    POWERDRIVE MD2S

    Thismanual

    istobegive

    nto

    theenduse

    r

    Variable speed drive

    Installation and maintenance

    en

    M

    IGBT IGBT IGBT

    Micro-

    controller

    I/O control

    Mains

    supply

    ASIC

    PWM

    Switching mode

    power supply

    (Optional

    encoder

    or sensor)

    MDXEncoder(optional)

    Control board

  • 8/12/2019 4972b_en_MD2S

    2/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    2

    enINSTALLATION AND MAINTENANCE

    Variable speed drive

    NOTE

    LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest

    technological developments. The information contained in this document may therefore be changed without notice.

    CAUTION

    For the user's own safety, this variable speed drive must be connected to an approved earth terminal).

    If accidentally starting the installation is likely to cause a risk to personnel or the machines being driven, it is essential to complywith the power connection diagrams recommended in this manual.

    The variable speed drive is tted with safety devices which, in the event of a problem, control stopping and thus stop the motor. The

    motor itself can become jammed for mechanical reasons. Voltage uctuations, and in particular power cuts, may also cause the

    motor to stop. The removal of the causes of the shutdown can lead to restarting, which may be dangerous for certain machines or

    installations.In such cases, it is essential that the user takes appropriate precautions against the motor restarting after an unscheduled stop.

    The variable speed drive is designed to be able to supply a motor and the driven machine above its rated speed.

    If the motor or the machine are not mechanically designed to withstand such speeds, the user may be exposed to serious dangerresulting from their mechanical deterioration.

    Before programming a high speed, it is important that the user checks that the installation can withstand it.

    The variable speed drive which is the subject of this manual is designed to be integrated in an installation or an electrical machine,

    and can under no circumstances be considered to be a safety device. It is therefore the responsibility of the machine manufacturer,

    the designer of the installation or the user to take all necessary precautions to ensure that the system complies with current

    standards, and to provide any devices required to ensure the safety of equipment and personnel.

    LEROY-SOMER declines all responsibility in the event of the above recommendations not being observed.

    ........................................

    This manual only describes the general features, characteristics and installation of the POWERDRIVE MD2S. For

    commissioning, refer to manual ref. 4617.

  • 8/12/2019 4972b_en_MD2S

    3/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    3

    enINSTALLATION AND MAINTENANCE

    Variable speed drive

    SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES

    (In accordance with the low voltage directive 2006/95/EC)

    Throughout the manual, this symbol warns of

    consequences which may arise from inappropriate

    use of the drive, since electrical risks may lead to material

    or physical damage as well as constituting a re hazard.

    1 - General

    Depending on their degree of protection, the variable speed

    drives may contain unprotected live parts, which may be moving

    or rotating, as well as hot surfaces, during operation.

    Unjustied removal of protection devices, incorrect use, faulty

    installation or inappropriate operation could represent a seriousrisk to personnel and equipment.

    For further information, consult the documentation.

    All work relating to transportation, installation, commissioning

    and maintenance must be performed by experienced, qualied

    personnel (see IEC 364, CENELEC HD 384 or DIN VDE 0100,as well as national specications for installation and accidentprevention).

    In these basic safety instructions, qualied personnel means

    persons competent to install, mount, commission and operate

    the product and possessing the relevant qualications.

    2 - Use

    Variable speed drives are components designed for integration

    in installations or electrical machines.

    When integrated in a machine, commissioning must not take

    place until it has been veried that the machine conforms

    with directive 2006/42/EC (Machinery Directive). It is alsonecessary to comply with standard EN 60204, which stipulates

    in particular that electrical actuators (which include variablespeed drives) cannot be considered as circuit-breaking devices

    and certainly not as isolating switches.

    Commissioning can take place only if the requirements of the

    Electromagnetic Compatibility Directive (EMC 2004/108/EC)are met.

    The variable speed drives meet the requirements of the Low

    Voltage Directive 2006/95/EC. The harmonised standards

    of the DIN VDE 0160 series in connection with standard VDE

    0660, part 500 and EN 60146/VDE 0558 are also applicable.

    The technical characteristics and instructions concerning theconnection conditions specied on the nameplate and in the

    documentation provided must be observed without fail.

    3 - Transportation, storageAll instructions concerning transportation, storage and correct

    handling must be observed.The climatic conditions specied in the technical manual must

    be observed.

    4 - Installation

    The installation and cooling of equipment must comply with thespecications in the documentation supplied with the product.

    The variable speed drives must be protected against any

    excessive stress. In particular, there must be no damage to

    parts and/or modication of the clearance between components

    during transportation and handling. Avoid touching the electronic

    components and contact parts.The variable speed drives contain parts which are sensitive to

    electrostatic stresses and may be easily damaged if handled

    incorrectly. Electrical components must not be exposed to

    mechanical damage or destruction (risks to health!).

    5 - Electrical connection

    When work is performed on variable speed drives which arepowered up, the national accident prevention regulations must

    be respected.

    The electrical installation must comply with the relevant

    specications (for example conductor cross-sections, protection

    via fused circuit-breaker, connection of protective conductor).

    More detailed information is given in the documentation.Instructions for an installation which meets the requirements

    for electromagnetic compatibility, such as screening, earthing,

    presence of lters and correct insertion of cables and

    conductors, are given in the documentation supplied with the

    variable speed drives. These instructions must be followed

    in all cases, even if the variable speed drive carries the CE

    mark. Adherence to the limits given in the EMC legislation isthe responsibility of the manufacturer of the installation or the

    machine.

    6 - Operation

    Installations in which variable speed drives are to be integrated

    must be tted with additional protection and monitoring

    devices as laid down in the current relevant safety regulations,

    such as the law on technical equipment, accident prevention

    regulations, etc. Modications to the variable speed drives

    using control software are permitted.Active parts of the device and the live power connections must

    not be touched immediately after the variable speed drive is

    powered down, as the capacitors may still be charged. In view

    of this, the warnings xed to the variable speed drives must beobserved.

    Permanent magnet motors generate electrical energy whilethey are rotating, even when the drive is switched off. In this

    case, the drive continues to be powered by the motor terminals.

    If the load is capable of turning the motor, a switching device

    must be provided upstream of the motor to isolate the drive

    during maintenance operations.During operation, all doors and protective covers must be kept

    closed.

    7 - Servicing and maintenance

    Refer to the manufacturers documentation.

    See the Maintenance section in this document.

    This manual is to be given to the end user.

  • 8/12/2019 4972b_en_MD2S

    4/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    4

    enINSTALLATION AND MAINTENANCE

    Variable speed drive

    FOREWORD

    This manual describes the installation of POWERDRIVE MD2Svariable speed drives. It also gives details of all its options and

    extensions which the user may choose to suit his requirements.

    POWERDRIVE MD2S

    MDX-KEYPAD

    MDX-SOFTParameter-setting

    software+ PC link cable

    MDX-Powerscreenparameter-setting

    interface

    Compabloc Axial output

    - Helical gears

    HPM motor

    Orthobloc Orthogonal output

    - Helical bevel gears

    Radial

    forcedventilation

    LSES-FLSES motor

    LSMV motor

    LSRPM motor

    Brake

    Axial forcedventilation

    Encoder/Sensor

    MotorsGearboxes Motor options

    OptionsParameter setting

    IP 54 Cabinet baseplate (100 or 200 mm) Isolator switch High-speed fuses RFI lter

    Line reactor (depending on rating)

    Encoder or resolver input Additional I/O Communication options

    (MDX-PROFIBUS, MDX-ETHERNET, MDX-MODBUS, etc.)

  • 8/12/2019 4972b_en_MD2S

    5/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    5

    enINSTALLATION AND MAINTENANCE

    Variable speed drive

    CONTENTS

    1 - GENERAL INFORMATION .................................................................................................................................. 7

    1.1 - General ........................................................................................................................................................ 71.2 - Product designation .................................................................................................................................... 71.3 - Environmental characteristics ...................................................................................................................... 71.4 - Electrical characteristics .............................................................................................................................. 8

    1.4.1 - General characteristics.......................................................................................................................................... 8

    1.4.2 - Electrical characteristics ........................................................................................................................................ 8

    1.4.3 - Derating at low frequency ...................................................................................................................................... 9

    1.4.4 - Derating according to the temperature and switching frequency ......................................................................... 10

    2 - MECHANICAL INSTALLATION ......................................................................................................................... 12

    2.1 - Checks upon receipt .................................................................................................................................. 122.2 - Handling .................................................................................................................................................... 12

    2.3 - Installation recommendations ................................................................................................................... 132.4 - Removing and re-tting the IP21 roof......................................................................................................... 132.5 -Assembly and dismantling of the IP54 roof ................................................................................................ 132.6 - Dimensions ................................................................................................................................................ 142.7 - Weight ....................................................................................................................................................... 152.8 - Drive losses ............................................................................................................................................... 152.9 - Drive ventilation ow rates and noise levels............................................................................................... 15

    3 - CONNECTIONS ................................................................................................................................................. 16

    3.1 - Power connections .................................................................................................................................... 163.1.1 - Location of the control terminal block, fuse boards and external power supply .................................................... 16

    3.1.2 - Electronics and forced ventilation power supply .................................................................................................. 17

    3.1.3 - Characteristics of connection terminals ............................................................................................................... 17

    3.1.4 - Location of power terminal blocks........................................................................................................................ 18

    3.1.5 - Cables and fuses ................................................................................................................................................. 20

    3.2 - Connection of the control ........................................................................................................................... 223.2.1 - Control terminal block location............................................................................................................................. 22

    3.2.2 - Control terminal block characteristics .................................................................................................................. 22

    3.2.3 - Factory conguration of control terminal blocks................................................................................................... 24

    3.3 - STO-1/STO-2 inputs: Safe Torque Off function .......................................................................................... 253.3.1 - Single channel locking (SIL1 - PLb) ..................................................................................................................... 25

    3.3.2 - Double channel locking (SIL3 - PLe).................................................................................................................... 25

    4 - GENERAL EMC - HARMONICS - MAINS INTERFERENCE ............................................................................. 26

