POWERDRIVE MD2S
Thismanual
istobegive
nto
theenduse
r
Variable speed drive
Installation and maintenance
en
M
IGBT IGBT IGBT
Micro-
controller
I/O control
Mains
supply
ASIC
PWM
Switching mode
power supply
(Optional
encoder
or sensor)
MDXEncoder(optional)
Control board
-
8/12/2019 4972b_en_MD2S
2/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
2
enINSTALLATION AND MAINTENANCE
Variable speed drive
NOTE
LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest
technological developments. The information contained in this document may therefore be changed without notice.
CAUTION
For the user's own safety, this variable speed drive must be connected to an approved earth terminal).
If accidentally starting the installation is likely to cause a risk to personnel or the machines being driven, it is essential to complywith the power connection diagrams recommended in this manual.
The variable speed drive is tted with safety devices which, in the event of a problem, control stopping and thus stop the motor. The
motor itself can become jammed for mechanical reasons. Voltage uctuations, and in particular power cuts, may also cause the
motor to stop. The removal of the causes of the shutdown can lead to restarting, which may be dangerous for certain machines or
installations.In such cases, it is essential that the user takes appropriate precautions against the motor restarting after an unscheduled stop.
The variable speed drive is designed to be able to supply a motor and the driven machine above its rated speed.
If the motor or the machine are not mechanically designed to withstand such speeds, the user may be exposed to serious dangerresulting from their mechanical deterioration.
Before programming a high speed, it is important that the user checks that the installation can withstand it.
The variable speed drive which is the subject of this manual is designed to be integrated in an installation or an electrical machine,
and can under no circumstances be considered to be a safety device. It is therefore the responsibility of the machine manufacturer,
the designer of the installation or the user to take all necessary precautions to ensure that the system complies with current
standards, and to provide any devices required to ensure the safety of equipment and personnel.
LEROY-SOMER declines all responsibility in the event of the above recommendations not being observed.
........................................
This manual only describes the general features, characteristics and installation of the POWERDRIVE MD2S. For
commissioning, refer to manual ref. 4617.
-
8/12/2019 4972b_en_MD2S
3/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
3
enINSTALLATION AND MAINTENANCE
Variable speed drive
SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES
(In accordance with the low voltage directive 2006/95/EC)
Throughout the manual, this symbol warns of
consequences which may arise from inappropriate
use of the drive, since electrical risks may lead to material
or physical damage as well as constituting a re hazard.
1 - General
Depending on their degree of protection, the variable speed
drives may contain unprotected live parts, which may be moving
or rotating, as well as hot surfaces, during operation.
Unjustied removal of protection devices, incorrect use, faulty
installation or inappropriate operation could represent a seriousrisk to personnel and equipment.
For further information, consult the documentation.
All work relating to transportation, installation, commissioning
and maintenance must be performed by experienced, qualied
personnel (see IEC 364, CENELEC HD 384 or DIN VDE 0100,as well as national specications for installation and accidentprevention).
In these basic safety instructions, qualied personnel means
persons competent to install, mount, commission and operate
the product and possessing the relevant qualications.
2 - Use
Variable speed drives are components designed for integration
in installations or electrical machines.
When integrated in a machine, commissioning must not take
place until it has been veried that the machine conforms
with directive 2006/42/EC (Machinery Directive). It is alsonecessary to comply with standard EN 60204, which stipulates
in particular that electrical actuators (which include variablespeed drives) cannot be considered as circuit-breaking devices
and certainly not as isolating switches.
Commissioning can take place only if the requirements of the
Electromagnetic Compatibility Directive (EMC 2004/108/EC)are met.
The variable speed drives meet the requirements of the Low
Voltage Directive 2006/95/EC. The harmonised standards
of the DIN VDE 0160 series in connection with standard VDE
0660, part 500 and EN 60146/VDE 0558 are also applicable.
The technical characteristics and instructions concerning theconnection conditions specied on the nameplate and in the
documentation provided must be observed without fail.
3 - Transportation, storageAll instructions concerning transportation, storage and correct
handling must be observed.The climatic conditions specied in the technical manual must
be observed.
4 - Installation
The installation and cooling of equipment must comply with thespecications in the documentation supplied with the product.
The variable speed drives must be protected against any
excessive stress. In particular, there must be no damage to
parts and/or modication of the clearance between components
during transportation and handling. Avoid touching the electronic
components and contact parts.The variable speed drives contain parts which are sensitive to
electrostatic stresses and may be easily damaged if handled
incorrectly. Electrical components must not be exposed to
mechanical damage or destruction (risks to health!).
5 - Electrical connection
When work is performed on variable speed drives which arepowered up, the national accident prevention regulations must
be respected.
The electrical installation must comply with the relevant
specications (for example conductor cross-sections, protection
via fused circuit-breaker, connection of protective conductor).
More detailed information is given in the documentation.Instructions for an installation which meets the requirements
for electromagnetic compatibility, such as screening, earthing,
presence of lters and correct insertion of cables and
conductors, are given in the documentation supplied with the
variable speed drives. These instructions must be followed
in all cases, even if the variable speed drive carries the CE
mark. Adherence to the limits given in the EMC legislation isthe responsibility of the manufacturer of the installation or the
machine.
6 - Operation
Installations in which variable speed drives are to be integrated
must be tted with additional protection and monitoring
devices as laid down in the current relevant safety regulations,
such as the law on technical equipment, accident prevention
regulations, etc. Modications to the variable speed drives
using control software are permitted.Active parts of the device and the live power connections must
not be touched immediately after the variable speed drive is
powered down, as the capacitors may still be charged. In view
of this, the warnings xed to the variable speed drives must beobserved.
Permanent magnet motors generate electrical energy whilethey are rotating, even when the drive is switched off. In this
case, the drive continues to be powered by the motor terminals.
If the load is capable of turning the motor, a switching device
must be provided upstream of the motor to isolate the drive
during maintenance operations.During operation, all doors and protective covers must be kept
closed.
7 - Servicing and maintenance
Refer to the manufacturers documentation.
See the Maintenance section in this document.
This manual is to be given to the end user.
-
8/12/2019 4972b_en_MD2S
4/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
4
enINSTALLATION AND MAINTENANCE
Variable speed drive
FOREWORD
This manual describes the installation of POWERDRIVE MD2Svariable speed drives. It also gives details of all its options and
extensions which the user may choose to suit his requirements.
POWERDRIVE MD2S
MDX-KEYPAD
MDX-SOFTParameter-setting
software+ PC link cable
MDX-Powerscreenparameter-setting
interface
Compabloc Axial output
- Helical gears
HPM motor
Orthobloc Orthogonal output
- Helical bevel gears
Radial
forcedventilation
LSES-FLSES motor
LSMV motor
LSRPM motor
Brake
Axial forcedventilation
Encoder/Sensor
MotorsGearboxes Motor options
OptionsParameter setting
IP 54 Cabinet baseplate (100 or 200 mm) Isolator switch High-speed fuses RFI lter
Line reactor (depending on rating)
Encoder or resolver input Additional I/O Communication options
(MDX-PROFIBUS, MDX-ETHERNET, MDX-MODBUS, etc.)
-
8/12/2019 4972b_en_MD2S
5/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
5
enINSTALLATION AND MAINTENANCE
Variable speed drive
CONTENTS
1 - GENERAL INFORMATION .................................................................................................................................. 7
1.1 - General ........................................................................................................................................................ 71.2 - Product designation .................................................................................................................................... 71.3 - Environmental characteristics ...................................................................................................................... 71.4 - Electrical characteristics .............................................................................................................................. 8
1.4.1 - General characteristics.......................................................................................................................................... 8
1.4.2 - Electrical characteristics ........................................................................................................................................ 8
1.4.3 - Derating at low frequency ...................................................................................................................................... 9
1.4.4 - Derating according to the temperature and switching frequency ......................................................................... 10
2 - MECHANICAL INSTALLATION ......................................................................................................................... 12
2.1 - Checks upon receipt .................................................................................................................................. 122.2 - Handling .................................................................................................................................................... 12
2.3 - Installation recommendations ................................................................................................................... 132.4 - Removing and re-tting the IP21 roof......................................................................................................... 132.5 -Assembly and dismantling of the IP54 roof ................................................................................................ 132.6 - Dimensions ................................................................................................................................................ 142.7 - Weight ....................................................................................................................................................... 152.8 - Drive losses ............................................................................................................................................... 152.9 - Drive ventilation ow rates and noise levels............................................................................................... 15
3 - CONNECTIONS ................................................................................................................................................. 16
3.1 - Power connections .................................................................................................................................... 163.1.1 - Location of the control terminal block, fuse boards and external power supply .................................................... 16
3.1.2 - Electronics and forced ventilation power supply .................................................................................................. 17
3.1.3 - Characteristics of connection terminals ............................................................................................................... 17
3.1.4 - Location of power terminal blocks........................................................................................................................ 18
3.1.5 - Cables and fuses ................................................................................................................................................. 20
3.2 - Connection of the control ........................................................................................................................... 223.2.1 - Control terminal block location............................................................................................................................. 22
3.2.2 - Control terminal block characteristics .................................................................................................................. 22
3.2.3 - Factory conguration of control terminal blocks................................................................................................... 24
3.3 - STO-1/STO-2 inputs: Safe Torque Off function .......................................................................................... 253.3.1 - Single channel locking (SIL1 - PLb) ..................................................................................................................... 25
3.3.2 - Double channel locking (SIL3 - PLe).................................................................................................................... 25
4 - GENERAL EMC - HARMONICS - MAINS INTERFERENCE ............................................................................. 26
4.1 - Low-frequency harmonics .......................................................................................................................... 26
4.2 - Radio-frequency interference: Immunity .................................................................................................... 264.2.1 - General ............................................................................................................................................................... 26
4.2.2 - Standards ............................................................................................................................................................ 26
4.2.3 - Recommendations .............................................................................................................................................. 26
4.3 - Radio-frequency interference: Emission .................................................................................................... 264.3.1 - General ............................................................................................................................................................... 26
4.3.2 - Standards ............................................................................................................................................................ 26
4.4 - Mains supply .............................................................................................................................................. 264.4.1 - General ............................................................................................................................................................... 26
4.4.2 - Mains transient overvoltages ............................................................................................................................... 27
4.4.3 - Unbalanced power supply ................................................................................................................................... 27
4.4.4 - Ground connections ............................................................................................................................................ 27
4.5 - Basic precautions for installation .............................................................................................................. 284.5.1 - Wiring inside the cabinet...................................................................................................................................... 28
4.5.2 - Wiring outside the cabinet ................................................................................................................................... 28
-
8/12/2019 4972b_en_MD2S
6/48
-
8/12/2019 4972b_en_MD2S
7/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
7
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL INFORMATION
1 - GENERAL INFORMATION
1.1 - General
The POWERDRIVE MD2Sis a variable speed drive with veryhigh performance levels that can be used to control:
- Induction motors without speed sensor (open loop mode
select ) for applications that do not need rated torque
control above 1/10thof the rated speed.
