Next Generation Belimo Energy Valve

28
1 Belimo Americas Danbury, Connecticut Belimo Energy Valve™ Investing in Efficiency

description

Next Generation Belimo Energy Valve. Belimo Energy Valve ™. The Energy Valve is a pressure independent control valve with an integrated BTU meter Measure Energy Control Power Manage Delta T. Belimo Energy Valve ™. BACnet. Actuator. Flow Sensor. Valve. - PowerPoint PPT Presentation

Transcript of Next Generation Belimo Energy Valve

Page 1: Next Generation Belimo Energy Valve

1Belimo Americas Danbury, Connecticut

Belimo Energy Valve™

Investing inEfficiency

Page 2: Next Generation Belimo Energy Valve

Chiller Plants Overall Energy Efficiency

2Belimo Americas Danbury, Connecticut

Source:

Plant Manufacturer Chiller Plant Efficiency Coefficient♦

A (Office) 4.26

B (Museum) 4.78

C (Bank) 3.15

D (Office) 3.87

Average Chiller Plant Efficiency Coefficient♦

2.02

2.87

2.14

0.84

Actual Delta T [F]

2.4

2.8

3.6

0.7

♦ Higher Efficiency Coefficient reflects higher plant efficiency

Page 3: Next Generation Belimo Energy Valve

Chiller Plants Overall Electric Consumption

3Belimo Americas Danbury, Connecticut

Chillers Avg51%

Pumps Avg

25.5%

Plant A (Office)

Plant D (Office)Plant C (Bank)

Plant B (Museum)

Page 4: Next Generation Belimo Energy Valve

US Cooling Energy Usage

4Belimo Americas Danbury, Connecticut

15%

85%

Cooling EnergyOther US Residential & Commercial Electric Energy

Source: US Energy Information Administration (eia)How much electricity is used for cooling in the United States?(www.eia.gov/tools/faqs/faq.cfm?id=98&t=3)

11%

89%

Cooling Energy Other US Electric Energy

Page 5: Next Generation Belimo Energy Valve

Belimo Energy Valve™is the Solution

5Belimo Americas Danbury, Connecticut

The Energy Valve is a:Pressure Independent

Control Valve

with an integrated Delta T Manager

Page 6: Next Generation Belimo Energy Valve

Belimo Energy Valve™

6Belimo Americas Danbury, Connecticut

• Chilled Water Plant Energy Consumption• Energy Valve Benefits and Features• Risk Free Investment• Savings Estimator• Case Studies• www.energyvalve.com

Page 7: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

7

Pressure Dependent 240 GPM

144 GPM

96 GPM

Pressure Independent (PI)

Delta T Manager + PI

Pressure Independent and Delta T ManagerPump Savings in Large Tech Company in NC

♦ Pressure Independent♦ Pressure Dependent

Page 8: Next Generation Belimo Energy Valve

Benefits of Energy Valve

8Belimo Americas Danbury, Connecticut

• Saves on Pump • and Chiller Energy

Page 9: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

9

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 801

50001

100001

150001

200001

250001

300001

350001

0

2

4

6

8

10

12

GPM

Pow

er =

kB

TU/h

r

Del

ta T

°F

335

10.5°F

65 GPM

12°F

55 GPM

330

CoilPower Curve

Delta T Curve

1

2

Benefits of using Energy ValveSave Energy

Page 10: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

10

Pump hp Hp increase = (65/55)3 65%

1 2 ΔkBTU/hr 330 335 1.5%GPM 55 GPM 65 GPM 18%

3

1

2

1

2

GPMGPM

HPHP

Low Delta TCost of Overflowing the Coil…

Page 11: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

11

Low Delta TCost of Chiller Staging

Chiller Plant Efficiency

• Design delta T=12oF (54oF - 42oF)

• 360 GPM

• 1 Chiller, 90% Load (180 Ton)

Design Condition

360 GPM Loop flow

Page 12: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

12

Chiller Plant Efficiency

A drop in delta T causes more GPM

Low delta T

• Delta T=10.4oF (52.4oF - 42oF)

• 415 GPM• 2 Chillers, 45% Load (180 Ton)

No change to the load, but a 2nd Pump and 2nd Chiller are started.If cooling towers exist, additional cooling tower and pump may start.

