1 of 12 © 2008 W 545 - 12/08 W 545 12/08 tekmarNet ® 4 Thermostat 545 - Wiring Brochure tNt 545 Two Stage Heat, One Stage Cool, One Fan Power: 24 V (ac) ±10% 60 Hz 1.5 VA Relays: 24 V (ac) 2 A G1 G1 Rc Y1 Com S2 S1 tN4 C R Rh1 W1 Rh2 W2 Fan 1 Relay Fan 1 Relay Power Cooling Cool 1 Relay Sensor Common Sensor 2 Sensor 1 tekmarNet 4 Power Neutral Power 24 V (ac) Heat 1 Relay Heat 1 Relay Heat 2 Relay Heat 2 Relay DIP Switch Functions 992-02 Meets Class B: Canadian ICES, FCC Part 15 ® No Power To isolate relay, cut jumper Terminal Functions Y1 Rc G1 G1 R C tN4 S1 S2 Com W1 Rh1 Rh2 W2 Overview Information Brochure Choose controls to match application 1 Application Brochure Design your mechanical applications 2 Layout Brochure Rough-in wiring instructions 3 Wiring Brochure Wiring and installation of specific control 4 Job Record Record settings & wiring details for future reference 6 Data Brochure Control settings and sequence of operation 5 The following brochure describes how to wire the tekmar tekmarNet ® 4 (tN4) thermostat 545. The 545 has outputs for: two heat stages, one cooling stage and one fan. The 545 has inputs for two auxiliary sensors. The wiring of 545 thermostat is simple and cost effective. Table of Contents: Definitions ....................................................................... 2 Rough-In Wiring ............................................................. 2 Remove the Wiring Cover .............................................. 3 Mounting the Thermostat ............................................... 3 Wiring Symbols............................................................... 3 Electrical Drawings ......................................................3-8 Wiring the Thermostat ............................................... 9-10 Troubleshooting the Wiring ........................................... 11 Testing the Wiring .................................................... 11-12 Technical Data .............................................................. 12 DIP Switches 1st Stage Cooling Auxiliary Sensors 1st Stage Fan Wiring Cover 24 V (ac) Power tN4 Network 1st Stage Heating 2nd Stage Heating

Transcript of - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2...

Page 1: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

1 of 12 © 2008 W 545 - 12/08

W 54512/08tekmarNet®4 Thermostat 545

- Wiring Brochure

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®No

Pow

erTo isolaterelay, cutjumper

Terminal Functions

Y1 Rc G1 G1

R

C

tN4

S1

S2

Com

W1Rh1 Rh2 W2

Overview

Information Brochure

Choose controlsto match

application

1 Application BrochureDesign your mechanical applications

2 LayoutBrochureRough-in

wiring instructions

3 WiringBrochureWiring and

installation of specific control

4 JobRecord

Record settings & wiring details for future reference

6DataBrochure

Control settings and sequence of

operation

5

The following brochure describes how to wire the tekmar tekmarNet®4 (tN4) thermostat 545. The 545 has outputs for: two heat stages, one cooling stage and one fan. The 545 has inputs for two auxiliary sensors. The wiring of 545 thermostat is simple and cost effective.

Table of Contents:

Definitions .......................................................................2Rough-In Wiring .............................................................2Remove the Wiring Cover ..............................................3Mounting the Thermostat ...............................................3Wiring Symbols ...............................................................3

Electrical Drawings ......................................................3-8Wiring the Thermostat ...............................................9-10Troubleshooting the Wiring ........................................... 11

Testing the Wiring .................................................... 11-12

Technical Data .............................................................. 12

DIPSwitches

1st StageCooling

AuxiliarySensors

1st StageFan

WiringCover

24 V (ac)Power

tN4Network

1st StageHeating

2nd StageHeating

Page 2: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

© 2008 W 545 - 12/08 2 of 12

Sensor 2

Sensor 1

Fan 1

2 Cond. / 18 AWG

2 Cond. / 18 AWG

2 Cond. / 18 AWG

2 Cond. / 18 AWG

2 Cond. / 18 AWG

4 Cond. / 18 AWG

2nd Stage Heat

1st Stage Cool

Note: When multiple wiresrun to the same equipmentlocation, wiring conductorscan share one wire jacket.