- Asynchronous or synchronous permanent magnet motorswith virtual speed feedback (ux vector mode with software
sensor function ) for applications that require rated torque
control from 1/20thof the rated speed.
Combined with the MDX-ENCODER option, the
POWERDRIVE MD2S is a drive that can also be used to
control asynchronous or synchronous magnet machines forapplications that require very high dynamic performances,
torque control from zero speed or high speed accuracy
(closed loop vector mode with speed feedback ).The performance of the POWERDRIVE MD2Sis compatible
with use in all 4 quadrants of the torque/speed plane with the
braking module option incorporated.With IP54 protection (optional), installation is possible directly
on the machine itself in harsh environments.
1.2 - Product designationPOWERDRIVE MD2S - 180 T
*
Drive versionMD2S : 6 pulsesMD2T : 12 pulsesMD2E : 18 pulsesMD2W : 24 pulsesMD2R : Regen
Rating in kVA
3-phase powersupply
T : 400 V to 480 VTH : 525 V to 690 V
Modular variablespeed drive withflux vector control
Cooling: - : Air L : Liquid
(*) See the corresponding installation manual
Depending on the options installed, a sufx (-B or -O) isadded to the product commercial designation.
Nameplate
MOTEURS LEROY-SOMER
16015 ANGOULEME
MADE IN FRANCE
ENTREE - INPUT
Ph V (V) Hz (Hz) I(A)
3 400-480 50/60 295Alim auxiliaire 800VA
400V/50Hz 480V/60Hz
TYPE :
S/N :
09999999999
POWERDRIVE MD2S 180T
I(A) = maximum input current for 400 V mains supply, in
normal duty
The nameplate can be found inside the cabinet door at the top
(another copy can be found on the outside of the cabinet, at
the top on the right-hand side).
1.3 - Environmental characteristics
Characteristic Level
Protection IP21 (IP54 as an option)
Storage andtransport
temperature
-30C to +60C (see section 7.2)
Ambient operating
temperature(outside the cabinet)
-10C to +40C, up to +50C with derating(see section 1.4.4)
Classication of
environmental
conditions
In accordance with IEC 60721-3-3:
Biological classication in accordance with
class 3B1Classication as regards chemically
active substances in acc. with class 3C2
Classication as regards mechanically
active substances in acc. with class 3S2
Relative humidity
In accordance with IEC 60068-2-56
< 90% non condensing
Altitude
1000 m without derating
> 1000 m up to 4000 m maximum(as required):
Current derating of 1% per additional 100
m
E.g. for 1300 m, derate the Ico and Imaxcurrents by 3%
Operating temperature derating of 0.6C
per 100 m
E.g. for 1300 m, the electricalcharacteristics are maintained for an
ambient temperature of
[40- (3 x 0.6)] = 38.2C.
Vibrations
In accordance with IEC 60068-2-6Exposed product: 2 m/s
(9-200 Hz), 0.6 mm (2-9 Hz)
Packaged product: 10m/s(9-200 Hz), 3 mm (2-9 Hz)
ShocksPackaged product: in accordance with
IEC 60068-2-29
Atmospheric
pressure700 to 1060 hPa
-
8/12/2019 4972b_en_MD2S
8/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
8
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL INFORMATION
1.4 - Electrical characteristics
All work relating to installation, commissioning and maintenance must be carried out by experienced, qualied
personnel.
1.4.1 - General characteristics
Characteristic Level
Power supply voltage3-phase mains supply: 400 V -10% to 480 V +5% ("T" ratings) or525 V -10% to 690 V +10% ("TH" ratings)
Phase voltage imbalance < 2%
Input frequency 5% around the rated frequency (50 or 60 Hz)
Maximum number of power-ups per hour (power) 20
Output frequency range 0 to 590 Hz
ROHS conformance Conforming to standard 2002-95-EC
For operation with a neutral IT point connection, follow the instructions given in section 4.4.3.
1.4.2 - Electrical characteristics
Ico: Continuous output current.
Pout: Output power.
Imax (60s): Maximum output current, available for 60 seconds every 600 seconds.
Heavy duty: For heavy-duty constant torque machines (presses, grinders, hoisting, etc) and all applications where signicant
inertia has to be accelerated quickly (centrifuges, translation of travelling cranes, etc).Normal duty: For normal-duty constant torque or centrifugal torque machines (fans, compressors, etc).
CAUTION: In its factory setting, the drive operates with a switching frequency of 3 kHz.
400 V 3-phase mains supplySwitching frequency = 3 kHz - ambient temperature 40C (35C with IP54 option)- altitude 1000 m.
POWERDRIVE MD2Srating
Heavy duty Normal dutyImax (60 s)
(A)Pout
(kW)
Ico
(A)
Pout
(kW)
Ico
(A)
100T 75 142 90 175 200
120T 90 172 110 212 240
150T 110 220 132 250 312
180T 132 260 160 315 365
220T 160 310 200 400 435
270T 200 380 250 470 530
340T 250 470 315 580 660400T 315 545 355 640 760
470T 355 670 450 800 940
600T 450 815 550 990 1140
750T 550 1000 675 1220 1400
900T 675 1230 750 1430 1725
1100T 750 1465 900 1700 2050
1400T 900 1775 1100 2100 2485
-
8/12/2019 4972b_en_MD2S
9/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
9
0 5 10 15 20
20 %
40 %
60 %
80 %
100 %
120 %
140 %
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL INFORMATION
525 V to 690 V 3-phase mains supply
Switching frequency = 3 kHz - ambient temperature 40C (35C with IP54 option) - altitude 1000 m.
POWERDRIVE MD2S
rating
Heavy duty Normal dutyImax (60 s)
(A)
Pout at 575 V
(kW)
Pout at 690 V
(kW)
Ico
(A)
Pout at 575 V
(kW)
Pout at 690 V
(kW)
Ico
(A)
270TH 160 200 220 200 250 280 308
340TH 200 250 270 250 315 340 378
400TH 250 315 330 315 400 415 465
500TH 315 400 390 400 450 480 545
600TH 400 450 455 450 550 580 638
750TH 450 550 570 550 700 730 800
900TH 550 700 715 700 850 900 1000
1200TH 700 850 880 850 1100 1120 1230
1500TH 850 1100 1060 1100 1300 1300 1485
Frequency(Hz)
% Ico or% Imax (60 s)1.4.3 - Derating at low frequency
Measuring the temperature of the power bridges in
conjunction with thermal modelling of the IGBTs protects the
POWERDRIVE MD2S against overheating.
At low motor frequencies, IGBT modules are subject to tough
temperature cycling, which may reduce their life time. To
prevent this risk, the curve opposite indicates the derating for
output currents Ico and Imax when operating at low motor
frequency in continuous operation.
