    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKSQQ01-CARPARKCARPARK LEVEL 1QQ01-DGP-PK-1-1

    1 HV SwitchgearMain Incoming CBs 1 Volt Free ContactC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485Tie BreakersC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactOutgoing CBs (To Transformers)C.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485

    1 ATS-1Generator Position 1 1 Volt Free ContactTransformer Position 1 1 Volt Free ContactBy Pass Generator Position 1 1 Volt Free ContactBy Pass Transformer Position 1 1 Volt Free Contact

    1 Fire Alarm System 1Panel Status/Supervisory Mode 1 1 Volt Free ContactGeneral Fault 1 1 Volt Free ContactGeneral Alarm 1 1 Volt Free Contact

    1 Security SystemGeneral Fault 1 1 Volt Free ContactGeneral Alarm 1 1 Volt Free Contact

    1 Generator Run Status 1 1 Volt Free ContactGeneral Alarm 1 1 Volt Free Contact

    1 LiftsRun Status 1 1 Volt Free Contact

    BMS INPUT/OUTPUT SUMMARY

    Run Status 1 1 Volt Free ContactGeneral Alarm 1 1 Volt Free Contact

    1 FM200FM200 LINE PRESSURE 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    2 Lighting Control System (PP/PK1-1)Power supply status of lighting control panels 2 2 Volt Free ContactSwitching ON/OFF of various lighting circuits 2 2 Interface Relay(DRAINAGE)

    3 DUPLEX SUBMERSIBLE PUMPS(PDS-QQ01-PK1-2-1 & 1-2-2, PK1-3-1 & 1-3-2 & PK1-8-1 & 1-8-2)Pump Status 6 6 Volt Free ContactPump Normal/Fault (Trip Status) 6 6 Volt Free ContactHOA Position 6 6 Volt Free ContactPower Failure 3 3 Volt Free ContactHigh sewage/drainage level alarm 3 Level Switch 3 To be supplied by OthersLow sewage/drainage level alarm 3 Level Switch 3 To be supplied by Others

    5 Parking Fans, EF-QQ01-PK1-2/3/6Fan Start/Stop 5 5 Interface RelayFan Status (On/Off) 5 5 Volt Free ContactFan Normal/Fault (Trip) 5 5 Volt Free ContactProof of Flow 5 P233A-10-AHC 5 Diff. Pressure Switch for FanHOA Position 5 5 Volt Free Contact

    2 MOTORIZED DAMPERS (for PF-QQ01-BU1-3 & BU4-3)Motorized Damper Status 4 4 Voltage Free Contact

    80 13 4 0 9716 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 0 5 8 8 21 22% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 1 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK-1-1A1 EMDB-1

    Main Incoming CBsC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactPower Fail Alarm 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485

    11 Outgoing Feeder CBsC.B. or Contactor On Status 11 11 Volt Free ContactC.B. or Contactor Tripped Status 11 11 Volt Free Contact

    1 MDB-1Main Incoming CBsC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactPower Fail Alarm 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485

    11 Outgoing Feeder CBsC.B. or Contactor On Status 11 11 Volt Free ContactC.B. or Contactor Tripped Status 11 11 Volt Free Contact

    54 4 0 0 5816 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller40 LP-XP91D05-000C 5 8 DI Expansion Module

    LP-XT91D00-000C 3 Extension ModuleELK 2.0 1 DDC Panel

    Spare Points 2 14 12 8 36 62% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 2 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK-1-2(PUMP ROOM)TREATED (FILTERED) WATER STORAGE TANKSCombined Fire & Raw Water SystemTanks Water Levels

    1 Water Level Raw Tank Compartment 1 1 DPT2301-050D 1 Differential Pressure Sensor1 Water Level Raw Tank Compartment 2 1 DPT2301-050D 1 Differential Pressure Sensor1 Water Level Treated Tank Compartment 1 1 DPT2301-050D 1 Differential Pressure Sensor1 Water Level Treated Tank Compartment 2 1 DPT2301-050D 1 Differential Pressure Sensor2 Multilayer Sand Filter

    Multilayer Sand Filter Status 2 DPT2301-050D 2 Differential Pressure Sensor2 Irrigation Booster Pump Set & Transfer Pumps

    Irrigation Pumps Start/Stop 2 2 Interface RelayPump Alarm 2 2 Volt Free ContactPump Status (On/Off) 2 2 Volt Free ContactPump Normal/Fault 2 2 Volt Free ContactWater Pressure Switch 1 P74DA-19C 2 WATER DIFF. PRESS. SWITCHIrrigation Water Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor

    2 Transfer PumpsTransfer Pumps Start/Stop 2 2 Interface RelayTransfer Pumps Status (on/off) 2 2 Volt Free ContactTransfer Pumps Normal/Fault 2 2 Volt Free ContactWater Pressure Switch 1 P74DA-19C 1 WATER DIFF. PRESS. SWITCH

    2 Fire PumpsFire Pump Status 2 Volt Free ContactFire Pump Alarm 2 Volt Free ContactWater Pressure Switch 2 P74DA-19C 2 WATER DIFF. PRESS. SWITCH

