DATE Apr. 27, 2004 No. B74A254H 1/12 (KY12024H) DAIKIN INDUSTRIES, LTD. INFORMATION ON REPAIRS OF PART In case of replacing the parts shown in the Current spec. column, please use the parts shown in the Substitute spec. column referring to the instructions below. Item: Pressure sensor Current spec. Substitute spec. *Part No. Drawing No. Model/Spec. *Part No. Drawing No. Model/Spec. Accessories For details, refer to page 3. Applicable model: Circle either one of the following Items 1. Applicable all models 2. Limited applicable models (Enter applicable model names in the blank) However, note that the columns *1 to 11 of the applicable models on page 3 have the following restrictions. *1: RSEYP8KJY1 and RSEYP10KJY1 that were manufactured in October 2000 or earlier, and all other models *2: RSEYP8KJY1 and RSEYP10KJY1 that were manufactured in November 2000 or later *3: FRDP170A and FRDP170AB that were manufactured in August 2001 or earlier, and all other models *4: FRDP170A and FRDP170AB that were manufactured in September 2001 or later *5: RYP112P (PE, PH), RP112P (PE), RZYP56·63·80PT (E, H), RZYP56·63·80PV (E, H), RZYP56·63·80MT (E, H), RZYP56·63·80MV (E, H), RZYP112·140·160P (E, H), RZYP112·140·160M (E, H), RZYP140MS (E), CU-P56·63·80XF (S, Y), CU-P56·63·80XG (S, Y), CU-P112·140·160XF (Y), CU- P112·140·160XG (Y), CU-P112CK (Y), CU-P112HK (Y), and LRYP48 (E, H) *6: RSX(Y)5KTAL (E), RSNY8KTAL (E), CU-8·10MX1NNA, and CU-8·10MC1NNB that were manufactured in April 2005 or earlier; RSX(Y)8·10KTAL, CU-5MX1NNA and CU-5MC1NNB that were manufactured in October 2004 or earlier LRLC18K (E) and LRLC24K (E) that were manufactured in August 2004 or earlier *7: RX8·10KY1 (E), RX8·10KYAL (E), RXY8·10KY1E, RXY8·10KYAL (E), CU8-10MA2XNA that were manufactured in April 2005 or earlier; RXY8·10KY1 and CU-8·10MF1XNA and CU-8·10MF1YNA that were manufactured in October 2004 or earlier LRE20K (E, H), LRE25K1 (E, H), LRLC12K (E), LRLC8K (E), LVE20·25K that were produced in August 2004 or earlier *8: RSX(Y)5KTAL (E), RSNY8KTAL (E), CU-8·10MX1NNA, and CU-8·10MC1NNB that were manufactured in May 2005 or later; RSX(Y)8·10KTAL, CU-5MX1NNA and CU-5MC1NNB that were manufactured in November 2004 or later; LRLC18K (E) and LRLC24K (E) that were manufactured in September 2004 or later *9: RX8·10KY1 (E), RX8·10KYAL (E), RXY8·10KY1E, RXY8·10KYAL (E), and CU8-10MA2XNA that were manufactured in May 2005 or later; RXY8·10KY1, CU-8·10MF1XNA and CU-8·10MF1YNA that were manufactured in November 2004 or later, LRE20K (E, H), LRE25K1 (E, H), LRLC12K (E), LRLC8K (E), and LVE20·25K that were manufactured in September 2004 or later *10: Any models other those listed in *6, *7, *8, and *9 *11: Any models other those listed in *2 and *9

Transcript of INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman...

Page 1: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

DATE Apr. 27, 2004 No. B74A254H 1/12

(KY12024H)

DAIKIN INDUSTRIES, LTD.

INFORMATION ON REPAIRS OF PARTIn case of replacing the parts shown in the Current spec. column, please use the parts shown in the Substitute spec. column referring to the instructions below.

Item: Pressure sensor

Current spec. Substitute spec.*Part No. Drawing No. Model/Spec. *Part No. Drawing No. Model/Spec. Accessories

For details, refer to page 3.

Applicable model: Circle either one of the following Items1. Applicable all models2. Limited applicable models (Enter applicable model names in the blank)

However, note that the columns *1 to 11 of the applicable models on page 3 have the following restrictions.