-
8/12/2019 4972b_en_MD2S
10/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
10
100T 142 142 142 130 118 175 175 162 148 134
120T 172 172 166 150 136 220 212 188 170 154
150T 222 220 198 176 160 260 250 224 200 182
180T 260 260 260 260 250 315 315 310 305 285
220T 310 310 310 310 285 400 400 385 355 325
270T 380 380 380 355 320 470 470 440 400 365
340T 470 470 465 420 380 580 580 525 475 430
400T 545 545 535 480 430 650 640 605 545 490
470T 670 670 640 575 515 800 800 725 650 585
600T 815 815 810 730 670 990 990 920 830 760
750T 1000 1000 985 900 820 1220 1220 1120 1020 930
900T 1230 1230 1145 1065 970 1430 1430 1300 1210 1100
1100T 1465 1465 1395 1260 1165 1700 1700 1580 1430 1320
1400T 1775 1775 1700 1550 1410 2100 2100 1930 1760 1600
100T 142 142 136 122 112 175 172 154 138 126
120T 172 172 156 140 126 215 200 176 158 144
150T 222 210 186 164 148 255 238 210 186 168
180T 260 260 260 260 235 315 310 305 295 265
220T 310 310 310 295 265 400 395 370 335 300
270T 380 380 370 330 295 470 465 420 375 335
340T 470 470 430 380 340 580 560 485 430 385
400T 545 540 490 430 385 650 610 555 490 435
470T 670 670 585 515 465 800 760 665 585 525
600T 815 815 750 660 600 990 960 850 750 680
750T 1000 1000 910 810 730 1220 1160 1030 920 830
900T 1230 1200 1050 960 875 1430 1360 1190 1090 990
1100T 1465 1455 1285 1135 1040 1700 1650 1460 1290 1180
1400T 1775 1765 1560 1400 1260 2100 2000 1770 1590 1430
270TH 220 220 220 280 280 250
340TH 270 270 270 340 340 310
400TH 330 330 330 415 415 380
500TH 390 390 345 500 480 390
600TH 455 455 455 580 580 520
750TH 570 570 570 730 730 700
900TH 715 715 660 900 900 750
1200TH 880 880 880 1150 1120 1020
1500TH 1060 1060 970 1350 1300 1100
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL INFORMATION
1.4.4 - Derating according to the temperature and switching frequency
Ambient temperature 40C ( 35C with IP54 option) - altitude 1000 m.
Rating
Ico (A)
Heavy duty Normal duty
2 kHz 3 kHz 4 kHz 5 kHz 6 kHz 2 kHz 3 kHz 4 kHz 5 kHz 6 kHz
400 V mains supply
460/480 V mains supply
525/690 V mains supply
For intermediate switching frequencies (3.5 - 4.5 - 5.5 kHz), the available current value will be the average of the upper frequency
and lower frequency currents.With IP54 protection, for an ambient temperature of 40C, the available current value is the average of currents at 35C and 45C.
-
8/12/2019 4972b_en_MD2S
11/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
11
100T 142 142 132 120 110 175 168 150 136 124
120T 172 170 152 138 126 215 192 172 156 142
150T 222 204 182 162 146 255 232 206 184 166
180T 260 260 260 255 230 315 315 305 290 260
220T 310 310 310 285 260 400 390 360 325 295
270T 380 380 360 320 290 470 450 410 365 330
340T 470 470 420 375 340 570 540 475 425 385
400T 545 520 485 430 385 630 590 550 485 435
470T 670 650 575 515 465 780 740 655 585 525
600T 815 795 715 645 590 930 900 810 730 670
750T 1000 985 865 795 725 1150 1120 980 900 820
900T 1200 1155 1015 925 855 1360 1310 1150 1050 970
1100T 1430 1365 1235 1100 1015 1620 1550 1400 1250 1150
1400T 1735 1685 1500 1365 1235 1970 1910 1700 1550 1400
100T 142 142 126 112 100 175 160 142 126 114
120T 172 162 142 128 114 210 184 162 146 130
150T 222 194 170 152 136 254 220 192 172 154
180T 260 260 260 240 215 315 305 295 270 245
220T 310 310 300 270 240 400 385 340 305 270
270T 380 380 340 300 270 470 435 385 340 305
340T 470 450 385 340 305 570 510 435 385 345
400T 545 485 440 385 340 630 550 500 435 385
470T 670 605 525 465 410 780 685 595 525 465
600T 815 750 660 590 530 930 850 750 670 600
750T 1000 935 795 715 645 1150 1060 900 810 730
900T 1200 1100 925 835 765 1360 1250 1050 950 870
1100T 1430 1320 1135 995 910 1620 1500 1290 1130 1030
1400T 1735 1605 1375 1235 1100 1970 1820 1560 1400 1250
270TH 220 210 195 280 240 220
340TH 270 270 240 340 310 270
400TH 330 330 300 415 400 340
500TH 390 365 305 500 415 345
600TH 455 455 395 570 525 450
750TH 570 570 540 740 730 610
900TH 715 690 545 890 780 620
1200TH 880 880 865 1120 1120 980
1500TH 1060 1060 900 1320 1220 1020
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL INFORMATION
Ambient temperature 50C ( 45C with IP54 option) - altitude 1000 m.
Rating
Ico (A)
Heavy duty Normal duty
2 kHz 3 kHz 4 kHz 5 kHz 6 kHz 2 kHz 3 kHz 4 kHz 5 kHz 6 kHz
400 V mains supply
460/480 V mains supply
525/690 V mains supply
For intermediate switching frequencies (3.5 - 4.5 - 5.5 kHz), the available current value will be the average of the upper frequency
and lower frequency currents.
With IP54 protection, for an ambient temperature of 40C, the available current value is the average of currents at 35C and 45C.
-
8/12/2019 4972b_en_MD2S
12/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
12
L
60mini
L
60mini
L
60mini
L
60mini
enINSTALLATION AND MAINTENANCE
Variable speed driveMECHANICAL INSTALLATION
2 - MECHANICAL INSTALLATION It is the responsibility of the owner or user of the
POWERDRIVE MD2S to ensure that the installation,
operation and maintenance of the drive and its optionscomply with legislation relating to the safety of personnel
and equipment and with the current regulations of thecountry of use.
POWERDRIVE MD2S drives must be installed in
an environment free from conducting dust, corrosive
fumes, gases and uids, dripping water and any source
of condensation (class 2 according to IEC 664.1). The
drive must not be installed in hazardous areas unless it is
in an appropriate enclosure. In this case, the installation
must be approved.
In atmospheres where condensation may form, install a
heating system.
Prevent access by unauthorised personnel.
2.1 - Checks upon receipt
Make sure that the cabinet has been transported
vertically, as otherwise it could be damaged.
Before installing the POWERDRIVE MD2S,check that:
- The drive has not been damaged during transport
- The information on the nameplate is compatible with thepower supply
2.2 - Handling The centre of gravity may be high up and / or off-
centre, so beware of the risk of the cabinet tipping
over. Check that the handling equipment is suitable for the
weight to be handled.
The lifting accessories provided are limited solely to
handling the cabinet. If subsequent handling operations
are carried out, always check that these lifting accessories
are in good condition.
The cabinet must be handled without the IP21 or IP54 roof in
place.
IP21 POWERDRIVE MD2S versions are supplied with theroof assembled. Before handling the cabinet, follow the
procedure described in section . For handling, follow theinstructions below, and then re-t the roof.
IP54 POWERDRIVE MD2S versions are supplied with the
lifting rings or rails assembled. When handling the cabinet,
follow the instructions below, depending on the cubicle width,
as indicated below. After handling, assemble the roof as
described in section .
Above 2400 mm wide (W), a baseplate 100 mm high is
installed as standard to ensure the rigidity of all the cabinets.
L= 4x 400 mmor 4x 600 mm
L= 3x 400 mmor 3x 600 mm
L = 2x 400 mmor 2x 600 mmor 2x 600 + 400 mm
L = 400 mmor 600 mmor 600 + 400 mm
-
8/12/2019 4972b_en_MD2S
13/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
13
enINSTALLATION AND MAINTENANCE
Variable speed driveMECHANICAL INSTALLATION
2.5 - Assembly and dismantling of the
IP54 roof
Assembly:
1 - Dismantle the 4 lifting rings or the 2 lifting rails.2 - Open up the roof assembly as shown in the diagrams below.
The side panels with no vent should be mounted facing eachother; the rear of the drive will have no vent.
3 - Insert the supplied M12 screws through the roof assembly
and tighten.
4 - Adjust the roof assembly to optimise sealing.
5 - Finally tighten the xing screws (tightening torque: 20 N.m).
Removal, if necessary:
Follow the reverse procedure.
2.3 - Installation recommendations
Ensure that hot air is not being recycled via the air inlets by
leaving sufcient free space above the POWERDRIVE MD2S
or providing a means of evacuating the hot air exhausted bythe product. If necessary, add a suction hood. Never obstruct
the drive ventilation grilles; the air intake lters must be
cleaned and changed regularly.
After connecting the power, reposition the cable
bush plates at the back of the cabinet and ll any
gaps with expanding foam.
2.4 - Removing and re-tting the IP21 roof
Dismantling
1 - Remove the M12 screws.
2 - Remove the roof(s).3 - Screw in the 4 lifting rings or the 2 lifting rails with the M12
screws at the places indicated (tightening torque = 20 N.m).
Re-tting
Follow the reverse procedure.
-
8/12/2019 4972b_en_MD2S
14/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
14
enINSTALLATION AND MAINTENANCE
Variable speed driveMECHANICAL INSTALLATION
2.6 - Dimensions
The cabinet-mounted POWERDRIVE MD2Ssolution is obtained by assembling cabinet modules of 400 or 600 mm wide and
600 mm deep.
The table below gives the productwidth (Win mm) depending on the options incorporated:
W/o options With options
MD2S ratingsWidth
W (mm)Switch
High-speed
fusesRFI lter Mains choke
Braking
transistorWidth
W (mm)
100T to 150T 406 included 406
180T to 270T 406 included 606
340T & 400T 606
606
606
1006
470T 606
606
606
1006
600T to 900T 1206
1206
1206
1606
1806
1100T & 1400T 1806 included 2406 (1)
270TH to 500TH 606 included 1006
600TH to 900TH 1206 included 1606
1200TH to 1500TH 1806 included 2406 (1)
The following options can be incorporated into thePOWERDRIVE MD2Swithout affecting its dimensions:
MD-AU1 emergency stop
Communication modules Additional I/O modules
Speed feedback modules
H
W D = 600 mm
The table below gives the productheight (H) depending onthe options incorporated:
Option Hauteur (mm)
POWERDRIVE MD2S standard 2100
IP21 protection + 0
IP54 protection + 100
100mm baseplate + 100
200mm baseplate + 200
baseplate for width 2400mm (1) + 100
(1) Above 2400 mm long (L), a 100 mm high baseplate mustbe installed to ensure the rigidity of the cabinet assembly.