1st Stage Heat24 V (ac) PowertN4 Network

Zone Manager

Zone Manageror 2nd StageEquipment

Defi nitions

The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the product.

– Caution: Refer to accompanying documents.

– Caution: Refer to accompanying documents.

INSTALLATIONCATEGORY II – Local level appliances.

Caution

Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for uses as a primary limit control. Other controls that are

Choose the placement of the thermostats early in the construction process to enable proper wiring during rough-in.

Consider the following:• Interior Wall.• Keep dry. Avoid potential leakage onto the control.

RH 80% to 88°F (31°C), down to 50% from 104 to 122°F (40 to 50°C). Non-condensing environment.

• No exposure to extreme temperatures beyond 32 - 122°F (0 - 50°C).

• No draft, direct sun, or other cause for inaccurate temperature readings.

Rough-In Wiring

• Away from equipment, appliances, or other sources of electrical interference.

• Easy access for wiring, viewing, and adjusting the display screen.

• Approximately 5 ft. (1.5 m) off the finished floor.

Use standard 18 AWG wire for the thermostat power, stages tN4 and sensor connections.

Refer to the diagram below to determine the number of conductors to run from each piece of equipment to the thermostat location.

intended and certified as safety limits must be placed into the control circuit. Do not attempt to service the control. Refer to qualified personnel for servicing. There are no user serviceable parts. Attempting to do so voids warranty and could result in damage to the equipment and possibly even personal injury or death.

Page 3: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

3 of 12 © 2008 W 545 - 12/08

Mounting the Thermostat

If a single or double gang switch box is used, mount the thermostat directly to the box.• Feed the wiring through the openings in the back of the

thermostat.• Use the upper and lower screw holes to fasten the

thermostat to the box.

Remove the Wiring Cover:

To remove the wiring cover:• Place a small slot screwdriver or similar tool into the slot located

on the right side of the thermostat.• While pushing against the plastic tab, lift off the wiring cover.

The electrical drawing examples on the following pages show the 545 in common applications. Choose the drawing that most accurately depicts the components in your system and use that drawing as a guide to aid in wiring your system.

These are only concept drawings, not engineered drawings. They are not intended to describe a complete system nor any particular system. It is up to the system designer to

Electrical Drawings

OR

Wiring Symbols

Dry contact switch. Operates a device. Do not apply power to these terminals. Serious control damage will result.

Powered switch. 24 V (ac), switched output to valve, pump relay etc. tekmarNet®4

Factory jumper.

If a switch box was not used, mount the thermostat directly to the wall.• Feed the wiring through the openings in the back of the

thermostat.• Use screws in the upper and lower screw holes to fasten

the thermostat to the wall. At least one of the screws should enter a wall stud or similar rigid material.

determine the necessary components for and configuration of the particular system being designed including additional equipment isolation relays (for loads greater than the controls specified output ratings) and any safety devices which in the judgement of the designer are appropriate in order to properly size, configure and design that system and to ensure compliance with building and safety code requirements.

StudThermostat

Base

TerminalCover

3 1/4”(83 mm)

Switch Box

Stud

Wall

ThermostatBase

TerminalCover

Page 4: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

© 2008 W 545 - 12/08 4 of 12

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®

No P

ower

To isolaterelay, cutjumper

Terminal Functions

10

9

8

7

6

5

1211 13 14

4 3 2 1

545 tNt

Slab Sensor079

tN4 C R W tN4 C R W

Zone Manager 337

Zone A1 Zone B1

Factory installed jumper connects R to Rh1 (terminals 10 to 11) To isolate Rh1-W1 relay,cut jumper

using same 24 V power supply

Cooling Equipment

1 Stage Cooling1 Stage Fan

Rc Y1 G1

Outdoor Sensor070

Y1 Rc G1

Com

S2

S1

tN4

C

R

Rh1 W1 Rh2 W2

G1

Electrical Application 545 E1

Description:Two Stage Heating (H1 = Radiant, H2 = Fin-tube Convector), One Stage Cooling (C1 = Compressor), One A/C Fan (F1 = C1), Fan Mode = 1.