*1: RSEYP8KJY1 and RSEYP10KJY1 that were manufactured in October 2000 or earlier, and all other models*2: RSEYP8KJY1 and RSEYP10KJY1 that were manufactured in November 2000 or later*3: FRDP170A and FRDP170AB that were manufactured in August 2001 or earlier, and all other models*4: FRDP170A and FRDP170AB that were manufactured in September 2001 or later*5: RYP112P (PE, PH), RP112P (PE), RZYP56·63·80PT (E, H), RZYP56·63·80PV (E, H),

RZYP56·63·80MT (E, H), RZYP56·63·80MV (E, H), RZYP112·140·160P (E, H), RZYP112·140·160M (E, H), RZYP140MS (E), CU-P56·63·80XF (S, Y), CU-P56·63·80XG (S, Y), CU-P112·140·160XF (Y), CU-P112·140·160XG (Y), CU-P112CK (Y), CU-P112HK (Y), and LRYP48 (E, H)

*6: RSX(Y)5KTAL (E), RSNY8KTAL (E), CU-8·10MX1NNA, and CU-8·10MC1NNB that were manufactured in April 2005 or earlier;RSX(Y)8·10KTAL, CU-5MX1NNA and CU-5MC1NNB that were manufactured in October 2004 or earlierLRLC18K (E) and LRLC24K (E) that were manufactured in August 2004 or earlier

*7: RX8·10KY1 (E), RX8·10KYAL (E), RXY8·10KY1E, RXY8·10KYAL (E), CU8-10MA2XNA that were manufactured in April 2005 or earlier;RXY8·10KY1 and CU-8·10MF1XNA and CU-8·10MF1YNA that were manufactured in October 2004 or earlier LRE20K (E, H), LRE25K1 (E, H), LRLC12K (E), LRLC8K (E), LVE20·25K that were produced in August 2004 or earlier

*8: RSX(Y)5KTAL (E), RSNY8KTAL (E), CU-8·10MX1NNA, and CU-8·10MC1NNB that were manufactured in May 2005 or later;RSX(Y)8·10KTAL, CU-5MX1NNA and CU-5MC1NNB that were manufactured in November 2004 or later;LRLC18K (E) and LRLC24K (E) that were manufactured in September 2004 or later

*9: RX8·10KY1 (E), RX8·10KYAL (E), RXY8·10KY1E, RXY8·10KYAL (E), and CU8-10MA2XNA that were manufactured in May 2005 or later;RXY8·10KY1, CU-8·10MF1XNA and CU-8·10MF1YNA that were manufactured in November 2004 or later,LRE20K (E, H), LRE25K1 (E, H), LRLC12K (E), LRLC8K (E), and LVE20·25K that were manufactured in September 2004 or later

*10: Any models other those listed in *6, *7, *8, and *9*11: Any models other those listed in *2 and *9

Page 2: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

DATE Apr. 27, 2004 No. B74A254H 2/12

(KY12024H)

DAIKIN INDUSTRIES, LTD.

INFORMATION ON REPAIRS OF PART

Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing method sheet.

Substitute part replacement procedures Replace the following parts according to the instructions I to IX in the List on page 3.

No. Name Part No. Drawing No. Q’tyQ’ty of each part

(Number of components for accessories shown below)

AA AB AC AD AE AF AG AH AJ AK AL AM AN

Accessory a’ssy (1) 1510168 RS406278-1 1 1 1 — 1 — — — 1 — 4 — — —

Accessory a’ssy (2) 1510751 RS406278-2 1 1 — — 1 — — — 1 — 4 — — —

Accessory a’ssy (3) 1510182 RS406278-3 1 2 1 1 1 — — — — 1 4 — 1 —

Accessory a’ssy (5) 1513826 RS406278-5 1 2 1 1 1 — — — — 1 4 1 — —

Pressure sensor (for high pressure) 159994J 3P138547-2 1

Accessory a’ssy (6) 1542196 RS406278-6 1 1 1 — 1 — — 1 1 — 4 — — —

Accessory a’ssy (7) 1678792 RS406278-7 1 2 — — — — — — 1 — 4 — — 2

Accessory a’ssy (8) 1682405 RS406278-8 1 2 — — 1 — — — 1 — 4 — — —

Cable tie 980774 NE43027-4 1

(Component parts of Accessories)No. Name Part No. Drawing No. Q’ty No. Name Part No. Drawing No. Q’ty

a Resin band 0944528 NE41015-7 AA h Capillary ass’y (1) 1510911 RS306276-1 AH

b Post with XA base 1121986 RS406178-1 AB j Capillary ass’y (2) 1510928 RS306277-1 AJ

c Wire harness 1510904 RS306275-1 AC k Machine screw 008802J 4SK05108-8 AK

d Pressure sensor mounting plate 1678817 4P142409-2 AD l Wire harness 1542165 RS406183-2 AL

e Wire harness 1122035 RS406183-1 AE m Wire harness 1542064 RS406298-1 AM

f Wire harness 0286811 4PA35382-1 AF n Pressure sensor mounting plate 1678800 4P145954-2 AN

g Wire harness 0286828 4PA35382-3 AG

Page 3: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

DATE Apr. 27, 2004 No. B74A254H 3/12

(KY12024H)

DAIKIN INDUSTRIES, LTD.

