windows/Doors

3- FairCondition

OPEN JOINTSDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of bulkhead BH1 northwest wall corner with open

horizontal joints at relieving angle line. Same condition exists at

opposite bulkhead BH2.

Violations No violations recorded

Does not existCupola/ Spires/ Towers

Page 20 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 21: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Roofing

Specialties

Does not existDormer

InspectedDunnage Steel

3- FairCondition

HEIGHT LESS THAN 18"Deficiency

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

HVAC air handler units at Gym rooftop with low clearance

dunnage.

Violations No violations recorded

InspectedSkylight

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedStairs/ramps: Exterior

InspectedBuilding Cheek/flank Walls

Condition 3- Fair

STONE:COPING MISSING/DAMAGEDDeficiency

North facade F at steps to river front park the flanking side walls

have displaced copings.

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Cracked and displaced stone coping at north facade steps.

Page 21 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 22: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Stairs/ramps: Exterior

Building Cheek/flank Walls

Deficiency Photo 2

North facade F at steps to river front park the flanking side walls

have displaced copings.

Violations No violations recorded

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs/ramps

Condition 3- Fair

STONE:CRACKS, SPALLINGDeficiency

North facade F at steps to river front park the stone steps have

several broken treads.

Deficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North facade F at steps to river front park the stone steps have

several broken treads.

Violations No violations recorded

STONE:OPEN JOINTSDeficiency

North facade F at steps to river front park the stone steps have

open or defective joints.

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT AND RECAULK

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North facade F at steps to river front park the stone steps have

open or defective joints.

Violations No violations recorded

Page 22 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 23: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Stairs/ramps: Exterior

Stairs/ramps

CAST IN PLACE CONCRETE:WORN-OUT

TREAD/RISER/NOSING

Deficiency

East facade entrance from West Street has spalling cement coating

at steps.

Deficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East facade entrance from West Street has spalling cement coating

at steps.

Violations No violations recorded

InspectedWindows

20,000Replacement Quantity

Replacement Uom S.F.

InspectedExterior Guards

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLintels

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedShades

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWindows

All facadesInstance

Instance Condition 2- Between Good and Fair

20,000Instance Quantity

Instance Quantity Uom SF

ALUMINUM:AIR/WATER INFILTRATIONDeficiency

Roof Plan Reference

Elevation

Facades E, G, J & A at various locations.

250Deficiency Quantity

Page 23 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 24: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

EXTERIOR

Windows

Windows

Quantity Uom L.F.

Potential Action REPLACE TRIM, SILLS OR WEATHERSTRIPPING

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

View of facade E, where the 7th to 9th floor windows are leaking

water into building at the escalator area and causing damages to

ceilings.

Deficiency Photo 2

View of window head soffits at facade E, where the 7th to 9th

floor windows are leaking water into building at the escalator area

and causing damages to ceilings.

Violations No violations recorded

INTERIOR Inspected

InspectedAuditorium

1st floor and 2nd floor balcony. Access from 3rd floor to sound

booth. Seats 864.

Instance

Acoustic Panels

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Ceiling

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

PLASTER:CRACKS, SPALLINGDeficiency

2nd floor, next to T270 balcony door entrance.Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 24 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 25: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Auditorium

Ceiling

Over balcony exit door T270

Violations No violations recorded

Door(s)

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

METAL:DETERIORATED/MISSING HARDWAREDeficiency

Backstage door to Stage-craft room, does not close properly.Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE HARDWARE

PRIORITY 1Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Backstage door, to Stage craft room

Violations No violations recorded

Fixed Seating

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

3- FairInstance Condition

VINYL TILES:BROKEN/MISSING TILESDeficiency

Theater floor over recessed orchestra pit.Deficiency Location/Instance

400Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Theater floor over recessed orchestra pit

Page 25 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 26: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Auditorium

Floor Finish

Deficiency Photo 2

Theater floor over recessed orchestra pit.

Violations No violations recorded

CARPET:WORN/DETERIORATEDDeficiency

Step missing thread nosing close to orchestra pit floor. Balcony

area, missing & damaged light cover for steps.

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Step by orchestra pit floor

Deficiency Photo 2

Steps at balcony

Violations No violations recorded

H/C Lift

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Does not exist

Sliding-folding Partition

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage and Curtain Rigging

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

Page 26 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 27: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Auditorium

Stage and Curtain Rigging

No deficiencies recordedDeficiency

Stage Curtains

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Wall

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st floor and 2nd floor balcony. Access from 3rd floor to

sound booth. Seats 864.