    4.1 - Low-frequency harmonics .......................................................................................................................... 26

    4.2 - Radio-frequency interference: Immunity .................................................................................................... 264.2.1 - General ............................................................................................................................................................... 26

    4.2.2 - Standards ............................................................................................................................................................ 26

    4.2.3 - Recommendations .............................................................................................................................................. 26

    4.3 - Radio-frequency interference: Emission .................................................................................................... 264.3.1 - General ............................................................................................................................................................... 26

    4.3.2 - Standards ............................................................................................................................................................ 26

    4.4 - Mains supply .............................................................................................................................................. 264.4.1 - General ............................................................................................................................................................... 26

    4.4.2 - Mains transient overvoltages ............................................................................................................................... 27

    4.4.3 - Unbalanced power supply ................................................................................................................................... 27

    4.4.4 - Ground connections ............................................................................................................................................ 27

    4.5 - Basic precautions for installation .............................................................................................................. 284.5.1 - Wiring inside the cabinet...................................................................................................................................... 28

    4.5.2 - Wiring outside the cabinet ................................................................................................................................... 28

  • 8/12/2019 4972b_en_MD2S

    6/48

  • 8/12/2019 4972b_en_MD2S

    7/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    7

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL INFORMATION

    1 - GENERAL INFORMATION

    1.1 - General

    The POWERDRIVE MD2Sis a variable speed drive with veryhigh performance levels that can be used to control:

    - Induction motors without speed sensor (open loop mode

    select ) for applications that do not need rated torque

    control above 1/10thof the rated speed.

    - Asynchronous or synchronous permanent magnet motorswith virtual speed feedback (ux vector mode with software

    sensor function ) for applications that require rated torque

    control from 1/20thof the rated speed.

    Combined with the MDX-ENCODER option, the

    POWERDRIVE MD2S is a drive that can also be used to

    control asynchronous or synchronous magnet machines forapplications that require very high dynamic performances,

    torque control from zero speed or high speed accuracy

    (closed loop vector mode with speed feedback ).The performance of the POWERDRIVE MD2Sis compatible

    with use in all 4 quadrants of the torque/speed plane with the

    braking module option incorporated.With IP54 protection (optional), installation is possible directly

    on the machine itself in harsh environments.

    1.2 - Product designationPOWERDRIVE MD2S - 180 T

    *

    Drive versionMD2S : 6 pulsesMD2T : 12 pulsesMD2E : 18 pulsesMD2W : 24 pulsesMD2R : Regen

    Rating in kVA

    3-phase powersupply

    T : 400 V to 480 VTH : 525 V to 690 V

    Modular variablespeed drive withflux vector control

    Cooling: - : Air L : Liquid

    (*) See the corresponding installation manual

    Depending on the options installed, a sufx (-B or -O) isadded to the product commercial designation.

    Nameplate

    MOTEURS LEROY-SOMER

    16015 ANGOULEME

    MADE IN FRANCE

    ENTREE - INPUT

    Ph V (V) Hz (Hz) I(A)

    3 400-480 50/60 295Alim auxiliaire 800VA

    400V/50Hz 480V/60Hz

    TYPE :

    S/N :

    09999999999

    POWERDRIVE MD2S 180T

    I(A) = maximum input current for 400 V mains supply, in

    normal duty

    The nameplate can be found inside the cabinet door at the top

    (another copy can be found on the outside of the cabinet, at

    the top on the right-hand side).

    1.3 - Environmental characteristics

    Characteristic Level

    Protection IP21 (IP54 as an option)

    Storage andtransport

    temperature

    -30C to +60C (see section 7.2)

    Ambient operating

    temperature(outside the cabinet)

    -10C to +40C, up to +50C with derating(see section 1.4.4)

    Classication of

    environmental

    conditions

    In accordance with IEC 60721-3-3:

    Biological classication in accordance with

    class 3B1Classication as regards chemically

    active substances in acc. with class 3C2

    Classication as regards mechanically

    active substances in acc. with class 3S2

    Relative humidity

    In accordance with IEC 60068-2-56

    < 90% non condensing

    Altitude

    1000 m without derating

    > 1000 m up to 4000 m maximum(as required):

    Current derating of 1% per additional 100

    m

    E.g. for 1300 m, derate the Ico and Imaxcurrents by 3%

    Operating temperature derating of 0.6C

    per 100 m

    E.g. for 1300 m, the electricalcharacteristics are maintained for an

    ambient temperature of

    [40- (3 x 0.6)] = 38.2C.

    Vibrations

    In accordance with IEC 60068-2-6Exposed product: 2 m/s

    (9-200 Hz), 0.6 mm (2-9 Hz)

    Packaged product: 10m/s(9-200 Hz), 3 mm (2-9 Hz)

    ShocksPackaged product: in accordance with

    IEC 60068-2-29

    Atmospheric

    pressure700 to 1060 hPa

  • 8/12/2019 4972b_en_MD2S

    8/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    8

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL INFORMATION

    1.4 - Electrical characteristics

    All work relating to installation, commissioning and maintenance must be carried out by experienced, qualied

    personnel.

    1.4.1 - General characteristics

    Characteristic Level

    Power supply voltage3-phase mains supply: 400 V -10% to 480 V +5% ("T" ratings) or525 V -10% to 690 V +10% ("TH" ratings)

    Phase voltage imbalance < 2%

    Input frequency 5% around the rated frequency (50 or 60 Hz)

    Maximum number of power-ups per hour (power) 20

    Output frequency range 0 to 590 Hz

    ROHS conformance Conforming to standard 2002-95-EC

    For operation with a neutral IT point connection, follow the instructions given in section 4.4.3.

    1.4.2 - Electrical characteristics

    Ico: Continuous output current.

    Pout: Output power.

    Imax (60s): Maximum output current, available for 60 seconds every 600 seconds.

    Heavy duty: For heavy-duty constant torque machines (presses, grinders, hoisting, etc) and all applications where signicant

    inertia has to be accelerated quickly (centrifuges, translation of travelling cranes, etc).Normal duty: For normal-duty constant torque or centrifugal torque machines (fans, compressors, etc).

    CAUTION: In its factory setting, the drive operates with a switching frequency of 3 kHz.

    400 V 3-phase mains supplySwitching frequency = 3 kHz - ambient temperature 40C (35C with IP54 option)- altitude 1000 m.

    POWERDRIVE MD2Srating

    Heavy duty Normal dutyImax (60 s)

    (A)Pout

    (kW)

    Ico

    (A)

    Pout

    (kW)

    Ico

    (A)

    100T 75 142 90 175 200

    120T 90 172 110 212 240

    150T 110 220 132 250 312

    180T 132 260 160 315 365

    220T 160 310 200 400 435

    270T 200 380 250 470 530

    340T 250 470 315 580 660400T 315 545 355 640 760

    470T 355 670 450 800 940

    600T 450 815 550 990 1140

    750T 550 1000 675 1220 1400

    900T 675 1230 750 1430 1725

    1100T 750 1465 900 1700 2050

    1400T 900 1775 1100 2100 2485

  • 8/12/2019 4972b_en_MD2S

    9/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    9

    0 5 10 15 20

    20 %

    40 %

    60 %

    80 %

    100 %

    120 %

    140 %

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL INFORMATION

    525 V to 690 V 3-phase mains supply

    Switching frequency = 3 kHz - ambient temperature 40C (35C with IP54 option) - altitude 1000 m.

    POWERDRIVE MD2S

    rating

    Heavy duty Normal dutyImax (60 s)

    (A)

    Pout at 575 V

    (kW)

    Pout at 690 V

    (kW)

    Ico

    (A)

    Pout at 575 V

    (kW)

    Pout at 690 V

    (kW)

    Ico

    (A)

    270TH 160 200 220 200 250 280 308

    340TH 200 250 270 250 315 340 378

    400TH 250 315 330 315 400 415 465

    500TH 315 400 390 400 450 480 545

    600TH 400 450 455 450 550 580 638

    750TH 450 550 570 550 700 730 800

    900TH 550 700 715 700 850 900 1000

    1200TH 700 850 880 850 1100 1120 1230

    1500TH 850 1100 1060 1100 1300 1300 1485

    Frequency(Hz)

    % Ico or% Imax (60 s)1.4.3 - Derating at low frequency

    Measuring the temperature of the power bridges in

    conjunction with thermal modelling of the IGBTs protects the

    POWERDRIVE MD2S against overheating.

    At low motor frequencies, IGBT modules are subject to tough

    temperature cycling, which may reduce their life time. To

    prevent this risk, the curve opposite indicates the derating for

    output currents Ico and Imax when operating at low motor

    frequency in continuous operation.

  • 8/12/2019 4972b_en_MD2S

    10/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    10

    100T 142 142 142 130 118 175 175 162 148 134

    120T 172 172 166 150 136 220 212 188 170 154

    150T 222 220 198 176 160 260 250 224 200 182

    180T 260 260 260 260 250 315 315 310 305 285

    220T 310 310 310 310 285 400 400 385 355 325

    270T 380 380 380 355 320 470 470 440 400 365

    340T 470 470 465 420 380 580 580 525 475 430

    400T 545 545 535 480 430 650 640 605 545 490

    470T 670 670 640 575 515 800 800 725 650 585

    600T 815 815 810 730 670 990 990 920 830 760

    750T 1000 1000 985 900 820 1220 1220 1120 1020 930

    900T 1230 1230 1145 1065 970 1430 1430 1300 1210 1100

    1100T 1465 1465 1395 1260 1165 1700 1700 1580 1430 1320

    1400T 1775 1775 1700 1550 1410 2100 2100 1930 1760 1600

    100T 142 142 136 122 112 175 172 154 138 126

    120T 172 172 156 140 126 215 200 176 158 144

    150T 222 210 186 164 148 255 238 210 186 168

    180T 260 260 260 260 235 315 310 305 295 265

    220T 310 310 310 295 265 400 395 370 335 300

    270T 380 380 370 330 295 470 465 420 375 335

    340T 470 470 430 380 340 580 560 485 430 385

    400T 545 540 490 430 385 650 610 555 490 435

    470T 670 670 585 515 465 800 760 665 585 525

    600T 815 815 750 660 600 990 960 850 750 680

    750T 1000 1000 910 810 730 1220 1160 1030 920 830

    900T 1230 1200 1050 960 875 1430 1360 1190 1090 990

    1100T 1465 1455 1285 1135 1040 1700 1650 1460 1290 1180

    1400T 1775 1765 1560 1400 1260 2100 2000 1770 1590 1430

    270TH 220 220 220 280 280 250

    340TH 270 270 270 340 340 310

    400TH 330 330 330 415 415 380

    500TH 390 390 345 500 480 390

    600TH 455 455 455 580 580 520

    750TH 570 570 570 730 730 700

    900TH 715 715 660 900 900 750

    1200TH 880 880 880 1150 1120 1020

    1500TH 1060 1060 970 1350 1300 1100

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL INFORMATION

    1.4.4 - Derating according to the temperature and switching frequency

    Ambient temperature 40C ( 35C with IP54 option) - altitude 1000 m.

