The impact of changes of the CAN/ULC S524 to Fire alarm systems

installation in Alberta

Agenda

2

CAN/ULC-S524-06 INSTALLATION OF FIRE

ALARM SYSTEMS Discussion of Code changes Have a good understanding of implications of new code changes and the impact of those changes to system design, installation and verification practices.

3

CAN/ULC-S524-06 INSTALLATION OF FIRE

ALARM SYSTEMS

CODE REVIEWS

4

Applicable Codes Affecting Life Safety in Alberta

• National Building Codes• Alberta Building Code• Alberta Fire Code• Standards and guidelines

– System manufacturer’s recommendations

– CAN/ULC• S524 (Installation)• S537(Verification)• S536 (Inspection)

– NFPA • NFPA 17A Chapter 7 (Wet

Chemical Extinguishing Systems)• NFPA 10 Chapter 6 (Portable

Fire Extinguishers)• NFPA 25 Chapter 2 (Sprinkler

Systems)• NFPA 101 Chapter 7

(Emergency Lighting)– Local/ Provincial AHJ– Insurance Carrier– City Building Inspector

• 1) Except as permitted by Articles 3.2.4.10 and 3.2.4.19, fire alarm systems, including the voice communication capability where provided, shall be installed in conformance with CAN/ULC S524 “Installation of Fire Alarm Systems”

• 2) Fire alarm systems shall be verified in conformance with CAN/ULC S537, “Verification of Fire Alarm Systems,” to ensure they are operating satisfactorily.

10

WHAT MAKES A GOOD FIRE ALARM INSTALLATION

Review of spec if availableReview of drawings if availableReview of the operation if available (specifically for retrofit applications)Understanding the equipment you are installingUnderstanding the requirements for the VerificationUnderstanding wiring practices such as polarities, isolators, signal loading, metering of wires, voltage drop.Programming information such as operations, preactions/releasing systems, relays and descriptors

WHAT MAKES A GOOD FIRE ALARM INSTALLATION

TYPE OF WIRE REQUIREDLOADING CALCULATIONS – how many signals per circuit/Voltage drop.NO SPLICES – this causes problems. Wire device to deviceProper in and out device terminals

3.3.1.3 In Class A circuit wiring, data communication link Style A and data communication link style C wiring, the primary wiring circuit and the alternate wiring circuit shall be installed in separate raceways or cable assemblies having a minimum separation of 300 mm where cables are installed vertically and 1200 mm where the cables are installed horizontally, except under the following conditions:

CAN/ULC-S524-06Standard for Installation

13

14

3.3.1.3 cont.A: For a distance not to exceed 3000 mm where the primary and return conductors enter or exit the field devices, control unit or transponder enclosuresB: Single conduit/raceway drops to individual field devices or,C: Single conduit/raceway drops to multiple field devices installed within a single room not exceeding 100m2

CAN/ULC-S524-06Standard for Installation

15

16

17

18

19

ISOLATORSULC-S524-06

New Data Circuit Isolator Requirements Added survivability during a fire Isolators required on both sides of a fire separation, offset horizontally and in different stud channel Waterflow or duct smokes mounted in one area but serving different floors or zones are consider same area and do not require isolator separation Isolators required on floor side only when picking up a single device in an exit or vertical shaft. (two modules, 1 in & 1 out)

What is an Isolator?Isolators provide short circuit protection between “floor areas” or fire zones so that a short circuit fault in one area does not affect normal operation in another area.

Hardwired systems• Isolators not required since separate zones

were on separate wires

Addressable systems• Devices from more than one zone are often

connected on the same pair of wires

4.2.7 Where a data communication link utilizing active field devices or supporting field device serves more than one National Building Code of Canada required fire alarm zone, a fault within on fire alarm zone shall not prevent the normal operation of other input or output field devices in another fire alarm zone, except as noted in Clause 4.2.8

CAN/ULC-S524-06Standard for Installation

22

5.14.5 Where a fire separation is provided, fault isolation modules required by Clause 5.14.2 shall be installed on each side of that fire separation.

CAN/ULC-S524-06Standard for Installation

23

CAN/ULC S 524-06 5.14 Fault Isolation Modules5.14.1 This Subsection

applies to the installation of fault isolation modules as required by Clause 4.2.10.

Note: Where available, fault isolation modules should be in a fire separated electrical room.

