S&C Scada=Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I
For Diagnosing Operating Problems
1 TABLE OF CONTENTS I Section Page Number Section Page Number
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CHART V. DART RTU WONT COMMUNICATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CHART I. SCADA-MATE SWITCH WON’T OPERATE WITH MASTER STATION .12
UNDER LOCAL CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CHART VI. QUESTIONABLE STATUS INPUTS . . . . . . . . . . . . . . . . . . . . . . CHART 11. SCADA-MATE SWITCH WON’T OPERATE REC,ElVED AT MASTER STATION .16
UNDER REMOTE CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . 6 CHART VII. QUESTIONABLE ANALOG INPUTS . . . . . . . . . . . . . . . . . . . . . . CHART 111. DART RTU OR TRANSCEIVER RECEIVED AT MASTER STATION .20
DOESN’T OPERATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 CHART IV. DART CONFIGURATION SYSTEM OR
DARTMAINT WON’T RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
New Publcatlon O1995 INSTRUCTION SHEET 76&554
S&C ELECTRIC COMPANY Chicago Page 1 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I INTRODUCTION I
1 e The equipment covered by this publication must be operated and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment.
1
The publication provides a troubleshooting guide for diagnosing operat,ing problems experienced with an S&C Scada-Mate Switching System. This guide is primarily intended for installations furnished with a communication and control unit that includes a WESDAC DART (Distribu- tion Automation Remot,e Terminal) RTU by Harris Con- trols, but, is also generally applicable to installations furnished with a remote terminal unit of other manufac- ture, as well as installations furnished with a switch-con- trol unit or a switch-control unit with battery charger and battery packs.
The DART RTI; and optional communication proces- sor module (CPM), if furnished, must be properly config- ured at the time of installation.
Instructions for configuring the DART RTU are pro- vided in Instruction Sheet 768-550. “S&C Scada-Mate Switching Systems: Communication and Control ITnit Fur- nished With DART RTU C,onfiguration System Software Version 2.02 or Higher.”
Instructions for configuring the CPM using the DBO/CPM Configuration System are provided in Instruc- tion Sheet 768-600, “S&C Scada-Mate Switching Systems: Communication Processor Module for Communication and Control Unit;” refer also to Harris Controls’ documen- tat,ion, “CPM Configuration Guide” and “DART Configura- tion Syst,enl User’s Guide.” Instructions for configuring the CPM using the ConfigPro Configuration System are provided in Harris Controls’ documentation, “ConfigPro Configuration System User’s Guide.”
In the troubleshooting procedures that follow, it is assumed that the user has a good working knowledge of the DARTMAINT maintenance program and, if the optional CPM has been furnished, the WESMAINT maink- nance program.
768.554 INSTRUCTION SHEET Page 2 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. - Toronto
INTRODUCTION - Continued I Where to Start . . . Refer to the table of contents on page 1 to determine the appropriate chart for diagnosing the problem. Refer to the illustrations in Instruction Sheets 768-550 and 768-555 to identify components indicated in the chart.
Instructions for replacing firmware and components of a communication and control unit are provided in Instruc- tion Sheet 768-555. As that instruction sheet points out, during the replacement procedure, precautions should be taken to prevent static charges, which can damage not only the existing item but the replacement item as well. Although replacement items are furnished in static- shielded bags, the use of a static-dissipative work surface, such as the 3M 8501 Portable Static-Dissipative Field Ser- vice Kit (available from S&C as Catalog Number 9931- 218), is highly recommended. This kit includes a static- dissipative work mat and a ground cord assembly with wrist strap, for connecting the mat-along with the person changing the item-to the same ground point.
If, after following the diagnostic procedure, you still can’t resolve the problem, or if the problem is intermittent in nature, contact the nearest S&C Sales Office.
Tools Required: e
e
e
e
e
e
e
e
e
e
True RMS digital multimeter.
IBM PC or compatible computer (XT or higher), or por- table, with hard disk drive.
DART Configuration System Software.
DSOWCPM or ConfigPro Configuration System Soft- ware if the optional communication processor module has been furnished. CPM Application Configuration Files.
