Introduction to MV Introduction to MV EQUIPMENTSEQUIPMENTS
Prepared by Triyanto Limantoro
Introduction to MV equipments Introduction to MV equipments Basic Magnitude in MV switchgear :
� Voltage
� Current
� Frequency
� Short Circuit power
� Voltage, rated current and rated frequency:
� Single line diagram / Specification
Schneider Electric 2- Industrial Division Σ July 2009
� Single line diagram / Specification
� to define the dielectric withstand of the components such
as: CB, insulators, CTs,VTs,etc
� Short circuit power :
� to choose various parts of a switchgear: withstand
against temperature rises and electro dynamic force.
VOLTAGE
� Operating/Service Voltage U (kV):
� Voltage across the equipment terminals.
� example : 22kV, 3.3kV,…
� Rated Voltage Ur (kV) : (nominal Voltage)
� Max rms (root mean square) value of the voltage that
Schneider Electric 3- Industrial Division Σ July 2009
� Max rms (root mean square) value of the voltage that
equipment can withstand under normal operating conditions.
� Rated voltage (Ur) is always greater than the operating voltage.
� Rated voltage associated with an insulation level
� Examples : Rated voltage 7.2kV, 17.5kV, 12kV and 24kV
VOLTAGE
�Insulation level Ud (kV rms, 1 minute) and Up (kV peak)
Definition: the electric withstand of equipment to switching under operation
over voltages and lightning impulse.
� Ud: Over voltage due to of internal switchgear, which accompany all
changes in the circuit: opening/closing CB or Switch, breakdown or shorting
across an insulator, etc…
Schneider Electric 4- Industrial Division Σ July 2009
� Simulated in laboratory/factory by the power-frequency withstand voltage for 1 minute.
� Example : Ur : 24kV � Ud : 50kVrms/1 min.
� Up: over voltage of external switchgear or atmospheric originoccur when lightning falls on or near a transmission line.
� Simulated in laboratory by the lightning impulse withstand voltage.
� Examples : Ur : 24kV � Up : 125kVp
� IEC Standard Voltage
20 7.2 60
Schneider Electric 5- Industrial Division Σ July 2009
20 7.2 60
12
17.5
24
36
Ur UpUd
170
12550
70
95
7528
38
1.2/50us 50Hz
� Standard
Schneider MV equipment is conformity with list 2 of the series 1
table IEC 60 071 and 60 298.
Rated
Voltage
Rated power-
frequency
withstand
voltage
Normal
operating
voltage
kV rms 1minute kV rms kV rms
list 1 list 2
Rated lightning
impulse
withstand voltage
1.2/50us 50Hz
.
kV peak
Schneider Electric 6- Industrial Division Σ July 2009
� Insulation level apply to MV swgr at altitudes of less than 1000
meters, 20 deg.C, 11 g/m3 humidity and press of 1.013 mbar.
� Above this ,derating should be considered.
list 1 list 2
7.2 40 60 20 3.3 to 6.6
12 60 75 28 10 to 11
17.5 75 95 38 13.8 to 15
24 95 125 50 20 to 22
36 145 170 70 25.8 to 36
Derating of the switchgear related to the altitude
Schneider Electric 7- Industrial Division Σ July 2009
� Altitude 2500 m ���� k is equal to 0.85
� Impulse withstand of the switchboard must be :125/0.85 = 147.05 kV
� Power frequency withstand 50 Hz must be 50/0.85 = 58.8 kV
2500
� Standard
Insulation level corresponds to a distance in air which
guarantees withstand without a test certificate.
Rated
Voltage
Rated power-
frequency
withstand
voltage
Distance live
to earth in air
.
Rated lightning
impulse
withstand voltage
1.2/50us 50Hz
.
