DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth...

88
1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13 th , 2017 At the 34 th Annual Hands-On Relay School Washington State University Pullman, Washington

Transcript of DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth...

Page 1: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

1

DISTRIBUTION PROTECTION OVERVIEW

Kevin Damron & Beth Andrews

Avista Utilities

Presented

March 13th, 2017

At the 34th Annual

Hands-On Relay School

Washington State University

Pullman, Washington

Page 2: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

2

Table of Contents

IEEE Device Designations …………………………………………….…….. 3

System Overview ………………………………………………………....… 4

Distribution (5-30MVA ) Transformer Protection damage curve …….…... 9

Relay Overcurrent Curves …………………………………………..……. 20

Symmetrical Components ……………………………………………..…….. 24

Distribution Fuse Protection ………………………………………….……. 39

Coordinating Time Intervals …………………………………………….… 43

Transformer Relay Settings using Electromechanical Relays ………….…… 52

Transformer Differential Protection ……………………………………….… 67

Smart Grid Challenges & Solutions……………………………………….… 70

Moscow 13.8kV Feeder Coordination Example ……………………………. 76

Page 3: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

3

2 – Time delay relay.

27 – Undervoltage relay.

43 – Manual transfer or selective device.

We use these for cutting in and out

instantaneous overcurrent relays,

reclosing relays etc.

50 (or 50P) – Instantaneous overcurrent

phase relay.

50N (or 50G) – Instantaneous overcurrent

ground (or neutral) relay.

50Q – Instantaneous Negative Sequence

overcurrent relay.

51 (or 51P) – Time delay overcurrent phase

relay.

51N (or 51G) – Time delay overcurrent

ground (or neutral) relay.

51Q – Time delay Negative Sequence

overcurrent relay.

52 – AC circuit breaker.

IEEE Device Designations commonly used in Distribution Protection

Avista sometimes adds letters to these such as F for feeders, T for transformers, B for bus and BF for

breaker failure.

52/a – Circuit breaker auxiliary switch closed

when the breaker is closed.

52/b – Circuit breaker auxiliary switch closed

when the breaker is open.

59 – Overvoltage relay.

62 – Time Delay relay

63 – Sudden pressure relay.

79 – AC Reclosing relay.

81 – Frequency relay.

86 – Lock out relay which has several contacts.

Avista uses 86T for a transformer lockout,

86B for a bus lockout etc.

87 – Differential relay.

94 – Auxiliary tripping relay.

Page 4: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

4

System Overview - Distribution Protection

Objective:

Protect people (company personnel and the public) and equipment by the proper

application of overcurrent protective devices.

Devices include:

Relays operating to trip (open) circuit breakers or circuit switchers, and/or fuses blowing

for the occurrence of electrical faults on the distribution system.

Design tools used:

1 – Transformer and conductor damage curves,

2 - Time-current coordination curves (TCC’s), fuse curves, and relay overcurrent

elements based on symmetrical components of fault current.

Documentation:

1 - One-line diagrams and Schematics with standardized device designations as defined

by the IEEE (Institute of Electrical and Electronics Engineers) – keeps everyone on the

same page in understanding how the system works.

2 - TCC’s

Page 5: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

XFMR 12/16/20 MVA

115/13.8kV

115 kV SYSTEM

13.8 kV BUS

500A, 13.8 kVFDR #515

DELTA/WYE

LINE RECLOSER P584

3Ø = 5158SLG = 5346

3Ø = 3453SLG = 2762

PT-2BPT-2A

3Ø = 3699SLG = 3060

PT-3B PT-3A PT-4

#4 ACSR

1 PHASE#4 ACSR #4 ACSR

#4 ACSR

#2 ACSR#4 ACSR

2/0 ACSR#2 ACSR

3Ø = 1907SLG = 1492

3Ø = 322SLG = 271

3-250 KVAWYE/WYE

PT-865T

A-172

MOSCOW

1 PHASE#4 ACSR

3Ø = 558SLG = 463

PT-3C

PT-6BPT-6A

PT-6C

HIGH LEAD LOW

3Ø = 1210SLG = 877

PT-1

PT-5

PT-7

FUSE

556 ACSR

556 ACSR

13.8 kV FDR #512

500 A FDR

5

System Overview – Inside the

Substation Fence

Transformer

relays

Feeder relay

Page 6: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

6

XFMR 12/16/20 MVA

115/13.8kV

115 kV SYSTEM

13.8 kV BUS

500A, 13.8 kVFDR #515

DELTA/WYE

LINE RECLOSER P584

3Ø = 5158SLG = 5346

3Ø = 3453SLG = 2762

PT-2BPT-2A

3Ø = 3699SLG = 3060

PT-3B PT-3A PT-4

#4 ACSR

1 PHASE#4 ACSR #4 ACSR

#4 ACSR

#2 ACSR#4 ACSR

2/0 ACSR#2 ACSR

3Ø = 1907SLG = 1492

3Ø = 322SLG = 271

3-250 KVAWYE/WYE

PT-865T

A-172

MOSCOW

1 PHASE#4 ACSR

3Ø = 558SLG = 463

PT-3C

PT-6BPT-6A

PT-6C

HIGH LEAD LOW

3Ø = 1210SLG = 877

PT-1

PT-5

PT-7

FUSE

556 ACSR

556 ACSR

13.8 kV FDR #512

500 A FDR

System Overview – Outside the

Substation Fence

Midline

recloser

relay

Page 7: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

XFMR 12/16/20 MVA

115/13.8kV

115 kV SYSTEM

13.8 kV BUS

500A, 13.8 kVFDR #515

DELTA/WYE

LINE RECLOSER P584

3Ø = 5158SLG = 5346

3Ø = 3453SLG = 2762

PT-2BPT-2A

3Ø = 3699SLG = 3060

PT-3B PT-3A PT-4

#4 ACSR

1 PHASE#4 ACSR #4 ACSR

#4 ACSR

#2 ACSR#4 ACSR

2/0 ACSR#2 ACSR

3Ø = 1907SLG = 1492

3Ø = 322SLG = 271

3-250 KVAWYE/WYE

PT-865T

A-172

MOSCOW

1 PHASE#4 ACSR

3Ø = 558SLG = 463

PT-3C

PT-6BPT-6A

PT-6C

HIGH LEAD LOW

3Ø = 1210SLG = 877

PT-1

PT-5

PT-7

FUSE

556 ACSR

556 ACSR

13.8 kV FDR #512

500 A FDR

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 252 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

MIDLINE OCR

MAXIMUM MIDLINE FUSE

Fault I=5665.9 A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

2

2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

4

4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

5

5f

5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

6

6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

A

A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

7

System Overview –Each device has at least one curve plotted with current and time values

on the Time Coordination Curve.

Page 8: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 252 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

MIDLINE OCR

MAXIMUM MIDLINE FUSE

Fault I=5665.9 A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

2

2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

4

4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

5

5f

5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

6

6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

A

A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

8

System Overview –

Damage Curves:

- transformer

- conductor

So, what curve goes where?

What are the types of curves?

Protective Curves:

- relay

- fuse

Damage curves are at the top and to

the right of the TCC.

Protective curves lowest and to the

left on the TCC correspond to those

devices farther from the substation

where the fault current is less.

Page 9: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

9

Transformer Protection - Damage Curve – ANSI/IEEE C57.109-1985

The main damage curve line shows only the thermal effect

from transformer through-fault currents. It is graphed

from data entered below (MVA, Base Amps, %Z ):10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

T IME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. M15 P584 GND INST INST TD=1.000CTR=100 Pickup=3.A No inst. TP@5=0.048s

A

A. T ransf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.

The dog leg on the curve is added to allow for additional

thermal and mechanical damage from (typically more

than 5) through-faults over the life of a transformer

serving overhead feeders.

Dog leg curve - 10 times base current at 2 seconds.

Main curve - 25 times base current at 2 seconds.

Time at 50% of the maximum per-unit

through fault current = 8 seconds.

Avista has Category III size (5-30MVA) Distribution Transformers in service per the above standard.