    1 Jockey PumpJockey Pump Status 1 Volt Free ContactJockey Pump Alarm 1 Volt Free ContactWater pressure switch 1 P74DA-19C 1 WATER DIFF. PRESS. SWITCHFire Line Static Pressure 1 P299EAB-2C 1 Water Pressure Sensor

    7 GeneralHOA Position 7 7 Volt Free ContactEMCC/PK1-1

    5 LIFTING & BOOSTER PUMPSPump Status 5 5 Volt Free ContactPump Normal/Fault 5 5 Volt Free Contact

    3 VFD BOOSTER PUMPSVSD Speed Display 3 Communication InterfaceVSD Speed Control 3 3 0-10vdc to VSDVSD Normal/Fault 3 3 Volt Free ContactVSD Status 3 3 0-10vdc from VFD

    1 Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor8 General Volt Free Contact

    HOA Position 8 8 Volt Free Contact2 Parking Fans (EF-QQ01-PK1-3/6)

    Fan Start/Stop 2 8 Interface RelayFan Start/Stop 2 8 Interface RelayFan Status (On/Off) 2 8 Volt Free ContactFan Normal/Fault (Trip) 2 8 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 8 Volt Free Contact

    2 DUPLEX SUBMERSIBLE PUMPS(PDS-QQ01-PK1-1-1&1-1-2 & PK1-5-1&1-5-2)Pump Status 4 4 Volt Free ContactPump Normal/Fault (Trip Status) 4 4 Volt Free ContactHOA Position 4 4 Volt Free ContactPower Failure 2 2 Volt Free ContactHigh sewage/drainage level alarm 2 Level Switch 2 To be supplied by OthersLow sewage/drainage level alarm 2 Level Switch 2 To be supplied by Others

    77 6 10 3 9616 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.0 1 DDC Panel

    Spare Points 3 12 2 5 22 23% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 3 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK-1-33 Lighting Control System (PP/PK1-3)

    Power supply status of lighting control panels 3 3 Volt Free ContactSwitching ON/OFF of various lighting circuits 3 3 Interface Relay

    1 FM200FM200 LINE PRESSURE 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC ENERGY TRANSFER STATION ROOM

    2 HEAT EXCHANGERSHEX Chilled Water Supply Temperature 2 TE-6322P-1 + WZ-1000-5 2 150mm Probe Length Immersion Temp. SensorHEX Chilled Water Return Temperature 2 TE-6322P-1 + WZ-1000-5 2 150mm Probe Length Immersion Temp. Sensor

    1 CHILLED WATERChilled Water Supply Temperature 1 TE-6322P-1 + WZ-1000-5 1 150mm Probe Length Immersion Temp. SensorChilled Water Return Temperature 1 TE-6322P-1 + WZ-1000-5 1 150mm Probe Length Immersion Temp. SensorChilled Water Flow 1 F-1111 1 Flow MeterMCC/PK1-1

    3 CHILLED WATER PUMPSChilled Water Pump Start/Stop 3 3 Interface RelayChilled Water Pump Status (On/Off) 3 3 Volt Free ContactPump VSD Speed Control 3 3 0-10vdc to VFDPump VSD Alarm 3 3 Volt Free ContactPump VSD Normal/Fault 3 3 Volt Free ContactPump VSD Speed 3 3 0-10vdc from VFDHOA Position 3 3 Volt Free Contact

    1 Expansion Tank Pressure 1 DPT2301-050D 1 Differential Pressure Sensor3 DUPLEX SUBMERSIBLE PUMPS

    (PDS-QQ01-PK1-4-1&1-4-2 & PK1-6-1&1-6-2)& PK1-7-1&1-7-2)Pump Status 6 6 Volt Free ContactPump Normal/Fault (Trip Status) 6 6 Volt Free ContactHOA Position 6 6 Volt Free ContactPower Failure 3 3 Volt Free ContactHigh sewage/drainage level alarm 3 Level Switch 3 To be supplied by OthersLow sewage/drainage level alarm 3 Level Switch 3 To be supplied by Others

    8 Parking Fans, EF-QQ01-PK1-3/4/5/6/7/8/9Fan Start/Stop 8 8 Interface RelayFan Status (On/Off) 8 8 Volt Free ContactFan Normal/Fault (Trip) 8 8 Volt Free ContactProof of Flow 8 P233A-10-AHC 8 Diff. Pressure Switch for FanHOA Position 8 8 Volt Free Contact

    2 MOTORIZED DAMPERS (for PF-QQ01-BU2-3 to BU3-3)Motorized Damper Status 4 4 Voltage Free Contact

    81 14 15 3 11324 27 18 12 LP-FX16X04-000C 3 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleLP-XT91D00-000C 4 Extension ModuleELK 3.0 1 DDC Panel

    Spare Points 7 13 3 9 32 28% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 4 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK-1-41 EMDB-2

    Main Incoming CBsC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactPower Fail Alarm 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485

    13 Outgoing Feeder CBsC.B. or Contactor On Status 13 13 Volt Free ContactC.B. or Contactor Tripped Status 13 13 Volt Free Contact