CAN/ULC-S524-06Standard for Installation

24

5.14.2 "Fault isolation modules shall be utilized when entering and leaving each fire alarm zone, as required by the National Building Code of Canada" Cont…

CAN/ULC-S524-06Standard for Installation

25

5.14.2 CONT…Note: Clause 5.14.2 is intended to

apply to the field devices located within the areas described above, which may include field devices monitoring mechanical equipment servicing other floor areas. For example, water flow devices on sprinkler systems or duct type detectors on HVAC systems serving other floors or areas are considered part of the same area specified in Clause 5.14.2 and need not be seperately fault isolated.

CAN/ULC-S524-06Standard for Installation

26

27

28

29

5.14.6 Fault isolation modules installed on opposite sides of same fire separation shall be offset horizontally to a minimum of 400 mm, and not located within the same stud space.

CAN/ULC-S524-06Standard for Installation

30

5.14.8 Fault Isolation modules serving a single field device in an exit of vertical service space shall be installed on the floor area side.

Note: Fault isolation modules are not required on the exit or vertical service space side.

CAN/ULC-S524-06Standard for Installation

31

5.14.9 "Fault isolation modules shall have an identifying mark or label on the cover plate or field device. The identifier shall be visible after installation. Where field devices incorporating fault isolation modules are used to comply with Clause 5.14.2 the first device entering and the last field device leaving each fire alarm zone shall be marked."

CAN/ULC-S524-06Standard for Installation

32

DATA RETURN

DATA OUT

IAM

IAM

IAM

IAM

FLOOR 1

FLOOR 4

FLOOR 3

FLOOR 2

IAM

ISO

ISO

ISO

ISO

DATA OUT

DATA RETURN

ISO

ISO BASE

IAM

IAM

IAM

IAM

ISO BASE

FLOOR 1

FLOOR 4

FLOOR 3

FLOOR 2

Address Count

12 detector addresses

4 module address

ISO

DATA OUT

DATA RETURN

ISO

ISO BASE

IAM

IAM

IAM

IAM

ISO BASE

FLOOR 1

FLOOR 4

FLOOR 3

FLOOR 2

Address Count

12 detector addresses

4 module address

ISO

DATA RETURN

DATA OUT

ISO

ISO BASE

IAM

IAM

IAM

IAM

ISO BASE

FLOOR 1

FLOOR 4

FLOOR 3

FLOOR 2

Address Count

16 detector addresses

4 module address

ISO

ISOISO

ISO

ISO BASE

ISO BASE

ISO

IAM

DATA RETURN

DATA OUT

Address Count

5 detector addresses

2 module address

Stairwell

ISO

Any now the rest of the story!!!

CAN/ULC-S524-06Standard for Installation

38

3.4.13 When using shielded cable, the shield shall be continuous and isolated from ground through all junction boxes. The shield shall be bonded in accordance with the manufacturers instructions.Note: The reason for this requirement is to prevent multiple ground loops that can disrupt proper system communications. At no time shall shields of specific groups of cables be common connected.

CAN/ULC-S524-06Standard for Installation

39

3.4.15 "Ancillary circuits shall not be used to activate circuits of a voltage level greater than 30V directly within the control unit and transponder. Multiple voltage relays or devices, mounted external to the control unit or transponder shall be utilized."

CAN/ULC-S524-06Standard for Installation

40

3.5.2 The plans of the building shall show the fire alarm zoning, device address, and the location of each field device of the fire alarm system, including fault isolation modules, ancillary devices, and annunciators, or display and control centres".

CAN/ULC-S524-06Standard for Installation

41

3.5.5 The documentation required by Clauses 3.5.1 to 3.5.4 shall be maintained on site.

CAN/ULC-S524-06Standard for Installation

42

CAN/ULC-S524-06Standard for Installation

43

CAN/ULC-S524-06Standard for Installation

44

5.1.2 Field devices shall be installed in accordance with manufacturers instructions.

Note: Field devices should be installed in a manner that provided accessibility for periodic maintenance.

CAN/ULC-S524-06Standard for Installation

45

5.6.1.3 Each fire detector shall be accessible for periodic maintenance and testing. Where spot type detectors are not readily accessible due to safety considerations (eg. Continuous process operations, energized electrical equipment, radiation, and excessive height) alternate methods of detection shall be utilized. (eg. Beam type smoke detector or aspiration type smoke detector).

CAN/ULC-S524-06Standard for Installation

46

5.2.5 Manual stations shall be installed on both sides of a series of doors exceeding 12m in total width and within 1500mm of each side of the opening.

CAN/ULC-S524-06Standard for Installation

47

5.4.1.1 Where ceiling heights allow, audible signal devices shall be installed so that the top of the device will not be less than 2300 mm above the finished floor level.

Exception: This requirement does not apply to in-suite signaling devices with integral silence means.

