IDR-144 Data Sheet - N00397 Digital Remote Indicator Page 1/3 April 2008 The Digital Remote Indicator, IDR 144, is micropocessed product that can be used both as master (for link to digital transducer) and slave (for link for link to RTU, net, etc). (1) RS 485 Serial Interface Modbus RTU is Standard, the second serial interface RS485 is optional. Frontal keyboard with tactile feedback. 3 LCDs displays alphanumeric 1 line 16 characters. Simultaneous indication of 3 voltages (U12, U23, U32) and 3 currents (I1, I2, I3), in the first reading screen. Simultaneous indication of Active Power (Pt), Reactive Power (Qt) and frequency (f), in the second reading screen. Others screens: preview of others electrical variables as: voltage line-neutral (UN1, UN2, UN3) active, reactive and apparent power for phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3), and total (Pt, Qt, St), power factor for phase and total (FP1, FP2, FF3, FPT), angular delay for phase and total (A1, A2, A3, At), active and reactive energy, consumed and supplied energy (Wh+, Wh-, Varh+, Varh-), current demand for phase (DI1, DI2, DI3), active, reactive and apparent total power demand (DPT, DQT, DST), frequency (f). Non volatile memory to store data of RTP, RTC, IDR address in the net, transmission rate and byte format. Auxiliary power supply universal AC/DC Protection: IP50 (Housing) and IP20 (terminal connection). Reading resolution: 0,01% . Processing resolution : 16 bits. Software parameterization. Phases indication : blue (1), white (2) and red (3). Technical Data (NBR 8145) Display Type Liquid crystal display (LCD) (1) line and (16) characters Number of Displays (3) independents, alphanumeric. Illumination Type backlight Characters dimension 8 x 4,34mm Variables indication numeric display until 6 digits Digits coverage until 999999 with decimal point configurable Reading resolution 0,01% Processing resolution 16 bits Return time to first screen configurable Communication fail indicated in the 3 displays (*****) Keyboard Type Frontal with tactile feedback Functions Configuration of indicator (RTP,RTC), Slave number, number of significant algarisms, time-out, polling time, display timer, RS485 (1) communication, transducer address in the net, transmission rate, byte format and display navigation. Protection Through password Internal memory Type Non volatile Stored records RTP, RTC, Slave number, number of significant algorisms, time-out, polling time, communication RS485 (1), transducer address in the net, transmission rate and byte format. Communication/ Serial Interface Communication protocol Modbus RTU Serial interface RS 485 Characteristics RS 485 (1) Master to link to ABB transducers (others: upon request) RS 485 (2) Slave to link to RTU, net, SMC, etc Time out in the master function Configurable. Polling time Configurable. Transmission rate Configurable between 4800,9600, 19200bps and 34800bps (only to RS485 (2)) Byte format Configurable by keyboard. (8 n 2), (8 n 1), (8 e 1) e (8 o 1) Maximum distance 1200m Maximum number of Slaves in the net 31 Electrical Characteristics Auxiliary power supply 20…60Vac/Vcc 85…265Vac e 90…300Vcc 38…265Vac/Vcc Power consumption 6 VA Test voltage 1,5kV/1 min – 60Hz Climatic conditions Operating temperature -20…+60ºC Functioning temperature -25…+70ºC Transport and storage temperature -40…+80ºC Relative humidity 20…90% UR without condensation 13.82kV 119.4kA 13.81kV 121.3kA 13.85kV 120.2kA

description

WEF

Transcript of IDR144EN

Page 1: IDR144EN

IDR-144 Data Sheet - N00397

Digital Remote Indicator Page 1/3 April 2008

• The Digital Remote Indicator, IDR 144, is micropocessed product that can be used both as master (for link to digital transducer) and slave (for link for link to RTU, net, etc).

• (1) RS 485 Serial Interface Modbus RTU is Standard, the second serial interface RS485 is optional.

• Frontal keyboard with tactile feedback. • 3 LCDs displays alphanumeric 1 line 16 characters. • Simultaneous indication of 3 voltages (U12, U23, U32) and 3

currents (I1, I2, I3), in the first reading screen. • Simultaneous indication of Active Power (Pt), Reactive Power

(Qt) and frequency (f), in the second reading screen. • Others screens: preview of others electrical variables as:

voltage line-neutral (UN1, UN2, UN3) active, reactive and apparent power for phase (P1, P2, P3, Q1, Q2, Q3, S1, S2, S3), and total (Pt, Qt, St), power factor for phase and total (FP1, FP2, FF3, FPT), angular delay for phase and total (A1, A2, A3, At), active and reactive energy, consumed and supplied energy (Wh+, Wh-, Varh+, Varh-), current demand for phase (DI1, DI2, DI3), active, reactive and apparent total power demand (DPT, DQT, DST), frequency (f).

