036-21511-001-A-0204 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE PACKAGE HEAT PUMP UNITS BQ 036, 048 & 060 3, 4 & 5 NOMINAL TONS (Export 50 Hz) ® TECHNICAL GUIDE DESCRIPTION YORK Sunline 2000 TM heat pumps are convertible single package units with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can eas- ily be installed on a roof curb, slab, roof jack or frame. These heat pumps utilize a unique ambient compensated time-temperature defrost system. The defrost module auto- matically increases the time interval between defrost cycles as the outdoor ambient temperature decreases. This helps to eliminate unnecessary and costly defrost cycles. All units include: Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards Permanently lubricated motors Bottom or side air discharge configuration capability (field convertible) Manufactured under the quality standards of ISO9001 3FJMIF@FQV TM Control Board Copper tube/aluminum fin coils Easy access to all components Rigging holes in base rails for lifting Fork lift slots on three sides Single point power connection Complete factory package - tested, charged and wired

Transcript of Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be...

Page 1: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

SING

BQ 03

3, 4 & 5

(Expor

TEC

LE PACKAGE HEAT PUMP UNITS

6, 048 & 060

NOMINAL TONS

t 50 Hz)

� �

HNICAL GUIDE

DESCRIPTION

YORK Sunline 2000TM heat pumps are convertible single package units with a common cabinet and a common roof curb for the 3, 4 and 5 ton sizes. The units were designed for light commercial and commercial applications. They can eas-ily be installed on a roof curb, slab, roof jack or frame.

These heat pumps utilize a unique ambient compensated time-temperature defrost system. The defrost module auto-matically increases the time interval between defrost cycles as the outdoor ambient temperature decreases. This helps to eliminate unnecessary and costly defrost cycles.

All units include:

• Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards

• Permanently lubricated motors

• Bottom or side air discharge configuration capability (field convertible)

• Manufactured under the quality standards of ISO9001

• ����������TM Control Board

• Copper tube/aluminum fin coils

• Easy access to all components

• Rigging holes in base rails for lifting

• Fork lift slots on three sides

• Single point power connection

• Complete factory package - tested, charged and wired

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . . . 3

FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9

FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 10

Fig. # Pg. #LIST OF FIGURES

1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2 TYPICAL FIELD POWER & CONTROLWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3 UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

4 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 26

5 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . . 27

6 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . . . . . . 27

7 DISCONNECT/BLOWER ACCESS LOCATION. . . . . . 28

8 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 29

9 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 30

10 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 31

Tbl. # Pg. #LIST OF TABLES

1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . 11

2 CAPACITY RATING (COOLING) . . . . . . . . . . . . . . . . 11

3 CAPACITY RATING (HEATING) . . . . . . . . . . . . . . . . . 11

4 BQ036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 12

5 BQ048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 13

6 BQ060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 14

7 BQ036 HEATING CAPACITIES (3 TON) . . . . . . . . . . 15

8 BQ048 HEATING CAPACITIES (4 TON) . . . . . . . . . . 16

9 BQ060 HEATING CAPACITIES (5 TON) . . . . . . . . . . 17

10 SUPPLY AIR BLOWER PERFORMANCE (3 TON DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . . . 18

11 SUPPLY AIR BLOWER PERFORMANCE (4 TON DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . . . 19

12 SUPPLY AIR BLOWER PERFORMANCE (5 TONBELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . 20

13 BELT DRIVE BLOWER MOTOR AND DRIVE DATA. . 21

14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 21

15 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 21

16 ELECTRICAL DATA - BQ036, 048, & 060 . . . . . . . . . 22

17 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

18 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 24

19 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 24

20 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

21 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 28

22 BQ 4 POINT LOADS WEIGHT DISTRIBUTION(KG / LBS.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

23 BQ 6 POINT LOADS WEIGHT DISTRIBUTION(KG / LBS.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

24 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 30

25 OPERATING WEIGHTS (KG / LBS.) . . . . . . . . . . . . . 30

2 Unitary Products Group

Page 3: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

PRODUCT NOMENCLATURE

3-5 Ton Sunline Model Number Nomenclature

Additional Options

(See Next Page)

Product Generation

1 = First Generation

Nominal Cooling

Capacity - MBH

036 = 3 Ton

048 = 4 Ton

060 = 5 Ton

Installation Options

A = No Options Installed

B = Option 1

C = Option 2

D = Options 1 & 2

E = Option 3

F = Option 4

G = Options 1 & 3

H = Options 1 & 4

J = Options 1, 2 & 3

K = Options 1, 2, & 4

L = Options 1,3 & 4

M = Options 1, 2, 3, & 4

N = Options 2 & 3

P = Options 2 & 4

Q = Options 2, 3, & 4

R = Options 3 & 4

Options

1 = Disconnect

2 = Non-Pwr'd Conv Oultet

3 = Smoke Detector S.A.

4 = Smoke Detector R.A.

Heat Type & Nominal Heat Capacity

C00 = Cooling Only. Suitable for field installed electric heat

Electric Heat Options

E07 = 7 kW Electric Heat

E10 = 10 kW Electric Heat

E15 = 15 kW Electric Heat

E20 = 20 kW Electric Heat

E30 = 30 kW Electric Heat

Product Catagory

B = Heat Pump, Single Package

B Q C00 A7A AA 1048

Product Identifier

Q = R-22 Std. Eff. Heat Pump

Voltage

7 = 380/415-3-50

* Belt Drive NOT available on 3 & 4 Ton 50 Hz models

Airflow

A = Direct Drive (Standard on 3 and 4 ton models)

B = Direct Drive/Single Input Econo

D = Direct Drive/Motorized Damper

L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra transformer & circuit bkr.

N = Belt Drive (Must be ordered on 5 ton BQ060)

P = Belt Drive/Single Input Econo

R = Belt Drive/Motorized Damper

Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters

Unitary Products Group 3

Page 4: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

PRODUCT NOMENCLATURE - Continued3-5T Sunline Model Number Nomenclature

Additional Options

AA None

AB Phase Monitor

AC Coil Guard

AD Dirty Filter Switch

AE Phase Monitor & Coil Guard

AF Phase Monitor & Dirty Filter Switch

AG Coil Guard & Dirty Filter Switch

AH Phase Monitor, Coil Guard, & Dirty Filter Switch

AS Bottom Condensate Pan

BA Hinged Filter Door & Toolless Access Panels

BB Phase Monitor, Hinged Filter Door & Toolless Access Panels

BC Coil Guard, Hinged Filter Door & Toolless Access Panels

BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels

BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

CA CPC Controller with Dirty Filter Switch & Air Proving Switch

CB CPC Controller, DFS, APS & Phase Monitor

CC CPC Controller, DFS, APS & Coil Guard

CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard

CE CPC Controller, DFS, APS & Technicoat Cond. Coil

CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

CJ CPC Controller, DFS, APS & Technicoat Evap. Coil

CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils

CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

4 Unitary Products Group

Page 5: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless AccessPanels

GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch

HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor

HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard

HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard

HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil

HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil

HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils

HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

Additional Options

Unitary Products Group 5

Page 6: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch

JB Johnson UNT Controller, DFS, APS & Phase Monitor

JC Johnson UNT Controller, DFS, APS & Coil Guard

JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard

JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil

JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

JJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil

JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils

JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch

NB Novar ETC-3 Controller, DFS, APS & Phase Monitor

NC Novar ETC-3 Controller, DFS, APS & Coil Guard

ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard

NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil

NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor

NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard

NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard

NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil

NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor

NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard

NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard

NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils

NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor

NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard

NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard

PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels

PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels

PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels

PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels

PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels

PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels

PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels

PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

TA Technicoat Condenser Coil

TB Technicoat Condenser Coil & Phase Monitor

TC Technicoat Condenser Coil & Coil Guard

Additional Options

6 Unitary Products Group

Page 7: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TD Technicoat Condenser Coil & Dirty Filter Switch

TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard

TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch

TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch

TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

TJ Technicoat Evaporator Coil

TK Technicoat Evaporator Coil & Phase Monitor

TL Technicoat Evaporator Coil & Coil Guard

TM Technicoat Evaporator Coil & Dirty Filter Switch

TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard

TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch

TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch

TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch

TS Technicoat Evaporator & Condenser Coils

TT Technicoat Evaporator & Condenser Coils & Phase Monitor

TU Technicoat Evaporator & Condenser Coils & Coil Guard

TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch

TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard

TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch

TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch

TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch

UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels

UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels

UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels

UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels

UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels

UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels

UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels

UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels

UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels

Additional Options

Unitary Products Group 7

Page 8: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FEATURES

All models are available with a wide variety of factory-mounted options such as phase monitor, dirty filter switch, and coil guard to make them suitable for almost every appli-cation.

All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over-head rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizon-tal duct, remove the supply and return air panels on the rear of the unit.

All models are available with these “factory mounted” outdoor air damper options:

• Single enthalpy economizer

• Motorized outdoor air damper

Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact require-ments of the job.

All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system compo-nents.

• ����������™ Controls - ����������™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.

• Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis-tance. Optionally, the control board can be pro-grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

• Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further

ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

• Fan Delays - Fan on and fan off delays are fully pro-grammable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

• Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

• Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor.

• On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.

• Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uni-form distribution of air across the heating elements. Every element is fully protected against excessive tem-perature by thermal limit switches.

The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit.

• BAS Controls - York’s Sunline™ series units offer fac-tory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.

8 Unitary Products Group

Page 9: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FACTORY-INSTALLED OPTIONS• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-posi-tion, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• PHENOLIC COATED EVAPORATOR AND CON-DENSER COILS - Special coating process that utilizes

Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection.

• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-vided with limit and automatic reset capability to prevent operation at excessive temperatures.

• FILTER OPTIONS - Standard units are shipped with 25mm (1in) throw-away filters installed. 50mm (2in) pleated filters are offered as a factory installed option.

• CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.

• DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

• BAS - See “Additional Options” section in the product nomenclature.

• SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.

FIGURE 1 - UNIT CUTAWAY

Unitary Products Group 9

Page 10: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.

• DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

• HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped inside the unit to prevent ship-ping damage. These must be field installed for tool-less operation.

FIELD-INSTALLED ACCESSORIES• SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

MIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capa-ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

• MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2-position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

• ELECTRIC HEATERS wired for single point power sup-ply. These nickel chromium heater elements are pro-

vided with limit and automatic reset capability to prevent operation at excessive temperatures.

• ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

• POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the condi-tioned space from being over-pressurized during econo-mizer operation.

The power exhaust option can only be used on bot-tom duct configurations.

• BAROMETRIC RELIEF DAMPER - This damper acces-sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

• ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

• BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

• CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

• COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

• PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of-phase condition.

10 Unitary Products Group

Page 11: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 1: SOUND POWER RATING1

UNITSIZE

CFMESP BLOWER

SOUND POWER (db 10-12 Watts)

Octave Band Centerline Frequency (Hz)SWLdB(A)

dB(A)@

10Ft.2IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000

036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41

048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42

060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-tee requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATING (COOLING)

MODELINDOOR DB/WB OUTDOOR DB/WB TOTAL OUTPUT TOTAL

OUTPUTkW

COP1°C °F °C °F kW MBH

036 29/19 84/66 46/24 85/75 8.34 28.5 4.37 1.9

048 29/19 84/66 46/24 85/75 11.7 39.9 5.85 2.0

060 29/19 84/66 46/24 85/75 13.9 47.5 7.7 1.8

1. COP = Coefficient of Performance - Total output kW divided by the total input kW.

TABLE 3: CAPACITY RATING (HEATING)

MODELRATINGPOINT

INDOOR DB/WB OUTDOOR DB/WB TOTAL OUTPUT TOTALOUTPUT

kWCOP1

°C °F °C °F kW MBH

036High 20/12 68/54 7/6 45/43 9.7 33 3.34 2.9

Low 20/12 68/54 2/1 36/34 7.9 27 3.0 2.6

048High 20/12 68/54 7/6 45/43 12.7 43.4 4.55 2.79

Low 20/12 68/54 2/1 36/34 10.4 35.5 4.15 2.51

060High 20/12 68/54 7/6 45/53 16.3 55.6 5.6 2.91

Low 20/12 68/54 2/1 36/34 13.5 46.1 5.20 2.60

1. COP = Coefficient of Performance - Total output kW divided by the total input kW.

Unitary Products Group 11

Page 12: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.46 kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the kW of the supply air blower motor.

TABLE 4: BQ036 COOLING CAPACITIES (3 TON)KW

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

27ºC 35ºC 46ºC

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºC ENTERING DRY BULB ºC ENTERING DRY BULB, ºC

M3/S WB ºC 31 28 25 22 31 28 25 22 31 28 25 22

0.59

23 13.2 2.9 8.6 6.6 6.2 -- 11.4 3.5 8.2 6.2 5.3 -- 10.3 3.9 7.9 5.9 4.7 --

20 14.9 2.8 11.3 8.3 7.2 5.1 10.3 3.4 10.0 7.9 6.7 4.7 9.1 3.8 9.1 7.6 6.4 4.4

17 11.0 2.7 11.0 11.0 9.8 7.8 9.7 3.3 9.7 9.7 8.5 6.4 8.8 3.7 8.8 8.8 7.6 5.6

14 11.0 2.7 11.0 11.0 9.8 7.8 9.7 3.3 9.7 9.7 8.5 6.4 8.8 3.7 8.8 8.8 7.6 5.6

0.47

23 12.6 2.7 8.2 6.0 5.1 -- 10.8 3.4 7.3 5.6 4.7 -- 9.7 3.9 6.7 5.3 4.4 --

20 11.7 2.7 9.2 7.5 6.6 4.8 10.0 3.3 8.8 7.0 6.2 4.4 8.8 3.7 8.5 6.7 5.9 4.1

17 10.7 2.6 10.7 9.8 8.5 6.7 9.4 3.2 9.4 8.5 7.6 5.9 8.5 3.6 8.5 7.6 7.0 5.3

14 10.7 2.6 10.7 9.8 8.5 6.7 9.4 3.2 9.4 8.5 7.6 5.9 8.5 3.6 8.5 7.6 7.0 5.3

0.41

23 11.9 2.8 6.6 6.2 5.1 -- 10.5 3.4 6.2 5.3 4.7 -- 9.7 3.8 5.9 4.7 4.4 --

20 11.0 2.7 8.1 6.9 7.0 5.4 9.7 3.3 7.6 6.4 6.2 5.0 8.8 3.7 7.3 6.2 5.6 4.7

17 10.0 2.6 9.8 8.8 8.2 7.3 9.1 3.2 8.5 7.9 7.3 6.4 8.5 3.6 7.6 7.3 6.7 5.9

14 10.0 2.6 9.8 8.8 8.2 7.3 9.1 3.2 8.5 7.9 7.3 6.4 8.5 3.6 7.6 7.3 6.7 5.9

MBH

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

80ºF 95ºF 115ºF

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºF ENTERING DRY BULB ºF ENTERING DRY BULB, ºF

