FA-200Microprocessor-Based Fire Alarm Control Panel
LT-636 Rev.
July 2006Installation and Operation Manual
Advanced Life Safety Solutions
A.C.ON
COMMON
SUPERVISORY
COMMON
TROUBLE
COMMON
ALARM
BATTERY
TROUBLE
GROUND
FAULT
REMOTETROUBLE
TEST
AUXILIARY
DISCONNECT
FIRE
DRILL
ZONE 1
ZONE 2
ZONE 3
ZONE 4
SIGNAL
SILENCE
S
E
R
I
E
S
2
FIRE ALARM CONTROL
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 2/52
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 3/52
FA-200 Series Installation and Operation Manua
Contents
List of Figures and Tables................................................................................................................................ ii i
Introduction ....................................................................................................................................................... 1
About this Manual .......................................................................................................................................... 1
About the FA-200........................................................................................................................................... 1Overall Features: ........................................................................................................................................... 1
Technical Support .......................................................................................................................................... 1
Document Conventions .................................................................................................................................... 2
Circuits and Zones ......................................................................................................................................... 2
Wiring Styles .................................................................................................................................................. 2
System Components..................................................................................................................................... 3
Chassis .......................................................................................................................................................... 3
Circuit Adder Modules.................................................................................................................................... 4
Auxiliary Models............................................................................................................................................. 4
FA-200 Accessories....................................................................................................................................... 4
Mechanical Installation and Dimensions ........................................................................................................ 5
Modu les Mounting Locations .......................................................................................................................... 7
Modu le Settings ............................................................................................................................................... 9Main Fire Alarm Module................................................................................................................................. 9
Zone Adder Module (Model DM-204) ............................................................................................................ 10
Relay Modules (Models RM-204 or RM-208) ................................................................................................ 10
DACT / Dialler Module (Model DACT-100A).................................................................................................. 11
Polarity Reversal and City Tie Module (Model: PR-100) ............................................................................... 11
Field Wir ing....................................................................................................................................................... 12
General Field Wiring Considerations ............................................................................................................. 12
Main Fire Alarm Module Terminal Connections ............................................................................................. 13
Zone Adder Module (DM-204) Terminal Connections ................................................................................... 15
Relay Module (RM-204 or RM-208) Terminal Connections ........................................................................... 16
DACT / Dialler Module (DACT-100A) Terminal Connections ........................................................................ 17
Polarity Reversal and City Tie Module (Model: PR-100) Terminal Connections .......................................... 18
Power Supply Connections............................................................................................................................ 19Wiring Tables ................................................................................................................................................ 20
System Checkout ............................................................................................................................................. 21
Before Turning The Power On... .................................................................................................................... 21
Power-up Procedure..................................................................................................................................... 21
Troubleshooting ............................................................................................................................................. 21
Indicators, Controls , & Operation .................................................................................................................... 22
Indicators ....................................................................................................................................................... 22
Controls......................................................................................................................................................... 24
Operation ....................................................................................................................................................... 25
Circuit Types ................................................................................................................................................. 25
Initiating (Detection) Circuit Types ................................................................................................................. 26
Indicating (Signal) Circuits Types .................................................................................................................. 27
System Configurati on ....................................................................................................................................... 28
Main Fire Alarm Board ................................................................................................................................... 28
DM-204 Module ............................................................................................................................................. 30
Walk Test Operat ion ......................................................................................................................................... 32
Appendix A: Compatible Devices .................................................................................................................... 33
Underwriter’s Labs Canada (ULC) Canadian: Two-wire Smoke Detector Control Panel Compatibility........ 33
Underwriter’s Labs Inc. (UL) United States: Two-Wire Smoke Detector Control Panel Compatibility .......... 34
Underwriter’s Laboratories Inc. (UL) United States: Four-Wire Smoke Detector Control Panel Compatibility 36
Underwriter’s Laboratories Inc. (UL) United States: Signalling Device Control Panel Compatibility ............. 36
Appendix B: RAM-208 Remote Annunc iator .................................................................................................. 37
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 4/52
ii
Appendix C: Module Speci fi cat ions And Features ....................................................................................... 38
FA-201 Fire Alarm Control Panel ................................................................................................................... 38
FA-202 Fire Alarm Control Panel ................................................................................................................... 38
FA-204 Fire Alarm Control Panel ................................................................................................................... 39
Polarity Reversal and City Tie Module (PR-100) ........................................................................................... 39
RM-204 / RM-208 Relay Module.................................................................................................................... 39
FA-204E Fire Alarm Control Panel................................................................................................................. 39
DM-204 Zone Adder Module.......................................................................................................................... 40
Appendix D: Power Supply & Battery Calculations ....................................................................................... 41Warranty ............................................................................................................................................................. 43
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 5/52
FA-200 Series Installation and Operation Manual
ii i
List of Figures and Tables
Figures
Figure 1: FA-201, 202, and 204 Enclosure Installation and Dimensions .................................. 5
Figure 2: FA-204 E Enclosure Installation and Dimensions...................................................... 6Figure 3: FA-201, 202, and 204 Module Mounting Locations ................................................... 7
Figure 4: FA-204E Module Mounting Locations ........................................................................ 8
Figure 5: Main Fire Alarm Module ............................................................................................. 9
Figure 7: RM-204 or RM-208 Relay Adder Module ................................................................... 10
Figure 8: DACT-100A Dialer Module......................................................................................... 11
Figure 9: PR-100 Polarity Reversal and City Tie Module.......................................................... 11
Figure 10: General Field Wiring Considerations ....................................................................... 12
Figure 11A: Main Fire Alarm Module Terminal Connections..................................................... 13
Figure 11B: Main Fire Alarm Module Terminal Connections (cont’d)........................................ 14
Figure 12: DM-204 Zone Adder Module Terminal Connections................................................ 15
Figure 13: Relay Module (RM-204 or RM-208) Terminal Connections..................................... 16
Figure 14: DACT-100A Wiring Diagram.................................................................................... 17
Figure 15: PR-100 Polarity Reversal and City Tie Module Terminal Connections.................... 18Figure 16: Power Supply Connections...................................................................................... 19
Figure 17: Indicators and Control Location ............................................................................... 22
Figure 18: Evacuation Codes.................................................................................................... 27
Tables
Table 1: Wiring Table for Initiating Circuits................................................................................ 20
Table 2: Wiring Table for Indicating Circuits.............................................................................. 20
Table 3: Configuration DIP Switch Functions on Main Fire Alarm Board.................................. 29
Table 4: Configuration DIP Switch Functions on DM-204 Module ............................................ 31
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 6/52
List of Figures and Tables
iv
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 7/52
FA-200 Series Installation and Operation Manua
Introduction
About this ManualThis installation and operation manual provides information on installing and operating the FA-200 Microprocessor
Based Fire Alarm Control Panel.
About the FA-200Mircom's FA-200 Fire Alarm Control Panels provide 1, 2, 4, or 8 supervised Class B (ULI Style B) Initiating Circuits
or 1, 2, 4 supervised Class A (ULI Style D) Initiating Circuits, and 2 or 4 supervised Class A or B (ULI Style Z or Y)
Indicating Circuits. All Circuits are supervised for opens and ground faults, and Indicating Circuits for shorts.
Optional Modules include a DM-204 Zone Adder (required for full capacity in the FA-204E only), a DACT-100A
Dialler or a PR-100 Polarity Reversal & City Tie Module, and RM-204 or RM-208 Relay Modules. The two
enclosures are flush or surface mountable, and can be used for retrofits and on new installations.
Overall Features:• The small enclosure versions, FA-201, FA-202, & FA-204, have 1, 2, 4 Class B (Style B) initiating circuits
respectively. The FA-202 & FA-204 may be configured as 1 or 2 Class A (Style D) Circuits respectively. These
also have 2 Power Limited Class A/B (Style Z/Y) indicating circuits with individual trouble indicators.
• The large enclosure version, FA-204E, has four Class B (Style B) initiating circuits which may be configured as
two Class A (Style D) circuits respectively. It also has two power limited Class A/B (Style Z/Y) indicating circuitswith individual trouble indicators. With a DM-204 Zone Adder Module, an extra four Class B (2 Class A)
initiating circuits, and two Class A/B indicating circuits are added.
• Each initiating circuit is configurable as a normal or verified alarm. In addition, on a Class B FA-204 or fa-204e
Initiating Circuit three may be a Waterflow Zone (as may Initiating Circuit 7 if a DM-204 is installed), and
initiating circuit four may be a latched or non-latched supervisory zone (as may initiating circuit eight if a DM-
204 is installed). On a Class A FA-204E with a DM-204, initiating circuit three may be a waterflow zone and
initiating circuit four may be a latched or non-latched supervisory zone.
• Indicating circuits can be configured as audible or visual and as silenceable or non-silenceable. Audibles may
be steady, temporal code, california code, or march time.
• Initiating circuits may be individually disconnected by a slide-switch.
• Configurable signal silence inhibit (disabled or 1 minute), auto signal silence (disabled or 5, 10, 20 minutes),
and one-man walk test.
• Subsequent alarm, supervisory, and trouble operation.
• Four-wire resettable smoke power supply (200 mA max.).
• Auxiliary relay contacts for common alarm and common supervisory (disconnectable), and a common trouble
relay. If no Supervisory zones are configured then the common supervisory relay can be used as an extra
common alarm relay.
• Interface for an RTI Remote Trouble Indicator.
• RS-485 Interface for 1 to 3 of RAM-208 Remote Multiplex Annunciators on FA-204 & FA-204E.
• The FA-201, FA-202, FA-204 may use one of optional DACT-100A (Dialler), PR-100 (City Tie), RM-204 or RM
208 Relay Modules.
• The FA-204E may use one of optional DACT-100A (Dialler), PR-100 (City Tie), and one of
RM-204 or RM-208 Relay Modules.
• Slide Switch controls and LED Common indicators.
• Easy configuration via DIP switches.
• Extensive transient protection.
Technical Support
For all technical support inquiries, please contact Mircom’s Technical Support Department between 8 A.M. and 5
P.M. (EDT) Monday through Friday, excluding holidays.
