Merlin Gerin Vip300 Test Set VAP6

download Merlin Gerin Vip300 Test Set VAP6

of 15

Transcript of Merlin Gerin Vip300 Test Set VAP6

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    1/15

    Merlin Gerin Modicon Square D Telemecanique

    Merlin GerinVIP 300 protection relayOperation, testing andcommissioning

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    2/153

    VIP 300

    Contents

    Content page

    Use and settings

    Relay front panel 4

    Curve selection 5

    Phase overcurrent

    setting area 6

    Earth fault setting area 7

    Other functions

    (labels, LEDs, VAP6) 8-9

    Testing and

    Commissioning

    Overview of VAP6 test unit 10

    VAP6 test sequence 11

    Commissioning Ringmaster

    with VIP 300 12-15

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    3/154

    VIP300

    0.40.20.60.1

    0.90.05

    1.50.03

    to>>(s)

    129156

    204

    off3 (x Is)

    0.20.15 0.30.1

    0.40.07

    0.60.05

    0.40.2

    0.60.1

    0.90.05

    1.50.03

    t>>(s)

    129156

    204

    off3(x Ios)

    2.11.82.41.5

    2.71.2

    31(s)

    0.20.150.30.1

    0.40.07

    0.60.05

    to>(s)

    curve selection

    DT onlyIo> Io>>

    I>>

    Is

    4842 56

    36 6430 72

    24 8020 90100

    (A)

    Ios

    2416 32

    12 408 50

    4 602 7080

    (A)

    I>

    I>

    trip

    reset

    trip

    Io>

    earth fault

    x10

    sensors:200/1 4509996A0VIP300LH range: x2

    minimum operatingphase current: 20A

    phaseovercurrent

    x1

    EIVISI

    offRI

    DT (s)

    2.11.82.41.5

    2.71.2

    31(x Is)

    x10

    x1

    EI, VI, SI

    DT

    RI

    t>

    t>>

    Is1.2 Is I> 10Is I>>

    VAP6 test plug

    EIVISI

    offRI

    DT

    DT only

    curve selection

    t>

    1 2 3 4 5 7 8 6 9 10

    C B A

    D E 11 12 13 14 15 17 18 16 19 20

    Phase overcurrent setting.1. Phase setting area

    (upper half of relay front panel).

    2. Red LED phase overcurrentpick-up indicator.

    3. Phase overcurrent trip indicator.

    4. Phase overcurrent setting Is.

    5. Choice of low set curve type I>.

    6. Low set pick-up (DT only) I>.7. Low set time delay t>

    8. Multiplying factor (low set).

    9. High set pick-up I>>

    10. High set time delay t>>

    Earth fault setting.11. Earth fault setting area

    (lower half of relay front panel).

    12. Red LED earth fault pick-upindicator.

    13. Earth fault trip indicator.

    14. Earth fault setting current Ios.

    15. Choice of low set curve type Io>.

    16. Low set pick-up (DT only) Io>.17. Low set time delay to>.

    18. Multiplying factor (low set).

    19. High set pick-up Io>>.

    20. High set time delay to>>.

    Other functions.A. Current setting scale label.

    B. Current transformer andrange information.

    C. Indicator reset button.

    D. Minimum operating current.

    E. VAP6 test plug socket.

    VIP 300

    Relay front panel

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    4/155

    VIP 300

    Curve selection

    Is

    SI, VI, EI RIG

    F

    J

    K

    Lt>>

    1.2 Is 10 Is I>>

    t>

    DT curve selection

    Is

    DTG

    Lt>>

    I>

    I>1.2 Is I>>

    F

    J

    K

    H

    t>

    t

    t

    Phase overcurrent setting

    The numbers indicated below are thoseof the setting switches (refer to thediagram of the front panel on page 4)The letters indicate the curvecharacteristic as shown opposite.

    Phase overcurrent setting:

    F Setting current Is (4)

    G Type of low set I> curve (5)IDMT: SI, VI, EI, RI.Definite time: DT

    H DT low set pick-up I> (6)This setting is only active for the

    low set DT curve selection (asshown). If IDMT curves areselected this switch is disabled,as SI,VI, EI, low set pick-up isfixed at 1.2 Is.

