6
power www.ppi.ph pazifik Manufactured by: Fully Gas Insulated Modular and Compact (RMU) System Up to 24 kV MV Switchgear Secondary Electrical Distribution • Full modularity, connectivity and future extendibility in both sides using the connecting set. • Internal arcs withstand for personal protection, in accordance with IEC 60298. • Small dimensions and low weights. • Simple and safe operation, possibility of mounting auxiliary components under voltage, additional interlocks, ergonomics and fuses in horizontal positions. • Easy cable connections, no need for a trench or placement of additional on-site frames. BO-CGMCM/3

Transcript of BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical...

Page 1: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

powerwww.ppi.ph

pazifik

Manufactured by:

Fully Gas Insulated Modular and Compact (RMU) System Up to 24 kV

MV Switchgear Secondary Electrical Distribution

•Fullmodularity,connectivityandfutureextendibilityinbothsidesusingtheconnectingset.

• Internalarcswithstandforpersonalprotection,inaccordancewithIEC60298.

•Smalldimensionsandlowweights.

•Simpleandsafeoperation,possibilityofmountingauxiliarycomponentsundervoltage,additionalinterlocks,ergonomicsandfusesinhorizontalpositions.

•Easycableconnections,noneedforatrenchorplacementofadditionalon-siteframes.

BO-CGMCM/3

Page 2: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

Themodular and compact switchgear is composed of a set of reduced sizemodular cubicles, single or multifunctional, for different Medium Voltagesecondarypowerdistributionconfigurationsupto24kVinpublicandindustrialsettings.

Boththebreakingandswitchingcomponentsaswellasthebusbararelocatedinside a stainless steel SF6-filled gas tank which is permanently sealed,thus building a fully insulated unit. This provides protection against harshenvironmentalelements(includingflooding),longservicelifeandmaintenance-freeofliveparts.

Main Features

• Fullmodularity, connectivity and future extendibility in bothsidesusingtheconnectingset.

•Internalarcswithstandforpersonalprotection,inaccordancewithIEC60298.

•Smalldimensionsandlowweights.

•Simple and safe operation, possibility ofmounting auxiliarycomponentsundervoltage,additionalinterlocks,ergonomicsandfusesinhorizontalpositions.

•Easycableconnections,noneedforatrenchorplacementofadditionalon-siteframes.

•Continuouslyvoltagepresenceindication.

•Availabilityofanacousticalarm,whichemitsanaudiblesignalwheneveranattemptofinadequateoperations.

Standards

IEC60298Metal-enclosed switchgear for alternating current ratedvoltagesover1kVandunder52kV.The system has been designed and tested towithstand aninternalarcinaccordancewithAppendixAA.

IEC60265High voltage switches - Part 1 : High voltage switches forratedvoltagesover1kVandunder52kV.

IEC60129Alternatingcurrentdisconnectorsandearthingdisconnectors.

IEC62271-105Alternatingcurrentswitch-fusecombinations.

Connecting Set

Thevariousmodulesareelectricallyconnectedbytheconnectingset,patentedin1991byOrmazabal.

This assembly connects the main busbar of the extendiblecubicles, allowing current to flow while also controlling theelectricfield.

Other important aspects are the capacity to maintain thesamefunctionalcharacteristicsofthecubiclesandtheeaseofinstallation,evenintransformersubstationswithunevenfloors.

Overview

IEC60694Common specifications for high-voltage switchgear andcontrolgearstandards.

IEC62271-100High-voltagealternating-currentcircuit-breakers.

IEC60255Electricalrelays.

Themodular and compact switchgearmeets the immersiontestatapressureof3metreswatercolumn,24hoursatratedvoltageandisolationtestatpowerfrequency.

Note: The IEC standards are currently being updated, and therefore thenomenclaturemayvaryinsomecases.

Page 3: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

Incomingfeederorlinefunctionalunit

Busbarswitchfunctionalunit.

Busbarswitchwithearthingontheright(Ptd)orleft(Pti)ofthebreakingpointfunctionalunit

Fused-protectionfunctionalunit.

Vacuumcircuitbreakerfunctionalunit

Meteringfunctionalunit.

Functionalunitforcablerisingtothebusbarontheright(RCd)orontheleft(RCi).