Schneider Electric 8- Industrial Division Σ July 2009
� lower than this distance, we need simulation/test in the
laboratory to check lightning impulse withstand voltage. Or using
additional insulation material such as heatshring, screen,etc
kV rms 1 minute kV rms cm
7.2 20 9
12 28 12
17.5 38 16
24 50 22
36 70 32
95
125
170
.
kV peak
60
75
Current
The rms value of current that equipment can withstand
when current flow without exceeding the temperature riseallowed in standards.
Temperature rises authorized by the IEC according to the
type of contacts.
Schneider Electric 9- Industrial Division Σ July 2009
OPERATING CURRENT : I (Ampere)
� Calculate from the load power.
� Actual current passes through the equipment.
• generally customer provide its value
• calculate if we know the power of the load
Exercise:
� A switchboard with a 630kW motor feeder and a 1250kVA
ηηηη
Schneider Electric 10- Industrial Division Σ July 2009
x’mer feeder at 5.5kV, cos ϕ = 0.85 and motor efficiency ηηηη =
90%
� How many ampere the operating current of Transformer
and Motor?
� In motor = 86.44 A
� In Trafo = 131.22AThe answer
Short Circuit Current
� Short circuit power depends on :
� Network configuration
(exp: single source, parallel source, network, generators)
� Impedance of each equipments or devices.
(exp: lines, cables, transformers, motors)
� Power short circuit is maximum power that network or source can deliver
Schneider Electric 11- Industrial Division Σ July 2009
� Power short circuit is maximum power that network or source can deliver
to an installation during a fault,
� expressed in MVA or in kA rms at operating voltage.
Exp: Psc = 500MVA @ 20KV or Isc : 31.5kA rms
� Determination of the short-circuit power requires analysis of the power
flows feeding the short circuit in the worst possible case.
�What is short circuit level for 500MVA @ 20KV ?
14.43kAAnswer
Short Circuit Current
D
E
Schneider Electric 12- Industrial Division Σ July 2009
� Isc at main busbar D when bustie D4 close?
� Isc at the outgoing feeder E?
E
Minimum short-circuit current: Isc (kA rms.)
� Corresponds to a short circuit at one end of the fault point.
� This value allows us to choose the setting of thresholds for over
current protection devices(F50/F51) and fuses
�Example: Isc: 23 kA rms
Schneider Electric 13- Industrial Division Σ July 2009
source load
Ith Isc
Maximum short-circuit current: Ith (kA rms. 1 s or 3 s)
� Corresponds to a short circuit in upstream terminals of the
switching device,
� express in : kA for 1s or 3 s
� thermal withstand of the equipment = Ith
� Example: Ith: 31.5 kA rms. 1 s or 3 s
Schneider Electric 14- Industrial Division Σ July 2009
source load
IscIth
Peak Value of the max. short circuit current (kA peak)
� Value of the initial peak in the transient period
� I dynamic (kA peak) is equal to :
� 2.5 x Isc at 50 Hz (IEC)
� 2.6 x Isc at 60 Hz (IEC)
� 2.7 x Isc (ANSI) times the short circuit current calculated at a given
point in the network.
Schneider Electric 15- Industrial Division Σ July 2009
� Example: Isc : 25kA � Idyn: 2.5 x 25= 63.75kA peak (IEC 60 056)
� Idyn: 2.7 x 25= 67.50kA peak (ANSI), 25kA at
a given point
� This value determines the breaking capacity and making (closing) capacity of CBs and Switches, as well as the electro dynamic withstand of
busbars and switchgear.
� Isc value based on IEC: 8 – 12.5 – 16 – 20 – 25 – 31.5 – 40- 50 kA rms
Frequency fr (Hz)
� 2 different frequency use in the world:
50 Hz in Europe
60 Hz in the USA
several countries use both frequencies indiscriminately
� Instrument Voltage Transformer rated 50 can operate at 60Hz
� Instrument Current Transformer rated 50 can operate at 60Hz.
Schneider Electric 16- Industrial Division Σ July 2009
� Instrument Current Transformer rated 50 can operate at 60Hz.
But CT with rated 60Hz can not be operated at 50Hz.