    1 MDB-2Main Incoming CBsC.B. or Contactor On Command 1 1 Volt Free ContactC.B. or Contactor Off Command 1 1 Volt Free ContactC.B. or Contactor On Status 1 1 Volt Free ContactC.B. or Contactor Off Status 1 1 Volt Free ContactC.B. or Contactor Tripped Status 1 1 Volt Free ContactAvailability of Power Status 1 1 Volt Free ContactPower Fail Alarm 1 1 Volt Free ContactCurrent/Phase 1 Interface via RS-485Voltage/Phase/Line 1 Interface via RS-485Power Factor 1 Interface via RS-485

    13 Outgoing Feeder CBsC.B. or Contactor On Status 13 13 Volt Free ContactC.B. or Contactor Tripped Status 13 13 Volt Free Contact

    1 ATS-2Generator Position 1 1 Volt Free ContactTransformer Position 1 1 Volt Free ContactBy Pass Generator Position 1 1 Volt Free ContactBy Pass Transformer Position 1 1 Volt Free Contact

    1 Generator -2Run Status 1 1 Volt Free ContactGeneral Alarm 1 1 Volt Free Contact

    3 Lighting Control System (PP/PK1-2)Power supply status of lighting control panels 3 3 Volt Free ContactSwitching ON/OFF of various lighting circuits 3 3 Interface Relay

    4 Parking Fans (EF-QQ01-PK1-4/5/6/)Fan Start/Stop 4 8 Interface RelayFan Status (On/Off) 4 8 Volt Free ContactFan Normal/Fault (Trip) 4 8 Volt Free ContactProof of Flow 4 P233A-10-AHC 4 Diff. Pressure Switch for FanHOA Position 4 8 Volt Free ContactHOA Position 4 8 Volt Free Contact

    1 FM200FM200 LINE PRESSURE 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    90 11 4 0 10524 27 18 12 LP-FX16X04-000C 3 BACnet Direct Digital Controller72 LP-XP91D05-000C 9 8 DI Expansion Module

    LP-XT91D00-000C 5 Extension ModuleELK 2.0 1 DDC Panel

    Spare Points 6 16 14 12 48 46% Spare points

    328 44 33 6 411

    12 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 12 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 12 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 12 Room Sensor Module

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 5 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    CARPARK LEVEL 2QQ01-DGP-PK2-1EMCC/PK2-4

    2 Parking Fans (EF-QQ1-PK1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK1-1)Motorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK2-1)Motorized Damper Status 8 8 Voltage Free Contact

    5 Parking Fans (EF-QQ1-PK2-3/4/5)Fan Start/Stop 5 5 Interface RelayFan Status (On/Off) 5 5 Volt Free ContactFan Normal/Fault (Trip) 5 5 Volt Free ContactProof of Flow 5 P233A-10-AHC 5 Diff. Pressure Switch for FanHOA Position 5 5 Volt Free Contact

    1 FM200FM200 LINE PRESSURE (CONTROL/TELE) 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    3 Lighting Control System (PP/PK2-3)Power supply status of lighting control panels 3 3 Volt Free ContactSwitching ON/OFF of various lighting circuits 3 3 Interface Relay

    2 MOTORIZED DAMPERS (for PF-QQ01-BU1-3 & BU4-3)Motorized Damper Status 4 4 Voltage Free Contact

    62 12 4 0 7816 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller48 LP-XP91D05-000C 6 8 DI Expansion Module

    LP-XT91D00-000C 3 Extension ModuleELK 2.0 1 DDC Panel

    Spare Points 2 6 8 8 24 31% Spare points

    QQ01-DGP-PK2-2EMCC/PK2-2

    1 OUTDOOR AHU WITH COOLING COIL w/ 2-WAY VALVE (AHU-QQ01-PK2-1)Supply Air Temperature 1 TE-6311P-1 1 Duct Temp. SensorSupply Fan Start/Stop 1 1 Interface RelaySupply Fan Start/Stop 1 1 Interface RelaySupply Fan Status (On/Off) 1 1 Current SensorSupply Fan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanFresh Air Damper Control 1 M9108-AGC-1 1 Damper Actuator on/off type 8 N.M., 24 Vac Fresh Air Damper Status 1Pre-Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchBag Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchChilled Water Valve Control (AHU-QQ01-PK2-1) 1 VG12A5GS+94NGGC 1 2-way Valve (65mm, CV=47) with Mod. ActuatorChilled Water Valve Position 1Solenoid Valve Control 1 Solenoid Valve By OthersSolenoid Valve Position 1Smoke Detection 1HOA Position 1 1 Volt Free ContactFire Alarm Signal 1

    2 Parking Fans (EF-QQ1-PK1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK1-1)Motorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK2-1)Motorized Damper Status 8 8 Voltage Free Contact

    5 Parking Fans (EF-QQ1-PK2-3/5/6)Fan Start/Stop 5 5 Interface RelayFan Status (On/Off) 5 5 Volt Free ContactFan Normal/Fault (Trip) 5 5 Volt Free ContactProof of Flow 5 P233A-10-AHC 5 Diff. Pressure Switch for FanHOA Position 5 5 Volt Free Contact