[List of Pressure Sensor Substitute Parts]Current spec. Substitute spec.

Part No. Part No.Drawing No. Drawing No.Manufacturer Type TypeIdentification Application Accessories Replacement Procedure Appliecble models

High pressure

Low pressure

High pressure (high accuracy)

2 outputs

Toyoda Machine Works

Saginomiya Seisakusho, Inc.

Toyoda Machine Works

Toyoda Machine Works

Saginomiya Seisakusho, Inc.

High pressure

High pressure

High pressure

High pressure

High pressure

Low pressure

Low pressure

Low pressure

Low pressure

Low pressure

High pressure (high accuracy)

High pressure (high accuracy)

(Low pressure side)(Accessory � for the high pressure side)

or

All models

All models

All models

All models

All models

Page 4: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

4/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement Procedure I[For replacement of old models (e.g. PD116) to PS8040A or PS8050A]

1. Dismount the pressure sensor. (Since the existing relay harness to the

PCB is reused, do not dismount it.)

2. Use the existing holes to mount the existing mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.)

To mount the capillary ass’y (1) to the pressure sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

5. Use the post with the XH base (accessory b ) to connect the harness from the existing PCB and that from the substitute pressure sensor.

Connect the harnesses to the connector, and then wind the vinyl tape around the connector.

Tie excess lead wires using the cable ties.

* The connector may be difference from the original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

Pressure sensor (substitute part)

Resin band (accessory a )

Capillary ass’y (1) (accessory h )

Cable tie

Post with XH base (accessory b )

Wind the vinyl tape here

Harness from the existing PCB

Page 5: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

5/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement Procedure II[For replacement of PS8030A to PS8040A or PS8050A]

1. Dismount the pressure sensor from both the capillary and the connector.

2 Make holes in proximity to the previous sensor mounting position as shown in figure on the left. And then, mount the mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (1) to the pressure

sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

* The connector may be difference from the original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

2-φ3.0 hole

Pressure sensor (substitute part)

Resin band (accessory a )

Capillary ass’y (1) (accessory h )

Cable tie

To the PCB connector

Page 6: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

6/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement Procedure III[For replacement of old model SP8601 (2 output products) to PS8040A or PS8050A]

1. Dismount the pressure sensor from the both capillary and connector.

2. Use the existing holes to mount the existing mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (2)

to the pressure sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

5. Connect the harness from the substitute pressure sensor to the wire harness (accessory c ), and further to the wire harness (accessory m ) using the post with the XH base (accessory b ).

Connect the harnesses to the connector, and then wind the vinyl tape around the connector.

Tie excess lead wires using the cable ties.* The connector may be difference from the

original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

Pressure sensor (substitute part)

Resin band (accessory a )

For low pressure

For high pressure

Capillary ass’y (2) (accessory i )

Cable tie

Wire harness (accessory c )

Post with XH base (accessory b )

Wind the vinyl tape here

Wire harness (accessory m )

For low pressure

For high pressure

Page 7: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

7/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure IV[For replacement of old model SPD91A (2 output products) to PS8040A or PS8050A]

1. Dismount the pressure sensor.

2. Use the existing holes to mount the existing mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (2) to the pressure

sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

5. Connect the harness from the substitute pressure sensor to the wire harness (accessory c ), and further to the wire harness (accessory m ) using the post with the XH base (accessory b ).

Connect the harnesses to the connector, and then wind the vinyl tape around the connector.

Tie excess lead wires using the cable ties.

* The connector may be difference from the original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

Pressure sensor (substitute part)

For low pressure

For high pressure Resin band

(accessory a )

Capillary ass’y (2) (accessory i )

Wire harness (accessory c )

Post with XH base (accessory b )

Cable tie

Wind the vinyl tape here

From PCB

Wire harness (accessory m )

For low pressure

For high pressure

Page 8: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

8/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure V[For replacement of PS8030A (2 output products) to PS8040A or PS8050A]

1. Dismount the pressure sensor from the both capillary and connector.

2. Make holes in proximity to the previous sensor mounting position as shown in figure on the left. And then, mount the mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (2) to the pressure

sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

5. Connect the harness from the substitute pressure sensor to the wire harness (accessory c ), and further to the wire harness (accessory l ) using the post with the XH base (accessory b ).