Electrical network can be disconnect, protect and control by using AIS SWITCHGEAR :
AIR INSULATED SWITCHGEAR (AIS)
METAL enclosed switchgear divided 3 types:
� Metal clad : example: MC set,NEX
� Compartmented : example: SM6
� Block : example Interface/joggle cubicle.
Introduction to MV equipments Introduction to MV equipments
Schneider Electric 17- Industrial Division Σ July 2009
� Block : example Interface/joggle cubicle.
DIFFERENT ENCLOSURE TYPE (AIS)
metal clad
LSC2B
Schneider Electric 18- Industrial Division Σ July 2009
compartment
Block type
LSC2A
LSC1
GIS
MV Switchgear to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity
Loss of Service Continuity
Class (LSC)
• Architecture based on “safe compartment access”
LSC 2A
• Safe access to compartment
• With power flow in busbar and the other units
• MV Cables must be earthed
• Safe access to compartment
LSC 2B
Maintainability of defined parts
Maintainability of one functional unit allowing normal service of the remaining units of the switchboard (busbar in a separate compartment)
Several levels of service continuity during maintenance
Schneider Electric 19- Industrial Division Σ July 2009
compartment
• With power flow in busbar and the other units
• MV Cable in separate compartment
• Cable of unit under maintenance can remain energized
• Metal enclosed not of LSC2 class
LSC 1
defined parts with no need of cable disconnection (separate cable compartment)
MOTORPACTMOTORPACT
MCSET or NEXMCSET or NEX
Partition Class PM
• All partitions and shutters of safe access compartment shall be metallic with some current carrying capacity
“Metal enclosed” compliant during maintenanceApplicable mainly to withdrawable system
Partition ClassI or M
• Classification based on electrical field presence in safe access compartment
Personnel comfort during maintenance
MV Switchgear to IEC 62271-200 Fully enclosed in metal enclosure and having some current carrying capacity
MCset or PIXMCset or PIX
Schneider Electric 20- Industrial Division Σ July 2009
Partition Class PI
• Partitions or shutters may be partially or totally of insulating material
Electrical and mechanical safety according to IEC 60466 or 60137
3.110 Shutter
Part of metal-enclosed switchgear and controlgear that can be moved from a position where it permits contacts of a removable part, or moving contact of a disconnector to engage fixed contacts, to a position where it becomes a part of the enclosure or partition shielding the fixed contacts.
MotorpactMotorpact
Definition
MV Switchgear to IEC 62271-200 Fully enclosed in metal enclosure and having current carrying capacity
IAC classified
• No projection of parts towards accessible sides
• No ignition of indicators
Safety in case of internal fault during service conditionDemonstrated by type tests(completely defined by the standard)
Internal Arc ClassIAC
• Classification based on consequences of internal arc on personnel safety
Personnel safety in case of internal arc
IAC not classifiedAccessibility TypesMotorpactcomplies with
Schneider Electric 21- Industrial Division Σ July 2009
IAC not classified
• No tests performed to assess behavior of enclosure under arc conditions
• A : restricted to authorized personnel only.
• B : unrestricted, including general public.
• Enclosure Identification code: F - for Front side
• L L - for Lateral sideR - for Rear side
Accessibility Typescomplies with AFLR type
SWITCHGEAR FUNCTION
Schneider Electric 22- Industrial Division Σ July 2009
STANDARDS DISTRIBUTION FEEDERS (AIS)
The MCset range meets the following international standards:
62271-1 : clauses common to high voltage switchgear
62271-200 : metal-enclosed switchgear for alternating current at
rated voltages of between 1 and 52 kV
IEC 62271-100 : high voltage alternating current circuit breakers
IEC 60470 : high voltage alternating current contactors
IEC 60265-1 : high voltage switches
IEC 60282-2 : high voltage fuses
Schneider Electric 23- Industrial Division Σ July 2009
IEC 60282-2 : high voltage fuses
IEC 60271-102 : alternating current disconnectors and earthing
switches
IEC 60255 : measurement relay and protection unit for the
applicable parts
IEC 60044-1 : current transformers
IEC 60044-2 : voltage transformers
IEC 60044-8 : electronic current transformers (for LPCT).
