Building Service 2 Report on Tesco Extra

43
BUILDING SERVICES 2 QSB 2714 BACHELOR OF QUANTITY SURVEYING (HONOURS) SEMESTER 3 TESCO EXTRA (MUTIARA DAMANSARA) Abang Azrin Bin Abang Affandi 0319073 Chua Jia Cheng 0315160 Goh Jeng Jhieh 0315080 Jake Sia Chyi Sern 0314396 Kellyann Hiew Yau Mei 0319532 Muhammad Aiman Bin Zainul Abidin 0321832 Rachel Emma Betty Ernesta 0317966

Transcript of Building Service 2 Report on Tesco Extra

Page 1: Building Service 2 Report on Tesco Extra

BUILDING SERVICES 2

QSB 2714

BACHELOR OF QUANTITY SURVEYING (HONOURS)

SEMESTER 3

TESCO EXTRA (MUTIARA DAMANSARA)

Abang Azrin Bin Abang Affandi

0319073

Chua Jia Cheng

0315160

Goh Jeng Jhieh

0315080

Jake Sia Chyi Sern

0314396

Kellyann Hiew Yau Mei

0319532

Muhammad Aiman Bin Zainul Abidin

0321832

Rachel Emma Betty Ernesta 0317966

Page 2: Building Service 2 Report on Tesco Extra

1

ABSTRACT

The case study of this report is on Tesco Extra which is located in Mutiara Damansara. The

four building services (mechanical and air-conditioning system, fire protection system,

vertical transportation and electrical supply) is analysed and information on the systems are

given. Recommendation is provided for the fire protection and vertical transportation to

improve the services.

Page 3: Building Service 2 Report on Tesco Extra

2

ABBREVIATIONS

% Percent

AC Alternating Current

AHU Air Handling Unit

CO₂ Carbon Dioxide

COPHK Hong Kong's Code of Practice for minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment

dB(a) A-weighted Decibel

DC Direct Current

IT Information Technology

kVAR Kilovolt Amperes Reactive

m/s Metre per Second

TNB Tenaga Nasional Berhad

W Watts

Page 4: Building Service 2 Report on Tesco Extra

3

LIST OF FIGURES

Figure 1: Air-conditioning (Refrigeration Cycle) .................................................................... 9

Figure 2: Cooling Tower ......................................................................................................10

Figure 3: Centralised System ..............................................................................................12

Figure 4: Multi Zone Variable Air Volume ............................................................................15

Figure 5: CO₂ Fire Extinguisher ...........................................................................................17

Figure 6: Escalator ..............................................................................................................20

Figure 7: Main Components of an Escalator ........................................................................21

Figure 8: One-Way Traffic Escalator ...................................................................................22

Figure 9: Two-Way Traffic (Parallel) ....................................................................................23

Figure 10: Two-Way Traffic (Crisscross) .............................................................................23

Figure 11: Electric Elevator ..................................................................................................27

Figure 12: Hydraulic System ................................................................................................28

Figure 13: Electrical Distribution Grid ..................................................................................29

Figure 14: Transformer ........................................................................................................30

Figure 15: Step-Up Transformer ..........................................................................................30

Figure 16: Step-Down Transformer .....................................................................................30

Figure 17: Service Entrance ................................................................................................31

Figure 18: Example of Distribution Panel.............................................................................33

LIST OF TABLES

Table 1: Differentiation of Systems ......................................................................................11

Table 2: General specification for car speed of a lift ............................................................27

Page 5: Building Service 2 Report on Tesco Extra

4

LIST OF PHOTOGRAPHS

Photograph 1: Supply and Extract grilles .............................................................................12

Photograph 2: Ducting in Tesco Extra .................................................................................13

Photograph 3: Rectangular Diffuser ....................................................................................13

Photograph 4: Square and Rectangular Diffuser .................................................................13

Photograph 5 : Plan view of 1st floor in Tesco Extra ............................................................16

Photograph 6: Dry Powder Fire Extinguisher .......................................................................17

Photograph 7: Hose reel and fire extinguisher located inside the cabinet with a break glass

and fire alarm above ............................................................................................................18

Photograph 8: Sign boards high above on the wall to easily locate the cabinet ..................18

Photograph 9: Fire Escape with “KELUAR” sign .................................................................19

Photograph 10:Smoke detectors and sprinklers which is noticeable by the red paint .........19

Photograph 11: Handrails of a Travelator ............................................................................22

Photograph 12: Floor Plan of Tesco Extra ...........................................................................24

Photograph 13: Travellator at Tesco Extra ..........................................................................24

Photograph 14: Escalator at Tesco Extra ............................................................................25

Photograph 15: Elevator in Tesco Extra ..............................................................................26

Photograph 16: Service Elevator .........................................................................................26

Photograph 17: Main Switchboard 1 ....................................................................................32

Photograph 18: Main Switchboard 2 ....................................................................................32

Photograph 19: Main Switchboard Room ............................................................................32

Photograph 20: Distribution Panel in Tesco .........................................................................33

Photograph 21: Food Court .................................................................................................34

Photograph 22: Bakery ........................................................................................................34

Page 6: Building Service 2 Report on Tesco Extra

5

TABLE OF CONTENT

INTRODUCTION .................................................................................................................. 6

PART 1 – PURPOSE OF THE BUILDING ............................................................................ 7

PART 2 – TYPES OF SYSTEM ............................................................................................ 8

Mechanical and Air-conditioning systems ...................................................................................... 8

Fire Protection System ................................................................................................................ 16

Vertical Transportation ................................................................................................................ 20

Electrical Supply .......................................................................................................................... 29

PART 3 – RECOMMENDATION AND SOLUTION .............................................................34

Fire Protection System ................................................................................................................ 34

Vertical Transportation ................................................................................................................ 36

PART 4 – CONCLUSION ....................................................................................................37

Page 7: Building Service 2 Report on Tesco Extra

6

INTRODUCTION

This report is to observe the building services systems available in our case study. The

building that was chosen is Tesco Extra which is located in Mutiara Damansara. A total of

four systems were analysed; the mechanical and air-conditioning system, fire protection

system, vertical transportation and lastly, the electrical supply. The purpose of the report is

to understand about the systems installed in the building and their functions. Information

about the report is then researched to fully understand the available building services.

