1. SEE EQUIPMENT REPORT FOR ADDITIONAL INFORMATION. 2. FURNITURE IS N.I.C., U.O.N. 3. SEE ARCHITECTURAL RCP FOR CEILING MOUNTED EQUIPMENT. 4. PROVIDE LATERAL BRACING & BACKING AS REQUIRED ON ALL CEILING OR WALL MOUNTED EQUIPMENT INDICATED AS VV, VC OR CC. SEE EQUIPMNET REPORT AND 32/AE9.2.4 FOR WALL MOUNTED EQUIPMENT BACKING. 5. RESPONSIBILITY FOR FURNISHING AND INSTALLATION OF EQUIPMENT IS LISTED IN THE EQUIPMENT REPORT. COORDINATE ALL EQUIPMENT TO BE FURNISHED BY THE VA AND INSTALLED BY THE CONTRACTOR (VC) WITH THE VA PRIOR TO INSTALLATION. REFER TO RESPONSIBILITY CODES IN EQUIPMENT REPORT FOR FURTHER INFORMATION. 6. FOR EQUIPMENT REQUIRING VENTILATION SEE EQUIPMENT REPORT. 7. FOR EQUIPMENT REQUIRING SPECIAL ELECTRICAL SERVICES REFER TO ELECTRICAL DRAWINGS. 8. FOR EQUIPMENT REQUIRING SPECIAL DATA SERVICES REFER TO COMMUNICATION DRAWINGS. 9. VERIFY LOCATIONS OF CONNECTION POINTS FOR MEP SERVICES ON ALL CONTRACTOR INSTALLED EQUIPMENT PRIOR TO INSTALLATION. VV ITEM: VA SUPPLIED AND INSTALLED CC ITEM: CONTRACTOR SUPPLIED AND INSTALLED, UON VC ITEM: VA SUPPLIED AND CONTRACTOR INSTALLED EQUIPMENT LEGEND C F / MF COUNTERTOP FLOOR / MOVEABLE FLOOR W / HW WALL / HEADWALL MOUNTED CEILING MOUNTED CLG BATTERY POWERED (HAND HELD) BP 3801 Miranda Ave., Palo Alto CA VA PALO ALTO HEALTH CARE SYSTEM CONSTRUCTION DOCUMENTS FULLY SPRINKLERED Drawing Title Approved: Project Director Project Title Date Location Checked Building Number Project Number Drawing Number Drawn Revisions: Date CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management Seals and Signatures one eighth inch = one foot 16 8 4 0 B A C D E F three inches = one foot 6" 1 0 6" one and one half inches = one foot one inch = one foot 2 0 6" 6" 0 2 three quarters inch = one foot one half inch = one foot 4 0 three eighths inch = one foot 4 0 0 4 8 one quarter inch = one foot VA FORM 08-6231 1 2 3 4 5 6 8 7 9 F E D C B A 9 7 8 6 5 4 3 2 1 595 Market Street, 12th Floor San Francisco, CA 94105 T 415.243.4170 F 415.243.4176 www.cannondesign.com SHEET NOTES Associate Architect: Department of Veterans Affairs PRINTED ON: 1629 Telegraph Avenue, Suite 500 Oakland, CA 94612 Phone: 415-777-3737 Fax: 415-777-3476 www.dpsf.com 9/19/2016 12:14:39 PM EQUIPMENT SCHEDULE QH2.0.0 NS LC JUNE 20, 2016 100 640-396 EXPAND EMERGENCY DEPT. FACILITIES L I C E N S E D A R C H I T E C T S T A T E O F C A L I F O R N I A John Boerger No. C8147 REN. 09/30/17 S T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E O O O O O O O O O O O O O O O O O O O F C A L I F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O O R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R N I A RE RE RE E E E E E R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R R N. N. N N. . . . . . . . . . . . . . N N N N N N N N N N N N N N N N N N N N N 09 9 9 9 09 9 09 09 09 09 09 9 09 09 09 09 09 9 9 9 9 9 9 09 09 09 9 9 9 9 9 9 09 09 09 9 09 9 9 9 09 09 09 09 9 9 9 9 9 09 09 9 09 9 9 9 09 09 9 9 9 09 9 09 9 9 9 09 09 9 9 9 9 9 9 9 9 9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 /3 /3 /3 3 3 3 3 /3 3 3 3 3 3 3 /3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 /3 /3 /3 3 3 3 /3 3 3 3 3 /3 /3 3 /3 3 3 /3 3 3 3 3 3 3 /3 /3 /3 /3 /3 /3 3 3 3 3 3 /3 /3 /3 3 3 3 3 / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / 0/17

Transcript of VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED...