Page 10: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

10

Copper Conductor Damage Curves ACSR Conductor Damage Curves

(2/0 damage at 1500A @ 100sec.) (2/0 damage at 900A @ 100sec.)

Conductor Damage Curves

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

For ACSR Conductor Damage Curves No.

Comment Date 12/13/05

1

1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.A No inst. TP@5=0.048s

A

A. Conductor damage curve. k=0.08620 A=355107.0 cmilsConductor ACSR336.4 ACSR

B

B. Conductor damage curve. k=0.08620 A=167800.0 cmilsConductor ACSR AWG Size 4/04/0 ACSR

C

C. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 2/02/0 ACSR

D

D. Conductor damage curve. k=0.08620 A=83690.0 cmilsConductor ACSR AWG Size 1/01/0 ACSR

E

E. Conductor damage curve. k=0.08620 A=52630.0 cmilsConductor ACSR AWG Size 2#2 ACSR

FF. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWG Size 4#4 ACSR

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

For Copper Conductor Damage Curves No.

Comment Date 12/13/05

1

1. M15-515 Phase INST INST TD=1.000CTR=160 Pickup=7.A No inst. TP@5=0.048s

A

A. Conductor damage curve. k=0.14040 A=105500.0 cmilsConductor Copper (bare) AWG Size 2/02/0 Copper

B

B. Conductor damage curve. k=0.14040 A=83690.0 cmilsConductor Copper (bare) AWG Size 1/01/0 Copper

C

C. Conductor damage curve. k=0.14040 A=52630.0 cmilsConductor Copper (bare) AWG Size 2#2 Copper

D

D. Conductor damage curve. k=0.14040 A=33100.0 cmilsConductor Copper (bare) AWG Size 4#4 Copper

EE. Conductor damage curve. k=0.14040 A=20820.0 cmilsConductor Copper (bare) AWG Size 6#6 Copper

Page 11: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

11

Conductor Rating

556 730

336.4 530

4/0 340

2/0 270

1/0 230

#2 180

#4 140

ACSR

Ampacity Ratings

Conductor Rating

2/0 360

1/0 310

#2 230

#4 170

#6 120

Copper

Ampacity Ratings

Conductor Ampacities

Conductor at 25°C ambient taken from the Westinghouse Transmission & Distribution book.

Page 12: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

12

Comparing a 140T fuse versus a

#4 ACSR Damage curve.

The 140T won’t protect the

conductor below about

550 amps where the curves cross.

Conductor Protection Graph

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV#4 ACSR & 140T By Protection

For Aspen File: HORS M15 EXP.olr No.

Comment Date 3/06

1

1. Moscow 515 Kear 140T Kearney 140TTotal clear.

A

A. Conductor damage curve. k=0.08620 A=33100.0 cmilsConductor ACSR AWG Size 4

Page 13: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

13

Transformer Protection using

115 kV Fuses

Page 14: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

14

Transformer Protection using

115 kV Fuses

Used at smaller substations up to 7.5 MVA

transformer due to low cost of protection.

Other advantages are:

- Low maintenance

- Panel house & station battery not required

There are also several disadvantages to

using fuses however which are:

Low interrupting rating from 1,200A (for

some older models) up to 10,000A at 115 kV.

By contrast a circuit switcher can have a rating

of 25KAIC and our breakers have normally

40KAIC.

The fuses we generally use are rated to blow

within 5 minutes at twice their nameplate

rating. Thus, a 65 amp fuse will blow at 130

amps. This compromises the amount of

overload we can carry in an emergency and

still provide good sensitivity for faults.

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 KVROK 451R2 By JDH

For ROK FDR 451, BUS FAULTS: 3LG=3580A, SLG=3782A, L-L=3100A No.

Comment ASPEN FILE: ROK NEW XFMR (2005 BASE).OLR Date 2-13-07

STATION TRANSFORMER PROTECTION

FEEDER VCR PROTECTION

MAXIMUM FEEDER FUSE

1

1. LAT RP4211 50N CO-11 INST TD=1.000CTR=500/5 Pickup=2.A No inst. TP@5=0.048s

2

2. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

3

3. LAT RP4211 50P CO-11 INST TD=1.000CTR=500/5 Pickup=3.5A No inst. TP@5=0.048s

4

4. LAT RP4211 51P CO-11 CO-11 TD=2.000CTR=500/5 Pickup=3.A No inst. TP@5=0.5043s

5

5. LAT RP4211 51N CO-11 CO-11 TD=4.000CTR=500/5 Pickup=2.A No inst. TP@5=1.0192s

6

6. LAT RP4211 FUSE S&C Link 65TTotal clear.

A

A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 7.3 percent.Rockford 13.8kV - ROCKFORD115 115.kV 1 T

Page 15: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

15

The fuse time current characteristic (TCC) is fixed (although you can buy a standard, slow

or very slow speed ratio which are different inverse curves).

The sensitivity to detect lo-side SLG faults isn’t as good as using a relay on a circuit

switcher or breaker. This is because we use DELTA/WYE connected transformers so the

phase current on the 115 kV is reduced by the 3 as opposed to a three phase fault.

Some fuses can be damaged and then blow later at some high load point.

When only one 115 kV fuse blows, it subjects the customer to low distribution voltages.

For example the phase to neutral distribution voltages on two phases on the 13.8 kV become

50% of normal.

No indication of faulted zone (transformer, bus or feeder).

Transformer Protection using 115 kV Fuses - continued

A

B

C

a

b

c

1.0 PU

0.5 PU0.5 PU

Page 16: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

16

Transformer Protection using a Circuit SwitcherShowing Avista’s present standard using Microprocessor relays.

13.8kV 115kV

Page 17: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

17

Transformer Protection using a Circuit SwitcherShowing Avista’s old standard using Electromechanical relays.

Page 18: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

18

Transformer Protection using a Circuit Switcher

Some advantages to this over fuses are:

Higher interrupting.

Relays can be set to operate faster

and with better sensitivity than

fuses.

Three phase operation.

Provide better coordination with

downstream devices.

Some disadvantages would be:

Higher cost.

Higher maintenance.

Requires a substation battery, panel

house and relaying.

Transformer requires CT’s.

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 251 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

LO-SIDE CT'S

MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

2

2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

3

3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

4

4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

5

5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

6

6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

7

7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

8

8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

9

9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

10

10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

11

11. 251 140T FUSE stn S&C Link140TTotal clear.

A

A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

Page 19: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

19

Transformer Protection using a Breaker

This is very similar to using a circuit switcher with a couple of advantages such as:

Higher interrupting – 40kAIC for the one shown below.

Somewhat faster tripping than a circuit switcher (3 cycles vs. 6 – 8 cycles).

Possibly less maintenance than a circuit switcher.

The CT’s would be located on the breaker so it would interrupt faults on the bus section up to

the transformer plus the transformer high side bushings.

Page 20: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

20

SEL Various Relay Overcurrent Curves.

Extremely Inverse – steepest

Very Inverse

Inverse

Moderately Inverse

Short Time Inverse – least steep

The five curves shown here have the same

pickup settings , but different time dial

settings.

These are basically the same as various E-M

relays.

Avista uses mostly extremely inverse on

feeders to match the fuse curves.

Relay Overcurrent Curves

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. EXTREMELY INVERSE SEL-EI TD=15.000CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

2

2. INVERSE SEL-I TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.8558s

3

3. MODERATELY INVERSE SEL-2xx-MI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.324s

4

4. SHORT TIME INVERSE SEL-STI TD=1.000CTR=800/5 Pickup=6.A No inst. TP@5=0.1072s

5 5. VERY INVERSE SEL-VI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.5478s

Page 21: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

21

Time dial

- at what time delay will the relay operate to

trip the breaker

- the larger time dial means more time delay

- also known as “lever” from the

electromechanical relay days

- Instantaneous elements have a “time dial”

of 1 and operate at 0.05 seconds.

- Instantaneous curves are shown as a flat

horizontal line starting at the left at the

pickup value and plotted at 0.05 seconds.

Relay Overcurrent Curves - Pickups & Time Dials

Pickup

- the current at which the relay will operate to trip the breaker.