Page 8: Building Service 2 Report on Tesco Extra

7

PART 1 – PURPOSE OF THE BUILDING

Tesco Stores (Malaysia) Sdn Bhd was first founded back in 2001. The company

commenced their operations in the following year in 2002 with the first hypermarket opening

in Puchong, Selangor. They currently have over 50 hypermarkets all across Peninsular

Malaysia. Their stores in Malaysia have a combined floor space of over 4 million square

feet.

The company operates 2 kinds of store formats; Tesco Hypermarkets and Tesco Extra

Hypermarkets. This report is based on the Tesco Extra which is located in Mutiara

Damansara, Selangor, Malaysia. The purpose of Tesco Extra is to provide customers with a

destination to shop for their needs with everything ranging from fresh foods to groceries,

and even including apparels. It carries over more than 60,000 lines of products including

nearly 3,000 of its own brand of products ranging from food to non-food items.

The products and services are focused to serve the needs of small businesses, families

and individuals. Tesco Extra includes a bigger pack sizes, special trolleys and checkouts

along with a committed business development team to support small business owners with

their orders.

Page 9: Building Service 2 Report on Tesco Extra

8

PART 2 – TYPES OF SYSTEM

Mechanical and Air-conditioning systems

Air-Conditioning System Design Considerations for Tesco Extra

Designing an air conditioning system is a complex process. Every building serves different

purpose. The most important criteria are to design an air conditioning system that is

efficient and cost effective for that particular area to provide comfort to the occupants. In

this case the occupant includes the staff and customers of Tesco Extra. Increasingly,

energy efficiency is a big concern given that it’s vital for reducing running costs and carbon

emissions.

Air Conditioning Design Consideration

1. Heating and/or cooling load

2. Range of suitable units with the required capacity

3. Positioning

4. Sizing the Air Conditioning Systems

Anything that can affect the heating and cooling load has to be considered. This includes

the heat transfer through walls, large windows, roofs, and especially to big hypermarkets,

any system such as mechanical and electrical, comprising of refrigerators for cooling

goods, cold stores which can emit heat into the area.

The system differs in the main shopping area, the server rooms, IT facilities and small

offices. The grilles are visible. The types of system found are common in large commercial

facilities as well as warehouses, and office buildings.

All air conditioning units need a certain amount of space to operate properly and should be

kept clear of dirt and debris.

Ventilation

Ventilation is a process where the air is circulated from the building to ensure there was a

changing of air in any space. Ventilation is important for controlling the temperature and

providing fresh air in closed area. Furthermore, it removes unpleasant smell, moisture and

heat. Ventilation is also used for health purposes to remove noxious dust, air pollution gas

and smoke. Air conditioning system is used to keep the temperature and relative humidity

of the space. The type of air conditioning system relevant to our case study is mechanical

ventilation.

Page 10: Building Service 2 Report on Tesco Extra

9

Figure 1: Air-conditioning (Refrigeration Cycle)

Compressor

Motorize machine that circulates coolant though a vapour compressor system. Refrigerant

will enter to compressor in vapour state. Compressor will compress the refrigeration to a

high pressure and followed by increasing of the temperature.

Condenser

Change the pressure of refrigeration from hot to cool it and include changing of vapour to

liquid form. Hot gas from compressor will be emitted the heat and condensed the

refrigeration through the coil.

Expansion valve

To make sure there are changing of pressure liquid from high to low pressure. The liquid

automatically become cool because of changing of pressure.

Evaporator

Happen when cold refrigerant is filled and produced by a system of the coil that filled out

cools air around it. The heat liquid refrigeration will be absorbed by coil of evaporator to

produce cool gas. This evaporator will change from liquid to gas form.

Page 11: Building Service 2 Report on Tesco Extra

10

Centralized System

Centralized system is most commonly used in large hypermarkets. It is actually more

economical if compared to a split unit for large surface areas. In this method a specific

space is provided for AHU/plant room for this system. The space will be used to house a

compressor, condenser, expansion valve and evaporator. Then, the cold air that is

produced by the evaporator will be chilled air and it flow through the ducting system to all

the required rooms. Air duct and diffuser are needed for ducting system.

Figure 2: Cooling Tower

Cooling tower is needed to cool the hot water. Hot water will be delivered to the cooling

tower and the water will be sprayed by sprinklers and then cooled by air in the cooling

tower. From our observation at Tesco Extra in Mutiara Damansara, it was concluded that a

centralized system is being used as a system for their air conditioning in order to achieve

safety, energy efficiency and cost efficiency. The centralization of these systems allow for

better management and system operation. On the other hand, they also require either a

mechanical room adjacent to the controlled space for locating the AHU and large ductwork

in the building space. It is not wise to use split units in the building because it takes high

power and also as it is high maintenance. It will require a large number of split units.