Page 1: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

1. SEE EQUIPMENT REPORT FOR ADDITIONAL INFORMATION.

2. FURNITURE IS N.I.C., U.O.N.

3. SEE ARCHITECTURAL RCP FOR CEILING MOUNTED EQUIPMENT.

4. PROVIDE LATERAL BRACING & BACKING AS REQUIRED ON ALLCEILING OR WALL MOUNTED EQUIPMENT INDICATED AS VV, VC ORCC. SEE EQUIPMNET REPORT AND 32/AE9.2.4 FOR WALL MOUNTEDEQUIPMENT BACKING.

5. RESPONSIBILITY FOR FURNISHING AND INSTALLATION OFEQUIPMENT IS LISTED IN THE EQUIPMENT REPORT. COORDINATEALL EQUIPMENT TO BE FURNISHED BY THE VA AND INSTALLED BYTHE CONTRACTOR (VC) WITH THE VA PRIOR TO INSTALLATION.REFER TO RESPONSIBILITY CODES IN EQUIPMENT REPORT FORFURTHER INFORMATION.

6. FOR EQUIPMENT REQUIRING VENTILATION SEE EQUIPMENTREPORT.

7. FOR EQUIPMENT REQUIRING SPECIAL ELECTRICAL SERVICESREFER TO ELECTRICAL DRAWINGS.

8. FOR EQUIPMENT REQUIRING SPECIAL DATA SERVICES REFER TOCOMMUNICATION DRAWINGS.

9. VERIFY LOCATIONS OF CONNECTION POINTS FOR MEP SERVICESON ALL CONTRACTOR INSTALLED EQUIPMENT PRIOR TOINSTALLATION.

VV ITEM: VA SUPPLIED AND INSTALLED

CC ITEM: CONTRACTOR SUPPLIED ANDINSTALLED, UON

VC ITEM: VA SUPPLIED ANDCONTRACTOR INSTALLED

EQUIPMENT LEGEND

CF / MF

COUNTERTOPFLOOR / MOVEABLE FLOOR

W / HW WALL / HEADWALL MOUNTEDCEILING MOUNTEDCLGBATTERY POWERED (HAND HELD)BP

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quar

ters i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/19

/201

6 12

:14:

39 P

M

EQUIPMENT SCHEDULE

QH2.0.0NS LCJUNE 20, 2016

100

640-396

EXPAND EMERGENCY DEPT. FACILITIES

LI C

E

N S E D A R C HI T

EC

T

ST

AT

EO F C A L I F O

RN

IA

John BoergerNo. C8147

REN. 09/30/17

STTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEOOOOOOOOOOOOOOOOOOO F C A L I FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO

RRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRN

IAREREREEEEEERRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRRR N.N.NN..............NNNNNNNNNNNNNNNNNNNNN 099990990909090909909090909099999990909099999990909099099990909090999999090990999909099990990999909099999999990000000000000000000000000000000000000000000000000000 /3/3/33333/3333333/3333333333333333/3/3/3333/33333/3/33/333/3333333/3/3/3/3/3/333333/3/3/33333//////////////////////////////////////////////////////////////////////////// 0/17