- also known as “tap” from the electromechanical relay days

-expressed in terms of the ratio of the current transformer (CTR) that the relay is connected to,

- e.g., a relay with a CTR of 120 and a pickup (or tap) of 4 will operate to trip the breaker at 480

amps10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 251 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

LO-SIDE CT'S

MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

2

2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

3

3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

4

4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

5

5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

6

6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

7

7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

8

8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

9

9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

10

10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

11

11. 251 140T FUSE stn S&C Link140TTotal clear.

A

A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

Page 22: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

22

Same Time Dial = 9

Right curve picks up at 960 Amps

Left curve picks up at 320Amps

Relay Overcurrent Curves - Example of Different Pickup & Time Dial Settings

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. EXT INV 1 SEL-EI TD=15.000CTR=800/5 Pickup=6.A No inst. TP@5=4.0718s

2 2. ~EXT INV 1 SEL-EI TD=12.000CTR=800/5 Pickup=6.A No inst. TP@5=3.2574s

3

3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

4

4. ~EXT INV 3 SEL-EI TD=6.000CTR=800/5 Pickup=6.A No inst. TP@5=1.6287s

5

5. ~EXT INV 4 SEL-EI TD=2.000CTR=800/5 Pickup=6.A No inst. TP@5=0.5429s

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. EXT INV 1 SEL-EI TD=9.000CTR=800/5 Pickup=6.A No inst. TP@5=2.4431s

2

2. ~EXT INV 1 SEL-EI TD=9.000CTR=800/5 Pickup=5.A No inst. TP@5=2.4431s

3

3. ~EXT INV 2 SEL-EI TD=9.000CTR=800/5 Pickup=4.A No inst. TP@5=2.4431s

4

4. ~EXT INV 3 SEL-EI TD=9.000CTR=800/5 Pickup=3.A No inst. TP@5=2.4431s

5

5. ~EXT INV 4 SEL-EI TD=9.000CTR=800/5 Pickup=2.A No inst. TP@5=2.4431s

Same Pickup = 960 Amps

Top curve Time Dial = 15

Bottom curve Time Dial = 2

Page 23: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

23

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVINT 12F1 By JDH

For Indian Trail feeder 12F1 in INT 2007base.olr No.

Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A Date 1-29-08

TRANSFORMER PROTECTION

STATION VCB 12F1 PROTECTION

1 1. INT A-742 51P 351 SEL-VI TD=10.000CTR=600/5 Pickup=0.8A No inst. TP@5=2.5797s H=8.33

2

2. INT 12F1 51P 351S SEL-VI TD=1.800CTR=800/5 Pickup=3.A No inst. TP@5=0.4643s

3

3. INT 12F1 51G 351S SEL-VI TD=0.900CTR=800/5 Pickup=3.A No inst. TP@5=0.2322s

4

4. INT 12F1 51Q 351S SEL-VI TD=0.500CTR=800/5 Pickup=3.A No inst. TP@5=0.129s

5 5. INT A-742 51G 351 SEL-VI TD=5.000CTR=600/5 Pickup=0.8A No inst. TP@5=1.2898s H=8.33

6

6. INT A-742 51Q 351 SEL-VI TD=3.000CTR=600/5 Pickup=0.8A No inst. TP@5=0.7739s H=8.33

A

A. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.4 percent.INDIAN TRAIL 12/16/20 MVA XFMR

B

B. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AAC556 kCMil AAC

Microprocessor relays have different

types of curves based on the type of

fault current being measured:

51P – phase time overcurrent

51N or 51G – ground time overcurrent

51Q – negative sequence time overcurrent

Transformer relay curves

Feeder relay curves

51P – phase time overcurrent

51N or 51G – ground time overcurrent

51Q – negative sequence time overcurrent

This brings us to a brief discussion of:

Page 24: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

24

Symmetrical Components

Symmetrical Components for Power Systems Engineering,

J. Lewis Blackburn,

There are three sets of independent components in a three-phase

system: positive, negative and zero for both current and voltage.

Positive sequence voltages (Figure 1) are supplied by generators

within the system and are always present. A second set of balanced

phasors are also equal in magnitude and displaced 120 degrees

apart, but display a counter-clockwise rotation sequence of A-C-B

(Figure 2), which represents a negative sequence. The final set of

balanced phasors is equal in magnitude and in phase with each

other, however since there is no rotation sequence (Figure 3) this is

known as a zero sequence.

Page 25: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

25

Symmetrical Components

Three phase (3LG) fault - Positive sequence currents – for setting phase elements in relays. Phase -Phase (L-L) fault - Negative sequence currents – for setting negative sequence elements in relays.Single phase (1LG or SLG) fault - Zero sequence currents – for setting ground elements in relays.

Symmetrical Components Notation:

Positive Sequence current = I + = I1

Negative Sequence current = I - = I2

Zero Sequence current = I 0 = I0

Phase Current notation:

IA – High side Amps

Ia – Low side Amps

8.33= 115/13.8 = transformer Voltage (turns) ratioPhasor diagram from Fault-study Software.

Examples of three 13.8kV faults showing the current distribution through a Delta-Wye high-lead-low transformer bank :

Page 26: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

26

Symmetrical Components – Positive Sequence, 3LG 13.8 kV Fault

You have only positive sequence voltage and current since the system is balanced.

A

B

C

a

b

c

RR

IA = 619 -88 Ia = 5158 -118

IB = 619 152 Ib = 5158 122

IC = 619 32 Ic = 5158 2

Phase current = Sequence current

That is; Ia = I+.

Phase currents and voltages for the 115kV side.

IA = Ia / 8.33 = 5158A / 8.33

IA = 619A

Page 27: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

27

Symmetrical Components – Negative Sequence, L-L 13.8 kV Fault

115kV side sequence currents and voltages

13.8kV side sequence currents and voltages

A

B

C

a

b

c

RR

IA = 309 -28 Ia = 0 0

IB = 619 152 Ib = 4467 152

IC = 309 -28 Ic = 4467 -28

3LG 13.8kV fault = 5158A,

Ib=Ic=4467 A, 4467/5158 = 86.6%=3/2

IB3LG = IBLL = 619A

IA & IC = IB or Ia & Ic = Ib

I2 = the phase current/3 = 4467/3 = 2579

Digital relays 50Q/51Q elements set using 3I2.

3I2 = Ib x 3 = 4467 x 1.732 = 7737,

Page 28: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

28

Symmetrical Components – Zero Sequence, 1LG 13.8 kV Fault

115kV side sequence currents and voltages

A

B

C

a

b

c

RR

3I0 is the sum of the 3 phase currents and since Ib & Ic

= 0, then 3I0 = Ia. This means the phase and ground

overcurrent relays on the feeder breaker see the same

amount of current.

5346/(8.33*3) = 370 amps. So the high side phase

current is the 3 less as compared to the 3Ø fault.

Digital relays ground elements set using 3I0.13.8kV side sequence currents and voltages

IA = 370 -118 Ia=3I0=5346 -118

IB = 0 0 Ib = 0 0

IC = 370 62 Ic = 0 0

Ia = 3Va/(Z1 + Z2 + Z0)

Page 29: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

29

Symmetrical Components - Summary of 13.8 kV Faults

3LG – positive sequence current

SLG – zero sequence current

L-L – negative sequence current

IA = 619 Ia = 5158

IB = 619 Ib = 5158

IC = 619 Ic = 5158

5158 / 8.33 = 619 Ia = 5158 = I1

5346/(8.33x3) = 370 Ia = 5346 = 3I0

If you have a Delta-Wye transformer bank, and you know the voltage ratio and secondary phase

current values for 13.8kV 3LG (5158) and SLG (5346) faults, you can find the rest:

IA = 309 Ia = 0

IB = 619 Ib = 4467

IC = 309 Ic = 4467

5158 x 3/2 = 4467 Ib x 3 = 7737 = 3I2

4467/(8.33x 3) = 309

309 x 2 = 619

IA = 370 Ia=5346

IB = 0 Ib = 0

IC = 370 Ic = 0

Page 30: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

30

Symmetrical Components - Summary of 13.8 kV Faults

You’ve heard of a Line-to-Line fault, how about an “Antler-to-Antler” fault?