CFM WB ºF

88 80 77 72 88 80 77 72 88 80 77 72

1250

73 45.0 2.9 29.5 22.5 21.0 -- 39.0 3.5 28.0 21.0 18.0 -- 35.0 3.9 27.0 20.0 16.0 --

66 41.0 2.8 38.5 28.5 24.5 17.5 35.0 3.4 34.0 27.0 23.0 16.0 31.0 3.8 31.0 26.0 22.0 15.0

62 37.5 2.7 37.5 37.5 33.5 26.5 33.0 3.3 33.0 33.0 29.0 22.0 30.0 3.7 30.0 30.0 26.0 19.0

57 37.5 2.7 37.5 37.5 33.5 26.5 33.0 3.3 33.0 33.0 29.0 22.0 30.0 3.7 30.0 30.0 26.0 19.0

1000

73 43.0 2.7 28.0 20.5 17.5 -- 37.0 3.4 25.0 19.0 16.0 -- 33.0 3.9 23.0 18.0 15.0 --

66 40.0 2.7 31.5 25.5 22.5 16.5 34.0 3.3 30.0 24.0 21.0 15.0 30.0 3.7 29.0 23.0 20.0 14.0

62 36.5 2.6 36.5 33.5 29.0 23.0 32.0 3.2 32.0 29.0 26.0 20.0 29.0 3.6 29.0 26.0 24.0 18.0

57 36.5 2.6 36.5 33.5 29.0 23.0 32.0 3.2 32.0 29.0 26.0 20.0 29.0 3.6 29.0 26.0 24.0 18.0

875

73 40.5 2.8 22.5 21.0 17.5 -- 36.0 3.4 21.0 18.0 16.0 -- 33.0 3.8 20.0 16.0 15.0 --

66 37.5 2.7 27.5 23.5 24.0 18.5 33.0 3.3 26.0 22.0 21.0 17.0 30.0 3.7 25.0 21.0 19.0 16.0

62 34.0 2.6 33.5 30.0 28.0 25.0 31.0 3.2 29.0 27.0 25.0 22.0 29.0 3.6 26.0 25.0 23.0 20.0

57 34.0 2.6 33.5 30.0 28.0 25.0 31.0 3.2 29.0 27.0 25.0 22.0 29.0 3.6 26.0 25.0 23.0 20.0

12 Unitary Products Group

Page 13: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.46 kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the kW of the supply air blower motor.

TABLE 5: BQ048 COOLING CAPACITIES (4 TON)KW

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

27ºC 35ºC 46ºC

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºC ENTERING DRY BULB ºC ENTERING DRY BULB, ºC

M3/SWB ºC 31 28 25 22 31 28 25 22 31 28 25 22

0.95

23 19.8 3.9 11.4 9.0 7.8 -- 18.4 4.4 10.6 8.4 7.3 -- 16.5 5.1 9.5 7.5 6.5 --

20 17.3 3.9 16.9 13.3 11.6 8.9 16.0 4.4 15.5 12.3 10.6 8.2 14.0 5.1 13.6 10.6 9.4 7.2

17 16.0 3.9 16.0 14.1 12.2 9.4 14.6 4.3 14.6 12.9 11.2 8.6 12.7 5.0 12.7 11.2 9.7 7.5

14 14.1 3.8 14.1 13.8 12.6 11.4 12.7 4.3 12.7 12.4 11.3 9.7 10.8 5.0 10.8 10.6 10.0 8.2

0.75

23 17.6 3.9 10.1 8.0 6.9 -- 16.3 4.4 9.4 7.4 6.5 -- 14.6 5.1 8.4 6.7 5.8 --

20 15.3 3.9 15.0 11.9 10.3 7.9 14.1 4.4 13.8 10.9 9.5 7.3 12.4 5.1 12.1 9.6 8.3 6.4

17 14.2 3.8 14.2 12.5 10.9 8.4 13.0 4.3 13.0 11.4 9.9 7.7 11.3 5.0 11.3 9.9 8.6 6.7

14 12.5 3.8 12.5 12.2 11.2 10.1 11.3 4.3 11.3 11.0 10.0 8.6 9.6 5.0 9.6 9.4 8.9 7.3

0.55

23 15.0 3.9 8.7 6.8 5.9 -- 14.0 4.4 8.0 6.4 5.5 -- 12.5 5.1 7.2 5.7 5.0 --

20 13.1 3.9 12.8 10.1 8.8 6.8 12.1 4.3 11.8 9.3 8.1 6.3 10.6 5.0 10.4 8.2 7.1 5.5

17 12.2 3.8 12.2 10.7 9.3 7.2 11.1 4.3 11.1 9.8 8.5 6.6 9.7 5.0 9.7 8.5 7.4 5.7

14 10.7 3.8 10.7 10.5 9.6 8.6 9.7 4.3 9.7 9.5 8.6 7.4 8.2 5.0 8.2 8.0 7.6 6.3

MBH

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

80ºF 95ºF 115ºF

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºF ENTERING DRY BULB ºF ENTERING DRY BULB, ºF

CFM WB ºF

88 80 77 72 88 80 77 72 88 80 77 72

2000

73 68.0 3.9 39.0 31.0 27.0 -- 63.0 4.4 36.0 29.0 25.0 -- 56.0 5.1 32.0 26.0 22.0 --

66 59.0 3.9 58.0 45.0 40.0 30.0 55.0 4.4 53.0 42.0 36.0 28.0 48.0 5.1 46.0 36.0 32.0 25.0

62 55.0 3.9 55.0 48.0 42.0 32.0 50.0 4.3 50.0 44.0 38.0 29.0 43.0 5.0 43.0 38.0 33.0 26.0

57 48.0 3.8 48.0 47.0 43.0 39.0 43.0 4.3 43.0 42.0 39.0 33.0 37.0 5.0 37.0 36.0 34.0 28.0

1600

73 60.0 3.9 35.0 27.0 24.0 -- 56.0 4.4 32.0 25.0 22.0 -- 50.0 5.1 29.0 23.0 20.0 --

66 52.0 3.9 51.0 41.0 35.0 27.0 48.0 4.4 47.0 37.0 32.0 25.0 42.0 5.1 41.0 33.0 28.0 22.0

62 48.0 3.8 48.0 43.0 37.0 29.0 44.0 4.3 44.0 39.0 34.0 26.0 39.0 5.0 39.0 34.0 33.0 23.0

57 43.0 3.8 43.0 42.0 38.0 34.0 39.0 4.3 39.0 38.0 34.0 29.0 33.0 5.0 33.0 32.0 30.0 25.0

1200

73 51.0 3.9 30.0 23.0 20.0 -- 48.0 4.4 27.0 22.0 19.0 -- 43.0 5.1 25.0 19.0 17.0 --

66 45.0 3.9 44.0 34.0 30.0 23.0 41.0 4.3 40.0 32.0 28.0 22.0 36.0 5.0 36.0 28.0 24.0 19.0

62 42.0 3.8 42.0 37.0 32.0 25.0 38.0 4.3 38.0 33.0 29.0 23.0 33.0 5.0 33.0 29.0 25.0 19.0

57 37.0 3.8 37.0 36.0 33.0 29.0 33.0 4.3 33.0 32.0 29.0 25.0 28.0 5.0 28.0 27.0 26.0 22.0

Unitary Products Group 13

Page 14: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.46 kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE table for the kW of the supply air blower motor.