Page 2: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

DN

CO02X CO02X

CO02X

CO02X CO02X

CO02X

CO02X

CO02X CO02X

CO02X

CO02X

CO02X

CO02X CO02X

CO02X MO7

3

CO02X

MO7

3

ST25

SH20X PR03X PR11 PR12

CO02X CO02X

MO33

H

F

G

E

12345678

I

J

J.2

MO13 HW01

PH94

AE7.1.21

AE7.1.154

DI05

BO74

WA59

CR20

TH01DI01

DI04EK01

PU10WA60

WA54

ISO2ISO2A

ISO2B

SL09

ET01

MO33A

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

TRIAGEEXAM 1A1-203

(E) 8 ENTROOMA1-201

(E) ERTRIAGEA1-143

(E) ERTRIAGEA1-141

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

STAXISTORAGEA1-140B

OFFICEA1-141

OFFICEA1-143

OFFICEA1-145

OFFICEA1-147

OFFICEA1-149

OFFICEA1-151

OPENOFFICE /

CONFERENCEA1-148

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

OFFICEA1-146OFFICE

A1-144

COPYA1-142

(E) ASSTNURSE

MANAGERA1-323

(E) EDOU 1A1-325A

(E) EDOU 2A1-325B

(E) EDOU 3A1-325C

(E) EDOU 4A1-325D

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMED ROOM

A1-325G

(E) ALCOVEA1-C05A

(E) EMS HACA1-324

(E) EDOUSOILEDUTILITYA1-328

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

A1-TC1T-1.6

(E) SIGNALSG-1.46

(E) SOILEDUTILITYSG-1.40

(E) CLEANUTILITYA1-228

(E) TOILETA1-322

(E) ER MEDROOMA1-224

(E) FOODALCOVEA1-222

(E) 7 EREXAM RM

A1-218

(E) 6 EREXAM RM

A1-216

(E) 5PROCEDURE

ROOMA1-214

(E) TOILETA1-334

(E) TOILETA1-332A

(E) LOCKERROOM

A1--332

(E) EDOUEQUIPMENT

ROOMA1-330

(E) 4 ERCODE ROOM

A1-212

(E)PHYSICIAN

WORKROOMA1-210

(E) ANTEROOMA1-208(E) 3 ER

ISOLATIONROOMA1-206

(E) 2 EREXAM RM

A1-204

(E) 1 EREXAM RM

A1-202

(E)CONFERENCE

A1-140 (E) ALCOVEA1-200

(E) NURSESTATIONA1-220

(E) ERRECEPTION

A1-120

(E) ERWAITINGA1-125

(E) TOILETA1-129

(E) TOILETA1-127

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E) MEN'SLOCKERS

A1-418

(E) WOMEN'SLOCKERS

A1-416

(E) TOILETA1-416A

(E) TOILETA1-418A

(E) HACSG-1.101

(E) STAFFLOUNGEA1-410

(E)CONFERENCE

A1-422

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09

(E)WHEELCHAIR/STRETCHER

ALCOVEA1-430

(E) STAFFTOILETROOMA1-403

(E)PHYSICIAN

CALL ROOMA1-402

(E)PROGRAMSUPPORT

ASSTA1-401

(E) MAINELEC.

SEV1.1

(E)SOCIALWORKERA1-331

(E) OFFICEA1-235

(E) NURSEOFFICEA1-245

1. SEE EQUIPMENT REPORT FOR ADDITIONAL INFORMATION.

2. FURNITURE IS N.I.C., U.O.N.

3. SEE ARCHITECTURAL RCP FOR CEILING MOUNTED EQUIPMENT.

4. PROVIDE LATERAL BRACING & BACKING AS REQUIRED ON ALLCEILING OR WALL MOUNTED EQUIPMENT INDICATED AS VV, VC ORCC. SEE EQUIPMNET REPORT AND 32/AE9.2.4 FOR WALL MOUNTEDEQUIPMENT BACKING.

5. RESPONSIBILITY FOR FURNISHING AND INSTALLATION OFEQUIPMENT IS LISTED IN THE EQUIPMENT REPORT. COORDINATEALL EQUIPMENT TO BE FURNISHED BY THE VA AND INSTALLED BYTHE CONTRACTOR (VC) WITH THE VA PRIOR TO INSTALLATION.REFER TO RESPONSIBILITY CODES IN EQUIPMENT REPORT FORFURTHER INFORMATION.

6. FOR EQUIPMENT REQUIRING VENTILATION SEE EQUIPMENTREPORT.

7. FOR EQUIPMENT REQUIRING SPECIAL ELECTRICAL SERVICESREFER TO ELECTRICAL DRAWINGS.

8. FOR EQUIPMENT REQUIRING SPECIAL DATA SERVICES REFER TOCOMMUNICATION DRAWINGS.

9. VERIFY LOCATIONS OF CONNECTION POINTS FOR MEP SERVICESON ALL CONTRACTOR INSTALLED EQUIPMENT PRIOR TOINSTALLATION.

VV ITEM: VA SUPPLIED AND INSTALLED

CC ITEM: CONTRACTOR SUPPLIED ANDINSTALLED, UON

VC ITEM: VA SUPPLIED ANDCONTRACTOR INSTALLED

EQUIPMENT LEGEND

CF / MF

COUNTERTOPFLOOR / MOVEABLE FLOOR

W / HW WALL / HEADWALL MOUNTEDCEILING MOUNTEDCLGBATTERY POWERED (HAND HELD)BP

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quar

ters i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/19

/201

6 1:

25:1

6 PM OVERALL EQUIPMENT PLAN

QH2.1.1NSJUNE 20, 2016

100

640-396

EXPAND EMERGENCY DEPT. FACILITIES

SCALE: 1/8" = 1'-0"1 Equipment Plan - Level 1

LI C

E

N S E D A R C HI T

EC

T

ST

AT

EO F C A L I F O

RN

IA

John BoergerNo. C8147

REN. 09/30/17

STTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

ATTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTTT

EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF C A LLLLLLLLLLLLLLLLL II FFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFFF OOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO

RN

IARERRRRRR N.N 0909990999099990909999999999999909999999999999999909999999999909990909909999999999999999990999999909999999999000000000000000000000000000000000000000 /30/17

Page 3: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

ROUND RETURN AIR DUCT (UP AND DOWN)

TRANSFER DUCT WITH GRILLES

ACCESS DOOR

AIR TERMINAL - SIDEWALL GRILLE/REGISTER(AIRFLOW DIRECTION AND TYPE SHOWN)

AIR TERMINAL - CEILING EXHAUST(AIRFLOW DIRECTION AND TYPE SHOWN)

AIR TERMINAL - CEILING RETURN(AIRFLOW DIRECTION AND TYPE SHOWN)

DUCT SMOKE DETECTOR

SMOKE DAMPER

FIRE DAMPER

BACKDRAFT DAMPER

ROUND EXHAUST AIR DUCT (UP AND DOWN)

ROUND OUTSIDE AIR DUCT (UP AND DOWN)

VOLUME DAMPER

MOTORIZED DAMPER

GENERAL SYMBOLS AND TAGSSYMBOL DESCRIPTION

CIRCULAR DUCT BRANCH

RECTANGULAR DUCT BRANCH

TRANSITION / REDUCER

ROUND SUPPLY AIR DUCT (UP AND DOWN)

DIRECTION OF AIR FLOW

FLEXIBLE DUCT

DUCTWORK SYMBOLSSYMBOL DESCRIPTION

XXXX - SERVICE TYPE. SEE ABBREVIATIONS

INSULATED PIPE

TEE TURN UP

CAPPED PIPE

PIPE TURN UP

ELBOW TURN DOWN

TEE TURN DOWN

EXISTING

NEW (LINETYPE VARIES PER SYSTEM)

SYMBOL DESCRIPTION

PIPING SYMBOLS

EXISTING DUCTWORK

AD

12ø24ø

12x6(L2)32x20(L2)

RorDRorD

12x632x20

XXXX

BDD

FD

M

SD

VD

SMD

UCUNDERCUT DOOR

R

D

PITCH OF PIPE (RISE)

PITCH OF PIPE (DROP)

DUCT - END CAP

AIR FLOW ARROW (SUPPLY)

AIR FLOW ARROW (RETURN/EXHAUST)

FSD

AHU8

AIR TERMINAL - CEILING SUPPLY(AIRFLOW DIRECTION AND TYPE SHOWN)

DOUBLE-LINE AND SINGLE-LINE RECTANGULAR DUCT,FIRST NUMBER INDICATES SIDE IN VIEW IN INCHES,SECOND NUMBER INDICATES SIDE IN DEPTH ININCHES

COMBINATION FIRE/SMOKEDAMPER

VANED ELBOW OR RADIUS ELBOW (USEVANED ELBOW WHERE SPACE WILL NOTPERMIT THE USE OF LONG RADIUS ELBOW)

RADIUS ELBOW WITH TURNING VANES &MITERED ELBOW WITH TURNING VANES

INCLINED RISE OR DROP IN DIRECTIONOR AIR FLOW

ACOUSTICAL LINED DUCTWORK, SIZES GIVENARE CLEAR INSIDE DIMENSIONS IN INCHES

DOUBLE-LINE AND SINGLE-LINE ROUND DUCT,NUMBER INDICATES DIAMETER IN INCHES

LINEAR DIFFUSER (AIR DIRECTIONAND TYPE SHOWN)

ROOF EXHAUST FAN (PLAN)

POINT OF DISCONNECTION OF WORK TO BEREMOVED (XXXX - SERVICE REFERENCE. SEEABBREVIATIONS)

COIL - HEATING

UNIT HEATER

FAN COIL UNIT

COIL - PRE-HEAT

COIL - RE-HEAT

COIL - COOLING

AIR HANDLING UNIT ACCESS SECTION

AIR HANDLING UNIT PLENUM SECTION

DUCTWORK SYMBOLS

FILTER - PLEATED

FILTER - CARBON

SYMBOL

FILTER - BAG

DESCRIPTION

VAV BOX - FAN ASSISTED - PARALLEL

LOUVER (DOOR AND WALL)AND LOUVER FREE AREA

FAN - AXIAL

FAN - CENTRIFUGAL

FAN - CENTRIFUGAL PLUG/PLENUM

SOUND ATTENUATOR

AP

CC

CP

CR

CH

HUMIDIFIER

C

DX COIL - DX

UNIT HEATER - CEILING - PLAN

AIR SEPARATOR

LOUVER

XXXX

AUTOMATIC FLOW LIMITING VALVE

CIRCUIT SETTER (BALANCING VALVE)

