1 Data Bulletin 0739DB9901R11/03 June 2004 Cedar Rapids, Iowa, USA International Miniature Circuit Breakers with QO® Plug-on and Bolt-on Connections Class Number 0739 Retain for future use. © 2000-2004 Schneider Electric All Rights Reserved GENERAL DESCRIPTION The following topics are covered in this bulletin. Characteristics on page 2 Circuit Breaker Operating Characteristics on page 3 Main Circuit Breakers on page 5 QO-MBGX main circuit breakers with residual current protection on page 7 Main Switch Disconnectors and Main Lugs on page 10 QOE200 Main Switch with Residual Current Protection on page 12 QOE Circuit Breakers on page 14 QOE-RCBO Circuit Breakers with Residual Current Protection on page 17 QOH-X Circuit Breakers on page 20 QOH-RCDX Circuit Breakers with Residual Current Protection on page 24 QOXD Circuit Breakers on page 27 In 1955 Square D Company introduced the QO ® Plug-on System and revolutionized the way electrical contractors install miniature circuit breakers in the United States. Today, as part of Schneider Electric, we offer the same Plug-on System technology around the world. A full line of IEC Certified QO products are available for residential, commercial and industrial applications. Table 1: International Miniature Circuit Breaker Description Circuit Breaker Description Single-phase Consumer Units Three-phase Distribution Boards QO-MBX Main circuit breakers QO-MBGX Main circuit breakers with residual current protection QO-M/QO-L Main switches and lugs QOE200 Main switches with residual current protection QOE Branch circuit breaker QOE-RCBO Branch circuit breaker with residual current protection QOH-X Branch circuit breaker QOH-RCDX Branch circuit breaker with residual current protection QOXD Branch circuit breaker

Transcript of 0739DB9901

Page 1: 0739DB9901

1

Data Bulletin0739DB9901R11/03

June 2004Cedar Rapids, Iowa, USA

International Miniature Circuit Breakerswith QO® Plug-on and Bolt-on Connections Class Number 0739Retain for future use.

© 2000-2004 Schneider Electric All Rights Reserved

GENERAL DESCRIPTION The following topics are covered in this bulletin.

■ Characteristics on page 2

■ Circuit Breaker Operating Characteristics on page 3

■ Main Circuit Breakers on page 5

■ QO-MBGX main circuit breakers with residual current protection on page 7

■ Main Switch Disconnectors and Main Lugs on page 10

■ QOE200 Main Switch with Residual Current Protection on page 12

■ QOE Circuit Breakers on page 14

■ QOE-RCBO Circuit Breakers with Residual Current Protection on page 17

■ QOH-X Circuit Breakers on page 20

■ QOH-RCDX Circuit Breakers with Residual Current Protection on page 24

■ QOXD Circuit Breakers on page 27

In 1955 Square D Company introduced the QO® Plug-on System and revolutionized the way electrical contractors install miniature circuit breakers in the United States. Today, as part of Schneider Electric, we offer the same Plug-on System technology around the world. A full line of IEC Certified QO products are available for residential, commercial and industrial applications.

Table 1: International Miniature Circuit Breaker Description

Circuit Breaker

DescriptionSingle-phase Consumer Units

Three-phase Distribution Boards

QO-MBX Main circuit breakers —

QO-MBGX Main circuit breakers with residual current protection —

QO-M/QO-L Main switches and lugs

QOE200 Main switches with residual current protection —

QOE Branch circuit breaker

QOE-RCBO Branch circuit breaker with residual current protection

QOH-X Branch circuit breaker

QOH-RCDX Branch circuit breaker with residual current protection

QOXD Branch circuit breaker

Page 2: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved2

CHARACTERISTICS • Circuit breakers are rated 240 Vac single-phase and 415 Vac three-phase, 50/60 Hz, 3–100 A.

• Circuit breakers are available in 1-, 2- or 3-pole construction.

• Thermal trip elements are factory calibrated to 40°C (IEC 947-2) and 30°C (IEC 898) ambient temperature.

• RCBO devices available with 10 mA, 30 mA and 100 mA residual current protection.

• Trip-free handle ensures tripping even when the circuit breaker is held or locked in the ON position.

• Circuit breakers are in compliance with international standards set by the International Electrotechnical Commission (IEC).

• The CE marking is located on each circuit breaker in accordance with the low-voltage directive of the European Union.

• The entire QO circuit breaker family provides the advantage of a plug-on connection. (Bolt-on connections also available.)

Advantages of the Plug-on System • A 50% reduction on installation time compared to a lug/lug (DIN) alternative.

• No link bars to fit and tighten.

• Contact jaws automatically align the circuit breakers in the equipment.

• High short circuits result in an increase in jaw pressure reducing the potential for hazardous arcs on the line side of the circuit breaker.

Figure 1: Plug-on System

0739

3011

Page 3: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 3

CIRCUIT BREAKER OPERATING CHARACTERISTICS

Table 2: Accessories

Accessory DescriptionAccessoryCatalog Number

Circuit Breaker Catalog Number

QO

-MB

X

QO

-MB

GX

QO

E-2

00

QO

E

QO

E-R

CB

O

QO

H-X

QO

H-R

CD

X

QO

XD

Handle Tie Converts any two adjacent 120/240 Vac single-pole circuit breakers to independent-trip 2-pole. QO1HT — — — — —

Handle Clamp

Clamp for holding QO single-pole circuit breaker handle in ON or OFF position. QO1LO — — — — —

Clamp for holding QO either 1-, 2- or 3-pole circuit breaker handles in ON or OFF position. HLO-1 — — —

HandlePadlock Attachment

Attaches to 1-, 2- and 3-pole circuit breaker handles (removable). QOEPLA — — — — — —

Attaches to single-pole circuit breaker handles (removable). QOE-1PL — — — — — — —

For padlocking single-pole QO circuit breaker in ON or OFF position (fixed). QO1PA — — — — —

For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3-pole QO circuit breakers which require padlocking in either ON or OFF position (fixed).