    J Low set time delay t> (7)and multiplier (8)

    K High set I>>(9)

    L High set time delay t>>(10)

    Earth fault setting

    The principle is the same as for phase

    protection.

    Set:

    F Setting current Ios (14)

    G Type of low setting Io> curve (15)IDMT: SI, VI, EI, RIDefinite time: DT

    H DT low set pick-up Io> (16)This setting is only active for thelow set DT curve selection (asshown). If IDMT curves areselected this switch is disabled,

    as SI, VI, EI low set pick-up isfixed at 1.2 Is.

    J Low set time delay to> (17)and multiplier (18)

    K High set Io>>(19)

    L High set time delay to>>(20)

    Operation

    The high and low set elementsoperate separately. The tripping orderresults from the logical OR betweenthe two settings.

    IDMT curve selection

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    5/156

    1. Phase overcurrent

    setting area.

    All information concerning the phaseovercurrent is grouped together in theupper half of the front panel. Thesection numbers below are related tothe numbering on the drawing shownon page 4.

    2. Phase overcurrentpick-up indicator.

    When the red LED blinks, it indicatesthat the low set element has picked up.If the current does not decrease below

    the pick-up level the relay will trip.

    For IDMT curves (SI, VI, EI) theLED blinks when the current isgreater than 1.2 times the settingcurrent Is.

    For the IDMT curve (RI), the LEDblinks when the current is greaterthan the setting.

    For the DT curve, the LED blinkswhen the I> pick-up settingis exceeded.

    Also refer to indicator reset button(page 9).

    3. Phase overcurrent tripindicator.

    The indicator is normally black andturns yellow when the phaseovercurrent has given a tripping order.It stays yellow, even when the relay isde-energised.

    4. Setting current Is.

    The setting depends on the current

    transformer (CT) used, and the rangeselected via the connections made tothe back of the relay. The scale labelinserted should match the CT andrange selected. The switch can then bepositioned to the primary currentmagnitude required in amperes.

    Phase overcurrent

    VIP 300

    Use and settings

    5. Choice of lowset curve.

    SI : Standard inverse time.

    VI : Very inverse time.

    EI : Extremely inverse time.

    RI : Specific curve- consult Merlin Gerin

    DT : Definite time.

    Off : Low set is disabled.

    6. Low set pick-up(DT only) I>.

    The setting is a multiple of Is. It is onlyactive when the low set curve type DTis selected.

    If the tripping curve is selected withIDMT (selector switch 5 set to SI, VI,EI, RI) the selector switch has no effect.

    7. Low set time delay t>.

    If the DT curve is selected,the value shown is the low settime delay.

    For IDMT curves the valuedisplayed is the tripping time for aphase current equal to 10 xIs.

    8. Multiplying factor(low set).

    In the x10 position, the time delaydisplayed on switch 7 is multiplied by 10.

    9. High set pick-up I>>.

    The high set is chosen as a multiple ofthe current Is. In the off position, thehigh set is disabled.

    10. High set time delay t>>.

    Time delay is set directly in seconds.

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    6/157

    15. Choice of lowset curve.

    SI : Standard inverse time.

    VI : Very inverse time.

    EI : Extremely inverse time.

    RI : Specific curve.

    DT : Definite time.

    Off : Low set is disabled.

    16. Low set pick-up(DT only) Io>.

    The setting is a multiple of Ios. It is

    only active when the low set curve typeDT is selected.

    17. Low settime delay to>.

    If the DT curve is selected, thevalue shown is the low set timedelay.

    For IDMT curves the valuedisplayed is the tripping time for aphase current equal to 10 xIos.

    18. Multiplying factor(low set)

    In the x10 position, the time delaydisplayed on switch 17 is multiplied by 10.

    19. High set pick-up Io>>.

    The high set is chosen as a multiple ofthe current Ios. In the off position, thehigh set is disabled.