Legend:Sensor 1 = FloorSensor 2 = Outdoor

Page 5: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

5 of 12 © 2008 W 545 - 12/08

10

9

8

7

6

5

1211 13 14

4 3 2 1

545 tNt

tN4 C R W tN4 C R W

Zone Managers

Factory installed jumper connects R to Rh1 (terminals 10 to 11) To isolate Rh1-W1 relay,cut jumper

Cooling Equipment

Y1 Rc G1 G1

Com

S2

S1

tN4

C

R

Rh1 W1 Rh2 W2

Universal Sensor071

Rc Y1 G1

1 Stage Cooling1 Stage Fan

Indoor Sensor076

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®

No P

ower

To isolaterelay, cutjumper

Terminal Functions

Electrical Application 545 E2

Description:Two Stage Heating (H1 = Radiant, H2 = Fan Coil), One Stage Cooling (C1= Compressor), One HVAC Fan (F1= H2 & C1),Fan Mode = 2.

Legend:Sensor 1 = RoomSensor 2 = Coil

Page 6: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

© 2008 W 545 - 12/08 6 of 12

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®

No P

ower

To isolaterelay, cutjumper

Terminal Functions

10

9

8

7

6

5

1211 13 14

4 3 2 1

545 tNt

tN4 C R W

Zone Manager

Factory installed jumper connects R to Rh1 (terminals 10 to 11) To isolate Rh1-W1 relay,cut jumper

HVAC Equipment

R Y1 G1W

Y1 Rc G1

Com

S2

S1

tN4

C

R

Rh1 W1 W2

Slab Sensor079

1 Stage Heat1 Stage Cooling1 Stage Fan

G1

Rh2

Universal Sensor071

Electrical Application 545 E3

Description:Two Stage Heating (H1 = Radiant, H2 = Furnace), One Stage Cooling (C1 = Compressor), One HVAC Fan (F1 = H2 & C1), Fan Mode = 2.

Legend:Sensor 1 = RemoteSensor 2 = Floor

Page 7: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

7 of 12 © 2008 W 545 - 12/08

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®

No P

ower

To isolaterelay, cutjumper

Terminal Functions

1211 13 14

4 3 2 1

10

9

8

7

6

5

545 tNt

tN4 C R W tN4 C R W

Zone Managers

Factory installed jumper connects R to Rh1 (terminals 10 to 11) To isolate Rh1-W1 relay,cut jumper

A/C Equipment

Y1 Rc G1 G1

Com

S2

S1

tN4

C

R

Rh1 W1 Rh2 W2

Universal Sensor071

Rc Y1 G1

1 Stage Cooling

Indoor Sensor076

VentilationEquipment

G1 G1

Electrical Application 545 E4

Description:Two Stage Heating (H1 = Radiant, H2 = Fin-tube Convector), One Stage Cooling (C1 = Compressor), One Ventilation Fan (F1 = HRV or Vent), Fan Mode = None.

Legend:Sensor 1 = RemoteSensor 2 = Room

Page 8: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

© 2008 W 545 - 12/08 8 of 12

tNt 545Two Stage Heat, One Stage Cool, One Fan

Power: 24 V (ac) ±10% 60 Hz 1.5 VARelays: 24 V (ac) 2 A

G1G1RcY1ComS2S1tN4CRRh1W1Rh2W2

Fan 1 RelayFan 1 RelayPower CoolingCool 1 RelaySensor CommonSensor 2Sensor 1tekmarNet 4Power NeutralPower 24 V (ac)Heat 1 RelayHeat 1 RelayHeat 2 RelayHeat 2 Relay

DIP Switch Functions

992-02

Meets Class B: Canadian ICES, FCC Part 15

®

No P

ower

To isolaterelay, cutjumper

Terminal Functions

10

9

8

7

6

5

1211 13 14

4 3 2 1

545 tNt

Factory installed jumper connects R to Rh1 (terminals 12 to 13) To isolate W1 relay,cut jumper

External Class 2Transformer

24 V (ac)

tN4 C

OthertN4 Thermostat

or Zone Manager

HVAC Equipment

R Y1 G1W

R C

Indoor Sensor076

Y1 Rc G1

Com

S2

S1

tN4

R

Rh1 W1 W2

C

G1

1 Stage Heat1 Stage Cooling1 Stage Fan

Rh2

Duct Sensor083

Electrical Application 545 E5

Description:Two Stage Heating (H1 = Fan Coil, H2 = Furnace), One Stage Cooling (C1 = Compressor), One HVAC Fan (F1 = H1 & H2, C1), Fan Mode = 2.

