Download - Se Puerto Maldonado 2013

Transcript
Page 1: Se Puerto Maldonado 2013

Out of CalculationDe-energized

Voltages / Loading

Lower Voltage Range0.95 p.u.

Upper Voltage Range1.05 p.u.

Loading Range100. %

PTO_MDO138

Ul=132.31 kVu=0.96 p.u.

phiu=139.00 deg

PTO_MDO22.9

Ul=21.78 kVu=0.95 p.u.

phiu=133.35 deg

PTO_MDO10

Ul=9.64 kVu=0.96 p.u.

phiu=-15.67 d..

PowerFactory 15.1.6

SIMULACION DEL SIST. ELECT. DE PUERTO MAL

BR. JUAN JOSE BELTRAN PALOMINO BR. NATALY MARY ESPINOZA SURCO

Project: 2013

Graphic: Sistema Electrico

Date: 8/4/2015

Annex:

Load Flow Balanced

Nodes

Line-Line Voltage, Magnitude [kV]

Voltage, Magnitude [p.u.]

Voltage, Angle [deg]

Branches

Active Power [MW]

Reactive Power [Mvar]

Maximum Loading [%]

PM-07

P=2.34 MWQ=1.18 Mvar

=

PM-06

P=0.95 MWQ=0.71 Mvar

=

PM-03

P=4.17 MWQ=1.65 Mvar

=

PM-02

P=3.77 MWQ=1.91 Mvar

=

PM-01

P=2.53 MWQ=1.22 Mvar

=

P=13.90 MWQ=8.40 Mvar

loading=50.85 %

P=-3.30 MWQ=-1.88 Mvar

loading=50.85 %

P=-10.48 MWQ=-4.78 Mvar

loading=50.85 %

-10

0

0

SISTEMA ELECTRICO DE PUERTO MALDONADO AÑO 2013