Cables cannot run through this baseplate, but a 100mm ou
200mm baseplate can be added.
For more details depending on the options chosen, use the
Leroy-Somer congurator:
http://congurateurls.leroy-somer.com/
http://configurateurls.leroy-somer.com/login_en.phphttp://configurateurls.leroy-somer.com/login_en.php -
8/12/2019 4972b_en_MD2S
15/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
15
enINSTALLATION AND MAINTENANCE
Variable speed driveMECHANICAL INSTALLATION
2.7 - Weight
The values indicated in the table below are maximum net
weights.
POWERDRIVE MD2rating
Weightwithout option (kg)
Maximum weight(kg)
100T to 150T 225 260
180T to 270T 260 360
340T to 470T 355 560
600T and 750T 710 990
900T 740 1040
1100T to 1400T 1350 1720
270TH and 340TH 355 560
400TH and 500 TH 400 620
600TH 720 780
750TH and 900TH 810 10501200TH and 1500TH 1250 1520
2.8 - Drive losses
Losses according to the switching frequency with currents
at 40 C.
MD2Srating
Losses (kW)
at 2 kHz at 3 kHz at 4 kHz at 5 kHz at 6 kHz
100T 2.4 2.6 2.4 2.4 2.3
120T 2.8 2.8 2.6 2.6 2.4
150T 3.2 3.5 3.3 3.1 3.1
180T 3.8 4.2 4.5 4.7 4.5
220T 4.9 5.4 5.6 5.5 5.2
270T 5.7 6.3 6.5 6 5.7
340T 7.4 7.9 8.5 8.3 8.1
400T 8.6 9.1 9.8 9.6 9.3
470T 10.8 11.2 11.8 11.5 11.2
600T 14.9 15.9 16.4 16 15.6
750T 16.1 16.9 17.8 17.4 16.9
900T 21.4 21.2 22.3 21.7 21.2
1100T 24.7 26 27.2 26.5 25.8
1400T32 32.5 34.5 33.6 32.8
270TH 5.6 6.0 6.2
340TH 9.2 9.7 9.7
400TH 8.7 9.4 9.4
500TH 10.5 11.3 11.2
600TH 15.9 16.8 16.6
750TH 16.1 17.3 19.7
900TH 20.9 22.3 22.5
1200TH 26.4 28.3 32.1
1500TH 31.8 34.2 34.2
Note: The values given above correspond to operation in
normal duty and the choke losses are included.
2.9 - Drive ventilation ow rates and
noise levels
POWERDRIVE MD2 rating
Forced
ventilationow rates
(m3/hr)
Noise level(dBA)
100T to 150T 600 75
180T to 270T 1200 77
340T to 470T 1700 77
600T to 900T 3400 80
1100T to 1400T 5100 82
270TH to 500TH 1700 77
600TH to 900TH 3400 80
1200TH and 1500TH 5100 82
Air can exit out from all sides of the roof. The cabinet can
be installed with one side only against a wall (with IP21 or
IP54 roof). Under no circumstance the difference between
the internal temperature of the cabinet and the ambient
temperature outside the cabinet must not exceed 5C.
In atmospheres where condensation may form, install
a heating system (to be switched off when the drive is
operating). It is advisable to control the heating system
automatically.
Air outlets
Air inlets
-
8/12/2019 4972b_en_MD2S
16/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
16
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3 - CONNECTIONS
All connections work must be performed by
qualied electricians in accordance with the laws in
force in the country in which the drive is installed. This
includes earthing to ensure that no directly accessiblepart of the drive can be at the mains voltage or any other
voltage which may be dangerous.
The drive must be supplied through an approved
circuit-breaking device so that it can be powered down
safely.
The optional isolator supplied with the drive doesnot isolate the drive input busbars. It must without
fail be associated with a circuit-breaking device in the
switchboard.
The drive power supply must be protected against
overloads and short-circuits.
Check that the voltage and current of the drive, the
motor and the mains supply are compatible. The voltages on the connections of the mains supply,
the motor, the braking resistor or the lter may cause
fatal electric shocks. The protective plates supplied with
the drive must always be installed correctly to protect theuser against electric shocks.
Only one permanent magnet motor can be connected
to the drive output. It is recommended to install a circuit-
breaking device between the permanent magnet motor
and the drive output to eliminate the risk of hazardous
voltage feedback when performing maintenance work. See also the recommendations in section 7.
3.1 - Power connections
3.1.1 - Location of the control terminal block, fuse boards and external power supply
Control terminal block
Removable screw terminal block: tightening torque = 0.3 N.m/0.22 lb ft cross-section = 1.5 mm2 screwdriver = 2 mm flat
Analog I/O Digital I/O RelaysPx1 Px2
Fuses and external power supply board
Depending on the rating, POWERDRIVE MD2S may includeone or more identical fuses board:
- 100T to 270T : 1 board (1)
- 340T to 470T & 270TH to 500TH : 1 board (2)
- 600T to 900T & 600TH to 900TH : 2 boards (2)
- 1100T and 1400T & 1200TH and 1500TH : 3 boards (2)
(1) Positioned right side each cabinet(2) Positioned left side each cabinet
Position the F8 fuse according to the mains supply
voltage
F1
F2 F3 F4 F5 F6F9F7
PX4
460V(T)
600V(TH
)
480V(T)
690V(TH
)
400V(T)
500V(TH
)
P1
F8
400V(T)/500V(TH)
460V(T)/600V(TH)
480V(T)/690V(TH)
P2
P3 P4
P6P7 P8
Interface
board
output
Power
Input S1
Power
Input S2External
power input
Fan
Control
F an 1 F an 2 Fa n3 F an 4 Fa n5
-
8/12/2019 4972b_en_MD2S
17/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
17
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.1.5 - Electronics and forced ventilationpower supply
The control electronics and forced ventilation units are
supplied through a single-phase transformer which primary
is connected to terminals L1-L2 of the power supply. If
necessary, this transformer can be supplied with an externalpower source (PX4 terminal block on fuse board).
The neutral of the electronics power supply must
not be connected to earth
Electrical characteristics:
Ratings Voltage
PrimaryT
400 V10%/50 Hz or
460-480 V 10%/60 Hz
TH 500-690 V 5%/50 Hz
Voltage Maximum power
Secondary 1(Electronics
power supply)
230 Visolated
100 VA
Secondary 2(Forced
ventilation and
auxiliaries power
supply)
230 V
connectedto earth
100T to 150T:
P = 300 VA
180T to 270T:
P = 500 VA340T to 470T:
P = 1200 VA
600T to 900T:
P = 2x 1200 VA1100T to 1400T:
P = 3x 1200 VA
270TH to 500TH:P = 1200 VA
600TH to 900TH:
P = 2x 1200 VA
1200TH to 1500TH: P = 3x 1200 VA
Disconnection of forced ventilation units
The fuse board described in section 3.1.1. enables the user to
switch off the power supply to the drive forced ventilation units
momentarily, if preheating resistors are used in the cabinet for
example.To disconnect the fans, remove the jumper connecting
terminals P7 and P8 and connect a normally closed contact
(230 V/7 A on resistive load). A closed contact allows the
ventilation units to operate, an open delayed contact cuts off
their power supply (delay 10 minutes for ambiant temperatureup to 40C, otherwise 30 minutes).
Connection exemple:
Px2
2 P7 P8
KA1
DO1+24
A1
A2
KA1
1
POWERDRIVE MD2S
Example of associated settings:
# 16.02 = 10.02 (Timer 1 source = Drive active) # 16.03 = 1 (OFF timer)
# 16.04 = 1 (minute)
# 16.05 = 20 (if T 40 C) or 30 (if T > 40 C)
# 8.26 = 16.01 (DO1 assigned to Timer 1)
# 8.16 = 1 (Invert DO1)
Refer to the commissioning manual (ref. 4617) for more
details on POWERDRIVE MD2Ssettings.
3.1.2 - Characteristics of connection terminals
Refs. Functions/connections
Type of connection and tightening torque
100T to 150T 180T to 270T340T to 1400T
270TH to 1500THL1, L2, L3,
or R, S, TMains power supply
M10 screw bolt - 20 Nm
U, V, W Motor outputs
PE Earth M10 bolt - 20 Nm M8 bolts - 12 Nm
BR1, BR2, PE braking resistor (1) M8 screw bolt - 12 Nm
P4, P5 EMC commoning link Torx screws 20 - 4 Nm
- Control block (2) Spring terminal block
Do not exceed the indicated maximum tightening torque.
(1) If braking transistor is tted.
(2) The neutral of the electronics power supply must not be connected to earth.