    20. High set time delay to>>.

    Time delay is set directly in seconds.

    The setting principle is the same as

    for phase overcurrent.

    11. Earth fault setting

    area.

    All information concerning earth faultsettings are grouped together in thelower half of the front panel. Sectionnumbers below are related to thenumbering on the drawing shown onpage 4.

    12. Earth fault pick-upindicator.

    When the red LED blinks, It indicatesthat the low set element has picked up.If the current does not decrease belowthe pick-up level the relay will trip.

    For IDMT curves (SI, VI, EI) theLED blinks when the current isgreater than 1.2 times the settingcurrent Is.

    For the IDMT curve (RI), the LEDblinks when the current is greaterthan the setting.

    For the DT curve, the LED blinks

    when the l> pick-up settingis exceeded.

    *N.B. The LED only blinks when thephase current is greater than theminimum operating current (refer tominimum operating current, page 9)

    Also refer to indicator reset button(page 9).

    13. Earth fault trip indicator.

    The indicator is normally black andturns yellow when the earth faultelement has given a tripping order. It

    stays yellow, even when the relay isde-energised.

    14. Setting current Ios.

    The setting depends on the currenttransformer (CT) used, and the rangeselected via the connections made tothe back of the relay. The scale labelinserted should match the CT andrange selected. The switch can then bepositioned to the primary amp valuerequired.

    For earth fault relay operation: linkbetween contacts 2 and 9 (x2 range)and 1 and 9 (x4 range) must be madeat back of relay.

    Earth fault

    VIP 300

    Use and settings

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    7/158

    Other functions

    VIP 300

    Use and settings

    A. Setting scale label

    The label indicates the range forthe phase overcurrent and earthfault primary amp settings. It isinserted from the top, behind thetransparent part of the frontpanel.

    The label is reversible and isprinted with the x2 range settingcurrents on one side, and the x4range setting currents on theother. The scale label wheninserted should match the CT andterminal positions on the rear ofthe relay, for the range required.

    Also refer to testing andcommissioning.

    B. CT and rangeindication.

    The CT and range are given on eachside of the setting scale label. The labelwill match the appropriate CT for theRingmaster panel type supplied. Thisinformation is hidden when the label isinserted.

    VIP 300LH range: x2

    (A)

    sensor200/1: 4509996A0

    Is48

    42 5636 64

    30 72

    24 8020 90

    100

    sensor200/1: 4509996A0

    VIP 300LHrange: x4

    Is96

    84 11272 128

    60 144

    48 16040 180

    200

    minimum operatingphase current: 20A

    Ios24

    16 3212 40

    8 50

    4 602 70

    80

    minimum operatingphase current: 40A

    (A)

    (A)

    x 2 range

    Reversible scale label for Ringmaster fitted with 200/1A CTs

    Ios48

    32 6424 80

    16 100

    8 1204 140

    160(A)

    x 4 range

    VIP 300LH range: x2

    (A)

    sensor800/1: 4509169A0

    Is192

    168 224144 256120 288

    96 32080 360400

    sensor800/1: 4509169A0

    VIP 300LHrange: x4

    Is384

    336 448288 512240 576

    192 640160 720800

    minimum operatingphase current: 80A

    Ios96

    64 12848 160

    32 200

    16 240

    8 280320

    minimum operatingphase current: 160A

    Ios192

    128 25696 320

    64 400

    32 480

    16 560640

    (A)

    (A)

    (A)

    x 2 range x 4 range

    Reversible scale label for Ringmaster fitted with 800/1A CTs

    Choice of setting scale label.

    Make sure that the informationgiven on the top of the labelmatches:1 - The current transformer used:

    200/1A or 800/1A2 - The range used.

    x2 or x4

    This information is hidden when thelabel is in position.

    For help with the choice of rangeto select, refer to the applicationsection.

    Installation.

    Slide the setting scale intoposition behind the transparentpart of the front face.

    Make sure the label is pushedright into the bottom of the slot. Toremove the label, use the hole in

    the top, if necessary with the helpof the tip of a pencil or ascrewdriver.