PRESSURE REDUCING VALVE

TAMPER VALVE

LOCK SHIELD VALVE

QUICK DISCONNECT VALVE (OPENING)

CURB VALVE

NEEDLE VALVE

COCK, DRAIN

QUICK DISCONNECT VALVE (CLOSING)

COCK, SHUT-OFF

FLOAT VALVE

CHECK VALVE - SPRINGs

CHECK VALVE - SWING GATE

CHECK VALVE

TRIPLE DUTY VALVE

BACKFLOW PREVENTER

SAFETY RELIEF VALVE

2-PORT SHUT-OFF VALVE (S)

3-WAY GATE VALVE

ANGLE VALVE

GLOBE VALVE

3-WAY GLOBE VALVE

BALL VALVE

PLUG VALVE

BUTTERFLY VALVE

DIAPHRAGM VALVE

SOLENOIDMOTORIZEDDIAPHRAGMCYLINDERMANUAL

GENERAL DUTY MANUAL AND CONTROL VALVESSYMBOL (WITH OPERATOR TYPE) DESCRIPTION

SYMBOL DESCRIPTION

PIPING SYMBOLS

ECCENTRIC REDUCER/EXPANDER

CONCENTRIC REDUCER/EXPANDER

FOB

FOT

PIPE ALIGNMENT GUIDE

EXPANSION JOINT

EXPANSION LOOP

PIPE ANCHOR

FLANGED JOINT

UNION JOINT

TEMPERATURE SENSOR

RELATIVE HUMIDITY SENSOR

DIFFERENTIAL PRESSURE

CARBON MONOXIDE SENSOR

FLOW OR PRESSURE SWITCH

STEAM TRAP

THERMOMETER

TEST POINT

PRESSURE GAUGE

FS

TTHERMOSTATIC RADIATOR

THERMOWELL

M FLOW METER

PUMP

FLOW INDICATOR

ABBREVIATIONSSYMBOL DESCRIPTION

ABBREVIATIONSSYMBOL DESCRIPTION

ABBREVIATIONSSYMBOL DESCRIPTION

CARBON DIOXIDE SENSOR

EQUIPMENT TYPE

EQUIPMENT TAG NUMBER

HOSE END DRAIN

STRAINER Y-TYPE

AIR VENT, MANUAL

AIR VENT, AUTOMATIC

VACUUM BREAKER

FLEXIBLE CONNECTION (BRAIDED HOSE)

VB

VAV BOX - SINGLE DUCT

OCCUPANCY SENSOR

SENSOR - SEE ABBREVIATIONS FOR TYPE

SENSOR (DUCT MOUNTED) - SEE ABBREVIATIONSFOR TYPE

XX-YY

POINT OF NEW CONNECTION TO EXISTING WORK

TYPE(CFM)

TYPE(CFM)

TYPE(CFM)

TYPE(CFM)

TYPE(CFM)

TYPE(CFM)

AIR TERMINAL - CEILING EXHAUST - ROUND(AIRFLOW DIRECTION AND TYPE SHOWN)

AIR TERMINAL - CEILING RETURN - ROUND(AIRFLOW DIRECTION AND TYPE SHOWN)

AIR TERMINAL - CEILING SUPPLY - ROUND(AIRFLOW DIRECTION AND TYPE SHOWN)

TYPE(CFM)

LINE BREAK

FLEXIBLE CONNECTION (SPHERICAL RUBBER)

RECTANGULAR RETURN AIR DUCT (UP AND DOWN)

RECTANGULAR EXHAUST AIR DUCT (UP AND DOWN)

RECTANGULAR OUTSIDE AIR DUCT (UP AND DOWN)

RECTANGULAR SUPPLY AIR DUCT (UP AND DOWN)

FAN - ROOF MOUNTED - UPBLAST

FAN - ROOF MOUNTED - MUSHROOM

XX-YY

FLEXIBLE CONNECTION

L(SQ.FT.)