STANDARDS MOTOR STARTER / MCC (AIS)
Motorpact meets IEC standardsIEC 62271-1 High-voltage switchgear and controlgear – Part 1: CommonspecificationsIEC 62271-200 AC metal-enclosed switchgear and controlgear for ratedvoltages above 1 kV and up to and including 52 kVIEC 60470 High voltage alternating current contactors and contactorbased motorstartersIEC 60282-1 High voltage fuses: limiting fusesIEC 62271-102 Alternating current disconnectors and earthing switchesIEC 60044-1 Instrument transformers - Part 1: current transformersIEC 60044-2 Instrument transformers - Part 2: inductive voltage transformers
Schneider Electric 24- Industrial Division Σ July 2009
IEC 60044-2 Instrument transformers - Part 2: inductive voltage transformersIEC 60044-8 Instrument transformers - Part 8: electronic current transformersIEC 61958 High-voltage prefabricated switchgear and controlgearassemblies - Voltage Presence Indicating SystemsIEC 60076-11 dry-type transformers
Other specificationsIACS International Association of Classification Societies
STANDARDS DISTRIBUTION FEEDERS (GIS)
Schneider Electric 25- Industrial Division Σ July 2009
SF6 and Vacuum
�SF6 is used for insulation and breaking functions:
�That is the only used technique for all voltages, in
secondary distribution (switches, RMU) and in high voltage
up to 800 kV.
Schneider Electric 26- Industrial Division Σ July 2009
�Vacuum is limited to the breaking function and only in medium voltage (mainly up to 36 kV):
�The vacuum bottles have dielectric weakness
(NSDD - contact surface state).
SF6 and Vacuum are two modern breakingtechniques used in Medium Voltage.
�They ensure the continuity of service expected by the users together with complete safety.
�The SF6 technique has differentiating advantages :
Schneider Electric 27- Industrial Division Σ July 2009
for specific applications (capacitor banks,
motor breaking, generator , etc …),
for particular network operating modes (e.g. on line
monitoring of breaking medium).
Equivalent reliability of SF6 and Vacuum CB ’s
�Excellent reliability for both techniques:
�experience built up by manufacturers and users,
�upgrading and optimization of equipment through the use of
modern development methods (CAD-CAM, FMECA, …)
�mastering of « sensitive » components such as operating
Schneider Electric 28- Industrial Division Σ July 2009
�mastering of « sensitive » components such as operating
mechanism and tightness.
�The actual failure rate on the installed 180 000 circuit-breakers throughout the world is :
�4/10 000 per year ==> MTBF ~ 2800 years.
Minimum maintenance for SF6 and Vacuum installed circuit-breakers
�SF6 pole-units and vacuum enclosures:
�are sealed for life,
�are maintenance free,
�have mechanical and electrical endurance that is much
greater than actual needs (several tens of times Isc,
10,000 Ir).
Schneider Electric 29- Industrial Division Σ July 2009
10,000 Ir).
�Operating mechanism:
�is based on the same technology, whatever the technique,
and is a component with high mechanical endurance
(10,000 operations minimum).
�The lifetime of the SF6 Merlin Gerin circuit-breakers is 30 years.
Installation security: assets of SF6.
�On-line monitoring of the breaking medium ispossible thanks to a pressure switch .
Schneider Electric 30- Industrial Division Σ July 2009
�All the ratings at the pressure switch level.
Installation security: assets of SF6.
�No overvoltage having detrimental effect on the equipment:
�No reignition nor restrike, during the switching of capacitors
banks.
�No or weak overvoltage during the switching of inductive
loads
Schneider Electric 31- Industrial Division Σ July 2009
loads
(unloaded transformer, starting motor).