DART maintenance cable.
Integrated-circuit extraction tool. In some instances, special extraction tools are required; in those instances, specific AMP Incorporated tool part num- bers are referenced in the instructions. Tom screwdriver for # 4 4 0 pan-head and #632 truss- head T10 machine screws.
Phillips screwdriver for #8-32 machine screws.
Nutdriver for #&I0 hex nuts.
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 3 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART I . SCADA-MATE SWITCH WON'T OPERATE UNDER LOCAL CONTROL I
Scada-Mate Switch won't operate
wlrlng dlagram and Refer to system
across swltch control connect voltmeter
termlnals to operator
1 Place 1ocal:remote
Press pushbutton and switch in "LOCAL '
listen for operatlon of output relay
Remove control cable from communlcatlon
and control unlt (CCW
NO
between termmals battery charger
1 and 2
t
1
battery charger and switch control Swltch
replacement Contact control may need
your nearest S&C Sales Offlce
I I L
need replacement Contact your nearest
S&C Sales Offlce
A
I CLOSED
Place 2 4-0hm. 75-wat reslstor across one
battery for 15 seconds whlle monttorlng
voltage Repeat for
1 1- With batteries stlll dlsconnected,
measure output of Dattery charger across termlnals 15 and 16
Replace fuse F2
Bussman MDA 10 or F3 wlth
equwalent ampere or
768.554 INSTRUCTION SHEET Page 4 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. - Toronto
I INTRODUCTION - Continued I Where to Start . . . Refer to the table of contents on page 1 to determine the appropriate chart for diagnosing the problem. Refer to the illustrations in Instruction Sheets 768-550 and 768-555 to identify components indicated in the chart.
Instructions for replacing firmware and components of a communication and control unit are provided in Instruc- tion Sheet 768-555. As that instruction sheet points out, during the replacement procedure, precautions should be taken to prevent static charges, which can damage not only the existing item but the replacement item as well. Although replacement items are furnished in static- shielded bags, the use of a static-dissipative work surface, such as the 3M 8501 Portable Static-Dissipative Field Ser- vice Kit (available from S&C as Catalog Number 9931- 218), is highly recommended. This kit includes a static- dissipative work mat and a ground cord assembly with wrist strap, for connecting the mat-along with the person changing the item-to the same ground point.
If, after following the diagnostic procedure, you still can't resolve the problem, or if the problem is intermittent in nature, contact the nearest S&C Sales Office.
Tools Required: True RMS digital multimeter.
IBM PC or compatible computer (XT or higher), or por- table, with hard disk drive.
DART Configuration System Software.
D20WCPM or ConfigPro Configuration System Soft- ware if the optional communication processor module has been furnished.
CPM Application Configuration Files.
DART maintenance cable.
Integrated-circuit extraction tool. In some instances, special extraction tools are required; in those instances, specific AMP Incorporated tool part num- bers are referenced in the instructions.
Torx screwdriver for #4-40 pan-head and "32 truss- head T10 machine screws. Phillips screwdriver for #8-32 machine screws.
Nutdliver for #4-40 hex nuts.
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 3 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART I. SCADA-MATE SWITCH WON'T OPERATE UNDER LOCAL CONTROL I
cada-Mate Swltch won't operate usmg openklose pushbuttons
Refer to system wlrlng dlagram and connect voltmeter
across swltch control
Place 1ocal:remote
Press pushbutton and swltch In "LOCAL "
Isten for operatlon of output relay
1
c L F
OPEN
t Remove control cable from comrnunlcatlon
and control unlt (CCW
CLOSED c e c
F
YES
1 NO
between termlnals battery charger.
