Line CurrenT diFFerenTiaL sysTeM - PLC · against measurement errors including CT saturation. ......
Transcript of Line CurrenT diFFerenTiaL sysTeM - PLC · against measurement errors including CT saturation. ......
1g Multilin
Tran
smis
sion
Lin
e Pr
otec
tion
• Provencurrentdifferentialprotectionensuressecurehigh-speedtripping
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• Increasedsensitivitythroughdynamicchargingcurrentcompensationandcommunicationchannelasymmetrycompensation
• AdaptiverestraintcharacteristicprovidesexcellentsecurityagainstmeasurementerrorsincludingCTsaturation.
• Advancedfaultanddisturbancerecording,includinginternalrelayoperatingsignalsthuseliminatingtheneedforexternalrecordingdevices
• PhasorMeasurementUnit-SynchronizedphasorinformationaccordingtoIEEEC37.118standard
• Overheadlinesandundergroundcablesofdifferentvoltagelevels
• Circuitswithtappedtransformerfeeders• Suitableforthreeterminallineconfigurations,withchannel
redundancyanddirecttransfertripping(DTT)
• Wideareasystemmonitoringandcontrolandusingintegratedprotectionandsynchrophasormeasurement
• Applicationsrequiringthree-poleautoreclosingandindependentsynchrochecksupervision
• Realtimemonitoringofremote,localanddifferentialperphasecurrents
• Oscillography-64samples/cycle,upto64records• EventRecorder-1024timetaggedevents,with0.5msscan
ofdigitalinputs• DataLogger-Upto16channelswithuserselectable
samplingrate• Synchronisedmeasurementofvoltage¤tand
sequencecomponentphasors-1to60phasors/sec
Monitoring and Metering
Protection and Control• Linecurrentdifferentialwithadaptiverestraint• Stubbusprotection• Breakerfailure• ThreepoleAutoreclose• Underfrequencyprotection• Non-Directionalovercurrent:Phase,neutralandnegative
sequence• Phaseover/undervoltage,negativesequenceovervoltage• TwoindependentSynchronismcheckelements
Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104• DirectI/O–secure,high-speedexchangeofdatabetween
L30sforDirectTransferTripapplications• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
L30CosteffectiveCurrentDifferential
Systemforhigh-speedLinesandCables
FeaTures
aPPLiCaTions
Key BeneFiTs
enerVista™ software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensurereference
materialanddeviceutilitiesareup-to-date
Line CurrenT diFFerenTiaL sysTeM
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingL30functions• Redundantarchitecturefordependabilityandsecurity
ieC 61850 Process Bus interface
www.GeMultilin.com
L30Line differential system
2
Tran
smis
sion
Lin
e Pr
otec
tion
Protection and ControlThe L30 is a cost effective line currentdifferential protection relay intended forsub-transmission and medium voltagelines and cables providing reliable andsecure operation even under the worstcase power system conditions. The L30providessecurehigh-speedfaultdetectionand clearance suitable for three-poletrippingapplications.PartoftheUniversalRelayfamily,theL30comeswithavarietyof versatile features truly integratingprotection, monitoring, metering,communicationandcontrol inoneeasy-to-usedevice.TheUniversalRelayfamilyoffers ahighdegreeofmodularity in itsdesignandfunctionalityprovidingsuperiorperformance in protection and controlmeetingthetoughestrequirementsofthemarketplace.
Current differential ProtectionTheL30currentdifferentialprotectionrelayusessuperiorandpatentedalgorithmstoaddress the challenges of bandwidth ,security, dependability and sensitivity incurrentdifferentialrelaying.Bandwidth requirements are effectivelyaddressedbymeansof a patentednewdata consolidation technique called“phaselets”.Thispermitsapplicationwithinacommunicationsbandwidthof64Kbps,andcandetect faultswithinahalfcyclepluschanneldelay.The L30 innovative dual slope adaptiverestraintcharacteristic,basedonestimates
ofmeasurementerrors,allowtherelaytobesecureonsevereexternalfaultswhilemaintainingsensitivityfor internalfaults.Theestimateoferrorsintheinputcurrentspermitsmoresensitivesettingsthanthoseusedinthetraditionalpercentdifferentialschemes.
TheL30approachtoclocksynchronizationrel ies upon precise distr ibutedsynchronization. Clocks are phasesynchronizedtoeachotherandfrequencysynchronized to the power systemfrequency.Eachrelaycomparesitsclockto the phase of the other clocks and
makes appropriate adjustments. Thisallows forgreater transient ride-throughfor power system and communicationsdisturbances.