QO1PL — — — — —

For padlocking single-pole QO circuit breaker in ON or OFF position (removable). QOHPL — — — — —

For padlocking single-pole QO circuit breaker in ON or OFF position. For 2- and 3-pole QO circuit breakers which require padlocking in either ON or OFF position (removable).

QO1HPL — — — —

For padlocking 2-pole QO-MBGX circuit breaker in either ON or OFF position (removable). GFI2PA — — — — — — —

For padlocking single-pole QO circuit breaker in the OFF position only (fixed). QO1PAF — — — — —

For padlocking 2- and 3-pole QO circuit breakers in the OFF position only (fixed). QO2PAF — — — — —

Table 3: Main Circuit Breakers

Circuit Breaker Catalog Number Prefix Number of Poles

Continuous Ampere Rating

IEC 60947-2 Service Rating Icu (Ics) Residual Trip Current BS4293

Plug-on Bolt-on 240 V 415 V

QO-MBX N/A 2 10–100 10 000 (25%) — —

QO-MBGX30 N/A 2 16–63 10 000 (25%) — 30 mA

Table 4: Branch Circuit Breakers

Circuit BreakerCatalog Number Prefix Number of

PolesContinuous Ampere Rating

IEC 898 Service Rating Icn Tripping Characteristics

Plug-on Bolt-on 240 V 415 V

QOXD QOBXD 1, 2, 3 10–32 3 000 3 000 Type D (10–20 In)

QO-EB6 N/A 1 3–63 6 000 — Type B (3–5 In)

QO-EC6 N/A 1, 3 6–63 6 000 6 000 Type C (5–10 In)

QO-ED6 N/A 1 6–63 6 000 — Type D (10–20 In)

QO-EB10 N/A 1 3–63 10 000 — Type B (3–5 In)

QO-EC10 N/A 1, 2, 3 6–63 10 000 10 000 Type C (5–10 In)

QO-ED10 N/A 1, 2, 3 6–63 10 000 10 000 Type D (10–20 In)

Page 4: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved4

Table 5: Branch Circuit Breakers

Circuit BreakerCatalog Number Prefix Number of Poles

Continuous Ampere Rating

IEC 947-2 Service Rating Icu (Ics)

Plug-on Bolt-on 240 V 415 V

QOXD QOBXD

1, 2, 3 10–32 3 000 (100%) 3 000 (100%)

1 40–63 3 000 (50%) —

2, 3 40–100 3 000 (50%) 3 000 (50%)

QOH-X QOBH-X

1, 2, 3 10–63 5 000 (25%) 5 000 (25%)

1, 2, 3 70–100 6 000 (25%) 6 000 (25%)

4 100 — 6 000 (25%)

Table 6: Residual Current Circuit Breakers

Circuit BreakerCatalog Number Prefix Number

of Poles

Continuous Ampere Rating

IEC 898 Service Rating Icn

Residual Trip Current BS4293Plug-on Bolt-on 240 V 415 V

QOE-B01 N/A 1 6–40 10 000 — 10 mA

QOE-B03 N/A 1 6–40 10 000 — 30 mA

QOE-C01 N/A 1 6–40 10 000 — 10 mA

QOE-C03 N/A 1 6–40 10 000 — 30 mA

QOE-C100 N/A 1 6–40 10 000 — 100 mA

Table 7: Residual Current Circuit Breakers

Circuit BreakerCatalog Number Prefix Number

of PolesContinuous Ampere Rating

IEC 947-2 Service Rating Icu (Ics)

Plug-on Bolt-on 240 V 415 V

QOH-RCDX10 QOBH-RCDX10 1 10–32 5 000 (25%) —

QOH-RCDX30 QOBH-RCDX30 1 10–32 5 000 (25%) —

Page 5: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 5

MAIN CIRCUIT BREAKERS QO-MBX main circuit breakers are designed for use as incoming main devices for single-phase consumer unit applications.

• Compliance with International Standards: Certified to IEC 60947-2, 10 kA at 240 Vac when used as a main incomer on single-phase systems, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent red trip indicator on the front of the circuit breaker).

• Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature.

• Endurance (Switching Operations):

— 1,500 full-load operations

— 8,500 no-load operations

• Mounting: Plug-on connection.

Accessories • Handle Clamp (HLO-1)The handle clamp accessory fastens the handle in the ON or OFF position. This handle clamp cannot be padlocked.