    Rating

    Ico (A)

    Heavy duty Normal duty

    2 kHz 3 kHz 4 kHz 5 kHz 6 kHz 2 kHz 3 kHz 4 kHz 5 kHz 6 kHz

    400 V mains supply

    460/480 V mains supply

    525/690 V mains supply

    For intermediate switching frequencies (3.5 - 4.5 - 5.5 kHz), the available current value will be the average of the upper frequency

    and lower frequency currents.With IP54 protection, for an ambient temperature of 40C, the available current value is the average of currents at 35C and 45C.

  • 8/12/2019 4972b_en_MD2S

    11/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    11

    100T 142 142 132 120 110 175 168 150 136 124

    120T 172 170 152 138 126 215 192 172 156 142

    150T 222 204 182 162 146 255 232 206 184 166

    180T 260 260 260 255 230 315 315 305 290 260

    220T 310 310 310 285 260 400 390 360 325 295

    270T 380 380 360 320 290 470 450 410 365 330

    340T 470 470 420 375 340 570 540 475 425 385

    400T 545 520 485 430 385 630 590 550 485 435

    470T 670 650 575 515 465 780 740 655 585 525

    600T 815 795 715 645 590 930 900 810 730 670

    750T 1000 985 865 795 725 1150 1120 980 900 820

    900T 1200 1155 1015 925 855 1360 1310 1150 1050 970

    1100T 1430 1365 1235 1100 1015 1620 1550 1400 1250 1150

    1400T 1735 1685 1500 1365 1235 1970 1910 1700 1550 1400

    100T 142 142 126 112 100 175 160 142 126 114

    120T 172 162 142 128 114 210 184 162 146 130

    150T 222 194 170 152 136 254 220 192 172 154

    180T 260 260 260 240 215 315 305 295 270 245

    220T 310 310 300 270 240 400 385 340 305 270

    270T 380 380 340 300 270 470 435 385 340 305

    340T 470 450 385 340 305 570 510 435 385 345

    400T 545 485 440 385 340 630 550 500 435 385

    470T 670 605 525 465 410 780 685 595 525 465

    600T 815 750 660 590 530 930 850 750 670 600

    750T 1000 935 795 715 645 1150 1060 900 810 730

    900T 1200 1100 925 835 765 1360 1250 1050 950 870

    1100T 1430 1320 1135 995 910 1620 1500 1290 1130 1030

    1400T 1735 1605 1375 1235 1100 1970 1820 1560 1400 1250

    270TH 220 210 195 280 240 220

    340TH 270 270 240 340 310 270

    400TH 330 330 300 415 400 340

    500TH 390 365 305 500 415 345

    600TH 455 455 395 570 525 450

    750TH 570 570 540 740 730 610

    900TH 715 690 545 890 780 620

    1200TH 880 880 865 1120 1120 980

    1500TH 1060 1060 900 1320 1220 1020

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL INFORMATION

    Ambient temperature 50C ( 45C with IP54 option) - altitude 1000 m.

    Rating

    Ico (A)

    Heavy duty Normal duty

    2 kHz 3 kHz 4 kHz 5 kHz 6 kHz 2 kHz 3 kHz 4 kHz 5 kHz 6 kHz

    400 V mains supply

    460/480 V mains supply

    525/690 V mains supply

    For intermediate switching frequencies (3.5 - 4.5 - 5.5 kHz), the available current value will be the average of the upper frequency

    and lower frequency currents.

    With IP54 protection, for an ambient temperature of 40C, the available current value is the average of currents at 35C and 45C.

  • 8/12/2019 4972b_en_MD2S

    12/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    12

    L

    60mini

    L

    60mini

    L

    60mini

    L

    60mini

    enINSTALLATION AND MAINTENANCE

    Variable speed driveMECHANICAL INSTALLATION

    2 - MECHANICAL INSTALLATION It is the responsibility of the owner or user of the

    POWERDRIVE MD2S to ensure that the installation,

    operation and maintenance of the drive and its optionscomply with legislation relating to the safety of personnel

    and equipment and with the current regulations of thecountry of use.

    POWERDRIVE MD2S drives must be installed in

    an environment free from conducting dust, corrosive

    fumes, gases and uids, dripping water and any source

    of condensation (class 2 according to IEC 664.1). The

    drive must not be installed in hazardous areas unless it is

    in an appropriate enclosure. In this case, the installation

    must be approved.

    In atmospheres where condensation may form, install a

    heating system.

    Prevent access by unauthorised personnel.

    2.1 - Checks upon receipt

    Make sure that the cabinet has been transported

    vertically, as otherwise it could be damaged.

    Before installing the POWERDRIVE MD2S,check that:

    - The drive has not been damaged during transport

    - The information on the nameplate is compatible with thepower supply

    2.2 - Handling The centre of gravity may be high up and / or off-

    centre, so beware of the risk of the cabinet tipping

    over. Check that the handling equipment is suitable for the

    weight to be handled.

    The lifting accessories provided are limited solely to

    handling the cabinet. If subsequent handling operations

    are carried out, always check that these lifting accessories

    are in good condition.

    The cabinet must be handled without the IP21 or IP54 roof in

    place.

    IP21 POWERDRIVE MD2S versions are supplied with theroof assembled. Before handling the cabinet, follow the

    procedure described in section . For handling, follow theinstructions below, and then re-t the roof.

    IP54 POWERDRIVE MD2S versions are supplied with the

    lifting rings or rails assembled. When handling the cabinet,

    follow the instructions below, depending on the cubicle width,

    as indicated below. After handling, assemble the roof as

    described in section .

    Above 2400 mm wide (W), a baseplate 100 mm high is

    installed as standard to ensure the rigidity of all the cabinets.

    L= 4x 400 mmor 4x 600 mm

    L= 3x 400 mmor 3x 600 mm

    L = 2x 400 mmor 2x 600 mmor 2x 600 + 400 mm

    L = 400 mmor 600 mmor 600 + 400 mm

  • 8/12/2019 4972b_en_MD2S

    13/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    13

    enINSTALLATION AND MAINTENANCE

    Variable speed driveMECHANICAL INSTALLATION

    2.5 - Assembly and dismantling of the

    IP54 roof

    Assembly:

    1 - Dismantle the 4 lifting rings or the 2 lifting rails.2 - Open up the roof assembly as shown in the diagrams below.

    The side panels with no vent should be mounted facing eachother; the rear of the drive will have no vent.

    3 - Insert the supplied M12 screws through the roof assembly

    and tighten.

    4 - Adjust the roof assembly to optimise sealing.

    5 - Finally tighten the xing screws (tightening torque: 20 N.m).

    Removal, if necessary:

    Follow the reverse procedure.

    2.3 - Installation recommendations

    Ensure that hot air is not being recycled via the air inlets by

    leaving sufcient free space above the POWERDRIVE MD2S

    or providing a means of evacuating the hot air exhausted bythe product. If necessary, add a suction hood. Never obstruct

    the drive ventilation grilles; the air intake lters must be

    cleaned and changed regularly.

    After connecting the power, reposition the cable

    bush plates at the back of the cabinet and ll any

    gaps with expanding foam.

    2.4 - Removing and re-tting the IP21 roof

    Dismantling

    1 - Remove the M12 screws.

    2 - Remove the roof(s).3 - Screw in the 4 lifting rings or the 2 lifting rails with the M12

    screws at the places indicated (tightening torque = 20 N.m).

    Re-tting

    Follow the reverse procedure.

  • 8/12/2019 4972b_en_MD2S

    14/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    14

    enINSTALLATION AND MAINTENANCE

    Variable speed driveMECHANICAL INSTALLATION

    2.6 - Dimensions

    The cabinet-mounted POWERDRIVE MD2Ssolution is obtained by assembling cabinet modules of 400 or 600 mm wide and

    600 mm deep.

    The table below gives the productwidth (Win mm) depending on the options incorporated:

    W/o options With options

    MD2S ratingsWidth

    W (mm)Switch

    High-speed

    fusesRFI lter Mains choke

    Braking

    transistorWidth

    W (mm)

    100T to 150T 406 included 406

    180T to 270T 406 included 606

    340T & 400T 606

    606

    606

    1006

    470T 606

    606

    606

    1006

    600T to 900T 1206

    1206

    1206

    1606

    1806

    1100T & 1400T 1806 included 2406 (1)

    270TH to 500TH 606 included 1006

    600TH to 900TH 1206 included 1606

    1200TH to 1500TH 1806 included 2406 (1)

    The following options can be incorporated into thePOWERDRIVE MD2Swithout affecting its dimensions:

    MD-AU1 emergency stop

    Communication modules Additional I/O modules

    Speed feedback modules

    H

    W D = 600 mm

    The table below gives the productheight (H) depending onthe options incorporated:

    Option Hauteur (mm)

    POWERDRIVE MD2S standard 2100

    IP21 protection + 0

    IP54 protection + 100

    100mm baseplate + 100

    200mm baseplate + 200

    baseplate for width 2400mm (1) + 100

    (1) Above 2400 mm long (L), a 100 mm high baseplate mustbe installed to ensure the rigidity of the cabinet assembly.