Page 31: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

31

Electromechanical Relays

used on Distribution Feeders

Avista’s standard distribution relay

package (until the mid-1990’s) included

the following:

3 phase 50/51 CO-11 relays,

1 reclosing relay

1 ground 50/51 CO-11 relay

.

Page 32: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

32

Objectives:

- Protect the feeder conductor

- Detect as low a fault current as

possible (PU = 50% EOL fault amps)

- Other than 51P, set pickup and time

dial as low as possible and still have

minimum Coordinating Time Interval

(CTI) to next device. CTI is minimum

time between operation of adjacent

devices.

- Carry normal maximum load (phase

overcurrent only).

- Pickup the feeder in a cold load

condition ( 2 times maximum normal

load) or pickup ½ of the next feeder

load·

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 KV By

For No.

Comment Date

TRANSFORMER PROTECTION

FEEDER VCB PROTECTION

MAXIMUM FEEDER FUSE

1

1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

2

2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

3

3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

4

4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

5

5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

6

6. LAT421 FUSE S&C Link100TTotal clear.

A

A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

B

B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

Electromechanical Relays

used on Distribution Feeders

Page 33: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

33

13 kV BUS

MIN FAULT3LG = 2000 A1LG = 1000 A

FEEDER SETTINGS51P = 2000 / 2 = 1000 A51N = 1000 / 2 = 500 A

Electromechanical Relays

used on Distribution Feeders

Pickup setting criteria of 2/1 ratio of “end of line” fault duty / pickup

- ensures that the relay will “see” the fault and operate when needed.

Page 34: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

34

13 kV BUS

FAULT at MIDLINE3LG = 2000 A1LG = 1000 A

FEEDER SETTINGS51P = 2000 / 2 = 1000 A51N = 1000 / 2 = 500 A

MIN FAULT at END OF LINE3LG = 1000 A1LG = 500 A

MIDLINE SETTINGS51P = 1000 / 2 = 500 A51N = 500 / 2 = 250 A

Electromechanical Relays

used on Distribution Feeders

Page 35: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

35

Electromechanical Relays

used on Distribution Feeders

13 kV BUS

500A FEEDER SETTINGS51P = 960 A51N = 480 A

SECTION LOAD = 500 A

Page 36: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

36

Electromechanical Relays

used on Distribution Feeders

13 kV BUS

500A FEEDER SETTINGS51P = 960 A51N = 480 A N.O.

SECTION LOAD = 250 A

SECTION LOAD = 500 A

SECTION LOAD = 250 A

Page 37: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

37

Most overhead feeders also use reclosing capability to automatically re-energize the feeder

for temporary faults. Most distribution reclosing relays have the capability of providing up to three

or four recloses.

-- Avista uses either one fast or one fast and one time delayed reclose to lockout.

The reclosing relay also provides a reset time generally adjustable from about 10 seconds to

three minutes. This means if we run through the reclosing sequence and trip again within the reset

time, the reclosing relay will lockout and the breaker will have to be closed by manual means. The

time to reset from the lockout position is 3 to 6 seconds for EM reclosing relays.

-- Avista uses reset times ranging from 90 to 180 seconds.

Lockout only for faults within the protected zone. That is; won’t lockout for faults beyond

fuses, line reclosers etc.

Most distribution reclosing relays also have the capability of blocking instantaneous tripping.

-- Avista normally blocks the INST tripping after the first trip to provide for a Fuse Protecting

Scheme.

Electromechanical Relays

used on Distribution Feeders

Reclosing

Page 38: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

38

13 kV BUS

RECLOSING SEQUENCE

Closed

Open

0.5" 12" LOCKOUT

RESET = 120"

(INST Blocked during Reset Time)

Electromechanical Relays

used on Distribution Feeders

Reclosing – Sequence shown for a permanent fault

Page 39: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

39

Distribution Fusing – Fuse Protection/Saving Scheme

Fault on fused lateral on an overhead feeder:

- Station or midline 51 element back up fuse.

- Station or midline 50 element protects fuse.

During fault:

Trip and clear the fault at the station (or line

recloser) by the instantaneous trip before the fuse

is damaged for a lateral fault.

Reclose the breaker. That way if the fault were

temporary the feeder is completely re-energized

and back to normal.

During the reclose the reclosing relay has to

block the instantaneous trip from tripping again.

That way, if the fault still exists you force the

time delay trip and the fuse will blow before you

trip the feeder again thus isolating the fault and

re-energizing most of the customers.

Of course if the fault were on the main trunk

the breaker will trip to lockout.

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVM15 515 51N to 140T By Protection

For Aspen File: HORS M15 EXP.olr No.

Comment Date 3/06

STATION FEEDER RELAYING

MAXIMUM FEEDER FUSE

1

1. M15 515 GND TIME CO-11 TD=4.000CTR=160 Pickup=3.A No inst. TP@5=1.0192s

2

2. Moscow 515 Kear 140T Kearney 140TTotal clear.

3

3. M15 50N CO-11 INST TD=1.000CTR=160 Pickup=3.A No inst. TP@5=0.048s

Page 40: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

40

Shows the maximum fault current for which

S&C type T fuses can still be protected by a

recloser/breaker instantaneous trip for

temporary faults (minimum melt curve at 0.1

seconds):

6T – 120 amps

8T – 160 amps

10T – 225 amps

12T – 300 amps

15T – 390 amps

20T – 500 amps

25T – 640 amps

30T – 800 amps

40T – 1040 amps

50T – 1300 amps

65T – 1650 amps

80T – 2050 amps

100T – 2650 amps

140T – 3500 amps

200T – 5500 amps

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. BR1 S&C 140T S&C Link140TMinimum melt.

2

2. ENDTAP S&C 40T S&C Link 40TMinimum melt.

3

3. M15 515 S&C 80T S&C Link 80TMinimum melt.

Distribution Fusing – Fuse Protection for Temporary Faults

Page 41: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

41

NOTE: These values were taken from the S&C data bulletin 350-170 of March 28, 1988 based on no

preloading and then preloading of the source side fuse link. Preloading is defined as the source side

fuse carrying load amps equal to it’s rating prior to the fault. This means there was prior heating of

that fuse so it doesn’t take as long to blow for a given fault.10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. T FUSE S&C Link100TMinimum melt.

2

2. 251 140T FUSE stn S&C Link140TTotal clear.

Distribution Fusing – Fuse to Fuse Coordination

Page 42: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

42

Typical continuous and 8 hour emergency rating of the S&C T rated silver fuse links plus the 140T

and 200T.

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

T IME-CURRENT CURVES @ Voltage By

For No.

Comment Date

1

1. BR1 S&C 140T S&C Link140TMinimum melt.

Distribution Fusing – S&C T-Fuse Current Ratings

General Rule: Fuse Blows at 2X Rating in 5 Minutes

Page 43: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

43

Typical Coordinating Time Intervals (CTI)

that Avista generally uses between protective

devices.

Other utilities may use different times.

DEVICES: CTI

(Sec.)

Relay – Fuse Total Clear 0.2

Relay – Series Trip Recloser 0.4

Relay – Relayed Line Recloser 0.3

Lo Side Xfmr Relay – Feeder Relay 0.4

Hi Side Xfmr Relay – Feeder Relay 0.4

Xfmr Fuse Min Melt – Feeder Relay 0.4

Coordinating Time Intervals

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 252 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

MIDLINE OCR

MAXIMUM MIDLINE FUSE

Fault I=5665.9 A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

2

2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

4

4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

5

5f

5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

6

6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

A

A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

Page 44: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

44

Typical Coordinating Time Intervals (CTI)

that Avista generally uses between protective

devices.

Other utilities may use different times.

DEVICES: CTI

(Sec.)

