Lv and Mv Switchgear 10

42
10 LV&MVSwitchgear #10

description

Lv and Mv Switchgear

Transcript of Lv and Mv Switchgear 10

Page 1: Lv and Mv Switchgear 10

10LV&MVSwitchgear #10

Page 2: Lv and Mv Switchgear 10

Equipment behaviourd i h i iduring short‐circuits

1. Passive equipment

2 Active equipment2. Active equipment

Page 3: Lv and Mv Switchgear 10

M M M M

Page 4: Lv and Mv Switchgear 10

Active equipmentActive equipment

• This category comprises the equipment designed toThis category comprises the equipment designed toclear short‐circuit currents, i.e. circuit breakers andfuses.

• This property is expressed by the breaking capacityp p y p y g p yand, if required, the making capacity when a faultoccurs.

Page 5: Lv and Mv Switchgear 10

12

77

2

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

‐3

‐8

Current Limiting                    Non‐current Limiting 

Page 6: Lv and Mv Switchgear 10

12

77

2

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

‐3

‐8

Current Limiting                    Non‐current Limiting 

Page 7: Lv and Mv Switchgear 10

12

77

2

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

‐3

‐8

Current Limiting                    Non‐current Limiting 

Page 8: Lv and Mv Switchgear 10

Making Current

12

7

2

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

‐3

0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1

‐8

Page 9: Lv and Mv Switchgear 10

LV Circuit Breaker TypesLV Circuit Breaker Types

• Air Circuit Breaker (ACB)• Air Circuit Breaker (ACB)

• Molded Case Circuit Breaker (MCCB)

• Miniature Circuit Breaker (MCB)

Page 10: Lv and Mv Switchgear 10

Circuit Breaker TypesCircuit Breaker Types

• ACB: 630 to 6000 A, motorizableACB:  630 to 6000 A, motorizable

• MCCB: up 1600A, motorizable

• MCB (below 100A)• MCB (below 100A)

Page 11: Lv and Mv Switchgear 10

LV Circuit Breakers 

ACB

MCCB

M M M M

MCCBACB

M M M M

Page 12: Lv and Mv Switchgear 10

Air Circuit BreakerAir Circuit Breaker

Page 13: Lv and Mv Switchgear 10

Molded Case Circuit BreakersMolded Case Circuit Breakers

• This is the external cover of the MCCB, which houses,all the sensing and operating components.

• Resin/glass‐fiber materials, with high dielectricstrength.

• It is to be noted that the case is moulded and assuch, it is not possible to access the internalpcomponents in case of any failures and it will benecessary to replace the complete MCCB under thosecircumstancescircumstances.

Page 14: Lv and Mv Switchgear 10

Miniature Circuit BreakersMiniature Circuit Breakers

• The miniature circuit breakers are similar to mouldedThe miniature circuit breakers are similar to mouldedcase circuit breakers but as their name implies, theseare smaller in size and are mostly used for currentratings below 100 A.

• These are normally available in single pole(SP), single pole neutral (SPN), double pole( ) l l ( ) l l l ( ) d(DP), triple pole (TP), triple pole neutral (TPN) andfour pole (FP) versions.

Page 15: Lv and Mv Switchgear 10
Page 16: Lv and Mv Switchgear 10

LV Circuit Breaker CurrentsLV Circuit Breaker Currents

• Rated uninterrupted current, Iup ,

• Rated current, In

• Rated ultimate short‐circuit breaking capacity, Icug p y,• Rated service short‐circuit breaking capacity, Ics• Rated short‐circuit making capacity, Icm

• Rated short‐time withstand current Icw (1sec. , 3 sec.)

Page 17: Lv and Mv Switchgear 10
Page 18: Lv and Mv Switchgear 10

In, IuIn, Iu

Page 19: Lv and Mv Switchgear 10

LV Circuit Breaker CurrentsLV Circuit Breaker Currents

• Rated uninterrupted current, Iup ,

• Rated current, In

• Rated ultimate short‐circuit breaking capacity, Icug p y,

• Rated service short‐circuit breaking capacity, Ics

• Rated short‐circuit making capacity, IcmRated short circuit making capacity, Icm

• Rated short‐time withstand current Icw (1sec. , 3 sec.)Rated short time withstand current Icw (1sec. , 3 sec.)