Local Phone: 905-695-3535 Toll -Free Phone: 1-888-449-3535
Local Fax: 905-660-4113 Tol l-Free Fax: 1-888-660-4113
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 8/52
Document Conventions
2
Document Conventions
Circuits and Zones
The term circuits refers to an actual electrical interface, initiating (detection), indicating (signal), or relay.
The term zone is a logical concept for a fire alarm protected area, and will consist of at least one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual the term circuit is used.
Wiring Styles
Initiating circuits are configured by default as Class B (Style B). They may be globally (all or none) configured as
Class A (Style D) as described in System Configuration on page 28. This operation uses odd and even pairs of two-
wire Class B (Style B) circuits to make one four-wire Class A (Style D) circuit, thus cutting in half the number of
available initiating circuits.
Indicating circuits may be individually wired as Class A (Style Z) or Class B (Style Y) without affecting the number
of circuits available (see Field Wiring on page 12).
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 9/52
FA-200 Series Installation and Operation Manua
3
System Components
Chassis
Model Description
FA-201
Small enclosure fire alarm control panel with one Class B (Style
B) Initiating circuit, and two power limited Class B (Style Y)indicating circuits (1.70 amperes each, 2.4 amperes total) with
individual trouble indicators. Common alarm & trouble relays.
Interface for remote trouble indicator. Resettable four-wire
smoke detector power supply. May have one of DACT-100A,
PR-100, RM-204, or RM-208 installed. Can be used with BA-
104 (four amp-hour) or BA-1065 (6.5 amp-hour) batteries (two
required).
FA-202
Small enclosure fire alarm control panel with two Class B (Style
B) or one Class A (Style D) Initiating Circuits, and 2 Power
Limited Class A/B (Style Z/Y) Indicating Circuits (1.70 amperes
each, 2.4 amperes total) with individual trouble indicators.
Common Alarm & Trouble Relays. Interface for RemoteTrouble Indicator. Resettable Four Wire Smoke Detector Power
Supply. May have one of DACT-100A, PR-100, RM-204, or
RM-208 installed. Can be used with BA-104 (4 amp-hour) or
BA-1065 (6.5 amp-hour) batteries (2 required).
FA-204
Small enclosure Fire Alarm Control Panel with four Class B
(Style B) or two Class A (Style D) Initiating Circuits, and 2
Power Limited Class A/B (Style Z/Y) Indicating Circuits (1.70
amperes each, 2.4 amperes total) with individual trouble
indicators. Common Alarm & Trouble Relays. Interface for
Remote Trouble Indicator and/or 1 to 3 of RAM-208 Remote
Multiplex Annunciators. Resettable Four Wire Smoke Detector
Power Supply. May have one of DACT-100A, PR-100, RM-204,
or RM-208 installed. Can be used with BA-104 (4 amp-hour) or
BA-1065 (6.5 amp-hour) batteries (2 required).
FA-204E
Large enclosure Fire Alarm Control Panel with four Class B
(Style B) or two Class A (Style D) Initiating Circuits, and 2
Power Limited Class A/B (Style Z/Y) Indicating Circuits (1.70
amperes each, 5 amperes total) with individual trouble
indicators. Common Alarm & Trouble Relays. Interface for
Remote Trouble Indicator and/or 1 to 3 of RAM-208 Remote
Multiplex Annunciators. Resettable Four Wire Smoke Detector
Power Supply. May have one of DACT-100A or PR-100, and
one DM-204 installed. May also have one of RM-204 or RM-
208 installed. Can be used with BA-104 (4 amp-hour), BA-
1065 (6.5 amp-hour), or BA-110 (10 amp-hour) batteries (2
required).
FIRE ALARM CONTROL
;
FIREDRILL
;
SIGNALSILENCE
;
AUXILIARYDISC.
A.C. ON
COMMON
ALARM
COMMONSUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
GROUNDFAULT
REMOTETROUBLE
TEST/CONFIG.
;
DISC. 1
ZONE1
ZONE2
ZONE3
ZONE4
;
DISC. 2
;
DISC. 3
;
DISC. 4
; ;
DISC. 5
ZONE5
ZONE6
ZONE7
ZONE8
; ;
DISC. 6
; ;
DISC. 7
; ;
DISC. 8
FIRE ALARM CONTROL
;
FIRE
DRILL
;
SIGNAL
SILENCE
;
AUXILIARY
DISC.
A.C. ON
COMMON
ALARM
COMMON
SUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
GROUND
FAULT
REMOTE
TROUBLE
TEST/CONFIG.
;
DISC. 1
ZONE1
Z ON E2
Z ON E3
ZONE4
;
;
DISC. 2
;
DISC. 3
;
DISC. 4
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 10/52
Document Conventions
4
Circuit Adder Modules
Auxiliary Models
These fire alarm control panels are normally provided with a beige enclosure. The FA-201U, FA-202U, FA-204U,
and FA-204EU models have red enclosures.
FA-200 Accessories
Models Description
DM-204
Zone Adder Module for the FA-204E. Brings the
total capacity to eight Class B (Style B) or four
Class A (Style D) Initiating Circuits, and 4 Power
Limited Class A/B (Style Z/Y) Indicating Circuits
(up to 1.7 amperes each, 5 amperes total).
RM-208
Relay Adder Module for the FA-204 or FA-204E.
Adds eight configurable Form-C Relays rated 1A,
28 VDC.
RM-204
Relay Adder Module for the FA-204 or FA-204E.
Adds four configurable Form-C Relays rated 1A,
28 VDC.
Model Description
PR-100 Polarity Reversal and City Tie Module
DACT-100A Digital Communicator / Dialler Module.
Model Description
RAM-208 Eight-Zone Remote Annunciator (ULC and ULI approved)
RTI-1 Remote Trouble Indicator (ULC and ULI approved)
MP-300 End-of-line Resistor Plate, stainless steel finish
MP-300R EOL Resistor Plate, red (ULC approved)
BC-160 External Battery Cabinet (ULC and ULI approved)
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 11/52
FA-200 Series Installation and Operation Manua
5
Mechanical Installation and Dimensions
Install the enclosure as shown in Figure 1, below for the FA-201, FA-202, or FA-204.
Figure 1: FA-201, 202, and 204 Enclosure Installation and Dimensions
DOOR
BACKBOXWALL
(SIDE VIEW)
SURFACE
DOOR
83 "3-
BACKBOX
DIA.
WALL
(SIDE VIEW)
FLUSH
BACKBOX
DOOR
-165
"
13 43- "
"-58
1
1- "2
10
7- "32 HOLE
1243- "
87- "
8 "
-1581"
-81"14
1-8
3 "
-
3
31 "
41"
#6 x 5/16" SCREW
KNOCKOUT
-87"&"1
8-1
158- "
FINISH: PAINTED
MATERIAL: 18GA (0.048") THICK
COLD ROLLED STEEL
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 12/52
Mechanical Installation and Dimensions
6
Figure 2: FA-204 E Enclosure Installation and Dimensions
FINISH: PAINTED
DOOR 16GA (0.059") THICK
COLD ROLLED STEEL
DOOR
BACKBOX
(SIDE VIEW)
SURFACE
DOOR
45 "1
-
BACKBOX
(SIDE VIEW)
FLUSH
BACKBOX
DOOR
-165"
WALL WALL
32"-
7DIA.
HOLE
"7
815 -
16 "5
16-
14-3"
11"
"-1
214
1"
"5
""-
4
31
21
1-
"-7
814
1-8
1 " & "7
8-
KNOCKOUT
-122
1"
8
3-1 "
2 "
8
3"4 -
2 "
#6 x 5/16" SCREW
MATERIAL: BACKBOX 18GA (0.048") THICK
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 13/52
FA-200 Series Installation and Operation Manua
7
Modules Mounting Locations
The FA-200 eries come pre-assembled with all components and boards, except for adder modules. Module
installation locations are shown below.
Be sure to connect a solid Earth Ground (from building system ground / to a cold water pipe) to the Chassis Earth
Ground Mounting Lug, and to connect the Earth Ground Wire Lugs from the Main Chassis to the ground screw on
the backbox.
Figure 3: FA-201, 202, and 204 Module Mounting Locations
Notes:
1. Relay module may be model RM-204 or RM-208.
2. Only one of PR-100 or DACT-100A may be installed.
PR-100)DACT-100A)
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 14/52
Modules Mounting Locations
8
Figure 4: FA-204E Module Mounting Locations
Notes:
1. Relay module may be model RM-204 or RM-208.
2. Only one of PR-100 or DACT-100A may be installed.
P8
P7
SEE NOTE 2
(MODEL DACT-100A)
DIALER MODULE
SEE NOTE 2
(MODEL PR-100)
POLARITY REVERSAL ANDCITY TIE MODULE
M/F HEX SPACER#6-32 x 7/8"
SCREW
#6-32 x 1/4"
DISPLAYPLATE
BACKBOX
ZONE ADDER
MODULE
(DM-204)
MAIN FIRE
ALARM
MODULE
RELAY MODULE
(NOTE 1)
P1
P6
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 15/52
FA-200 Series Installation and Operation Manua
9
Module Settings
Main Fire Alarm Module
Class A / B Selection
On the FA-202, FA-204 and FA-204E only, JW1 & JW2 are connected from 1 to 2 for initiating circuit Class B (Style
B) operation, and from 2 to 3 for Class A (Style D) operation. These are not present on the FA-201, and only JW2 is
present on the FA-202.
Zone Adder Module: On an FA-204E only, remove the jumper on JW4 if a DM-204 Zone Adder Module is installed
The zone adder module is plugged into P6 & P7.
Relay Module: Remove the jumper on JW3 if an RM-204 or RM-208 Relay Module is installed. The relay module is
plugged into P1.
Digital Communicator: Remove the jumper on JW6 if a DACT-100A Digital Communicator is installed. The digita
communicator is plugged into P8.
City Tie: Remove the jumper on JW6 if a PR-100 City Tie is installed. The City Tie is plugged into P8.