Instead, the centralized system produces high capacity air so that all occupants in the

Tesco Extra can receive the cold air continuously and throughout the daily operations and

services of the market.

Page 12: Building Service 2 Report on Tesco Extra

11

Table 1: Differentiation of Systems

Page 13: Building Service 2 Report on Tesco Extra

12

Figure 3: Centralised System

Types of Diffusers

The air is either supplied into or extracted from the

space, and as seen it is wall-mounted. The external

louvers are which through which air is extracted or

discharged from the building.

Photograph 1: Supply and Extract grilles

Page 14: Building Service 2 Report on Tesco Extra

13

Photograph 2: Ducting in Tesco Extra

The Ductworks branches by a network of round or rectangular tubes made of fiberglass

board particularly in this case. However, other material such as metal sheets, flexible plastic

and wire composite can also be used.

Photograph 3: Rectangular Diffuser

Photograph 4: Square and Rectangular Diffuser

Page 15: Building Service 2 Report on Tesco Extra

14

Zoning

Zoning is required to divide a space into different zones that have different cooling needs.

With zoning, we can control over the cooling and heating system in order to achieve control

over the temperature. Most places does not get the same amount of sun or shade all day,

therefore the same type of cooling or heating is not the same throughout the day. This

system must include thermostats that is connected through it and controlled by control a

panel. It is an easy-to-use advanced command that provides a seamless interface between

the system and occupancy. The zoning will operate the damper to control the temperature

in case for high or low temperature by control panel. This will achieve high comfort and

control over the humidity.

Control

Control is achieved when a signal is sent to the air conditioner. This enables different

results as desired by the occupant. It can be manual or automatic to control in order to

provide comfort, safety and energy efficiency. An Individual can adjust the temperature,

humidity of air, speed of air condition, pressure of air, and can switch the control on or off.

Adjustment can be done for damper whether one requires it to be closed or open, with the

control for volume of air purpose. Sometimes air conditioning has their own sensor to

control the damper by seeking volume of the room temperature or volume of the room. For

example, if the outside air temperature drops very low, the system adjusts to prevent the

mixed air temperature from dropping below a certain set point.

Page 16: Building Service 2 Report on Tesco Extra

15

Multi Zones Variable Air Volume

Figure 4: Multi Zone Variable Air Volume

From our research, Tesco Extra uses multi zones variable air volume. Air Handling Unit is

used to supply chilled air through the ducting. The air is then distributed throughout the

whole building. Each zone contains the same temperature and it depends on the individual

comfort to adjust them through a control panel. This can be observed easily in the separate

retail areas and corridors in Tesco Extra.

The system requires installation of a motorized damper for each zone as well as associated

sensors and controller. A thermostat is required to control each pair of zone dampers.

Minimum ceiling space requirements is preferable for the multi-zone system as it allows the

system to operate smoother and with less noise compared to single zone. Basically, the

office (closed area) and the supermarket have different temperature needs. With multi

zones, temperature can be adjusted from warm and cold air that have been mixed and

produced for a comfort purpose.

Mixing is done at the AHU and connected to the control panel. Variable Air Volume is used

to save more energy because the speed can be controlled depending on the demand. But

as per our observation, Tesco Extra has several ducting due to multi zoning. During a

sunny day, Tesco Extra will increase the speed however at night the speed will be reduced.

If one zone needs medium temperature, both cooling and heating coils will work together

and produce same power. However if one desires the room to remain cold, cooling coils will

use more power to enable cooling.

Page 17: Building Service 2 Report on Tesco Extra

16

Fire Protection System

Photograph 5 : Plan view of 1st

floor in Tesco Extra

Tesco Extra provides various types of fire protection services; the first is that fire

extinguishers are available throughout the whole building in both floors near potential fire

hazards. There are 2 types of fire extinguisher available in the building which is CO₂ Fire

Extinguisher and Dry Powder Fire Extinguisher. CO₂ fire extinguisher is suitable for

flammable liquids, electrical equipment and cooking oils & fats (Fire Equipment

Manufacturers' Association, 2015). It is red in color with a black stripe and there are five

numbers of CO₂ fire extinguishers throughout the building which is located in the Kitchen,

the Genset room, the Switch room, the Computer room, and in the Bakery. They are placed

in such locations to match the type of fire expected which are mostly causes by cooking oils

& fats and electrical equipment.

Page 18: Building Service 2 Report on Tesco Extra

17

Figure 5: CO₂ Fire Extinguisher

Photograph 6: Dry Powder Fire Extinguisher

On the other hand, Dry Powder fire extinguishers are suitable for solids, flammable liquid,

flammable gasses, and electrical equipment (Fire Equipment Manufacturers' Association,

2015). It is red in color with a blue stripe and is separated evenly throughout the whole

building with a total number of 40 Dry Powder fire extinguishers. It is placed in general

locations with solid objects, liquids and gasses so that when there is an outbreak of fire, the

occupants will be able to use the fire extinguisher to put out the fire.

Fire extinguisher must be generally located close to the proximity of fire hazards so that

when there is an outbreak of fire, it would be easier to be put it out before it turns into a full

scale fire. It is not used for large fires as it is not effective and as it is made for the purpose

of initial outbreak of fire. The placement of the type of fire extinguishers is determined by

the type of fire anticipated. If it used for the wrong type of initial fire, instead of eliminating

the fire, it might make the situation worst.