Functionalunitforbusbarrisingontheright(RBd)oronbothsides(RBa).

Functionalunitforbusbarrisingontheright(RBd-Pt)oronbothsides(RBa-Pt),withearthingdisconnector

Technical Characteristics Fully Gas-Insulated Modular and Compact (RMU) System up to 24kV

L S S-Pt_ P V M RC_ RB_ RB_-Pt 2LP RLP 2L 3LP 2L2P 3L2P

RatedVoltage[kV] 12/24

RatedCurrent[A]

Busbars 400/630

Outgoing 400/630 - - 200 400/630 - - 400/630 400/630 400/630200

400/630200

400/630 400/630200

400/630200

400/630200

Short-timeCurrent(kA)

16/20# 16/20# 16/20# 16/20# 16/20 - - 16/20# 16/20# 16/20# 16/20# 16/20# 16/20# 16/20# 16/20#

Height(mm) 1740* 1740 1740 1740* 1740 1740 1740 1740 1740 1740* 1740 1740* 1740* 1740* 1740*

Width(mm) 365 450 450 470 480 800 365 365 365 1190 1190 730 1565 1670 2035

Depth(mm) 735 735 735 735 850 1025 735 735 735 735 735 735 735 735 735

Weight(kg) 95 105 110 140 218 165 40 95 100 290 290 180 385 430 525

#Testconductedwithacurrentof21kA.*1300mmhighunderrequest.

Page 4: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

Operating MechanismsType Mechanical

enduranceRatedVoltage

Maximumpowerconsumption

Averagemotoroperationtime

Signallingcontacts

ManualwithtripcoilSwitch-disconnector

B/BR M1Class 24Vdc/48Vdc/230Vac/110Vdc

80W/80VA - 1NOC/1NOC+2NO2NO

CircuitBreaker RAV M1Class 24Vdc/48Vdc/110Vdc/125Vdc/230Vac

60W/60VA - 6NO+6NC

MotorSwitch-disconnector

BM M2Class 24Vdc/48Vdc/110Vdc125Vdc/230Vac

5.1A/3.7A/2.1A/2.1A/1.5A

3s Switch2NO+2NC

Earthing2NO

Circuitbreaker RAMV M1Class 24Vdc/48Vdc/110Vdc125Vdc/230Vac

2.1A/1.1A/0.45A0.45A/0.22A

13s Circ.Breaker2NO+2NC

Earthing1NO+1NC

Compactcubiclecomposedoftwofeederandonefused-protectionfunctions(RMUtype)

Groupofmodulesformingoneunitcomposedofthreefeederandonefused-protectionfunctions.

Compactcubiclecomposedofonebusbarriser,onefused-protectionandonefeederfunctions.

Groupofmodulesformingoneunit;composedoftwofeederandtwofused-protectionfunctions.

Compactcubiclecomposedoftwoincomingfeederfunctions.

Groupofmodulesformingoneunit;composedofthreefeederandtwofused-protectionfunctions.

Page 5: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

Interlocks

The system has a series of interlocks to ensure safe, reliableservice, inaccordancewith the requirementsof the IEC60298standard. Based on the design and the inclusion of additionalinterlocks, the switch-disconnector and the earthing switchcannotbeclosedsimultaneously.

AninterlockoperatedbytheearthingswitchpreventstheaccesscovertotheMVcableterminalsfromopening,therebyavoidingunsafeoperations.

In addition, the access to the fuse holders in the protectionfunctionalunitsisalsosecuredwiththesameinterlock.

The cubicles allow switching to be disabled by padlocks (upto three) for both the switch-disconnector and the earthingdisconnector.

Optionally, switching lockingdevicesequippedwitha lockareavailableforanyoftheoperations.

Voltage Presence Indicator

The design is according to IEC 61958 standard, indicates thepresenceofvoltageinthephasesofeachfunction.

Acoustic Alarm

Acousticalarm topreventearthing, isa self-poweredaudibleindicatorthatisactivatedwhenanattemptismadetooperatethe earthing disconnector shaft under power cable voltage,therebyalertingtheoperatorofperformingaswitchingoperationthatmayproduceafaultinthenetwork.