Enhancedadditionalsecurity isprovidedbyasensitivecurrentdisturbancedetector,whichcanbeusedtosupervisethecurrentdifferentialelement.
Charging Current Compensation
For long lines and especially forundergroundcables,thechargingcurrentmaybelargeandresultinexcessivelyhighpickupsettings.TheL30candynamically
The L30 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
831706AS.CDR
L30 Line Differential System
52
Monitoring CLOSE TRIP
Data From/To Remote End(via Dedicated Communications) MeteringFlexElement
TM TransducerInputs
50DD 87L50BF51_251P50_2
79
50P
27P
27X59N
59X
59P
25
51G50G
50N 51N
Functional Block diagram
L30 - Protection, Metering, Monitoring and Control
DeviceNumber Function25 SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage50BF BreakerFailure50DD CurrentDisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50_2 NegativeSequenceInstantaneousOvercurrent51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent51_2 NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage79 AutomaticRecloser87L SegregatedLineCurrentDifferential
ANSIDeviceNumbers&Functions
www.GeMultilin.com 3
L30Line differential system
Tran
smis
sion
Lin
e Pr
otec
tion
compensate the charging current thusincreasingitssensitivitytothefaultcurrentonlongtransmissionlines.
enhanced Monitoring Features
TheL30usesadvancederrordetectionandsupervising functions to secure the L30against maloperation due to erroneousdata.Highbiterrorratesareaddressedbymeansofcomputinga32bitCRCchecksum,effectivelyaddressingtheconcernsofmultiplebiterrorsduetohighchannelnoise.On multiplexed channels, channelasymmetrymaybeexpectedduetopathswitching spurious differential currents,which can endanger the security of thedifferential system. By using GPS timesynchronization, up to 10ms of channelasymmetrycanbecompensatedfor.ExtrasecurityhasbeenimplementedintheL30toensureproperoperationontheeventofIRIG-Bsignalfailure.Integrated channel monitoring providesreal-time diagnostic data on the healthof the L30. Communications channeldeterioration or failure will activate analarm,andcanbeusedtoenablebackupprotection. Channel propagation delayismonitored and adjusted according tovariationsincommunicationpaths.
Communication Topologies
Relays can communicate through directfiber,RS422,G.703,IEEEC37.94interfacesat 64Kbps, with extensive channelmonitoringanddiagnosticsare included.Inacurrentdifferentialscheme,theL30sexchange data via the communicationlink, acting either as master collectingdata,makingcalculationsandmakingallrelevant trip and restraint decisions, oras slave only transmitting current datato the one acting as master. For twoterminalapplications,use the redundantcommunicationscapabilityoftheL30foroptimalreliabilityofthecurrentdifferentialline protection. For this scheme, datais continuously transmitted over bothchannels, so if a failure occurs, the L30willcontinuetoprovidecurrentdifferentialprotection.Forthreeterminalapplications,advancedinter-relay communication features
selectable through user configurablelogic.
autoreclosing
The L30 provides multi-shot autoreclosingforthreepoleapplicationswithindependentlysettabledeadtimeforeachshot . Auto-reclose can be dynamicallyblockedbyuserprogrammablelogic.Fourdifferentauto-relcosemodesareavailableenablingtheuserstoselectthereclosingmodetosuitspecificapplications.
synchronism Check
The L30 monitors voltage difference,phaseangledifferenceandslipfrequencyto ensureproper breaker closureasperuser requirements. The L30 providesadditionalenhancementsinsynchronizingby checking dead source conditionsfor synchronism bypass under theseconditions.
Breaker Failure
The L30 provides two fully independentbreakerfailureprotectionelements.
ieC 61850 Process BusThe IEC 61850 Process Bus module isdesignedtointerfacewiththeGEMultilinHardFiberSystem,allowingbi-directional
Typical two and application of L30. L30 supports a variety of media cards for signalling between L30’s including direct multimode or single mode fibre, RS422, G.703 and IEEE C37.94.
TYPICAL 3-TERMINAL APPLICATION
MAIN
ALT.