Battery: Connected to P2(+) & P3(-) via the factory installed cables.
Transformer: Factory wired to P4 & P5, do not disconnect.
JW5: There should be no jumper here; do not use.
SW9,11,13: Configuration DIP switches.
Battery Fuse F1: Replace with 10 amp, 1-1/4" fast acting fuse.
Figure 5: Main Fire Alarm Module
Note: The Class A/B selection affects all initiating circuits, and must be used with the correct Configuration
DIP switch setting.
P6
F110 AMPBATTERYFUSE
SW13
1
2
3
JW2
P3
23 1
BATT+
P4
P5
P2
BATT-
XMFR
XMFR
JW1P7
P8
JW4
JW5
JW3
JW6SW11 SW9
P1
SUPV RLYC O M -
C O M + S I N D 2 -
I N D 2 -
I N D 1 -
I N D 1 -
I N D 1 +
I N D 1 +
I N I 4 -
I N I 4 +
I N I 3 -
I N I 3 +
I N I 2 -
I N I 2 +
I N I 1 -
I N I 1 +
4 8 5 -
4 8 5 + - + T R B
T R L I N D 2 +
I N D 2 + N O N C
C O M
ALM RLYN O N C
C O M
TBL RLY4 WIREN O N C
C O M
Note: Do not plug DACT into P1 on main
board. Plug into P8 only when system is
powered off.
Note: Do not plug RM-204/
208 into P8 on main board.
Plug into P1 only when
system is powered off.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 16/52
Module Settings
10
Zone Adder Module (Model DM-204)
Figure 6: DM-204 Zone Adder Module
Class A / B Selection: JW2 & JW3
are connected from 1 to 2 for initiating
circuit Class B (Style B) operation,
and from 2 to 3 for Class A (Style D)
operation.
P1 & P2: Connections to P7 & P6
respectively on the main fire alarm
board.
SW5,6: Config DIP switches.
Relay Modules (Models RM-204 or RM-208)
Figure 7: RM-204 or RM-208 Relay Adder Module
P1: Connect to P1 on the main fire
alarm board.
By the factory setting, the four or
eight relays are controlled by
initiating circuits 1 to 8
respectively. This is configured by
selecting:
• JW1: Initiating Circuit #1
controls Relay #1.
• JW2: Initiating Circuit #2
controls Relay #2.
• JW8: Initiating Circuit #8
controls
Relay #8.
Alternately, each relay may be set
as a Common Alarm or Common
Supervisory Relay by removing
the jumper from JW1 to JW1A,
etc. These jumpers have two
positions to select Alarm or
Supervisory each.
• JW1A: Alarm or supervisory control for Relay #1.
• JW2A: Alarm or supervisory control for Relay #2.
• JW8A: Alarm or supervisory control for Relay #8.
Finally, there are jumpers JW1.2, JW2.3, up to JW7.8 that allow a relay to have the same control as an adjacent
relay. For example, starting with the factory default setting, moving the jumper from JW2 to JW1.2 will make both
relays 1 & 2 operate with Initiating Circuit #1.Contact Mircom Technical Support for assistance if required.
Note: The Class A/B
selection affects all
initiating circuits, and
must be used with the
correct Configuration
DIP switch setting.
P1
F I E L D W I R I N G T E R M I N A L
S
P2
SW5
2 31
JW3
SW6
2 31
JW2
ALM
K1
RLY1
R M -
2 0 8 / R M - 2 0 4
R E L
A Y
M O D U L E
RLY2 RLY3 RLY4 RLY5 RLY6 RLY7 RLY8
N O
N O
N C
C O M
N O
N C
C O M
N O
N C
C O M
C O M
N O
N C
C O M
N O
N C
C O M
N O
N C
N C
C O M
N O
N C
C O M
K2 K3 K4 K5 K6 K7 K8
J W 1 A
SUPV
JW1 JW2 JW3 JW4
P1
JW5 JW6 JW7 JW8
JW1.2
AL M J W 2 A
SUPV
JW2.3
AL M J W 3 A
SUPV
JW3.4
AL M J W 4 A
SUPV
JW4.5
AL M J W 5 A
SUPV
JW5.6
ALM J W 6 A
SUPV
JW6.7
AL M J W 7 A
SUPV
AL M J W 8 A
SUPV
JW7.8
Note: Do not plug RM-204/
208 into P8 on main board.
Plug it into P1 only when
the system is powered off.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 17/52
FA-200 Series Installation and Operation Manua
1
DACT / Dialler Module (Model DACT-100A)
P1: Cable to P8 on the main fire alarm board.
Jumper JW6 on the main fire alarm module must be removed if a DACT-100A is installed. note that this module
cannot be installed if a polarity reversal and city tie module is used.
Figure 8: DACT-100A Dialer Module
Please see the DACT-100A Manual (LT-639) for more information.
Polarity Reversal and City Tie Module (Model: PR-100)
P1: Cable to P8 on the main fire alarm module.
JW1: Cut this jumper for trouble transmission. When this jumper is cut and a system trouble occur, the designated
terminals will transmit a "zero volts" or "open" circuit. Please note that at normal condition, the terminals polarity is
read exactly as labelled on the circuit board.
Jumper JW6 on the main fire alarm module must be removed if a polarity reversal and city tie module is installed.
note that this module cannot be installed if a DACT / dialler module is used.
Figure 9: PR-100 Polarity Reversal and City Tie Module
Note: The DACT is Tip & Ring sensitive. If any of the two LEDs are illuminated amber, reverse the wiring,
then wait 30 seconds for the LED to clear.
P 1
F I E L D W I R I N G T E R M I N A L S
Note: Do not plug DACT into P1 on main board.Plug it into P8 only when the system is powered off.
JW1
P1
CITY
TIE
+ -
POL.
RVS.
+ -
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 18/52
Field Wiring
12
Field Wiring
General Field Wiring Considerations
Because most of the Field Wiring on the FA-200’s is to the Main Boards on the swinging dead front, it is very
important to properly dress the wires so as not to place stress on either their connection to the boards, or running to
conduit. The Figure below shows the required wiring techniques.
Figure 10: General Field Wiring Considerations
USE AT LEAST
3 WIRE TIES
AS SUPPLIED
THROUGH HOLES
ON DEADFRONT
WIRE TIE
IN 2 PLACES
TO BACK OF
ENCLOSURE
DRESS WIRES NEAR
TOP OF ENCLOSURE
CLEAR OF ADDER
MODULES
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 19/52
FA-200 Series Installation and Operation Manua
13
Main Fire Alarm Module Terminal Connections
Wire devices to terminals as shown in Figure 11 below. See Wiring Tables on page 20 for wiring instructions,
Appendix A on page 33 for compatible devices, and Appendix C on page 38 for specifications.
Figure 11A: Main Fire Alarm Module Terminal Connections
When wiring devices, please keep in mind the following:
• All terminals are shown from the back of the main fire alarm board assembly (pointing towards the rear of the
enclosure).
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 vp-p ripple, 50 mA max. alarm.
They may be configured as required. The alarm threshold is 21 mA. Maximum loop resistance is 100 ohms, 50
ohms per side.
• Indicating circuits are fully supervised and rated for 24 VDC unfiltered 1.7 amp max. each They must be wired
as shown in the wiring tables on page 20.
• On the FA-204 & FA-204E, the auxiliary common supervisory relay contacts will act as a second set of common
alarm contacts if there are no initiating circuits set as supervisory.
• Initiating circuits must be all either Style B or D. If Style D is selected, cut the number of circuits in half.
ATTENTION: Do not exceed power supply ratings:
•FA-201, FA-202, FA-204, total current for indicating circuits is 2.4 A max.
•FA-204E, total current for indicating circuits is 5 A max.
AUX. POWER NEGATIVE FOR
REMOTE ANNUNCIATORS
NO
NC
COM
TROUBLE
RELAY
NO
NC
COM
SUPV.
RELAY
NO
NC
ALARM
RELAY
MUST BE
CONNECTED TO A
LISTED POWER
LIMITED SOURCE
OF SUPPLY
COMMON TROUBLE
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
AUXILIARY COMMON
SUPERVISORY
CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
(NOT PRESENT ON
FA- 201 & FA-202)
AUXILIARY COMMON
ALARM CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
IND2+ (Z)
IND2- (Z)
IND2- (Y/Z)
SUPERVISED INDICATING CIRCUIT #2
(POWER LIMITED)
IND1+ (Z)
CLASS A /
STYLE Z
WIRING
IND1- (Y/Z)
IND1+ (Y/Z)
IND2+ (Y/Z)
IND1- (Z)
EXAMPLES OF BOTH CLASS AA@ AND AB@ WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
SUPERVISED INDICATING CIRCUIT #1
(POWER LIMITED)
BELL, HORN, OR STROBE
Legend: See Appendix A for compatible devices.
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
COM
COM-
CLASS B /
STYLE Y
WIRING
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 20/52
Field Wiring
14
Figure 11B: Main Fire Alarm Module Terminal Connections (cont’d)
When wiring devices, please keep in mind the following:
• All terminals are shown from the back of the main fire alarm board assembly (pointing towards the rear of the
enclosure).
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable.
• Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 vp-p ripple, 50 mA max. alarm.
They may be configured as required. The alarm threshold is 21 mA. Maximum loop resistance is 100 ohms, 50
ohms per side.
• Initiating circuits are compatibility ID “A”.
SUPERVISORY OR
WATERFLOW
SWITCH (NO)
HEAT DETECTOR
LEGEND:See Appendix A for compatible devices.
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOM
PULL STATION
S
-RS-485
1 TO 3 OF RAM-208 REMOTE ANNUNCIATORS
SEE RAM-208 OPERATION & INSTALLATION
MANUAL. (NOT USED WITH RTI)
24VDC PO WER +
(POWER LIMITED) -
-
+
4-WIRE
SUPPLY
INI1+
INI1-
INI2+
INI2-
INI3+
INI3-
INI4+
INI4-
STYLE D
INI2
STYLE D
INI1
CLASS B /
STYLE B
WIRING
CLASS A /
STYLE D
WIRING
SUPERVISED INITIATING CIRCUIT #4
(SHOWN AS SUPV ZONE, POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #3
(SHOWN AS ALARM ZONE, POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #1
(POWER LIMITED)
RESETTABLE 4-WIRE
SMOKE DETECTOR POWER
LIMITED, POWER SUPPLY.