°FØ

AAVABANABVAC

ACCACCU

ADAFFAHUAMBAP

APPROXARCH

ASATM

ATMVAWT

BBASBDDBFPBHP

BLDGBLDWN

BLWBMBOT

BSMTBTU

BTUHC

C/CCAVCCCD

CFMCFPCGCH

CHWCHWRCHWS

CJCL

CLGCLR

COCO2COL

CONCCOND

CONDRCONNCONTCONVCOPCP

CPFCRPCSRCT

CU FTCU IN

DBDC

DDCDEGFDEMODETDGDH

DHWDIADIMDLV

DMPRDP

DPSDRDSDTDW

DWG(E)

DEGREE FARENHEITDIAMETER OR PHASEAUTOMATIC AIR VENTABANDONABOVEAIR CONDITIONING UNITAIR COOLED CONDENSERAIR COOLED CONDENSING UNIT

ACCESS DOORABOVE FINISHED FLOORAIR HANDLING UNITAMBIENTACCESS PANELAPPROXIMATEARCHITECTURALAIR SEPARATORATMOSPHEREATMOSPHERIC VENTAVERAGE WATER TEMPERATUREBOILERBUILDING AUTOMATION SYSTEMBACKDRAFT DAMPERBACKFLOW PREVENTERBRAKE HORSEPOWERBUILDINGBLOWDOWNBELOWBEAMBOTTOMBASEMENTBRITISH THERMAL UNITBTU PER HOURCONVERTERCENTER TO CENTERCONSTANT AIR VOLUMECOOLING COILCEILING DIFFUSERCUBIC FEET PER MINUTECHEMICAL FEED PUMPCEILING GRILLCHILLERCHILLED WATERCHILLED WATER RETURNCHILLED WATER SUPPLYCONSTRUCTION JOINTCENTERLINECEILINGCLEAR

CARBON MONOXIDECARBON DIOXIDECOLUMNCONCRETECONDENSATECONDENSORCONNECTIONCONTINUATION / CONTINUOUSCONVECTORCOEFFICIENT OF PERFORMANCECONTROL PANELCHEMICAL POT FEEDERCONDENSATE RETURN PUMPCURRENT SENSING RELAYCOOLING TOWERCUBIC FEETCUBIC INCHESDRY BULBDRY AIR COOLERDIRECT DIGITAL CONTROLDEGREE FAHRENHEITDEMOLITIONDETAILDOOR GRILLEDOMESTIC WATER HEATERDOMESTIC HOT WATERDIAMETERDIMENSIONDOOR LOUVERDAMPERDEWPOINTDIFFERENTIAL PRESSURE SENSORDRAINDISCONNECT SWITCHDRAW THROUGHDOMESTIC WATERDRAWINGEXISTING

EAEA

EADEATED

EDBEEREF

EFFEGEJ

ELECENTEQERES

ESPET

EWBTEWTEXPEXT

FF/OFAFAIFB

FCUFCVFD

FDRFF

FLAFMDFPMFPTFSDFSSFT

FTRGA

GALGALVGNDGPMGRL

GSNKH

HCHFDHHW

HWHRHWH

HORIZHP

HPSHTGHTPHXHZIN

KWKX(L1)(L2)

LLATLBLD

LDBLL

LPSLWBTLWTMATMAXMBH

MBTUMCAMCCMD

MECHMEZZMFSDMIN

MISC

MV

EXHAUST AIREACH

EXHAUST AIR DAMPERENTERING AIR TEMPERATUREEXHAUST DIFFUSERENTERING DRY BULB TEMPERATUREENERGY EFFICIENCY RATIOEXHAUST FANEFFICIENCYEXHAUST GRILLEEXPANSION JOINTELECTRICALENTERINGEQUALEXHAUST REGISTERELECTRIC SUPPLYEXTERNAL STATIC PRESSUREEXPANSION TANKENTERING WET BULB TEMPERATUREENTERING WATER TEMPERATUREEXPANSIONEXTERIORFANFLAT OVALFROM ABOVEFRESH AIR INTAKEFROM BELOWFAN COIL UNITFLOW CONTROL VALVEFIRE DAMPERFLOOR DRAINFINAL FILTERFULL LOAD AMPFLOW MEASURING DEVICEFEET PER MINUTEFAN POWERED TERMINALCOMBINATION FIRE/SMOKE DAMPERFLOW SENSING SWITCHFEETFINNED TUBE RADIATIONGAUGEGALLONGALVANIZEDGROUNDGALLON PER MINUTEGRILLEGOOSENECKHUMIDITYHEATING COILHORIZONTAL FIRE DAMPERHEATING HOT WATERHEATING HOT WATER RETURNHEATING HOT WATER SUPPLYHORIZONTALHORSEPOWER