    Cables cannot run through this baseplate, but a 100mm ou

    200mm baseplate can be added.

    For more details depending on the options chosen, use the

    Leroy-Somer congurator:

    http://congurateurls.leroy-somer.com/

    http://configurateurls.leroy-somer.com/login_en.phphttp://configurateurls.leroy-somer.com/login_en.php
  • 8/12/2019 4972b_en_MD2S

    15/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    15

    enINSTALLATION AND MAINTENANCE

    Variable speed driveMECHANICAL INSTALLATION

    2.7 - Weight

    The values indicated in the table below are maximum net

    weights.

    POWERDRIVE MD2rating

    Weightwithout option (kg)

    Maximum weight(kg)

    100T to 150T 225 260

    180T to 270T 260 360

    340T to 470T 355 560

    600T and 750T 710 990

    900T 740 1040

    1100T to 1400T 1350 1720

    270TH and 340TH 355 560

    400TH and 500 TH 400 620

    600TH 720 780

    750TH and 900TH 810 10501200TH and 1500TH 1250 1520

    2.8 - Drive losses

    Losses according to the switching frequency with currents

    at 40 C.

    MD2Srating

    Losses (kW)

    at 2 kHz at 3 kHz at 4 kHz at 5 kHz at 6 kHz

    100T 2.4 2.6 2.4 2.4 2.3

    120T 2.8 2.8 2.6 2.6 2.4

    150T 3.2 3.5 3.3 3.1 3.1

    180T 3.8 4.2 4.5 4.7 4.5

    220T 4.9 5.4 5.6 5.5 5.2

    270T 5.7 6.3 6.5 6 5.7

    340T 7.4 7.9 8.5 8.3 8.1

    400T 8.6 9.1 9.8 9.6 9.3

    470T 10.8 11.2 11.8 11.5 11.2

    600T 14.9 15.9 16.4 16 15.6

    750T 16.1 16.9 17.8 17.4 16.9

    900T 21.4 21.2 22.3 21.7 21.2

    1100T 24.7 26 27.2 26.5 25.8

    1400T32 32.5 34.5 33.6 32.8

    270TH 5.6 6.0 6.2

    340TH 9.2 9.7 9.7

    400TH 8.7 9.4 9.4

    500TH 10.5 11.3 11.2

    600TH 15.9 16.8 16.6

    750TH 16.1 17.3 19.7

    900TH 20.9 22.3 22.5

    1200TH 26.4 28.3 32.1

    1500TH 31.8 34.2 34.2

    Note: The values given above correspond to operation in

    normal duty and the choke losses are included.

    2.9 - Drive ventilation ow rates and

    noise levels

    POWERDRIVE MD2 rating

    Forced

    ventilationow rates

    (m3/hr)

    Noise level(dBA)

    100T to 150T 600 75

    180T to 270T 1200 77

    340T to 470T 1700 77

    600T to 900T 3400 80

    1100T to 1400T 5100 82

    270TH to 500TH 1700 77

    600TH to 900TH 3400 80

    1200TH and 1500TH 5100 82

    Air can exit out from all sides of the roof. The cabinet can

    be installed with one side only against a wall (with IP21 or

    IP54 roof). Under no circumstance the difference between

    the internal temperature of the cabinet and the ambient

    temperature outside the cabinet must not exceed 5C.

    In atmospheres where condensation may form, install

    a heating system (to be switched off when the drive is

    operating). It is advisable to control the heating system

    automatically.

    Air outlets

    Air inlets

  • 8/12/2019 4972b_en_MD2S

    16/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    16

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3 - CONNECTIONS

    All connections work must be performed by

    qualied electricians in accordance with the laws in

    force in the country in which the drive is installed. This

    includes earthing to ensure that no directly accessiblepart of the drive can be at the mains voltage or any other

    voltage which may be dangerous.

    The drive must be supplied through an approved

    circuit-breaking device so that it can be powered down

    safely.

    The optional isolator supplied with the drive doesnot isolate the drive input busbars. It must without

    fail be associated with a circuit-breaking device in the

    switchboard.

    The drive power supply must be protected against

    overloads and short-circuits.

    Check that the voltage and current of the drive, the

    motor and the mains supply are compatible. The voltages on the connections of the mains supply,

    the motor, the braking resistor or the lter may cause

    fatal electric shocks. The protective plates supplied with

    the drive must always be installed correctly to protect theuser against electric shocks.

    Only one permanent magnet motor can be connected

    to the drive output. It is recommended to install a circuit-

    breaking device between the permanent magnet motor

    and the drive output to eliminate the risk of hazardous

    voltage feedback when performing maintenance work. See also the recommendations in section 7.

    3.1 - Power connections

    3.1.1 - Location of the control terminal block, fuse boards and external power supply

    Control terminal block

    Removable screw terminal block: tightening torque = 0.3 N.m/0.22 lb ft cross-section = 1.5 mm2 screwdriver = 2 mm flat

    Analog I/O Digital I/O RelaysPx1 Px2

    Fuses and external power supply board

    Depending on the rating, POWERDRIVE MD2S may includeone or more identical fuses board:

    - 100T to 270T : 1 board (1)

    - 340T to 470T & 270TH to 500TH : 1 board (2)

    - 600T to 900T & 600TH to 900TH : 2 boards (2)

    - 1100T and 1400T & 1200TH and 1500TH : 3 boards (2)

    (1) Positioned right side each cabinet(2) Positioned left side each cabinet

    Position the F8 fuse according to the mains supply

    voltage

    F1

    F2 F3 F4 F5 F6F9F7

    PX4

    460V(T)

    600V(TH

    )

    480V(T)

    690V(TH

    )

    400V(T)

    500V(TH

    )

    P1

    F8

    400V(T)/500V(TH)

    460V(T)/600V(TH)

    480V(T)/690V(TH)

    P2

    P3 P4

    P6P7 P8

    Interface

    board

    output

    Power

    Input S1

    Power

    Input S2External

    power input

    Fan

    Control

    F an 1 F an 2 Fa n3 F an 4 Fa n5

  • 8/12/2019 4972b_en_MD2S

    17/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    17

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.1.5 - Electronics and forced ventilationpower supply

    The control electronics and forced ventilation units are

    supplied through a single-phase transformer which primary

    is connected to terminals L1-L2 of the power supply. If

    necessary, this transformer can be supplied with an externalpower source (PX4 terminal block on fuse board).

    The neutral of the electronics power supply must

    not be connected to earth

    Electrical characteristics:

    Ratings Voltage

    PrimaryT

    400 V10%/50 Hz or

    460-480 V 10%/60 Hz

    TH 500-690 V 5%/50 Hz

    Voltage Maximum power

    Secondary 1(Electronics

    power supply)

    230 Visolated

    100 VA

    Secondary 2(Forced

    ventilation and

    auxiliaries power

    supply)

    230 V

    connectedto earth

    100T to 150T:

    P = 300 VA

    180T to 270T:

    P = 500 VA340T to 470T:

    P = 1200 VA

    600T to 900T:

    P = 2x 1200 VA1100T to 1400T:

    P = 3x 1200 VA

    270TH to 500TH:P = 1200 VA

    600TH to 900TH:

    P = 2x 1200 VA

    1200TH to 1500TH: P = 3x 1200 VA

    Disconnection of forced ventilation units

    The fuse board described in section 3.1.1. enables the user to

    switch off the power supply to the drive forced ventilation units

    momentarily, if preheating resistors are used in the cabinet for

    example.To disconnect the fans, remove the jumper connecting

    terminals P7 and P8 and connect a normally closed contact

    (230 V/7 A on resistive load). A closed contact allows the

    ventilation units to operate, an open delayed contact cuts off

    their power supply (delay 10 minutes for ambiant temperatureup to 40C, otherwise 30 minutes).

    Connection exemple:

    Px2

    2 P7 P8

    KA1

    DO1+24

    A1

    A2

    KA1

    1

    POWERDRIVE MD2S

    Example of associated settings:

    # 16.02 = 10.02 (Timer 1 source = Drive active) # 16.03 = 1 (OFF timer)

    # 16.04 = 1 (minute)

    # 16.05 = 20 (if T 40 C) or 30 (if T > 40 C)

    # 8.26 = 16.01 (DO1 assigned to Timer 1)

    # 8.16 = 1 (Invert DO1)

    Refer to the commissioning manual (ref. 4617) for more

    details on POWERDRIVE MD2Ssettings.

    3.1.2 - Characteristics of connection terminals

    Refs. Functions/connections

    Type of connection and tightening torque

    100T to 150T 180T to 270T340T to 1400T

    270TH to 1500THL1, L2, L3,

    or R, S, TMains power supply

    M10 screw bolt - 20 Nm

    U, V, W Motor outputs

    PE Earth M10 bolt - 20 Nm M8 bolts - 12 Nm

    BR1, BR2, PE braking resistor (1) M8 screw bolt - 12 Nm

    P4, P5 EMC commoning link Torx screws 20 - 4 Nm

    - Control block (2) Spring terminal block

    Do not exceed the indicated maximum tightening torque.

    (1) If braking transistor is tted.

    (2) The neutral of the electronics power supply must not be connected to earth.