Does not exist

InspectedCafeteria

5th floor, both student and staff cafeteria.Instance

Ceiling

Instance on 5th floor, both student and staff cafeteria. Inspected

3- FairInstance Condition

PLASTER:CRACKS, SPALLINGDeficiency

Throughout student cafeteriaDeficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

At entrance of student cafeteria

Deficiency Photo 2

Staff cafeteria, by window

Violations No violations recorded

ACOUSTIC TILES:MISSING, WATER DAMAGED,

DETERIORATED

Deficiency

5th floor Student and staff cafeteriaDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 27 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 28: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Cafeteria

Ceiling

Deficiency Photo 1

Middle of student cafeteria

Deficiency Photo 2

Staff cafeteria, by window

Violations No violations recorded

Door(s)

Instance on 5th floor, both student and staff cafeteria. Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 5th floor, both student and staff cafeteria. Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 5th floor, both student and staff cafeteria. Does not exist

Wall

Instance on 5th floor, both student and staff cafeteria. Inspected

3- FairInstance Condition

WOOD:DETERIORATEDDeficiency

5th floor, student cafeteria/ fixed wood sitting, damaged

throughout.

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Student cafeteria by windows

Violations No violations recorded

Does not existCafeteria/Multi-Purpose Room

InspectedClassrooms/Corridors/Admin Spaces

InspectedCeiling

Page 28 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 29: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Classrooms/Corridors/Admin Spaces

Ceiling

Condition 3- Fair

PLASTER:CRACKS, SPALLINGDeficiency

1st floor hallway by North entrance/ leakage damageDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Above window, next to north entrance

Deficiency Photo 2

hallway next to north entrance

Violations No violations recorded

ACOUSTIC TILES:MISSING, WATER DAMAGED,

DETERIORATED

Deficiency

Rooms 502A, 402, 436, 336, 371E and other rooms.Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 502A

Deficiency Photo 2

Room 336

Violations No violations recorded

Page 29 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 30: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Classrooms/Corridors/Admin Spaces

InspectedDoor(s)

Condition 2- Between Good and Fair

METAL:DETERIORATED DOOR AND FRAMEDeficiency

Basement/ Rusted door frames in rooms 081, 082, 083, 084Deficiency Location/Instance

4Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Rooms 081 and 082

Violations No violations recorded

InspectedFloor Finish

Condition 3- Fair

VINYL TILES:WORN-OUTDeficiency

3rd floor/ room 301A, damage throughout.Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 301A

Violations No violations recorded

InspectedWall

Condition 3- Fair

WOOD:DETERIORATEDDeficiency

5th floor, next to stair G/ wood fixed sitting by windowsDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 30 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 31: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Classrooms/Corridors/Admin Spaces

Wall

Deficiency Photo 1

5th floor, fixed sitting by windows

Violations No violations recorded

CERAMIC TILES:BROKEN/MISSING TILESDeficiency

4th floor/ hallwayDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Cracked tile Across room 411

Deficiency Photo 2

Missing tile next to room 438

Violations No violations recorded

PLASTER:CRACKS, SPALLINGDeficiency

Room 339, 301A, 371BDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 371B by window

Page 31 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 32: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Classrooms/Corridors/Admin Spaces

Wall

Deficiency Photo 2

Room 339

Violations No violations recorded

InspectedGymnasium

Room 680, 6th floor Gym and Room 380, 3rd floor Auxilary

Gym. (Room 380 has no deficiencies). Seating and sliding/folding

partition exists at Gym - Room 380.

Instance

Ceiling

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Flooring

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

3- FairInstance Condition

WOOD:WORN OUT, WARPED, OR DETERIORATEDDeficiency

West side of Gym 680, the floor has a wall moulding missing and

exposes the sub-floor. Mid court area worn out.

Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

West side of floor, Gym 680

Page 32 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 33: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Gymnasium

Flooring

Deficiency Photo 2

Mid-court area, Gym 680

Violations No violations recorded

Seating

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Does not exist

Walls

Instance on Room 680, 6th floor Gym and Room 380, 3rd floor

Auxilary Gym. (Room 380 has no deficiencies). Seating and

sliding/folding partition exists at Gym - Room 380.

Inspected

2- Between Good and FairInstance Condition

PLASTER:CRACKS/SPALLEDDeficiency

East wall of Gym around windows.Deficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East wall of Gym around windows.