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    8/159

    C. Indicator reset button

    The reset button can be operated withthe sealable cover either open orclosed. When the button is pressed, thefollowing actions are initiated:

    It resets the phase overcurrentand earth fault trip indicators.N.B.

    If reset is more than 48 hoursafter the relay has operated andis left without being energised,the VAP6 must be used to resetthe trip indicators or the operatormust wait for the relay to bere-energised.

    The two red LEDs light upsimultaneously for approximatelythree seconds to indicate thefollowing:- The relay is energized and theminimum operating current levelhas been reached.

    -The relay self testing results arehealthy

    N.B.If one of the two conditions is notmet, the indicators do not light up.

    This function may be used tocarry out a basic relay operation test.

    D. Minimum operatingcurrent

    The minimum operating current is thephase current required for the relay tobe energized and operational. Thesetting depends on the CT used, andthe range selected via the connectionsmade to the back of the relay. Thevalue given on either side of the scalelabel is the single phase RMS minimumoperating current.

    N.B. Regarding minimum operatingcurrent:

    The VIP 300 does not operate belowthe minimum operating current level. Asa result, if the earth fault setting (Ios) isbelow the minimum operating current, itwill only take effect when there is phasecurrent greater than or equal to theminimum operating current.

    VIP 300

    Use and settings

    E. VAP6 test plug

    The test plug is exclusively designedfor connection of the VAP6 which isused for fast, simplified relay testing.The operation may be carried out whilethe relay is operating since the VAP6and VIP 300 provide the possibility oftesting with inhibition of circuit breakertripping.

    Also refer to the testing andcommissioning chapter.

    Fitting of reversible scale label

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    9/1510

    VIP 300

    Overview of the VAP6

    Indicators

    A On:

    Indicates that the batteries areoperating. Also lights up when thebattery test is carried out bypressing battery test.

    B Test in progress:

    Confirms sending of the teststimulus to the VIP 300.

    C Trip:Is used to test other relays in theVIP range. It is not to be

    considered for the VIP 300 test (itlights up for a transient periodwhen the VIP 300 sends a trippingorder; whether or not the circuitbreaker is inhibited).

    D External MITOP output:

    This feature may be used toconnect an external MITOP tripcoil which could be used tooperate a timer etc. The externalcoil is triggered at the same timeas the circuit breaker MITOP. The

    trip inhibit button does not effectthe external coil.

    Batteries:

    The batteries are normallydeactivated and are automaticallyactivated when the VAP6 isconnected to the VIP 300. Theyare activated in the followingcases:

    - Pressing the battery testbutton.

    - Direct connection to a VIP 300

    relay.

    To install or change the batteries,open the unit by removing the 4screws on the bottom of the unit.Be sure to use the correctpolarities.

    Technical characteristics:

    Supply: 3 x 9V 6LR61batteries

    Weight: 0.45KG

    Dimensions: 93 X 157 X 45mm

    The VAP6 is a portable unit which isconnected to the VIP 300 to carry out

    simplified testing.The test can be carried out in thefollowing two cases:

    - the VIP 300 is already powered up by the sensors (CTs).

    - The VIP 300 is not supplied. Inthis case, the VAP6 batteriessupply power to the relay.

    Push buttons:

    1 Battery test:

    If the batteries are healthy, theon indicator(A) lights up whenthe button is pressed.

    2 Phase overcurrent:

    Sends the phase overcurrent teststimulus, which is equivalent to 20times the setting current Is.

    3 Earth fault:

    Sends the earth fault teststimulus, which is equivalent to 20times the earth setting currentIos.

    4 Trip inhibition:

    By pressing and holding thisbutton down the relay can betested with the VAP6 withouttripping the circuit breaker. Thisfacility will inhibit the circuitbreaker tripping even if a realfault occurs during the test.