Legend:Sensor 1 = RoomSensor 2 = Duct

Page 9: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

9 of 12 © 2008 W 545 - 12/08

Wire the tN4 communication to terminals tN4 and C.

If a Zone Manager is used:• Connect the tN4 on the thermostat to the tN4 on the

proper zone of the Zone Manager used for the first stage of heat. The C terminal is already connected.

If a Zone Manager is not used:• Connect the tN4 on the thermostat to the tN4 on another

tN4 device on the same tN4 bus. • Connect the C on the thermostat to the C terminal on

another tN4 device on the same tN4 bus.

tN4 Communication Terminals 8, 9

Wire the first stage of heating to the Heat 1 Relay. (Rh1 - W1)• Use these terminals as a switch to operate the first stage

of heating.If a Zone Manager is used:• Connect W1 on the thermostat to W on the proper

zone of the Zone Manager.

If a Zone Manager is not used:• Determine if the factory jumper must be cut.• When the factory jumper is not cut, W1 is a powered

output that is internally connected to R.• When the factory jumper is cut, Rh1- W1 is an isolated

switch. No power is available from these terminals.

Heat 1 Relay Terminals 11, 12

Wire the second stage of heating to the Heat 2 Relay. (RH2 - W2)• Use these terminals as a switch to operate the second

stage of second.

If a Zone Manager is used:• Connect RH2 to R on the proper zone of the Zone

Manager. Connect W2 to W on the proper zone of the Zone Manager.

If a Zone Manager is not used:• Rh2 - W2 is an isolated switch. No power is available

from these terminals.

Heat 2 Relay Terminals 13, 14

Wire 24 V (ac) to terminals C and R.

If a Zone Manager is used:• Connect C on the thermostat to C on the proper zone

of the Zone Manager. • Connect R on the thermostat to R on the proper zone

of the Zone Manager.

If a 24 V (ac) transformer is used: • Connect C on the thermostat to C on the transformer. • Connect R on the thermostat to R on the transformer.

Power (24 V (ac)) Terminals 9, 10

Zone Manager

Thermostat

Zone Manageror Thermostat

Thermostat

Zone Manager

Thermostat

*Factory installed jumper connects terminals R to Rh1 (To isolate Rh1-W1 relay, cut jumper)

2nd Zone Manager or2nd Stage EquipmentThermostat

Note: This connection is polarity sensitive.

Wiring the Thermostat:

9 C

10 R

tN4 C R W

8 tN4

9 C

10 R tN4 C R W

9 C

10 R

Rh1 W111 12

tN4 C R W

Rh2 W213 14

tN4 C R W

Page 10: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

© 2008 W 545 - 12/08 10 of 12

Wire the first stage of fan to the Fan 1 Relay. (G1 - G1)• G1 - G1 is an isolated switch. No power is available from

these terminals.• Use these terminals as a switch to operate the first stage

of fan.• If the fan is part of the cooling equipment you may be able

tojumper power from Rc (3) to G1 (2) (not shown).

Fan 1 Relay Terminals 1, 2, 3

Thermostat

Wire the first stage of cooling to the Cool 1 Relay. (Rc - Y1)• Rc - Y1 is an isolated switch. No power is available from

these terminals• Use these terminals as a switch to operate the first stage

of cooling.

Cool 1 Relay Terminals 3, 4

Thermostat

The auxiliary sensors are connected to the thermostat on terminals Com, S1 and S2.• • Connect sensor 1 to terminals S1 and Com.• • Connect sensor 2 to terminals S2 and Com.

Do not apply power to terminals 5 - 7, permanent damage to the sensors and / or thermostat will result!

Auxiliary Sensors Terminals 5 - 7

Do

Not

App

ly P

ower

ThermostatUniversal Sensor

OutdoorSensor

To various tekmar sensors

4 3Y1 Rc

3 2 1Rc G1 G1

5 Com

6 S2

7 S1

1st Stage Cooling

1st Stage Fan

Page 11: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

11 of 12 © 2008 W 545 - 12/08

Troubleshooting the Wiring

The following tests are to be performed using standard testing practices and procedures and should only be carried out by properly trained and experienced persons.