Page 19: Building Service 2 Report on Tesco Extra

18

Photograph 7: Hose reel and fire extinguisher

located inside the cabinet with a break glass and fire alarm above

Photograph 8: Sign boards high above on the

wall to easily locate the cabinet

Another type of fire protection which is installed in the building is the fixed type of hose reels

and they are fixed to the wall of the building (Grundfos Holding A/S, n.d.).There are a total

of 9 hose reels available in the building. The hose reels are located at areas which can be

easily spotted and it is painted red so that it can catch the attention of the occupants. There

are sign boards above the hose reels and fire extinguishers so that occupants are able to

identify the location the equipment. Hose reels are normally placed with a fire extinguisher,

a Break Glass, and an alarm bell. The hose reel consist of a hose reel pump, hose reel

tank, pipework and valves. During early stage of a fire, occupants may use the hose reel to

control the fire before the fire brigades arrive.

Break Glass is a component that acts as an active fire protection system which requires the

help of people to start an alarm during the event of fire. Break Glass are fixed together with

the alarm bell and is distributed evenly throughout the whole building. The Break Glass is

installed at a height of 1.2m above finishing floor level for the occupants to reach it with

ease. During the event of a fire, occupants can manually break the Break Glass and trigger

a fire alarm so that the others are aware of the event of a fire. Fire alarm bells should have

a 65dB(a) or +5dB(a) sound pressure and last more than 30 seconds.

Page 20: Building Service 2 Report on Tesco Extra

19

Photograph 9: Fire Escape with “KELUAR” sign

Photograph 10:Smoke detectors and sprinklers

which is noticeable by the red paint

Fire escape exits are available throughout the building and the door is constantly locked.

During the event of fire, occupants need to unlock the door and use the nearest fire escape

exit. The fire escape exit is made out of fire resistant walls which will enable the occupants

to evacuate within a limited time. There are “Keluar” signs near the fire escape exit which

will light up when the power of the building is cut off so that the occupants are able to find

the fire escape exit.

In addition, smoke detectors are used in the building to detect smoke and initiate the alarm

(Woodford, 2015). Tesco Extra is using ionized smoke detector; the ionized smoke detector

constantly ionizes the air to encourage small electric current. When smoke enters the

detector and reaches the chamber, it reduces the current and activates the alarm.

There are sprinkles installed evenly throughout the whole building. The building is using a

wet sprinklers system as it is constantly filled with pressurized liquid which expand when it

receives pressurized liquid which expands when it receives heat. During the event of a fire

the pressurized liquid would expand until a certain point and it will break the glass tube at

the head of the sprinkler. The plug will be forced out by the pressurized liquid and the water

will be sprayed from the sprinklers head until the main valve is shut off.

Lastly, the Genset room is equipped with an automatic CO₂ system which will flood the

whole room with CO₂ in a delay of 30 seconds and will cool down the electronic machines.

Occupants or workers must evacuate from the room when the CO₂ system is activated as it

can cause insufficiency of air and may lead to death. The main purpose of the CO₂ system

is to protect the electrical devices in the Genset room and prevent the spreading of fire to

another area.

Page 21: Building Service 2 Report on Tesco Extra

20

Vertical Transportation

Escalator

Figure 6: Escalator

Walking can sometimes be very tiring after a long day of work. In the modern day, every

human being whether or not a doctor, teacher, fireman or a student, are obliged to have a

decent amount of walking time in a day. The invention of a moving walkway called the

escalator is the simplest solution to these problems. Escalators are an essential service

provided as a conveying transport designed for moving people in a more efficient manner

between floors of a building. It is a simple variation on the conveyer belt. A pair of rotating

chain loops pulling a series of stairs in a constant cycle, making it a really convenient and

efficient way of travelling in buildings by moving a big number of people in a short distance

at a decent speed. This simple yet expensive machine also requires zero waiting time.

Page 22: Building Service 2 Report on Tesco Extra

21

Figure 7: Main Components of an Escalator

1. Electric Control 2. Drive 3. Main Shaft 4. Handrail Drive

5. Balustrade 6. Main Truss 7. Steps 8. Step Chains

9. Handrail Compensation 10. Chain Tensioning Device 11. Comb Plates 12. Handrail Return

A typical escalator normally runs at a speed of 0.45m/s – 0.60m/s, through a 100

horsepower motor, which rotates the gears. The core of an escalator is a pair of chains,

looped around these two pairs of gears. An electric motor turns the drive gears at the top,

which rotate the chain loops. Both the motor and chain system are housed inside a metal

structure extending between two floors called a truss. To create a stable surface to step on,

at the top and bottom of the escalator, the steps collapse on each other, creating a flat

platform. This makes it easier to get on and off the escalator.

Escalators are used all around the world to move pedestrian traffic in places where

elevators would be impractical, for instance, a two storied shopping center. Principle areas

of usage include shopping centers, airports, transit systems, hotels, trade centers, public

buildings and many more. The mechanics to an escalator is very simple as the steps are

constantly rotated to provide continuous flights for pedestrians. Each step in the escalator

has two sets of wheels, which roll along two separate tracks. The upper sets are connected

to the rotating chains, and so are pulled by the drive gear at the top of the escalator. The

other set of wheels glide along the tracks, following behind the first one. The tracks are

spaced apart in such a way that each step will always remain level. Each step has a series

of grooves in it, so it will fit together with the steps behind it and in front of it during this

flattening.

Page 23: Building Service 2 Report on Tesco Extra

22

Photograph 11: Handrails of a Travelator

The handrail on the other hand, is moved by the provided electric motor. The handrail is

made of rubber, which is looped around a series of wheels. This belt is precisely configured

so that it moves at exactly the same speed as the steps, to give pedestrians stability.