TABLE 6: BQ060 COOLING CAPACITIES (5 TON)KW

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

27ºC 35ºC 46ºC

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºC ENTERING DRY BULB ºC ENTERING DRY BULB, ºC

M3/SWB ºC 31 28 25 22 31 28 25 22 31 28 25 22

1.15

23 24.7 4.7 14.2 11.2 9.7 -- 22.7 5.7 13.0 10.3 9.0 -- 19.9 7.0 11.4 9.1 7.9 --

20 21.2 4.7 20.7 16.4 14.2 11.0 19.2 5.7 18.8 14.9 12.9 10.0 16.5 7.0 16.1 12.7 11.1 8.5

17 19.5 4.6 19.5 17.2 14.9 11.5 17.5 5.7 17.5 15.4 13.4 10.3 14.8 6.9 14.8 13.0 11.3 8.7

14 16.9 4.6 16.9 16.5 15.4 12.5 14.9 5.6 14.9 14.6 14.3 12.1 12.2 6.9 12.2 11.9 11.4 9.1

0.95

23 22.4 4.7 12.9 10.2 8.9 -- 20.6 5.7 11.8 9.4 8.1 -- 18.1 7.0 10.4 8.2 7.1 --

20 19.3 4.6 18.8 14.9 12.9 10.0 17.5 5.7 17.1 13.5 11.7 9.0 15.0 7.0 14.6 11.6 10.0 7.8

17 17.7 4.6 17.7 15.6 13.5 10.5 15.9 5.6 15.9 14.0 12.2 9.4 13.4 6.9 13.4 11.8 10.2 7.9

14 15.4 4.6 15.4 15.0 14.0 11.4 13.6 5.6 13.6 13.3 13.0 11.0 11.1 6.9 11.1 10.8 10.4 8.3

0.75

23 19.9 4.7 11.5 9.1 7.9 -- 18.3 5.7 10.5 8.3 7.2 -- 16.1 7.0 9.2 7.3 6.4 --

20 17.1 4.6 16.7 13.2 11.5 8.9 15.5 5.7 15.2 12.0 10.4 8.0 13.3 7.0 13.0 10.3 8.9 6.9

17 15.8 4.6 15.8 13.9 12.0 9.3 14.1 5.6 14.1 12.4 10.8 8.3 11.9 6.9 11.9 10.5 9.1 7.0

14 13.7 4.6 13.7 13.4 12.4 10.1 12.1 5.6 12.1 11.8 11.6 9.8 9.8 6.9 9.8 9.6 9.2 7.4

MBH

AIR ON EVAPORATOR

COIL

TEMPERATURE OF AIR ON OUTDOOR COIL

80ºF 95ºF 115ºF

TOTAL CAP.1

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, KWTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBHTOTAL CAP1.

KW

POWER INPUT2

KW

SENSIBLE CAPACITY1, MBH

ENTERING DRY BULB, ºF ENTERING DRY BULB ºF ENTERING DRY BULB, ºF

CFM WB ºF

88 80 77 72 88 80 77 72 88 80 77 72

2400

73 84.0 4.7 48.0 38.0 33.0 -- 77.0 5.7 44.0 35.0 31.0 -- 68.0 7.0 39.0 31.0 27.0 --

66 72.0 4.7 71.0 56.0 48.0 38.0 66.0 5.7 64.0 51.0 44.0 34.0 56.0 7.0 55.0 43.0 38.0 29.0

62 67.0 4.6 67.0 59.0 51.0 39.0 60.0 5.7 60.0 53.0 46.0 35.0 51.0 6.9 51.0 44.0 39.0 30.0

57 58.0 4.6 58.0 56.0 53.0 43.0 51.0 5.6 51.0 50.0 49.0 41.0 42.0 6.9 42.0 41.0 39.0 31.0

2000

73 76.0 4.7 44.0 35.0 30.0 -- 70.0 5.7 40.0 32.0 28.0 -- 62.0 7.0 36.0 28.0 24.0 --

66 66.0 4.6 64.0 51.0 44.0 34.0 60.0 5.7 58.0 46.0 40.0 31.0 51.0 7.0 50.0 40.0 34.0 27.0

62 60.0 4.6 60.0 53.0 46.0 36.0 54.0 5.6 54.0 48.0 42.0 32.0 46.0 6.9 46.0 40.0 35.0 27.0

57 53.0 4.6 53.0 51.0 48.0 39.0 46.0 5.6 46.0 45.0 44.0 38.0 38.0 6.9 38.0 35.0 36.0 30.0

1600

73 68.0 4.7 39.0 31.0 27.0 -- 62.0 5.7 36.0 28.0 25.0 -- 55.0 7.0 31.0 25.0 22.0 --

66 58.0 4.6 57.0 45.0 39.0 30.0 53.0 5.7 52.0 41.0 36.0 27.0 45.0 7.0 44.0 35.0 30.0 24.0

62 54.0 4.6 54.0 47.0 41.0 32.0 48.0 5.6 48.0 42.0 37.0 28.0 40.0 6.9 41.0 36.0 31.0 24.0

57 47.0 4.6 47.0 46.0 42.0 34.0 41.0 5.6 41.0 40.0 40.0 33.0 33.0 6.9 33.0 33.0 31.0 25.0

14 Unitary Products Group

Page 15: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 7: BQ036 HEATING CAPACITIES (3 TON)

kw

M3/S RETURN AIR ºC

OUTPUT, kw IMPUT, kW

OUTDOOR AIR TEMPEATURE ºC (72% RH)

-23 -18 -12 -7 -1 4 10 16

0.59

13OUTPUT 2.5 3.3 4.2 5.2 6.3 7.6 9.0 10.5

INPUT 2.7 2.7 2.7 2.8 2.9 3.1 3.3 3.6

21OUTPUT 2.4 3.2 4.0 5.0 6.1 7.3 8.6 10.1

INPUT 2.9 2.9 2.9 3.0 3.1 3.3 3.5 3.8

27OUTPUT 2.2 2.9 3.7 4.6 5.6 6.7 8.0 9.3

INPUT 3.0 3.0 3.1 3.1 3.3 3.5 3.7 4.0

0.47

13OUTPUT 2.5 3.2 4.0 5.0 6.1 7.4 8.7 10.2

INPUT 2.7 2.7 2.8 2.9 3.0 3.2 3.4 3.6

21OUTPUT 2.4 3.1 3.9 4.8 5.9 7.1 8.4 9.8

INPUT 2.8 2.8 2.9 3.0 3.1 3.3 3.5 3.8

27OUTPUT 2.2 2.8 3.6 4.5 5.4 6.5 7.7 9.0

INPUT 2.9 2.9 3.0 3.1 3.3 3.5 3.7 4.0

0.35

13OUTPUT 2.3 3.0 3.8 4.7 5.8 6.9 8.2 9.6

INPUT 2.5 2.7 2.6 2.7 2.8 3.0 3.2 3.4

21OUTPUT 2.2 2.9 3.7 4.6 5.6 6.7 7.9 9.2

INPUT 2.6 2.6 2.7 2.8 2.9 3.1 3.3 3.6

27OUTPUT 2.0 2.6 3.4 4.2 5.1 6.2 7.3 8.5

INPUT 2.8 2.8 2.8 2.9 3.1 3.3 3.5 3.8

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (kW)

