ADT490 TroubleShootingLocating Opens A
![Page 2: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/2.jpg)
2
Introduction
• Breakdown in Circuit Integrity -> Trouble• Metallic continuity interrupted
• an “open” occurs
• System Trouble LED is lit.
• Open on a conventional Initiating circuit• Yellow Zone LED -> on
![Page 3: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/3.jpg)
3
Introduction
‣ Open on signal circuit indicate ‣ circuit is Open
‣ “Circuit” or “NAC” yellow LED
‣ System Trouble‣ LED
‣ Buzzer
3
![Page 4: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/4.jpg)
4
Introduction
‣ Class B Initiating circuit :
4
![Page 5: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/5.jpg)
5
Typical Input Circuit
‣ Continuous power 24 Vdc≅
‣ EOL Installed after last device‣ Regulates current 5 to 6 mA≅
‣ Current called -> supervisory current‣ Break -> current stops -> 0 mA‣ Sketch – why no supervisory current‣ Insert Multimeter (series) at FACP, set to mA -> 0.0 mA‣ Insert Multimeter (parallel) at FACP, set to V -> 25 Vdc
5
![Page 6: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/6.jpg)
6
Typical Input Circuit
‣ Break -> ome devices still operate‣ If 1st device is a Manual Station Operated
‣ Places short on circuit prior to break (still powered)‣ Causes Alarm Condition
‣ Remaining three devices electrically disconnected‣ Cannot cause Alarm
‣ Devices panel side of break – function‣ Device on EOL side of break - inoperable
6
![Page 7: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/7.jpg)
7
Simple Exercise - 1
‣ Example of using senses, logic and DMM to find an open circuit in a simple Class B circuit
‣ Imagine the circuit in Trouble is on Zone 2 on a 4 Zone FACP
‣ In this Apartment Building Zone 2 is the entire Second Floor
7
![Page 8: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/8.jpg)
8
Simple Exercise - 2
8
![Page 9: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/9.jpg)
9
Simple Exercise - 3
‣ Wire disconnected somewhere on this circuit.‣ “Disconnected” implies what type of a circuit fault?
____________________________
‣ What will FACP to tell us?
1) _____________________________
2) ____________________________
9
![Page 10: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/10.jpg)
10
Simple Exercise - 4
Visit 2nd floor. ‣ What will suggest where the open has
occurred?
1)_______________________________________
2)_______________________________________
10
![Page 11: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/11.jpg)
11
Simple Exercise - 5
The raceway layout might look like this:
11
![Page 12: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/12.jpg)
12
Simple Exercise - 6
After a visual inspection‣ open location not obvious (hanging device, damage
caused by renovation or repair, etc.), and‣ will probably require some meter work to locate it.‣ Visual inspection suggests problem -> middle to end
of circuit
12
![Page 13: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/13.jpg)
13
Simple Exercise - 7
What clue(s)?Remember:
“Any device on the panel side of a break in a Class B circuit will continue to work, while any device after the break is inoperable”.
1)____________________________________
2)____________________________________
13
![Page 14: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/14.jpg)
14
Simple Exercise - 8
Inspection -> both hallway smokes flashing LEDsFirst Manual Station workedLast one did not. Let’s look at the circuit again:
14
![Page 15: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/15.jpg)
15
Simple Exercise - 9
Open circuit has occurred between the last smoke detector and last Manual Station.
we haven’t to access into any suites.
15
![Page 16: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/16.jpg)
16
Simple Exercise - 10
‣ Convenient test point is second smoke because:
__________________________________and, because of the way the conduit is run,we can_______________________________
16
![Page 17: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/17.jpg)
17
Simple Exercise - 11
Remove the second smoke & Check with Meter
17
![Page 18: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/18.jpg)
18
Simple Exercise - 12
Meter to conductors into octagon-box from the FACP.
What should meter be set for?_______________________________
What reading is expected (app.)?______________________________
18
![Page 19: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/19.jpg)
19
Simple Exercise - 13
We got what we were looking forLook the other way down the circuit to the EOL.Locate other two wires removed from smoke detector.
19
![Page 20: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/20.jpg)
20
Simple Exercise - 14Do we leave the meter as previously set?
________________
What setting is going to be helpful?________________
If this part good (pretty sure it isn’t)What read should we expect? (app.)? _______
With circuit open between Test Point and the EOL What reading will you get? _____________________
20
![Page 21: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/21.jpg)
21
Simple Exercise - 15
Wiring looks like this:
21
![Page 22: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/22.jpg)
22
Simple Exercise - 16
22
![Page 23: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/23.jpg)
23
Simple Exercise - 17
Open is between octagon box and the EOL.
23
![Page 24: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/24.jpg)
24
Simple Exercise - 18
Resistance reading of 4.8 kΩ, seeing EOL.
Open is not between the octagon box and the EOL.
Open has seemingly between the heat detector in suite 203 or the heat detector in suite 204.
24
![Page 25: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/25.jpg)
25
Simple Exercise - 19Remove remaining Marrettes and short together RED and BLACK going to Suite 204.
Put your DMM (on resistance) across the returning blue and brown wires.
If shorted (0 Ω) -> the wires intact & connected to the detector -> wires to Suite 204 OK
25
![Page 26: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/26.jpg)
26
Simple Exercise - 20
26
![Page 27: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/27.jpg)
27
Simple Exercise - 21
Apply same routine and find there is an open-> DMM’s resistance is infinity.
27
![Page 28: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/28.jpg)
28
Simple Exercise - 22
28
![Page 29: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/29.jpg)
29
Simple Exercise - 23Access 203Dismount the detector &Blue wire broken off detector’s terminal screw,
-> causes open circuit.
Re-strip &re-connect blue wireRemake the connections in the octagon boxRe-mount the heat detector. Check to see that the FACP is clear.
29
![Page 30: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/30.jpg)
30
Discussion
How to troubleshoot an open on a Class A circuit?Typically a Class A looks like this:
30
![Page 31: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/31.jpg)
31
Discussion
1) There are 4 wires associated with the Class A “loop”, 2 leaving the panel and 2 returning.
2) The EOL function is inside the FACP.3) The circuit is actually working like a Class B loop, in
the normal mode.4) The arrows represent 2 “switches” that are “open
state”
31
![Page 32: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/32.jpg)
32
Discussion
When open occurs relay causes switches to close
Feeds the voltage to the other side of the open
32
![Page 33: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/33.jpg)
33
DiscussionAn open/break occurred. 1) FACP senses drop in current on loop and closes
the two “switches” (as indicated by the arrows).2) Now we have +24VDC being supplied to the 4th
terminal, and the 0VDC reference being supplied to the 3rd terminal.
3) The FACP is now back feeding the operating voltage and current to the devices beyond the break.
4) ALL DEVICES CONTINUE TO FUNCTION.
33
![Page 34: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/34.jpg)
34
Discussion
All devices work -> smoke detectors flash LED’s-> location of break more difficult to find
34
![Page 35: ADT490 TroubleShooting Locating Opens A. 2 Introduction Breakdown in Circuit Integrity -> Trouble Metallic continuity interrupted an “ open ” occurs System.](https://reader036.fdocuments.net/reader036/viewer/2022081520/5697c0011a28abf838cc223c/html5/thumbnails/35.jpg)
35
endofpresentation