Cse & WTe 1000FlaT bed uniT1 or 2 roW oF Fans

air cooLed condensed Unit | drY cooLer Unit

Page 2: Cse & WTe 1000 - Aermec

AIR CONDENSER AND lIquID COOlERSwITH AxIAl fANS• Configuration: 1 or 2 exchangers• 1 or 2 indipendent circuits• 1 or 2 fans row• Wide range of capacity• 72 models available as condenser• 72 models available as dry cooler• Fan diameter: 1000 mm• Number of fans: from 1 to 8• Vertical or horizontal installation

COSTRuCTION CHARACTERISTICSThey are realized with technologies and material which guarantee strength against atmospheric agents.High efficiency finned block heat exchangers realized with copper tubes and alluminium fins. New generation axial fans with 1000 mm diameter both available version AC and EC chosen for minimizing the energy consumption. Standard unit are supplied with cabled fans and electrical box with clamps.

AVAIlAblE fANSBTD: 6-poles with delta connectionBTY: 6-poles with star connectionSTD: 8-poles with delta connectionSTY: 8-poles with star connectionCTB: fan motor EC high powerCTS: fan motor EC low noise level

ACCESSORIESCSE and WTE unit could be equipped with main switch, switchboard, cut phase fan speed regulator (with 1 set point or 2 set point) or inverter with shielded cables, EC controller and temperature sensor, pressure sensor or 0-10V signal.All fan motors could be equipped with switch for each motor. Anti-vibration device are also available for reducing machine’s vibrations and only for dry coolers flanges in oreder to simplify hydraulic connection.

Models

Model

Main switch

Switch for each motor

Switchboard

Phase cut regulatori

Controller ec Inverter

Probe

Anti-vibration

device

CSE-WTE BTD p p p p p p p

CSE-WTE BTY p p p p p p p

CSE-WTE STD p p p p p p p

CSE-WTE STY p p p p p p p

CSE-WTE CTB p p p p p p

CSE-WTE CTS p p p p p p

Cse condenser and WTe dry cooler’s serie meet equipment’s power requirements.They are available from 1 up to 8 fans both version aC and eC

Page 3: Cse & WTe 1000 - Aermec

CApACITYIn air condenser unit power range with refrigerant R134a is from 12.8 up to 252.8 tons (ambient air temperature +77°F, average condensing temperature +104°F according to EN 327)

In air condenseer unit power range with refrigerant R410A is from 14.7 up to 267.7 tons (ambient air temperature +77°F, average condensing temperature +104°F according to EN 327)

In dry cooler unit power range with ethylene glycol 30% is from 11.4 up to 214.7 tons (ambient air temperature +77°F, inlet liquid temperature +104°F outlet liquid temperature +95°F according to EN 1048)

TeChniCal draWinG

Quota a

- CSE/WTE° 101(3/4) (single row of fans)

- CSE/WTE° 102(3/4) (single row of fans)

- CSE/WTE° 103(3/4) (single row of fans)

- CSE/WTE° 104(3/4) (single row of fans)

- CSE/WTE° 106(3/4) (double row of fans)

- CSE/WTE° 108(3/4) (double row of fans)

20 120

220

320

420

520

620

720

820

920

CTS

CTB

STY

STD

BTY

BTD

kW (T.air 25°C - T.cond 40°C)

CSE 1000 R134a

50 150

250

350

450

550

650

750

850

950

CTS

CTB

STY

STD

BTY

BTD

kW (T.air 25°C - T.cond 40°C)

CSE 1000 R410A

20 70 120

170

220

270

320

370

420

470

520

570

620

670

720

770

CTS

CTB

STY

STD

BTY

BTD

kW (T.air 25°C - T.liq 35/40°C)

WTE 1000

90.5 in

181.1 in

271.6 in

362.2 in

271.6 in

362.2 in

Quota A 95.7 in

69.3 in

49.5 in

69.3 in

44.4 in

49.2 in

61.4 in

95.5 in

Page 4: Cse & WTe 1000 - Aermec

AERMECAddress: 1608 Bonhill Road. Mississauga, Ontario, CA L5T 1C7Website: www.aermec.usEmail: [email protected]: 1-800-567-2221US: 1-888-567-2227