MBH

CFM RETURN AIR ºF

OUTPUT, MBH INPUT, kW

OUTDOOR AIR TEMPEATURE ºF (72% RH)

-10 0 10 20 30 40 50 60

1250

55OUTPUT 8.6 11.2 14.3 17.7 21.6 25.9 30.7 35.8

INPUT 2.7 2.7 2.7 2.8 2.9 3.1 3.3 3.6

70OUTPUT 8.3 10.9 13.7 17.1 20.8 25.0 29.5 34.5

INPUT 2.9 2.9 2.9 3.0 3.1 3.3 3.5 3.8

80OUTPUT 7.6 10.0 12.6 15.7 19.2 23.0 27.2 31.7

INPUT 3.0 3.0 3.1 3.1 3.3 3.5 3.7 4.0

1000

55OUTPUT 8.4 10.9 13.8 17.2 20.9 25.1 29.7 34.7

INPUT 2.7 2.7 2.8 2.9 3.0 3.2 3.4 3.6

70OUTPUT 8.1 10.5 13.3 16.5 20.2 24.2 28.6 33.4

INPUT 2.8 2.8 2.9 3.0 3.1 3.3 3.5 3.8

80OUTPUT 7.4 9.6 12.2 15.2 18.5 22.2 26.3 30.7

INPUT 2.9 2.9 3.0 3.1 3.3 3.5 3.7 4.0

750

55OUTPUT 7.8 10.2 13.0 16.2 19.8 23.7 28.1 32.8

INPUT 2.5 2.7 2.6 2.7 2.8 3.0 3.2 3.4

70OUTPUT 7.5 9.8 12.5 15.6 19.0 22.8 27.0 31.5

INPUT 2.6 2.6 2.7 2.8 2.9 3.1 3.3 3.6

80OUTPUT 6.9 9.0 11.5 14.3 17.5 21.0 24.8 29.0

INPUT 2.8 2.8 2.8 2.9 3.1 3.3 3.5 3.8

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x kW)

Unitary Products Group 15

Page 16: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 8: BQ048 HEATING CAPACITIES (4 TON)

kw

M3/S RETURN AIR ºC

OUTPUT, kw INPUT, kW

OUTDOOR AIR TEMPEATURE ºC (72% RH)

-23 -18 -12 -7 -1 4 10 16

0.95

13OUTPUT 3.6 5.1 6.6 8.3 10.6 13.0 15.8 18.0

INPUT 3.4 3.5 3.6 3.6 3.8 4.0 4.6 5.2

21OUTPUT 3.5 4.9 6.3 7.9 10.2 12.4 15.1 17.3

INPUT 3.5 3.6 3.8 3.8 4.0 4.2 4.8 5.4

27OUTPUT 3.2 4.5 5.8 7.3 9.4 11.5 13.9 16.0

INPUT 3.6 3.7 4.0 4.0 4.1 4.4 5.0 5.7

0.75

13OUTPUT 3.5 5.0 6.4 8.1 10.1 12.4 15.0 17.2

INPUT 3.3 3.4 3.5 3.6 3.6 3.8 4.4 5.0

21OUTPUT 3.4 4.8 6.2 7.8 9.7 11.9 14.4 16.5

INPUT 3.4 3.5 3.6 3.7 3.8 4.0 4.6 5.2

27OUTPUT 3.1 4.4 5.7 7.2 8.9 11.0 13.3 15.2

INPUT 3.5 3.6 3.8 3.9 4.0 4.2 4.8 5.4

0.55

13OUTPUT 3.2 4.5 5.8 7.9 9.3 11.4 13.8 15.8

INPUT 3.1 3.2 3.3 3.4 3.5 3.7 4.2 4.8

21OUTPUT 3.1 4.3 5.6 7.0 8.9 11.0 13.2 15.1

INPUT 3.2 3.3 3.4 3.5 3.6 3.8 4.4 5.0

27OUTPUT 2.8 4.0 5.2 6.4 8.2 10.1 12.2 13.9

INPUT 3.3 3.4 3.5 3.6 3.8 4.0 4.6 5.2

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT ( kW)

MBH

CFM RETURN AIR ºF

OUTPUT, MBH INPUT, kW

OUTDOOR AIR TEMPEATURE ºF (72% RH)

-10 0 10 20 30 40 50 60

2000

55OUTPUT 12.3 17.3 22.5 28.2 36.3 44.5 53.8 61.6

INPUT 3.4 3.5 3.6 3.6 3.8 4.0 4.6 5.2

70OUTPUT 11.8 16.6 21.6 27.1 34.9 42.8 51.7 59.2

INPUT 3.5 3.6 3.8 3.8 4.0 4.2 4.8 5.4

80OUTPUT 10.9 15.3 19.9 24.9 32.1 39.4 47.6 54.5

INPUT 3.6 3.7 4.0 4.0 4.1 4.4 5.0 5.7

1600

55OUTPUT 12.1 17.0 22.0 27.7 34.5 42.3 51.2 58.6

INPUT 3.3 3.4 3.5 3.6 3.6 3.8 4.4 5.0

70OUTPUT 11.6 16.3 21.2 26.6 33.2 40.7 49.2 56.3

INPUT 3.4 3.5 3.6 3.7 3.8 4.0 4.6 5.2

80OUTPUT 10.7 15.0 19.5 24.5 30.5 37.4 45.3 51.8

INPUT 3.5 3.6 3.8 3.9 4.0 4.2 4.8 5.4

1200

55OUTPUT 10.9 15.3 19.9 24.9 31.7 38.9 47.0 53.8

INPUT 3.1 3.2 3.3 3.4 3.5 3.7 4.2 4.8

70OUTPUT 10.5 14.7 19.1 24.0 30.5 37.4 45.2 51.7

INPUT 3.2 3.3 3.4 3.5 3.6 3.8 4.4 5.0

80OUTPUT 9.6 13.5 17.6 22.0 28.1 34.4 41.6 47.6

INPUT 3.3 3.4 3.5 3.6 3.8 4.0 4.6 5.2

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x kW)

16 Unitary Products Group

Page 17: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 9: BQ060 HEATING CAPACITIES (5 TON)

kw

M3/S RETURN AIR ºC

OUTPUT, kw INPUT, kW

OUTDOOR AIR TEMPEATURE ºC (72% RH)

-23 -18 -12 -7 -1 4 10 16

1.18

13OUTPUT 5.3 7.2 9.1 11.2 13.4 16.2 18.9 22.1

INPUT 5.0 5.1 5.2 5.3 5.3 5.6 5.9 6.5

21OUTPUT 5.1 6.9 8.8 10.8 12.9 15.6 18.2 21.3

INPUT 5.2 5.3 5.4 5.5 5.6 5.9 6.2 6.8

27OUTPUT 4.7 6.4 8.1 10.0 11.8 14.4 16.8 19.6

INPUT 5.4 5.6 5.7 5.8 5.9 6.0 6.5 7.2

0.95

13OUTPUT 5.3 7.1 9.0 11.2 13.2 16.0 18.7 21.9

INPUT 4.7 4.8 4.9 5.0 5.3 5.5 5.8 6.4

21OUTPUT 5.1 6.9 8.7 10.7 12.7 15.4 18.0 21.0

INPUT 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7

27OUTPUT 4.7 6.3 8.0 9.9 11.7 14.2 16.5 19.4

INPUT 5.1 5.3 5.4 5.5 5.8 6.1 6.4 7.0

0.71

13OUTPUT 4.7 6.4 8.1 10.0 12.1 14.7 17.2 20.1

INPUT 4.5 4.6 4.7 4.8 5.0 5.3 5.5 6.1

21OUTPUT 4.6 6.2 7.8 9.7 11.7 14.1 16.5 19.3

INPUT 4.7 4.8 4.9 5.0 5.2 5.5 5.8 6.4

27OUTPUT 4.2 5.7 7.2 8.9 10.7 13.0 15.2 17.8

INPUT 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (kW)

