HVAC_BOQ

11
ITEM DESCRIPTION UNIT QTY UNIT PRICE (SR) TOTAL AMOUNT IN WORDS Div.15A MECHANICAL- HVAC AMOUNT IN NUMBERS

description

hvac equipment details

Transcript of HVAC_BOQ

Div.15

ITEMDESCRIPTIONUNITQTYUNIT PRICE (SR)TOTALAMOUNT IN NUMBERSAMOUNT IN WORDS

Div.15AMECHANICAL- HVAC

15-A.01DUCTED SPLIT CONCEALED UNITS DX-TYPE

Supply and installation of ducted split concealed units DX type complete with referegerant pipes, filters valves and all related accessories,Indoor and outdoor units shall be installed with hangers and supports and vibration isolators, room thermostat control wires condensate drainage connections as per drawings and specification.

aFCU-2 / ACCU-2: @ Basemetn M.P.RoomAirflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO111,500.00

bFCU-4 / ACCU-4: @ Basemetn BUFIAAirflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO19,000.00

cFCU-3 / ACCU-3: @ 1st, 2nd & 3rd Floor Enterance Hall both side flatsAirflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO610,000.00

dFCU-2 / ACCU-2: @ 1st, 2nd & 3rd Floor Family Dining Both side flatsAirflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO611,500.00

eFCU-5/ACCU-5:@1st,2nd&3rd floor Bedroom & Maids room Both side flats, Airflow = 1000 CFM, Total Cooling / Heating Capacity= 2.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO68,500.00SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

fFCU-6/ACCU-6:@1st,2nd & 3rd Double Bedroom Both side flatsAirflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO68,000.00gFCU-6A/ACCU-6A:@1st,2nd&3rd Floor Master Bedroom Both side flatsAirflow = 800 CFM, Total Cooling / Heating Capacity= 4.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO611,500.00

hFCU-1 / ACCU-1: @ Fourth Floor Enterance HallAirflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO113,000.00

iFCU-1A / ACCU-1A: @ Fourth Floor StudipAirflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO113,000.00

jFCU-1A / ACCU-1A: @ Fourth Floor Main Reception ORomAirflow = 2000 CFM, Total Cooling / Heating Capacity= 5.0 TonsPower Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO113,000.00

kFCU-2 / ACCU-2: @ Fourth Floor Guest Dining RoomAirflow = 1600 CFM, Total Cooling / Heating Capacity= 4.0 TonsPower Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO111,500.00

lFCU-4 / ACCU-4: @ Fourth Floor Corridor/stairs Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO19,000.00

SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

mFCU-6/ACCU-6:@ Fourth floor KitchenAirflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO18,000.00

nFCU-3 / ACCU-3: @ Fifth Floor Dressing RoomAirflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO110,000.00

oFCU-3A / ACCU-3A: @ Fifth Floor Master Bed PavilionAirflow = 1400 CFM, Total Cooling / Heating Capacity= 3.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO110,000.00

pFCU-4 / ACCU-4: @ Fifth floor Bedroom/Dressing Room Airflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO19,000.00

qFCU-4A / ACCU-4A: @ Fifth floor CorridorAirflow = 1200 CFM, Total Cooling / Heating Capacity= 3 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO19,000.00

SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

15-A.02WALL MOUNTED SPLIT UNITS DX-TYPE

Supply and installation of Wall mounted split units DX type complete with referegerant pipes, filters valves and all related accessories,Indoor and outdoor units shall be installed with hangers and supports and vibration isolators, room thermostat, control wires and condensate drainaige connections as per drawings and specification.

aFCU-9 / ACCU-9: @ Basement floor Driver Rooms Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 TonsPower Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO46,000.00

bFCU-8 / ACCU-8: @ Ground Floor Enterance Hall Airflow = 800 CFM, Total Cooling / Heating Capacity= 2.0 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO28,000.00

cFCU-9 / ACCU-9: @ Ground floor Driver Rooms Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO37,000.00

dFCU-9 / ACCU-9: @ Fourth Floor Maids Room Airflow = 600 CFM, Total Cooling / Heating Capacity= 1.5 Tons Power Supply 220 V- 1 Ph - 60 HzManfacturer - Trane or Approved equivalentNO17,000.00

SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

15-A.03EXHAUST& VENTILATION FANS

Supply and installation of exhasut fans Inline and Ceiling type complete with flexible ducts, back draft dmapers and disc valves, the internal construction as shown drawings and specification.

aEF-1 : Inline Type@ Basement floor Toilets M.P. Room & Driver roomAirflow = 150 CFM, ESP= 0.5 inch wg Power Supply 220 V- 1 Ph - 60 HzManfacturer - Green Heck or Approved equivalentNO21,500.00

bCEF-1 : Celing exhust fan cassete Type@ Ground floor Airflow = 75 CFM, ESP= 0.25 inch wg Power Supply 220 V- 1 Ph - 60 HzManfacturer - Green Heck or Approved equivalentNO31,000.00

cCEF-1 : Celing exhust fan cassete Type@ 1st,2nd & 3rd floor toilets Airflow = 75 CFM, ESP= 0.25 inch wg Power Supply 220 V- 1 Ph - 60 HzManfacturer - Green Heck or Approved equivalentNO361,000.00

dEF-2 : Inline Type@ Fourth floor ditrty KitchenAirflow = 225 CFM, ESP= 0.5 inch wg Power Supply 220 V- 1 Ph - 60 HzManfacturer - Green Heck or Approved equivalentNO11,800.00

eEF-1 : Inline Type@ Fourth floor ditrty KitchenAirflow = 150 CFM, ESP= 0.5 inch wg Power Supply 220 V- 1 Ph - 60 HzManfacturer - Green Heck or Approved equivalentNO11,500.00

SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

15-A.04Supply Linear Diffuser with Plenum box (SLD)Supply linear diffuser, aluminum steel complete w/ deflectors, dampers,hangers, support, insulated plenum box, accessories, etc.

aSLD 2 SlotLM36600.00bSLD 3 SlotLM135650.00cSLD 4 SlotLM17700.00cSLD 5 SlotLM5760.00

15-A.05ReturnLinear Diffuser (RLD)Return linear diffuser, aluminum steel complete,hangers, support, accessories, etc.

aRLD 2 SlotLM62600.00bRLD 3 SlotLM135650.00cRLD 4 SlotLM27700.00

15-A.06Supply Ceiling Diffuser with Plenum Box (SCD)Supply ceiling diffuser, square face type, aluminum steel complete w/ deflectors, dampers, insulated plenum box, hangers, support, accessories, etc.

aSCD 300 mmNO10450.00bSCD 300 x 300 mmNO6400.00c RCD 300 x 300 mmNO6400.00

15-A.06Exhsut Air Diffursers (EAD)

aEAD 150 x 150NO12250.00

15-A.06Exhaust Grille (EG)

aEG 200 x 200NO3200.00bEG 250 x 150NO1200.00cEG 150 x 150NO39200.00

SUB-TOTAL:

Div.15AMECHANICAL- HVAC (Continuation)

15-A.07Sheet Metal Duct Work( Supply / Return Air Duct )

Supply and Install galvanized steel duct according to SMACNA specifications fabrication - including all formers, hangers fasteners, flanges, sealant, Volume dampers and all accessories shall be included, access doors etc. as per drawings and specifications. Including Air Balancing & Testing commissioning

aSupply / Return Air Duct Gauge-24 & 22M275022 sr per kg

bExhaust Air duct of Gauge -24M212022 sr per kg

15-A.08Fiber Glass Insulation

bSupply and Install insulation for HVAC ducts by fiber glass wall (density 24 kg/m) and thickness 25mm according to the specification and as shown on drawings, complete with all accessories.M290035.00

15-A.09Accoustic Lining

aSupply and Install Acoustic linning for internal HVAC duct by fiber glass wall (density 48 kg/m) and thickness 25 mm according to the specification , and it fixed from inside by a stick pin Item include testing commissioning.M220045.00

15-A.10Flexible Duct

Flexible duct as per required diameter with minimum of 1.5 meters long.Complete with fittings and accessories.

aFD 250 mmLM6075.00bFD 200 mmLM5065.00cFD 150 mmLM16060.00

15-A.11TESTING, ADJUSTING, BALANCING & COMMISSIONINGLS120% of all cost

SUB-TOTAL: