Belimo Energy Valve™ Investing in Efficiency

28
1 Belimo Americas Danbury, Connecticut Belimo Energy Valve™ Investing in Efficiency

description

Belimo Energy Valve™ Investing in Efficiency. Chiller Plants Overall Energy Efficiency. ♦ Higher Efficiency Coefficient reflects higher plant efficiency. Source:. Chiller Plants Overall Electric C onsumption. Plant A (Office). Plant B (Museum). Chillers Avg 51%. Pumps Avg 25.5%. - PowerPoint PPT Presentation

Transcript of Belimo Energy Valve™ Investing in Efficiency

Page 1: Belimo Energy Valve™ Investing in Efficiency

1Belimo Americas Danbury, Connecticut

Belimo Energy Valve™

Investing inEfficiency

Page 2: Belimo Energy Valve™ Investing in Efficiency

Chiller Plants Overall Energy Efficiency

2Belimo Americas Danbury, Connecticut

Source:

Plant Manufacturer Chiller Plant Efficiency Coefficient♦

A (Office) 4.26

B (Museum) 4.78

C (Bank) 3.15

D (Office) 3.87

Average Chiller Plant Efficiency Coefficient♦

2.02

2.87

2.14

0.84

Actual Delta T [F]

2.4

2.8

3.6

0.7

♦ Higher Efficiency Coefficient reflects higher plant efficiency

Page 3: Belimo Energy Valve™ Investing in Efficiency

Chiller Plants Overall Electric Consumption

3Belimo Americas Danbury, Connecticut

Chillers Avg51%

Pumps Avg

25.5%

Plant A (Office)

Plant D (Office)Plant C (Bank)

Plant B (Museum)

Page 4: Belimo Energy Valve™ Investing in Efficiency

US Cooling Energy Usage

4Belimo Americas Danbury, Connecticut

15%

85%

Cooling EnergyOther US Residential & Commercial Electric Energy

Source: US Energy Information Administration (eia)How much electricity is used for cooling in the United States?(www.eia.gov/tools/faqs/faq.cfm?id=98&t=3)

11%

89%

Cooling Energy Other US Electric Energy

Page 5: Belimo Energy Valve™ Investing in Efficiency

Belimo Energy Valve™is the Solution

5Belimo Americas Danbury, Connecticut

The Energy Valve is a:Pressure Independent

Control Valve

with an integrated Delta T Manager

Page 6: Belimo Energy Valve™ Investing in Efficiency

Belimo Energy Valve™

6Belimo Americas Danbury, Connecticut

• Chilled Water Plant Energy Consumption• Energy Valve Benefits and Features• Risk Free Investment• Savings Estimator• Case Studies• www.energyvalve.com

Page 7: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

7

Pressure Dependent 240 GPM

144 GPM

96 GPM

Pressure Independent (PI)

Delta T Manager + PI

Pressure Independent and Delta T ManagerPump Savings in Large Tech Company in NC

♦ Pressure Independent♦ Pressure Dependent

Page 8: Belimo Energy Valve™ Investing in Efficiency

Benefits of Energy Valve

8Belimo Americas Danbury, Connecticut

• Saves on Pump • and Chiller Energy

Page 9: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

9

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 801

50001

100001

150001

200001

250001

300001

350001

0

2

4

6

8

10

12

GPM

Pow

er =

kB

TU/h

r

Del

ta T

°F

335

10.5°F

65 GPM

12°F

55 GPM

330

CoilPower Curve

Delta T Curve

1

2

Benefits of using Energy ValveSave Energy

Page 10: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

10

Pump hp Hp increase = (65/55)3 65%

1 2 ΔkBTU/hr 330 335 1.5%GPM 55 GPM 65 GPM 18%

3

1

2

1

2

GPMGPM

HPHP

Low Delta TCost of Overflowing the Coil…

Page 11: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

11

Low Delta TCost of Chiller Staging

Chiller Plant Efficiency

• Design delta T=12oF (54oF - 42oF)

• 360 GPM

• 1 Chiller, 90% Load (180 Ton)

Design Condition

360 GPM Loop flow

Page 12: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

12

Chiller Plant Efficiency

A drop in delta T causes more GPM

Low delta T

• Delta T=10.4oF (52.4oF - 42oF)

• 415 GPM• 2 Chillers, 45% Load (180 Ton)

No change to the load, but a 2nd Pump and 2nd Chiller are started.If cooling towers exist, additional cooling tower and pump may start.