MBH

CFM RETURN AIR ºF

OUTPUT, MBH INPUT, kW

OUTDOOR AIR TEMPEATURE ºF (72% RH)

-10 0 10 20 30 40 50 60

2500

55OUTPUT 18.2 24.7 31.1 38.4 45.6 55.4 64.7 75.6

INPUT 5.0 5.1 5.2 5.3 5.3 5.6 5.9 6.5

70OUTPUT 17.5 23.7 29.9 37.0 43.9 53.3 62.2 72.7

INPUT 5.2 5.3 5.4 5.5 5.6 5.9 6.2 6.8

80OUTPUT 16.1 21.8 27.5 34.0 40.4 49.0 57.2 66.9

INPUT 5.4 5.6 5.7 5.8 5.9 6.0 6.5 7.2

2000

55OUTPUT 18.0 24.4 30.8 38.1 45.0 54.7 63.9 74.7

INPUT 4.7 4.8 4.9 5.0 5.3 5.5 5.8 6.4

70OUTPUT 17.3 23.5 29.6 36.6 43.3 52.6 61.4 71.8

INPUT 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7

80OUTPUT 15.9 21.6 27.2 33.7 39.8 48.4 56.5 66.1

INPUT 5.1 5.3 5.4 5.5 5.8 6.1 6.4 7.0

1500

55OUTPUT 16.2 22.0 27.8 34.3 41.4 50.2 58.7 68.6

INPUT 4.5 4.6 4.7 4.8 5.0 5.3 5.5 6.1

70OUTPUT 15.6 21.2 26.7 33.0 39.8 48.3 56.4 66.0

INPUT 4.7 4.8 4.9 5.0 5.2 5.5 5.8 6.4

80OUTPUT 14.4 19.5 24.6 30.4 36.6 44.5 51.9 60.7

INPUT 4.9 5.0 5.1 5.2 5.5 5.8 6.1 6.7

THE MBH AND KW VALUES DO NOT INCLUDE THE SUPPLY AIR BLOWER MOTOR.FOR NET CAPACITY, ADD THE SUPPLY AIR BLOWER MOTOR HEAT (MBH = 3.415 x kW)

Unitary Products Group 17

Page 18: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (3 TON DIRECT DRIVE) - SIDE DUCT APPLICATION

M3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS

HI - - - - - - 0.81 825 0.78 795

MED 0.78 850 0.77 820 0.75 780 0.73 750 0.70 720

LOW 0.69 750 0.69 725 0.66 700 0.64 675 0.62 650

M3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS

HI 0.75 765 0.72 735 0.70 700 0.65 670

MED 0.68 690 0.66 665 0.64 650 0.60 610

LOW 0.60 625 0.59 610 0.57 600 0.53 560

CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS

HI - - - - - - 1720 825 1665 795

MED 1660 850 1630 820 1590 780 1550 750 1500 720

LOW 1470 750 1440 725 1410 700 1370 675 1330 650

CFM WATTS CFM WATTS CFM WATTS CFM WATTS

HI 1600 765 1540 735 1490 700 1380 670

MED 1450 690 1400 665 1360 650 1270 610

LOW 1290 625 1250 610 1220 600 1130 560

31

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

M3/S

14950 74 99 124UNIT

TONNAGEMOTOR SPEED

31

174UNIT

TONNAGEMOTOR SPEED

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

223198 248

CFM

UNIT

TONNAGEMOTOR SPEED

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.20 0.30 0.40 0.50 0.60

31

UNIT

TONNAGEMOTOR SPEED

31

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.70 0.80 0.90 1.00

1. Side Duct application (380/415 Volts)

* . Includes allowances for a wet evaporator coil, 25mm [1 in] filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values

on applications other than units with side duct airflows.

18 Unitary Products Group

Page 19: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (4 TON DIRECT DRIVE) - SIDE DUCT APPLICATION

M3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS

HI - - - - 0.94 1010 0.92 975 0.90 945

MED 0.85 910 0.84 880 0.82 850 0.80 825 0.79 800

LOW 0.77 810 0.76 780 0.75 760 0.73 740 0.73 730

M3/S WATTS M

3/S WATTS M

3/S WATTS M

3/S WATTS

HI 0.87 910 0.93 825 0.78 825 0.72 775

MED 0.76 775 0.74 740 0.70 700 0.66 660

LOW 0.71 715 0.69 690 0.66 660 0.61 615

CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS

HI - - - - 2000 1010 1950 975 1905 945

MED 1810 910 1780 880 1740 850 1700 825 1665 800

LOW 1635 810 1610 780 1580 760 1555 740 1540 730

CFM WATTS CFM WATTS CFM WATTS CFM WATTS

HI 1840 910 1770 825 1660 825 1530 775

MED 1620 775 1560 740 1480 700 1390 660

LOW 1510 715 1460 690 1400 660 1300 615

41

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

M3/S

14950 74 99 124UNIT

TONNAGEMOTOR SPEED

41

174UNIT

TONNAGEMOTOR SPEED

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

223198 248

CFM

UNIT

TONNAGEMOTOR SPEED

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.20 0.30 0.40 0.50 0.60

41

UNIT

TONNAGEMOTOR SPEED

41

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.70 0.80 0.90 1.00

1. Side Duct application (380/415 Volts)

* . Includes allowances for a wet evaporator coil, 25mm [1 in] filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values

on applications other than units with side duct airflows.

Unitary Products Group 19

Page 20: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION

RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS

1.18 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 - -

1.13 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640

1.08 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535

1.04 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440

0.99 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340

0.94 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225

0.90 - - - - 894 885 940 940 980 980 1014 1020 1047 1095

0.85 - - - - 855 815 903 860 950 905 988 940 1022 970

0.80 - - - - - - 884 815 925 850 964 880 1001 910

0.75 - - - - - - 864 770 908 805 948 835 987 870

0.71 - - - - - - - - 882 740 926 780 965 830

RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS

1.18 - - - - - - - - - - - - - -

1.13 - - - - - - - - - - - - - -

1.08 1170 1580 - - - - - - - - - - - -

1.04 1148 1480 1180 1530 - - - - - - - - - -

0.99 1121 1385 1155 1425 - - - - - - - - - -

0.94 1100 1285 1133 1340 1169 1385 - - - - - - - -

0.90 1079 1180 1110 1240 1143 1280 1178 1330 - - - - - -

0.85 1058 1060 1090 1135 1122 1190 1158 1240 - - - - - -

0.80 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 - - - -

0.75 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 - -

0.71 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 - -

RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS

2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 - -

2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640

2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535

2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440

2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340

2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225

1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095

1800 - - - - 855 815 903 860 950 905 988 940 1022 970

1700 - - - - - - 884 815 925 850 964 880 1001 910

1600 - - - - - - 864 770 908 805 948 835 987 870

1500 - - - - - - - - 882 740 926 780 965 830

RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS

2500 - - - - - - - - - - - - - -

2400 - - - - - - - - - - - - - -

2300 1170 1580 - - - - - - - - - - - -

2200 1148 1480 1180 1530 - - - - - - - - - -

2100 1121 1385 1155 1425 - - - - - - - - - -

2000 1100 1285 1133 1340 1169 1385 - - - - - - - -

1900 1079 1180 1110 1240 1143 1280 1178 1330 - - - - - -

1800 1058 1060 1090 1135 1122 1190 1158 1240 - - - - - -

1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 - - - -

1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 - -

1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 - -

149 174 198

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

50 74 99 124UNIT

TONNAGE

AIR

FLOW

M3/S

51

UNIT

TONNAGE

AIR

FLOW

M3/S

51

AVAILABLE EXTERNAL STATIC PRESSURE-Pa*

223 248 273 298 322 347 372

UNIT

TONNAGE

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.20 0.30 0.40 0.50 0.60 0.70 0.80

1.10 1.20 1.30 1.40 1.50

51

M3/S

CFM

51

UNIT

TONNAGE

AIR

FLOW

CFM

AVAILABLE EXTERNAL STATIC PRESSURE-IWG*

0.90 1.00

1. 380/415 Volts

* . Includes allowances for a wet evaporator coil, 25mm [1in] filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for

resistance values on applications other than units with side duct airflows.