- G.703- RS422- C37.94
- G.703- RS422- C37.94
GE’s JungleMUX(SONET)
GE’s JungleMUX(SONET)
GE’s JungleMUX(SONET)
GE’s JungleMUX(SONET)
L30 L30
TYPICAL 2-TERMINAL APPLICATIONTypical applications
eliminate the need for redundantcommunicationchannelsduetotheabilityoftheL30toautomaticallyswitchbetweenmaster and slave mode, maintaining adependablesystemevenwithafailureofoneofthecommunicationchannels.
overvoltage and undervoltage protection
Longlinesunderlightlyloadedconditionsor no-load may experience voltagesexceeding rated per unit voltage levelof the line. Use the phase overvoltageelementoftheL30toinitiatealocaltripaswellasaremotetripusingdirecttransfertrip.
overcurrent Functions
The L30 provides overcurrent functionsforphase,neutralandgroundwhichcanrunparallelwith theprimarydifferentialelementorcanbeprogrammedtoprovideprimary protection under conditions thedifferentialelementisnotavailable.
direct transfer trip (dTT)
UsethedirecttransfertripfeatureofL30to trip remote breaker. Both single poleand three pole direct transfer trips aresupported. Up to eight signals can besentoverpilotcommunicationschannels
www.GeMultilin.com
L30Line differential system
4
Tran
smis
sion
Lin
e Pr
otec
tion
IEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existingUniversal Relay applications, includingprotection functions,FlexLogic,meteringandcommunications.
The GEMultilin HardFiber System offersthefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingT60’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
VisittheHardFiberSystemproductpageontheGEMultilinwebsiteformoredetails.
advanced automationTheL30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmablelogic,communication,andSCADAcapabilitiesthatfarsurpasswhatisfoundintheaveragelinerelay.TheL30integratesseamlesslywithotherURrelays
forcompletesystemprotection.
FlexLogic™
FlexLogic™ is the powerful UR-platformprogramming logic engine thatprovidesthe ability of creating customizedprotection and control schemes therebyminimizingtheneed,andtheassociatedcosts,ofauxiliarycomponentsandwiring.Using FlexLogic™, the L30 can beprogrammedtoproviderequiredtrippinglogicalongwithcustomschemelogicforlinebreakercontroland interlockinganddynamicsettinggroupchanges.
scalable HardwareTheL30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesignallowsforeasyconfigurationandfutureupgrades.
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays
Monitoring and Metering
TheL30includeshighaccuracymeteringand recording forallACsignals.Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. CurrentandvoltageparametersareavailableastotalRMSmagnitude,andasfundamentalfrequencymagnitudeandangle.
Fault and disturbance recording
The advanced disturbance and eventrecording features within the L30 cansignificantly reduce the timeneeded forpostmortem analysis of power systemeventsandcreationofregulatoryreports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports
-Powerfulsummaryreportofpre-faultandfaultvalues
The very high sampling rate and largeamount of storage space available fordata recording in the L30 can eliminatetheneed for installingcostly standalonerecordingequipment.
advanced device Health diagnostics
TheL30performscomprehensivedevicehealth diagnostic tests during startupand continuously at runtime to testits own major functions and criticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impactsecurityandavailabilityofprotection,andpresentdevicestatusviaSCADAcommunicationsand front panel display. Providingcontinuousmonitoringandearlydetectionof possible issues helps improve systemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitryto
FlexLogicTM designer
Flexlogic™ allows for customizing the L30 to operate and control the breakers and other auxiliary devices needed to fit most line protection schemes and applications.
www.GeMultilin.com 5
L30Line differential system
Tran
smis
sion
Lin
e Pr
otec
tion
validatetheintegrityofallsignals
CommunicationsThe L30 provides advanced commun-icationstechnologiesforremotedataandengineering access,making it easy andflexibletouseandintegrateintonewandexisting infrastructures. Direct supportfor fiber optic Ethernet provides high-bandwidth communications allowing forlow-latency controls andhigh-speed filetransfersof relay faultandevent recordinformation. The available redundantEthernet option and the embeddedmanaged Ethernet switch providethe means of creating fault tolerantcommunicationarchitectures inaneasy,cost-effectivemannerwithouttheneedforintermediarycommunicationhardware.TheL30supportsthemostpopularindustrystandardprotocols enablingeasy, directintegrationintoDCSandSCADAsystems.
• IEC61850
• DNP3.0
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
interoperability with embedded ieC61850
Use the L30 with integrated IEC61850 tolowercostsassociatedwithlineprotection,control and automation. GE Multilin’sleadership in IEC61850 comes fromthousandsof installeddevicesandfollowsonsevenyearsofdevelopmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer
• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring
Multi-Language
TheL30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, andproduct
manual. Easily switch between Englishandanadditional languageon the localdisplayswithoutuploadingnewfirmware.
enerVistaTM softwareTheEnerVista™Suiteisanindustry-leadingset of software programs that simplifiesevery aspect of using the L30 relay. TheEnerVista™ suite provides all the toolsto monitor the status of the protectedasset , maintain the relay, and integrateinformation measured by the L30 intoDCS or SCADA monitoring systems.ConvenientCOMTRADEandSequenceofEventsviewersareanintegralpartoftheUR Setup software included with everyUR relay, tocarryoutpostmortemeventanalysis to ensure proper protectionsystemoperation.
enerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftwarepackagethatprovidesuserswithallofthesetupandsupporttoolsneededforconfiguringandmaintainingGEMultilinproducts. The setup software withinLaunchpadallowsconfiguringdevices in
Record the operation of the internal L30 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during line faults and disturbances.