• Handle Padlock Attachments (QO1PL, QO1HPL)Handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: Fixed and removable. The fixed style (QO1PL) is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style (QO1HPL) is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

— Removable attachment: QO1HPL

— Fixed attachment: QO1PL

Figure 2: QO-MBX Circuit Breaker

0739

3002

Table 8: QO-MBX Circuit Breaker

Continuous Ampere RatingCircuit Breaker

Catalog Number

2-Pole Circuit Breaker

16 QO216MBX

20 QO220MBX

32 QO232MBX

45 QO245MBX

63 QO263MBX

70 QO270MBX

80 QO280MBX

100 QO2100MBX

Figure 3: QO-MBX Circuit Breaker Accessories

0739

3026

0739

3043

0739

3042

HLO-1 Handle Clamp

QO1PL Fixed Padlock Attachment

QO1HPL RemovablePadlock Attachment

Page 6: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved6

Lugs

Dimensions

Figure 4: QO-MBX Circuit Breaker Lugs

0739

3015

10–32 A Lugs 45–63 A Lugs 70–100 A Lugs

(2)

(1)

Table 9: QO-MBX Circuit Breaker Lugs

ContinuousAmpereRating

Wire Type

Wire Size Tempera-tureRating

Torque Value

mm2 AWG N•m lb-in

10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36

10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36

45–63 Al/Cu (1) 10–25 (1) #8–#2 75°C 5 45

70–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50

Figure 5: QO-MBX Circuit Breaker Dimensions

0739

3030 0.94

(24)

26°

21°22°

ON Trip

ped

OFF

Res

et

0.25(6) 2.92

(74)

2.75(70)

2.31(59)

2.91(74)

0.16(4)

Dim. A

Dim. B

Dim. C

1.48(38)

1.34(34)

0.53(13)

0.75(19)

Dim. A: 3.0 in. (76 mm), 10–32 ADim. B: 3.125 in. (79 mm), 45–63 ADim. C: 3.5 in. (89 mm), 70–100 A

Dual Dimensions: in.(mm)

Page 7: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 7

QO-MBGX MAIN CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION

QO-MBGX main circuit breakers with residual current protection are designed for use as incoming main devices for single-phase consumer unit applications.

• Compliance with International Standards: Certified to IEC 61009-1 10 kA at 240 Vac when used as a main incomer on single-phase systems, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload, short circuit or residual current ground fault is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker).

• Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface.

• Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature

• Residual Current Protection: Residual ground-fault trip currents are factory set at 30 mA.

• Endurance (Switching Operations):

— 1,500 full-load operations

— 8,500 no-load operations

• Mounting: Plug-on connection.

Accessories

• Handle Clamp (HLO-1)The handle clamp accessory fastens the handle in the ON or OFF position. This handle clamp cannot be padlocked.

• Handle Padlock Attachments (GFI2PA, QO1HPL)Handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed (GFI2PA) and removable (QO1HPL). The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

Figure 6: QO-MBGX Circuit Breaker

0739

3009

Table 10: QO-MBGX Circuit Breakers

ContinuousAmpere Rating

Circuit BreakerCatalog Number

Residual TripCurrent 30 mA

2-Pole

16 QO216MBGX30

20 QO220MBGX30

32 QO232MBGX30

45 QO245MBGX30

63 QO263MBGX30

Figure 7: QO-MBGX Circuit Breaker Accessories

0739

3026

0739

3043

0739

3042

HLO-1 Handle Clamp

GFI2PA Fixed Padlock Attachment

QO1HPL RemovablePadlock Attachment

Page 8: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved8

Lugs

Dimensions

Figure 8: QO-MBGX Circuit Breaker Lug

16–63 A Lug

0739

3016

Table 11: QO-MBGX Circuit Breaker Lug

ContinuousAmpereRating

Wire Type

Lug Wire SizeTemperatureRating

Torque Value

mm2 AWG N•m lb-in

16–63 Al/Cu (1) 2.5-16 (1) #14–#6 75°C 5 45

Figure 9: QO-MBGX Circuit Breaker Dimensions

0739

3031

2.91(74)

2.31(59)

4.12(103)

1.49(38)

0.94(24)

26°

21°22°

ON Trip

ped

OFF

Res

et

Dual Dimensions: in.(mm)

Page 9: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 9

Connections

Figure 10: QO-MBGX Circuit Breaker Connections in 240 Vac Single-phase Consumer Unit

0739

3029

240 V

240 V

Load

Load

Load

S/N

GND

Branch Circuit Breakers240 Vac Source

LN

QO-MBGXMain Circuit Breaker

Page 10: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved10

MAIN SWITCH DISCONNECTORS AND MAIN LUGS

QO-M main switch disconnectors and QO-L main lugs are designed for use as incoming main devices in single-phase consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: QO-M switches are certified to IEC 60947-3 at 240 Vac single phase and 415 Vac three phase, 50/60 Hz, CE marked.

— Duty category AC21-A (125 A) and AC22-B (100 A).

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Over-center toggle mechanism. ON-OFF isolator switch disconnector.

• Mounting: Plug-on connection.

• Accessories: A padlocking feature is incorporated into the design of the switch disconnector.