Escalators can be arranged in so many different ways, depending on its usage to the

building. The arrangement of the escalators can be in a one-way traffic or a two-way traffic

system:-

ONE-WAY TRAFFIC (Interrupted Arrangement)

Figure 8: One-Way Traffic Escalator

While relatively inconvenient for users, for the owner of the stores from existing buildings for

example, a shopping complex, it provides an advantage as customers have to walk past

specially placed merchandise displays due to the spatial separation of the upward and

downward directions.

Page 24: Building Service 2 Report on Tesco Extra

23

TWO-WAY TRAFFIC (Parallel, Interrupted Arrangement)

Figure 9: Two-Way Traffic (Parallel)

This arrangement is used mainly in department stores and public transportation buildings

with heavy traffic volumes. When there are more than 2 escalators, it is possible to reverse

the direction of travel depending on the traffic flow.

TWO-WAY TRAFFIC (Crisscross, Continuous Arrangement)

Figure 10: Two-Way Traffic (Crisscross)

This type of installation is most frequently used as it allows customers to travel quickly to

the upper floors without any waiting time.

Page 25: Building Service 2 Report on Tesco Extra

24

Application of Vertical Transportation at Tesco Extra

Photograph 12: Floor Plan of Tesco Extra

In the case of Tesco Extra, the building only has two and a half floors whereby the half

floor, being named Mezzanine floor, only has 4 shops compared to the vast amount of

retails provided in the ground and first floor. For a renowned hypermarket store like Tesco

Extra, it is extremely vital for the design team to plan, arrange and provide efficient vertical

transport to the building.

Photograph 13: Travellator at Tesco Extra

To travel from the ground to first floor, the building acquires the use of an inclined moving

walkway. A moving walkway is also known as a travellator. It is very similar to a normal

escalator. The main difference of an escalator to a moving walkway is that it provides a flat

platform throughout the whole transportation system in comparison to the steps provided by

escalators. This system provides the same function as an escalator, which is to transport

people across an inclined plane over a short to medium distance by using a conveyor

mechanism. This system suits the requirement for Tesco Extra, as customers of the

hypermarket are bound to be pushing their trollies full of groceries to their respective cars.

Page 26: Building Service 2 Report on Tesco Extra

25

The provision of these moving walkways could help the customers save energy by reducing

the amount of effort in pushing the trollies from a fair amount of distance considering the

load bearing of the trollies. These moving walkway machines are provided at both ends of

the rectangular shaped building, which is very much as efficient as it can get.

Photograph 14: Escalator at Tesco Extra

To get to the Mezzanine floor, a normal sized two-way traffic escalator flight is installed for

the use of the customers of Tesco Extra. A moving walkway is not required around this area

as trollies are prohibited within the Mezzanine floor area. The arrangement of both the

escalator and travellator in Tesco Extra use two-way traffic system. During the course of

emergencies or a case of a very heavy pedestrian traffic, both the escalator and the

travellator directions could be adjusted to suit the traffic flow. This gives precision to

travelling within the building.

Page 27: Building Service 2 Report on Tesco Extra

26

Elevators

Photograph 15: Elevator in Tesco Extra

Photograph 16: Service Elevator

An elevator is a platform, either open or enclosed, which is used for lifting of people or

freight to upper floors within a building. Elevators are a standard part of any tall commercial

or residential building. Factors that affect the number of lifts in a building are: -

1. Population of the building

2. Type of building occupancy

3. The starting and finishing times of the population, whether staggered or unified.

4. Number of floors and heights.

5. Position of building in relation to public transport services.

General specification of a lift car should be able to carry 21 ~ 24 passengers, lift entrances

are about 1100 ~ 1200mm wide with 2 pieces of doors, door closing time should take 3.1

seconds for 1100mm width door and 3.4 seconds for 1200mm doors, transfer time of

passengers are about 1.6 ~ 2.0 seconds in and out, and the acceleration of lift car is

1.0m/sec2.

Page 28: Building Service 2 Report on Tesco Extra

27

Type of lift Car speed (m/s)

Passengers, up to 4 floors 0.3 ~ 0.8

4 ~ 9 floors 0.8 ~ 2.0

9 ~ 15 floors 2.0 ~ 5.0

Over 15 floors 5.0 ~ 7.0

Paternoster Up to 0.4

Goods, to any height 0.2 ~ 1.0

Hydraulic, passengers or goods, max 4 or 5 floors 0.1 ~ 1.0

Table 2: General specification for car speed of a lift

A round trip time is basically the time in seconds taken by a single lift to travel from ground

floor to the top floor, including the probable number of stops, and return to the ground floor.

The flow rate percentage (%) of the total population requiring lift service during a 5 minute

peak demand period is 10 % to 25 %. If flow rate is not given for staggered starting time, it

is assumed to be 12 % and if flow rate is not given for unified starting time, it is assumed to

be 17 %.

There are 2 main types of elevator available in Tesco Extra, which are hydraulic and

electric elevators. Electric elevator is a type of vertical transport equipment that efficiently

moves people or goods between floors of a building. It is powered by electric motors that

either drives traction cables or counterweight systems. Hydraulic elevators are elevators

which are powered by a piston that travels inside a cylinder. An electric motor pumps oil

into the cylinder to move the piston. The piston smoothly lifts the elevator cab. Electrical

valves control the release of the oil for a gentle descent.