1 and 2 I I <\i >24 VDC
Check w m g betweer battery charger and
swltch control Swltch control may need
replacement Contact your nearest S&C
Sales Offlce
1 I Battery charger may need replacement
Contact your nearest S&C Sales Offlce
I I
Dlsconnect batterles Place 2 4-0hm, 75-wat
reslstor across one battery for 15 seconds
whlle rnonltormg voltage Repeat for
other battery
O Y E S battery voltage drop below Replace
10 7 VDC
dlsconnected, measure output of
battery charger across terrnlnals 15 and 16
1 E l I 4 charger and check cover I
Bussman MDA 10 or F3 wlth
ampere or equivalent
768.554 INSTRUCTION SHEET Page 4 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART I. SCADA-MATE SWITCH WON'T OPERATE UNDER LOCAL CONTROL- Continued I
Measure voltage
Check contlnulty across control
cable connector terminals 2 and 3
Close dlsconnect usmg a hookstlck Reconnect control !I
There may be a cable to CCU rnechanlsm
problem. Contact your nearest S&C
Sales Offlce
Is
YES
7 " L r
across control cable connector
terminals 1 and 3
INSTRUCTION SHEET 768-554 S&C ELECTRIC COMPANY Chicago Page 5 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART I I . SCADA-MATE SWITCH WON'T OPERATE UNDER REMOTE CONTROL I
under remote control but does operate Scada-Mate Switch won't operate
usmg openiclose pushbuttons
4 Remove DART RTU
cover
Swltch on "ON" posltlon
If DS2 Isn't Ilt or IS
Control" Indicator may be corrupted on conttnuously Shut off DART RTU, v I then turn It back on I
Shut off DART RTU Connect malntenance
MAINTENANCE cable to "DART
PORT' on DART RTU and "COM1 P O R T
on your personal computer, and run
DART Conflguratlon System
t Set "on tme" for 500
download revised configuratlon
at 500
i Run DARTMAINT lnltlate control output
and llsten for operatlon of output
relay
lnltiate control output for another relay and listen for Its operatlon
YES
\I
" + NO f i relay
operate
Reconflgure DART RTU and I
conflguratlon lnltlate download revlsed
control output If relay sttll doesn't operate, contact your nearest
S&C Sales Offlce
NO
!I
V YES
replacement Contact your nearest S&C
Sales Offlce
L
Shut off DART RTU and CPM Connect
"CPM MAINTENANCE mamtenance cable to
PORT'' on DART RTU and "COM1 PORT" on (our personal computer.
and run D20/CPM Conflguratlon System Select appllcatlon flle
and check pulse duratlon settlng
c Set pulse duration
for 500 mllllseconds and download I YES c
lnltlate control output
operatlon of output and llsten for
768.554 INSTRUCTION SHEET Page 6 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART II. SCADA-MATE SWITCH WON'T OPERATE UNDER REMOTE CONTROL- Continued I
I YES
and download
lnltlate control output. revlsed conflguratlon
If output relay stlll
contact your nearest doesn't operate,
S&C Sales Offlce
Check connector at Swltch DART RTU terminal operate board TB4
Scada-Mate Swltch from
master statlon If unsuccessful,
verlfy that DART RTU IS receivmg proper command
I sequence I Correct DART
DART RTU may need replacement
Contact your nearest S&C Sales Offlce
1 Allgn connector
reattach + properly and
Check connectors on switch control
NO Allgn connector(s) + properly and
reattach
between DART Check wlrlng
RTU and swltch
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 7 of 23 S&C ELECTRIC CANADA LTD. 9 Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART Ill. DART RTU OR TRANSCEIVER DOESN'T OPERATE I
DART RTU doesn't operate DS1 "Mlcroprocessor Run" LED Indicator
Isn t Ilt or IS Ilt conttnuously
Put power swltch In "ON" posltlon
Replace fuse F1 wlth Bussman MDL 1
ampere or equivalent
1 No Measure voltage at DART RTU termlnal board TB1 , between terminals TB1-1 (+)
doesn't operate
t FROM CHART VI.