Lug

Figure 11: QO-M Main Switch Disconnector

0730

3008

Figure 12: QO-L Main Lug

0730

3014

Table 12: QO-M/QO-L Main Switch Disconnect and Main Lug

Ampere Rating

Catalog Number

Main Switch Units

1-Pole 2-Pole 3-Pole 4-Pole

100 N/A QO1100M — —

125 N/A N/A QO3100M —

125 (4-pole) N/A N/A QO4100M QO4100M

125 (4-pole with solid neutral)

N/A N/A QO4100MN QO4100MN

Main Lug Units

100 QO1100L N/A N/A —

125 N/A N/A QO3100L —

125 (4-pole) N/A N/A QO4100L QO4100L

Figure 13: QO-M/QO-L Lug

100–125 A Lug

0739

3020

Table 13: Table 11: QO-M/QO-L Lug

ContinuousAmpereRating

Wire Type

Lug Wire SizeTemperatureRating

Torque Value

mm2 AWG N•m lb-in

100–125 Al/Cu (1) 10–50 (1) #12–#2/0 75°C 6 50

Page 11: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 11

DimensionsFigure 14: QO-M Main Switch Disconnector Dimensions

0739

3032

Dual Dimensions: in.(mm)

2.25(57)

1.62(41)

0.25(6.3)

0.34(8.7)

0.20(5)

0.29(7.5)

0.56(39)

0.25(6.3)

0.43(11)

60°

0.75(19)

3.20(81)

3.36(85)

0.55(14)

1.50(38)

2.25(57)

3.0(76)

Page 12: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved12

QOE200 MAIN SWITCH WITH RESIDUAL CURRENT PROTECTION

QOE200 main switches with residual current protection are designed for use as incoming main devices in single-phase consumer unit applications.

• Compliance with International Standards: Certified to BS 4293 at 240 Vac single-phase, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on residual current ground fault is by location of the handle in the OFF position. The circuit breaker is also equipped with a red trip indicator on the front of the device.

• Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface.

• Residual Current Protection: Residual ground-fault trip currents are factory set at 30 mA, 100 mA or 300 mA. They are sensitive to ac currents.

• Mounting: Plug-on connection.

Accessory Handle Padlock Attachment (QOEPLA)

The handle padlock attachment allows padlocking of the main switch handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

Figure 15: QOE200 Main Switch

0739

3004

ContinuousAmpere Rating

Circuit BreakerCatalog Number (2-Pole)

Residual Trip Current 30 mA

63 QOE200R30

100 QOE20030

Residual Trip Current 100 mA

63 QOE200R100

100 QOE200100

100 with time delay QOE200100S

Residual Trip Current 300 mA

63 QOE200R300

100 QOE200300

Figure 16: QOEPLA Handle Padlock Attachment

0739

3023

Page 13: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 13

Lug

Dimensions

Connections

Figure 17: QOE200 Circuit Breaker Lug

63–100 A Lug

0739

3019

Table 14: QOE200 Circuit Breaker Lug

ContinuousAmpereRating

Wire Type

Lug Wire SizeTemperatureRating

Torque Value

mm2 AWG N•m lb-in

63–100 Cu (1) 10–50 (1) #8–#1/0 75°C 3.5 32

Figure 18: QOE200 Circuit Breaker Dimensions

0739

3033

Dual Dimensions: in.(mm)

1.45(37)

1.40(35)

4.13105 2.68

(68)

0.19(5)

0.35(8.8)

0.45(11)

0.19(5)

0.49(12)

85°

Figure 19: QOE200 Circuit Breaker Connections

0739

3040

Load Switches

Load Neutral

S/N

GND

Load 3

Load 2

Load 1

240 V

LN

QOE-2002-pole Circuit Breaker

240 V Load Power

Line Power

Page 14: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved14

QOE CIRCUIT BREAKERS QOE current-limiting branch circuit breakers are designed for use in single-phase consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: Certified to IEC 60898, 6 kA and 10 kA at 240 Vac single-phase and 415 Vac three-phase, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the handle of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle that ensures tripping even when held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position.

• Thermal Trip Element: Thermal trip elements are factory calibrated at 30°C ambient temperature (50°C calibration available: Contact your local sales office). Instantaneous-trip level types B, C and D:— Type B—(3–5 In) Overcurrent protection for sensitive equipment

— Type C—(5–10 In) Overcurrent protection for all application types

— Type D—(10–14 In) Overcurrent protection for loads with high inrush currents

• Mounting: Plug-on connection.

Accessory Handle Padlock Attachment (QOEPLA)The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

Lugs

Figure 20: QOE 1-Pole Circuit Breaker

0739

3077

Figure 21: QOE 3-Pole Circuit Breaker

0739

3005

Figure 22: Handle Padlock Attachment (QOEPLA)

0739

3023

Figure 23: QOE Circuit Breaker Lugs

3–25 A Lug 32–63 A Lug

0739

3018

0739

3017

Table 15: QOE Circuit Breaker Lugs

ContinuousAmpereRating

Wire Type

Lug Wire Size TemperatureRating

Torque Value

mm2 AWG N•m lb-in

3–25 Cu 1–25 (1) #18–#14 75°C 3.5 32

32–63 Cu 2.5–35 (1) #14–#2 75°C 3.5 32

Page 15: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 15

Thermal-magnetic Plug-on Circuit Breakers 240/415 Vac, 10–63 A, Certified to IEC 898Table 16: QOE Circuit Breakers (10 kA) and QOE Circuit Breakers (6 kA)

QOE Circuit Breakers (10 kA) QOE Circuit Breakers (6 kA)

Ampere Rating Circuit Breaker Catalog Number Ampere Rating Circuit Breaker Catalog Number

