Understanding Arc Flash
Presented by
Eddie F. Jones, PE
8/12/2019 Arcflash Pres
2/34
Engineering Services2
8/12/2019 Arcflash Pres
3/34
Engineering Services3
8/12/2019 Arcflash Pres
4/34
Engineering Services4
8/12/2019 Arcflash Pres
5/34
Engineering Services5
8/12/2019 Arcflash Pres
6/34
Engineering Services6
Five to 10 arc flash explosions occur inelectric equipment every day in the
United States. This number does not
include cases in which the victim is sentto an ordinary hospital. Instead, these
incidents are so severe the victimsrequire treatment from a special burn
center.
8/12/2019 Arcflash Pres
7/34
Engineering Services7
Type of faults Bolted Fault
Bolted faults are characterized by a solidly connected fault path
causing high levels of current to flow through this solidconnection.
Arcing Faults
Arcing faults differ in the fact that the current actually flows
through ionized air causing an arc.
The major difference between these two types of faults is thatthe energy in a bolted fault condition is dissipated in the faulted
equipment while an arcing fault releases energy out into the
surrounding enviroment
8/12/2019 Arcflash Pres
8/34
Engineering Services8
What causes electrical arcing
Inadvertent contact
Loose connections
Insulation failure
Poorly maintained equipment
Voltage transients
Unsuccessful Short Circuit Interruption
Animals (squirrels, snakes .. Etc)
8/12/2019 Arcflash Pres
9/34
Engineering Services9
Why is arc flash dangerous?An arc is a source of intense heat, light, sound and
pressure!
North Carolina in August: 100o F (311K)
Surface of the Sun: 8,540o F (5,000 K)
Arc @ arc terminals: 35,540o F (20,000+ K)
Max. arc power = 1/2 x bolted fault kW
Heat transfer depends on:
Size of arc (arc power)Duration of arc
Distance from arc (1/x^2)
Enclosure (arc in a box focuses heat in one direction)
8/12/2019 Arcflash Pres
10/34
Engineering Services10
Physical Effects of Arc Blast Metal vapor and air expand very rapidly due to arc heating
Pressure wave knocks worker away from arc Good: removes personnel from heat source
Bad: removes personnel from ladder
Pressure propels molten metal droplets out from arc source Hot enough to ignite clothing
Structural damage to buildings
Damaging sound pressure
Eardrum rupture
Blindness
Lung damage
Death!
8/12/2019 Arcflash Pres
11/34
Engineering Services11
8/12/2019 Arcflash Pres
12/34
Engineering Services12
Standards used to protect
workers from Arc-flash
hazards.
8/12/2019 Arcflash Pres
13/34
Engineering Services13
Covers electrical safety-related work
practices and proceduresfor employees who
work on or near exposed energized electrical
conductors or circuit parts in work places
Switchboards, panelboards, industrial
control panels, and motor control centers ...
shall be field markedto warn qualified
persons of potential electric arc flash
hazards.
The employer shall ensure that each
employee exposed to electric arcs shall not
wear clothing that could increase the injury
when exposed to these arcs.
This guide presents methods for the
calculation of arc-flash incident energy and
arc-flash boundaries in three-phase ac systems
to which workers may be exposed.
8/12/2019 Arcflash Pres
14/34
Engineering Services14
Safe operations
Equipment
(ProductStandards)
AnalysisPractices Training
OSHA (Workplace Safety)NEC (Installation)
IEEE 1584Calculations
OSHA StandardsNFPA 70E
Employer (Facility)
Employee
(Work, PPE)Enforcement
by inspectorsEnforcement
by OSHA
Electrical Safety Program
Design for Safety Electrical Safety Program
8/12/2019 Arcflash Pres
15/34
Engineering Services15
NEC 110.16
Switchboards, panelboards, industrial control panels, and motor
control centers that are in other than dwelling occupancies and
are likely to require examination, adjustment, servicing, or
maintenance while energized shall be field marked to warn
qualified persons of potential electric arc flash hazards. The
marking shall be located so as to be clearly visible to qualifiedpersons before examination, adjustment, servicing, or
maintenance of the equipment.