28 VDC, 100 mA MAX.,
1.5VP-P RIPPLE.
COM+
RTI REMOTE TROUBLE INDICATOR
(NOT USED WITH RAM-208'S)
TRBRTI
INTERFACE
TRL
+
EXAMPLES OF BOTH CLASS AA@ AND AB@ WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
CLASS B /
STYLE B
WIRING
COM-
(SEE FIG.11)
BLU
RS-485 INTERFACE
(POWER LIMITED)
AUX. POWER POSITIVE
BLK
RED & WHTRTI
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 21/52
FA-200 Series Installation and Operation Manua
15
Zone Adder Module (DM-204) Terminal Connections
Wire devices to terminals as shown below in Figure 12. See Wiring Tables for on page 20wiring instructions,
Appendix A on page 33 for compatible devices, and Appendix "C on page 38 for Module specifications.
Figure 12: DM-204 Zone Adder Module Terminal Connections
Notes:
• All terminals are shown from the back of the main fire alarm board assembly (pointing towards the rearof the enclosure).
• All power limited circuits must use type fPL, FPLR, or FPLP power limited cable.
• Initiating circuits are fully supervised and rated for 26 VDC, 3 ma standby, 1.5 vp-p ripple, 50 mA max.
alarm. They may be configured as required. The alarm threshold is 21 mA. Maximum loop resistance
is 100 ohms, 50 ohms per side.
• Initiating circuits are compatibility ID “A”.
SUPERVISORY OR
WATERFLOW
SWITCH (NO)
HEAT DETECTOR
LEGEND: See Appendix A for compatible devices.
SMOKE DETECTOR
3.9K 1/2W ELR LISTED S5434
MODEL MP-300 MANUFACTURED
BY MIRCOMPULL STATION
CLASS A / STYLE D NOTE:INITIATING CIRCUITS MUST BE ALL EITHER STYLE B OR
D.IF ST YLE D IS SELECTED, THE NUMBER OF CIRCUITS
IS CUT IN HALF.
BELL, HORN, OR STROBE
INI5+
INI5-
INI6+
INI6-
INI7+
INI7-
INI8+
INI8-
STYLE D
INI4
STYLE D
INI3
CLASS B /
STYLE B
WIRING
CLASS A /
STYLE D
WIRING
SUPERVISED INITIATING CIRCUIT #8
(SHOWN AS SUPV ZONE, POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #7
(SHOWN AS ALARM ZONE, POWER LIMITED)
SUPERVISED INITIATING CIRCUIT #3
(POWER LIMITED)
IND4+ (Z)
IND4- (Z)
IND4-(Y/Z)
SUPERVISED INDICATING CIRCUIT #4
(POWER LIMITED)
IND3+ (Z)
CLASS A /
STYLE Z
WIRING
IND3- (Y/Z)
IND3+ (Y/Z)
IND4+ (Y/Z)
IND3- (Z)
CLASS B /
STYLE Y
WIRING
SUPERVISED INDICATING CIRCUIT #3
(POWER LIMITED)
CLASS B /
STYLE B
WIRING
EXAMPLES OF BOTH CLASS AA@ AND AB@ WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
EXAMPLES OF BOTH CLASS AA@ AND AB@ WIRING ARE SHOWN, BUT
ONLY ONE CLASS OF WIRING MAY BE USED IN ANY INSTALLATION.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 22/52
Field Wiring
16
Relay Module (RM-204 or RM-208) Terminal Connections
Note that only relays #1 to #4 are present on the RM-204.
Figure 13: Relay Module (RM-204 or RM-208) Terminal Connections
Notes:
• All power limited circuits must use type FPL, FPLR, or FPLP power limited cable. Must be connected to a
listed power limited source of supply.
NO
NCRELAY #2
COM
NO
NCRELAY #1
COM
NO
NCRELAY #3
COM
NO
NCRELAY #4
COM
NO
NCRELAY #5
COM
NO
NCRELAY #6
COM
NO
NCRELAY #7
COM
NO
NCRELAY #8
COM
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
RELAY CONTACTS
28 VDC, 1 AMP
RESISTIVE LOAD
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 23/52
FA-200 Series Installation and Operation Manua
17
DACT / Dialler Module (DACT-100A) Terminal Connections
The following diagram shows the wiring connection for the DACT-100A, refer to the Manual for more details.
Wire the two telephone lines devices to terminals as shown in Figure 14 below.
Line 1 Input (Tip/Ring): To the first Telephone Line via the required RJ31X Connector.
Line 1 Output (Tip/Ring): To an optional Premise Telephone on the first Telephone Line via the required RJ31X
Connector.
Line 2 Input (Tip/Ring): To the second Telephone Line via the required RJ31X Connector.Line 3 Output (Tip/Ring): To an optional Premise Telephone on the second Telephone Line via the required RJ31X
Connector.
Note that most AHJs do not allow the connection of premise telephones. See Wiring Tables on page 20and
Appendix C page 38 for more information.
Figure 14: DACT-100A Wiring Diagram
Note: The terminal blocks are “depluggable” for ease of wiring.
P1 FOR
CONNECT
TO FIRE
ALARM
PANEL
P2 FOR RS-485
I/F TO PC
LINE-1
TIP / RING TIP / RING TIP / RING
DACT-100A MAIN BOARD
IN OUT INOUT
LINE-2
RING / TIP
PREMISE PHONE
(IF PERMITTED)
TO
TELEPHONE
COMPANY
WIRING
B R O W N
G R A Y
G R E E N
R E D
TIP
RING
RJ31X
4
3 2
1
5
6 7
8
V
RED
BLACK
-
+
VOLTAGEMEASUREDSHOULD BEAPPROX. 40V
AlanticScientificModel#24544ProtectiveDevice orsimilar ULListedQVRGSecondary
Protector
PROTECTORBLOCK
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 24/52
Field Wiring
18
Polarity Reversal and City Tie Module (Model: PR-100) Terminal Connections
See Appendix C on page 38 for module specifications. Wire as shown in Figure 15 below using proper wire gauges.
Note that for use in the USA, the installer must add an Atlantic Scientific (Tel. 407-725-8000) Model #24544
Protective Device, or similar ULI-Listed QVRG Secondary Protector, as shown. For use in Canada, the protective
device is still recommended, but the PR-100 may be connected directly to polarity reversal and city tie wiring.
Figure 15: PR-100 Polarity Reversal and City Tie Module Terminal Connections
When wiring devices, please keep in mind the following:
• Plug PR-100 ribbon cable (P1) into the main fire alarm module.
• Cut Jumper (JW!) on the PR-100 module in order to transmit a trouble condition to the monitoring station.
• All circuits are power limited and must use type FPL, FPLR, or FPLP power limited cable.
• For polarity reversal operation, short the city tie connection.
Notes:
• The terminal blocks are “depluggable” for ease of wiring.
• The city tie interface is not power limited.
• Use either the PR-100’s City Tie or Reverse Polarity Interface Module--not both.
+
-
USE A SHORTING WIRE WHEN
THE CITY TIE IS NOT IN USE.
P R O T E C T E D
+
-
2
1
S
1
2
S
1
1
2
2
S
S
POLARITY REVERSAL
24VDC OPEN
12VDC AT 3.5 mA
8 mA MAX SHORT.
(See Note 4)
PR-100
U N P R O T E C T E D
+
+
-
-
DIN RAIL CONNECTION
TO EARTH GROUND.
CITY TIE LOCAL ENERGY
24 VDC UNFILTERED
TRIP COIL 14 OHMS,
210mA,5mV RIPPLE.
CONFORMS TO NEMA STANDARD
SB3-1969 INTENDED FOR
CONNECTION TO POLARITY
REVERSAL CIRCUIT OF A REMOTE
STATION RECEIVING UNIT HAVING
COMPATIBLE RATINGS.
PROTECTOR
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 25/52
FA-200 Series Installation and Operation Manua
19
Power Supply Connections
The power supply is part of the main fire alarm module and the chassis. The ratings are:
See Appendix C on page 38 for module specifications. Wire as shown in Figure 16 below, using proper wire
gauges.
Figure 16: Power Supply Connections
ModelElectrical Input
RatingsPower Supply Total
CurrentBattery Fuse on Main
Module
FA-201, FA-202,
FA-204
120 V 60Hz 2A /
240V 50 Hz 1A2.75 A maximum
F1: Replace with 10 amp, 1-
1/4" fast acting fuse
FA-204E120 V 60Hz 2A /
240V 50 Hz 1A6 A maximum
F1: Replace with 10 Amp,
1-1/4" Fast Acting Fuse
ATTENTION:
• Do not exceed power supply ratings:
• To prevent sparking, connect batteries after the systems main A.C. power is turned on.
P2
MAIN FIRE ALARM MODULE
GREEN
TO 24 VDC
BATTERY
BLACK
P4P5 P3
+- BAT
RED
EARTH GROUNDDIMPLE ONENCLOSURE,FORGROUNDINGWIRES ANDSCREW.
GREEN EARTH GROUNDWIRE SOLDERED ONTO MAINFIRE ALARM MODULE PCB.
LL N G
TO DEDICATED
BRANCH CIRCUIT
2 4 0 V ,
5 0 H z
1 2 0 V ,
6 0 H z
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 26/52
Field Wiring
20
Wiring Tables
Table 1: Wiring Table for Initiating Circuits.
Table 2: Wiring Table for Indicating CircuitsMain board indicating circuits are rated for 1.7 amps each. The SGM-1004(A) indicating circuits are rated for 1.7
amps each.
RS-485 Wiring : See the wiring information for the remote annunciator being used.
4-Wire Smoke Wiring: The maximum allowable current is 0.2 amperes. The maximum allowed voltage drop is 1
volt. Refer to Table 2: WIring for Indicating Circuits above.