Type B Instantaneous TripCircuit Breakers

1-Pole 2-Pole 3-PoleType B Instantaneous Trip Circuit Breakers

1-Pole 2-Pole 3-Pole

3 QO103EB10 N/A N/A 3 QO103EB6 N/A N/A

6 QO106EB10 N/A N/A 6 QO106EB6 N/A N/A

10 QO110EB10 N/A N/A 10 QO110EB6 N/A N/A

16 QO116EB10 N/A N/A 16 QO116EB6 N/A N/A

20 QO120EB10 N/A N/A 20 QO120EB6 N/A N/A

25 QO125EB10 N/A N/A 25 QO125EB6 N/A N/A

32 QO132EB10 N/A N/A 32 QO132EB6 N/A N/A

40 QO140EB10 N/A N/A 40 QO140EB6 N/A N/A

50 QO150EB10 N/A N/A 50 QO150EB6 N/A N/A

63 QO163EB10 N/A N/A 63 QO163EB6 N/A N/A

Type C Instantaneous-trip Circuit Breakers Type C Instantaneous-trip Circuit Breakers

6 QO106EC10 QO206EC10 QO306EC10 6 QO106EC6 N/A QO306EC6

10 QO110EC10 QO210EC10 QO310EC10 10 QO110EC6 N/A QO310EC6

16 QO116EC10 QO216EC10 QO316EC10 16 QO116EC6 N/A QO316EC6

20 QO120EC10 QO220EC10 QO320EC10 20 QO120EC6 N/A QO320EC6

25 QO125EC10 QO225EC10 QO325EC10 25 QO125EC6 N/A QO325EC6

32 QO132EC10 QO232EC10 QO332EC10 32 QO132EC6 N/A QO332EC6

40 QO140EC10 QO240EC10 QO340EC10 40 QO140EC6 N/A QO340EC6

50 QO150EC10 QO250EC10 QO350EC10 50 QO150EC6 N/A QO350EC6

63 QO163EC10 QO263EC10 QO363EC10 63 QO163EC6 N/A QO363EC6

Type D Instantaneous-trip Circuit Breakers Type D Instantaneous-trip Circuit Breakers

6 QO106ED10 QO206ED10 QO306ED10 6 QO106ED6 N/A N/A

10 QO110ED10 QO210ED10 QO310ED10 10 QO110ED6 N/A N/A

16 QO116ED10 QO216ED10 QO316ED10 16 QO116ED6 N/A N/A

20 QO120ED10 QO220ED10 QO320ED10 20 QO120ED6 N/A N/A

25 QO125ED10 QO225ED10 QO325ED10 25 QO125ED6 N/A N/A

32 QO132ED10 QO232ED10 QO332ED10 32 QO132ED6 N/A N/A

40 QO140ED10 QO240ED10 QO340ED10 40 QO140ED6 N/A N/A

50 QO150ED10 QO250ED10 QO350ED10 50 QO150ED6 N/A N/A

63 QO163ED10 QO263ED10 QO363ED10 63 QO163ED6 N/A N/A

Page 16: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved16

DimensionsFigure 24: QOE Circuit Breaker Dimensions

0739

3034

Dual Dimensions: in.(mm)

3.2081

2.24(57)

0.11(2.8)

2.03(51)

82°

0.5(14)

3.2(81)

2.21(56)

1.47(37)

0.73(18)

2.31(59)

2.91(74)

Page 17: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 17

QOE-RCBO CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION

QOE-RCBO branch circuit breakers with residual current protection and integral overcurrent protection are designed for use in single-phase consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: Certified to IEC 60898 and BS4293, 10 kA at 240 Vac, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the OFF position. Indication of a tripped circuit breaker on residual current ground fault is by location of the handle in an intermediate position.

• Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface.

• Thermal Trip Element: Thermal trip elements are factory calibrated at 30°C ambient temperature.

• Instantaneous trip level types B and C:

— Type B—(3–5 In) Overcurrent protection for sensitive equipment

— Type C—(5–10 In) Overcurrent protection for all application types

• Residual Current Protection: Residual ground-fault trip currents are factory set at 10 mA, 30 mA or 100 mA: Type A.

• Trip Mechanism: Device will trip on loss of neutral. Device is sensitive to both ac and pulsating dc fault current. Device will trip on voltage between neutral and earth greater than 50 Vac.

• Mounting: Plug-on connection.

Figure 25: QOE-RCBO Circuit Breaker

0739

3013

Page 18: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved18

Accessory

Handle Padlock Attachment (QOE1PL)The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. The padlock attachment is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

Lugs

Table 17: QOE-RCBO Circuit Breakers with Instantaneous Trip and Residual Trip Current

Type B Type C Type D

Ampere Rating

Circuit BreakerCatalog Number

Ampere Rating

Circuit BreakerCatalog Number

Ampere Rating

Circuit BreakerCatalog Number

10 mA 1-Pole 10 mA 1-Pole 10mA 1-Pole

6 QOE106B01 6 QOE106C01

10 QOE110B01 10 QOE110C01

16 QOE116B01 16 QOE116C01

20 QOE120B01 20 QOE120C01

32 QOE132B01 32 QOE132C01

40 QOE140B01 40 QOE140C01

30 mA 30 mA 30 mA

6 QOE106B03 6 QOE106C03 6 QOE106D03

10 QOE110B03 10 QOE110C03 10 QOE110D03

16 QOE116B03 16 QOE116C03 16 QOE116D03

20 QOE120B03 20 QOE120C03 20 QOE120D03

32 QOE132B03 32 QOE132C03 32 QOE132D03

40 QOE140B03 40 QOE140C03

100 mA 100 mA 100 mA

6 QOE106C100 6 QOE106D10

10 QOE110C100 10 QOE110D10

16 QOE116C100 16 QOE116D10

20 QOE120C100 20 QOE120D10

32 QOE132C100 32 QOE132D10

Figure 26: QOE1PL Handle PadlockAttachment

0739

3023

Figure 27: QOE-RCBO Circuit Breaker Lug

0739

3021

6–40 A Lug

Table 17: QOE-RCBO Circuit Breaker Lug

ContinuousAmpereRating

Wire Type

Lug Wire Size TemperatureRating

Torque Value

mm2 AWG N•m lb-in

6–40 Cu (1) 1–10 (1) #18–#8 75°C 1.0 9

Page 19: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 19

Dimensions

Connections

Figure 28: QOE-RCBO Circuit Breaker Dimensions

0739

3035

Dual Dimensions: in.(mm)