    3 Lighting Control System (PP/PK2-1)Power supply status of lighting control panels 3 3 Volt Free ContactSwitching ON/OFF of various lighting circuits 3 3 Interface Relay

    1 FM200FM200 LINE PRESSURE (CONTROL/TELE) 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    68 15 6 1 9016 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller56 LP-XP91D05-000C 7 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 4 3 6 7 20 22% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 6 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK2-3EMCC/PK2-1

    2 Parking Fans (EF-QQ1-PK1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK1-1)Motorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK2-1)Motorized Damper Status 8 8 Voltage Free Contact

    4 Parking Fans (EF-QQ1-PK2-2/3/5)Fan Start/Stop 4 4 Interface RelayFan Status (On/Off) 4 4 Volt Free ContactFan Normal/Fault (Trip) 4 4 Volt Free ContactProof of Flow 4 P233A-10-AHC 4 Diff. Pressure Switch for FanHOA Position 4 4 Volt Free Contact

    1 FM200FM200 LINE PRESSURE (CONTROL/TELE) 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    2 MOTORIZED DAMPERS (for PF-QQ01-BU2-3 & BU3-3)Motorized Damper Status 4 4 Voltage Free Contact

    55 8 4 0 6716 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller40 LP-XP91D05-000C 5 8 DI Expansion Module

    LP-XT91D00-000C 3 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 1 10 8 8 27 42% Spare points

    QQ01-DGP-PK2-4EMCC/PK2-3

    2 Parking Fans (EF-QQ1-PK1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK1-1)Motorized Damper Status 8 8 Voltage Free ContactMotorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK2-1)Motorized Damper Status 8 8 Voltage Free Contact

    9 Parking Fans (EF-QQ1-PK2-4/5/6/7/8Fan Start/Stop 9 9 Interface RelayFan Status (On/Off) 9 9 Volt Free ContactFan Normal/Fault (Trip) 9 9 Volt Free ContactProof of Flow 9 P233A-10-AHC 9 Diff. Pressure Switch for FanHOA Position 9 9 Volt Free Contact

    1 FM200FM200 LINE PRESSURE (CONTROL/TELE) 4 by others 4 0-10Vdc signal to DDC FM200 CONTROL PANEL ALARM 1 1 VFC to DDC FM200 CONTROL PANEL NORMAL FAULT 1 1 VFC to DDC FM200 CONTROL PANEL POWER STATUS 1 1 VFC to DDC

    2 Lighting Control System (PP/PK2-2)Power supply status of lighting control panels 2 2 Volt Free ContactSwitching ON/OFF of various lighting circuits 2 2 Interface Relay

    73 15 4 0 9216 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 7 3 8 8 26 133% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 7 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-PK2-5EMCC/PK2-5

    2 Parking Fans (EF-QQ1-PK1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK1-1)Motorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    4 MOTORIZED DAMPERS (FOR EF-QQ01-PK2-1)Motorized Damper Status 8 8 Voltage Free Contact

    2 Parking Fans (EF-QQ1-PK2-4/5)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    40 6 0 0 468 9 6 4 LP-FX16X04-000C 1 BACnet Direct Digital Controller

    32 LP-XP91D05-000C 4 8 DI Expansion ModuleLP-XT91D00-000C 2 Extension Module

    ELK 2.5 1 DDC PanelSpare Points 0 3 6 4 13 133% Spare points

    PK2 298 56 18 1 373

    29 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 29 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 29 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 29 Room Sensor Module

    QQ01-BUILDING 1QQ01-DGP-B1-3F-1First Floor

    5 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 5 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 5 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 5 Room Sensor Module

    7 Lighting Control System (LP/LS-1)Power supply status of lighting control panels 7 7 Volt Free ContactSwitching ON/OFF of various lighting circuits 7 7 Interface RelaySwitching ON/OFF of various lighting circuits 7 7 Interface Relay

    8 Lighting Control System (PP/B1-L1-1)Power supply status of lighting control panels 8 8 Volt Free ContactSwitching ON/OFF of various lighting circuits 8 8 Interface Relay

    1 MOTORIZED DAMPERS (For PF-QQ01-BU1-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactSecond Floor

    5 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 5 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 5 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 5 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU1-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactThird Floor

    5 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 5 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 5 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 5 Room Sensor Module

    8 Lighting Control System PP/B1-L3-1Power supply status of lighting control panels 8 8 Volt Free ContactSwitching ON/OFF of various lighting circuits 8 8 Interface Relay

    1 MOTORIZED DAMPERS (For PF-QQ01-BU1-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactFourth Floor

    4 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 4 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 4 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 4 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU1-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free Contact

    87 23 0 0 11024 27 18 12 LP-FX16X04-000C 3 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 1 4 18 12 35 32% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 8 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    ROOF FLOORQQ01-DGP-B1-RF-1