Violations No violations recorded

WALL PADDING:DETERIORATEDDeficiency

6th floor, Gym 680Deficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 33 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 34: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Gymnasium

Walls

Deficiency Photo 1

South wall, Gym 680

Deficiency Photo 2

South wall, Gym 680

Violations No violations recorded

InspectedInterior Window Guards

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedKitchen/Warming Pantry

5th floor, next to staff and student cafeteriaInstance

Ceiling

Instance on 5th floor, next to staff and student cafeteria Inspected

2- Between Good and FairInstance Condition

METAL PAN:DETERIORATEDDeficiency

Room K540ADeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room K540A

Deficiency Photo 2

Cooking area, 3 rusted vent grills

Violations No violations recorded

PLASTER:CRACKS, SPALLINGDeficiency

Page 34 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 35: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Kitchen/Warming Pantry

Ceiling

cooking areaDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Cooking area by window

Violations No violations recorded

Door(s)

Instance on 5th floor, next to staff and student cafeteria Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 5th floor, next to staff and student cafeteria Inspected

2- Between Good and FairInstance Condition

QUARRY TILES:BROKEN/MISSING TILESDeficiency

Room 550K/ floor baseDeficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

PRIORITY 1Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Floor base, room550K

Violations No violations recorded

Wall

Instance on 5th floor, next to staff and student cafeteria Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedLibrary

6th floor, Room 615Instance

Workroom Storage Yes

Office/Conference Room Yes

Built-in Furnishing

Instance on 6th floor, Room 615 Does not exist

Ceiling

Instance on 6th floor, Room 615 Inspected

2- Between Good and FairInstance Condition

Page 35 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 36: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Library

Ceiling

ACOUSTIC TILES:MISSING, WATER DAMAGED,

DETERIORATED

Deficiency

Room 615, 615C, 615DDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

near windows and throughout

Deficiency Photo 2

Room 615D

Violations No violations recorded

Door(s)

Instance on 6th floor, Room 615 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 6th floor, Room 615 Inspected

3- FairInstance Condition

CARPET:WORN/DETERIORATEDDeficiency

ThroughoutDeficiency Location/Instance

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Wall

Instance on 6th floor, Room 615 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedLocker Room & Shower

5th floor, Boy's locker room G583Instance

Alternative Use No

5th floor, Girl's locker room G584Instance

Alternative Use No

1st floor, Boy's pool locker shower room 182Instance

Alternative Use No

Page 36 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 37: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Locker Room & Shower

1st floor, Girl's pool locker shower room 184Instance

Alternative Use No

Ceiling

Instance on 5th floor, Boy's locker room G583 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 5th floor, Girl's locker room G584 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Boy's pool locker shower room 182 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Girl's pool locker shower room 184 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Flooring

Instance on 5th floor, Boy's locker room G583 Inspected

2- Between Good and FairInstance Condition

CERAMIC TILES:BROKEN/MISSING TILESDeficiency

Room 538, Deficient flooring is vinylDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Boy's locker room 583

Violations No violations recorded

Instance on 5th floor, Girl's locker room G584 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Boy's pool locker shower room 182 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Girl's pool locker shower room 184 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Locker Room Lockers

Instance on 5th floor, Boy's locker room G583 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 5th floor, Girl's locker room G584 Inspected

3- FairInstance Condition

DAMAGED UNITSDeficiency

Throughout room G584Deficiency Location/Instance

3Deficiency Quantity

Page 37 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 38: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Locker Room & Shower

Locker Room Lockers

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Girl's lockers, room G584

Violations No violations recorded

Instance on 1st floor, Boy's pool locker shower room 182 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Girl's pool locker shower room 184 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on 5th floor, Boy's locker room G583 Inspected

2- Between Good and FairInstance Condition

CONCRETE MASONRY BLOCKS:CRACKS/SPALLEDDeficiency

CMU wall cracked, next to entrance to locker room G583. Also

missing one glass block at opposite wall.

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Wall next to door entrance to G583

Deficiency Photo 2

opposite wall, glass block

Violations No violations recorded

Instance on 5th floor, Girl's locker room G584 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Page 38 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 39: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Locker Room & Shower

Walls

Instance on 1st floor, Boy's pool locker shower room 182 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st floor, Girl's pool locker shower room 184 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existMulti-Purpose Room

InspectedPools

1st floor, upper levelInstance

Ceiling

Instance on 1st floor, upper level Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Deck/Floor

Instance on 1st floor, upper level Inspected

5- PoorInstance Condition

CERAMIC TILES:BROKEN/MISSING/WORN TILESDeficiency

Entire ceramic tile flooring around pool is defective and needs to

be removed and new ceramic tiles installed after floor slab is

repaired and new waterproofing membrane installed.