    Fuse board on controlterminal board

  • 8/12/2019 4972b_en_MD2S

    18/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    18

    U V W

    L1

    / R

    L2

    / S

    L3

    / T

    MD2S 100T - MD2S 150T

    PE PEPE

    350

    535.5

    241

    535.5

    U V WMD2S 180T - MD2S 270T

    PE PE

    320

    PE

    L1 L2 L3

    MD2S 180T - MD2S 270T

    PE PE

    PE

    R S T U V W

    BR1/BR2MD2S 340T - MD2S 470T

    MD2S 270TH - MD2S 500TH

    93

    50

    50 5075 75 105 75 75

    U V WL1 L2 L3

    PE100

    PE220

    MD2S 340T - MD2S 470T

    MD2S 270TH - MD2S 500TH

    2

    20

    BR1/BR2

    U V WR S T93

    50

    5075 75

    PE100PE

    75 75112 112

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.1.3 - Location of power terminal blocks

    W/o options

    W/o options

    With options

    With options

  • 8/12/2019 4972b_en_MD2S

    19/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    19

    MD2S 600T - MD2S 900T

    MD2S 600TH - MD2S 900TH

    L1 L2 L3 U V WBR1

    BR2

    220 50 75 75 75 75 75 50 45 50 75 75 75 75 75 95

    PE

    93

    50

    100

    PE

    MD2S 600T - MD2S 900T

    MD2S 600TH - MD2S 900TH

    R T

    U V WBR1

    BR2

    220

    55

    70 70105 105 45 50 75 75 75 75 75 95

    PE

    93

    50

    100

    PE

    S

    MD2S 1100T - MD2S 1400T

    MD2S 1200TH - MD2S 1500TH

    50 75 75 105 75 75 5050 75 75 55 75 75

    L1 L2 L3

    50 5050 75 75 120 75 75

    U V W

    PE

    50

    BR1

    BR2

    93

    50

    100

    PE220

    MD2S 1100T - MD2S 1400T

    MD2S 1200TH - MD2S 1500TH

    55

    55 75 75 50 5050 75 75 120 75 75

    U V W

    PE65 190 190 65

    BR1

    BR2

    93

    50

    100 PE2

    20

    150

    R S T

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    W/o options

    With options

    W/o options

    With options

  • 8/12/2019 4972b_en_MD2S

    20/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    20

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.1.4 - Cables and fuses

    It is the responsibility of the user to connect and provide protection for the POWERDRIVE MD2S in accordance

    with the current legislation and regulations in the country of use. This is particularly important with regard to the

    size of the cables, the type and rating of fuses, the earth or ground connection, powering down, acknowledging trips,

    isolation and protection against overcurrents.

    The installation must have a short circuit current (Isc) > 20 ILat the point of drive connection.

    This table is given for information only, and must under no circumstances be used in place of the current standards.

    IL: Maximum line current Ico: Continuous output current

    POWERDRIVE

    rating

    Mains power supplyMotor

    400 V - 50 Hz 460/480 V - 60 Hz

    IL(A)

    Fuses (1)Cable

    cross-section(mm) (2)

    IL

    (A)

    Fuses (1)Cable

    cross-section(mm) (2)

    Ico

    (A)

    Cable

    cross-section(mm) (3)

    Gg

    typeaR type

    Gg

    type

    Class

    J

    ( UL)

    aR type

    100THeavy 140 160 250 3x70 + 35 125 160 200 250 3x70 + 30 145 3x70 + 35

    Normal 170 200 315 3x95 + 50 150 200 225 250 3x70 + 35 175 3x95 + 50

    120THeavy 170 200 315 3x95 + 50 150 200 225 250 3x70 + 35 175 3x95 + 50

    Normal 198 250 350 3x120 + 70 175 200 250 315 3x95 + 50 215 3x120 + 70

    150THeavy 205 250 400 3x120 + 70 175 200 250 315 3x95 + 50 220 3x120 + 70

    Normal 245 315 450 3x150 + 70 215 250 300 350 3x120 + 70 260 3x150 + 70

    180THeavy 245 315 500 3x150 + 70 215 250 300 400 3x120 + 70 260 3x150 + 70

    Normal 295 315 500 3x240 +120 255 315 400 450 3x185 + 90 305 3x240 +120

    220THeavy 290 315 550 3x240 +120 255 315 400 450 3x185 + 90 305 3x240 +120

    Normal 370 400 630 2x(3x95 + 50) 320 400 500 550 3x240 + 120 380 2x(3x95+50)

    270THeavy 375 400 700 2x(3x95 + 50) 325 400 500 550 3x240 + 120 380 2x(3x95+50)

    Normal 460 500 800 2x(3x150 + 95) 405 500 600 700 2x(3x120 + 70) 470 2x(3x150+95)

    340THeavy 465 500 800 2x(3x150 + 95) 410 500 600 700 2x(3x120 + 70) 470 2x(3x150+95)

    Normal 580 630 1000 2x(3x185 + 95) 495 630 -- 800 2x(3x150 + 95) 580 2x(3x185+95)

    400THeavy 585 630 1000 2x(3x185 + 95) 500 630 -- 900 2x(3x150 + 95) 570 2x(3x185+95)

    Normal 650 800 1100 2x(3x240 + 120) 560 630 -- 900 2x(3x185 + 95) 630 2x(3x240+120)

    470THeavy 655 800 1250 2x(3x240 + 120) 560 630 -- 1000 2x(3x185 + 95) 680 2x(3x240 + 120)

    Normal 815 1000 1400 3x(3x185 + 95) 700 800 -- 1250 2x(3x240 + 120) 800 3x(3x185 + 95)

    600THeavy 825 1000 2x630 3x(3x185 + 95) 710 800 -- 2 x 550 2x(3x240 + 120) 820 3x(3x185 + 95)

    Normal 998 1250 2x800 4x(3x150 + 95) 856 1000 -- 2 x 700 3x(3x185 + 95) 990 4x(3x150 + 95)

    750THeavy 1010 1250 2x800 4x(3x150 + 95) 865 1000 -- 2 x 700 4x(3x150 + 95) 990 4x(3x150 + 95)

    Normal 1225 1600 2x1000 3x(3x240 + 120) 1050 1250 -- 2 x 800 4x(3x150 + 95) 1220 3x(3x240 + 120)

    900THeavy 1250 1600 2x1000 3x(3x240 + 120) 1060 1250 -- 2 x 800 3x(3x240 + 120) 1220 3x(3x240 + 120)

    Normal 1360 1600 2x1100 4x(3x240 + 120) 1170 1600 -- 2 x 900 3x(3x240 + 120) 1430 4x(3x240 + 120)

    1100THeavy 1380 1800 3x800 4x(3x240 + 120) 1180 1600 -- 3 x 700 4x(3x240 + 120) 1430 4x(3x240 + 120)

    Normal 1635 2000 3x900 4x(3x240 + 120) 1400 1800 -- 3 x 800 4x(3x240 + 120) 1700 4x(3x240 + 120)

    1400THeavy 1680 2000 3 x 900 1520 1800 -- 3 x 800 1750

    Normal 2000 2500 3 x 1000 1810 2000 -- 3 x 900 2100

  • 8/12/2019 4972b_en_MD2S

    21/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    21

    U

    WV

    PE

    PE PE

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    POWERDRIVE

    rating

    Mains power supplyMotor

    525 V 690 V

    IL(A)

    Fuses Cable

    cross-section(mm)

    (1)

    IL(A)

    FusesCable cross-section

    (mm)(1)

    Ico(A)

    Cable cross-

    section (mm)(2)

    Ggtype

    aR type(IEC&UL)

    Ggtype

    aR type(IEC&UL)

    270THHeavy 205 250 400 3x120 + 70 215 250 400 3x120 + 70 220 3x120 + 70

    Normal 250 315 450 3x120 + 70 265 315 450 3x120 + 70 280 3x150 + 70

    340THHeavy 250 315 450 3x120 + 70 265 315 500 3x120 + 70 270 3x150 + 70

    Normal 305 400 550 3x150 + 70 320 400 550 3x150 + 70 340 3x240 +120

    400THHeavy 305 400 550 3x150 + 70 320 400 630 3x150 + 70 330 3x240 +120

    Normal 370 400 700 3x240 +120 390 400 700 3x240 +120 415 2x(3x120+70)

    500THHeavy 370 400 700 3x240 +120 390 400 700 3x240 +120 390 2x(3x120+70)

    Normal 445 500 800 3x240 +120 470 500 800 3x240 +120 480 2x(3x150+95)

    600TH

    Heavy 445 500 2x400 3x240 +120 470 500 2x450 3x240 +120 455 2x(3x150+95)

    Normal 520 630 2x450 2x(3x150+95) 545 630 2x500 2x(3x150+95) 580 2x(3x185+95)

    750THHeavy 520 630 2x500 2x(3x150+95) 545 630 2x500 2x(3x150+95) 570 2x(3x185+95)

    Normal 650 800 2x630 2x(3x240 + 120) 685 800 2x630 2x(3x240 + 120) 730 2x(3x240+120)

    900THHeavy 650 800 2x630 2x(3x240 + 120) 685 800 2x630 2x(3x240 + 120) 715 2x(3x240 + 120)

    Normal 805 1000 2x700 3x(3x185 + 95) 845 1000 2x800 3x(3x185 + 95) 900 3x(3x185 + 95)

    1200THHeavy 805 1000 3x450 3x(3x185 + 95) 845 1000 3x500 3x(3x185 + 95) 880 3x(3x185 + 95)

    Normal 1000 1250 3x550 3x(3x185 + 95) 1050 1250 3x550 3x(3x185 + 95) 1120 3x(3x240 + 120)

    1500THHeavy 1000 1250 3x550 3x(3x185 + 95) 1050 1250 3x550 3x(3x185 + 95) 1060 3x(3x240 + 120)

    Normal 1205 1600 3x630 3x(3x240 + 120) 1265 1600 3x630 3x(3x240 + 120) 1300 4x(3x240 + 120)

    Note: The line current value ILis a typical value which depends on the source impedance. The higher the impedance, the lower the

    current.

    (1) gG fuse or equivalent solution (fuses connected in parallel, preferably C type circuit-breaker, etc). This protection must always

    be connected in series with aR semi-conductor fuses.

    (2) Semiconductor aR fuses do not ensure the protection of the drive power supply line and must always be associated with a

    protection device against overload, localized at the head of the line.

    (3) The recommended mains cable cross-sections have been determined for single-core cable with a maximum length of 20 m. For

    longer cables, take line voltage drops into consideration due to large cable length.

    (4) The motor cable cross-sections are given for information only for a current corresponding to the value of the

    Ico current at 3 kHz, a maximum length of 50 m, output frequency less than 100 Hz and an ambient temperature of40C. The recommended motor cables are shielded multicore type(see section 4.5.2). The values supplied

    are typical values.