Page 20: Lv and Mv Switchgear 10
Page 21: Lv and Mv Switchgear 10

LV Circuit Breaker CurrentsLV Circuit Breaker Currents

• Rated uninterrupted current, Iup ,

• Rated current, In

• Rated ultimate short‐circuit breaking capacity, Icu

• Rated service short‐circuit breaking capacity, Ics

• Rated short‐circuit making capacity, Icm

• Rated short‐time withstand current Icw (1sec. , 3 sec.)

Page 22: Lv and Mv Switchgear 10

Utilisation CategoryUtilisation Category

Utilization category Ag y• Without an intentional short‐time delay forselectivity under short‐circuit condition andtherefore without a short time withstand currenttherefore without a short‐time withstand currentrating.

Utilization Category B• With an intentional short‐time delay (which mayy ( ybe adjustable) provided for selectivity undershort‐circuit conditions.

Page 23: Lv and Mv Switchgear 10

Rated Short‐time Withstand CurrentRated Short time Withstand Current

Page 24: Lv and Mv Switchgear 10

MCBMCB

• For type ‘B’ the breaker must trip between the limits yp pof 3 to 5 times rated current

• For type ‘C” the breaker must trip between the limits of 5 to 10 times rated current

• For type ‘D’ the breaker must trip between the limits of 10 to 20 times rated currentof 10 to 20 times rated current.

Page 25: Lv and Mv Switchgear 10
Page 26: Lv and Mv Switchgear 10

CascadingCascading

NS250L (breaking capacity 150 kA)

NS100N (breaking capacity 25 kA)NS100N (breaking capacity 25 kA)

C60N (breaking capacity 10 kA)

Page 27: Lv and Mv Switchgear 10

MV Circuit Breakers 

M M M MM M M M

Page 28: Lv and Mv Switchgear 10

MV Circuit BreakersMV Circuit Breakers 

• Oil circuit breakersOil circuit breakers

• SF6 circuit breakers

• Vacuum circuit breakers

Page 29: Lv and Mv Switchgear 10

MV Circuit Breaker CurrentsMV Circuit Breaker Currents

• Rated normal currentRated normal current

• Rated short‐circuit breakingRated short circuit breaking

• Rated short‐circuit making

• Rated short‐time withstand current (1sec. , 3 sec.)

Page 30: Lv and Mv Switchgear 10

SubstationSubstation

• Medium‐voltage switchgear rooms

• Low‐voltage switchgear rooms

Page 31: Lv and Mv Switchgear 10

1 Medium voltage switchgears shall be1. Medium‐voltage switchgears shall be installed in separate rooms. 

Page 32: Lv and Mv Switchgear 10

2. In the case of single‐row arrangement, a passageway of min. 1‐1.5 m shall be provided.of min. 1 1.5 m shall be provided. 

3. On the rear side of the switchgear a clearance of 1‐1,5 m shall be foreseen. 

1.5 m

1.5m

Page 33: Lv and Mv Switchgear 10

4. In the case of two‐row arrangement, the g ,passageway between the two operating panels shall be min. 1‐1.5 m. 

1.5 m

Page 34: Lv and Mv Switchgear 10

5. The room height shall be min. 4 m. (clear height from floor level to lower edge of HVAC ducts)floor level to lower edge of HVAC ducts).

4 m

Page 35: Lv and Mv Switchgear 10

Incoming TypesIncoming Types

1. Cable 1. Top

2. Bus duct 2. Bottom

Page 36: Lv and Mv Switchgear 10

1‐ Cable‐Bottom

Page 37: Lv and Mv Switchgear 10

2‐ Cable ‐Top

Page 38: Lv and Mv Switchgear 10

3‐ Bus duct‐Top

Page 39: Lv and Mv Switchgear 10

4‐ Bus duct‐Bottom

Page 40: Lv and Mv Switchgear 10
Page 41: Lv and Mv Switchgear 10
Page 42: Lv and Mv Switchgear 10