0.15(4)

0.35(9)

0.37(9.5)

0.59(5)0.29

(7.3)

2.53(64)

0.73(18)

0.19(5)

0.68(17)

0.27(7)

0.17(4.5)

0.34(8.8)

60°

60°

4.36(110)

Figure 29: QOE-RCBO Circuit Breaker Connections

0739

3041

N L

Line Power QOE-RCBO 1-pole Circuit Breaker

A—Load Power

Load 1

Load 2

B—Load Neutral

C—Panel Neutral Wire Blue

D—Panel Earth Wire Yellow/GreenA

B

C

D

Page 20: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved20

QOH-X CIRCUIT BREAKERS QOH-X branch circuit breakers are designed for use in single-phase consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: Certified to IEC 60947-2, 5 kA (10–63 A) and 6 kA (70–100 A) at 240 Vac single-phase and 415 Vac three-phase, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker).

• Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature.

• Endurance (Switching Operations):

— 1,500 full-load operations

— 8,500 no-load operations

• Mounting: Plug-on and bolt-on connection available.

QOH-X and QOBH-X Circuit Breakers Thermal-magnetic, 240/415 Vac, 10–63 A Certified to IEC 947-2 at 5 kA, 70–100 A Certified to IEC 947-2 at 6 kA

Figure 30: QOH-X 1-Pole Circuit Breaker

0739

3006

Figure 31: QOH-X 4-Pole Circuit Breaker

0739

3007

Table 18: QOH-X and QOBH-X Circuit Breakers

QOH-X Plug-on Circuit Breakers QOBH-X Bolt-on Circuit Breakers

ContinuousAmpere Rating

Circuit Breaker Catalog Number ContinuousAmpere Rating

Circuit Breaker Catalog Number

1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole

10 QOH110X QOH210X QOH310X 10 QOBH110X QOBH210X QOBH310X

16 QOH116X QOH216X QOH316X 16 QOBH116X QOBH216X QOBH316X

20 QOH120X QOH220X QOH320X 20 QOBH120X QOBH220X QOBH320X

32 QOH132X QOH232X QOH332X 32 QOBH132X QOBH232X QOBH332X

45 QOH145X QOH245X QOH345X 45 QOBH145X QOBH245X QOBH345X

63 QOH163X QOH263X QOH363X 63 QOBH163X QOBH263X QOBH363X

70 QOH170X QOH270X QOH370X 70 QOBH170X QOBH270X QOBH370X

80 QOH180X QOH280X QOH380X 80 QOBH180X QOBH280X QOBH380X

100 QOH1100X QOH2100X QOH3100X 100 QOBH1100X QOBH2100X QOBH3100X

100 (4-pole) N/A N/A QOH4100X 100 (4-pole) N/A N/A QOBH4100X

Page 21: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 21

Accessories• Handle Tie (QO1HT)

The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip, multi-pole circuit breaker.

• Handle Clamps (QO1LO and HLO-1)The handle clamp accessories fasten the circuit breaker handle in the ON or OFF position. These handle clamps cannot be padlocked.

— 1-pole circuit breaker handle clamp: QO1LO

— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1

• Handle Padlock Attachments (QOHPL, QO1PA, QO1PL and QO1HPL)The handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. Padlock is not included.

— 1-pole circuit breaker removable attachment: QOHPL

— 1-pole circuit breaker fixed attachment: QO1PA

— 2- and 3-pole removable attachment: QO1HPL

— 2- and 3-pole fixed attachment: QO1PL

Lugs

Figure 32: QOH-X Circuit Breaker

0739

3025

0739

3027

0739

3028

QO1HT Handle Tie QO1LO Handle Clamp

QO1PA Fixed Padlock Attachment

QO1HPL RemovablePadlock Attachment

0739

3043

0739

3026

HLO-1 Handle Clamp

QO1PL FixedPadlock Attachment

0739

3042

0739

3044

QOHPL RemovablePadlock Attachment

Figure 33: QOH-X Circuit Breaker Lugs

0739

3016

0739

3022

10–32 A Lugs 45–100 A Lug

(1)

(2)

Table 19: Table 19: QOH-X Circuit Breaker Lugs

ContinuousAmpereRating

Wire Type

Lug Wire SizeTemperatureRating

Torque Value

mm2 AWG N•m lb-in

10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36

10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36

45–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50

Page 22: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved22

Dimensions NOTE: QOBH-X circuit breaker dimensions are the same as the QOH-X circuit breaker dimensions except as shown

Figure 34: QOH-X Circuit Breaker Dimensions

Dual Dimensions: in.(mm)

0739

3036

Dim. A: 3.5 in. (88.9 mm), 45–100 A for 1-, 2- and 3-poleDim. B: 3.00 in. (76.2 mm), 10–32 A for 1-, 2- and 3-pole

0.9424

21°22°

ON Tr

ippe

d

OFF

Res

et

Dim. A2.25(57)