    Example: Cable cross-section of 3 x (3 x 185 + 95) corresponds to 3 cables each consisting of 3 phase conductors

    (cross-section 185 mm) + earth conductors (cross-section 95 mm).

  • 8/12/2019 4972b_en_MD2S

    22/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    22

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.2 - Connection of the control

    The POWERDRIVE MD2S inputs have a positive

    logic conguration. Using a drive with a control system

    which has a different control logic may cause unwantedstarting of the motor.

    The POWERDRIVE MD2S control circuit is isolated from

    the power circuits by single insulation. Its electronic 0V

    is connected to the connection terminal on the outer

    protective conductor (earth terminal). The installer must

    ensure that the external control circuits are isolatedagainst any human contact.

    If the control circuits need to be connected to circuits

    conforming to SELV safety requirements, additional

    insulation must be inserted to maintain the SELV

    classication (see EN 61140).

    3.2.1 - Control terminal block location

    Px1 Px2 Px3P1 P2

    1 1 1

    RL2 status relay LED

    RL1 status relay LED

    Control terminal blocks

    Control terminal block

    Removable screw terminal block: tightening torque = 0.3 N.m/0.22 lb ft cross-section = 1.5 mm2 screwdriver = 2 mm flat

    Analog I/O Digital I/O RelaysPx1 Px2

    3.2.2 - Control terminal block characteristics

    3.2.2.1 - PX1 terminal block characteristics

    1 10V +10 V internal analog source

    Accuracy 2%

    Maximum output current 10 mA

    2 AI1+ Differential analog input 1 (+)

    3 AI1- Differential analog input 1 (-)

    Factory setting 0-10V speed reference

    Input type 10 V differential bipolar analogvoltage (for common mode,connect terminal 3 to terminal 6)

    Absolute maximum voltagerange

    36 V

    Voltage range in common mode 24 V/0 V

    Input impedance > 100 k

    Resolution 11 bits + sign

    Sampling period 2 ms

    Input lter bandwidth ~ 200 Hz

    4 AI2+ Differential analog input 2 (+)

    5 AI2- Differential analog input 2 (-)

    Factory setting 0-20 mA speed reference

    Input typeUnipolar current(0 to 20 mA, 4 to 20 mA,20 to 0 mA, 20 to 4 mA)

    Absolute maximum current 30 mA

    Voltage range in common mode 24 V/0 V

    Input impedance 100

    Resolution 12 bits

    Sampling period 2 ms

    Input lter bandwidth ~ 200 Hz

    6 0V Analog circuit common 0 V

    The 0 V on the electronics is connected to the metal ground of thedrive

    7 AI3 Analog input 3

    Factory setting No assignment

    Input type 10 V bipolar analog voltage incommon mode or unipolar current(0 to 20 mA, 4 to 20 mA)

    Resolution 11 bits + sign

    Sampling period 2 ms

    Input lter bandwidth ~ 200 Hz

    Voltage range in common mode 24 V/0 V

    Voltage mode

    Input impedance > 50 k

    Absolute maximum voltagerange

    30 V

    Current mode

    Input impedance 100

    Absolute maximum current 30 mA

  • 8/12/2019 4972b_en_MD2S

    23/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    23

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    8 AO1 Analog output

    Factory setting 4-20 mA motor current signal

    Output type

    Bipolar analog voltage in common

    mode or unipolar current in

    common mode

    Resolution 13 bits

    Sampling period 2 ms

    Voltage mode

    Voltage range 10 V

    Load resistance 1 k minimum

    Current mode

    Current range 0 to 20 mA, 4 to 20 mA

    Load resistance 500 maximum

    9 DI1PTC Digital input 1or PTC thermal sensor

    Factory setting No assignment

    Sampling period 2 ms

    Thermal sensor input

    Voltage range 10 V

    Trip threshold > 3.3 k

    Reset threshold < 1.8 k

    Digital input

    Type Digital input in positive logic

    Voltage range 0 to + 24 V

    Absolute maximum voltage

    range0 V to + 35 V

    Thresholds0 : < 5 V

    1 : > 13 V

    10 0V Analog circuit common 0 V

    The 0 V on the electronics is connected to the metal ground of the

    drive

    3.2.2.2 - PX2 terminal block characteristics

    1+24V ref +24 VDC user output

    9

    +24 VDC user outputOutput current 100 mA

    Accuracy 5%

    ProtectionCurrent limiting and setting to trip

    mode

    2 DO1 Digital output

    Factory setting Zero speed

    Characteristic Open collector

    Absolute maximum voltage + 30 V/0 V

    Overload current 150 mA

    3 STO-1Drive enable input 1

    (Safe Torque Off function)

    6 STO-2Drive enable input 2

    (Safe Torque Off function)

    Input type Positive logic only

    Absolute maximum voltage + 30 V

    Thresholds0 : < 5 V

    1 : > 13 V

    Response time < 20 ms

    4 DI2 Digital input 2

    5 DI3 Digital input 3

    7 DI4 Digital input 4

    8 DI5 Digital input 5

    DI2 factory settingSelection of speed reference

    DI3 factory setting

    DI4 factory setting Run FWD/Stop input

    DI5 factory setting Run reverse/Stop input

    Type Digital inputs in positive logic

    Voltage range 0 to + 24 V

    Absolute maximum voltage

    range0 to + 35 V

    Thresholds0 : < 5 V

    1 : > 13 V

    3.2.2.3 - PX3 terminal block characteristics

    1 COM-RL1N/O (normally open) relay output

    2 RL1

    3 COM-RL2N/O (normally open) relay output

    4 RL2

    Factory setting RL1 Drive status relay

    Factory setting RL2 Maximum speed alarm

    Voltage 250 VAC

    Maximum contact current

    2 A - 250 VAC, resistive load

    1 A - 250 VAC, inductive load

    2 A - 30 VDC, resistive load

    Provide a fuse or other overcurrent protection in

    the relay circuit.

    Note: When the RL1 or RL2 relay is activated, the

    corresponding status LED on the control board lights up (see

    diagram in section 3.2.1).

  • 8/12/2019 4972b_en_MD2S

    24/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    24

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.2.3 - Factory conguration of control terminalblocks

    Note: For details of the parameters, refer to the

    commissioning manual, ref. 4617.

    +10V ref

    AI1+

    AI1-

    AI2+

    AI2-

    0V

    COM-RL1

    RL1

    COM-RL2

    RL2

    AO1

    AI3

    +24V ref

    DO1

    STO-1

    DI2

    DI3

    STO-2

    DI5

    DI4

    +24V ref

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    8

    7

    0V

    DI1/CTP

    10

    9

    1

    2

    3

    4

    5

    6

    8

    7

    9

    PX1

    PX2

    PX3

    status relayDrive (N/O)

    Alarm relaymaximum speed (N/O)

    0-10 Vspeed reference

    4-20 mA speed reference

    4-20 mA current image

    Motor PTC*

    Zero speed

    Safe Torque Off/Drive enable input 1Reference selection

    Reference selection

    Safe Torque Off/

    Drive enable input 2Run FWD/Stop

    Run REV/Stop

    Note:This conguration has been obtained from a drive with

    factory settings (default parameter settings).The STO-1 and STO-2 inputs must be closed before giving a

    run command.

    (*) If the motor thermal sensor needs to be connected to DI1/

    PTC, set Mtr.06 (05.70)= Drive terminal (1).

    Modication of the Run/Stop control logic

    - For "3-wire" control (jog Run/Stop):

    DI4

    DI5

    +24V ref

    7

    8

    9

    Run FWD

    Stop

    List of parameters to adjust: Ctr.06 (06.04)= Run Latched (1)

    I/O.10 (08.25) =06.39 Stop (DI5 terminal)

    - For Run/Stop control with change of direction:

    DI4

    DI5

    +24V ref

    7

    9

    8

    Run/Stop

    Change of direction

    List of parameters to adjust:

    Ctr.06 (06.04) = Run Fwd/Rev (2) I/O.09 (08.24) = 06.34 Run/Stop (DI4 terminal)

    I/O.10 (08.25) = 06.33 Fwd/Reverse (DI5 terminal)

    Selection of the reference via digital inputs:

    DI2 DI3 Selection

    0 0Voltage speed reference (0-10 V) on analog input

    AI1+, AI1-

    0 1

    Current speed reference (4-20 mA) on analog

    input AI2+, AI2-

    1 0 Preset reference 2

    Spd.05 (01.22)to be set1 1

  • 8/12/2019 4972b_en_MD2S

    25/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    25

    enINSTALLATION AND MAINTENANCE

    Variable speed driveCONNECTIONS

    3.3 - STO-1/STO-2 inputs: Safe Torque Off

    function

    The STO-1 and STO-2 inputs are safety inputs that can be

    used to disable the drive output so no torque at the motorshaft is provided.

    They are independent of one another. They are created bysimple hardware not connected to the microcontroller. They

    acts on two different stages of the IGBT output bridge control.

    To enable the drive, the STO-1 and STO-2 inputs must be

    connected to the +24V source.

    The opening of, at minimum, one of the inputs locks the

    output bridge.

    These 2 inputs can be used in conjunction to create a "Safe

    Torque Off" function with a logic combining 2 separate

    channels.

    In this conguration, the "Safe Torque Off" function is

    guaranteed with a very high level of integrity in conformitywith standards:

    - EN 61800-5-2

    - EN/ISO 13849-1: 2006; PLe

    - IEC/EN 62061: 2005; SIL3

    (CETIM approval no. CET0047520)

    In a safety system, this built-in function enables the drive to

    act as a substitute for a contactor so the motor can run in

    freewheel mode.

    The STO-1 and STO-2 inputs are compatible with self-testedlogic outputs in controllers such as PLCs, for which the test

    pulse lasts for 1 ms maximum.

    If the data sent by the 2 inputs is not identical, this generates

    a drive trip. The RL1 relay opens and the drive indicates

    a "t.r./63" trip on the drive 2-digit display or "STO input

    inconsistency" trip on the parameter-setting interface.