PAGE 18
Y E S
connector P1 between DART RTU
and WESTERM
NO
+ EXTERNAL
O N 0 211 voltage 8 VDC &NO charger battery power . Put power switch In
light on "ON" posltlon
4 YES
PROCEED TO CHARTIII. PAGE 10
and reattach
f VOLTAGE
SOURCE SENSOR
V I Put swltch in "OFF'
posltlon and measure open-clrcult voltage .
of each battery at test points
Remove battery charger cover and
check fuses
Replace F2 or F3 fuse wlth YES 0 Bussman MDA 10 F3 operated
ampere or equivalent
1 No
Y . Replace
battery packs
voltage
"EXTERNAL SOURCE" Input selector swltch in
posltion Connect Isolated
"EXTIAC " Put swltch In 120-VAC source to
"ON" posltlon and charge batterles for 24 hours
- 768.554 INSTRUCTION SHEET Page 8 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
CHART Ill. DART RTU OR TRANSCEIVER DOESN'T OPERATE - Continued I
Check w m g between external source and
battery charger I Measure voltage at
battery charger, between terminals
Measure voltage at battery charger, voltage
between terminals 21 20 VAC
r
Hlgh-voltage clrcult must be energized for battery
deslred, check operatlon charger to functlon If
wlth battery charger input selector swltch in
"EXTERNAL SOURCE" positlon, wlth 120-VAC source connected to termmals 34 and 35
Voltage sensor or voltage llmlter may
battery charger, need replacement
between termmals Contact your nearest
27 and 28 (DART S&C Sales Offlce
RTU) and 25 and 26 (transceiver)
i i
~ ~
.+ or voltage sensor source Dlsconnect external source
cover and check fuse F1 Remove battery charger
Fuse F1 can't be
Contact your nearest L S&C Sales Offlce
battery charger
YES . Plug 11-pln connector back In
measure voltage at battery at battery charger and
charger, between terminals 27 and 28 (DART RTU) and 25
and 26 (transceiver)
Plug 11-pln connector back
Remove qulck-disconnect In at battery charger
terminals from battery power llght packs, noting polarity and to whlch pack connector
was attached
J No
Battery charger
replacement Contact your nearest S&C Sales Offlce I17
NO L c
Check wirlng between battery charger and
DART RTU
L
Put swltch In "OFF positlon and measure open-clrcult voltage of each battery at
test polnts
I I I I Place batterv charaer Input I A
replacement may need
Contact your nearest S&C Sales Offlce
posltlon "EXTERNAL selecto; Connect swltch SOURCE" Isolated In 1 NO <:>-I of eftherbattery
120-VAC source to 510 5 VDC battery "EXTIAC " Put switch In packs
"ON" posltlon and charge I batteries for 24 hours I V
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 9 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Outdoor Distribution
Troubleshooting Guide
[ CHART 1 1 1 1 DART RTU OR TRANSCEIVER DOESN'T OPERATE -Continued ~~
FROM CHART 111. PAGE 8
CHART VI. OR
PAGE 17
Y Remove DART
RTU cover
c
1 YES
Carefully remove wlth extractlon tool, check
and reseat * If DART for damaged plns,
RTU stlll doesn't operate, It may need replacement Contact
your nearest S&C Sales Offlce
extractlon tool and redace wlth correct
verslon * If DART RTU still doesn't operate. It I
may need replacement. Contact your nearest
S&C Sales Offlce I
NO
extraction tool, check
and reseat.* If DART for damaged plns,
replacement Contact operate, It may need
your nearest S&C
Statlc-Dlsslpatlve Fleld Servlce Kit (avallable from S&C as Catalog Number * The use of a statlc-dlsslpatlve work surface, such as the 3M 8501 Portable
9931 -21 8) IS hlghly recommended
appropnate flrrnware verslon Contact your nearest S&C Sales Office If necessary to determlne the
A Speclal extractlon tools are requlred for U19 (CPU) and U43 (DSP). For U19 (CPU), use AMP Incorporated Part Number 821648-1 or equlvalent For U43 (DSP), use AMP Incorporated Part Number 821566-1 or equlvalent.