Relay – Fuse Total Clear 0.2

Relay – Series Trip Recloser 0.4

Relay – Relayed Line Recloser 0.3

Lo Side Xfmr Relay – Feeder Relay 0.4

Hi Side Xfmr Relay – Feeder Relay 0.4

Xfmr Fuse Min Melt – Feeder Relay 0.4

Coordinating Time Intervals

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVHORS 2010 By JDH

For Idaho Rd Feeder 252 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 252 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

MIDLINE OCR

MAXIMUM MIDLINE FUSE

Fault I=5665.9 A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096sIa= 679.8A (5.7 sec A) T= 0.78s H=8.33

2

2. IDR 252 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072sIa= 5665.9A (35.4 sec A) T= 0.30s

3. IDR 252 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s3Io= 0.0A (0.0 sec A) T=9999s

4

4. 252 140T FUSE stn S&C Link140TTotal clear.Ia= 5665.9A T= 0.09s

5

5f

5. Phase unit of recloser MID LINE OCR Fast: ME-341-B Mult=0.2 Slow: ME-305-A Add=1000. Ia= 5665.9A T(Fast)= 0.03s

6

6. T FUSE S&C Link 50TMinimum melt.Ia= 5665.9A T= 0.01s

A

A. Conductor damage curve. k=0.06710 A=556000.0 cmilsConductor AACFEEDER 252 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

FAULT DESCRIPTION:Bus Fault on: 0 IDR 252 13.8 kV 3LG

Page 45: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVRAT 231 MID C390R By JDH

For Huetter feeder 142 (2008) Rat feeder 231 (2009+) Midline Recloser C390R No.

Comment Saved in: HUE142-RAT231 MID C390R 2007base.olr Date 2-25-08

HUETTER FDR 142 PROTECTION

RATHDRUM FDR 231 PROTECTION

HUE 142 MID C270R PROTECTION

MIDLINE 390R PROTECTION

CALLED "HUE 142 LINE" IN POWERBASE

RECLOSE IS 1SEC, 12SEC, LO, 120 SEC RESET

RECLOSE IS 1SEC, 12 SEC, LO, 180 SEC RESET

LARGEST DOWNSTREAM FUSE FROM 390R MIDLINE

1

1. C390R MID 51P CO-9 CO-9 TD=2.500

CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s

2

2. C390R MID 50P CO-9 INST TD=1.000

CTR=300/5 Pickup=6.A No inst. TP@5=0.048s

3 3. C390R MID 50N CO-9 INST TD=1.000

CTR=300/5 Pickup=5.A No inst. TP@5=0.048s

4

4. C390R MID 51N CO-9 CO-9 TD=2.500

CTR=300/5 Pickup=5.A No inst. TP@5=0.6037s

5

5. HUE 142 50P 251 INST TD=1.000

CTR=160 Pickup=7.A No inst. TP@5=0.048s

6

6. HUE 142 51P 251 SEL-EI TD=1.500

CTR=160 Pickup=6.A No inst. TP@5=0.4072s

7

7. HUE ML C270R 50P INST TD=1.000

CTR=400/5 Pickup=8.1A No inst. TP@5=0.048s

8

8. HUE ML C270R 51P CO-11 TD=1.500

CTR=400/5 Pickup=7.A No inst. TP@5=0.3766s

9

9. HUE 142 50N 251 INST TD=1.000

CTR=160 Pickup=3.A No inst. TP@5=0.048s

10

10. HUE 142 51N 251 SEL-EI TD=4.000

CTR=160 Pickup=3.A No inst. TP@5=1.0858s

11

11. HUE 142 51Q 251 SEL-EI TD=4.000

CTR=160 Pickup=5.2A No inst. TP@5=1.0858s

12

12. HUE ML C270R 50N INST TD=1.000

CTR=400/5 Pickup=3.A No inst. TP@5=0.048s

13

13. HUE ML C270R 51N CO-11 TD=7.000

CTR=400/5 Pickup=3.A No inst. TP@5=1.8052s

14

14. RAT 231 50N CO-11 INST TD=1.000

CTR=800/5 Pickup=3.A No inst. TP@5=0.048s15

15. RAT 231 51N CO-11 CO-11 TD=5.000

CTR=800/5 Pickup=3.A No inst. TP@5=1.3192s

16

16. RAT 231 50P CO-11 INST TD=1.000

CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

17

17. HUE 142 FUSE S&C Link 65T

Total clear.

18

18. RAT 231 FUSE S&C Link100T

Total clear.

19

19. RAT 231 51P CO-11 CO-11 TD=1.800

CTR=800/5 Pickup=6.A No inst. TP@5=0.4533s

A

A. Conductor damage curve. k=0.08620 A=133100.0 cmils

Conductor ACSR AWG Size 2/0

MIDLINE C390 FED FROM RAT 231 - MINIMUM CONDUCTOR TO PROTECT

B

B. Conductor damage curve. k=0.06710 A=556000.0 cmils

Conductor AAC

MIDLINE C390 FED FROM HUE 142 - MINIMUM CONDUCTOR TO PROTECT

45

Typical Coordinating Time Intervals (CTI)

that Avista generally uses between protective

devices.

Other utilities may use different times.

DEVICES: CTI

(Sec.)

Relay – Fuse Total Clear 0.2

Relay – Series Trip Recloser 0.4

Relay – Relayed Line Recloser 0.3

Lo Side Xfmr Relay – Feeder Relay 0.4

Hi Side Xfmr Relay – Feeder Relay 0.4

Xfmr Fuse Min Melt – Feeder Relay 0.4

Coordinating Time Intervals

Page 46: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVIDR FEEDER 251 By JDH

For Idaho Rd Feeder 251 in Idaho Rd PHASE 1 2007base.olr No.

Comment At Sub: 3LG=5667A, SLG=5863A, L-L=4909A Date 11-25-2008

TRANSFORMER PROTECTION

STATION VCB 251 PROTECTION

MAXIMUM FEEDER FUSE

HI-SIDE CT'S

LO-SIDE CT'S

MINIMUM FAULT TO DETECT:3LG=2460A, SLG=1833A, L-L=2130A

1

1. IDR A-777 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

2

2. IDR A-777 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

3

3. IDR A-777 51N 351 SEL-EI TD=5.700CTR=1200/5 Pickup=3.A No inst. TP@5=1.5473s

4

4. IDR A-777 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

5

5. IDR A-777 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

6

6. IDR 251 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

7

7. IDR 251 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

8

8. IDR 251 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

9

9. IDR 251 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

10

10. IDR 251 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

11

11. 251 140T FUSE stn S&C Link140TTotal clear.

A

A. Conductor damage curve. k=0.08620 A=133100.0 cmilsConductor ACSR AWG Size 2/0FEEDER 251 SMALLEST CONDUCTOR TO PROTECT

B

B. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.2 percent.IDAHO RD 12/16/20 MVA XFMR

46

Typical Coordinating Time Intervals (CTI)

that Avista generally uses between protective

devices.

Other utilities may use different times.

DEVICES: CTI

(Sec.)

Relay – Fuse Total Clear 0.2

Relay – Series Trip Recloser 0.4

Relay – Relayed Line Recloser 0.3

Lo Side Xfmr Relay – Feeder Relay 0.4

Hi Side Xfmr Relay – Feeder Relay 0.4

Xfmr Fuse Min Melt – Feeder Relay 0.4

Coordinating Time Intervals

Page 47: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 KV By

For No.

Comment Date

TRANSFORMER PROTECTION

FEEDER VCB PROTECTION

MAXIMUM FEEDER FUSE

1

1. SMD-2B 65E VERY SLOW 176-19-065Minimum melt. H=8.33

2

2. LAT421 50P CO-9 INST TD=1.000CTR=600/5 Pickup=4.6A No inst. TP@5=0.048s

3

3. LAT421 51P CO-9 CO-9 TD=1.900CTR=600/5 Pickup=4.A No inst. TP@5=0.4618s

4

4. LAT421 50N CO-9 INST TD=1.000CTR=600/5 Pickup=3.A No inst. TP@5=0.048s

5

5. LAT421 51N CO-9 CO-9 TD=3.000CTR=600/5 Pickup=3.A No inst. TP@5=0.7228s

6

6. LAT421 FUSE S&C Link100TTotal clear.

A

A. Transf. damage curve. 7.50 MVA. Category 3Base I=313.78 A. Z= 6.9 percent.Latah Jct 13.8kV - LATAHJCT115 115.kV T

B

B. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 1/0

47

Typical Coordinating Time Intervals (CTI)

that Avista generally uses between protective

devices.