�No NSDD ’s during breaking, nor multiple prestrikes in
making.
�The use of vacuum circuit-breakers requires to have overvoltage protection (ZnO-RC).
U source side
U load side
Schneider Electric 32- Industrial Division Σ July 2009
SF6 circuit-breaker (12kV)
U source side
U load side
Schneider Electric 33- Industrial Division Σ July 2009
45 kV
Vacuum circuit-breaker (12kV)
Installation security: assets of SF6.
�Rated characteristics maintained at 0 bar gauge SF6 pressure with breaking once at 80 % or 100 % of the maximum breaking capacity and a dielectric withstand atleast 80 % of the insulation level, for example:
Schneider Electric 34- Industrial Division Σ July 2009
�SF1 circuit-breaker at 0 bar gauge: 25 kA at 24 kV
125 kV BIL.
Safety of people related to the switchboards which the circuit breakers are integrated.
�Preponderance of the toxicity of copper vapours present in all electrical equipment in the event of internal arcing, whatever breaking technique.
�The information is in the IEC report 1634:
Schneider Electric 35- Industrial Division Σ July 2009
�The information is in the IEC report 1634:
Use and handling of SF6 in high voltage switchgear and controlgear.
SF6 or vacuum which one is the best technology in circuit breakers to the user’s view point ?
• Both can be safe, long lasting, adapted to the utilisation.• It all depends upon who is the manufacturer.• You can be confident when he is Schneider (Merlin Gerin-MG) who
A COMPARISON OF SF6 AND VACUUM CIRCUIT BREAKERS
Schneider Electric 36- Industrial Division Σ July 2009
is the most experienced maker of MV switchgear with SF6 and an expert in vacuum.•But the technologies have different features and merits which are compared in the attached document.
Schneider Electric 37- Industrial Division Σ July 2009
Schneider Electric 38- Industrial Division Σ July 2009
Schneider Electric 39- Industrial Division Σ July 2009
DIELECTRIC WITHSTAND
depends on 3 parameters:
� The Dielectric strength of the medium
� The Shape of the parts
� The distance :
� ambient air between the live parts
Schneider Electric 40- Industrial Division Σ July 2009
� ambient air between the live parts
� insulating air interface between the live parts
Dielectric Strength of air depends on ambient conditions:
� Pollution � reducing the insulating performance by a
factor <10. Pollution may occur from external dust, lack of cleanliness,
breaking down of an internal surface, pollution & humidity causes
electrochemical conduction which will worsen discharge phenomena.
� Condensation � reducing the insulating performance by a
. factor 3
� Pressure � related to the altitude, derating performance.
� Humidity � % of humidity can cause a change in insulating
Schneider Electric 41- Industrial Division Σ July 2009
� Humidity � % of humidity can cause a change in insulating
performances. (liquid always leads to a droop in performance)
� Temperature � temp. increases can cause decreases insulation performance. Thermal shock can be the cause of the micro
fissuration which can lead very quickly to insulator breakdown. Insulator
expands by 5 and 15 times more than a conductor.
� The Shape of the parts
� It is essential to eliminate any “peak” effect to avoid disastrous effect on the impulse wave withstand in particular and on the surface ageing of insulator.
� Air Ionization � Generate Ozone � Breakdown of insulator surface or skin
� Distance between parts
(there is ambient air between live parts)
� For installations sometime we can not test under impulse conditions, the table below gives the minimum distance to comply with in air either phase to earth or phase to phase .
�The table based on IEC 71-2 according to the rated lightning impulse withstand voltage and these distances guarantee correct withstand for unfavorable configurations: altitude < 1 000 m.
Schneider Electric 42- Industrial Division Σ July 2009
configurations: altitude < 1 000 m.
Note : the table above does not include any increase which could be required to take account of design tolerances, short circuit effects, wind effects, operator safety, pollution, etc.