Carefully remove wlth extractlon tool
and replace wlth verslon match
verslon indicated on If DART RTU stlll label on DART doesn't operate,
It may need replacement
Contact your nearest S&C Sales Offlce
NO
DART RTU may need replacement Contact
your nearest S&C Sales Offlce
extractlon tool.Acheck for damaged plns,
and reseat * If DART RTU still doesn't
replacement. Contact operate, it may need
your nearest S&C
768.554 INSTRUCTION SHEET Page 10 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART IV. DART CONFIGURATION SYSTEM OR DARTMAINT WON'T RUN I
DART Configuration System or DARTMAINT won't run
DART RTU and 'TOM1
and personal computer and properly
DART RTU and PC. cable Then turn on
and reboot
Shut off DART RTU and personal computer, and disconnect malntenance
cable Check connector pln contlnultym
7- O N 0 pln contlnulty Repalr malntenance or replace
cable
1 YES
Reconnect malntenance cable Turn on DART RTU
and PC and reboot
V < > N O replacement Contact your emulator set Set baud rate
for 2400 bps nearest S&C Sales Offlce
See S&C lnstructlon Sheet 768-550, Appendlx C for pln conflguratlon of
munlcation port, Cable Catalog Number TA-2247 (or user-furnlshed equlva- DART malntenance cable For personal computers havlng 25-pln serlal com-
communicatlon port. Cable Catalog Number TA-2248 (or user-furnished lent) should be used For personal computers havlng 9-pln serlal
equlvalent) should be used
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 11 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART V. DART RTU WON'T COMMUNICATE WITH MASTER STATION I
Y wlth master statlon
Put power switch In "ON" posltlon
* YES
transcelver
and DART RTU.
Set correct address address. correct
beatsisecond corrupted Shut off DART RTU, then turn
\ / 4 BEATS/
r
i Shut off DART RTU
Connect mamtenance cable to "DART MAINTENANCE
PORT on DART RTU and "COMI PORT"
on your personal
DART Conflguratlon computer, and run
System
Reconflgure DART RTU Then download
DSI stlll
need replacement. Or conflguratlon software may be lncompatlble wlth funware. Contact your nearest S&C
Sales Offlce
+ L t
L
See S&C lnstructlon Sheet 768-550, Appendlx B or Appendlx C + In D2OiCPM Conflguratlon System Software Verslons 4 40 to 5 03, corrupt V See S&C lnstructlon Sheet 768-550 for procedure conflguratlons can contam hldden characters In conflguratlon flle If. after
* Applicable to DART Conflguratlon System Software Verslon 2 01 and card working copy of software and use back-up copy downloadmg. CPM DSI "Mlcroprocessor Run" lndlcator is stlll flashing. dis-
hlgher See S&C lnstructlon Sheet 768-550 for procedure for speclfylng DNP verslon A A speclal extraction tool IS requlred Use AMP Incorporated Part Number
* The use of a statlc-dlsslpatlve work surface, such as the 3M 8501 Portable Statlc-DIsslpatwe Fleld Servce Klt (avallable from S&C as Catalog Number 9931 -21 8) IS hlghly recommended
822253-2 or equivalent
768.554 INSTRUCTION SHEET Page 12 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART V. DART RTU WON'T COMMUNICATE WITH MASTER STATION - Continued I
DNP verslon Select approprlate
speclfledt modeT
Select approprlate modeT
communlcatlons parameters parameters.
YES lh
Select approprlate analog InputsT
Download revlsed conflguratlonv
Send test slgnal
master statlon b to transcelver from
I \ I I
FROM CHART VII. > PAGE 20
communicate wlth master
slgnal and Contact your transmlt nearest S&C
Sales Offlce may need replacement. Contact your nearest S&C
Carefully
extractlon tool remove wlth
and reseat* IYES DART RTU, then turn
corrupted Shut off
I t back on+
CPM may need replacement Contact your nearest S&C
1 CPM may need
nearest S&C Sales Offlce
Carefully remove wlth extractlon toolA and
reseat*
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 13 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART V. DART RTU WON'T COMMUNICATE WITH MASTER STATION -Continued I
FROM CHART V. PAGE 13 Send test slgnal to
transcetver from
Y I
Shut off DART RTU Connect malntenance cable to "CPM MAINTENANCE PORT"
on DART RTU and "COM 1 PORT" on your personal computer, and run D20ICPM
Conftguratlon System
-
Open mam menu and select "SYSTEM FUNCTIONS
Transceiver may need replacement.