Other utilities may use different times.

DEVICES: CTI

(Sec.)

Relay – Fuse Total Clear 0.2

Relay – Series Trip Recloser 0.4

Relay – Relayed Line Recloser 0.3

Lo Side Xfmr Relay – Feeder Relay 0.4

Hi Side Xfmr Relay – Feeder Relay 0.4

Xfmr Fuse Min Melt – Feeder Relay 0.4

Coordinating Time Intervals

Page 48: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

48

Coordinating Time Intervals

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

For M15 A-172 CS with fdr 515 with Kearney 140T Fuse No.

Comment Three Phase Fault Date 12/12/05

1

1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 5158.1A T= 0.10s

2

2. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5158.1A (32.2 sec A) T= 0.33s

3

3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 3LG

3LG Fault Coordination

Example:

Top – Ckt Swr w/ Phase E-M relay

----- 0.4 sec. ------

Middle - E-M Phase relay for a 500

Amp Feeder

----- 0.2 sec. ------

Bottom – 140T Feeder Fuse (Total

Clear)

Page 49: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

49

Coordinating Time Intervals

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

For Moscow CS with fdr 515 with 140T fuses No.

Comment Single Line to Ground Fault Date 12/12/05

1

1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 5346.4A T= 0.09s

2

2. M15 515 GND TIME CO-11 TD=4.000CTR=160 Pickup=3.A No inst. TP@5=1.0192sI= 5346.5A (33.4 sec A) T= 0.29s

3

3. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 5346.4A (33.4 sec A) T= 0.31s

4 4. M15 A-172 GND TIME CO-11 TD=4.000CTR=240 Pickup=4.A No inst. TP@5=1.0192sI= 5346.5A (22.3 sec A) T= 0.83s

FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L 1LG Type=A

SLG Fault Coordination

Example:

Top – Ckt Swr w/ E-M Phase relay

----- 0.4 sec. ------

Middle - E-M relays (Phase &

Ground) for a 500 Amp Feeder

----- 0.2 sec. ------

Bottom – 140T Feeder Fuse (Total

Clear)

Page 50: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

50

Coordinating Time Intervals

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

2

3

45

7

10

20

30

4050

70

100

200

300

400500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kV By DLH

For Moscow CS A-172 with fdr 515 with 140T Fuse No.

Comment Line to Line Fault Date

1

1. Moscow 515 Kear 140T Kearney 140TMinimum melt.I= 4467.0A T= 0.12s

2

2. M15-515 Phase Time CO-11 TD=1.500CTR=160 Pickup=6.A No inst. TP@5=0.3766sI= 4467.0A (27.9 sec A) T= 0.43s

3

3. M15 A-172 Phase CO- 9 TD=1.500CTR=120 Pickup=2.A Inst=1200A TP@5=0.3605sI= 619.0A (5.2 sec A) T= 1.03s H=8.33

FAULT DESCRIPTION:Close-In Fault on: 0 MoscowCity#2 13.8kV - 0 BUS1 TAP 13.8kV 1L LL Type=B-C

L-L Fault Coordination

Example:

Top – Ckt Swr w/ E-M relay

----- 0.4 sec. ------

Middle - E-M (Phase) relay for a 500

Amp Feeder

----- 0.2 sec. ------

Bottom – 140T Feeder Fuse (Total

Clear)

Page 51: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

51

The Final Product10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7

10 2 3 4 5 7 100 2 3 4 5 7 1000 2 3 4 5 7 10000 2 3 4 5 7CURRENT (A)

SECONDS

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

2

3

4

5

7

10

20

30

40

50

70

100

200

300

400

500

700

1000

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

.01

.02

.03

.04

.05

.07

.1

.2

.3

.4

.5

.7

1

TIME-CURRENT CURVES @ Voltage 13.8 kVINT 12F2 & MID 466R By JDH

For Indian Trail feeder 12F2 and 12F2 Midline 466R in INT 2007base.olr No.

Comment AT SUB: 3LG= 5719A, LL=4951A, SLG= 5880A Date 1-29-08

TRANSFORMER PROTECTION

STATION VCB 12F2 PROTECTION

EAST BRANCH - FEEDER MAXIMUM FUSE

FAULT DUTY AT 140T - WHEN FED FROM NORTH (N.O. PT)

12F2 MIDLINE 466R PROTECTION

WEST OR NORTH BRANCH - FEEDER MAXIMUM FUSE

FAULT DUTY AT 150E; 3LG=2318, LL=2008, SLG=1684

3LG=1932, LL=1673, SLG=1388

FAULT DUTY AT 140T - WHEN FED FROM WEST MID 466R 3LG=2093, LL=1813, SLG=1520

9&15

11&4

1

1. INT A-742 51P 351 SEL-VI TD=1.200CTR=600/5 Pickup=2.A No inst. TP@5=0.3096s H=8.33

2

2. INT A-742 51G 351 SEL-VI TD=1.000CTR=600/5 Pickup=1.A No inst. TP@5=0.258s H=8.33

3

3. INT A-742 51N 351 SEL-EI TD=5.600CTR=1200/5 Pickup=3.A No inst. TP@5=1.5201s

4

4. INT A-742 51Q 351 SEL-EI TD=4.200CTR=600/5 Pickup=1.3A No inst. TP@5=1.1401s H=8.33

5

5. INT F2 150E FUSE SMU-20_150ETotal clear.

6

6. INT 12F2 50P 351S INST TD=1.000CTR=800/5 Pickup=7.A No inst. TP@5=0.048s

7

7. INT 12F2 51P 351S SEL-EI TD=1.500CTR=800/5 Pickup=6.A No inst. TP@5=0.4072s

8

8. INT 12F2 50G 351S INST TD=1.000CTR=800/5 Pickup=3.A No inst. TP@5=0.048s

9

9. INT 12F2 51G 351S SEL-EI TD=3.900CTR=800/5 Pickup=3.A No inst. TP@5=1.0587s

10

10. INT 12F2 51Q 351S SEL-EI TD=3.500CTR=800/5 Pickup=5.2A No inst. TP@5=0.9501s

11

11. INT A-742 51Q 587 W2 SEL-EI TD=4.300CTR=1200/5 Pickup=5.4A No inst. TP@5=1.1672s

12

12. F2 MID 466R 50P 351R INST TD=1.000CTR=500/1 Pickup=1.68A No inst. TP@5=0.048s

13

13. F2 MID 466R 51P 351R SEL-EI TD=2.300CTR=500/1 Pickup=1.44A No inst. TP@5=0.6243s

14

14. F2 MID 466R 50G 351R INST TD=1.000CTR=500/1 Pickup=0.89A No inst. TP@5=0.048s

15

15. F2 MID 466R 51G 351R SEL-EI TD=4.200CTR=500/1 Pickup=0.89A No inst. TP@5=1.1401s

16

16. F2 MID 466R 51Q 351R SEL-EI TD=3.800CTR=500/1 Pickup=1.54A No inst. TP@5=1.0315s

17

17. INT F2 140T FUSE stn S&C Link140TTotal clear.

A

A. Transf. damage curve. 12.00 MVA. Category 3Base I=502.00 A. Z= 8.4 percent.INDIAN TRAIL 12/16/20 MVA XFMR

B

B. Conductor damage curve. k=0.14040 A=52630.0 cmilsConductor Copper (bare) AWG Size 2NORTH BRANCH SMALLEST TRUNK CONDUCTOR

C

C. Conductor damage curve. k=0.04704 A=350000.0 cmilsCable XLPE 90C/250CEAST BRANCH SMALLEST TRUNK CONDUCTOR - 350 CN15

D

D. Conductor damage curve. k=0.08620 A=105500.0 cmilsConductor ACSR AWG Size 2/0WEST BRANCH SMALLEST TRUNK CONDUCTOR

An example of a completed 13.8kV

Feeder Coordination Study with 20

Time-Current Curves representing:

Instantaneous & Time-Delay Curves

for the:

- Transformer high side protection,

- Transformer low side protection,

- Station feeder breaker protection,

- Midline feeder breaker protection.