A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac), 0 - 2,000,000 Ohms, and testing for continuity is essential to properly test the wiring and sensors.

General

Testing the Wiring

Testing 24 V (ac) Power Supply

1. Remove the front cover from the thermostat.2. Use an electrical test meter to measure (ac) voltage between the R and C terminals. The reading should be 24 V (ac)

+/– 10%.3. Install the front cover.

1. Remove the front cover from the thermostat.2. Disconnect the wires from the relay that is to be

tested.3. Place the thermostat into the test routine.4. Use an electrical test meter and check for continuity

across the relay.• • When the relay’s symbol is displayed in the LCD,

there should be continuity.• • When the relay’s symbol is not displayed in the

LCD, there should be no continuity.5. Reconnect the wires to the relay.6. Repeat steps 2 to 5 for each relay that is to be tested.7. Install the front cover on the thermostat.

Cool 1Fan 1

545 LCD Display Segments

Heat 1 Heat 2

Testing the Relays

To test the sensors, the actual temperature at each sensor location must be measured.

Use a good quality digital thermometer with a surface temperature probe for ease of use and accuracy. Where a digital thermometer is not available, place a spare sensor alongside the one to be tested and compare the readings.

Testing the Sensors

1. Remove the front cover from the thermostat.2. Disconnect the wires from the sensor that is to be

tested.3. Test the sensor’s resistance according to the

instructions in the sensor Data Brochure D 070, D 074, D 079 or D 083.

4. Reconnect the wires.5. Install the front cover on the thermostat.

5 Com

6 S2

7 S1

8 tN4

9 C

10 RRh1 W1 Rh2 W211 12 13 14

4 3 2 1Y1 Rc G1 G1

###

For an explanation on the use of the ‘Test’ sequence or any error messages, refer to the Data Brochure.

Page 12: - Wiring Brochure W 545 - SupplyHouse.coms3.supplyhouse.com/product_files/545-wiring.pdfRh1 Rh2W1 W2 Overview Information Brochure Choose controls to match application 1 Application

tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4(250) 545-7749 Fax. (250) 545-0650Web Site: www.tekmarcontrols.com

Product design, software and literature are Copyright © 2008 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc. 12 of 12 All specifications are subject to change without notice.

Printed in Canada. W 545 - 12/08.

To test the tN4 Network, check the wires for continuity.1. Remove the front cover from the thermostat.2. Disconnect the two wires (tN4 and C) at one end and

connect them together.

Testing the tN4 Network

3. Go to the other end of the wires and disconnect them.4. Using an electrical test meter, check for continuity.5. Reconnect the wires.6. Install the front cover on the thermostat.

Technical Data:

tekmarNet®4 Thermostat 545: Two Stage Heat, One Stage Cool, One Fan

Control Microprocessor PID control; This is not a safety (limit) control

Packaged weight 1.15 lb. (522 g)

Enclosure White PVC plastic

Dimensions 4-1/2” H x 4-3/4” W x 7/8” D (114 x 120 x 22 mm)

Approvals CSA C US, CSA/UL 61010-1, meets Class B: ICES and FCC Part 15

Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C)

RH 80% to 88°F (31°C), down to 50% from 104 to 122°F (40 to 50°C)

Altitude <6560 feet (2000 m), Installation Category II, Pollution Degree 2

Power supply 24 V (ac) ± 10% 60 Hz, 1.5 VA, NEC / CEC Class 2

W1 Relay 24 V (ac) 2 A

W2 Relay 24 V (ac) 2 A

Y1 Relay 24 V (ac) 2 A

G1 Relay 24 V (ac) 2 A

Sensors: NTC thermistor, 10 k @ 77°F (25°C ± 0.2°C) ß = 3892

– Included None

– Optional tekmar type # 070, 071, 072, 073, 076, 077, 078, 079, 083, 083, 084

Technical Data

The installer must ensure that this control and its wiring are isolated and / or shielded from strong sources of electromag-netic noise. Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception, which is determined by turning the control off and on, the user is encouraged to try to correct the interference by re-orientating or relocating the receiving antenna, relocating the receiver with respect to this control, and / or connecting the control to a different circuit from that to which the receiver is connected.

Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.