Dim. B

1.48(38)

2.23(57)2.09(53)

1.34(34)

0.18(4)

0.59(15)0.38(10)

0.9424

0.9424

0.53(13)

0.53(13)

0.73(19)

2.91(74)

2.31(59)

2.75(70)

0.16(4)

0.25(6) 2.92

(74)

26°

Page 23: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 23

Figure 35: QOBH-X Circuit Breaker Dimensions

Dual Dimensions: in.(mm)

0.38(10)

0.75(19)

0.75(19)

0.75(19) 2.94

(75)

0739

3036

Page 24: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved24

QOH-RCDX CIRCUIT BREAKERS WITH RESIDUAL CURRENT PROTECTION

QOH-RCDX branch circuit breakers with residual current protection and integral overcurrent protection are designed for use in consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: Certified to IEC 60947-2 and BS4293, 5 kA at 240 Vac, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload, short circuit or residual current ground fault is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker).

• Push-to-test Function: A yellow push-to-test button is positioned on the front of the device for testing the residual current electronic trip circuit and mechanical tripping interface.Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient temperature.

• Residual Current Protection: Residual ground-fault trip currents are factory set at 10 or 30 mA.

• Endurance (Switching Operation):

— 1,500 full-load operations

— 8,500 no-load operations

Figure 36: QOH-RCDX Circuit Breaker

0739

3001

Table 20: QOH-RCDX and QOBH-RCDX Circuit Breakers with Instantaneous Trip and Residual Trip Current

QOH-RCDX Circuit Breaker QOBH-RCDX Circuit Breaker

ContinuousAmpere Rating

Circuit Breaker Catalog Number(1-Pole)

ContinuousAmpere Rating

Circuit BreakerCatalog Number(1-Pole)

Residual Trip Current 10 mA

Residual Trip Current 10 mA

10 QOH110RCDX10 10 QOBH110RCDX10

16 QOH116RCDX10 16 QOBH116RCDX10

20 QOH120RCDX10 20 QOBH120RCDX10

32 QOH132RCDX10 32 QOBH132RCDX10

Residual Trip Current 30 mA

Residual Trip Current 30 mA

10 QOH110RCDX30 10 QOBH110RCDX30

16 QOH116RCDX30 16 QOBH116RCDX30

20 QOH120RCDX30 20 QOBH120RCDX30

32 QOH132RCDX30 32 QOBH132RCDX30

Page 25: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 25

Accessories • Mounting: Plug-on and bolt-on connections available.

• Handle Tie (QO1HT)

• The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip, multi-pole circuit breaker.

• Handle Clamps (HLO-1 and QO1LO)

• The handle clamp accessories fasten the handle in the ON or OFF position. These handle clamps cannot be padlocked.

• Handle Padlock Attachments (QO1PA and QOHPL)The handle padlock attachment allows padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. Padlock is not included.

— Fixed padlock attachment: QO1PA

— Removable padlock attachment: QOHPL

Lugs

QOH-RCDX Circuit Breaker Figure 37: Accessories

0739

3026

0739

3027

0739

3028

0739

3025

HLO-1 Handle Clamp

QO1HT Handle Tie

QO1LO Handle Clamp

QO1PA Fixed Padlock Attachment

0739

3044

QOHPL RemovablePadlock Attachment

Figure 38: QOH-RCDX Circuit Breaker Lugs

0739

3022

10–32 A Lugs

(1)

(2)

Table 21: QOH-RCDX Circuit Breaker Lugs

ContinuousAmpereRating

Wire TypeLug Wire Size Temperature

Rating

Torque Value

mm2 AWG N•m lb-in

10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36

10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36

Page 26: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved26

Dimensions

Connections

Figure 39: QOH-RCDX Circuit Breaker Dimensions

0739

3037

Dual Dimensions: in.(mm)

4.12(108)

2.31(59)

2.91(74)

0.74(19)

26°

21°22°

ON Trip

ped

OFF

Res

et

Figure 40: QOH-RCDX Circuit Breaker Connections

0739

3039

240 Vac

240 V

N L

240 Vac Source

Load Power 250 V DuplexReceptacle

Load Neutral

Equipment Ground

S/N

GND

Page 27: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 27

QOXD CIRCUIT BREAKERS QOXD branch circuit breakers are designed for use in single-phase consumer unit and three-phase distribution panelboard applications.

• Compliance with International Standards: Certified to IEC 947-2 (3 kA [10–63 A]) and IEC 898 (3 kA [10–32 A]) at 240 Vac single phase and 415 Vac three phase, 50/60 Hz, CE marked.

• ON/OFF Indication: ON/OFF markings are on the face of the circuit breaker along with the international I/O markings.

• Handle Operation: Trip-free handle through an over-center toggle mechanism that ensures tripping even when the handle is held or locked in the ON position.

• Trip Indication: Indication of a tripped circuit breaker on overload or short circuit is by location of the handle in the center position. The circuit breaker is also equipped with the Square D exclusive Visi-Trip® indicator (a luminescent, red trip indicator on the front of the circuit breaker).

• Thermal Trip Element: Thermal trip elements are factory calibrated at 40°C ambient (IEC 947-2) and 30°C ambient (IEC 898) temperature.