    VAP6 front panel

    I>

    on

    external mitop

    VAP6

    + -

    test in progress

    trip

    tripinhibition

    earth fault

    phase overcurrent

    battery test

    circuit breakermitop

    circuit breakermitop

    earth faultVIP 30VIP 35

    VIP300VIP50VIP75

    VIP 11, 11RVIP 12RVIP13VIP17VIP200, 201

    test

    phaseovercurrent

    test

    phaseovercurrent

    triptripinhibition

    externalmitop

    A

    B

    C

    4

    D D

    1

    2

    3

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    10/1511

    VIP 300

    VAP6 test sequence

    The test consists of:

    - Initiation of the VIP 300 self

    monitoring and diagnostic routine.- Injecting a stimulus to stimulatea phase fault.

    - Check tripping

    * The VAP6 is supplied bybatteries. Therefore the parts ofthe VIP 300 that run on ACcurrent are not checked using thismethod (input and supplycircuits).

    Press the phase overcurrent button tosend the test stimulus.

    - Continue pressing the buttonthroughout the duration of thestimulus. The stimulus representsabout 20 times the setting currentIs.

    -The VAP6 test in progressindicator lights up to confirm thesending of the stimulus to theVIP300 relay.

    - The red I> indicator of theVIP300 blinks during the timerelay delay period.

    - Then the VIP 300 phase trip

    indicator turns yellow.- The circuit breaker trips if it isnot inhibited.

    *If the phase overcurrent button isheld down after tripping, the VIP300starts the time delay/tripping cycleagain; this is normal operation.

    In that case:

    - The VAP6 red trip indicatorlights up for a transient periodeach time there is a trip.

    - Depending on the time delay

    setting, the VIP 300 red I>indicator may be off or blinkrapidly and/or in an irregularmanner.

    Press earth fault to test the relaysoperation. The stimulus injected isequal to 20 times the setting currentIos. Use the procedure as for the phaseovercurrent test.

    Disconnect the VAP6. In order to savebatteries, do not leave the VAP6connected to the relay unnecessarily.

    The test may be carried out with orwithout the relay energised by the

    Ringmaster current transformers, andall the relay settings are effective.During the test, the relay remainsoperational and will give a trippingorder in the event of a fault, unless thetrip inhibit button is pressed and helddown.

    Connect the VAP6 to the VAP6 testplug. The VAP6 batteries are activated

    and the on indicator lights up.

    Press the trip inhibition button if thetest should be carried out withouttripping the circuit breaker.*Be sure to continue pressing thetrip inhibition button throughout thetime it takes to send the stimulus.

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    11/1512

    VIP 300

    Commissioning Ringmaster with VIP 300

    Secondary injection:

    Testing using secondary injection isused to test the following parts of theprotection system:

    The electronic circuit.

    The integrity of the power supplyof the VIP 300.

    The link to the mitop trip coil andalso the circuit breakermechanical tripping mechanism.

    The integrity of the switches onthe front panel to ensure theygive the correct tripping times forthe curves selected.

    Reduced commissioning:

    Since the system is fully tested it is onlynecessary to prove the relay on site atthe service settings, therefore reducingcommissioning time to a minimum.Once the switchgear has been installedand cabled up, it is impractical orsometimes impossible to carry outinjection tests. It is suggested that forcommissioning and maintenancepurposes either of the following twomethods can be used.1. Simple trip test using the VAP6

    test unit (described previously).

    2. Secondary injection using

    standard equipment with anoutput filter.

    Factory tests:

    All Ringmaster panel types are fullytested before leaving the factory. Thesetests include the whole protectionsystem including current transformers,wiring harness, relay, trip coil and thecircuit breaker itself using primaryinjection to energise the system.Tripping tests are carried out usingdifferent settings for each of the IDMTand DT curves available on the relay.The tripping times are measured with achronometer and its accuracy is verifiedagainst the theoretical times calculated.

    Test set connections:The injection set is connected to the VIP 300 relay without disconnecting the CTs.This is done via the sockets on the terminal rail located in the pilot cable box, justabove the relay itself.

    Phase overcurrent connections:To test the overcurrent protection the connection should be made across two CTs(terminal rails nos 4 to 5, 5 to 6 or 6 to 4).