Connect the harnesses to the connector, and then wind the vinyl tape around the connector.

Tie excess lead wires using the cable ties.* The connector may be difference from the

original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

2-φ3.0 hole

Pressure sensor (substitute part)

For low pressure

For high pressure Resin band

(accessory a )

Capillary ass'y (2) (accessory i )

Cable tie

Wire harness (accessory c )

Post with XH base (accessory b )

To PCB connector

Wind the vinyl tape here

Wire harness (accessory l )

For low pressure

For high pressure

Page 9: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

9/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure VI

Since the part concerned has perfect compatibility, replace it without modification.

1. However, follow the fastening procedure below to prevent the threads from being broken due to excessive fastening.

a. Mount the pressure sensor by fastening it by hand.[For Toyoda Machine Works, Ltd. make, make sure that a spacer (e.g. brass C ring) is inserted in the nut.]

b. Fasten the pressure sensor in the range of 30 to 60° from the position to which it is fastened by hand.

c. Check for airtightness.

2. To mount the harness to the pressure sensor, follow the procedure shown below to prevent rainwater from entering the switch box (for the substitute parts PS8050A and PS8051A).

To prevent the harness from coming in contact with other piping or else, form an upward half loop in the base of the protection tube.

Pressure sensor

Connect the harness with the protection tube end facing downward.

Fix the harness with cable ties provided.

Press fitting spacer

Page 10: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

10/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure VII[For replacement of PS8030A to PS8040A and PS8050A]

1. Dismount the pressure sensor from the both capillary and connector.

2. Make holes in proximity to the previous sensor mounting position as shown in figure on the left. And then, mount the mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (1) to the

pressure sensor, torque it to 15.7N·m±10%.

4. Connect the harness from the substitute pressure sensor to the wire harness (accessory g ), using the post with the XH base (accessory b ).

Connect the harnesses to the connector, and then wind the vinyl tape around the connector.

Tie excess lead wires using the cable ties.

* The connector may be difference from the original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

2-φ3.0 hole

Pressure sensor (substitute part)

Resin band (accessory a )

Capillary ass’y (1) (accessory h )

Cable tie

Post with XH base (accessory b )

Wind the vinyl tape here

Wire harness (accessory g )

Page 11: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

11/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure VIII[For replacement of PS8030A to PS8040A and PS8050A]

1. Dismount the pressure sensor from the both capillary and connector.

2. Make holes in proximity to the previous sensor mounting position as shown in figure on the left. And then fix the mounting plate (accessory n ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.) To mount the capillary ass’y (1) to the pressure

sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

Tie excess lead wires using the cable ties.

* The connector may be difference from the original one in the color. However, that will present no problem.

Capillary ass’y (1) (accessory h )

Pressure sensor (existing part)

Mounting plate (accessory n )

2-φ5.0 hole

Pressure sensor (substitute part)

Resin band (accessory a )

Cable tie

To the PCB connector

Page 12: INFORMATION ON REPAIRS OF PART - Daikin · INFORMATION ON REPAIRS OF PART Note: If the serviceman needs to do works such as a modification and setting change, mention it in the replacing

Replacing method sheet Parts name Pressure sensor

DATE No.DAIKIN INDUSTRIES, LTD.Apr. 27, 2004 B74A254H

(KY12024H)

12/12

* In case of repair using this parts, replace the parts according to the following instruction.

Replacement procedure IX[For replacement of PS8030A to PS8040A and PS8050A]

1. Dismount the pressure sensor from the both capillary and connector.

2. Make holes in proximity to the previous sensor mounting position as shown in figure on the left. And then, mount the mounting plate (accessory d ).

3. Use the resin band (accessory a ) to fix the pressure sensor.

(Securely fix the band in the nut position.)

To mount the capillary ass’y (1) to the pressure sensor, torque it to 15.7N·m±10%.

4. Reinstall the wirings and the capillary of the pressure sensor.

Form a single loop in the capillary after coming out from the switch box.

Tie excess lead wires using the cable ties.

* The connector may be difference from the original one in the color. However, that will present no problem.

Pressure sensor (existing part)

Mounting plate (accessory d )

2-φ5.0 hole

Pressure sensor (substitute part)

For low pressure

For high pressure Resin band

(accessory a )

Capillary ass’y (1) (accessory h )

Cable tie

To PCB connector

For low pressure

For high pressure