• Endurance (Switching Operations):

— IEC 947-2: 1,500 full-load operations

— IEC 947-2: 8,500 no-load operations

— IEC 898: 4,000 full-load operations

Figure 41: QOXD Circuit Breaker

0739

3010

Table 21: Thermal-Magnetic Circuit Breakers

QOXD Plug-on Circuit Breakers QOBXD Bolt-on Circuit Breakers

ContinuousAmpere Rating

Circuit Breaker Catalog Number ContinuousAmpere Rating

Circuit Breaker Catalog Number

1-Pole 2-Pole 3-Pole 1-Pole 2-Pole 3-Pole

10 QOXD110 QOXD210 QOXD310 10 QOBXD110 QOBXD210 QOBXD310

16 QOXD116 QOXD216 QOXD316 16 QOBXD116 QOBXD216 QOBXD316

20 QOXD120 QOXD220 QOXD320 20 QOBXD120 QOBXD220 QOBXD320

25 QOXD125 QOXD225 QOXD325 25 QOBXD125 QOBXD225 QOBXD325

32 QOXD132 QOXD232 QOXD332 32 QOBXD132 QOBXD232 QOBXD332

40 QOXD140 QOXD240 QOXD340 40 QOBXD140 QOBXD240 QOBXD340

45 QOXD145 QOXD245 QOXD345 45 QOBXD145 QOBXD245 QOBXD345

50 QOXD150 QOXD250 QOXD350 50 QOBXD150 QOBXD250 QOBXD350

63 QOXD163 QOXD263 QOXD363 63 QOBXD163 QOBXD263 QOBXD363

70 — QOXD270 QOXD370 70 — QOBXD270 QOBXD370

80 — QOXD280 QOXD380 80 — QOBXD280 QOBXD380

100 — QOXD2100 QOXD3100 100 — QOBXD2100 QOBXD3100

Page 28: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved28

Accessories Mounting: Plug-on and bolt-on connection available.

• Handle Tie (QO1HT)The handle tie accessory converts any adjacent 1-pole QO circuit breaker to one independent-trip multi-pole circuit breaker.

• Handle Clamps (HLO-1 and QO1LO)The handle clamp accessories fasten the circuit breaker handle in the ON or OFF position. These handle clamps cannot be padlocked.

— 1-pole circuit breaker handle clamp: QO1LO

— 1-, 2- and 3-pole circuit breaker handle clamp: HLO-1

• Handle Padlock Attachments (QOHPL, QO1PA, QO1HPL and QO1PL)The handle padlock attachments allow padlocking the circuit breaker handles in the ON or OFF position. They are available in two styles: fixed and removable. The fixed style is intended to be a permanent device. The padlock can be removed to resume normal operation. The removable style is intended to be a temporary device and must be removed to resume normal operation. (Padlock is not included.)

— 1-pole circuit breaker removable attachment: QOHPL

— 1-pole circuit breaker fixed attachment: QO1PA

— 2- and 3-pole removable attachment: QO1HPL

— 2- and 3-pole fixed attachment: QO1PL

Lugs

QOXD Circuit BreakerFigure 42: Accessories

0739

3025

0739

3026

0739

3027

0739

3028

QO1HT Handle Tie

HLO-1 Handle Clamp QO1LO Handle Clamp

QO1PA FixedPadlock Attachment

QO1PL FixedPadlock Attachment

QO1HPL RemovablePadlock Attachment

QOHPL RemovablePadlock Attachment

0739

3044

0739

3042

0739

3043

Figure 43: QOXD Circuit Breaker Lug

0739

3016

0739

3022

10–32 A Lugs 45–100 A Lug

(1)

(2)

Table 23: QOXD Circuit Breaker Lugs

ContinuousAmpereRating

Wire Type

Lug Wire Size TemperatureRating

Torque Value

mm2 AWG N•m lb-in

10–32 Al/Cu (1) 2.5–6 (1) #14–#8 60–75°C 4 36

10–32 Cu (only) (2) 2.5–6 (2) #14–#10 60–75°C 4 36

45–100 Al/Cu (1) 25–50 (1) #4–#2/0 75°C 6 50

Page 29: 0739DB9901

0739DB9901R11/03 International Miniature Circuit BreakersJune 2004

© 2000-2004 Schneider Electric All Rights Reserved 29

Dimensions NOTE: QOBX-D circuit breaker dimensions are the same as the QOXD circuit breaker dimensions except as shown.

Figure 44: QOXD Circuit Breaker Dimensions

0739

3036

Dim. A: 3.5 in. (89 mm), 70–100 A for 1-, 2- and 3-poleDim. B: 3.125 in. (79 mm), 45–63 A for 1-, 2- and 3-poleDim. C: 3.0 in. (76 mm), 10–32 A for 1-, 2- and 3-pole

0.94(24)

26°

21°22°

ON Trip

ped

OFF

Res

et

2.25(57)

Dim. A

Dim. B

Dim. C3.00(76)

2.23(57)2.09(53)

1.48(38)1.34(34)

0.75(19)

0.75(19)

0.75(19)

2.91(74)

2.31(59)

2.75(70)

0.73(19)

0.59(15)

0.38(10)

2.92(74)

0.25(6)

0.53(13)

0.53(13)

0.16(24)

Dual Dimensions: in.(mm)

Page 30: 0739DB9901

International Miniature Circuit Breakers 0739DB9901R11/03June 2004

© 2000-2004 Schneider Electric All Rights Reserved30

Figure 45: QOBX-D Circuit Breaker Dimensions

Dual Dimensions: in.(mm)

0.38(10)

0.75(19)

0.75(19)

0.75(19)

2.94(75)

0739

3036