Power system TroubleshootingTheL30containsmanytoolsandreportsthatsimplifyandreducetheamountoftimerequiredfortroubleshootingpowersystemevents.
Analyze line faults using both analog and digital power system quantities that are measured and recorded up to a rate of 64 samples per cycle.
www.GeMultilin.com
L30Line differential system
6
Tran
smis
sion
Lin
e Pr
otec
tion
real-timebycommunicatingusingserial,Ethernet , or modem connections, orofflinebycreatingsettingfilestobesenttodevicesatalatertime.Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and availablewhen needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQ’s
• ServiceBulletins
Viewpoint Monitoring
ViewpointMonitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems.ViewpointMonitoringprovidesacompleteHMIpackagewiththefollowingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint engineer
ViewpointEngineerisasetofpowerfultoolsthatwillallowtheconfigurationandtestingofURrelaysatasystemlevelinaneasy-to-usegraphicaldrag-and-dropenvironment.ViewpointEngineerprovidesthefollowingconfigurationandcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint Maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security compliance
audits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
enerVista™ integrator
EnerVista™IntegratorisatoolkitthatallowsseamlessintegrationofGEMultilindevicesintoneworexistingautomationsystems.IncludedinEnerVista™Integratoris:
• OPC/DDEServer
• GEMultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
user interfaceTheL30 frontpanelprovidesextensive localHMI capabilities. The localdisplay isused formonitoring, statusmessaging,faultdiagnosis,anddeviceconfiguration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
LEDIndicators
Multi-LanguageDisplay• English• Russian• French• Chinese
UserProgrammablePushbuttons
www.GeMultilin.com 7
L30Line differential system
Tran
smis
sion
Lin
e Pr
otec
tion
Typical Wiring
L30
A B C
52
1
Powersupply
9
CPU
7
COM
8
CT/VT
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
6
Inputs/outputs
6Inputs/outputs
*
JU MX LW KV BHT DN GS FPR
RS-232
DB-9
(front)
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTOR
PERSONALCOMPUTER
CONNECTOR
2 23 34 45 56 67 78 89 9
DC
TOREMOTE
L30
OPTIONAL
TC
TC
N
2
1H1a
H2b
H1cH1b
H2c
H2a
H4a
H4c
H3bH3a
H4b
H3c
SURGE
H6a
H8a
H5b
H7b
H8b
H5a
H7a
H6c
H8c
H5c
H7c
H1
H2
H3
H4
I
V
I
V
I
V
I
V
6G
U8a
U7b
U7a
U8c
U7c U1b
U2b
U3b
U4b
U5b
U6b
U1a
U2a
U3a
U4a
U5a
U6a
U1c
U2c
U3c
U4c
U5c
U6c
SURGEU8b
U1
U5
U2
U6
U3
U4
6H I
V
I
V
I
V
I
V
I
V
I
V
N7a
N1a
N2b
N7c
N1c
N7b
N1b
N8cN8b
N2c
N8a
N2a
N4a
N5b
N4c
N6b
N3bN3a
N6a
N4b
N5c
N5a
N3c
N6c
6K N1
N5
N2
N6
N3
N7
N4
N8
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
Tx1 Rx1
Tx2 Rx2
INTE
R-RE
LAY
CO
MM
S.W
7A
FIBER
FIBER
6C
S1
S5
S2
S6
S3
S7
S4
S8
S7a
S1a
S2b
S7c
S1c
S7b
S1b
S8cS8b
S2c
S8a
S2a
S4a
S5b
S4c
S6b
S3bS3a
S6a
S4b
S5c
S5a
S3c
S6c
L6a
L8a
L5b
L7b
L5a
L7a
L6c
L8c
L5c
L7c
SURGE
L1a
L8b
L4c
L2c
L3aL3c
L1c
L3b
L1b
L4a
L2a
6D
minimum
PROVIDED
8L
F1c
F4a
F3c
F2c
F4c
F1a
F4b
F1b
F2a
F3a
F2b
F3b
IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
F8c
F8a
F5a
F5c
F7c
F6a
F7a
F6c
VX
VA VB
VC VX
VA VB
VC
Multilin
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
L30-H00-HCL-F8L-H6G-L6d-n6K-s6C-u6H-W7a
www.GeMultilin.com
L30Line differential system
8
Tran
smis
sion
Lin
e Pr
otec
tion
L30 - * 00 -H * * -F ** -H ** -L ** -N ** -S ** -U ** -W/X ** ForFullSizedHorizontalMountBaseUnit L30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable)