    Earth fault connections:To test the earth fault protection, the connection should be made across one CT(terminal rail nos 4 to 7, 5 to 7, or 6 to 7).These terminal numbers should be cross checked with the relevant circuit breakerschematic diagram. Terminals 15 and 16 (not shown above - see Ringmasterselection guide) give access to a normally open contact, which is normally openwhen the CB is in the open position. This can be used to connect a timing device tomeasure the opening time of the relay and circuit breaker.The type of test plug used to connect to the DIN rail connectors is a standard 2mm19A test plug.

    Note: When using a secondary injection set with VIP 300 a filter (e.g. Foster SF30)should be used to improve the wave form. If a filter is not used the operating time ofthe relay may not follow the theoretical operating times.

    VIP 300 IDMT RELAY

    P1

    P2

    S1

    S2

    C11

    MITOP - ITC

    S2

    CT1

    52

    P1

    P2

    S1

    S2

    P1

    P2

    S1

    S2

    C114

    5

    6

    7

    8

    9

    10

    C31 C31

    C51 C51

    C10 C10

    C30

    C50 C70

    C90

    8

    7

    6

    5

    4

    3

    2

    1

    x 2 r a n g e

    2 0 A o r 8 0 A

    m i n i m u m

    o p e r a t in g

    cu r r e n t

    x4 r a n g e

    4 0 A o r 1 6 0 A

    m i n i m u m

    o p e r a t in g

    cu r r e n t

    950/51

    50N/51N

    10

    11

    12

    13

    14

    15

    16

    0v

    YR B

    K8 (-VE)

    K7 (+VE)

    C71

    Injection test setwith filter

    CB auxiliary contact(for timing purposes)

    connect to terminal blocks above for secondary injection

    N.B. - Always check against the relevantCB schematic diagram before carryingout tests

    MITOP - CB trip coil

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    12/1513

    RN2, CE2, CN2 CE6, RN6

    CT ratio 200/1A CT ratio 800/1A Range x 2, Range x 4, Range x 2, Range x 4,

    Minimum Operating Current=20A Minimum Operating Current=40A Minimum Operating Current=80A Minimum Operating Current=160A

    Secondary Equivalent Secondary Equivalent Secondary Equivalent Secondary Equivalent

    injected current primary current injected current primary current injected current primary current injected current primary current

    100mA 20A 200mA 40A 100mA 80A 200mA 160A

    120mA 24A 240mA 48A 120mA 96A 240mA 192A

    150mA 30A 300mA 60A 150mA 120A 300mA 240A

    180mA 36A 360mA 72A 180mA 144A 360mA 288A

    210mA 42A 420mA 84A 210mA 168A 420mA 336A240mA 48A 480mA 96A 240mA 192A 480mA 384A

    280mA 56A 560mA 112A 280mA 224A 560mA 448A

    320mA 64A 640mA 128A 320mA 256A 640mA 512A

    360mA 72A 720mA 144A 360mA 288A 720mA 576A

    400mA 80A 800mA 160A 400mA 320A 800mA 640A *

    450mA 90A 900mA 180A 450mA 360A 900mA 720A *

    500mA 100A 1A 200A 500mA 400A 1A 800A *

    VIP 300

    Commissioning Ringmaster with VIP 300

    Recommended test

    procedure forsecondary injection:

    The test procedure outlined here is onlya guide and may need modifying to suitthe different test sets available.The manufacturers instructions shouldbe read before attempting to secondaryinject the VIP 300 relay.

    The VIP 300 relay can be secondaryinjected like any conventional 1A relay,therefore the output recommended for1A relays should be used.

    Calculate the secondary current to beinjected from the equivalent primarycurrent, taking into account the CTsused and the range selected byconnections to the terminals on theback of the relay.

    With the VIP 300 connected so as topresent the correct burden, thefollowing tests can be carried out:

    1. Pick-up check

    - Increase the current slowly untilthe appropriate LED indicatorstarts to blink.