20 Unitary Products Group

Page 21: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA

mm inch mm inch mm inch mm inch mm inch

5 TON 850-1180 1.5 1450 56 1.0 IVL44 69-97 2.8-3.8 22 7/8 127 5.0 25 1 922 36.3 A35

MODEL

BLOWER

RANGE

(RPM)

MOTOR1 ADJUSTABLE MOTOR PULLY

HP RPMFRAME

SIZE

SERVICE

FACTOR

DESIG-

NATION

PITCH DIA. DESIG-

NATION

BELTFIXED BLOWER PULLY

BORE PITCH DIA. BOREPITCH

LENGTH

1. All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor because

they are located in the moving air, upstream of any heating device

TABLE 14: STATIC RESISTANCES

1000 1200 1400 1600 1800 2000 2200 2400 2600

0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23

5-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16

20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20

0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16BOTTOM DUCT CONNECTIONS1

ELECTRIC

HEATERS1

RESISTANCE, IWG

CFMDESCRIPTION

ECONOMIZER1, 2

1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.

2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air

duct system is less than 62.0 Pa [0.25 IWG], the unit will deliver less CFM during full economizer operation.

0.47 0.57 0.66 0.75 0.85 0.94 1.03 1.13 1.23

17.4 19.8 22.3 27.3 32.2 37.2 42.2 49.6 57.0

5-15KW 10.0 12.4 14.9 17.4 19.8 24.8 29.8 34.7 39.7

20-30KW 14.9 17.4 19.8 22.3 27.3 32.2 37.2 42.2 49.6

14.9 17.4 19.8 22.3 24.8 27.3 29.8 34.7 39.7BOTTOM DUCT CONNECTIONS1

ELECTRIC

HEATERS1

RESISTANCE, Pa

MDESCRIPTION

ECONOMIZER1, 2

3/S

TABLE 15: ELECTRIC HEATER CFM LIMITATIONS

7 10 15 20 30

M3/S 0.47 0.57 0.57 0.61 -

CFM 1100 1200 1200 1300 -

M3/S 0.61 0.61 0.61 0.61 -

CFM 1300 1300 1300 1300 -

M3/S 0.75 0.75 0.75 0.75 0.75

CFM 1600 1600 1600 1600 1600

HEATER SIZE NOMINAL KWMINIMUM

SUPPLY AIRVOLTAGE

UNIT MODEL SIZE

NOMINAL TONS

3

4

5

380/415-3-50

380/415-3-50

380/415-3-50

Unitary Products Group 21

Page 22: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 16: ELECTRICAL DATA - BQ036, 048, & 060

0.0 9.6 15

2CE045107462 4.3 6.5 17.8 20

2CE045110462 6.3 9.6 21.6 25

2CE045115462 8.5 12.9 25.8 30

2CE045120462 12.2 18.5 32.8 35

0.0 9.6 15

2CE045107462 5.1 7.1 18.5 20

2CE045110462 7.5 10.4 22.7 25

2CE045115462 10.2 14.2 27.4 30

2CE045120462 14.6 20.3 35.0 40

0.0 15.3 20

2CE045107462 4.3 6.5 23.5 30

2CE045110462 6.3 9.6 27.3 30

2CE045115462 8.5 12.9 31.4 35

2CE045120462 12.2 18.5 38.5 40

0.0 15.3 20

2CE045107462 5.1 7.1 24.2 30

2CE045110462 7.5 10.4 28.3 35

2CE045115462 10.2 14.2 33.0 35

2CE045120462 14.6 20.3 40.7 45

0.0 16.5 25

2CE045107462 4.3 6.5 24.7 30

2CE045110462 6.3 9.6 28.5 35

2CE045115462 8.5 12.9 32.6 35

2CE045120462 12.2 18.5 39.7 45

2CE045130462 18.1 27.5 50.9 60

0.0 16.5 25

2CE045107462 5.1 7.1 25.4 30

2CE045110462 7.5 10.4 29.5 35

2CE045115462 10.2 14.2 34.2 40

2CE045120462 14.6 20.3 41.9 45

2CE045130462 21.5 29.9 53.9 60

Note 1: HACR Type per NEC

Note 2: These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local

code, the fuse block accessory 2FB04700546 is available for field installation.

Note 3: Heaters are suitable for operation on 380/415V-3-50Hz power supply.

1.3 2.7

415-3-50 10.0 74 1.3 2.7

5

380-3-50 10.0 74

1.3 2.0

415-3-50 9.6 66 1.3 2.0

4

380-3-50 9.6 66

1.3 1.7

415-3-50 5.3 37.7 1.3 1.7

3

380-3-50 5.3 37.7

Heater

Amps

Minimum

Circuit

Ampacity

Amps

Max

Fuse /

BRKR1

Size

RLA

Each

LRA

Each

ID

Blower

Motor

FLA

Electric

Heater Model

No.3

Heater

kW

Model

TonnageVoltage

CompressorsOD Fan

Motors

FLA

Each

NONE 0.0

NONE 0.0

NONE 0.0

NONE 0.0

NONE 0.0

NONE 0.0

22 Unitary Products Group

Page 23: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TABLE 17: PHYSICAL DATA

MODELSBQ

036 048 060

EVAPORATORBLOWER

Centrifugal Blower (Dia. x Wd. mm) (in.)305 X 254(12X10)

305 X 254(12X10)

305 X 254(12X10)

Fan Motor HP (Direct Drive) 1/2 3/4 N/A

Fan Motor HP (Belt Drive) N/A N/A 1 1/2

EVAPORATORCOIL

Rows Deep 4 3 3

Fins Per Inch (25mm) 16 15 15

Face Area m2 (ft2) 0.40 (4.3) 0.57 (5.1) 0.57 (5.1)

CONDENSERFANS

Propeller Dia. mm (in.) 610 (24) 610 (24) 610 (24)

Fan Motor Hp 1/3 1/2 1/2

Nom. CFM 4300 4200 4500

CONDENSERCOILS

Rows Deep 1 1 1

Fins Per Inch (25mm) 20 20 20

Face Area m2 (ft2) 1.60 (17.1) 1.60 (17.1) 1.60 (17.1)

COMPRESSOR(Qty. Per Unit)

Type / Quantity Reciprocating / 1 Reciprocating / 1 Scroll / 1

AIRFILTERS

Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2

Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1

Face Area m2 (ft2) 0.59 (6.6) 0.59 (6.6) 0.59 (6.6)

CHARGE Refrigerant 22 kg (lbs./oz.) 3.6 (8/0) 4.2 (9/2) 3.7 (8.4)

TABLE 18: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE VOLTAGEkW CAP. MULTI-

PLIER

380 380 .627

415 415 0.75

TABLE 19: VOLTAGE LIMITATIONS1

1. Utilization Range “A” in accordance with ARI Standard 110.

POWER SUPPLY VOLTAGE

MIN. MAX.