    For correct use, the power and control connection diagrams

    described in the following paragraphs must be adhered to.

    The STO-1/STO-2 inputs are safety components

    which must be incorporated in the complete

    system dedicated to machine safety. As for any

    installation, the complete machine must be subject to a

    risk analysis. The integrator must determine the safety

    category which the installation must comply with. The STO-1 and STO-2 inputs, when open, lock the

    drive, so the dynamic braking function is no longer

    available. If a braking function is required before the

    drive secure disable lock is applied, a time-delayed

    safety relay must be installed to activate the locking

    automatically after the end of braking.If braking needs to be a machine safety function, it must

    be provided by an electromechanical solution since the

    dynamic braking by the drive function is not considered

    as a secure disable function.

    The STO-1/STO-2 inputs do not provide theelectrical isolation function. Prior to any work carry out

    on tre drive/installation, the power supply must therefore

    be switched of an approved isolating device (isolator,switch, etc).

    3.3.1 - Single channel locking (SIL1 - PLb)

    3-phase AC power supply, in accordance with safety standardIEC/EN 62061: 2005 and EN/ISO 13849-1: 2006 - Single

    channel locking (SIL1 - PLb).

    U V W

    Px2

    +24V Ref

    DO1

    STO-1

    DI2

    DI3

    STO-2

    DI4

    DI5

    +24V Ref

    M

    3

    PE

    PEL1 L2 L3

    POWERDRIVE MD2S

    Safe Torque Off/Driveenable input

    Run FWD/Stop

    Run REV/Stop

    3.3.2 - Double channel locking (SIL3 - PLe).

    3-phase AC power supply, in accordance with safety standard

    IEC/EN 62061: 2005 and EN/ISO 13849-1: 2006 - Doublechannel locking (SIL3 - PLe)

    U V W

    Px2

    +24V Ref

    DO1

    STO-1

    DI2

    DI3

    STO-2

    DI4

    DI5

    +24V Ref

    M

    3

    PE

    PEL1 L2 L3

    POWERDRIVE MD2S

    Output stage of asafety relay

    Run FWD/Stop

    Run REV/Stop

  • 8/12/2019 4972b_en_MD2S

    26/48

  • 8/12/2019 4972b_en_MD2S

    27/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    27

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE

    4.4.2 - Mains transient overvoltages

    There are numerous sources of overvoltages on an electricalinstallation:

    Connection/disconnection of banks of power factor

    correction capacitors High-power thyristor-controlled equipment (oven, DC drive,

    etc)

    Results of lighning

    4.4.2.1 - Connection/disconnectionofabankofpowerfactor

    correction capacitors

    Connecting power factor correction capacitors in parallel on

    the drive power supply line when the drive is running cangenerate transient overvoltages that are likely to trip the drive

    safety devices, or even damage it in extreme cases.

    If banks of power factor correction capacitors are used on the

    power supply line, make sure that:

    The threshold between steps is low enough to avoidcausing overvoltage on the line The capacitors are not permanently connected

    4.4.2.2 - Presence of commutation notches on the line

    When high-power thyristor-controlled equipment is connected

    on the same line as the drive, it is essential to ensure that

    the harmonics generated by the commutation notches do

    not excessively distort the mains voltage and do not create

    voltage peaks with amplitude higher than 2 x mains Vrms. If

    this is the case, it is essential to take corrective measures byinserting a choke in the line supplying the thyristor-controlled

    equipment or by moving the drive power supply line to

    another source.

    4.4.3 - Unbalanced power supply

    Similar to what is observed on an electric motor, the linecurrent imbalance of a drive operating on an unbalanced

    mains supply may be several times the value of the

    voltage imbalance measured on the power supply. A highly

    unbalanced mains supply (>2%) associated with a low

    mains impedance may result in a high level of stress on the

    components at the input stage of a drive.Additional mains chokes can be installed upstream of a

    POWERDRIVE MD2S supplied by an unbalanced mains

    in order to reduce the current imbalance factor (see

    characteristics in section 5.4).

    Neutral IT point connection

    For IT power supplies, open the commoning link connecting

    the EMC capacitors to earth as indicated below.

    POWERDRIVE MD2S 100T to 270T

    Other POWERDRIVE MD2S ratings

    4.4.4 - Ground connections

    The equipotential earth bonding of some industrial sites

    is not always observed. This lack of equipotentiality leads

    to leakage currents which ow via the earth cables (green/

    yellow), the machine chassis, the pipework, etc, and alsovia the electrical equipment. In some extreme cases, these

    currents can trip the drive.

    It is essential that the earth network is designed and

    implemented by the installation supervisor so that its

    impedance is as low as possible, so as to distribute the fault

    currents and high-frequency currents without them passingthrough electronic equipment.

    Metal grounds must be mechanically connected to each other

    with the largest possible electrical contact area. Under no

    circumstances can the earth connections designed to protectpeople, by linking metal grounds to earth via a cable, serve as

    a substitute for the ground connections (see IEC 61000-5-2).

    The immunity and radio-frequency emission level are directly

    linked to the quality of the ground connections.

  • 8/12/2019 4972b_en_MD2S

    28/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    28

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE

    4.5 - Basic precautions for installation

    These should be taken into account when wiring the cabinet

    and the external components. In each paragraph, they are

    listed in decreasing order of effect on correct operation of theinstallation.

    4.5.1 - Wiring inside the cabinet

    - Do not run the control cables and the power cables in the

    same cable ducts.

    - For control cables, use shielded twisted cables.

    4.5.2 - Wiring outside the cabinet

    Connect the motor earth terminal directly to that of

    the drive.

    It is recommended that a shielded symmetrical cable is

    used: three phase conductors and three PE conductors

    arranged symmetrically.

    U

    WV

    PE

    PE PE

    Shielding

    A separate PE protective conductor is mandatory if the

    conductivity of the cable shielding is less than 50% of the

    conductivity of the phase conductors.

    - The shield must be connected at both ends: drive end and

    motor end (connected round the whole circumference).- In the second industrial environment, the shielded motor

    power supply cable can be replaced by a 3-core + earth

    cable placed in a fully enclosed metal conduit (metal cable

    duct for example). This metal conduit must be mechanically

    connected to the electrical cabinet and the structure

    supporting the motor.

    If the conduit consists of several pieces, these should be

    interconnected by braids to ensure earth continuity. The

    cables must be positioned and held in a cloverleaf formationin the conduit.

    U

    WVPE

    U

    WV

    PE

    EMCbraid

    Clamp

    - There is no need to shield the power supply cables between

    the mains supply and the drive.

    - Isolate the power cables from the control cables. The powercables must intersect the other cables at an angle of 90.

    - Isolate sensitive elements (probes, sensors, etc) from metal

    structures which may be shared by the motor support.

  • 8/12/2019 4972b_en_MD2S

    29/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    29

    enINSTALLATION AND MAINTENANCE

    Variable speed driveGENERAL EMC - HARMONICS - MAINS INTERFERENCE

    4.6 - Electromagnetic compatibility (EMC)

    CAUTION:

    Conformity of the drive is only assured when the mechanical and electrical installation instructions described in thismanual are adhered to.

    Immunity

    Standard Description Application Conformity

    IEC 61000-4-2Electrostatic discharges Product casing Level 3 (industrial)

    EN 61000-4-2

    IEC 61000-4-3 Immunity standards for radiated

    radio-frequencyProduct casing Level 3 (industrial)

    EN 61000-4-3

    IEC 61000-4-4Bursts of fast transients

    Control cable Level 4 (industrially hardened)

    EN 61000-4-4 Power cable Level 3 (industrial)

    IEC 61000-4-5Shock waves Power cables Level 4

    EN 61000-4-5

    IEC 61000-4-6 Generic immunity standards for

    conducted radio-frequency

    Control and power

    cablesLevel 3 (industrial)

    EN 61000-4-6

    EN 50082-2Generic immunity standards forthe industrial environment

    - ConformingIEC 61000-6-2

    EN 61000-6-2

    EN 61800-3

    Variable speed drive standards Conforming to the rst and second environmentIEC 61800-3

    EN 61000-3

    Emission

    Standard Description CategoryConformity conditions

    Standard With external RFI lter(1)

    EN 61800-3 Variable speed drive standards

    C1 - -

    C2 -

    Conforming

    - Cable length < 20 m- Switching frequency < 4 kHz

    C3

    Conforming

    - Cable length < 100 m

    - Switching frequency < 4 kHz

    Conforming

    - Cable length < 100 m

    - Switching frequency < 6 kHz

    (1) See 5.4

  • 8/12/2019 4972b_en_MD2S

    30/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    30

    enINSTALLATION AND MAINTENANCE

    Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS

    5.1 - Parameter setting

    5.1.1 - MDX-Powerscreen General

    The POWERSCREEN interface is a touch screen which can

    be used to access various menus to setup and supervise thedrive. It is installed as standard on the POWERDRIVE MD2S.

    After the loading phase following the power-up of the drive,

    the parameter-setting interface displays the screen below in

    french. Select language using the "F" buttons below

    COM CPU PWR

    F

    C D E

    A

    B

    Ref. Function

    A 4.3" touch screen

    B Touch-sensitive button to access the main menu

    C

    "COM" LED, indicates the state of the communicationwith the drive.

    Off: no communication

    Flashing: communicating

    D "CPU" LED, indicates the status of the interface CPU

    E"PWR" LED, indicates the state of the interface power

    supply

    FTouch-sensitive buttons for language selection (can take

    a few minutes to load)

    5 - PARAMETER-SETTING INTERFACE AND OPTIONS

    Connection to the drive

    Px1 Px2 Px3P1 P 2

    1 1 1

    Connector for optionaleldbus and/or

    speed feeback

    Connector for MDX-

    KEYPAD or MDX-Powerscreen display

    USB connector for

    MDX-SOFT

    P1 connector

    This connector is a slave type B USB socket, and is used to

    communicate via PC using the MDX-SOFT software.In conformity with standard EN 60950, the USB link

    can only be used via a device that provides

    isolation of 4 kV (MDX-USB isolator option).