    2. Setting check:

    - Set the current to be injected ( atrue RMS ammeter should beused to measure the current).

    - The CB should then be closedand the counter/timer reset. Thecurrent should then be applied.

    - When the CB has operated, theapplied current should be turned

    off if not done automatically.- The time shown on the counterdisplay includes the operatingtime of the circuit breaker(approx. 90mS). The actual relayoperating time can then becalculated by subtracting this timefrom the counter reading.

    Note. - No connection should be made to the MITOP trip coil from the secondaryinjection test set.

    *Note. These values exceed the rating of the circuit breaker

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    13/1514

    VIP 300

    Commissioning Ringmaster with VIP 300

    VIP300

    0.40.20.60.1

    0.90.05

    1.50.03

    to>>(s)

    129156

    204

    off3 (x Is)

    0.20.150.30.1

    0.40.07

    0.60.05

    0.40.20.60.1

    0.90.05

    1.50.03

    t>>(s)

    129156

    204

    off3 (x Ios)

    2.11.82.41.5

    2.71.2

    31 (s)

    0.20.150.30.1

    0.40.07

    0.60.05

    to>(s)

    curve selection

    DT onlyIo> Io>>

    I>>I>

    I>

    trip

    reset

    trip

    Io>

    earth fault

    x10

    phaseovercurrent

    x1

    EIVISI

    offRI

    DT (s)

    2.11.82.41.5

    2.71.2

    31 (x Is)

    x10

    x1

    EI, VI, SI

    DT

    RI

    t>

    t>>

    Is1.2 Is I> 10Is I>>

    VAP6 test plug

    EIVISI

    offRI

    DT

    DT only

    curve selection

    t>

    VIP 300LH range: x2

    (A)

    sensor200/1: 4509996A0

    Is48

    42 5636 64

    30 72

    24 8020 90

    100

    sensor200/1: 4509996A0

    VIP 300LHrange: x4

    Is96

    84 11272 128

    60 144

    48 16040 180

    200

    minimum operatingphase current: 20A

    Ios24

    16 3212 40

    8 50

    4 602 70

    80

    minimum operatingphase current: 40A

    (A)

    (A)

    Ios48

    32 6424 80

    16 100

    8 1204 140160

    (A)

    VIP 300LH range: x2

    (A)

    sensor800/1: 4509169A0

    Is192

    168 224144 256

    120 288

    96 32080 360400

    sensor800/1: 4509169A0

    VIP 300LHrange: x4

    Is384

    336 448288 512

    240 576

    192 640160 720

    800

    minimum operatingphase current: 80A

    Ios96

    64 12848 160

    32 200

    16 2408 280

    320

    minimum operatingphase current: 160A

    Ios192

    128 25696 320

    64 400

    32 48016 560

    640

    (A)

    (A)

    (A)

    Mark settings with an arrow e.g.

    ASetting scale label selection to belocated at point A for appropriate CTtype 200/1A & 800/1A

    Commisioning test record:

    Secondary injection of Merlin GerinVIP 300 self powered overcurrent andearth fault relay.

    tick as appropriate

    Customer site

    Contact ref. Panel

    Relay type Relay serial no.

    Current transformers Setting range, Miniumum operating current

    200/1A x2, 20A

    x4, 40A

    800/1A x2, 80A

    x4, 160A

    Note. Ensure connections on the rear of the relay are made to the appropriateterminals for the x2 or x4 setting ranges and that the scale labels are insertedcorrectly to match the range selected.

    Indicate on the diagram below actual settings. Carry out tests and record the resultsin the table provided.

    200/1A 800/1A

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    14/15

  • 7/22/2019 Merlin Gerin Vip300 Test Set VAP6

    15/15

    Merlin Gerin Modicon Square D Telemecanique

    Merlin Gerin - MediumVoltageMeanwood Road, Leeds LS6 2BN.Tel: 0113 275 7121/7 Fax: 0113 274 3698 Internet address: http://www.schneider.co.uk.

    PublicationNo.PB

    1197LIP2000WO

    /S-BP