415 GPM Loop flow

Low Delta TCost of Chiller Staging

Page 13: Belimo Energy Valve™ Investing in Efficiency

Features of Energy Valve

13Belimo Americas Danbury, Connecticut

• Power Control maintains coil power regardless of system variations

• Built-in Energy Metering• Multiple Communication

Options

Page 14: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

14

Power ControlDefinition

What is Power Control ?• A control algorithm that

creates a Linear relationship between control signal and kBTU/hr output

• Power Control maintains a coil power set point regardless of pressure and temperature fluctuations

Control Signal

0 10

00

0V 10V

Coi

l Pow

er (k

BTU

/hr)

Page 15: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

15

• Power Control allows the controller to deliver exact energy to the space• 0 to 10 VDC = 0 to 100% kBTU/hr Capacity

Coi

l Pow

er (k

BTU

/hr)

0V 10VControl Signal

0 10

00

3V30

0

Example: 83 Ton AHU83 Tons ~ 1000 kBTU/hr coil

3 VDC = 300 kBTU/hr

7.5 VDC = 750 kBTU/hr

7.5V

750

Power ControlExample

Page 16: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

16

Belimo Energy Valve™Energy Metering

• By measuring Flow (Electronic Flow Sensors)and

• Delta Temperature (RTD sensors)

• the Energy Valve can calculate Power/Energy

Power: Q (BTU/hr) = 500 x Flow (GPM) xTemperature Change (°F)

Page 17: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

17

Belimo Energy Valve™Energy Metering Usage

• Energy Measurement

• Use as System Verification Tool during commissioning.

• Establishes a baseline performance for operation over time.

• Contributes to LEED.

Page 18: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

18

Belimo Energy Valve™Communication

VOLT CURRENT

Page 19: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

19

Belimo Energy Valve™Communication: Web Server

• Energy Analysis• Flow and Temperature Analysis• Comparative Analysis

Page 20: Belimo Energy Valve™ Investing in Efficiency

Low Risk Investment

20Belimo Americas Danbury, Connecticut

Energy Efficiency Investing?

Page 21: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

21

Energy Efficiency is a Low Risk Investment

Source: Laitner, J., Ehrhardt-Martinez, K. and Prindle, W., 2007, “American Energy Efficiency Investment Market”, Energy Efficiency Finance Forum, American Council or and Energy Efficient Economy .

Page 22: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

22

Belimo Energy Valve™Savings Estimator

Page 23: Belimo Energy Valve™ Investing in Efficiency

Belimo Energy Valve

Does it really work?

23Belimo Americas Danbury, Connecticut

Page 24: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

24

Case StudyMIT University Hayden Library - Boston, MA

Building and Project Details• 150,000 sq. ft. on 3 floors• 6 AHU provide majority of the cooling

Results• Aug 9 - Oct 9, 2010

DT = 6.15°F

• Aug 9 - Oct 9, 2011DT = 12.14°F

Page 25: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

25

Case StudyUniversity of Miami Hospital

Building and Project Details• Rosenstiel Building• 11 AHUs• 2600 Tons of Cooling• Over 10,000 GPM

Results• Delta T raised from

5.5°F to 10.5°F• Flow ~ 5600 GPM• Estimated $66,000/yr savings• Estimated 2.9 year payback

Page 26: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

26

Conclusion

Page 27: Belimo Energy Valve™ Investing in Efficiency

Belimo Americas Danbury, Connecticut

27

www.energyvalve.comInformation and resources

Page 28: Belimo Energy Valve™ Investing in Efficiency

Belimo Energy Valve™

Thank You

28Belimo Americas Danbury, Connecticut