Protection, Metering, Control and Signalling

This family includesaseriesofunits,whichcanbe integratedin the system to provide protection, measuring, control andsignallingfunctionintheMediumVoltagedistributionnetworks.The various units, composed by a set of elements: relays,measuring sensors, power supply cards, toroidal currenttransformers, low energy bistable tripping units, etc, provideadded value to the facilities by extending service life, whilefurtherensuringequipmentandpersonalsafetyandenhancingthequalityofservice:• Protection,measuringandcontrolunit,specificallydevelopedforapplicationtothefuseprotectionfunctionalunit.

• Protection,measuringandcontrolunitdevelopedforapplicationtothecircuitbreakerfunctionalunit.

• Signalling,measuringandintegratedcontrolunit,specificallydevelopedforapplicationtothefeederfunctionalunit.

• Detectionunitforthepresence/absenceofvoltage.• Measuringsensorsandself-powertoroidalcurrenttransformers.

• Powersupplycard.• Bistabletrippingunit.• Integratedsignallingvoltagepresenceindicator.• Phasecomparator.Devicetoindicatephasecoincidencebetweentwocubicles.

• Acousticalarmtopreventearthing.• Programmablecubiclecontroller.• Automaticincomingfeedertransfer.• ComputerapplicationforremotecontrolandautomationoftransformersubstationsfromaSCADAbasedcontrolstation.

Detectionunitforthepresence/absenceofvoltageProgrammable

CubicleController

Acousticalarmtopreventearthing

IntegratedSignalingVoltagePresenceIndicator

ProtectionMeasuringControlforapplicationtothecircuitbreakerfunctionalunit

ProtectionMeasuringControlforapplicationtothefusebreakerfunctionalunit

PhaseComparator

Page 6: BO-CGMCM/3 MV Switchgear Secondary Electrical Distribution · MV Switchgear Secondary Electrical Distribution ... , for different Medium Voltage ... Programmable absence of voltage

4/F South Park Plaza, Santiago Street Paseo de MagallanesCommercial Center, Makati City, 1232 Philippines

#8 Lapu-Lapu St., Magallanes Village, Makati City, 1232 PhilippinesTel.: +63 2 8675619, 8675620 Fax:+63 2 8364323

Email: [email protected] www.ppi.ph

pazifikpowerwww.ppi.ph

4/F South Park Plaza, Paseo de Magallanes CommercialCenter, Makati City, 1232 Philippines

Tel: +63 2 511 8888 | Fax: +63 2 836 4323Email: [email protected] | Website: www.ppi.ph

scadaflex

Substation Automation SystemSolutionpackageforsystemintegration,automationandenergymanagement

Dry-type Cast Resin TransformersGlassFibreReinforcedVacuum

Technology(GVT)upto36kVandcapacityupto30MVA

Surge ArresterDistributionTypeSurgeArresterinpolymerichousedgaplessdesign

upto36kV

Instrument TransformersIndoor/OutdoorCurrentandPotentialTransformersfrom15KVupto69KV

Protection RelayCompleteProtectionSolutionsControlandMeasurement

Solid Insulation SystemDesignsareavailableforapplicationupto69kVandupto7000Aforbothindoorandoutdoorinstallations

Turnkey Substation Designconstructionandenergizationofsubstationupto500MVA

DISTRIBUTIONEQUIPMENT

Medium Voltage SwitchgearsHermeticallysealedandSF6Insulated

CompactSwitchgearVoltageratingupto36kVandcurrent

ratingupto2,500A

Spain

Efficient Electricity SolutionsInaspanoftwodecades,PPIPazifikPower,Inc.successfullysuppliedthePhilippinemarketawiderangeofhighqualityinnovativepowerandinfrastructureequipmentfromthebestmanufacturersinEuropeandfromitsownautomateddesignconcepttomorethan200customerswhoareattheforefrontofthecountry’senginesofindustrialgrowth.

AmongPPI’smostsoughtafterpowerproductlinesare:TurnkeyprojectsforSupplyofSubstationsratedvoltageofupto230kV,ElectricityMeters,Transformers,Switchgears,Disconnectors,FaultIndicators,SurgeArresters,ProtectiveRelays,DiagnosticandTestingEquipments,Batteries,HarmonicFilters,UPSandAVRsystems.