Wire Gauge Maximum Wiring Run to Last Device (ELR)
(AWG) ft. m
22 2990 910
20 4760 1450
18 7560 2300
16 12000 3600
14 19000 5800
12 30400 9200
Note: Maximum loop resistance should not exceed 100 Ohms.
Total SignalLoad
Maximum Wiring Run to Last Device (ELR)Max Loop
Resistance
18AWG 16AWG 14AWG 12AWG 0hms
Amperes ft. m ft. m ft. m ft. m Ohms
0.06 2350 716 3750 1143 6000 1829 8500 2591 30
0.12 1180 360 1850 567 3000 915 4250 1296 15
0.30 470 143 150 229 1200 366 1900 579 6
0.60 235 71 375 114 600 183 850 259 3
0.90 156 47 250 76 400 122 570 174 2
1.20 118 36 185 56 300 91 425 129 1.5
1.50 94 29 150 46 240 73 343 105 1.2
1.7 78 24 125 38 200 61 285 87 1.0
Note: Maximum voltage drop should not exceed 1.8 volts.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 27/52
FA-200 Series Installation and Operation Manua
2
System Checkout
Before Turning The Power On...
1. To prevent sparking, do not connect the batteries. Connect the batteries after powering the system from the
main AC supply.
2. Check that all modules are installed in the proper location with the proper connections.3. Check all field (external) wiring for opens, shorts, and ground.
4. Check that all interconnection cables are secure, and that all connectors are plugged-in properly.
5. Check all jumpers and switches for proper setting.
6. Check the AC power wiring for proper connection.
7. Check that the chassis is connected to Earth Ground (cold water pipe).
8. Make sure to close the front cover plate before powering the system from main AC supply.
Power-up Procedure
1. After completing the System Checkout procedures, power-up the panel. The "AC-ON" green LED should illu-
minate, the “Common Trouble” LED should illuminate, and the buzzer should sound.
2. Press the System Reset button. Since the batteries are not connected, the "Battery Trouble" LED shouldilluminate, and the buzzer should sound intermittently, and the Common Trouble LED should flash.
3. Connect the batteries while observing correct polarity; the red wire is positive (+) and black wire is negative (-)
All indicators should extinguish except for normal power "AC-ON" green LED.
4. Configure the fire alarm control panel as described in the System Configuration section on page 28.
Troubleshooting
Message Description
Circuit Trouble
Normally when a circuit trouble occurs, its designated trouble indicator will be illuminated,
as well as the Common Trouble indicator and Trouble buzzer. To correct the fault, check for
open wiring on that particular circuit loop or see if the circuit disconnect switch is in the ON
or CLOSED position. Note: disconnecting a circuit will cause a system trouble (off-normal
position).
Remote FailThe panel will display a Remote Fail for any failure reported by, or failure to communicate
with a remote annunciator, DACT-100A, or PR-100.
Ground FaultThe FA-200 panel has a Common Ground Fault Detector. To correct the fault, check for any
external wiring touching the chassis or other earth ground connection.
Battery Trouble
Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will
cause a battery trouble. If battery trouble condition persists, replace the batteries as soon
as possible.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 28/52
Indicators, Controls, & Operation
22
Indicators, Controls, & Operation
Refer to Figure 17 below for LED Indicators and control switch locations.
Figure 17: Indicators and Control Location
Indicators
Buzzer
The buzzer is activated by any of the following:
• Fire alarm: steady
• Supervisory alarm: steady
• Trouble: trouble flash rate
If the buzzer turns on in response to a non-latching trouble or supervisory, it will be turned off if the condition causing
it goes away and there is no other reason for it to be on.
AC On LED
The green AC On LED illuminates steadily while the main AC power is within acceptable levels. It turns off when thelevel falls below the power-fail threshold and the panel switches to standby (battery) power.
Common Alarm LED
The Common Alarm indicator turns on steady red whenever the panel is in alarm as a result of an alarm on any
initiating circuit. Since all alarms are latched until the panel is reset, the indicator will remain on until reset.
FIRE
DRILL
SIGNAL
SILENCE
AUXILIARY
DISC.
A.C. ON
COMMON
ALARM
COMMON
SUPERVISORY
COMMON
TROUBLE
BATTERY
TROUBLE
GROUND
FAULT
REMOTE
TROUBLE
TEST
DISC. 1
ZONE 1
ZONE 2
ZONE 3
ZONE 4
DISC. 2
DISC. 3
DISC. 4
DISC. 1
ZONE 5
ZONE 6
ZONE 7
ZONE 8
DISC. 2
DISC. 3
DISC. 4
SIG.ZONE 2
TROUBLE
SIG.ZONE 1
TROUBLE
SIG.ZONE 4
TROUBLE
SIG.ZONE 3
TROUBLESYSTEM
RESET
BUZZER
SILENCE
LAMP
TEST
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 29/52
FA-200 Series Installation and Operation Manua
23
Common Supervisory LED (FA-204 or FA-204E only)
The amber Common Supervisory LED illuminates steadily when there is a supervisory alarm in the panel resulting
from any latching or non-latching supervisory circuit. The LED turns off if all non-latching supervisory circuits are
restored and there are no active latching supervisory circuits. Latching supervisory alarms remain active until the
panel is reset.
Common Trouble LED
The Common Trouble indicator flashes amber (at 20 flashes per minute) when the panel detects any trouble
condition. It turns off when all non-latching troubles are cleared.
Remote Trouble LED (FA-204 or FA-204E only)
The Remote Failure indicator illuminates amber if the panel detects trouble at a city tie or dialler module, or
communication or local trouble with a remote annunciator. It turns off once these conditions return to normal.
Fire Drill LED
The amber Fire Drill LED illuminates steadily while fire drill is active.
Auxiliary Disconnect LED
The Auxiliary Disconnect Indicator flashes amber (20 flashes per minute) when the Auxiliary Disconnect switch is
activated. It turns off when the switch is activated a second time. When on, the Auxiliary Disconnect LED indicates
that common alarm and common supervisory relays, and any RM-204 / RM-208 relays are not activated. The
trouble relay is activated. If installed, dialler or polarity reversal and city tie modules are also inactive, causing a
trouble condition.
Signal Silence LED
The amber Signal Silence LED flashes at the trouble flash rate when indication circuits are silenced either by the
Signal Silence button or by the Auto Signal Silence timer. It turns off when the signals are re-sounded by a
subsequent alarm.
Battery Trouble LED
The Battery Trouble LED flashes amber at the trouble flash rate when the battery is either low (below 20.4 VDC) or
disconnected.
Ground Fault LEDThe Ground Fault LED flashes amber at the trouble flash rate when the Ground Fault Detector detects a ground
fault on any field wiring. It turns off when the ground fault is cleared.
Test LED
The Test LED illuminates amber when the fire alarm panel is in walk test mode.
Circuit Status LEDs
These LEDs indicate the status of initiating circuits. They illuminate
• Alarm: Steady red
• Alarm Verification or waterflow retard in progress: fast flashing red (120 flashes per minute)
• Pending Alarm: (see Circuit Disconnect Switches on the following page) fast flashing red (120 flashes per
minute)• Supervisory: Steady amber
Circuit Trouble LEDs
These LEDs indicate trouble for initiating and indicating circuits. They flash (20 flashes per minute) for any field
wiring fault, or if the circuit has been disconnected.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 30/52
Indicators, Controls, & Operation
24
Controls
System Reset Switch
The System Reset momentary switch resets the fire alarm control panel and all circuits:
Signal Silence Switch
Activating the Signal Silence momentary switch when the panel is in alarm turns on the signal silence indicator and
deactivates any silenceable indicating circuits. Non-silenceable circuits are unaffected. Signals will re-sound upon
any subsequent alarm. This switch does not function during any configured Signal Silence Inhibit timer period. It
also does not function if the indicating circuits are active as the result of a fire drill.
Fire Drill Switch
The Fire Drill momentary switch activates all non-disconnected indicating circuits, but does not transmit any alarms
via the dialler, city tie, or common alarm relay, nor are any RM-204 or RM-208 relays activated. The fire drill iscancelled by activating the switch again, or if the panel goes into a real alarm.
Auxiliary Disconnect Switch
Activating the Auxiliary Disconnect momentary switch activates the auxiliary disconnect function. Activating the
switch again de-activates the function. When auxiliary disconnect is active, common alarm and common
supervisory relays, and any RM-204 / RM-208 relays are not activated. The trouble relay is activated. If installed,
dialler or polarity reversal and city tie modules are also inactive, causing a trouble condition.
Lamp Test Switch
Activation of the Lamp Test momentary switch turns all front panel Indicators and the buzzer on.
Buzzer Silence Switch
Activation of the Buzzer Silence momentary switch while the Buzzer is sounding silences the Buzzer. The Buzzer
will resound if there is a subsequent event. Switch activation will also silence the buzzer on all attached
annunciators.
Circuit Disconnect Switches
Activation of these non-momentary switches disconnects the respective Initiating Circuit, and causes a Circuit
Trouble for that Initiating Circuit while active. If the disconnect switch is turned off (to its normal position) while there
is an Alarm condition in that circuit, the respective circuit Status LED will flash at a rate of 120 flashes per minute to
indicate a Pending Alarm, for 5 seconds. If the disconnect switch is not turned back on, an Alarm will be processed
normally.