• Non volatile memory to store data of RTP, RTC, IDR address in the net, transmission rate and byte format.

• Auxiliary power supply universal AC/DC • Protection: IP50 (Housing) and IP20 (terminal connection). • Reading resolution: 0,01% . • Processing resolution : 16 bits. • Software parameterization. • Phases indication : blue (1), white (2) and red (3). Technical Data (NBR 8145) Display Type Liquid crystal display (LCD) (1) line and (16) characters Number of Display s (3) independents, alphanumeric. Illumination Type backlight Characters dimension 8 x 4,34mm Variables indication numeric display until 6 digits Digits coverage until 999999 with decimal point

configurable Reading resolution 0,01% Processing resolution 16 bits Return time to first screen configurable Communication fail indicated in the 3 displays (*****) Keyboard Type Frontal with tactile feedback Functions Configuration of indicator

(RTP,RTC), Slave number, number of significant algarisms, time-out, polling time, display timer, RS485 (1) communication, transducer address in the net, transmission rate, byte format and display navigation.

Protection Through password

Internal memory Type Non volatile Stored records RTP, RTC, Slave number,

number of significant algorisms, time-out, polling time, communication RS485 (1), transducer address in the net, transmission rate and byte format.

Communication/ Serial Interface Communication protocol Modbus RTU Serial interface RS 485 Characteristics RS 485 (1) Master to link to ABB

transducers (others: upon request) RS 485 (2) Slave to link to RTU, net, SMC,

etc Time out in the master function Configurable. Polling time Configurable. Transmission rate Configurable between 4800,9600,

19200bps and 34800bps (only to RS485 (2))

Byte format Configurable by keyboard. (8 n 2), (8 n 1), (8 e 1) e (8 o 1) Maximum distance 1200m Maximum number of Slaves in the net 31 Electrical Characteristics Auxiliary power supply 20…60Vac/Vcc 85…265Vac e 90…300Vcc 38…265Vac/Vcc Power consumption 6 VA Test voltage 1,5kV/1 min – 60Hz Climatic conditions Operating temperature -20…+60ºC Functioning temperature -25…+70ºC Transport and storage temperature -40…+80ºC Relative humidity 20…90% UR without

condensation

13.82kV 119.4kA

13.81kV 121.3kA

13.85kV 120.2kA

��������������

Page 2: IDR144EN

IDR-144 Data Sheet - N00397

Digital Remote Indicator Page 2/3 April 2008

Construction and mounting Housing Plastic Noril Flame resistant

UL94-UO Fastening By pairs of clamp Electric connections Terminals for pin shaped cable shoes Frontal frame Plastic gray color Assembly Embedded in panel. Protection Housing: IP50 Electric connections: IP20 Dimensions 144x144x70mm Weight ~0,75Kg Electrical Connection

Dimensional Drawing Dimensions in mm

View behind the equipment

Obs.: All the configurations can be made by keyboard except of the Tag, that only can be configured through IBIS-BE-cnf software.

Additional Information The following items contain tips and cautions to be observed by the user for a good functional performance, as well as the maintenance of the instrument and the safety of the installations.

Cautions Be sure that the voltage to be connected to the instrument are compatible

Assembly Instructions Observe the ambient temperature range. At the place of installation, values for vibration, dust, dirt and humidity, which must remain between the limits, established by the protection class of the housing and the climatic group, specified in this data sheet, have to be observed. For mounting on DIN rail, use the snap-in device on the rear of the instrument. The connections can be made with pin for shaped cable shoes, for the input signals in Voltage and Current and for the Auxiliary Power, RS485 and digital outputs terminals type pin.

Product codification

Page 3: IDR144EN

IDR-144 Data Sheet - N00397

Digital Remote Indicator Page 3/3 April 2008

DIGITAL REMOTE INDICATOR N 0 0 3 9 7 - Model: IDR-144 Interface: (01) RS 485 Protocol: Modbus RTU Auxiliary Power Supply 20… 60Vca/Vcc 12 86…265Vca/90…300Vcc 13 38…265Vca/Vcc 14 Optional Standard 1 Two (02) Interface RS485 2 Additional Information Standard configuration 1 Client configuration C

ABB Ltda - ATLV/IE Electrical Instrumentation Av. Dos Autonomistas, 1496 - 06020-902 - Osasco - SP