Two Fuses

Transformer Damage Curve

Three Conductor Damage Curves

Page 52: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

52

Criteria (for outdoor bus arrangement, not switchgear)

Protect the Transformer from thermal damage

- Refer to Damage Curves

Backup feeder protection (as much as possible)

- Sensitivity is limited because load is higher

Coordinate with downstream devices (feeder relays)

Carry normal maximum load (phase only)

Pick up Cold Load after outages

Distribution Transformer Electromechanical Relays

Page 53: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

53

Relays:

3 High Side Phase Overcurrent (with time and instantaneous elements)

1 Low Side Ground Overcurrent (with time and instantaneous elements)

Sudden Pressure Relay

Distribution Transformer

Electromechanical Relays - Setting Criteria

Page 54: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

54

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Advantages:

More precise TAP settings

More Relay Elements

Programmable Logic / Buttons

Lower burden to CT

Event Reports!!!!!!!!!

Communications

Coordinate with like elements

(faster)

More Settings

Microprocessor Relay

Page 55: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

55

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Elements We Set:

51P

50P

50P2 (FTB)

51G

50G (115kV)

51N (13.8kV)

50N1 (FTB)

FTB = Fast Trip Block (feeder relays must be Microprocessor)

Page 56: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

56

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Fast Trip Blocking

Fault

Page 57: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

57

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Fast Trip Blocking

Fault

Page 58: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

Distribution Transformer

Relay Setting Criteria

Electromechanical Relays

51P Pickup (time overcurrent)

Don’t trip for load or cold load pickup (use

2.4 * highest MVA rating)

Ends up being higher than the feeder phase

element pickup

Example: 12/16/20 MVA unit would use

2.4*20*5 = 240 amps (1940A low side)

51P Time Lever (time dial)

Coordinate with feeder relays for

maximum fault (close in feeder fault)

CTI is 0.4 seconds

Worst coordination case: Ø-Ø on low side

(discrepancy due to delta/wye conn.)

Multiple feeder load can make the

transformer relay operate faster

50P Pickup (instantaneous overcurrent)

Must not trip for feeder faults set at

170% of low side bus fault

Accounts for DC offset

Microprocessor Relays

51P - Phase Time Overcurrent Pickup

Set to 240% of nameplate (same as EM

relay)

51P - Time Dial

Set to coordinate with feeder’s fastest

element for each fault

CTI is still 0.4 seconds

50P1 – Phase instantaneous #1 Pickup

Direct Trip

Set to 130% of max 13.8 kV fault (vs.

170% with EM relay)

50P2 – Phase instantaneous pickup for Fast Trip Block

scheme

Set above transformer inrush

4 Cycle time delay

Blocked if any feeder overcurrent elements are

picked up

58

Phase Overcurrent Settings – Current measured on 115kV side

Page 59: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

Electromechanical Relays

51N – Ground Time Overcurrent Pickup

Set to same sensitivity as feeder

phase relay (in case the feeder ground

relay is failed)

This setting is higher than the feeder

ground, so we lose some sensitivity

for backup

51N - Time Lever (time dial)

Coordinate with feeder relays for

ground faults

CTI is 0.4 seconds

50N - Pickup (instantaneous overcurrent)

DO NOT USE!!!!

Microprocessor Relays

51N - Ground Time Overcurrent Pickup

Set slightly higher than feeder

ground pickup (about 1.3 times)

51N - Time Dial

Set to coordinate with feeder

ground

CTI is 0.4 seconds

50N1 – Ground Instantaneous for Fast Trip

Block

Set slightly above the feeder

ground instantaneous pickup

Time Delay by 4 cycles

Blocked if Feeder overcurrent

elements are picked up

59

Phase Overcurrent Settings – Current measured on 13.8kV side

Distribution Transformer

Relay Setting Criteria

Page 60: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

60

Transformer Ground Overcurrent Settings - Current calculated from 115kV CTs

51G - Ground Time Overcurrent Pickup

Set very low (will not see low side ground faults due to transformer

connection). Usually 120 Amps.

51GTime Dial

Set very low

50G1 – Ground Instantaneous #1 Pickup

Set very low. Usually 120 Amps.

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Symmetrical

Components!

Page 61: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

61

Inrush – The current seen when

energizing a transformer.

Need to account for inrush when using

instantaneous elements (regular or FTB).

Inrush can be approximately 8 times the

nameplate of a transformer.

Note that the microprocessor relay only responds to the 60 HZ fundamental and that this

fundamental portion of inrush current is 60% of the total. So to calculate a setting, we could use

the 8 times rule of thumb along with the 60% value. For a 12/16/20 MVA transformer, the

expected inrush would be 8*12*5*0.6 = 288 amps. We set a little above this number (360 Amps).

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Page 62: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

62

Transformer inrush UNFILTERED

current. The peak current is about 1200

amps.

Transformer inrush FILTERED current

(filtered by digital filters to show

basically only 60 HZ).

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Page 63: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

63

Transformer inrush UNFILTERED

current. The peak current is about 1200

amps.

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Page 64: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

64

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Microprocessor Feeder Relay

Overcurrent

Reclosing

Fast Trip Block Output

Breaker Failure Output

Elements We Set:

51P

50P

51G

50G

51Q

Page 65: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Feeder Phase Overcurrent Settings

51P - Phase Time Overcurrent Pickup

Set above load and cold load

(960 Amps for 500 Amp

feeder)

Same as EM pickup

51P - Time Dial

Same as EM relay (coordinate

with downstream protection

with CTI)

Select a curve

50P – Phase instantaneous Pickup

Set the same as the 51P pickup

(960 Amps)

Feeder Ground Overcurrent Settings

51G - Phase Time Overcurrent Pickup

Same as EM pickup which is

480 Amps

51G - Time Dial

Same as EM relay (coordinate

with downstream protection)

Select a curve

50G – Phase instantaneous Pickup

Set the same as the 51G

pickup

65

Page 66: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

66

Feeder Ground Overcurrent Settings

51G - Phase Time Overcurrent Pickup

Same as EM pickup which is 480 Amps

51G Time Dial

Same as EM relay (coordinate with downstream protection)

Select a curve

50G – Phase instantaneous Pickup

Set the same as the 51G pickup

Distribution Transformer & Feeder Protection

with Microprocessor Relays

Page 67: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

67

87R1

87OP

87R2

PRI I

PRI I

SEC I

SEC I

EXTERNAL FAULTTHE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN THE SAME DIRECTION AND THENCIRCULATE BACK THROUGH THE CT'S. THEY DO NOTFLOW THROUGH THE OPERATE COIL

CURRENT FLOW THROUGH AN E/M 87 DIFFERENTIAL RELAY FOR AN INTERNAL AND EXTERNAL FAULT

BCT'S

BCT'S

CT POLARITY MARK

Transformer Differential Protection – External Fault

Page 68: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

68

87R1

87OP

87R2

PRI I

PRI I

INTERNAL FAULTTHE SECONDARY CURRENTS FLOW THROUGH BOTHRESTRAINT COILS IN OPPOSITE DIRECTIONS, ADD AND THEN FLOW THROUGH THE OPERATE COIL ANDBACK TO THE RESPECTIVE CT'S

SEC I

SEC I

BCT'S

BCT'S

CT POLARITY MARK

Transformer Differential Protection – Internal Fault

Page 69: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

69

The differential relay is connected to both the high and low side transformer BCT’s.

EM Differential Relay

Since the distribution transformer is connected delta – wye the transformer CT’s

have to be set wye – delta to compensate for the phase shift.

Transformer Differential Protection

Page 70: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

BACK-TO-BACK MIDLINE RECLOSERS COORDINATION

*

Feeder Breaker

Feeder Breaker

Switch

MidlineRecloser

N.C.

70

Page 71: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

BACK-TO-BACK MIDLINE RECLOSERS COORDINATION

*

Feeder Breaker

Feeder Breaker

SwitchMidlineRecloser N.O. Tie

MidlineRecloser

N.C.Fwd

Fwd

71

Page 72: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

BACK-TO-BACK MIDLINE RECLOSERS COORDINATION

*

Feeder Breaker

Feeder Breaker

SwitchMidlineRecloser Closed Tie

MidlineRecloser

N.C.Fwd

Rev

*

72

Page 73: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

BACK-TO-BACK MIDLINE RECLOSERS COORDINATION

*

Feeder Breaker

Feeder Breaker

SwitchMidlineRecloser Closed Tie

MidlineRecloser

T/R/T/R T/R/T-LO

Fwd

Rev

T = Trip

R = Reclose

LO = Lockout

73

Page 74: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

RECLOSER/SWITCH FUNCTIONALITY

Substation

R

R R

R

R

FEEDER 1

FEEDER 2

FWD

FWD

FWD

N.O.

N.O.

Z01R

Z02R

Z03R

74

Page 75: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

RECLOSER/SWITCH FUNCTIONALITY

Substation

R

R R

R

FEEDER 1

FEEDER 2

FWD

FWD

CLOSED

N.O.

Z01R

Z02R

Z03R

Now Z02R is a

switch 75

Page 76: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

76

GRAB YOUR HANDOUT!

MOSCOW FEEDER 515 PROTECTION EXAMPLE

Page 77: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

77

The Scenario

A hydraulic midline recloser on a 13.8kV feeder in Moscow, ID is

being replaced by a newer relayed recloser. The recloser is P584

on feeder 515.

The field engineer would like to replace the recloser in the existing

location.

Protection engineer must review the feeder protection and report

back to the field engineer.

NOTE: Avista designs for a “fuse saving” scheme with one

instantaneous trip. The field engineers decide if they want to

enable or disable the instantaneous tripping.

Page 78: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

78

MOSCOW FEEDER 515 PROTECTION EXAMPLE

• Where do we start the protection design?

1) Gather Information:

• Feeder Rating (expected load)

• Protective devices (Breakers, line reclosers, fuses)

• Fault Duty (at each protective device)

• Conductors to be protected

• Project deadline (tomorrow?)

Page 79: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

79

How do we proceed?

• At each coordination point– Loading

– Coordination• What will coordinate with the downstream device

• Are we above the fuse rating

– Conductor Protection• minimum conductor that can be protected by the feeder settings or

fuse

– Fault Detection• Can we detect the fault by our 2:1 margin

– Fuse Saving for Temporary faults• What can a fuse be protected up to?

Page 80: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

80

Begin at the END

• POINT 8: This is a customers load and we are using 3-250 KVA

transformers to serve the load. The full load of this size of bank is 31.4

amps. The Avista transformer fusing standard says to use a 65T on this

transformer so that’s what we’ll choose.

Page 81: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

81

FUSE - POINT 6B:

What we know:– 3Ø lateral feeding to a 65T at the end

– #4 ACSR conductor

Fuse Selection:– Loading – Assume the load is all downstream of point 8, so a 65T or higher will

still suffice.

– Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

100T or smaller fuse

– Fault Detection - Under the Relay Setting Criteria we want to detect the minimum

line end fault with a 2:1 margin. The SLG is 463 so we calculate the max fuse as

follows:

• 463/2 (2:1 margin) = 231 amps. “T” fuses blow at twice their rating so divide

by 2 again, with a result of 115. Fuse must be 100T or less.

– Coordination – From Table 2, we see that we need an 80T or larger to coordinate

with the downstream 65T fuse (at fault duties < 1400A w/preload)

– Fuse Saving - From Table 1 we see that an 80T fuse can be protected up to 2,050

amps for temporary faults and the 3Ø fault is 1,907 amps so we could choose an

80T or higher from that standpoint

Page 82: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

82

Point 6B - So what fuse size should we use?

Page 83: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

83

POINT 5 – Midline Recloser

• What we know:

– Conductor to protect: #4 ACSR (can carry 140A load)

– Max fuse to coordinate with = 100T (FUTURE per distribution engineer)

– Maximum load (per engineer) = 84A

• Settings Considerations:

– Loading: Cold load would be 84*2 = 168 A, but the conductor can carry 140A max. Size for some

load growth by setting at 2*conductor rating. 300 Amp phase pickup setting.

NOTE: we don’t design settings to protect for overload.

– Conductor Protection: From Table 7, Avista’s 300A feeder settings can protect down to #2 ACSR, so 300A pickup is still acceptable. Review curves to confirm.

– Fault Detection: detect the minimum fault with a 2:1 margin. Here the min fault is at point 6

1. The Ø-Ø fault at point 6 is 0.866*1907 = 1,651 so our margin to detect that fault would be 1651/300

= 5.5:1 so no problem with the 300 amps Ø PU from that standpoint (used Ø-Ø because it’s the

minimum multi phase fault)

2. The SLG at point 6 is 1,492 so we could set the ground up to 1492/2 = 745 amps and still detect the

fault. However, our criteria says to set as low as possible and still coordinate with the largest

downstream device and from above we’re trying to use a 100T. Based on curves, this is 300 amps

(same as phase, which is unusual).

– Coordination: Based on fault study, set the time dial to coordinate with a 100T fuse with 0.2 second

CTI.

– Fuse Saving: The fault duty at the recloser is 3453 3PH and 2762 1LG. An instantaneous trip will

protect the 80T fuse if the fault duty is less than 2050 Amps. Some fuse protection is compromised but

there is nothing we can do about it.

Page 84: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

84

TRUNK FUSE - POINT 3C:

What we know:– #4 ACSR 3Ø trunk

– Load is 84 Amps

– Downstream protection is the midline recloser

Fuse Selection:– Loading – Assume the load is the same as at the midline recloser. We set that at

300A, and a 200T can carry 295 A continuous (Table 3).

– Conductor Protection - From Table 7 we see that #4 ACSR can be protected by a

100T or smaller fuse.

– Fault Detection - Under the Relay Setting Criteria we want to detect the minimum

line end fault with a 2:1 margin.

• SLG at midline is 2762 so even a 200T would provide enough sensitivity.

– Coordination – PROBLEM! We have coordinated the midline with

a 100T, so the upstream fuse must coordinate with that.

– Fuse Saving: As before, some fuse saving is compromised due to higher fault duty.

Page 85: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

85

TRUNK FUSE Point 3C - Solutions?

Page 86: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

86

TRUNK FUSE Point 3C - Solutions?

• Move Recloser

• Re-conductor

Page 87: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

87

FEEDER BREAKER - POINT 1:

What we know:– This is a 500 amp feeder design. The load is 325 amps and cold load 650 per field engineer.

– Downstream protection is either the midline recloser or a 140T fuse.

Settings Considerations: Loading: A standard 500 amp feeder phase pickup setting of 960 A will carry all normal

load and pick up cold load. The ground pickup does not consider load and will be set at

480A.

Conductor Protection : The main trunk is 556 ACSR and from Table 7 a 500 amp feeder

setting of 960 A can protect 1/0 ACSR or higher. Laterals with smaller conductor must be

fused.

Fault Detection:

The Ø-Ø fault at point 5 is 0.866*3453 = 2990 so our margin to detect that fault would

be 2990/960 = 3.1:1

The SLG at point 5 is 2,762 so our margin to detect that fault is: 2762/480 = 5.7:1

Coordination: Use fault study to calculate settings to achieve 0.2 second CTI to fuses and

0.3 second CTI to the recloser.

Fuse Saving – We have decided that a 140T fuse is the maximum fuse we will use on the

feeder even though it can’t be saved by an instantaneous trip at the maximum fault duties.

Page 88: DISTRIBUTION PROTECTION OVERVIEW - etouches...1 DISTRIBUTION PROTECTION OVERVIEW Kevin Damron & Beth Andrews Avista Utilities Presented March 13th, ... 115 kV SYSTEM 13.8 kV BUS 500A,

88

Questions?