•Resets all latching trouble conditions •Resets all initiating circuits
•Resets four-wire smoke supply •Turns off all indicating circuits
•Turns off Signal Silence •Turns off Fire Drill•Stops and resets all timers •Processes inputs as new events
•Aux Disconnect is not affected
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 31/52
FA-200 Series Installation and Operation Manua
25
Operation
All alarm inputs are treated in a similar manner. Alarm inputs include non-verified or verified alarms, and water-flow
alarms. Activation of any alarm input when the panel is not already in alarm cause the following:
• The buzzer sounds steadily
• If fire drill is active, it is cancelled
• The Common Alarm indicator turns on
• the common alarm relay activates if aux disconnect is not active• The Auto Signal Silence timer, if configured, starts
• The Signal Silence Inhibit timer, if configured, starts
• RM-204 / RM-208 relays are activated as configured, provided that aux disconnect is not active
• Signals and strobes are activated
Subsequent Alarms when the panel is already in alarm, cause the following:
• The buzzer sounds steadily
• If signals have been silenced as a result of the signal silence button or the auto signal silence timer, signals are
resounded as they were before signal silence, the signal silence indicator is turned off, and the auto signal
silence timer, if configured, is restarted
• Signals and strobes are activated
Circuit Types
The term circuits refers to an actual electrical interface, either initiating (detection) or indicating (signal). The term
zone is a logical concept for a fire alarm protected area, and will consist of at least one circuit. Often the terms zone
and circuit are used interchangeably, but in this manual the term circuit is used.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 32/52
Indicators, Controls, & Operation
26
Initiating (Detection) Circuit Types
Circuit Type Description
Non-Verified Alarm
This is a "normal" type of alarm which may have pull stations, smoke detectors, or heat
detectors attached. Any activation of these devices will immediately result in an alarm condition
in the fire alarm control panel. An alarm condition causes the associated circuit Status LED and
the Common Alarm LED to illuminate red.
Verified Alarm
These alarms are verified by a reset and timing procedure, and may have pull stations, smoke
detectors, or heat detectors attached. Any activation of pull stations or heat detectors will result
in an alarm condition in the fire alarm control panel within four seconds. Smoke detectors will
be verified for a real alarm within 60 seconds depending upon the startup time of the smoke
detectors being used. If four seconds is too long a response time for pull stations, then they
should be wired separately on a non-verified alarm circuit. An alarm condition causes the
associated circuit Status LED and the Common Alarm LED to illuminate red.
Water-Flow Alarm
An alarm for water-flow sensors. These alarms are identical to normal non-verified alarms
except that any indicating circuits programmed to these circuits (all are by default) are non-
silenceable. Also, if water-flow retard operation is enabled, then these circuits are sampled
every one second; if ten samples are active within any 15 second interval, the water-flow alarm
is confirmed and processed. An alarm condition causes the associated circuit Status LED andthe Common Alarm LED to illuminate red. Note: Do not use the retard operation with any
external retarding device; maximum retard may not exceed 120 seconds.
Non-Latching
Supervisory
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit
Status LED and the Common Supervisory LED to illuminate amber. The buzzer will sound
continuously. If the circuit activation is removed, the supervisory condition will clear (so long as
there are no other supervisory conditions in the system) and the circuit Status LED will
extinguish.
Latching
Supervisory
These alarms are for supervisory devices. An activation on these circuits will cause the Circuit
Status LED and the Common Supervisory LED to illuminate amber. The buzzer will sound
continuously. If the circuit activation is removed, the Supervisory condition will not clear.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 33/52
FA-200 Series Installation and Operation Manua
27
Indicating (Signal) Circuits Types
Evacuation Codes
Single stage codes
Figure 18: Evacuation Codes
Circuit Type Description
Silenceable Signal
For audible devices such as bells and piezo mini-horns that may be silenced either manually
or automatically. While sounding, these follow the pattern appropriate for the condition: the
configured evacuation code (default is temporal code) during single-stage alarm, or two stage
general alarm, or the alert code during a two stage system's alert (first) stage.
Non-Silenceable
Signal
For audible devices such as bells and piezo mini-horns that may not be silenced either
manually or automatically. While sounding, these follow the pattern appropriate for the
condition: the configured evacuation code (default is temporal code) during single-stage
alarm, or two-stage general alarm, or the alert code during a two stage system's alert (first)
stage.
Silenceable Visual For visual devices such as strobes that use no code pattern (they are continuous).
Non-Silenceable
VisualSame as previous, but is non-silenceable.
Continuous On 100% of the time
Temporal Code 3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code 0.5 second on, 0.5 second off
California Code 5 seconds on, 10 seconds off
0.5s
0.5s
1.5s
0.5s
0.5s
5s 10s
CONTINOUS
TEMPORAL CODE
MARCH CODE
CALIFORNIA CODE
0.5s
2.5s
ALERT CODE
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 34/52
System Configuration
28
System Configuration
Main Fire Alarm Board
Configuration of the FA-200 Series is accomplished simply by DIP Switch Settings on the Main Fire Alarm Board.
For DIP Switches, 0 = switch “off”, 1 = Switch “on’). The DIP switches are located on the bottom left side of the
main fire alarm board.
MAIN FIRE ALARM BOARD
FIELD WIRING TERMINALS
P6
F1
10 AMP
BATTERY
FUSE
SW13
1
2
3
JW2
P3
23 1
BATT+
P4
P5
P2
BATT-
XMFR
XMFR
JW1
P7
P8
JW4
JW5
JW3
JW6
SW11 SW9
P1
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 35/52
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 36/52
System Configuration
30
When configuring the FA-200 main board, keep in mind the following information:
• Only indicating circuit two may be configured for visual devices.
• If initiating circuit three is configured as waterflow, the corresponding verified selection becomes a retard
selection.
• If initiating circuit four is configured as alarm, the corresponding latching selection has no effect.
• If initiating circuit four is configured as supervisory, the corresponding verified selection has no effect.
• The selection of Class A/B (Style Z/Y) indicating circuits is only a matter of how they are wired. See connection
information on page 13 .
• If Class A (Style D) initiating circuits are selected (FA-202, FA-204, FA-204E only), the appropriate board
jumpers must also be set. Class B initiating circuits one and two combine to create Class A Circuit #1, and Class
B initiating circuits three and four combine to create Class A Circuit #2. DIP switches for circuits three and four
are ignored except for an FA-204E with a DM-204 Adder Module. LED indicators for circuits three and four are
non-functional except for an FA-204E with a DM-204 Adder Module.
DM-204 Module
On the DM-204 Zone Adder Module the DIP switches are located on the bottom right-hand corner.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 37/52
FA-200 Series Installation and Operation Manua
3
Table 4: Configuration DIP Switch Functions on DM-204 Module
When configuring the DM-204, keep in mind the following information:
• Only Indicating Circuit #4 may be configured for visual devices.
• If Initiating Circuit #7 is configured as waterflow, the corresponding verified selection becomes a retard
selection.
• If Initiating Circuit #8 is configured as alarm, the corresponding latching selection has no effect.• If Initiating Circuit #8 is configured as supervisory, the corresponding verified selection has no effect.
• The selection of Class A/B (Style Z/Y) indicating circuits is only a matter of how they are wired. See connection
information on page 15.
• If Class A (Style D) initiating circuits are selected the appropriate board jumpers must also be set. Class B
initiating circuits 5 and 6 combine to create Class A Circuit #3, and Class B initiating circuits 7 and 8 combine to
create Class A Circuit #4. DIP switches for circuits 5 to 8 are ignored, and led indicators for circuits 5 to 8 are
non-functional.
FunctionDIP Switchon DM-204
ModuleSwitch “Off” Switch “On”
Indicating Circuit #3
Audible Device (Bell)
Only
Switch 6, #1 Silenceable Non-Silenceable
Indicating Circuit #4
Audible or Visual
Device
Switch 6, #2 Silenceable Non-Silenceable
Switch 6, #3 Audible Device (Bell) Visual Device (Strobe)
Not Used Switch 6, #4 ----------------- -----------------
Initiating Circuit #5
Alarm OnlySwitch 5, #1 Normal Alarm Verified Alarm
Initiating Circuit #6
Alarm OnlySwitch 5, #2 Normal Alarm Verified Alarm
Initiating Circuit #7
Alarm or Waterflow
Switch 5, #3 NormalVerified Alarm / Retarded
Waterflow
Switch 5, #4 Alarm Waterflow
Initiating Circuit #8
Alarm or Supervisory
Switch 5, #5 NormalVerified Alarm (no effect
on Supv.)
Switch 5, #6 Alarm Supervisory
Switch 5, #7
Non-Latching
Supervisory
(No effect on Alarm)
Latching Supervisory
(No effect on Alarm)
Not Used Switch 5, #8 ----------------- -----------------
Notes:
• After you change any configuration switches, perform a system reset.
• Do not use retard operation with any external retarding device; maximum retard may not exceed 120
seconds.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 38/52
Walk Test Operation
32
Walk Test Operation
A walk test allows an installer to verify the Initiating Circuit wiring in a system. To enter walk test, press and hold both
the Buzzer Silence and Lamp Test momentary switches for at least one second. You can identify circuits to be tested
using the Circuit Disconnect slide switches. Activation of any initiating circuit that has been selected for the walk test
will cause the audible indicating circuits to activate briefly for a number of short bursts corresponding to the circuit
number. Any subsequent activations on the same initiating circuit will activate the audible indicating circuit onlyonce. If another initiating circuit is activated then the audible indicating circuits will activate for a number of short
bursts corresponding to the circuit number of the new zone being walk-tested, and so on.
For example, if Initiating Circuit #3 is first activated, the indication circuits will sound for three bursts. Any
subsequent activations of Initiating Circuit #3 will sound for one burst. The initial burst interval denoting the count of
the circuit number is one second on followed by 1/2 second off. The subsequent burst interval denoting additional
activations on the same initiating circuit is 1/2 second on then off. After the sounding pattern has been sent on the
indicating circuits, the initiating circuit is reset and tested again. If it is still active (in alarm) the pattern will be re-sent.
Trouble on any initiating circuit when in walk test mode causes all indicating circuits to be activated continuously for
five seconds.
Alarm verification and water-flow alarm retard operations are disabled on circuits being walk tested. All circuits not
selected for walk-test continue to function normally. The walk test operation is disabled if the fire alarm control panel
is in alarm or goes into alarm while walk-test is active. It will also time out after 60 minutes of no activity.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 39/52
FA-200 Series Installation and Operation Manua
33
Appendix A: Compatible Devices
Underwriter’s Labs Canada (ULC) Canadian: Two-wire Smoke Detector Control PanelCompatibility
Note: Whether mixing different models of compatible smoke detectors or using the same model on thesame circuit, the total standby current of all detectors must not exceed 3 mA.
