BX_ESL_DS_T131460_en

download BX_ESL_DS_T131460_en

of 2

Transcript of BX_ESL_DS_T131460_en

  • 8/12/2019 BX_ESL_DS_T131460_en

    1/2

    Data sheet

    __________________________________________________________________________________________________________________

    Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 131 460 en 1 / 2

    SecuriFire

    Fig. 1 BX-ESL

    BX-ESLEnd switch module eXtended forSecuriLine eXtended

    from edition 20-00007-01-011

    The BX-ESL end switch module eXtended Linecommunicates

    the position of the actuation rod using an internal light barrier.

    The state active/passive is reported to the FAS and indicated

    on the BX-ESL with a LED.

    It meets the specifications of SecuriLine eXtended for operation

    on the ring circuit of the SecuriFire fire detection system.

    Description

    The BX-ESL can be connected to the SecuriLine eXtended ringcircuit of the SecuriFire 1000/2000/3000 fire detection systems.

    Typical applications include sprinkler monitoring and blocking

    equipment.

    The BX-ESL measures the movement of an actuation rod by

    means of an infrared light barrier. This realises the function as

    limit switch.

    On the front, a multi-colour LED can indicate an end position of

    the rod in either red or yellow.

    Addressing and assigning BX-ESL parameters is performed with

    PC software via the fire alarm control panel.

    The BX-ESL includes a short-circuit isolator. In the event of wire

    breakage or short-circuit this functionality ensures that the fault

    is localised and that operation of the ring circuit remains fullyfunctional.

    The BX-ESL is built into a plastic switch housing. The cables are

    led in through PG screw fittings.

    The SecuriLine eXtended is connected via the X1-X4 screw ter-

    minals.

    Interfaces

    Fig. 2 BX-ESL interfaces

    SecuriL ine eXtended (X1-X4)

    Terminal Designation Description1 L1 Data A

    2 L2- Data B

    3 SHLD Screen

    4 GND GND A/B

    ProgrammingSecuriFire software documentation is planned for programming and

    planning.

    Power requirementFor mixed operation of detectors and modules on the ring circuit, it is

    important to know that the BX-ESL has the power consumption of

    about 4 detectors. This reduces the number of connectable detectorsby 4 for each BX-ESL in use. A maximum of 32 BX-ESLs are permit-

    ted per ring circuit.

    A tool is available for calculating the maximum possible ring length

    and the maximum number of participants.

    Dimensioned drawing

    Fig. 3 Dimensioned drawing

  • 8/12/2019 BX_ESL_DS_T131460_en

    2/2

    Data sheet

    2 / 2 T 131 460 en BX-ESL

    First edition: 26.11.2010 Bed/ksaThe product specifications contained in this document are subject to change without notice. Copyright by Securiton

    Article numbers / spare partsShort designation Art. number CH Art. number

    BX-ESL 115.239 704 20-2100007-01-01

    Technical dataType BX-ESL

    Operating voltage 12 to 30 VDC

    Power consumption LED passive 0.4 mA

    LED active 1.3 mA

    Signal transmission Serial data transmission, 2-conductor technology

    Protection type 66 with housing IP

    Ambient temperature -20 to +60 C

    Connection Screw terminals, max. 1.5 mm2

    VdS approval G210130

    EU certificate of conformity (EN 54-17/18) 0786-CPD-21014

    Dimensions (H x W x D) 58 x 58 x 34 mm

    1

    Reference document: BX-ESL, V.1.0