CAN/ULC-S524-06Standard for Installation

48

5.4.1.2 Wall-mounted audible signal devices shall be installed at least 150 mm below the ceiling measured to the top edge of the device.

CAN/ULC-S524-06Standard for Installation

49

5.4.3.1 Where silencing means are separately installed or incorporated in the audible signal device, the silencing means shall be clearly identified and located not less than 1200 mm and nor more than 1400 mm above the finished floor level measured from the centre of the silencing means.

CAN/ULC-S524-06Standard for Installation

50

5.4.3.4 Signal circuit fault isolation modules shall have an identifying label, listing the suite served, and be securely attached to the cover plate..

CAN/ULC-S524-06Standard for Installation

51

5.4.3.5 Signal circuit fault isolation devices shall be installed so as to be visible and accessible at all times.

CAN/ULC-S524-06Standard for Installation

52

ABC 3.2.4.18.(10) Audible signal devices within a dwelling unit or a suite of residential occupancy shall be connected to the fire alarm system

a) in a manner such that a single open circuit at one device will not impair the operation of the other audible signal devices on that same circuit that serve the other dwelling units or suites of residential occupancy, or

A-3.2.4.18.(10) Signal circuits. Cont…

ABC 2006

53

ABC 2006

A-3.2.4.18.(10) Signal circuits. Clause 3.2.4.18.(10)(a) permits Class A wiring, or Class B wiring with signal isolators located outside of the suites,to serve audible signal devices within residential suites.

b) on separate signal circuits that are not connected to the devices in any other dwelling unit, public corridor or suite of residential occupancy.

Clause 3.2.4.18.(10)(b) permits a separate signal circuit to serve each suite without the need for signal circuit isolators or Class A wiring.

54

ABC 3.2.4.18.(11) In a building or part thereof classified as a residential occupancy,

a) separate circuits shall be provided for audible signal devices on each floor area, and

b) audible signal devices within dwelling units of suites of residential occupancy shall be wired on separate signal circuits from those not within suites of residential occupancy or dwelling units.

ABC 2006

55

ABC 3.2.4.18.(13) Audible signals devices within dwelling units that are wired on separate signal circuits need not include a means for silencing as required by Sentence (9) provided the fire alarm system includes a provision for an automatic signal silence within dwelling units, where:

ABC 2006

56

ABC 3.2.4.18.(13) cont…a) the automatic signal silence cannot

occur within the first 60 seconds of operation or thin the zone in initiation,

b) a subsequent alarm elsewhere in the building, will reactuate the silenced audible signal devices within dwelling units,

c) after a period of not more than 10 min, the silenced audible signal devices will be restored to the continuous audible signal if the alarm is not acknowledged, and

ABC 2006

57

ABC 3.2.4.18.(13) cont…

d) the voice communication system referred to in Article 3.2.4.21 has a provision to override the automatic signal silence to allow the transmission of voice messages through silenced audible signal device circuits that serve the dwelling units

ABC 2006

58

5.4.5.2 Two or more visible signal devices is corridors or rooms in the same field of view shall flash in synchronization.

CAN/ULC-S524-06Standard for Installation

59

5.6.1.5 Fire detectors installed in buildings during construction or renovation phase shall be protected from contamination by dust and paint.

Note: Fire detectors should not be installed until after the construction clean-up of all trades is complete and final.

CAN/ULC-S524-06Standard for Installation

60

5.6.1.6 Unless specifically designed for expected conditions, fire detectors shall not be installed if any of the following ambient conditions exist:

A Temperature below 0’CB Temperature above

38’CC Relative humidity

above 93%; orD Air velocity greater

than 1.5 m/sec

CAN/ULC-S524-06Standard for Installation

61

5.7.4.2 On 3000 to 9000 mm high ceilings, spot type heat detectors spacing shall be reduced in accordance with figure 15. Cont….

CAN/ULC-S524-06Standard for Installation

62

5.7.4.2 Cont….Note: In areas with high ceilings (eg. Atriums)

beam type smoke detectors or aspiration detectors should be considered to provide better maintenance and testing access. Data is not available for ceilings higher than 9000mm, therefore, in such installations, fire type, growth rate, engineering judgement and manufacturers recommendations should be used. For additional information refer to NFPA 72, National Fire Alarm Code – Appendix B, Fire Detector Applications.

CAN/ULC-S524-06Standard for Installation

63

5.13.3 End-of-Line devices shall have an identifying label securely attached to the front of the cover plate, listing the zone served.

CAN/ULC-S524-06Standard for Installation

64

THE IMPACT OF CAN/ULC S524-06 ON FIRE ALARM DESIGN PRACTICES IN

CANADA

Questions?