Wires and Voltage Ratings Calculation _ Utilities _ Notifier
Transcript of Wires and Voltage Ratings Calculation _ Utilities _ Notifier
-
7/27/2019 Wires and Voltage Ratings Calculation _ Utilities _ Notifier
1/2
08/05/13 Wires and Voltage Ratings Calculation | Utilities | Notifier
www.notifier.it/page.asp?id=31&ln=eng 1/2
Wires and Voltage Ratings Calculation
CABLES DIMENSIONING
This is a method to help on calculations relative to the electric cables dimensioning in the direct current operating
systems.
From the following formulas it is possible to obtain:
which voltage drop will be in relation to the line length, the current draw, the section of the cable usedhow much current can be drawn in the end of a line depending on its length, the section of the cable used
and the voltage drop accepted
which cable section must be used to have a certain voltage drop in relation to the length and the current
draw of the load
Each conductor, depending on its section, gives a certain resistance to the passage of current. The following is a
table that summarizes the specific resistance values for the copper cables and the sections more usually used.
Cable section in mm2Specific resistance
0,22 0,090
0,50 0,0351,00 0,018
1,50 0,012
2,00 0,009
2,50 0,007
3,00 0,006
Definitions
V. drop: Voltage drop on the load (difference between the output tension from the supplier and the minimum
operating tension of the connected device)
Length: Line length ( distance from the supplierx 2 ) in metres
I. load: Max. Current drawn from the device connected in the end of the line ( in mA )
Section: Section of the cable used ( which corresponds to the specific resistance as shown in the table
above) in mm2
Calculation of the VOLTAGE DROP
(Specific resistance x Line length) x I.load
V. drop = = Volt
1000
EXAMPLEA sounder that draws max. 2A must be installed on a 100 metres line. The line is installed using a cable with a section
of 1 mm2.
Which voltage drop will be in the end of the line?
Solution: ( 0,018 x 200 ) x 2000 / 1000 = 7,2 Volt
Calculation of the maximum current allowed in the end of the line
V. drop max allowed x 1000
I.load max = = mA
Specific resistance x Line length
EXAMPLE
Is it possible to install a 24 V sounder that draws 2A max. in the end of a line 100 metres long using a cable with the
section of 1 mm2 taking into consideration that the sounder operates with a minimum of 13 V ?
Solution:
http://www.notifier.it/immup/uti/calc_cavi_tens_eng.html#fondo_lineahttp://www.notifier.it/immup/uti/calc_cavi_tens_eng.html#quale_cavohttp://www.notifier.it/immup/uti/calc_cavi_tens_eng.html#fondo_lineahttp://www.notifier.it/immup/uti/calc_cavi_tens_eng.html#cad_tens -
7/27/2019 Wires and Voltage Ratings Calculation _ Utilities _ Notifier
2/2
08/05/13 Wires and Voltage Ratings Calculation | Utilities | Notifier
www.notifier.it/page.asp?id=31&ln=eng 2/2
( 24 - 13 ) x 1000 / 0,018 x 200 = 3055 mA = 3 A .... so the answer is : YES.
And if the sounder operates with a minimum of 18 V ?
Solution:
( 24 - 18 ) x 1000 / 0,018 x 200 = 1666 mA = 1,6 A .... so the answe is : NO.
Dimensioning of the CONDUCTORS SECTIONS that supply a sensor or a call point
Together with the choice of the battery capacity and the definition of the current suppliable by the supplier, the
correct dimensioning of the cables sections allows the devices to have optimal tension values according with the
regulations established by the manufacturer.
Supplying a sensor or a call point with a lower tension than the minimum value stated means for the device a
situation of instability, low efficiency, poor immunity to the noises.
The following data must be considered:
Example
Voltage at
SourceVs
For a correct and preferable result consider a
critical situation as mains loss24 V
Minimum
voltage on
sensor
Vc Pointed out by the manufacturer data 13,5 V
Sensor current Ic
Refer to manufacturer data sheet or measured by
a multimeter (in milliampere)
NOTE: In the case of NOT self-powered devices
must be used the higher absorption in the
different conditions: Service, Stand-By, Alarm
10 mA
Line length LSegment of cable between the source and the
sensor (in metres)50 m
Calculated the data, they can be insert in an easy formula to obtain the measure of the smallest cable sec tion that is
able to guarantee the optimal functioning: the minimum section, measured in mm2, must be equal or bigger than:
Section = ( 2L x Ic x 0,038 ) : [ ( VS - Vc ) x 1000 ]
EXAMPLE
Section = (100 m x 10 mA x 0,038 ) : ( 24 V - 13,5 V) x 1000 ) = 0,0036 mm2
The c able for the installation must have the c onductors sec tion equal or bigger than 0,04 mm2
The method described can be used to dimension with a good approximation a more complex tension network, with
ramifications.
In this case it is enough to identify all the connection points from the source on, to effect the calculation for each
single segment between two points and then summing all the results.
IMPORTANT NOTE
Take always into account the minimum sections given by the bodies of regulations that happen to be bigger than
those obtained from the calculations.