380/415-3-50 342 456

Unitary Products Group 23

Page 24: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

TYPICAL POWER WIRING

TYPICAL CONTROL WIRING

FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING

W1

W2

Y1

G

OCC

P

P1

Y2

X

R

SD

C

C

SD

SD

R

OCC

C

RC

G

Y2

Y1

W2

W1

Jumper

Smoke

Detector

24 VAC

Class 2

X

R

THERMOSTAT

TERMINALSCONTROL

TERMINAL

BLOCK

TERMINALS ON

A LIMITED

NUMBER OF

THERMOSTATS

3

1

2

4

3

1

2

4

Second stage heating not required on single stage heating units.

Second stage cooling not required on single stage cooling units.

Jumper is required if there is no Smoke Detector circuit.

Jumper is required for any combination of R, RC, or RH.

6

5

5

6

OCC is an output from the thermostat to indicate the Occupied condition.

X is an input to the thermostat to display Error Status conditions.

24 Unitary Products Group

Page 25: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 3 - UNIT DIMENSIONS (3 - 5 TON HEAT PUMP) FRONT VIEW

829

[325/8]

1140

[447/8]

64

[21/2]

213

[83/8]

292

[111/2]

445 [171/2]

445 [171/2]

181

[77/8]

171 [63/4]

206

[81/8]

137

[53/8]

2089

[821/4]

165 [61/2]

mm[inch]

FIGURE 4 - UNIT WITH ECONOMIZER RAINHOOD

DETAIL “A”

699

[271/2]

699

[271/2]

41

[15/8]

260

[101/4]

1140

[447/8]

502

[193/4]

mm[inch]

Unitary Products Group 25

Page 26: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 5 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD

DETAIL “B”

454

[177/8]

184

[71/4]

699

[271/2]

485

[191/8]

1140

[447/8]

305 [12]

419 [161/2]mm[inch]

260

[101/4]

89

[31/2]

210

[81/4]

111

[43/8]

FIGURE 6 - UNIT DIMENSIONS (REAR VIEW)

mm[inch]445

[171/2]

445

[171/2]

165

[61/2]

292

[111/2]

76 [3]

200

[77/8]

117 [45/8]

292

[111/2]

26 Unitary Products Group

Page 27: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 7 - DISCONNECT/BLOWER ACCESS LOCATION

DISCONNECT SWITCH LOCATION

AND MOTOR ACCESS PANEL FOR

UNIT WITH “BELT-DRIVE” OPTION

CONTROL BOX

ACCESS

A,B

WIRING ENTRY

(See Detail “B”)

MOUNTING BRACKET

FOR DICONNECT SWITCH

(Shipped attached to the

blower housing inside

the blower compartment)

FIELD-SUPPLIED

DISCONNECT SWITCH

LOCATION

BLOWER MOTOR

ACCESS

FILTER

ACCESS

DOT PLUGS

TABLE 20: UTILITIES ENTRYHOLE OPENING SIZE (DIA.) USED FOR

A 22 / 0.88 KO1 Control Wiring2Side

Bottom

B 51 / 2.0 KO1 Power WiringSide

Bottom

C 41 / 1.63 KO Gas Piping (Front)

D 38 / 1.5 KO Gas Piping (Bottom)

1. Opening in the bottom to the unit can be located by the side in the insulation.

2. Do not remove the 2” knockout ring.

TABLE 21: MINIMUM CLEARANCESLOCATION CLEARANCE (mm / In.)

Front610 / 24.0 (Cooling/Electric

Heat)813 / 32.0 (Gas Heat)

Back305 / 12.0 (Less Economizer)

914 / 36.0 (With Economizer or Fixed Air/Motorized Damper)

Left Side (Filter Access) 610 / 24.0 (Less Economizer)914 / 36.0 (With Economizer)

Right Side (Cond. Coil) 610 / 24.0

Below Unit1 0

Above Unit21829 / 72.0 (For

Condenser Air Discharge)

1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.

2. Units must be installed outdoors. Overhanging struc-tures or shrubs should not obstruct condenser air dis-charge outlet.

Unitary Products Group 27

Page 28: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 8 - TYPICAL APPLICATIONS

28 Unitary Products Group

Page 29: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 9 - FOUR AND SIX POINT LOADING

1140

[447/8] 2089

[821/4]

Y

X

A

B

C

D

CONDENSER COIL

END OF UNITFRONT OF UNIT

APPROXIMATE

CENTER OF GRAVITY

BACK OF UNIT mm[inch] 1140

[447/8] 2089

[821/4]

Y

X

A

B

C

DCONDENSER COIL

END OF UNITFRONT OF UNIT

APPROXIMATE

CENTER OF GRAVITY

BACK OF UNIT mm[inch]

E

F

TABLE 22: BQ 4 POINT LOADS WEIGHT DISTRIBUTION (kg / Lbs.)UNIT TOTAL A B C D

BQ036 252 / 555 56 / 123 55 / 121 70 / 154 71 / 157

BQ048 270 / 595 60 / 132 59 / 130 75 / 165 76 / 168

BQ060 281 / 620 62 / 138 61 / 135 78 / 172 79 / 175

TABLE 23: BQ 6 POINT LOADS WEIGHT DISTRIBUTION (kg / Lbs.)UNIT TOTAL A B C D E F

BQ036 252 / 555 37 / 82 37 / 81 36 / 80 46 / 102 47 / 104 48 / 105

BQ048 270 / 595 40 / 88 40 / 87 39 / 86 50 / 110 50 / 111 51 / 112

BQ060 281 / 620 42 / 92 41 / 91 41 / 90 52 / 114 52 / 116 53 / 117

TABLE 24: CENTER OF GRAVITYDIMENSION 3 - 5 TON

X 1035 / 40-¾

Y 502 / 19-¾

TABLE 25: OPERATING WEIGHTS (kg / Lbs.)MODEL SIZE 3 TON 4 TON 5 TON

BASIC UNIT BQ 252 / 555 270 / 595 281 / 620

OPTIONS

Economizer 23 / 50

Motorized Damper 12 / 26

Electric Heater

5 - 7 kW 8 / 18

10 - 15 kW 10 / 23

20 - 30 kW 13 / 28

ACCY.Roof Curb 42 / 92

Barometric Relief / Fixed Air Damper 5 / 10

Belt-Drive Blower 2.3 / 5

Unitary Products Group 29

Page 30: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

FIGURE 10 - ROOF CURB DIMENSIONS

mm[inch]

495

[191/2]

495

[191/2]

495

[191/2]

946

[371/4]

1854

[73]

356 [14]

51

[2]

114

[41/2]

51

[2]

51

[2]

DUCT SIZES:

SUPPLY AIR = 489 X 489 [191/4 X 191/4]

RETURN AIR = 489 X 489 [191/4 X 191/4]

30 Unitary Products Group

Page 31: Y-TG-Single Package Heat Pump Units...036-21511-001-a-0204 for distribution use only - not to be used at point of retail sale single package heat pump units bq 036, 048 & 060 3, 4

036-21511-001-A-0204

Unitary Products Group 31