    2 PRESSURIZATION FANS (PF-QQ01-BU1-1)HOA Position 2 2 Volt Free ContactFan Start (Fire Alarm Signal) 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU1-2)HOA Position 2 2 Volt Free ContactFan Start (Fire Alarm Signal) 2 2 Volt Free ContactFan Start (Fire Alarm Signal) 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU1-3)HOA Position 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU1-4)HOA Position 2 2 Volt Free ContactFan Start (Fire Alarm Signal) 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    4 MOTORIZED DAMPERS (For PF-QQ01-BU1-1)Motorized Damper Status 8 8 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU1-2)Motorized Damper Status 8 8 Voltage Free Contact

    5 MOTORIZED DAMPERS (For PF-QQ01-BU1-3)Motorized Damper Status 10 10 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU1-4)Motorized Damper Status 8 8 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU1-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free Contact

    1 PRESSURE RELIEF DAMPERS (For PF-QQ01-BU1-1)Motorized Damper Status 2 2 Voltage Free Contact

    3 EXHAUST FAN (EF-QQ01-BU1-1 to BU1-2)Fan Start/Stop 3 3 Interface RelayFan Status (On/Off) 3 3 Volt Free ContactFan Normal/Fault (Trip) 3 3 Volt Free ContactProof of Flow 3 P233A-10-AHC 3 Diff. Pressure Switch for FanHOA Position 3 3 Volt Free ContactHOA Position 3 3 Volt Free Contact

    2 SMOKE EXHAUST FAN (SEF-QQ01-BU1-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    1 CORRIDOR SUPPLY FAN (SF-QQ01-BU1-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for Fan

    107 14 0 0 12124 27 18 12 LP-FX16X04-000C 3 BACnet Direct Digital Controller88 LP-XP91D05-000C 11 8 DI Expansion Module

    LP-XT91D00-000C 6 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 5 13 18 12 48 40% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 9 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-B1-RF-23 Lifts

    Run Status 3 3 Volt Free ContactGeneral Alarm 3 3 Volt Free ContactRoof Domestic Water Storage Tanks

    3 PUMPSPump Status 3 P74DA-19C 3 Diff Pressure SwitchPump Normal/Fault 3 3 Volt Free ContactHOA Position 3 3 Volt Free ContactVSD Speed Display 3 Communication InterfaceVSD Speed Control 3 3 0-10vdc to VSDVSD Normal/Fault 3 3 Volt Free ContactVSD Status 3 3 0-10vdc from VFD

    1 Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor1 GRP Water Break Tank 2 Level Switch 2 By Others2 Roof Water Tank 2 Level Switch 2 By Others1 OUTDOOR AIR HANDLING UNIT WITH

    COOLING COIL WITH 2-WAY VALVESupply Air Temperature 1 TE-6311P-1 1 Duct Temp. SensorSupply Fan Start/Stop 1 1 Interface RelaySupply Fan Status (On/Off) 1 1 Current SensorSupply Fan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanFresh Air Damper Control 1 M9108-AGC-1 1 Damper Actuator on/off type 8 N.M., 24 Vac Fresh Air Damper Status 1Pre-Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchBag Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchChilled Water Valve Control (AHU-QQ01-BU1-1) 1 VG18A5GS+94NGGC 1 3-way Valve (65mm, CV=47) with Mod. ActuatorChilled Water Valve Position 1Coil Differential Pressure 1 DPT2301-050D 1 Differential Pressure SensorSolenoid Valve Control 1 Solenoid Valve By OthersSolenoid Valve Position 1 By OthersSmoke Detection 1 By OthersHOA Position 1 1 Volt Free ContactFire Alarm Signal 1 By Others

    28 3 11 4 468 9 6 4 LP-FX16X04-000C 1 BACnet Direct Digital Controller

    6 2 LP-XP91D02-000C 1 6AI / 2 AO Expansion Module24 LP-XP91D05-000C 3 8 DI Expansion Module

    LP-XT91D00-000C 2 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 4 6 1 2 13 28% Spare points

    4 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 4 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 4 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 4 Room Sensor ModuleRoom Sensor Module RS-1180-0000 4 Room Sensor Module

    222 40 11 4 277

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 10 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-BUILDING 2QQ01-DGP-B2-3F-1First Floor

    5 Lighting Control System PP/B2-L1-1Power supply status of lighting control panels 5 5 Volt Free ContactSwitching ON/OFF of various lighting circuits 5 5 Interface Relay

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU2-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactSecond Floor

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU2-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactThird Floor

    6 Lighting Control System PP/B2-L3-1Power supply status of lighting control panels 6 6 Volt Free ContactSwitching ON/OFF of various lighting circuits 6 6 Interface Relay

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU2-3)Motorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free ContactFourth Floor

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU2-3)Motorized Damper Status 2 2 Voltage Free ContactMotorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free Contact

    75 11 0 0 8616 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 5 7 12 8 32 37% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 11 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    ROOF FLOORQQ01-DGP-B2-RF-1

    2 PRESSURIZATION FANS (PF-QQ01-BU2-1)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU2-2)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU2-3)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    1 PRESSURE RELIEF DAMPERS (For PF-QQ01-BU2-1)Motorized Damper Status 2 2 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU2-1)Motorized Damper Status 8 8 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU2-2)Motorized Damper Status 8 8 Voltage Free Contact