G RS485+Multi-modeST10BaseFH RS485+Mutli-modeSTRedundant10BaseFJ RS485+Multi-modeST100BaseFXK RS485+Multi-modeSTRedundant100BaseFXL RS485+Single-modeSC100BaseFXM RS485+Single-modeSCRedundant100BaseFXN RS485+10/100BaseTP RS485+Single-modeST100BaseFXR RS485+Single-modeSTRedundant100BaseFXS RS485and6-portmanagedEthernetSwitch
Software 00 NoSoftwareOptions03 IEC6185006 PhasorMeasurementUnit(PMU)07 IEC61850+PhasorMeasurementUnit(PMU)18 3PAutorecloseandSynchrocheck19 3PAutoreclose,Synchrocheck,IEC61850andPhaseMeasurementUnit(PMU)
Mount/Coating H Horizontal(19"rack)-StandardA Horizontal(19"rack)-HarshEnvironmentCoatingV Vertical(3/4size)-StandardB Vertical(3/4size)-HarshEnvironmentCoating
UserInterface C English
NOTE:Theseselectionsareonlyforhorizontalunits
P Englishwithadditional4smalland12largeprogrammablepushbuttonsA ChineseB Chinesewithadditional4smalland12largeprogrammablepushbuttonsD FrenchG Frenchwithadditional4smalland12largeprogrammablepushbuttonsR RussianS Russianwithadditional4smalland12largeprogrammablepushbuttonsK EnhancedEnglishFrontPanelL EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttonsM EnhancedFrenchFrontPanelN EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttonsQ EnhancedRussianFrontPanelT EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttonsU EnhancedChineseFrontPanelV EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons
PowerSupply H 125/250VAC/DC*SeeBelow H RH 125/250VAC/DCwithredundant125/250VAC/DC
L 24-48V(DConly)L RL 24-48V(DConly)withredundant24-48V(DConly)
CT/VTDSP 8F Standard4CT/4VT8H Standard8CT8L Standard4CT/4VTwithenhanceddiagnostics8N Standard8CTwithenhanceddiagnostics
IEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX NoModule
4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs67 67 67 67 67 8Form-A(NoMonitoring)Outputs6C 6C 6C 6C 6C 8Form-COutputs6D 6D 6D 6D 6D 16DigitalInputs6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs6F 6F 6F 6F 6F 8FastForm-COutputs6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputs
TransducerI/O 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputsSelectamaximumof3 5C 5C 5C 5C 5C 8RTDInputs
5D 5D 5D 5D 5D 4RTDInputs,4dcmAOutputs5E 5E 5E 5E 5E 4dcmAInputs,4RTDInputs5F 5F 5F 5F 5F 8dcmAInputs
Inter-RelayCommunications 7A 7A 820nm,multi-mode,LED,1Channelselectamaximumof1 7B 7B 1300nm,multi-mode,LED,1Channel
7H 7H 820nm,multi-mode,LED,2Channels7I 7I 1300nm,multi-mode,LED,2Channels7R 7R G.703,1Channel7S 7S G.703,2Channels7T 7T RS422,1Channel7W 7W RS422,2Channels72 72 1550nm,single-mode,LASER,1Channel73 73 1550nm,single-mode,LASER,2Channels76 76 IEEEC37.94,820nm,multimode,LED,1Channel77 77 IEEEC37.94,820nm,multimode,LED,2Channel2A 2A C37.94SM,1300nmSinglemode,ELED,1ChannelSinglemode2B 2B C37.94SM,1300nmSinglemode,ELED,2ChannelSinglemode
EthernetSwitchoptionwillexcludetheRedundantPowerSupplyoption
2S HighPowerSupply6-portmanagedEthernetSwitch2T LowPowerSupply6-portmanagedEthernetSwitch
ordering note: ToviewthelatestoptionsavailablefortheL30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
accessories for the L30 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• Reviewapplicationsnotesandsupportdocuments
• BuyaL30online
• ViewtheURFamilybrochure
Visit www.GeMultilin.com/L30 to:
ordering
080702-v1
*Redundantpowersupplyonlyavailableinhorizontalunit .Ifredundantchosen,mustbesametypeMaximum2perchassis