Deficiency Location/Instance

3,500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Typical tile cracks at pool deck surrounding pool. Most open

joints have been caulked however the grout and waterproofing

membrane is defective and water is leaking into basement.

Deficiency Photo 2

Typical photo of underside of pool deck viewed from basement

showing extensive water infiltration and leaks through concrete

floor slab.

Violations 34279172Z

34421126M

34432501Z

34465953K

34509256R

Diving Board

Instance on 1st floor, upper level Inspected

Page 39 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 40: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Pools

Diving Board

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Pool Lining

Instance on 1st floor, upper level Inspected

2- Between Good and FairInstance Condition

TILE:BROKEN/MISSING/WORN TILESDeficiency

Steps down into pool have broken tiles at bottom tread.Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Steps down into the pool have broken tiles at bottom tread.

Deficiency Photo 2

Close-up of damaged step in pool. This presents a condition for an

accident to happen.

Violations No violations recorded

Roof Structure

Instance on 1st floor, upper level Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on 1st floor, upper level Inspected

2- Between Good and FairInstance Condition

CERAMIC:MISSING/DETERIORATEDDeficiency

Several steps leading up to observation area have broken tiles at

treads.

Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 40 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 41: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Pools

Seating

Deficiency Photo 1

Several steps leading up to observation area have broken tiles at

treads.

Violations No violations recorded

Walls

Instance on 1st floor, upper level Inspected

2- Between Good and FairInstance Condition

CERAMIC TILES:BROKEN/MISSING TILESDeficiency

A few areas around pool walls have cracked tile.Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Southeast corner of room has a few cracked wall tiles.

Violations No violations recorded

InspectedScience Demonstration Room

Rooms 715, 717, 735, 737, 739, 829, 833, 835, 837, 839, 902,

935, 936, 939 and 940.

Instance

Been Upgraded in the Last 25 Years No

Alternative Use No

Fixed Equipment

Instance on Rooms 715, 717, 735, 737, 739, 829, 833, 835, 837, 839,

902, 935, 936, 939 and 940.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedScience Lab

Rooms 703, 709, 727, 731, 803, 807, 811, 815, 827, 903, 911,

913, and 927.

Instance

Been Upgraded in the Last 25 Years No

Alternative Use No

Fixed Equipment

Instance on Rooms 703, 709, 727, 731, 803, 807, 811, 815, 827, 903,

911, 913, and 927.

Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedScience Preparation Room

Rooms 704, 705, 707, 729, 807, 817, 907, 909 and 925.Instance

Page 41 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 42: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Science Preparation Room

Been Upgraded in the Last 25 Years No

Alternative Use No

Fixed Equipment

Instance on Rooms 704, 705, 707, 729, 807, 817, 907, 909 and 925. Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

InspectedSpecialties

InspectedCabinet Work

Condition 2- Between Good and Fair

DAMAGED CLASSROOM WARDROBES/STORAGEDeficiency

4th floor, Room 440/ missing hardwareDeficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 440

Violations No violations recorded

InspectedChalkboard

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedClassroom Locker(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDisplay Unit

Condition 2- Between Good and Fair

DAMAGED UNITSDeficiency

2nd floor hallway next to theater balcony entrance T-270. 3rd

floor across room 333. 6th floor next to gym 680. Missing and

broken glass.

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

2nd floor hallway next to theater balcony entrance.

Page 42 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 43: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Specialties

Display Unit

Deficiency Photo 2

Across Room 333

Violations No violations recorded

InspectedTack Board

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs: Interior

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

METAL:DETERIORATED/MISSING HARDWAREDeficiency

7th floor, stair HDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE HARDWARE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

7th floor, stair H

Violations No violations recorded

InspectedHandrails

Condition 2- Between Good and Fair

METAL:BROKEN/MISSINGDeficiency

8th floor, stair HDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 43 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 44: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Stairs: Interior

Handrails

8th floor, stair H

Violations No violations recorded

METAL:LOOSE, DAMAGEDDeficiency

1st floor Auditorium entrance 170A, and others.Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Auditorium entrance 107A

Violations No violations recorded

Does not existPartition

InspectedStairs and Landings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWall

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStructural

InspectedColumns/beams/bearing Walls

Condition 4- Between Fair and Poor

STEEL COLUMNS/BEAMS:MINOR RUSTINGDeficiency

All wall bracing steel beams, columns and connections are rusting

at high roof cooling tower enclosure.

Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR AND REPAINT

PRIORITY 5Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

View from above at rusting beams.

Deficiency Photo 2

Page 44 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 45: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Structural

Columns/beams/bearing Walls

View from below looking up at rusting beams.

Violations No violations recorded

STEEL COLUMNS/BEAMS:DETERIORATEDDeficiency

At underside of steps to pool deck and at elevator #5 machine

room, there are corroded steel supports.

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

At underside of steps to pool deck and at elevator #5 machine

room, there are corroded steel supports.

Deficiency Photo 2

At underside of steps to pool deck and at elevator #5 machine

room, there are corroded steel supports.

Violations No violations recorded

InspectedFloor Structure

Condition 3- Fair

CONCRETE:CRACKS/SPALLED/REINFORCEMENT

EXPOSED

Deficiency

Pool deck floor slab has cracks and deterioration. Leaks are

continuous and re-bars in slab are being compromised plus other

building systems are being affected.

Deficiency Location/Instance

2,000Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Cracks in slab at pool deck area are leaking chlorinated water into

basement below. Photo of cracks below diving board location. If

slab and waterproofing membrane not repaired properly re-bars

will be destroyed.

Page 45 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 46: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Structural

Floor Structure

Deficiency Photo 2

View of cellar ceiling and rusting electrical conduits in machine

and tank room below pool deck floor slab which has numerous

cracks and penetration leaching chlorinated water.

Violations 34279172Z

34421126M

34465953K

34509256R

InspectedFoundation Walls

Condition 3- Fair

CONCRETE:WATER INFILTRATION THRU AREADeficiency

Caged storage room at SW corner of cellar has incoming service

line penetrations from Chambers Street that have leaked water in

heavy rains. Also ground and river water appears to be

contributing to the some water in the NE cellar area.

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL EXTERIOR WATER BARRIER

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Constant water at rooms C81 & C83.

Violations No violations recorded

InspectedRoof Structure

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVaults-Bunkers

InspectedToilet Rooms - Staff

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedWall

Condition 2- Between Good and Fair

CERAMIC TILES:BROKEN/MISSING TILESDeficiency

Page 46 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 47: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

INTERIOR

Toilet Rooms - Staff

Wall

Men's toilet 1st. floor Main Lobby.Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE-IN-KIND

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

InspectedToilet Rooms - Students

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWall

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. Holding Area

Does not existSteel Stairs

SITE Inspected

Does not existContainerization

InspectedDrainage System for Asphalt

Does not existCatch Basins - Surrounded by asphalt

InspectedDrainage System for Concrete

InspectedCatch Basins - Surrounded by concrete

Condition 4- Between Fair and Poor

BLOCKEDDeficiency

East sidewalk by entranceDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East sidewalk by entrance

Violations No violations recorded

InspectedDrainage System for Soil

Does not existCatch Basins - Surrounded by Soil

Does not existDrinking Fountains

InspectedFences

Condition 2- Between Good and Fair

Page 47 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 48: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

SITE

Fences

No deficiencies recordedDeficiency

Does not existIrrigation System

InspectedPaving - Non-vehicular Area

Does not existAsphalt

Does not existConcrete

InspectedPaving - Vehicular Area

Does not existAsphalt

InspectedConcrete

Condition 3- Fair

CRACKSDeficiency

1st floor interior garage and loading area exiting to Chambers St.Deficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

1st floor interior garage

Violations No violations recorded

Does not existPlaygrounds

InspectedRetaining Walls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSidewalks

Condition 3- Fair

HEAVINGDeficiency

Chambers St. at main entranceDeficiency Location/Instance

400Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Chamber St. at main entrance

Page 48 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)

Page 49: NYC DoE Building Condition Assessment Survey 2007-2008 - Stuyvesant High School (new)

NYC Department of Education

Building Condition Assessment Survey 2007-2008

M477Architectural Inspection

Question Response

SITE

Sidewalks

Deficiency Photo 2

Camber St. at main entrance

Violations No violations recorded

InspectedSite Structures

Does not existBulletin Boards

InspectedFlagpole(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existSite Walls (not Retaining Walls)

Does not existStairs/ramps: Exterior

Page 49 of 49 Print Date: 7/17/2008Mobile Validity Version 2.0 (P)