HIGH PRESSURE STEAMHEATINGHEAT TRANSFER PACKAGEHEAT EXCHANGERHERTZINCHESKILOWATTKITCHEN EXHAUST1 ACOUSTICAL DUCT LINING2 ACOUSTICAL DUCT LININGLINED DUCTWORKLEAVING AIR TEMPERATUREPOUNDLINEAR DIFFUSERLEAVING DRY BULB TEMPERATURELOW LEVEL

LOW PRESSURE STEAMLEAVING WET BULB TEMPERATURELEAVING WATER TEMPERATUREMIXED AIR TEMPERATUREMAXIMUMTHOUSAND BTUHTHOUSAND BTUMINIMUM CIRCUIT AMPACITYMOTORIZED CONTROL CENTERMOTORIZED DAMPERMECHANICALMEZZANINEMODULATING FIRE SMOKE DAMPERMINIMUMMISCELLANEOUS

MANUAL VENT

NIC

NONOPNNTSOA

OADOBDOCOD

OPNGOPWT

PPA

PCFPD

PENPERF

PFPGPHPL

POCPRVPSI

PSIAPSIGRA

RAD

RC

RDRDR

RGRH

RHG

RLRPMRRRSS

SASAD

SDSD

SEERSFSGSP

SPDSQ FT

SRSS

SSTSTST

STLSTM

STRUCTT

TATATBTG

THKTNLTYPUFD

UGNDUH

UONVAVVBVCVD

VFDVIFW/OWBWCWF

WFRWFSWG

WMSWSWTWW

NOT IN CONTRACT

NUMBERNORMALLY OPENNOT TO SCALEOUTSIDE AIROUTSIDE AIR DAMPEROPPOSED BLADE DAMPERON CENTEROUTSIDE DIAMETEROPENINGOPERATING WEIGHTPUMPPIPE ANCHORPOUNDS PER CUBIC FOOTPRESSURE DROPPENETRATIONPERFORATEDPRE-FILTERPRESSURE GAUGEPHASEPLATEPOINT OF CONNECTIONPRESSURE REDUCING VALVEPOUNDS PER SQUARE INCHPOUNDS PER SQUARE INCH (ABS)POUNDS PER SQUARE INCH (GAUGE)RETURN AIRRETURN AIR DAMPER

REHEAT COIL

RETURN DIFFUSERROOF DRAIN

RETURN GRILLRELATIVE HUMIDITYREFRIGERANT HOT GAS

REFRIGERANT LIQUID LINEREVOLUTIONS PER MINUTERETURN REGISTERREFRIGERANT SUCTION LINESLABSUPPLY AIRSEE ARCHITECTURAL DRAWINGS

SMOKE DAMPERSUPPLY DIFFUSERSEASONAL ENERGY EFFICIENCY RATIOSUPPLY FANSUPPLY GRILLESTATIC PRESSURESEE PLUMBING DRAWINGSSQUARE FEETSUPPLY REGISTERSTAINLESS STEELSTAINLESS STEELSOUND TRAP (ATTENUATOR)SURFACE TEMPERATURESTEELSTEAMSTRUCTURALTEMPERATURETRANSFER AIRTO LEVEL ABOVETO LEVEL BELOWTRANSFER GRILLETHICKTUNNELTYPICALUNDERFLOOR DUCTUNDERGROUNDUNIT HEATERUNLESS OTHERWISE NOTEDVARIABLE AIR VOLUMEVACUUM BREAKERVENT COILVOLUME DAMPERVARIABLE FREQUENCY DRIVE/CONTROLLERVERIFY IN FIELDWITHOUTWET BULBWATER COLUMNWATER FILTERWATER FILTER RETURNWATER FILTER SUPPLYWATER GAUGE OR WALL GRILLEWIRE MESH SCREENWATER SOFTENERWEIGHTWELL WATER

2-PORT THROTTLING VALVE (T)