Fuse board on controlterminal board
-
8/12/2019 4972b_en_MD2S
18/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
18
U V W
L1
/ R
L2
/ S
L3
/ T
MD2S 100T - MD2S 150T
PE PEPE
350
535.5
241
535.5
U V WMD2S 180T - MD2S 270T
PE PE
320
PE
L1 L2 L3
MD2S 180T - MD2S 270T
PE PE
PE
R S T U V W
BR1/BR2MD2S 340T - MD2S 470T
MD2S 270TH - MD2S 500TH
93
50
50 5075 75 105 75 75
U V WL1 L2 L3
PE100
PE220
MD2S 340T - MD2S 470T
MD2S 270TH - MD2S 500TH
2
20
BR1/BR2
U V WR S T93
50
5075 75
PE100PE
75 75112 112
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.1.3 - Location of power terminal blocks
W/o options
W/o options
With options
With options
-
8/12/2019 4972b_en_MD2S
19/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
19
MD2S 600T - MD2S 900T
MD2S 600TH - MD2S 900TH
L1 L2 L3 U V WBR1
BR2
220 50 75 75 75 75 75 50 45 50 75 75 75 75 75 95
PE
93
50
100
PE
MD2S 600T - MD2S 900T
MD2S 600TH - MD2S 900TH
R T
U V WBR1
BR2
220
55
70 70105 105 45 50 75 75 75 75 75 95
PE
93
50
100
PE
S
MD2S 1100T - MD2S 1400T
MD2S 1200TH - MD2S 1500TH
50 75 75 105 75 75 5050 75 75 55 75 75
L1 L2 L3
50 5050 75 75 120 75 75
U V W
PE
50
BR1
BR2
93
50
100
PE220
MD2S 1100T - MD2S 1400T
MD2S 1200TH - MD2S 1500TH
55
55 75 75 50 5050 75 75 120 75 75
U V W
PE65 190 190 65
BR1
BR2
93
50
100 PE2
20
150
R S T
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
W/o options
With options
W/o options
With options
-
8/12/2019 4972b_en_MD2S
20/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
20
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.1.4 - Cables and fuses
It is the responsibility of the user to connect and provide protection for the POWERDRIVE MD2S in accordance
with the current legislation and regulations in the country of use. This is particularly important with regard to the
size of the cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging trips,
isolation and protection against overcurrents.
The installation must have a short circuit current (Isc) > 20 ILat the point of drive connection.
This table is given for information only, and must under no circumstances be used in place of the current standards.
IL: Maximum line current Ico: Continuous output current
POWERDRIVE
rating
Mains power supplyMotor
400 V - 50 Hz 460/480 V - 60 Hz
IL(A)
Fuses (1)Cable
cross-section(mm) (2)
IL
(A)
Fuses (1)Cable
cross-section(mm) (2)
Ico
(A)
Cable
cross-section(mm) (3)
Gg
typeaR type
Gg
type
Class
J
( UL)
aR type
100THeavy 140 160 250 3x70 + 35 125 160 200 250 3x70 + 30 145 3x70 + 35
Normal 170 200 315 3x95 + 50 150 200 225 250 3x70 + 35 175 3x95 + 50
120THeavy 170 200 315 3x95 + 50 150 200 225 250 3x70 + 35 175 3x95 + 50
Normal 198 250 350 3x120 + 70 175 200 250 315 3x95 + 50 215 3x120 + 70
150THeavy 205 250 400 3x120 + 70 175 200 250 315 3x95 + 50 220 3x120 + 70
Normal 245 315 450 3x150 + 70 215 250 300 350 3x120 + 70 260 3x150 + 70
180THeavy 245 315 500 3x150 + 70 215 250 300 400 3x120 + 70 260 3x150 + 70
Normal 295 315 500 3x240 +120 255 315 400 450 3x185 + 90 305 3x240 +120
220THeavy 290 315 550 3x240 +120 255 315 400 450 3x185 + 90 305 3x240 +120
Normal 370 400 630 2x(3x95 + 50) 320 400 500 550 3x240 + 120 380 2x(3x95+50)
270THeavy 375 400 700 2x(3x95 + 50) 325 400 500 550 3x240 + 120 380 2x(3x95+50)
Normal 460 500 800 2x(3x150 + 95) 405 500 600 700 2x(3x120 + 70) 470 2x(3x150+95)
340THeavy 465 500 800 2x(3x150 + 95) 410 500 600 700 2x(3x120 + 70) 470 2x(3x150+95)
Normal 580 630 1000 2x(3x185 + 95) 495 630 -- 800 2x(3x150 + 95) 580 2x(3x185+95)
400THeavy 585 630 1000 2x(3x185 + 95) 500 630 -- 900 2x(3x150 + 95) 570 2x(3x185+95)
Normal 650 800 1100 2x(3x240 + 120) 560 630 -- 900 2x(3x185 + 95) 630 2x(3x240+120)
470THeavy 655 800 1250 2x(3x240 + 120) 560 630 -- 1000 2x(3x185 + 95) 680 2x(3x240 + 120)
Normal 815 1000 1400 3x(3x185 + 95) 700 800 -- 1250 2x(3x240 + 120) 800 3x(3x185 + 95)
600THeavy 825 1000 2x630 3x(3x185 + 95) 710 800 -- 2 x 550 2x(3x240 + 120) 820 3x(3x185 + 95)
Normal 998 1250 2x800 4x(3x150 + 95) 856 1000 -- 2 x 700 3x(3x185 + 95) 990 4x(3x150 + 95)
750THeavy 1010 1250 2x800 4x(3x150 + 95) 865 1000 -- 2 x 700 4x(3x150 + 95) 990 4x(3x150 + 95)
Normal 1225 1600 2x1000 3x(3x240 + 120) 1050 1250 -- 2 x 800 4x(3x150 + 95) 1220 3x(3x240 + 120)
900THeavy 1250 1600 2x1000 3x(3x240 + 120) 1060 1250 -- 2 x 800 3x(3x240 + 120) 1220 3x(3x240 + 120)
Normal 1360 1600 2x1100 4x(3x240 + 120) 1170 1600 -- 2 x 900 3x(3x240 + 120) 1430 4x(3x240 + 120)
1100THeavy 1380 1800 3x800 4x(3x240 + 120) 1180 1600 -- 3 x 700 4x(3x240 + 120) 1430 4x(3x240 + 120)
Normal 1635 2000 3x900 4x(3x240 + 120) 1400 1800 -- 3 x 800 4x(3x240 + 120) 1700 4x(3x240 + 120)
1400THeavy 1680 2000 3 x 900 1520 1800 -- 3 x 800 1750
Normal 2000 2500 3 x 1000 1810 2000 -- 3 x 900 2100
-
8/12/2019 4972b_en_MD2S
21/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
21
U
WV
PE
PE PE
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
POWERDRIVE
rating
Mains power supplyMotor
525 V 690 V
IL(A)
Fuses Cable
cross-section(mm)
(1)
IL(A)
FusesCable cross-section
(mm)(1)
Ico(A)
Cable cross-
section (mm)(2)
Ggtype
aR type(IEC&UL)
Ggtype
aR type(IEC&UL)
270THHeavy 205 250 400 3x120 + 70 215 250 400 3x120 + 70 220 3x120 + 70
Normal 250 315 450 3x120 + 70 265 315 450 3x120 + 70 280 3x150 + 70
340THHeavy 250 315 450 3x120 + 70 265 315 500 3x120 + 70 270 3x150 + 70
Normal 305 400 550 3x150 + 70 320 400 550 3x150 + 70 340 3x240 +120
400THHeavy 305 400 550 3x150 + 70 320 400 630 3x150 + 70 330 3x240 +120
Normal 370 400 700 3x240 +120 390 400 700 3x240 +120 415 2x(3x120+70)
500THHeavy 370 400 700 3x240 +120 390 400 700 3x240 +120 390 2x(3x120+70)
Normal 445 500 800 3x240 +120 470 500 800 3x240 +120 480 2x(3x150+95)
600TH
Heavy 445 500 2x400 3x240 +120 470 500 2x450 3x240 +120 455 2x(3x150+95)
Normal 520 630 2x450 2x(3x150+95) 545 630 2x500 2x(3x150+95) 580 2x(3x185+95)
750THHeavy 520 630 2x500 2x(3x150+95) 545 630 2x500 2x(3x150+95) 570 2x(3x185+95)
Normal 650 800 2x630 2x(3x240 + 120) 685 800 2x630 2x(3x240 + 120) 730 2x(3x240+120)
900THHeavy 650 800 2x630 2x(3x240 + 120) 685 800 2x630 2x(3x240 + 120) 715 2x(3x240 + 120)
Normal 805 1000 2x700 3x(3x185 + 95) 845 1000 2x800 3x(3x185 + 95) 900 3x(3x185 + 95)
1200THHeavy 805 1000 3x450 3x(3x185 + 95) 845 1000 3x500 3x(3x185 + 95) 880 3x(3x185 + 95)
Normal 1000 1250 3x550 3x(3x185 + 95) 1050 1250 3x550 3x(3x185 + 95) 1120 3x(3x240 + 120)
1500THHeavy 1000 1250 3x550 3x(3x185 + 95) 1050 1250 3x550 3x(3x185 + 95) 1060 3x(3x240 + 120)
Normal 1205 1600 3x630 3x(3x240 + 120) 1265 1600 3x630 3x(3x240 + 120) 1300 4x(3x240 + 120)
Note: The line current value ILis a typical value which depends on the source impedance. The higher the impedance, the lower the
current.
(1) gG fuse or equivalent solution (fuses connected in parallel, preferably C type circuit-breaker, etc). This protection must always
be connected in series with aR semi-conductor fuses.
(2) Semiconductor aR fuses do not ensure the protection of the drive power supply line and must always be associated with a
protection device against overload, localized at the head of the line.
(3) The recommended mains cable cross-sections have been determined for single-core cable with a maximum length of 20 m. For
longer cables, take line voltage drops into consideration due to large cable length.