    P2 terminal blockThis is a standard RS485/RS422 terminal block which

    is used to connect a parameter-setting interface or to

    communicate via Modbus RTU.

    Terminals Description

    1 0V

    2 Rx\, Tx\

    3 Rx, Tx

    4 24V

    Check that control circuits are powered downbefore disconnecting the programming interface

    from the P2 connector.

  • 8/12/2019 4972b_en_MD2S

    31/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    31

    A

    E

    D

    F

    C

    B

    G

    enINSTALLATION AND MAINTENANCE

    Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS

    Architecture

    From the welcome screen, press the button to access the

    main page of the parameter-setting interface, consisting of 5

    touch-sensitive buttons:- Information: Can be used to obtain information very quicklyabout the drive, the eldbus option, the parameter-setting

    interface, and can also be used to select the language.

    - Read mode: Is used to display the status of the drive when

    stopped or in operation, as well as its main measurement

    data points.- Parameter setting: Used for reading and/or modication of

    all the drive parameters, as well as to set the date and time on

    the display.

    - Control via keypad: Gives direct access to motor control

    via the touch screen (Run/Stop, direction of rotation, speed

    reference). These screen parameters can be set using the

    Parameter setting/Parameter setting via the keypad menu.

    Control via the keypad is disabled in factory-set conguration.- Trip history: Gives a quick overview of the last 10 drive

    trips.

    - : This button is accessible on all screens in factory-setconguration and is used to give a stop command (can be

    disabled).

    At any time and regardless of the screen displayed, the

    button can be used to return to previous pages, as far as the

    interface main page.

    For further information, see the commissioning manual

    ref. 4617.

    5.1.2 - MDX-KEYPAD

    5.2.3.1 - General

    This keypad, which is remote from the drive, makes easy the

    setting of the POWERDRIVE MD2S and provides accessto all parameters. Its LCD display, consisting of one line of

    12 characters and 2 lines of 16 characters, offers text which

    can be displayed in 4 languages (English, French, German

    and Spanish).

    The MDX-KEYPAD has 2 main functions:

    - A read mode for POWERDRIVE MD2S supervision anddiagnostics

    - An access mode to all the POWERDRIVE MD2Sparameters

    in order to optimise settings or congure special applications.

    As soon as it is switched on, the MDX-KEYPAD is set to read

    mode. The buttons are used to scroll through the allparameters required for supervision and diagnostics:

    - Motor current

    - Motor frequency

    - Motor voltage

    - Analog I/O levels- Digital I/O states

    - Logic function states

    - Timer

    Ref. Function

    A

    3-line backlit LCD display indicating:- The drive operating status and its main data

    - The main adjustment parameters via a "Quick

    parameter setting" menu

    - All the drive parameters via 21 "Advanced parameter

    setting" menus (access via a code)

    B

    Green button for run command if control via the keypad is

    enabled.See "Keypad set up".

    C

    Red button for drive reset or to give a stop command if

    control via the keypad is enabled.

    See parameters Ctr.05 (6.43)and 06.12.

    D

    Blue button for change of direction of rotation if control via

    the keypad is enabled.

    See parameter Ctr.05 (6.43).

    ENavigation button ( , , , ) for movingthrough the various menus and changing the contents of

    parameters.

    F button for saving and changing the mode (display,

    read, set parameters).

    G "?"button not used.

    For more information, see the commissioning manual

    ref. 4617. This manual describes conguration using the

    MDX-Powerscreen parameter-setting interface, but thecommissioning procedure also applies to the MDX-KEYPAD.

    Installation

    The MDX-KEYPAD does not require any special installation.At the power off, simply connect it via its 1.5 metre cable

    (supplied with the keypad), on P2 connector.

    5.1.3 - MDX-SOFT

    The MDX-SOFT enables parameter setting or supervision of

    the POWERDRIVE MD2S from a PC. Numerous functionsare available:

    - Fast commissioning

    - File saving

    - Comparison of 2 les or one le with the factory settings

    - Printing of a complete le or differences compared to the

    factory settings

    - Supervision- Diagnostics

    To connect the PC to the POWERDRIVE MD2S, use an"MDX-USB Isolator" isolated USB cable.

    This software can be downloaded from the web at the

    following address: http://www.leroy-somer.com/

    http://www.leroy-somer.com/en/downloads/software/http://www.leroy-somer.com/en/downloads/software/
  • 8/12/2019 4972b_en_MD2S

    32/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    32

    enINSTALLATION AND MAINTENANCE

    Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS

    5.2 - Add-on options

    The POWERDRIVE MD2S control board is designed to be

    plugged with various optional modules. Several options can

    be combined: Speed feedback option (see section 5.2.1)

    Fieldbus option (see section 5.2.2)

    Additionnal I/O option (see section 5.2.3)

    5.2.1 - Fieldbus modules

    Fieldbus modules can be used to communicate with the

    corresponding networks respective. They can be integrated

    in and are supplied by the drive.

    Two types of options are offered (with the same functionality):

    MDX option: option to be tted to the control board (white)

    CM module: compact module to be integrated in an

    existing MDX board (grey)

    Option / Module Fieldbus

    MDX-PROFIBUS

    CM-PROFIBUSProbus DP V1

    MDX-MODBUS

    CM-MODBUSModbus RTU on RS485/232

    MDX-ETHERNET

    CM-MODBUSModbus TCP on Ethernet

    MDX-CAN-OPENCM-CAN-OPEN

    Can Open

    MDX-ETHERNET-IPCM-ETHERNET-IP

    EtherNet/IP

    Check that the optional module is in good

    condition: never install a damaged module in the

    drive.

    Before installing or removing the option, or when it is

    necessary to disconnect the cables connected to it, it is

    essential for the drive to be switched off.

    CAUTION:

    Do not break the cut-out part.

    A MDX-Fieldbus option can never take the MDX-ENCODER terminal block.

    For more information, refer to the manuals for the relevantoptions available on www.leroy-somer.com.

    5.2.2 - Speed feedback option

    5.2.2.1 - MDX-ENCODER

    The MDX-ENCODER option is used to manage the motor

    speed feedback. It manages incremental encoders with orwithout commutation channels.

    Before installing or removing the MDX Speed

    feedback option, or when it is necessary todisconnect the cables connected to the option, it is

    essential for the drive to be switched off.

    5.3.2.2 - General

    Use a shielded cable for connection, and connect the

    shield over 360 using the grounding bracket (see section

    5.2.4).

    The MDX-Encoder module can manage the motor PTC

    thermal probe via terminals T1 and T2. In this case, someparameters need to be set. Refer to parameter Mtr.06 (05.70)

    in the commissioning manual ref. 4617.

    Terminals 0 and 0\ are not used.

    Note: LEROY-SOMER offers optional connection cables. For

    more information, please get in touch with your usual LEROY-

    SOMER contact.

    CAUTION: The encoder cable shielding must always be

    connected to the grounding bracket supplied with the

    option.

    Connection terminal blocks

    - + A B O

    T1 T2 U V W

    A B O

    U V W

    +Power supply

    -

    Rated voltage

    5V 10% - Output current 300mA

    15V 10% - Output current 200mA

    A

    Encoder channel connectionA\

    B

    B\

    Maximumfrequency

    500 kHz

  • 8/12/2019 4972b_en_MD2S

    33/48

  • 8/12/2019 4972b_en_MD2S

    34/48

    LEROY-SOMER 4972 - 2013.06 / b

    POWERDRIVE MD2S

    34

    enINSTALLATION AND MAINTENANCE

    Variable speed drivePARAMETER-SETTING INTERFACE AND OPTIONS

    5.2.2.2 - MDX-RESOLVER

    The MDX-RESOLVER option is used to manage the motor

    speed feedback. It manages 2 to 8 poles resolvers.

    Before installing or removing the MDX Speed

    feedback option, or when it is necessary to

    disconnect cables from the option, it is essential

    for the drive to be switched off.

    General

    The MDX-RESOLVER module can manage the motor

    PTC thermal probe via terminals T1 and T2. In this case,

    some parameters need to be set. Refer to parameter Mtr.06

    (05.70) in the commissioning manual ref. 4617.

    Note: LEROY-SOMER offers optional connection cables. For

    more information, please get in touch with your usual LEROY-

    SOMER contact.

    Use a single twisted pair cable, shielded pairs with

    an outer shield for the connection.

    Connect the shield over 360 at both ends (grounding

    bracket supplied with the option).

    Connection terminal blocks

    MDX-RESOLVER wiring

    1 Resolver

    excitation

    LOW

    2 HIGH

    Characteristic 10 kHz sine wave signal

    Rated voltage

    Transformer ratio (03.58):

    4 : 1 = 5.2 Vrms

    3 : 1 = 3.8 Vrms

    2 : 1 = 2.6 Vrms 1 : 1 = 1.3 Vrms

    Max. current 80 mA (EXC HIGH)

    3 x

    4 x

    5Encoder

    simulation

    Channel A output6 Channel /A output

    7 Channel B output

    8 Channel /B output

    CharacteristicRS 485 differential voltage

    (A and /A, B and /B)

    9 x

    10 x

    11

    Resolver inputs

    SIN HIGH

    12 SIN LOW

    13 COS HIGH

    14 COS LOW

    Characteristic 2 Vrms sine wave signal (max)

    Frequency 10 kHz15 x

    5.2.3 - MDX-I/O TIMER option

    General:

    The MDX-I/O TIMER option is used to:

    Increase the number of drive inputs and outputs Access the drive conguration: WEB server function

    Back up and restore the drive parameter settings (via PC) Save parameters for a period of time (including an SD

    type memory card): Data logger function

    Detail of the features :

    - 2 analog inputs (including a differential analog input)

    - 1 KTY temperature sensor input- 1 analog output

    - 4 digital inputs

    - 2 digital inputs

    - 2 programmable relays

    - 1 internal clock

    - year, month, day, hours, minutes, seconds backup mode- 1 Ethernet port on RJ45 connector

    Connection

    Please consult the specic documentation for the MDX-I/O

    TIMER.

    5.2.4 - Option installation

    5.2.4.1 - grounding b