INSTRUMENT TRANSFORMER
Schneider Electric 43- Industrial Division Σ July 2009
Schneider Electric 44- Industrial Division Σ July 2009
Schneider Electric 45- Industrial Division Σ July 2009
Metering transformer applicationsInstrument transformers are necessary to provide values
that can be used by these devices which can be analogue
devices, digital processing units with a microprocessor,
after analogue/digital conversion of the input signal (e.g.:
Sepam or Power Logic System).
Current transformer
Schneider Electric 46- Industrial Division Σ July 2009
Current transformers (CT) meet standard IEC 60044-1.
InsulationCharacterized by the rated voltage:
� of the insulation, which is that of the installation (e.g.: 24 kV)
� of the power frequency withstand 1 min (e.g.: 50 kV)
� of the impulse withstand (e.g.: 125 kV).
� Rated frequency
Characteristics Of Current Transformer:Based on standard IEC 60044-1.
Schneider Electric 47- Industrial Division Σ July 2009
� Rated frequency50 or 60 Hz.
� Rated primary current (Ipn)Rms value of the maximum continuous primary current.
Usual values are 25, 50, 75, 100, 200, 400, 600 A.
Rated secondary current (Isn)This is equal to 1 A or 5 A.
� Rated transformation ratioKn = I rated primary / I rated secondary (e.g.: 100 A / 5 A)
� Short-time thermal current Ith - 1 second
Characteristics Of Current Transformer:Based on standard IEC 60044-1.
Schneider Electric 48- Industrial Division Σ July 2009
� Short-time thermal current Ith - 1 secondThis characterizes the thermal withstand under short circuit conditions
for 1 second.
It is expressed in kA or in a multiple of the rated primary current (e.g.: 80
x Ipn) for 1 second.
The value for a duration that is different to 1 second is given by:
I’th =SQRT ( Ith^2 / t ) � Ith : 16kA/1 sec, I’th for 2 sec : SQRT (16^2/2) = 11.31kA/2sec
Characteristics Of Current Transformer:Based on standard IEC 60044-1.
Short-time thermal current peak valueThis value is standardized from Ith - 1 s at:
� IEC: 2.5 Ith at 50 Hz and 2.6 Ith at 60 Hz
� ANSI: 2.7 Ith 60 Hz.
Accuracy load
Schneider Electric 49- Industrial Division Σ July 2009
Accuracy loadThe value of the load on which is based the metered current accuracy
conditions.
Accuracy power PnApparent power (VA) that the CT can supply on the secondary for the
rated secondary current for which the accuracy is guaranteed
(accuracy load).
Usual values 5 - 7.5 - 10 - 15 VA (IEC).
Accuracy classDefines the limits of error guaranteed on the transformation ratio and
on the phase
shift under the specified conditions of power and current. Classes 0.5 and 1 are used
for metering class P for protection.
Characteristics Of Current Transformer:Based on standard IEC 60044-1.
Schneider Electric 50- Industrial Division Σ July 2009
Current error ε (%)Error that the transformer introduces in the measurement of a current when the transformation ratio is different from the rated value.
Phase shift or phase error ψ (minute)Difference in phase between the primary and secondary currents, in angle minutes
Characteristics Of Current Transformer:Based on standard IEC 60044-1.
Schneider Electric 51- Industrial Division Σ July 2009
magnetization curve (for a given temperature and frequency).
This magnetization curve (voltage Vo, magnetizing current function Im) can be divided into 3 zones:1 - non-saturated zone: Im is low and the voltage Vo (and therefore Is) increases virtually proportionately to the primary current.2 - intermediary zone: there is no real break in the curve and it is difficult to situate a precise point corresponding to the saturation voltage.3 - saturated zone: the curve becomes virtually horizontal; the error in transformation ratio is high, the secondary current is distorted by saturation.
Schneider Electric 52- Industrial Division Σ July 2009
Schneider Electric 53- Industrial Division Σ July 2009
Metering CTThis requires good accuracy (linearity zone) in an area close to the normal service current; it must also protect metering devices from high currents by saturating earlier
Protection CT
Schneider Electric 54- Industrial Division Σ July 2009
Protection CTThis requires good accuracy at high currents and will have a higher precision limit (linearity zone) for protection relays to detect the protection thresholds that they are meant to be monitoring.