(4) The motor cable cross-sections are given for information only for a current corresponding to the value of the
Ico current at 3 kHz, a maximum length of 50 m, output frequency less than 100 Hz and an ambient temperature of40C. The recommended motor cables are shielded multicore type(see section 4.5.2). The values supplied
are typical values.
Example: Cable cross-section of 3 x (3 x 185 + 95) corresponds to 3 cables each consisting of 3 phase conductors
(cross-section 185 mm) + earth conductors (cross-section 95 mm).
-
8/12/2019 4972b_en_MD2S
22/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
22
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.2 - Connection of the control
The POWERDRIVE MD2S inputs have a positive
logic conguration. Using a drive with a control system
which has a different control logic may cause unwantedstarting of the motor.
The POWERDRIVE MD2S control circuit is isolated from
the power circuits by single insulation. Its electronic 0V
is connected to the connection terminal on the outer
protective conductor (earth terminal). The installer must
ensure that the external control circuits are isolatedagainst any human contact.
If the control circuits need to be connected to circuits
conforming to SELV safety requirements, additional
insulation must be inserted to maintain the SELV
classication (see EN 61140).
3.2.1 - Control terminal block location
Px1 Px2 Px3P1 P2
1 1 1
RL2 status relay LED
RL1 status relay LED
Control terminal blocks
Control terminal block
Removable screw terminal block: tightening torque = 0.3 N.m/0.22 lb ft cross-section = 1.5 mm2 screwdriver = 2 mm flat
Analog I/O Digital I/O RelaysPx1 Px2
3.2.2 - Control terminal block characteristics
3.2.2.1 - PX1 terminal block characteristics
1 10V +10 V internal analog source
Accuracy 2%
Maximum output current 10 mA
2 AI1+ Differential analog input 1 (+)
3 AI1- Differential analog input 1 (-)
Factory setting 0-10V speed reference
Input type 10 V differential bipolar analogvoltage (for common mode,connect terminal 3 to terminal 6)
Absolute maximum voltagerange
36 V
Voltage range in common mode 24 V/0 V
Input impedance > 100 k
Resolution 11 bits + sign
Sampling period 2 ms
Input lter bandwidth ~ 200 Hz
4 AI2+ Differential analog input 2 (+)
5 AI2- Differential analog input 2 (-)
Factory setting 0-20 mA speed reference
Input typeUnipolar current(0 to 20 mA, 4 to 20 mA,20 to 0 mA, 20 to 4 mA)
Absolute maximum current 30 mA
Voltage range in common mode 24 V/0 V
Input impedance 100
Resolution 12 bits
Sampling period 2 ms
Input lter bandwidth ~ 200 Hz
6 0V Analog circuit common 0 V
The 0 V on the electronics is connected to the metal ground of thedrive
7 AI3 Analog input 3
Factory setting No assignment
Input type 10 V bipolar analog voltage incommon mode or unipolar current(0 to 20 mA, 4 to 20 mA)
Resolution 11 bits + sign
Sampling period 2 ms
Input lter bandwidth ~ 200 Hz
Voltage range in common mode 24 V/0 V
Voltage mode
Input impedance > 50 k
Absolute maximum voltagerange
30 V
Current mode
Input impedance 100
Absolute maximum current 30 mA
-
8/12/2019 4972b_en_MD2S
23/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
23
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
8 AO1 Analog output
Factory setting 4-20 mA motor current signal
Output type
Bipolar analog voltage in common
mode or unipolar current in
common mode
Resolution 13 bits
Sampling period 2 ms
Voltage mode
Voltage range 10 V
Load resistance 1 k minimum
Current mode
Current range 0 to 20 mA, 4 to 20 mA
Load resistance 500 maximum
9 DI1PTC Digital input 1or PTC thermal sensor
Factory setting No assignment
Sampling period 2 ms
Thermal sensor input
Voltage range 10 V
Trip threshold > 3.3 k
Reset threshold < 1.8 k
Digital input
Type Digital input in positive logic
Voltage range 0 to + 24 V
Absolute maximum voltage
range0 V to + 35 V
Thresholds0 : < 5 V
1 : > 13 V
10 0V Analog circuit common 0 V
The 0 V on the electronics is connected to the metal ground of the
drive
3.2.2.2 - PX2 terminal block characteristics
1+24V ref +24 VDC user output
9
+24 VDC user outputOutput current 100 mA
Accuracy 5%
ProtectionCurrent limiting and setting to trip
mode
2 DO1 Digital output
Factory setting Zero speed
Characteristic Open collector
Absolute maximum voltage + 30 V/0 V
Overload current 150 mA
3 STO-1Drive enable input 1
(Safe Torque Off function)
6 STO-2Drive enable input 2
(Safe Torque Off function)
Input type Positive logic only
Absolute maximum voltage + 30 V
Thresholds0 : < 5 V
1 : > 13 V
Response time < 20 ms
4 DI2 Digital input 2
5 DI3 Digital input 3
7 DI4 Digital input 4
8 DI5 Digital input 5
DI2 factory settingSelection of speed reference
DI3 factory setting
DI4 factory setting Run FWD/Stop input
DI5 factory setting Run reverse/Stop input
Type Digital inputs in positive logic
Voltage range 0 to + 24 V
Absolute maximum voltage
range0 to + 35 V
Thresholds0 : < 5 V
1 : > 13 V
3.2.2.3 - PX3 terminal block characteristics
1 COM-RL1N/O (normally open) relay output
2 RL1
3 COM-RL2N/O (normally open) relay output
4 RL2
Factory setting RL1 Drive status relay
Factory setting RL2 Maximum speed alarm
Voltage 250 VAC
Maximum contact current
2 A - 250 VAC, resistive load
1 A - 250 VAC, inductive load
2 A - 30 VDC, resistive load
Provide a fuse or other overcurrent protection in
the relay circuit.
Note: When the RL1 or RL2 relay is activated, the
corresponding status LED on the control board lights up (see
diagram in section 3.2.1).
-
8/12/2019 4972b_en_MD2S
24/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
24
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.2.3 - Factory conguration of control terminalblocks
Note: For details of the parameters, refer to the
commissioning manual, ref. 4617.
+10V ref
AI1+
AI1-
AI2+
AI2-
0V
COM-RL1
RL1
COM-RL2
RL2
AO1
AI3
+24V ref
DO1
STO-1
DI2
DI3
STO-2
DI5
DI4
+24V ref
1
2
3
4
5
6
1
2
3
4
8
7
0V
DI1/CTP
10
9
1
2
3
4
5
6
8
7
9
PX1
PX2
PX3
status relayDrive (N/O)
Alarm relaymaximum speed (N/O)
0-10 Vspeed reference
4-20 mA speed reference
4-20 mA current image
Motor PTC*
Zero speed
Safe Torque Off/Drive enable input 1Reference selection
Reference selection
Safe Torque Off/
Drive enable input 2Run FWD/Stop
Run REV/Stop
Note:This conguration has been obtained from a drive with
factory settings (default parameter settings).The STO-1 and STO-2 inputs must be closed before giving a
run command.
(*) If the motor thermal sensor needs to be connected to DI1/
PTC, set Mtr.06 (05.70)= Drive terminal (1).
Modication of the Run/Stop control logic
- For "3-wire" control (jog Run/Stop):
DI4
DI5
+24V ref
7
8
9
Run FWD
Stop
List of parameters to adjust: Ctr.06 (06.04)= Run Latched (1)
I/O.10 (08.25) =06.39 Stop (DI5 terminal)
- For Run/Stop control with change of direction:
DI4
DI5
+24V ref
7
9
8
Run/Stop
Change of direction
List of parameters to adjust:
Ctr.06 (06.04) = Run Fwd/Rev (2) I/O.09 (08.24) = 06.34 Run/Stop (DI4 terminal)
I/O.10 (08.25) = 06.33 Fwd/Reverse (DI5 terminal)
Selection of the reference via digital inputs:
DI2 DI3 Selection
0 0Voltage speed reference (0-10 V) on analog input
AI1+, AI1-
0 1
Current speed reference (4-20 mA) on analog
input AI2+, AI2-
1 0 Preset reference 2
Spd.05 (01.22)to be set1 1
-
8/12/2019 4972b_en_MD2S
25/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
25
enINSTALLATION AND MAINTENANCE
Variable speed driveCONNECTIONS
3.3 - STO-1/STO-2 inputs: Safe Torque Off
function
The STO-1 and STO-2 inputs are safety inputs that can be
used to disable the drive output so no torque at the motorshaft is provided.
They are independent of one another. They are created bysimple hardware not connected to the microcontroller. They
acts on two different stages of the IGBT output bridge control.
To enable the drive, the STO-1 and STO-2 inputs must be
connected to the +24V source.
The opening of, at minimum, one of the inputs locks the
output bridge.
These 2 inputs can be used in conjunction to create a "Safe
Torque Off" function with a logic combining 2 separate
channels.
In this conguration, the "Safe Torque Off" function is
guaranteed with a very high level of integrity in conformitywith standards:
- EN 61800-5-2
- EN/ISO 13849-1: 2006; PLe
- IEC/EN 62061: 2005; SIL3
(CETIM approval no. CET0047520)
In a safety system, this built-in function enables the drive to
act as a substitute for a contactor so the motor can run in
freewheel mode.
The STO-1 and STO-2 inputs are compatible with self-testedlogic outputs in controllers such as PLCs, for which the test
pulse lasts for 1 ms maximum.