    5 MOTORIZED DAMPERS (For PF-QQ01-BU2-3)Motorized Damper Status 10 10 Voltage Free Contact

    4 MOTORIZED DAMPERS (For SEF-QQ01-BU2-1) Damper Actuator to be supplied by othersMotorized Damper Status 8 8 Voltage Free Contact

    2 Fan (EF-QQ01-BU2-1 to BU2-2)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    2 SMOKE Fan (SEF-QQ01-BU2-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    1 CORRIDOR SUPPLY FAN (SF-QQ01-BU2-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for Fan

    85 11 0 0 9624 27 18 12 LP-FX16X04-000C 3 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 3 16 18 12 49 51% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 12 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-B2-RF-22 Lifts

    Run Status 2 Volt Free ContactGeneral Alarm 2 Volt Free ContactRoof Domestic Water Storage Tanks

    3 PUMPSPump Status 3 P74DA-19C 3 Diff Pressure SwitchPump Normal/Fault 3 3 Volt Free ContactHOA Position 3 3 Volt Free ContactVSD Speed Display 3 Communication InterfaceVSD Speed Control 3 3 0-10vdc to VSDVSD Normal/Fault 3 3 Volt Free ContactVSD Status 3 3 0-10vdc from VFD

    1 Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor1 GRP Water Break Tank 2 Level Switch By Others2 Roof Water Tank 2 Level Switch By Others1 OUTDOOR AIR HANDLING UNIT WITH

    COOLING COIL WITH 2-WAY VALVESupply Air Temperature 1 TE-6311P-1 1 Duct Temp. SensorSupply Fan Start/Stop 1 1 Interface RelaySupply Fan Status (On/Off) 1 1 Current SensorSupply Fan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanFresh Air Damper Control 1 M9108-AGC-1 1 Damper Actuator on/off type 8 N.M., 24 Vac Fresh Air Damper Status 1Pre-Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchBag Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchChilled Water Valve Control (AHU-QQ01-BU2-1) 1 VG12A5GS+94NGGC 1 2-way Valve (65mm, CV=47) with Mod. ActuatorChilled Water Valve Position 1Coil Differential Pressure 1 DPT2301-050D 1 Differential Pressure SensorSolenoid Valve Control 1 Solenoid Valve By OthersSolenoid Valve Position 1Smoke Detection 1HOA Position 1 1 Volt Free ContactFire Alarm Signal 1 1 Volt Free Contact

    26 3 11 4 448 9 6 4 LP-FX16X04-000C 1 BACnet Direct Digital Controller

    6 2 LP-XP91D02-000C 1 6AI / 2 AO Expansion Module24 LP-XP91D05-000C 3 8 DI Expansion Module

    LP-XT91D00-000C 2 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 6 6 1 2 15 34% Spare points1 FAN COIL UNITS

    FX03 Bacnet FCU Controller LP-FX03A11-0C 1 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 1 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 1 Room Sensor Module

    186 25 11 4 226

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 13 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-BUILDING 3QQ01-DGP-B3-3F-1First Floor

    3 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 3 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 3 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 3 Room Sensor Module

    7 Lighting Control System PP/B3-L1-1Power supply status of lighting control panels 7 7 Volt Free ContactSwitching ON/OFF of various lighting circuits 7 7 Interface Relay

    1 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SEF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free ContactSecond Floor

    3 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 3 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 3 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 3 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SEF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free ContactThird Floor

    3 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 3 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 3 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 3 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SEF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free ContactFourth Floor

    6 Lighting Control System PP/B3-L4-1Power supply status of lighting control panels 6 18 Volt Free ContactSwitching ON/OFF of various lighting circuits 6 18 Interface Relay

    3 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 3 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 3 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 3 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 2 2 Voltage Free ContactMotorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SEF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free ContactFifth Floor

    3 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 3 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 3 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 3 Room Sensor Module

    1 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 2 2 Voltage Free Contact

    1 MOTORIZED DAMPERS (For SF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 2 2 Voltage Free Contact

    3 MOTORIZED DAMPERS (For SEF-QQ01-BU3-1) Damper Actuator to be supplied by othersMotorized Damper Status 6 6 Voltage Free Contact

    59 13 0 0 7216 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller48 LP-XP91D05-000C 6 8 DI Expansion Module

    LP-XT91D00-000C 3 Extension ModuleELK 3.0 1 DDC Panel

    Spare Points 5 5 12 8 30 42% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 14 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    ROOF FLOORQQ01-DGP-B3-RF-1

    2 PRESSURIZATION FANS (PF-QQ01-BU3-1)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU3-2)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU3-3)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    1 PRESSURE RELIEF DAMPERS (For PF-QQ01-BU3-1)Motorized Damper Status 2 2 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU3-1)Motorized Damper Status 8 8 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU3-2)Motorized Damper Status 8 8 Voltage Free Contact

    5 MOTORIZED DAMPERS (For PF-QQ01-BU3-3)Motorized Damper Status 10 10 Voltage Free Contact

    2 Exhaust Fan (EF-QQ01-BU3-1 )Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    2 Smoke Exhaust Fan (SEF-QQ01-BU3-1)Fan Start/Stop 2 2 Interface RelayFan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for FanHOA Position 2 2 Volt Free Contact