Contact your nearest S&C Sales Offlce
1 YES
Contact your nearesl S&C Sales Offlce or,
If you have the
WESMINT At expertise, run
D20M> or 68K>
"SA COM 1 " or prompt, type
"SA COM2
-D FROM CHART VI. PAGE 19
RTU address address Then download revlsed configurations
1 YES y correct
Select appropriate appllcatlon flle and
to CPM address indicator check master station
BOO8 and BO11
'i / t YES
NO master
correct n Set correct address Then
download
I configuration I revlsed
S&C Sales Offtce or, if you have the expertise, run WESMAINT
i YES
A I A Revlse the CPM conflguratlon as
approprlate. Then download revlsed
configuration
coml replacement Contact
your nearest S&C Sales Office
settings agree 4RT RTU
v parameters
I YES
Check message quallty at master
statlon If necessary, contact your nearest
S&C Sales Office
9 See S&C lnstructlon Sheet 768-600 for procedure
768.554 INSTRUCTION SHEET Page 14 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART V. DART RTU WON'T COMMUNICATE WITH MASTER STATION - Continued I
1 YES
nearest S&C Sales Offlce
There's a frammg error, usually caused by poor
communlcatlon lmk Check communlcatlon path and verlfy slgnal
strength
There's a parlty error, usually caused by
Incorrect baud rate, Incorrect parlty
checkmg, or incorrect number of stop blts
Check master statlon settings agalnst
appllcatlon flle settlngs
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 15 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I
CHART VI. QUESTIONABLE STATUS INPUTS RECEIVED AT MASTER STATION I status Inputs recelved at master station
No status inputs or unreasonable
I I A
generaied In hardware or
HARDWARE
A input termlnal v block
is the expected
state
Check voltage at Is NO DART RTU voltage
Input 0 VDC ?
YES
- Run DARTMAINT and view status
of the pomt
A PROCEED TO
CHART VI. PAGE 18
-4- PROCEED TO
CHART VI. PAGE 19 Put DART RTU
power switch In
"ON" posltlon
L
"OFF position, then c
I Put DART RTU
"OFF" posltlon, then power swltch In
"ON" positlon
768.554 INSTRUCTION SHEET Page 16 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART VI. QUESTIONABLE STATUS INPUTS RECEIVED AT MASTER STATION - Continued 1
Locate the + assoclated contact on wlrlng dlagram
aa CONTACT
IS the from back of
status Input communlcatlon and
control unit and check contlnulty across a and b contacts
CHARGER
'ALARM 1 A
Mechanlsm may need replacement Contact
your nearest S&C continulty
\Y Sales Offlce
r
localiremote swltch IS Make sure that
plug connected to In "LOCAL " Remove Is
local/remote contact on swltch control and
check contlnulty across localiremote contact
L°CA"REMoTE there YES Swltch control may need replacement
S&C Sales Offlce con:lnulty Contact your nearest
NO
,
There may be a
Contact your nearest hardware problem
S&C Sales Offlce
Put swltch on battery charger In "OFF posltlon Remove
11 -pin connector from battery charger and
check contlnulty between termlnals
23 and 24
Contact your nearest S&C Sales Offlce
NO
There may be a software problem
Contact your nearest S&C Sales Offlce
Contact your nearest lost conflguratlon
I
flashlng at Reconflgure flash~ng at PROCEED TO 4 beats/ DART RTU 4 beats/ CHART 111. seconds PAGE 10
YES
Check wlrlng back to DART RTU for short clrcults Check plugs
for mlsaliqnment
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 17 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART VI. QUESTIONABLE STATUS INPUTS RECEIVED AT MASTER STATION - Continued I
FROM CHART VI. PAGE 16
Y status polnt that
another
should have 24 VDC
DART RTU status wettmg voltage at
block. but v doesn't
Check wlrlng between DART RTU and battery
charger
1 BATTERY
i YES
24 VDC