If the data sent by the 2 inputs is not identical, this generates
a drive trip. The RL1 relay opens and the drive indicates
a "t.r./63" trip on the drive 2-digit display or "STO input
inconsistency" trip on the parameter-setting interface.
For correct use, the power and control connection diagrams
described in the following paragraphs must be adhered to.
The STO-1/STO-2 inputs are safety components
which must be incorporated in the complete
system dedicated to machine safety. As for any
installation, the complete machine must be subject to a
risk analysis. The integrator must determine the safety
category which the installation must comply with. The STO-1 and STO-2 inputs, when open, lock the
drive, so the dynamic braking function is no longer
available. If a braking function is required before the
drive secure disable lock is applied, a time-delayed
safety relay must be installed to activate the locking
automatically after the end of braking.If braking needs to be a machine safety function, it must
be provided by an electromechanical solution since the
dynamic braking by the drive function is not considered
as a secure disable function.
The STO-1/STO-2 inputs do not provide theelectrical isolation function. Prior to any work carry out
on tre drive/installation, the power supply must therefore
be switched of an approved isolating device (isolator,switch, etc).
3.3.1 - Single channel locking (SIL1 - PLb)
3-phase AC power supply, in accordance with safety standardIEC/EN 62061: 2005 and EN/ISO 13849-1: 2006 - Single
channel locking (SIL1 - PLb).
U V W
Px2
+24V Ref
DO1
STO-1
DI2
DI3
STO-2
DI4
DI5
+24V Ref
M
3
PE
PEL1 L2 L3
POWERDRIVE MD2S
Safe Torque Off/Driveenable input
Run FWD/Stop
Run REV/Stop
3.3.2 - Double channel locking (SIL3 - PLe).
3-phase AC power supply, in accordance with safety standard
IEC/EN 62061: 2005 and EN/ISO 13849-1: 2006 - Doublechannel locking (SIL3 - PLe)
U V W
Px2
+24V Ref
DO1
STO-1
DI2
DI3
STO-2
DI4
DI5
+24V Ref
M
3
PE
PEL1 L2 L3
POWERDRIVE MD2S
Output stage of asafety relay
Run FWD/Stop
Run REV/Stop
-
8/12/2019 4972b_en_MD2S
26/48
-
8/12/2019 4972b_en_MD2S
27/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
27
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE
4.4.2 - Mains transient overvoltages
There are numerous sources of overvoltages on an electricalinstallation:
Connection/disconnection of banks of power factor
correction capacitors High-power thyristor-controlled equipment (oven, DC drive,
etc)
Results of lighning
4.4.2.1 - Connection/disconnectionofabankofpowerfactor
correction capacitors
Connecting power factor correction capacitors in parallel on
the drive power supply line when the drive is running cangenerate transient overvoltages that are likely to trip the drive
safety devices, or even damage it in extreme cases.
If banks of power factor correction capacitors are used on the
power supply line, make sure that:
The threshold between steps is low enough to avoidcausing overvoltage on the line The capacitors are not permanently connected
4.4.2.2 - Presence of commutation notches on the line
When high-power thyristor-controlled equipment is connected
on the same line as the drive, it is essential to ensure that
the harmonics generated by the commutation notches do
not excessively distort the mains voltage and do not create
voltage peaks with amplitude higher than 2 x mains Vrms. If
this is the case, it is essential to take corrective measures byinserting a choke in the line supplying the thyristor-controlled
equipment or by moving the drive power supply line to
another source.
4.4.3 - Unbalanced power supply
Similar to what is observed on an electric motor, the linecurrent imbalance of a drive operating on an unbalanced
mains supply may be several times the value of the
voltage imbalance measured on the power supply. A highly
unbalanced mains supply (>2%) associated with a low
mains impedance may result in a high level of stress on the
components at the input stage of a drive.Additional mains chokes can be installed upstream of a
POWERDRIVE MD2S supplied by an unbalanced mains
in order to reduce the current imbalance factor (see
characteristics in section 5.4).
Neutral IT point connection
For IT power supplies, open the commoning link connecting
the EMC capacitors to earth as indicated below.
POWERDRIVE MD2S 100T to 270T
Other POWERDRIVE MD2S ratings
4.4.4 - Ground connections
The equipotential earth bonding of some industrial sites
is not always observed. This lack of equipotentiality leads
to leakage currents which ow via the earth cables (green/
yellow), the machine chassis, the pipework, etc, and alsovia the electrical equipment. In some extreme cases, these
currents can trip the drive.
It is essential that the earth network is designed and
implemented by the installation supervisor so that its
impedance is as low as possible, so as to distribute the fault
currents and high-frequency currents without them passingthrough electronic equipment.
Metal grounds must be mechanically connected to each other
with the largest possible electrical contact area. Under no
circumstances can the earth connections designed to protectpeople, by linking metal grounds to earth via a cable, serve as
a substitute for the ground connections (see IEC 61000-5-2).
The immunity and radio-frequency emission level are directly
linked to the quality of the ground connections.
-
8/12/2019 4972b_en_MD2S
28/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
28
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE
4.5 - Basic precautions for installation
These should be taken into account when wiring the cabinet
and the external components. In each paragraph, they are
listed in decreasing order of effect on correct operation of theinstallation.
4.5.1 - Wiring inside the cabinet
- Do not run the control cables and the power cables in the
same cable ducts.
- For control cables, use shielded twisted cables.
4.5.2 - Wiring outside the cabinet
Connect the motor earth terminal directly to that of
the drive.
It is recommended that a shielded symmetrical cable is
used: three phase conductors and three PE conductors
arranged symmetrically.
U
WV
PE
PE PE
Shielding
A separate PE protective conductor is mandatory if the
conductivity of the cable shielding is less than 50% of the
conductivity of the phase conductors.
- The shield must be connected at both ends: drive end and
motor end (connected round the whole circumference).- In the second industrial environment, the shielded motor
power supply cable can be replaced by a 3-core + earth
cable placed in a fully enclosed metal conduit (metal cable
duct for example). This metal conduit must be mechanically
connected to the electrical cabinet and the structure
supporting the motor.
If the conduit consists of several pieces, these should be
interconnected by braids to ensure earth continuity. The
cables must be positioned and held in a cloverleaf formationin the conduit.
U
WVPE
U
WV
PE
EMCbraid
Clamp
- There is no need to shield the power supply cables between
the mains supply and the drive.
- Isolate the power cables from the control cables. The powercables must intersect the other cables at an angle of 90.
- Isolate sensitive elements (probes, sensors, etc) from metal
structures which may be shared by the motor support.
-
8/12/2019 4972b_en_MD2S
29/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
29
enINSTALLATION AND MAINTENANCE
Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE
4.6 - Electromagnetic compatibility (EMC)
CAUTION:
Conformity of the drive is only assured when the mechanical and electrical installation instructions described in thismanual are adhered to.
Immunity
Standard Description Application Conformity
IEC 61000-4-2Electrostatic discharges Product casing Level 3 (industrial)
EN 61000-4-2
IEC 61000-4-3 Immunity standards for radiated
radio-frequencyProduct casing Level 3 (industrial)
EN 61000-4-3
IEC 61000-4-4Bursts of fast transients
Control cable Level 4 (industrially hardened)
EN 61000-4-4 Power cable Level 3 (industrial)
IEC 61000-4-5Shock waves Power cables Level 4
EN 61000-4-5
IEC 61000-4-6 Generic immunity standards for
conducted radio-frequency
Control and power
cablesLevel 3 (industrial)
EN 61000-4-6
EN 50082-2Generic immunity standards forthe industrial environment
- ConformingIEC 61000-6-2
EN 61000-6-2
EN 61800-3
Variable speed drive standards Conforming to the rst and second environmentIEC 61800-3
EN 61000-3
Emission
Standard Description CategoryConformity conditions
Standard With external RFI lter(1)
EN 61800-3 Variable speed drive standards
C1 - -
C2 -
Conforming
- Cable length < 20 m- Switching frequency < 4 kHz
C3
Conforming
- Cable length < 100 m
- Switching frequency < 4 kHz
Conforming
- Cable length < 100 m
- Switching frequency < 6 kHz
(1) See 5.4
-
8/12/2019 4972b_en_MD2S
30/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
30
enINSTALLATION AND MAINTENANCE
Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS
5.1 - Parameter setting
5.1.1 - MDX-Powerscreen General
The POWERSCREEN interface is a touch screen which can
be used to access various menus to setup and supervise thedrive. It is installed as standard on the POWERDRIVE MD2S.
After the loading phase following the power-up of the drive,
the parameter-setting interface displays the screen below in
french. Select language using the "F" buttons below
COM CPU PWR
F
C D E
A
B
Ref. Function
A 4.3" touch screen
B Touch-sensitive button to access the main menu
C
"COM" LED, indicates the state of the communicationwith the drive.
Off: no communication
Flashing: communicating
D "CPU" LED, indicates the status of the interface CPU
E"PWR" LED, indicates the state of the interface power
supply
FTouch-sensitive buttons for language selection (can take
a few minutes to load)
5 - PARAMETER-SETTING INTERFACE AND OPTIONS
Connection to the drive
Px1 Px2 Px3P1 P 2
1 1 1
Connector for optionaleldbus and/or
speed feeback
Connector for MDX-
KEYPAD or MDX-Powerscreen display
USB connector for
MDX-SOFT
P1 connector
This connector is a slave type B USB socket, and is used to
communicate via PC using the MDX-SOFT software.In conformity with standard EN 60950, the USB link
can only be used via a device that provides
isolation of 4 kV (MDX-USB isolator option).