    1 CORRIDOR SUPPLY FAN (SF-QQ01-BU3-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for Fan

    77 11 0 0 8816 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller64 LP-XP91D05-000C 8 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.5 1 DDC Panel

    Spare Points 3 7 12 8 30 34% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 15 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-B3-RF-23 Lifts

    Run Status 3 3 Volt Free ContactGeneral Alarm 3 3 Volt Free ContactRoof Domestic Water Storage Tanks

    3 PUMPSPump Status 3 P74DA-19C 3 Diff Pressure SwitchPump Normal/Fault 3 3 Volt Free ContactHOA Position 3 3 Volt Free ContactVSD Speed Display 3 Communication InterfaceVSD Speed Control 3 3 0-10vdc to VSDVSD Normal/Fault 3 3 Volt Free ContactVSD Status 3 3 0-10vdc from VFD

    1 Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor1 GRP Water Break Tank 2 Level Switch 2 By Others2 Roof Water Tank 2 Level Switch 2 By Others1 OUTDOOR AIR HANDLING UNIT WITH

    COOLING COIL WITH 2-WAY VALVESupply Air Temperature 1 TE-6311P-1 1 Duct Temp. SensorSupply Fan Start/Stop 1 1 Interface RelaySupply Fan Status (On/Off) 1 P233A-10-AHC 1 Diff Pressure SwitchSupply Fan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanFresh Air Damper Control 1 M9108-AGC-1 1 Damper Actuator on/off type 8 N.M., 24 Vac Fresh Air Damper Status 1 1Pre-Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchBag Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchChilled Water Valve Control (AHU-QQ01-BU3-1) 1 VG18A5GS+94NGGC 1 3-way Valve (65mm, CV=47) with Mod. ActuatorChilled Water Valve Position 1 1Coil Differential Pressure 1 DPT2301-050D 1 Differential Pressure SensorSolenoid Valve Control 1 Solenoid Valve 1 By OthersSolenoid Valve Position 1 1Smoke Detection 1 1HOA Position 1 1 Volt Free ContactFire Alarm Signal 1 1

    28 3 11 4 468 9 6 4 LP-FX16X04-000C 1 BACnet Direct Digital Controller

    6 2 LP-XP91D02-000C 1 6AI / 2 AO Expansion Module24 LP-XP91D05-000C 3 8 DI Expansion Module

    LP-XT91D00-000C 2 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 4 6 1 2 13 28% Spare points

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor ModuleRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    164 27 11 4 206

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 16 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-BUILDING 4QQ01-DGP-B4-3F-1First Floor

    5 Lighting Control System PP/B4-L1-1Power supply status of lighting control panels 5 5 Volt Free ContactSwitching ON/OFF of various lighting circuits 5 5 Interface Relay

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    3 MOTORIZED DAMPERS (For PF-Q01-BU4-3) Damper Actuator to be supplied by othersMotorized Damper Status 6 2 Voltage Free Contact

    2 MOTORIZED DAMPERS (For SEF-Q01-BU4-1) Damper Actuator to be supplied by othersMotorized Damper Status 4 2 Voltage Free ContactSecond Floor

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    3 MOTORIZED DAMPERS (For PF-Q01-BU4-3)Motorized Damper Status 6 2 Voltage Free Contact

    2 MOTORIZED DAMPERS (For SEF-Q01-BU4-1) Damper Actuator to be supplied by othersMotorized Damper Status 4 2 Voltage Free ContactThird Floor

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    3 MOTORIZED DAMPERS (For PF-Q01-BU4-3)Motorized Damper Status 6 2 Voltage Free Contact

    2 MOTORIZED DAMPERS (For SEF-Q01-BU4-1) Damper Actuator to be supplied by othersMotorized Damper Status 4 2 Voltage Free ContactFourth Floor

    4 Lighting Control System PP/B4-L4-1Power supply status of lighting control panels 4 4 Volt Free ContactSwitching ON/OFF of various lighting circuits 4 4 Interface Relay

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    3 MOTORIZED DAMPERS (For PF-Q01-BU4-3)Motorized Damper Status 6 2 Voltage Free Contact

    2 MOTORIZED DAMPERS (For SEF-Q01-BU4-1) Damper Actuator to be supplied by othersMotorized Damper Status 4 2 Voltage Free ContactFifth Floor

    2 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 2 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + Modulating20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 2 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 2 Room Sensor Module

    3 MOTORIZED DAMPERS (For PF-Q01-BU4-3)Motorized Damper Status 6 2 Voltage Free Contact

    2 MOTORIZED DAMPERS (For SEF-Q01-BU4-1) Damper Actuator to be supplied by othersMotorized Damper Status 4 2 Voltage Free Contact

    59 9 0 0 6816 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller48 LP-XP91D05-000C 6 8 DI Expansion Module

    LP-XT91D00-000C 3 Extension ModuleELK 2.5 1 DDC Panel

    Spare Points 5 9 12 8 34 50% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 17 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    ROOF FLOORQQ01-DGP-B4-RF-1