415 GPM Loop flow

Low Delta TCost of Chiller Staging

Page 13: Next Generation Belimo Energy Valve

Features of Energy Valve

13Belimo Americas Danbury, Connecticut

• Power Control maintains coil power regardless of system variations

• Built-in Energy Metering• Multiple Communication

Options

Page 14: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

14

Power ControlDefinition

What is Power Control ?• A control algorithm that

creates a Linear relationship between control signal and kBTU/hr output

• Power Control maintains a coil power set point regardless of pressure and temperature fluctuations

Control Signal

0 10

00

0V 10V

Coi

l Pow

er (k

BTU

/hr)

Page 15: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

15

• Power Control allows the controller to deliver exact energy to the space• 0 to 10 VDC = 0 to 100% kBTU/hr Capacity

Coi

l Pow

er (k

BTU

/hr)

0V 10VControl Signal

0 10

00

3V30

0

Example: 83 Ton AHU83 Tons ~ 1000 kBTU/hr coil

3 VDC = 300 kBTU/hr

7.5 VDC = 750 kBTU/hr

7.5V

750

Power ControlExample

Page 16: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

16

Belimo Energy Valve™Energy Metering

• By measuring Flow (Electronic Flow Sensors)and

• Delta Temperature (RTD sensors)

• the Energy Valve can calculate Power/Energy

Power: Q (BTU/hr) = 500 x Flow (GPM) xTemperature Change (°F)

Page 17: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

17

Belimo Energy Valve™Energy Metering Usage

• Energy Measurement

• Use as System Verification Tool during commissioning.

• Establishes a baseline performance for operation over time.

• Contributes to LEED.

Page 18: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

18

Belimo Energy Valve™Communication

VOLT CURRENT

Page 19: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

19

Belimo Energy Valve™Communication: Web Server

• Energy Analysis• Flow and Temperature Analysis• Comparative Analysis

Page 20: Next Generation Belimo Energy Valve

Low Risk Investment

20Belimo Americas Danbury, Connecticut

Energy Efficiency Investing?

Page 21: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

21

Energy Efficiency is a Low Risk Investment

Source: Laitner, J., Ehrhardt-Martinez, K. and Prindle, W., 2007, “American Energy Efficiency Investment Market”, Energy Efficiency Finance Forum, American Council or and Energy Efficient Economy .

Page 22: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

22

Belimo Energy Valve™Savings Estimator

Page 23: Next Generation Belimo Energy Valve

Belimo Energy Valve

Does it really work?

23Belimo Americas Danbury, Connecticut

Page 24: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

24

Case StudyMIT University Hayden Library - Boston, MA

Building and Project Details• 150,000 sq. ft. on 3 floors• 6 AHU provide majority of the cooling

Results• Aug 9 - Oct 9, 2010

DT = 6.15°F

• Aug 9 - Oct 9, 2011DT = 12.14°F

Page 25: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

25

Case StudyUniversity of Miami Hospital

Building and Project Details• Rosenstiel Building• 11 AHUs• 2600 Tons of Cooling• Over 10,000 GPM

Results• Delta T raised from

5.5°F to 10.5°F• Flow ~ 5600 GPM• Estimated $66,000/yr savings• Estimated 2.9 year payback

Page 26: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

26

Conclusion

Page 27: Next Generation Belimo Energy Valve

Belimo Americas Danbury, Connecticut

27

www.energyvalve.comInformation and resources

Page 28: Next Generation Belimo Energy Valve

Belimo Energy Valve™

Thank You