P2 terminal blockThis is a standard RS485/RS422 terminal block which
is used to connect a parameter-setting interface or to
communicate via Modbus RTU.
Terminals Description
1 0V
2 Rx\, Tx\
3 Rx, Tx
4 24V
Check that control circuits are powered downbefore disconnecting the programming interface
from the P2 connector.
-
8/12/2019 4972b_en_MD2S
31/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
31
A
E
D
F
C
B
G
enINSTALLATION AND MAINTENANCE
Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS
Architecture
From the welcome screen, press the button to access the
main page of the parameter-setting interface, consisting of 5
touch-sensitive buttons:- Information: Can be used to obtain information very quicklyabout the drive, the eldbus option, the parameter-setting
interface, and can also be used to select the language.
- Read mode: Is used to display the status of the drive when
stopped or in operation, as well as its main measurement
data points.- Parameter setting: Used for reading and/or modication of
all the drive parameters, as well as to set the date and time on
the display.
- Control via keypad: Gives direct access to motor control
via the touch screen (Run/Stop, direction of rotation, speed
reference). These screen parameters can be set using the
Parameter setting/Parameter setting via the keypad menu.
Control via the keypad is disabled in factory-set conguration.- Trip history: Gives a quick overview of the last 10 drive
trips.
- : This button is accessible on all screens in factory-setconguration and is used to give a stop command (can be
disabled).
At any time and regardless of the screen displayed, the
button can be used to return to previous pages, as far as the
interface main page.
For further information, see the commissioning manual
ref. 4617.
5.1.2 - MDX-KEYPAD
5.2.3.1 - General
This keypad, which is remote from the drive, makes easy the
setting of the POWERDRIVE MD2S and provides accessto all parameters. Its LCD display, consisting of one line of
12 characters and 2 lines of 16 characters, offers text which
can be displayed in 4 languages (English, French, German
and Spanish).
The MDX-KEYPAD has 2 main functions:
- A read mode for POWERDRIVE MD2S supervision anddiagnostics
- An access mode to all the POWERDRIVE MD2Sparameters
in order to optimise settings or congure special applications.
As soon as it is switched on, the MDX-KEYPAD is set to read
mode. The buttons are used to scroll through the allparameters required for supervision and diagnostics:
- Motor current
- Motor frequency
- Motor voltage
- Analog I/O levels- Digital I/O states
- Logic function states
- Timer
Ref. Function
A
3-line backlit LCD display indicating:- The drive operating status and its main data
- The main adjustment parameters via a "Quick
parameter setting" menu
- All the drive parameters via 21 "Advanced parameter
setting" menus (access via a code)
B
Green button for run command if control via the keypad is
enabled.See "Keypad set up".
C
Red button for drive reset or to give a stop command if
control via the keypad is enabled.
See parameters Ctr.05 (6.43)and 06.12.
D
Blue button for change of direction of rotation if control via
the keypad is enabled.
See parameter Ctr.05 (6.43).
ENavigation button ( , , , ) for movingthrough the various menus and changing the contents of
parameters.
F button for saving and changing the mode (display,
read, set parameters).
G "?"button not used.
For more information, see the commissioning manual
ref. 4617. This manual describes conguration using the
MDX-Powerscreen parameter-setting interface, but thecommissioning procedure also applies to the MDX-KEYPAD.
Installation
The MDX-KEYPAD does not require any special installation.At the power off, simply connect it via its 1.5 metre cable
(supplied with the keypad), on P2 connector.
5.1.3 - MDX-SOFT
The MDX-SOFT enables parameter setting or supervision of
the POWERDRIVE MD2S from a PC. Numerous functionsare available:
- Fast commissioning
- File saving
- Comparison of 2 les or one le with the factory settings
- Printing of a complete le or differences compared to the
factory settings
- Supervision- Diagnostics
To connect the PC to the POWERDRIVE MD2S, use an"MDX-USB Isolator" isolated USB cable.
This software can be downloaded from the web at the
following address: http://www.leroy-somer.com/
http://www.leroy-somer.com/en/downloads/software/http://www.leroy-somer.com/en/downloads/software/ -
8/12/2019 4972b_en_MD2S
32/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
32
enINSTALLATION AND MAINTENANCE
Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS
5.2 - Add-on options
The POWERDRIVE MD2S control board is designed to be
plugged with various optional modules. Several options can
be combined: Speed feedback option (see section 5.2.1)
Fieldbus option (see section 5.2.2)
Additionnal I/O option (see section 5.2.3)
5.2.1 - Fieldbus modules
Fieldbus modules can be used to communicate with the
corresponding networks respective. They can be integrated
in and are supplied by the drive.
Two types of options are offered (with the same functionality):
MDX option: option to be tted to the control board (white)
CM module: compact module to be integrated in an
existing MDX board (grey)
Option / Module Fieldbus
MDX-PROFIBUS
CM-PROFIBUSProbus DP V1
MDX-MODBUS
CM-MODBUSModbus RTU on RS485/232
MDX-ETHERNET
CM-MODBUSModbus TCP on Ethernet
MDX-CAN-OPENCM-CAN-OPEN
Can Open
MDX-ETHERNET-IPCM-ETHERNET-IP
EtherNet/IP
Check that the optional module is in good
condition: never install a damaged module in the
drive.
Before installing or removing the option, or when it is
necessary to disconnect the cables connected to it, it is
essential for the drive to be switched off.
CAUTION:
Do not break the cut-out part.
A MDX-Fieldbus option can never take the MDX-ENCODER terminal block.
For more information, refer to the manuals for the relevantoptions available on www.leroy-somer.com.
5.2.2 - Speed feedback option
5.2.2.1 - MDX-ENCODER
The MDX-ENCODER option is used to manage the motor
speed feedback. It manages incremental encoders with orwithout commutation channels.
Before installing or removing the MDX Speed
feedback option, or when it is necessary todisconnect the cables connected to the option, it is
essential for the drive to be switched off.
5.3.2.2 - General
Use a shielded cable for connection, and connect the
shield over 360 using the grounding bracket (see section
5.2.4).
The MDX-Encoder module can manage the motor PTC
thermal probe via terminals T1 and T2. In this case, someparameters need to be set. Refer to parameter Mtr.06 (05.70)
in the commissioning manual ref. 4617.
Terminals 0 and 0\ are not used.
Note: LEROY-SOMER offers optional connection cables. For
more information, please get in touch with your usual LEROY-
SOMER contact.
CAUTION: The encoder cable shielding must always be
connected to the grounding bracket supplied with the
option.
Connection terminal blocks
- + A B O
T1 T2 U V W
A B O
U V W
+Power supply
-
Rated voltage
5V 10% - Output current 300mA
15V 10% - Output current 200mA
A
Encoder channel connectionA\
B
B\
Maximumfrequency
500 kHz
-
8/12/2019 4972b_en_MD2S
33/48
-
8/12/2019 4972b_en_MD2S
34/48
LEROY-SOMER 4972 - 2013.06 / b
POWERDRIVE MD2S
34
enINSTALLATION AND MAINTENANCE
Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS
5.2.2.2 - MDX-RESOLVER
The MDX-RESOLVER option is used to manage the motor
speed feedback. It manages 2 to 8 poles resolvers.
Before installing or removing the MDX Speed
feedback option, or when it is necessary to
disconnect cables from the option, it is essential
for the drive to be switched off.
General
The MDX-RESOLVER module can manage the motor
PTC thermal probe via terminals T1 and T2. In this case,
some parameters need to be set. Refer to parameter Mtr.06
(05.70) in the commissioning manual ref. 4617.
Note: LEROY-SOMER offers optional connection cables. For
more information, please get in touch with your usual LEROY-
SOMER contact.
Use a single twisted pair cable, shielded pairs with
an outer shield for the connection.
Connect the shield over 360 at both ends (grounding
bracket supplied with the option).
Connection terminal blocks
MDX-RESOLVER wiring
1 Resolver
excitation
LOW
2 HIGH
Characteristic 10 kHz sine wave signal
Rated voltage
Transformer ratio (03.58):
4 : 1 = 5.2 Vrms
3 : 1 = 3.8 Vrms
2 : 1 = 2.6 Vrms 1 : 1 = 1.3 Vrms
Max. current 80 mA (EXC HIGH)
3 x
4 x
5Encoder
simulation
Channel A output6 Channel /A output
7 Channel B output
8 Channel /B output
CharacteristicRS 485 differential voltage
(A and /A, B and /B)
9 x
10 x
11
Resolver inputs
SIN HIGH
12 SIN LOW
13 COS HIGH
14 COS LOW
Characteristic 2 Vrms sine wave signal (max)
Frequency 10 kHz15 x
5.2.3 - MDX-I/O TIMER option
General:
The MDX-I/O TIMER option is used to:
Increase the number of drive inputs and outputs Access the drive conguration: WEB server function
Back up and restore the drive parameter settings (via PC) Save parameters for a period of time (including an SD
type memory card): Data logger function
Detail of the features :
- 2 analog inputs (including a differential analog input)
- 1 KTY temperature sensor input- 1 analog output
- 4 digital inputs
- 2 digital inputs
- 2 programmable relays
- 1 internal clock
- year, month, day, hours, minutes, seconds backup mode- 1 Ethernet port on RJ45 connector
Connection
Please consult the specic documentation for the MDX-I/O
TIMER.
5.2.4 - Option installation
5.2.4.1 - grounding b