avallable at battery
NO
+ CHART 111. PROCEED TO
PAGE 8
A A SWITCH CONTROL
Swltch control may wettlng voltage need replacement
avallable at status Dolnt Contact vour nearest
aa CONTACT
bb CONTACT
Verify contact path If I I necessary, contact I
your nearest S&C Sales Offlce
c I
,
1 YES
Check wlrlng between battery charger and
DART RTU
768.554 INSTRUCTION SHEET Page 18 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART VI. QUESTIONABLE STATUS INPUTS RECEIVED AT MASTER STATION - Continued I
FROM CHART VI. PAGE 16
Y mapplng at master
WESMAINT
status agree wlth Input
status
Verlfy status pomt S&C Sales Office or, If . mappmg In protocol No b Contact your nearest
you have the expertise. appllcatlon flle remap status polnts
O Y E S polnts software There may problem be a
Contact your nearest S&C Sales Offlce
1 No PROCEED TO
CHART V. PAGE 14
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 19 of 23 S&C ELECTRK CANADA LTD. Toronto April 24, 1995
S&C ScadaMateQP Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION I
PROCEED TO CHART V. PAGE 13
PROCEED TO CHART V. PAGE 12
Refer to analog
Input pomt deflnltions Inputs llst for analog
L v
current or oseudo
T
Run DARTMAINT and view analogs
Check for large voltage or current unbalance
Check phase angles anc power factor for senslble
correctlons may not be correct. Current sensor
output leads may be transposed.
Check that correct conftguratlon system
software IS used Check wattshars
scaling*
1 p correct
RTU. Then download conflauratlon
* Applicable to DART Conflguratlon System Software Verslon 2 02 and hlgher
768.554 INSTRUCTION SHEET Page 20 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION - Continued I
CURRENT
Run DARTMAINT
Measure voltage at DART RTU
TB2, TB3, and termlnal board
TB4, between termlnals
A I a n d v l e ~ n a ' o g s Convert count to YES NO . actual current or 4 to 6 VAC
voltage
PROCEED TO CHART VII.
PAGE 22
A I lrmg back to -----f Y Y L ~ I LRM DART / values \
1 No
Check voltage and current scaling
Remove control cable I xs from back of
cornmunlcatlon and control unlt and measure current between termlnals correspond to
9 and 12 (phase A) prlmary 10 and 12 (phase €3) 11 and 12 (phase C)
If swltch IS closed,
S&C Sales Offlce Current sensor may need replacement
x V SINGLE CURRENT POINT
correct affected or multlple
Reconflgure DART RTU Then download
MULTIPLE POINTS
Verlfy that rlbbon connector between
WESTERM DART IS
DART RTU and
properly attached at both ends
A connector YES
Contact your nearest S&C Sales
properly attached
properly and reattach
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 21 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada=Mate@ Switching Systems Troubleshooting Guide Outdoor Distribution I I CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION - Continued I
FROM CHART VII. PAGE 21
Y Measure voltage
battery charger, between 4 Measure voltage at PHASE
termlnals 29 and 30 25 and 26 (phase C) 23 and 26 (phase A)
V + l Check w m g
WESTERM DART and battery charger
or "VOLTAGE
In "VOLTAGE SENSOR
SOURCE Dosltlon SOURCE I I I
Measure voltage at batterycharger,
between termlnals 21 and 22
A voltage
50 TO 90 VAC
Battery charger may need replacement
Contact your nearest S&C Sales Offlce 120 TO
140 VAC
PHASE A PHASE B
PHASE C &
<=4 TO 6/voltage\ I Make sure that I c=4 to 6 VAC 69 VAC voltage sensor =4 to 6 VAC, output selector
swltch IS In 5 VAC posltlon
=4 TO 6
back to
Measure voltage at swltch control,
between terminals A and N (phase A) -+ C and N (phase C)
.i) 4 to 6 VAC
Remove control cable from back of
communlcation and r-. Swltch control may
Contact your nearest need replacement.