Make Model / Base Make Model / Base Make Model / Base
Hochiki Edwards Fenwal
DCD-135/NS6-220 6249C PSD-7131/70-201000-001
DCD-135/NS4-220 6250C PSD-7131/70-201000-002
DCD-135/HSC-220R 6264C PSD-7131/70-201000-003
DCD-190/NS6-220 6266C PSD-7131/70-201000-005
DCD-190/NS4-220 6269C PSD-7130/70-201000-001
DCD-190/HSC-220R 6270C PSD-7130/70-201000-002
SIJ-24/NS6-220 6269C-003 PSD-7130/70-201000-003
SIJ-24/NS4-220 6270C-003 PSD-7130/70-201000-005
SIJ-24/HSC-220R PSD-7128/70-201000-001
SLR-24/NS6-220 Cerebrus Pyrotron ics PSD-7126/70-201000-002
SLR-24/NS4-220 D1-2 PSD-7126/70-201000-003
SLR-24/HSC-220R D1-3/DB-3S PSD-7126/70-201000-005
SLR-24H/NS6-220 PSD-7129/70-201000-000
SLR-24H/NS4-220 Mircom PSD-7125/70-201000-001
SLR-24H/HSC-220R MIR-525 PSD-7126/70-201000-002SLR-835/NS6-220 MIR-525T PSD-7125/70-201000-003
SLR-835/NS4-220 PSD-7125/70-201000-005
SLR-835/HSC-220R Mirtone CPD-7021/70-201000-001
SLR-835B-2 73471 CPD-7021/70-201000-002
73494 CPD-7021/70-201000-003
System Sensor 73575 CPD-7021/70-201000-005
1400-A 73495/73486
NAPCO
FW-2
2400-A 73495/73487
1451-A/B401B 73595/73486
1451-A/B406B 73595/73497
2451-A/B401B 73594/73400
2451-A/B406B 73405/73400Simplex
2098-91101451DH/DH400A 73594/73401
2451-A/DH400A 73405/73401
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 40/52
Appendix A: Compatible Devices
34
Underwriter’s Labs Inc. (UL) United States: Two-Wire Smoke Detector Control PanelCompatibility
Notes:
• Whether mixing different models of compatible smoke detectors or using the same model on the same
circuit, total standby current of all detectors must not exceed 3 mA.
• The below listed smoke detectors are compatible with initiating circuits having Compatibility Identifier
"A".
Smoke
Detector Make
Model / Base
Compatibility
Identifier Head
/ Base
Rated
Standby
Current
Smoke Detector Make
Model / Base
Compatibilit
y Identifier
Head / Base
Rated
Standby
Current
Hochiki System Sensor (cont’d)
DCD-135/NS6-
220HD-3/HB-72 0.035mA 2400AIT A - N/A 0.12 mA
DCD-135/NS4-
220HD-3/HB-3 0.035mA 2451 / B401B A - A 0.12 mA
DCD-135/HSC-220R
HD-3/HB-3 0.035mA 2451 / B406B A - A 0.12 mA
DCD-190/NS6-
220HD-3/HB-3 0.035mA 2451 / DH400 A - N/A 0.12 mA
DCD-190/NS4-
220HD-3/HB-3 0.035mA 2451TH / B406B A - A 0.12 mA
DCD-190/HSC-
220RHD-3/HB-3 0.035mA 2451 / B401 A - A 0.12 mA
SIJ-24/NS6-220 HD-3/HB-72 0.040mA 2451TH / B401 A - A 0.12 mA
SIJ-24/NS4-220 HD-3/HB-3 0.040mA 4451HT / B401B A - A 0.12 mA
SIJ-24/HSC-
220R HD-3/HB-3 0.040mA 4451HT / B406B A - A 0.12 mA
SLR-24/NS6-220 HD-3/HB-72 0.045mA 4451HT / B401 A - A 0.12 mA
SLR-24/NS4-220 HD-3/HB-3 0.045mA 5451 / B401B A - A 0.12 mA
SLR-24/HSC-
220RHD-3/HB-3 0.045mA 5451 / B401 A - A 0.12 mA
SLR-24H/NS6-
220HD-3/HB-3 0.045mA 5451 / B406B A - A 0.12 mA
SLR-24H/NS4-
220HD-3/HB-3 0.045mA
SLR-24H/HSC-
220R
HD-3/HB-72 0.045mA
SLR-835/NS6-
220HD-3/HB-3 0.045mA Sentrol - ESL
SLR-835/NS6-
220HD-3/HB-3 0.045mA 429C S10A - N/A 0.10 mA
SLR-835/NS4-
220HD-3/HB-3 0.045mA 429CT S10A - N/A 0.10 mA
SLR-835/HSC-
220RHD-3/HB-72 0.045mA 429CST S11A - N/A 0.10 mA
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 41/52
FA-200 Series Installation and Operation Manua
35
Hochiki (cont’d)
SLR-835B-2 HD-655ua @
24VDC429CRT S11A - N/A 0.10 mA
711U/701E, 701U, 702E,702U
S10A - S00 0.10 mA
System Sensor 712U / 701E, 701U, 702E,
702US10A - S00 0.10 mA
1100 A - N/A 0.12 mA713-5U / 701E, 701U, 702E,
702US10A - S00 0.10 mA
1151/ B110LP A - A 0.12 mA713-6U / 701E, 701U, 702E,
702US10A - S00 0.10 mA
1151/ B116LP A - A 0.12 mA 721U / 702E, 702U S10A - S00 0.10 mA
1400 A - N/A 0.10 mA 721UT / 702E, 702U S10A - S00 0.10 mA
1451/B401 A - A 0.12 mA 722U / 702E, 702U S10A - S00 0.10 mA
1451/ B401B A - A 0.12 mA731U / 702E, 702U, 702RE,
702RUS11A - S00 0.10 mA
1451/ B406B A - A 0.12 mA732U / 702E, 702U, 702RE,
702RUS11A - S00 0.10 mA
1451DH/ DH400 A - A 0.12 mA Detection Systems Inc.
2100 A - N/A 0.12 mA DS250 B - N/A 0.10 mA
2100T A - N/A 0.12 mA DS250TH B - N/A 0.10 mA
2151/ B110LP A - A 0.12 mA DS282 B - N/A 0.10 mA
2151/ B116LP A - A 0.12 mA DS282TH B - N/A 0.10 mA
2400 A - N/A 0.12 mA Mircom
2400TH A - N/A 0.12 mA MIR-525U FDT-1 0.10 mA
2400AT A - N/A 0.12 mA MIR-525TU FDT-1 0.10 mA
NAPCO
FW-2 HD-655uA @
24VDC
Smoke
Detector Make
Model / Base
Compatibility
Identifier Head
/ Base
Rated
Standby
Current
Smoke Detector Make
Model / Base
Compatibilit
y Identifier
Head / Base
Rated
Standby
Current
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 42/52
Appendix A: Compatible Devices
36
Underwriter’s Laboratories Inc. (UL) United States: Four-Wire Smoke Detector ControlPanel Compatibility
Underwriter’s Laboratories Inc. (UL) United States: Signalling Device Control PanelCompatibility
Mircom MIR-545U MIR-545TU
Sentrol-ESL
541C 541CXT 709-MV-21 709-24V-21
741U WITH 702U or
702E Base
449AT, 449C, 449CT, 449CRT, 449CST, 449CSTE, 449CSRT,
449CSRH, 449CSST, 449CSSTE, 449CTE, 449CLTCSLT
System Sensor1424 6424 6424A A77-716B
DH400ACDCI DH400ACDCP DH400ACDCIHT
System Sensor - SpecrAlert
P2415 P2415W P241575 P241575W P2475
P2475W P24110 P24110W S2415 S2415W
S241575 S241575W S2475 S2475W S24110
S24110W H12/24 H12/24W MDL MDLW
Wheelock
AS-2415W-24-FR AS-241575W-FR AS-2430W-FR AS-2475W-FR AS-24110W-FR
AS-2415C-FW AS-2430C-FW AS-2475C-FW AS-24100C-FW AH-24-R
AH-24-WP-R NS-2415W-FR NS-241575W-FR NS-2430W-FR NS-2475W-FR
NS-24110W-FR NS4-2415W-FR NS4-241575W-FR NS4-2430W-FR NS4-2475W-FR
NS4-24110W-FR RS-2415W-FR RSS-241575W-FR RSS-2415W-FR RSS-241575W-FR
RSS-2430W-FR RSS-2475W-FR RSS-24110W-FR RSS-2415C-FW RSS-2430C-FW
RSS-2475C-FW RSS-24100C-FW MT-12/24-ULCMT-24-LS-VFR-
ULCMT-24-WS-VFR-ULC
AMT-12/24-R-
ULC
AMT-24-LS-VFR-
ULCMB-G6-24-R MB-G10-24-R SM-12/24-R
DSM-12/24-R
Gentex
AVP-4-15-1 AVP-4-15/75 AVP-4-30/75 AVP-4-110-1 GXS-4-15-1
GXS-4-15/75-W GXS-4-30/75-W GXS-4-15/75-C GXS-4-110-1 GX90S-4-15-1
GX90S-4-15/75-
WGX90S-4-30/75W GX90S-4-15/75-C GX90S-4-110-1 SHG24-15-1
SHG15/75-W SHG24-30/75-W SHG24-15/75-C SHG24-110-1 GOT24
GOS24-15-1 GOS24-15/75 GOS24-15/75 GOS24-30/75 GOS24-110-1
GMH-24 GMS-24-15-1 GMS-24-15/75-W GMS-24-30/75-W GMS-24-15/75-C
GMS-24-110-1 WGMS-4/75
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 43/52
FA-200 Series Installation and Operation Manua
37
Appendix B: RAM-208 Remote Annunciator
The RAM-208 Eight Zone Remote Annunciator mounts in an electrical box. It provides annunciation for the FA-204
or FA-204E’s full complement of 8 Initiating circuits.