Warning for awareness, to prepare for future work
Field marked - not marked by manufacturer
No mention of values - only warning of hazard
8/12/2019 Arcflash Pres
16/34
Engineering Services16
OSHA 29 CFR 1910.335
Employees working in areas where there are potentialelectrical hazards shall be provided with, and shall use,
electrical protective equipment that is appropriate for the
specific parts of the body to be protected and for the work
to be performed.
Notice that OSHA does not specifically mention
calculations or NFPA 70E. However, since NFPA70E is a recognized, published standard available
to the industry, OSHA will cite using requirements
of NFPA 70E.
Personal Protective Equipment
8/12/2019 Arcflash Pres
17/34
Engineering Services17
OSHA 29 CFR 1910.333 Safety related work practices shall be employed to prevent electric
shock or other injuries resulting from either direct or indirectelectrical contacts.
Live parts to which an employee may be exposed shall be
deenergized before the employee works on or near them, unless
the employer can demonstrate that deenergizing introducesadditional or increased hazards or is infeasible.
The fundamental requirement is to de-energize!
Working on energized equipment is always a risk!
8/12/2019 Arcflash Pres
18/34
Engineering Services18
When is it acceptable to work onenergized equipment?
Examples of increased or additional hazards
Interruption of:
Life support systems
Emergency alarm systemsHazardous location ventilation
Examples of unfeasibility:
Start-up testing
Trouble shooting diagnostics
Continuous process segment
8/12/2019 Arcflash Pres
19/34
Engineering Services19
NFPA 70E 2-1.3.3
Flash hazard analysis shall be donebefore a person approaches any
exposed electrical conductor or circuitpart that has not been placed in anelectrically safe work condition.
8/12/2019 Arcflash Pres
20/34
Engineering Services20
Electrically SafeThe following steps must be taken to ensure an electrically safe work
condition.
Find all possible sources of supply
Open the disconnecting device for each source
Where possible visually verify the device is open Apply lock-out/tag-out devices
Test voltage on each conductor to verify that it is de-energized
Apply grounding devices where stored energy or induced voltage could
exist or where de-energized parts could contact live parts
Remember personal protective equipment must be worn when
working within the flash protective boundary until the circuit is
verified to be de-energized.
8/12/2019 Arcflash Pres
21/34
Engineering Services21
Incident energyIncident energy:
The amount of energy impressed on a surface, a certain distance
from the source, generated during an arc event.
Incident energy is measured in calories/cm2 or Joules/cm2.
1.2 cal/cm2 is the minimum amount of Incident Energy to produce
second degree burns on human skin. The flash protection
boundary is the distance at which the incident energy equals 1.2
cal/cm2.
8/12/2019 Arcflash Pres
22/34
Engineering Services22
Classes of Protective ClothingIncidentEnergy
(cal/cm2)
ClothingClass
Description ATPV
0-2 0 UntreatedCotton
n/a
2-5 1 FR shirt andpants
5-7
5-8 2A Cotton
Underwear +Cl. 1
8-18
5-16 2B FR Underwear + Cl. 1
16-22
8-25 3 FR Coverall +
Cl. 2A
25-50
25-40 4 Double Layer Switching Coat
+ Cl. 2A
40-60+
NFPA70E lists the
clothing that is
appropriate for each
hazard class.
ATPV - Arc thermal performance exposure value (cal/cm2)
8/12/2019 Arcflash Pres
23/34
Engineering Services23
Hazard/Risk CategoryTask Assumes Equipment is energized, and work is done
within Flash Boundary
Hazard/Risk
Category
V-rated
Gloves
V-rated
Tools
Panelboards or Switchboards rated >240V(with Molded Case or
Insulated case circuit breakers) - Notes 1 and 3- - -
CB or fused switch operation with covers on 0 N N
CB or fused switch operation with covers off 1 N N
Work on energized parts, including voltage testing 2* Y Y
Note 1. 25kA short circuit current available, 0.03 sec (2 cycle) fault
clearing
Note 3. For < 10 kA short circuit current available, the Hazard/Risk
Category required may be reduced by one Number.
8/12/2019 Arcflash Pres
24/34
Engineering Services24
Limits of approach
NFPA70E establishesapproach boundaries to
live parts for shock
protection for both
qualified and unqualifiedpersonnel.