Schneider Electric 55- Industrial Division Σ July 2009
SafetyThe CT secondary is used at low impedance (virtually in short circuit).
The secondary circuit should never be left open, since this would
mean connecting across an infinite impedance. Under these conditions,
hazardous voltages for personnel and equipment may exist across the
terminals.
Terminal markingCT connection is made to the terminals identified according to the IEC:
� P1 and P2 on the MV side
� S1 and S2 on the corresponding secondary. In the case of a double
output, the first output is identified by 1S1 and 1S2, the second by 2S1
Schneider Electric 56- Industrial Division Σ July 2009
output, the first output is identified by 1S1 and 1S2, the second by 2S1
and 2S2.
Schneider Electric 57- Industrial Division Σ July 2009
CT for meteringAccuracy class� A metering CT is designed to send as accurate an image as possible of
currents below 120% of the rated primary.
� Accuracy guaranteed from load 25% and 100% of the accuracy power.
� IEC standard 60044-1 determines the maximum error:
Schneider Electric 58- Industrial Division Σ July 2009
CT for metering
Safety factor: FSIn order to protect the metering device connected to the CT from high currents on the MV side, instrument transformers must have early saturation characteristics.The limit primary current (Ipl) is defined for which the current error in the secondary is equal to 10%. The standard then defines the Safety Factor FS.:
Schneider Electric 59- Industrial Division Σ July 2009
This is the multiple of the rated primary current from which the error
becomes greater than 10% for a load equal to the accuracy power.
CT for protection� Accuracy class
A protection CT is designed to send as reliable an image as possible of the fault current (overload or short circuit).
� IEC standard 60044-1 determines the maximum error for each accuracy class in the
phase and in the module according to the indicated operating range.
Schneider Electric 60- Industrial Division Σ July 2009
For example for class 5P the maximum error is y ± 5% at the accuracy limit current
and y ± 1% at the rated current.
Standardized classes are 5P and 10P. The choice depends on the application.
The accuracy class is always followed by the accuracy limit factor.
Accuracy limit factor: FLPA protection CT must saturate at sufficiently high currents to enable sufficient
accuracy in the measurements of fault currents by the protection device whose
operating threshold can be very high.
The limit primary current (Ipl) for which current errors and phase shift
Schneider Electric 61- Industrial Division Σ July 2009
The limit primary current (Ipl) for which current errors and phase shift
errors in the secondary do not exceed values in the table below
The standard then defines the accuracy limit factor FLP.
In practice this corresponds to the linearity limit (saturation curve) of the CT.
Schneider Electric 62- Industrial Division Σ July 2009
� If ϕ and η are not known, use
approx value cos ϕ: 0.8 and η =
0.8
� Capacitor Feeder :Derating
coefficient of 30% to take into
account of temp. rise due to
capacitor harmonic
Schneider Electric 63- Industrial Division Σ July 2009
� Bus section
The greatest value of current that
can flow in the bus section on a
permanent basis.
Ips = In bus
� Standardized values :
10-12.5-15-20-25-30-40-50-60-75-80 and their multiples and factors
� CT must be able to withstand 120% the rated current
CURRENT TRANSFORMER
Example:
A thermal protection device for a motor has a setting range of between 0.6 and 1.2 x Ir (CT).
In order to protect this motor, the required setting must correspond to the motor’s rated current.
� If we assume that Ir for the motor = 45 A, the required setting is therefore: 45A
� If we use a 100/5A CT, the relay will never see 45A , because: 100A x 0.6 = 60A > 45A.
� If we use a 75/5A CT, the relay will see , 75 x 0.6 = 45 A
� The range of setting will be: 0.6 < 45/75 < 1.2 . This CT is suitable.