For more detailed information see Mircom Document LT-648.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 44/52
Appendix C: Module Specifications And Features
38
Appendix C: Module Specifications And Features
FA-201 Fire Alarm Control Panel
General
• One supervised Class B (Style B) initiating circuit; configurable (normal or verified). [Compatibility ID “A”]
Power Limited: 26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
• Two Class A/B (Style Y/Z) indicating circuits; configurable as strobes or audibles.
Power limited: 24 VDC unfiltered
• 1.7 A @ 49°C per circuit (2.4 a total)
• Initiating circuit disconnect switch.
• Optional DACT or city tie adder module.
• Optional RM-204 / RM-208 Relay Module.
• Resettable four-wire smoke supply.
Power Limited: 28VDC, 100mA max, 1.5Vp-p ripple
• Aux power supply.
Power limited: 24VDC, 300mA max, unfiltered for RTI or remote annunciators
• 1 RTI Interface for connection to an RTI Remote Trouble Indicator.
• Auxiliary relays (resistive loads):
Common Alarm: Form C, 1Amp, 28VDC
Common Trouble: Form C, 1Amp, 28VDC
• Micro-controller based design.
• DIP switch configurable.
• Walktest function.
Electrical ratings
• AC Line Voltage: 120V 60 Hz / 240V 50 Hz
2A / 1A
• Two amps (primary, transformer inline fuse)
• Power supply ratings: 2.75 amps. max. (secondary)
• For indicating circuits: 24VDC unfiltered 2.40 amps. max.
• Battery: 24VDC, gel-cell/sealed lead-acid
• Charging capability: 4 to 12 AH batteries
• Fuse on main board: 10 Amps.
• Current consumption: standby: 110 mA
alarm: 220 mA
FA-202 Fire Alarm Control Panel
Same as FA-201, plus ...• Two supervised Class B (Style B) or 1 Class A (Style D) initiating circuits; configurable (normal or verified).
[Compatibility ID “A”]
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 45/52
FA-200 Series Installation and Operation Manua
39
FA-204 Fire Alarm Control Panel
Same as FA-201, plus ...
• Four supervised Class B (Style B) or two Class A ( Style D) Initiating circuits; configurable (normal or verified,
and for Class B there may be one waterflow and one supervisory). [Compatibility ID “A”]
• Optional RM-204 or RM-208 Relay Module.
• One RS-485 connection for up to 3 RAM-208 Remote Annunciators.
• Auxiliary relays: (resistive loads) common alarm, supervisory, troubleall are Form C, 1 amp, 28VDC
• DACT / Dialler Module (DACT-100A)
• DACT - “Digital Alarm Communicator Transmitter”
• Using Ademco Contact ID and SIA-DCS Protocols.
• See Mircom document LT-617 for further info.
• Current Consumption: standby: 45 mA
alarm: 120 mA
Polarity Reversal and City Tie Module (PR-100)
• Supervised city tie: not power limited
• 24VDC unfiltered, 210 mA max., Trip coil: 14 ohms• Polarity reversal: power limited
• 24VDC open, 12VDC @ 3.5 mA, 8 mA max. (shorted)
• Current consumption: standby: 35 mA
alarm: 300 mA
RM-204 / RM-208 Relay Module
• Four or eight relays: Form C, 1A (resistive), 28 VDC per contacts
• Each individual relay can be relay per zone, common alarm, common supervisory
• Current Consumption: standby: 5 mA
alarm: 160 mA
FA-204E Fire Alarm Control Panel
General
• Four supervised Style B (Class B) or 2 Style D (Class A) initiating circuits; configurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
• Two Class A/B (Style Y/ Z) indicating circuits; configurable as strobes or audibles.
Power limited:24 VDC unfiltered
• 1.7 A @ 49°C per circuit (5A total)
• One DM-204 Zone Adder Module may be added.
• Initiating circuit disconnect switches.
• Optional DACT or city tie adder module.
• Optional RM-204 / RM-208 Relay Module.
• Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
• Aux power supply.
• Power limited: 24VDC, 300mA max, unfiltered
• for RTI or Remote Annunciators
• 1 RS-485 connection for up to 3 RAM-208 Remote Annunciators.
• 1 RTI interface for connection to an RTI Remote Trouble Indicator.
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 46/52
Appendix C: Module Specifications And Features
40
• Auxiliary relays: (resistive loads) common alarm, supervisory, trouble
all are Form C, 1 amp, 28VDC
• Microcontroller-based design.
• DIP switch configurable.
• Walktest function.
Electrical ratings:
• AC Line Voltage: 120V 60Hz / 240V 50Hz1.25A
• Power supply ratings: 6 amps max. (secondary)
• For indicating circuits: 24VDC unfiltered, 5 amps max.
• Battery: 24VDC, Gel-Cell/Sealed Lead-Acid
• Charging capability: 1 0 to 24 AH batteries
• Fuse on main board: 10 Amps.
• Current consumption: standby: 110 mA
alarm: 220 mA
DM-204 Zone Adder Module
• May be added to FA-204E.
• Four supervised Class B (Style B) or two Class A (Style D) initiating circuits; configurable. [Compatibility ID “A”]
Power limited: 22VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
• Two Class B or A (Style Y or Z ) indicating circuits; configurable as strobes or audibles.
Power limited: 24 VDC unfiltered, 1.7A @49°C per Circuit
• Current consumption: standby: 45 mA
alarm: 120 mA
• Eight-zone remote annunciator (RAM-208)
• RS-485 Interface, up to 3 per FA-200 Panel.
• Current consumption: standby: 35 mA
alarm: 90 mA
• Remote trouble indicator (RTI-1)
• Trouble LED and trouble buzzer
• Current consumption: standby: 35 mA
alarm: 35 mA
• End-of-line resistor plates (MP-300, MP-300R)
• Internal 3.9 Kohm, ½ Watt, 5% resistor.
• External battery cabinet (BC-160)
• Up to 24 A-H batteries for FA-200 panels.
System model: FA-200 Fire Alarm Control Panel
System type: Local, auxiliary (using PR-100), remote station protected premises (using DACT-100A or PR-100),
central station protected premises (using DACT-100A).
Type of service: A, M, WF, SS (SS is only local or with DACT-100A)
Type of signalli ng: Non-Coded
Appl icable standards: NFPA 70 and 72, UL-864, ULC S-524, ULC S-527
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 47/52
FA-200 Series Installation and Operation Manua
4
Appendix D: Power Supply & Battery Calculations
Use the form below to determine the required main chassis and secondary power supply (batteries).
Total Current Requirement
ALARM (B)______ Amps.
Battery Capacity Requirement
([STANDBY ( A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [♣ Alarm in Hr.] _____) = (C) ______AH
* Assuming three initiating circuits in alarm.♣ Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
♦
Using the MIR-425/U 2-wire smoke detector. See Appendix A on page33 for other available smoke detectors.Total Alarm Current
• Must be 2.75 amperes or less for FA-201, FA-202, and FA-204. Indicating Circuits not to exceed 2.4 amperes.
• Must be 6 amperes or less for FA-204E. Indicating Circuits not to exceed 5 amperes.
Battery Selection
• Multiply (C) by 1.20 to derate battery.
• Use BA-1065(6.5AH) Batteries for the FA-201, FA-202, and FA-204 which charges up to 12 AH Batteries.
• Use BA-110(10AH) Batteries for the FA-204E.
• The FA-204E will charge up to 24AH batteries if they are in an external Mircom BC-160 Battery Cabinet.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated
continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt
insulation and proper over-current circuit protection that complies with the local codes. Refer to
Appendix C
on page 38 for specifications.
Power Requirements (All currents are in amperes)
Model
Number Description
Qt
y Standby
Total
Standby Alarm
Total
Alarm
FA-201, FA-
202, FA-204,
FA-204E
Fire Alarm
Control PanelX 0.110 = 0.220 =
DM-204Zone Adder
Module X 0.045 = 0.120 =
RM-204/RM-
208Relay Module X 0.005 = 0.160 =
PR-100
Polarity Reversal
and City Tie
Module
0.035 = 0.300 =
DACT-100ADACT/Dialler
Module0.045 = 0.120 =
RAM-208Remote
Annunciator 0.035 = 0.090 =
RTI-1Remote Trouble
Indicator 0.035 = 0.035 =
Two-Wire Smoke Detectors ♦ 0.0001 = * 0.090 = 0.090
Four-Wire Smoke Detectors X = =Signal Load (bells, horns,
strobes, and etc.)=
Auxiliary Power Supply for Remote Annunciators Alarm =
Total currents (Add above currents) STANDBY ( A) (B)
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 48/52
Appendix D: Power Supply & Battery Calculations
42
Examples:
Configuration 24 Hrs Standby 60 hrs standby, 5 min alarm
FA-201/2/4 Basic4 AH batteries 4 AH batteries not possible
FA-201/2/4, DACT-100A, RM-208, RTI 6.5 AH batteries not possible
FA-204E, DM-204 10 AH batteries 12 AH batteries
FA-204E, DM-204, DACT-100A, RM-208, 3of RAM-208
10 AH batteries 24 AH batteries
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 49/52
FA-200 Series Installation and Operation Manua
43
Warranty
Mircom Technologies Ltd., manufactured equipment is guaranteed to be free of defects in material and
workmanship for a period of one (1) year from the date of original shipment. Mircom will repair or replace, at its
option, any equipment which it determines to contain defective material or workmanship. Said equipment must be
shipped to Mircom prepaid. Return freight will be prepaid by Mircom. We shall not be responsible to repair or
replace equipment which has been repaired by others, abused, improperly installed, altered or otherwise misusedor damaged in any way. Unless previously contracted by Mircom, Mircom will assume no responsibility for
determining the defective or operative status at the point of installation, and will accept no liability beyond the repair
or replacement of the product at our factory authorized service depot.
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Phone: 1-888-660-4655
Fax: 1-888-660-4113
www.mircom.com
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 50/52
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 51/52
8/11/2019 LT-636 FA-200 Installation and Operation Manual1
http://slidepdf.com/reader/full/lt-636-fa-200-installation-and-operation-manual1 52/52
Advanced Life Safety Solutions