Voltage(L-L)
LimitedApproach
(movable)
LimitedApproach
(fixed)
RestrictedApproach
FlashProtection
< 300 V 10 3 6 AvoidContact
3
300 750 V 10 3 6 1 3
750 2,000V
10 4 2 4
2,000 15,000 V
10 5 2 2 16
8/12/2019 Arcflash Pres
25/34
Engineering Services25
IEEE 1584-2002
IEEE Guide for Performing Arc-Flash Hazard Calculations
Incorporates results of extensive testing performed by several parties
Provides tools to calculating incident arc-flash energy and protection
boundries.
Does not replace NEC or 70E--instead, works with and alongside of
them
8/12/2019 Arcflash Pres
26/34
Engineering Services26
What is an Arc flash Analysis?
A study investigating a workers
potential exposure to arc flashenergy,
conducted for the purpose of
injury prevention
and the determination of safe
work practices
and appropriate levels of PPE.
8/12/2019 Arcflash Pres
27/34
Engineering Services27
Analysis Process
1 Collect system and installation data2 Determine system modes of operation
3 Determine bolted fault current
4 Calculate arc fault current
5 Find protective device characteristic and arc duration
6 Select working distances
7 Calculate incident energy
8 Calculate flash protection boundary
9 Determine PPE (risk hazard) category
8/12/2019 Arcflash Pres
28/34
Engineering Services28
Arc Flash Study Deliverables
AFIE and resulting PPE levels
Single-line diagram
Short circuit duty assessment
Time-current coordination settings
Equipment labels (optional)
8/12/2019 Arcflash Pres
29/34
Engineering Services29
Flash Hazard Analysis Table
8/12/2019 Arcflash Pres
30/34
Engineering Services30
Can arc flash exposure be reduced?
Design considerations
Main circuit breakers
Especially on the load side of service entrance
transformers
High resistance grounded systems
Limits the line to ground fault energy
Performing Arc-flash analysisReview circuit breaker settings (INST)
125E
2000 KVA
3000A MAIN
SUB 1BLV 46.0 kALV X/R 8.2
MTRI-SUB1
1600A1 800A1 1200A2 800A
2 sets: 500
EQUIP CP
BUS-0031LV 9.1 kALV X/R 1.9
8/12/2019 Arcflash Pres
31/34
Engineering Services31
Breaker Settings Comparison
TX Inrush
2000 KVA
2 sets: 500
2000 KVA
125E
3000A MAIN
800A1
2 sets: 500
1 10 100 1K 10K0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw
TIMEIN
SECONDS
TX Inrush
2000 KVA
2 sets: 500
2000 KVA
125E
3000A MAIN
800A1
2 sets: 500
1 10 100 1K 10K0.01
0.10
1
10
100
1000
CURRENT IN AMPERES
Case 3.tcc Ref. Voltage: 480 Current Scale x10^2 Ford Sharonville.drw
TIM
EIN
SECONDS
IA = 6K
IB = 9K
Fault clears in 8
seconds
Incident energy
= 718 cal/cm2
No FR class for IE
values this high
Fault clears in 0.1
second
Incident energy
= .97 cal/cm2
FR class 0
IA = 6K
IB = 9K
8/12/2019 Arcflash Pres
32/34
Engineering Services32
Can arc flash exposure be reduced?Maintenance considerations
Direct replacements, reconditioning, retrofills
of older devices
New, improved protective relays
MasterPact clearing times
Remote racking
Arc Terminator for MV MetalClad s/g Arc resistant switchgear
HVIR windows, remote thermal monitoring
Thermographic imaging requires
Equipment energized and serving normal loads
Equipment open and visible
8/12/2019 Arcflash Pres
33/34
Engineering Services33
Parting thoughtNumerous injuries and deaths are caused each year by
arc-flash incidents. While arc-flash can not be completelyeliminated, there are many things that we can do to prevent
it. The single most important thing we can do to prevent
arc-flash incidents is to place the equipment in a safe
working condition. If it is more dangerous to turn theequipment off workers must wear appropriate PPE.
Thank you for your time and attention