1. Control System – Located in a machine room above the elevator shaft.

2. Electric Motor – Motor rotates and the sheave will either raise or lower the elevator.

3. Sheave – A pulley with grooves around the circumference. The sheave grips the hoist ropes, and it moves as the sheave is rotating.

4. Counter weight – Weighs about the same as the car filled to 40-percent capacity, mainly to balance the speed of elevator when it goes too fast.

5. Guide rails – Along the sides of the elevator shaft, to prevent the car from swaying back and forth, also work with the safety system to stop the car in emergency.

Figure 11: Electric Elevator

Page 29: Building Service 2 Report on Tesco Extra

28

In Tesco, there are 2 different types of elevators to serve different purposes. The first one is

an electric type which is to carry customers or workers to different levels in the building and

another one is the freight elevator which is to transport trolleys from basement floor to

levels above for shopping purpose. Electric elevator is only provided at 1 side of the

building while the escalator is provided at another side of the building. The arrangement of

escalator and elevator is considered good to provide vertical transport at both different

entrances. But the problem comes in during peak hour, as a lot of people have to wait at

the elevator for a long time since only 1 elevator is provided and the car lift is small and is

unable to carry a lot of people at once. It also cannot be easily found as the elevator is

placed behind a wall.

1. Tank - Shall have sufficient capacity to provide an adequate reserve to prevent the entrance of air or other gas into the system.

2. Motor - Used in hydraulic elevator is constantly pushing Liquid into the cylinder to lift the elevator.

3. Valve - Let liquid out of system, keep the pressure low when open & increase pressure when closed.

4. Actuator - The device that transfers fluid or electrical energy into mechanical energy.

Figure 12: Hydraulic System

Page 30: Building Service 2 Report on Tesco Extra

29

Electrical Supply

Electrical System

Figure 13: Electrical Distribution Grid

Figure 13 shows the design for electrical distribution for a city or a town. Electricity is

generated from the generating station or power plant (Brain & Roos, 2015). There are a few

types of generating stations some of which are thermal power plant, hydropower plant and

nuclear power plant. The power travels through a distribution grid that works by dividing the

electrical power into networks which then supplies electrical power to every building in the

vicinity.

Page 31: Building Service 2 Report on Tesco Extra

30

Transformers

Figure 14: Transformer

The transformer is an apparatus used to convert the system’s voltage to increase the

efficiency of distribution for each respective area as per Figure 14. Substations may include

transformers that reduce the voltage of two different transmission voltages. Electrical

transformers can be configured as either a single-phase or a three-phase configuration.

There are several necessary specifications to specify when it comes to electrical

transformers. These include: maximum secondary voltage rating, maximum secondary

current rating, maximum power rating, and output type. An electrical transformer may give

more than one secondary voltage value. Output choices include AC or DC.

Figure 15: Step-Up Transformer

Figure 16: Step-Down Transformer

The transformers can perform both step-up and step-down depending on how it is built. The

transformer increases the voltage from high to low of the electricity being supplied by

increasing the number of coils and decreases the voltage by reducing the number of coils

as per Figure 15 and Figure 16 respectively (Electrical4U, 2015).

Page 32: Building Service 2 Report on Tesco Extra

31

Service Entrance

Figure 17: Service Entrance

The service entrance is the point where electricity enters the building, which in this case

would be Tesco Extra. It is the directly linked to the TNB substation and is located in Tesco

Extra. A grounding system is used that acts like a drain for current to flow into the building.

The grounding system consist of two parts which are the equipment grounding conductors

and earth grounding conductors used for ground fault protection and dissipating induced

voltages and surges respectively. Although TNB substation is located in the premises of

Tesco, no personnel can simply enter without the permission of TNB.

Page 33: Building Service 2 Report on Tesco Extra

32

Main Switchboard

Photograph 17: Main Switchboard 1

Photograph 18: Main Switchboard 2

Photograph 19: Main Switchboard Room

The main switchboard (MSB), as shown in

Photograph 17 and

Photograph 18, is an important part of any electrical installation and is generally where the

service protection device and supply authority metering equipment is located. The main

switchboard is located inside Tesco Extra at the point which incoming power supply

distributes throughout the building (Schneider Electric, 2015). It distributes the large

incoming power supply into a smaller form that can be easily controlled. Protection is also

provided; tripping the breakers for when current overloads or short circuits.

Page 34: Building Service 2 Report on Tesco Extra

33

Distribution Panel

Figure 18: Example of Distribution Panel

Photograph 20: Distribution Panel in Tesco

The diagram above shows one of the many distribution panels in Tesco. It is usually

positioned in strategic locations all around Tesco and fixed to the wall. It is used to

distribute power to consuming appliances while providing a fuse or circuit breaker for each

circuit. The distribution panel normally comes with a metre for when the power oversupplies

and actives the circuit breaker to trip. Circuit breakers are automatic protection devices in

the distribution panel that turns off a circuit when they detect an overload. Circuit breakers

are similar in size to fuses, but gives better protection. When they trip, you can simply reset

the switch whereas fuses need to be replaced when there is an overload.

Requirements of Electrical Installation

There are some factors to be considered before installing the electrical system in a building

and Tesco has satisfied all of the some of which are enough capacity for purpose, minimum

wastage of current, prevention of fire, isolated and corresponding with laws and regulations.

As stated in the Uniform Building By Law 2012 Amendments on EE Bylaw 38A and

MS1525, 7.5, power factor correction capacitors should be the low loss type with losses per

kVAR not exceeding 0.35 W at upper temperature limit excluding the losses in the

discharge resistors. This is to reduce the energy lost in the capacitors and cables. It is also

written in 7.6, that to facilitate monitoring of energy consumption and energy management,

electrical energy meters should be installed at strategic load centre to identify consumption

by functional use (air conditioning, lighting, etc) (Izdihar, 2013). This is to effectively record

and control the usage of the electrical energy.

Page 35: Building Service 2 Report on Tesco Extra

34

PART 3 – RECOMMENDATION AND SOLUTION

Fire Protection System

There are various fire protection services installed in the vicinity of Tesco Extra such as the

two types of fire extinguisher, fire escape, hose reel, alarm bell, smoke detector and

sprinklers. Despite having sufficient fire protection, the building can be further improved to

withstand the disaster of a fire. Compartmentalisation should be included to help prevent

the spread of fire.

Even though Tesco Extra has taken the measures to provide plenty of sprinklers in the

building, there are times when a sprinkler can fail to douse the fire. The top five reasons

that sprinkler systems failed to operate or were ineffective during a fire were (Long, et al.,

2010):

1. System shut off (38%)

2. Inappropriate system for the type of fire (18%)

3. Water discharged did not reach fire (12%)

4. Lack of maintenance (12%)

5. Problem with water supply or not enough water discharged (9%)

Photograph 21: Food Court

Photograph 22: Bakery

As you can see from Photograph 21 as well as Photograph 22, Tesco Extra has a kitchen

that cooks and bakes freshly made food. If a fire were to ever occur in the kitchen and the

sprinklers were ineffective, the initial fire may erupt into a large scale fire and spread to

different areas and floors. Fire Compartmentation is designed to contain the fire to within

the area of starting point of the fire (A L Fire Systems, 2014). Compartmentation can help in

delaying the spread of fire before the fire brigade arrives to the location.

Page 36: Building Service 2 Report on Tesco Extra

35

According to COPHK Part 4.14, low rise commercial buildings are required to install

‘Automatic Actuating Devices’ (Fire Services Hong Kong, 2012). Fire shutters can be

installed in the premise to help satisfy the requirement. Modernised fire shutter can now

close at a controlled speed (typically 10 centimetres per second). With a combination of a

Fire Detection Interface (FDI) panel it is now possible for a fire roller shutter to initially

deploy to a pre-determined safe height, (normally just above head height) to act as a smoke

barrier while allowing people to escape (HVP Security Shutters , 2015).

The fire shutter is fully closed after a pre-determined time (following fire protocol for the

building) to create a fire resistant barrier. The FDI panel can also act as a visual and

acoustic alarm, alerting occupants that the fire shutter is about to close (HVP Security

Shutters , 2015)

Page 37: Building Service 2 Report on Tesco Extra

36

Vertical Transportation

Escalator/Travellator

A simple recommendation to the vertical transport of the building would be to adjust the

direction of the two-way traffic to only one-way traffic on each end of the building. Instead of

having a travellator moving in different directions at both ends, Tesco Extra could adjust the

travellator on one end going up and the other travellator on the other end of the building to

go down. This could help enhance the number of customers going all the way round the

building. This change to the arrangement of the moving walkway could also inevitably

increase the customer density and thus help boost sales among the retails available inside

the building area.

Elevator

Instead of having an elevator, we propose to have another escalator to replace the area

that the elevator was serving. Escalator can carry more people and save time compared to

waiting for the lift car from other levels to reach. At the same time, it is more spacious to

carry goods bought by customers, especially during peak hour.

Page 38: Building Service 2 Report on Tesco Extra

37

PART 4 – CONCLUSION

In conclusion, Tesco Extra has fulfilled the requirements of the required building services.

The building is operating a centralized air-conditioning system with a multi zone variable air

volume. This will allow the retail shops within Tesco Extra to adjust the temperature to their

own satisfaction. According to the first floor plan, they have over 40 Dry Powder fire

extinguishers, 5 CO₂ fire extinguishers, 9 hose reel, 9 alarm bells and 9 breakglass. Their

premise is installed with an automatic CO₂ at selected areas and a sufficient amount of

smoke detector and sprinklers. Despite that, the fire protection services can be further

improved with the implementation of fire shutters which would compartmentalise the area.

Instead of escalators, Tesco Extra has a travellator to accommodate the use of trolleys and

service elevators to transport the trolleys back into the storage for customers to use. It is

recommended for the travellator to change from a two-way direction to a one-way direction.

This will allows customers to venture and notice the retail stores along the sides of Tesco

Extra.

Page 39: Building Service 2 Report on Tesco Extra

38

REFERENCES

A L Fire Systems, 2014. Fire Compartmentation - A L Firesystems. [Online]

Available at: http://www.alfiresystems.co.uk/compartmentation.aspx

[Accessed 22 June 2015].

B-DACS Air Conditioning Services , 2015. How Do We Design Your Air Conditioning

System?. [Online]

Available at: http://www.bdacs.com/air-conditioning-design/

[Accessed June 23 2015].

Brain, M. & Roos, D., 2015. How Power Grids Work. [Online]

Available at: http://www.electrical4u.com/electrical-power-distribution-system-radial-ring-

main-electrical-power-distribution-system

[Accessed 23 June 2015].

Dr. M., Z. H., 2011. Vertical Transportation: Elevators & Escalators. [Online]

Available at: http://teacher.buet.ac.bd/zahurul/ME415/ME415_elevators.pdf

[Accessed 5 June 2015].

Electrical Knowhow, 2013. Air Conditioning System Configurations - Part Two. [Online]

Available at: http://www.electrical-knowhow.com/2012/03/in-previous-air-conditioning-

system.html

[Accessed 10 May 2015].

Electrical Knowhow, 2013. Elevators Types and Classification - Part Two. [Online]

Available at: http://www.electrical-knowhow.com/2012/04/elevators-types-and-classification-

part_04.html

[Accessed 5 June 2015].

Electrical4U, 2015. Electrical Power Distribution System. [Online]

Available at: http://www.electrical4u.com/electrical-power-distribution-system-radial-ring-

main-electrical-power-distribution-system/

[Accessed 23 June 2015].

Fire Equipment Manufacturers' Association, 2015. Types of Fire Extinguishers. [Online]

Available at: http://www.femalifesafety.org/types-of-extinguishers.html

[Accessed 18 May 2015].

Page 40: Building Service 2 Report on Tesco Extra

39

Fire Services Hong Kong, 2012. Code of Practice for minimum Fire Service Installations

and Equipment and Inspection, Testing and Maintenance of Installations and Equipment.

[Online]

Available at:

https://www.google.com/url?sa=t&rct=j&q=&esrc=s&source=web&cd=2&ved=0CCUQFjAB

&url=http%3A%2F%2Fwww.hkfsd.gov.hk%2Feng%2Fsource%2Fsafety%2FFile2012.pdf&e

i=WI6JVaj5AcmVuATzgY3YDw&usg=AFQjCNFOc3lcqD9mS7eWQjkSBqewuL3rwQ&bvm=

bv.96339352,d.c2E&cad=rja

[Accessed 10 June 2015].

Grundfos Holding A/S, n.d. Fire hose reel system. [Online]

Available at:

http://cbs.grundfos.com/CBS_Master/lexica/Fire/FI_Fire_hose_reel_systems.html#-

[Accessed 15 May 2015].

HVP Security Shutters , 2015. Understanding fire shutters. [Online]

Available at: http://www.hvpshutters.co.uk/fire-shutters.php

[Accessed 22 June 2015].

hydraulicmania.com, 2010. The Working of a Hydraulic Lift. [Online]

Available at: http://www.hydraulicmania.com/hydraulic_lift.htm

[Accessed 6 June 2015].

Izdihar, I. A., 2013. UBBL 2012 Amendments on EE Bylaw 38A and MS1525:2014. [Online]

Available at:

http://www.eria.org/events/6.%20UBBL%202012%20Amendments%20on%20EE%20and%

20MS1525%20-%20Ir%20Ahmad%20Izdihar.pdf

[Accessed 18 June 2015].

Lawrence Webster Forrest, 2015. Fire Precautions - Compartmentation. [Online]

Available at: http://www.lwf.co.uk/bulletin/fire-precautions-compartmentation/

[Accessed 22 June 2015].

Long, R. T., Wu, N. P. & Blum, A. F., 2010. Lessons Learned From Unsatisfactory Sprinkler

Performance: An update on trends and a root cause discussion from the investigating

engineer's perspective. [Online]

Available at: http://magazine.sfpe.org/sprinklers/lessons-learned-unsatisfactory-sprinkler-

performance-update-trends-and-root-cause-discuss

[Accessed 10 June 2015].

Schneider Electric, 2015. Distribution Switchboards. [Online]

Available at: http://www.electrical-installation.org/enwiki/Distribution_switchboards

[Accessed 23 June 2015].

Shafiza, N. N., 2013. Lift. [Online]

Available at: http://www.slideshare.net/NurulAdha2/lift-29150998

[Accessed 6 June 2015].

Page 41: Building Service 2 Report on Tesco Extra

40

STANLEY ELEVATOR COMPANY INC™, 2015. HYDRAULIC ELEVATOR

MODERNIZATION. [Online]

Available at: http://www.stanleyelevator.com/hydraulic-elevator-modernization/

[Accessed 7 June 2015].

VFP Fire Systems, Inc, n.d. Wet Pipe Fire Sprinkler System. [Online]

Available at: http://www.vfpfire.com/systems-wet-pipe.php

[Accessed 5 June 2015].

Woodford, C., 2015. Smoke Detectors. [Online]

Available at: http://www.explainthatstuff.com/smokedetector.html

[Accessed 26 May 2015].

Page 42: Building Service 2 Report on Tesco Extra

41

APPENDIX

Job Scope

Abang Azrin Bin Abang Affandi

Vertical Transportation – Escalator/Travellator

Recommendation for Escalator/Travellator

Chua Jia Cheng

Fire Protection System

Goh Jeng Jhieh

Vertical Transportation – Elevator

Recommendation for Elevator

Jake Sia Chyi Sern

Electrical Supply

Kellyann Hiew Yau Mei

Recommendation for Fire Protection System

Structure of the whole Report

Compilation of the report

Muhammad Aiman Bin Zainul Abidin

Mechanical and Air-Conditioning System

Rachel Emma Betty Ernesta

Mechanical and Air-Conditioning System

Page 43: Building Service 2 Report on Tesco Extra

42

Schedule of Assignment

DATE

Kelly went to site to request for permission. Received no reply

18th of April, 2015

1st discussion, distribution of workload

29th of April, 2015

Sent an email to Tesco Extra. Received reply, but no confirmation

30th of April, 2015

Whole group went to the site to take pictures and gain information of site

7th of May, 2015

Started on report

8th of May, 2015

2nd discussion, checking on each other’s progress

21st of May, 2015

3rd discussion, checking on each other’s progress

13th of June, 2015

Compilation of report

23rd of June, 2015

Submission of report Presentation

24th of June 2015