RATED THERMAL SHORT CIRCUIT CURRENT (Ith)
Schneider Electric 64- Industrial Division Σ July 2009
RATED THERMAL SHORT CIRCUIT CURRENT (Ith)
� Value of the installation max. short circuit current and the duration 1s or 3 s.
� Each CT must be able to withstand short circuit current both thermally and dynamically until the
fault is effectively cut off.
� Ith = Ssc / (U x V3), Ssc = power short circuit MVA
� When the CT is installed in a fuse protected, the Ith = apprx. 80 Ir.
RATED SECONDARY CURRENT:
� Local use or inside switchgear Isr = 5A
� Remote use or long distance Isr = 1A
Schneider Electric 65- Industrial Division Σ July 2009
INSIDE MV CURRENT TRANSFORMER
Schneider Electric 66- Industrial Division Σ July 2009
Schneider Electric 67- Industrial Division Σ July 2009
Schneider Electric 68- Industrial Division Σ July 2009
Schneider Electric 69- Industrial Division Σ July 2009
� RATED PRIMARY VOLTAGE (Upr)
� According to the design, VT will be connected :
� Phase to earth 22.000V/V3 / 110V/V3, where Upr = U/V3
� Phase to phase 22.000 / 110V, where Upr = U
� RATED SECONDARY VOLTAGE (Usr)
� Phase to phase VT, rated secondary voltage : 100V or 110 V
� Phase to Ground VT, rated secondary voltage : 100/V3 or 110V/V3
Schneider Electric 70- Industrial Division Σ July 2009
� RATED OUTPUT
� The apparent power output that VT can supply the secondary circuit when connected at rated primary voltage and connected to the nominal load.
� It must not introduce any error exceeding the values guaranteed by the accuracy class . (S = V3. U. I in 3 phase circuit)
� Standardized value are:
10-15-25-30-50-75-100-150-200-300-400-500 VA
ACCURACY CLASS
� The limits of errors guaranteed in terms of transformation ratio and phase under the specified conditions of both power and voltage.
PROTECTION ACCORDING TO IEC 60 186
Schneider Electric 71- Industrial Division Σ July 2009
PROTECTION ACCORDING TO IEC 60 186
� Classes 3P and 6P (but in practice only class 3P is used)
� The accuracy class is guaranteed for values :
� of voltage of between 5% of the primary voltage and the max. value of this voltage which is the product of the primary voltage and the rated voltage factor (kT x Upr)
� For secondary load between 25% and 100% of the rated output with a power factor of 0.8 inductive.
Schneider Electric 72- Industrial Division Σ July 2009
INSIDE MV VOLTAGE TRANSFORMER
Schneider Electric 73- Industrial Division Σ July 2009
� INDEX PROTECTION
� Protection of people against direct contact and protection of
equipment against certain external influences.
� Requested by international standard for electrical installations
and products (IEC 60 529)
INDEX PROTECTION OF THE SWGR
Schneider Electric 74- Industrial Division Σ July 2009
and products (IEC 60 529)
� The protection index is the level of protection provided by an
enclosure against access to hazardous parts, penetration of
solid foreign bodies and of water.
�The IP code is a coding system to indicate the protection
index.
INDEX PROTECTION- first index
Schneider Electric 75- Industrial Division Σ July 2009
INDEX PROTECTION: second index
Schneider Electric 76- Industrial Division Σ July 2009
INDEX PROTECTION : third index
Definitions
� The protection mentions correspond to impact energy levels expressed in joules
� hammer blow applied directly to the equipment
� impact transmitted by the supports, expressed in terms of vibrations therefore in terms of frequency and acceleration
� The protection indices against mechanical impact can be checked by different types of hammer: pendulum
Schneider Electric 77- Industrial Division Σ July 2009
be checked by different types of hammer: pendulum hammer, spring-loaded hammer or vertical free-fall hammer (diagram below).
PROTECTION INDEX: third index
Schneider Electric 78- Industrial Division Σ July 2009