    2 PRESSURIZATION FANS (PF-QQ01-BU4-1)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU4-2)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    2 PRESSURIZATION FANS (PF-QQ01-BU4-3)HOA Position 2 2 Volt Free ContactFan Start 2 2 Volt Free ContactFan Start/Stop 2 2 Interface Relay Fan Status (On/Off) 2 2 Volt Free ContactFan Normal/Fault (Trip) 2 2 Volt Free ContactProof of Flow 2 P233A-10-AHC 2 Diff. Pressure Switch for Fan

    1 PRESSURE RELIEF DAMPERS (For PF-QQ01-BU4-1)Motorized Damper Status 2 2 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU4-1)Motorized Damper Status 8 8 Voltage Free Contact

    4 MOTORIZED DAMPERS (For PF-QQ01-BU4-2)Motorized Damper Status 8 8 Voltage Free Contact

    5 MOTORIZED DAMPERS (For PF-QQ01-BU4-3)Motorized Damper Status 10 10 Voltage Free Contact

    1 Fan (EF-QQ01-BU4-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanHOA Position 1 1 Volt Free Contact

    1 SMOKE Fan (SEF-QQ01-BU4-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanHOA Position 1 1 Volt Free Contact

    1 CORRIDOR SUPPLY FAN (SF-QQ01-BU4-1)Fan Start/Stop 1 1 Interface RelayFan Status (On/Off) 1 1 Volt Free ContactFan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for Fan

    69 9 0 0 7816 18 12 8 LP-FX16X04-000C 2 BACnet Direct Digital Controller56 LP-XP91D05-000C 7 8 DI Expansion Module

    LP-XT91D00-000C 4 Extension ModuleELK 3.0 1 DDC Panel

    Spare Points 3 9 12 8 32 41% Spare points

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 18 of 19

    Date Created: December 23, 2008

    Date Revised: March 17, 2010

  • Project: THE PEARL - QANAT QUARTIER (Apartment) J46 , Doha, Qatar

    Qty DESCRIPTION DI DO AI AO Control Device QTY REMARKS

    BMS INPUT/OUTPUT SUMMARY

    QQ01-DGP-B4-RF-21 Lifts

    Run Status 1 Volt Free ContactGeneral Alarm 1 Volt Free ContactRoof Domestic Water Storage Tanks

    2 PUMPSPump Status 2 P74DA-19C 2 Diff Pressure SwitchPump Normal/Fault 2 2 Volt Free ContactHOA Position 2 2 Volt Free ContactVSD Speed Display 2 Communication InterfaceVSD Speed Control 2 2 0-10vdc to VSDVSD Normal/Fault 2 2 Volt Free ContactVSD Status 2 2 0-10vdc from VFD

    1 Line Pressure 1 P299EAB-2C 1 Water Pressure Sensor1 GRP Water Break Tank 2 Level Switch By Others2 Roof Water Tank 2 Level Switch By Others1 OUTDOOR AIR HANDLING UNIT WITH

    COOLING COIL WITH 2-WAY VALVESupply Air Temperature 1 TE-6311P-1 1 Duct Temp. SensorSupply Fan Start/Stop 1 1 Interface RelaySupply Fan Status (On/Off) 1 1 Volt Free ContactSupply Fan Normal/Fault (Trip) 1 1 Volt Free ContactProof of Flow 1 P233A-10-AHC 1 Diff. Pressure Switch for FanFresh Air Damper Control 1 M9108-AGC-1 1 Damper Actuator on/off type 8 N.M., 24 Vac Fresh Air Damper Status 1Pre-Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchBag Filter Status 1 P233A-4-AHC 1 Diff. Pressure SwitchChilled Water Valve Control (AHU-QQ01-BU4-1) 1 VG1245EP+956GGC 1 2-way Valve (40mm, CV=18.7) with Mod. ActuatorChilled Water Valve Position 1 1Coil Differential Pressure 1 DPT2301-050D 1 Differential Pressure SensorSolenoid Valve Control 1 Solenoid Valve 1 By OthersSolenoid Valve Position 1 1 By OthersSmoke Detection 1 1HOA Position 1 1 Volt Free ContactFire Alarm Signal 1 1

    20 3 10 3 368 9 6 4 LP-FX16X04-000C 1 BACnet Direct Digital Controller

    6 2 LP-XP91D02-000C 1 6AI / 2 AO Expansion Module16 LP-XP91D05-000C 2 8 DI Expansion Module

    LP-XT91D00-000C 2 Extension ModuleELK 2.0 1 DDC Panel

    Spare Points 4 6 2 3 15 42% Spare points

    1 FAN COIL UNITSFX03 Bacnet FCU Controller LP-FX03A11-0C 1 FCU Controller20mm Motorized Valve + Modulating VG4400GC + VA-7060-21 1 20mm Motorized Valve + ModulatingRoom Sensor Module RS-1180-0000 1 Room Sensor Module

    148 21 10 3 182

    Other SystemHome Automation System Interface via software integration

    Total Project Points - QQ1 Buildings 1161 188 86 22 1457

    Originator: Buddy R. Ropan, Jr.

    File Name: QQ Updated BMS Points List.xlsx

    Sheet Name: QQ01 IO Summary Updated Page 19 of 19