S&C Sales Office ~~
0 VAC voltage between . "--b
control unlt and measure
13 and 16 (phase A) terminals
14 and 16 (phase B) 15 and 16 (phase C)
Check connectlons to battery charger,
termlnals 29 and 30
Contact your nearest S&C Sales Offlce
Check wirlng to battery charger or
swltch control
768.554 INSTRUCTION SHEET Page 22 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION - Continued I
CURRENT
Run DARTMAINT and vlew analogs Convert count to actual current or
"i voltage
YES
Measure voltage at DART RTU termlnal board TB2, TB3, and TB4, between
termlnals 1 and 2
1
phase voltage NO . PROCEED TO
CHART VII. PAGE 22
reasonable CHART VII.
PAGE 23 If 0 K . proceed
NO
Check voltage and current scallng
Remove control cable from back of
cornmunlcatlon and control unit and measure surrent between termlnals
9 and 12 (phase A) 10 and 12 (phase B) 11 and 12 (phase C)
If swltch IS closed,
S&C Sales Offlce Current sensor may need replacement
CURRENT POINT
YES affected or
Reconflgure DART RTU Then download
conflguratlon
c . Verify that rlbbon
connector between DART RTU and
WESTERM DART IS
properly attached at both ends
1 Contact your
nearest S&C Sales Off Ice
t
properly and reattach
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 21 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995
S&C Scada-Mate@ Switching Systems Outdoor Distribution
Troubleshooting Guide
]CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION - Continued I FROM CHART VII.
PAGE 21
Y
battery charger, between 4 Measure voltage at PHASE
termlnals 29 and 30
or "VOLTAGE
In "VOLTAGE
SOURCE" posltlon SENSOR SOURCE
SENSOR
w Measure voltage at
batterycharger, I 21 and 22 I between terrnlnals
0 VAC + 50T0 1 need replacement
Contact your nearest S&C Sales Offlce 120 TO
140 VAC
Check connectlons to battery charger,
termlnals 29 and 30
Measure voltage
between termlnals at swltch control,
23 and 26 (phase A) 25 and 26 (phase C)
PHASE A PHASE B
PHASE C &
5=4 to 6 VAC, output selector
5 VAC posltlon or swltch IS In
Check wtrtng back to
WESTERM DART
Measure voltage at
between terrnlnals swltch control,
A and N (phase A)
\ /A
"U Swttch control may
Remove control cable need replacement Contact your nearest
S&C Sales Offlce from back of
cornrnunlcatlon and control unlt and measure
voltage between
13 and 16 (phase A) terrnlnals
14 and 16 (phase B) 15 and 16 (phase C)
S&C Sales Offlce
Contact your nearest S&C Sales Offlce
~
Check wlnng to battery charger or
swltch control
76&554 INSTRUCTION SHEET Page 22 of 23 S&C ELECTRIC COMPANY Chicago April 24, 1995 S&C ELECTRIC CANADA LTD. Toronto
I CHART VII. QUESTIONABLE ANALOG INPUTS RECEIVED AT MASTER STATION - Continued I
FROM CHART VII. PAGE 21
Y Run DARTMAINT and vlew current unbalance
1
value Vlew voltage reasonable unbalance
1 No I
current
conslstent wlth current
unbalance
c I
Check phase
mappmg and analog scalmg in protocol
If 0 K , Droceed appllcatlon flle.
conslstent wlth -” voltage
unbalance
Check voltage sensor phase angle correctlon
factors Verlfy that phase(s) wlthout battery
charger 4 9 ’ . wlth battery charger =25”
t YES
Verlfy potnt rnappmg and full-scale values
at master statlon RTU furnished
No
Current sensor output leads may be
transposed If 0 K , proceed
angle = I 80” dlfferent
-”
Check current sensor phase angle correctton factors
J
L
INSTRUCTION SHEET 768.554 S&C ELECTRIC COMPANY Chicago Page 23 of 23 S&C ELECTRIC CANADA LTD. Toronto April 24, 1995