THERMOSTAT

HUMIDITY SENSOR

STATIC PRESSURE SENSOR

CNDCNDRCNDS

CONDENSER WATERCONDENSER WATER RETURNCONDENSER WATER SUPPLY

MPS MED PRESSURE STEAMMPC MED PRESSURE CONDENSATE

LPC LOW PRESSURE CONDENSATE

(N)NANC

NFA

NEWNOT APPLICABLENORMALLY CLOSEDNET FREE AREA

HPC HIGH PRESSURE CONDENSATE

REFG REFRIGERATION SYSTEMREFGR REFRIGERATION RETURNREFGS REFRIGERATION SUPPLY

SCHWSCHWRSCHWS

SECONDARY CHILLED WATERSECONDARY CHILLED WATER RETURNSECONDARY CHILLED WATER SUPPLY

PLATE AND FRAME HEAT EXCHANGER

RCHWR RADIANT CHILLED WATER RETURNRCHWS RADIANT CHILLED WATER SUPPLY

RHHWRRHHWS

RADIANT HEATING HOT WATER RETURNRADIANT HEATING HOT WATER SUPPLY

CO

TS

R

DPS

CO2

O

T

H

SP

SS S M S S S

TT T M T S T

M S

M S

M S

M S

M S

M S

M S

M SUPSLOPE DIRECTION ARROW

DN

SB-V SUPPLY BOX - VARIABLESB-C SUPPLY BOX - CONSTANT

RB-V RETURN BOX - VARIABLERB-C RETURN BOX - CONSTANT

ACH AIR CHANGE RATE

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:46:

48 P

M

TITLE PAGE, SYMBOLS,ABBREVIATIONS, AND NOTES

MH0.1.1TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Page 4: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

TYPE##

TYPE##

DESCRIPTIONSYMBOLSYMBOL DESCRIPTION

SYMBOLS

CA

FLP

FLSS

CPF

ET

FBK

FAS

DI

DES

AS

C02

CHWS

AO

AI

AFT

SYMBOL

AFS

DESCRIPTION

ABBREVIATIONS

FIRE AND LIFE SAFETY SYSTEM

FAIL LAST POSITION

ANALOG INPUT

FEEDBACK

FIRE ALARM SYSTEM

EXPANSION TANK

DIGITAL INPUT

DAMPER END SWITCH

CHEMICAL POT FEEDER

CARBON DIOXIDE

CHILLED WATER SUPPLY

AIR SEPARATER

ANALOG OUTPUT

AIR FLOW TRANSMITTER

AIR FLOW SWITCH

AC ALARM CONTACT

AHU

CHWR CHILLED WATER RETURN

CS

CRAC

CURRENT SENSOR

COMPUTER ROOM A/C UNIT

DDCP

DC

DIRECT DIGITAL CONTROL PANEL

DRY COOLER

DPT

DO

DIFFERENTIAL PRESSURE TRANSMITTER

DIGITAL OUTPUT

DRS

EGCP

DAMPER RESET SWITCH

EMERGENCY GENERATOR CONTROL PANEL

EFSO

FCU FAN COIL UNIT

EMERGENCY FUEL SHUT OFF SYSTEM

FAN - CENTRIFUGAL

AIR-HANDLING UNIT

COMMON ALARM

FAN - PLENUM / PLUG

FAN - AXIAL

FILTER - PLEATED

FILTER - BAG

FILTER - CARBON

COIL - HEATING

COIL - COOLING

COIL - REHEATING

DAMPER

XX - DEVICE TYPEEQUIPMENT TAG

YY - DEVICE NUMBER

GWR

SCD

SD

I/P

PSH

PT

PSL

NC

NIC

FZ

HX

HT

FT

FSD

FMS

FMS

SMOKE DETECTOR

SMOKE CONTROL DAMPER

FIRE SMOKE DAMPER

PRESSURE TRANSMITTER

PRESSURE SWITCH LOW

PRESSURE SWITCH HIGH

NORMALLY CLOSED

NETWORK INTERFACE CONTROLLER

INTERNET PROTOCOL

HEAT EXCHANGER

HUMIDITY TRANSMITTER

FREEZE PROTECTION DEVICE (FREEZESTAT)

FLOW TRANSMITTER

FLOW MEASURING STATION

FACILITY MANAGEMENT SYSTEM

FLT FAULT

FSC

GWS GLYCOL WATER SUPPLY

MIV

LS

MOTORIZED ISOLATION VALVE

LEAK SENSOR

HWS

HWR

HOT WATER SUPPLY

HOT WATER RETURN

P

NO

PUMP

NORMALLY OPEN

PCV

PCD

PRESSURE CONTROL VALVE

PRESSURE CONTROL DAMPER

PDS

RFL RESETTABLE FUSIBLE LINK

PRESSURE DIFFERENTIAL SWITCH

FAN START CIRCUIT

GLYCOL WATER RETURN

TT

VES

THL

VAV

UH

TF

TEC

TCD

SW

TERMINAL EQUIPMENT C0NTROLLER

VALVE END SWITCH

VARIABLE AIR VOLUME

UNIT HEATER

TEMPERATURE HIGH LIMIT

TRANSFER FAN

TEMPERATURE C0NTROL DAMPER

SWITCH

ST STATUS

TCV

UPS UNINTERRUPTIBLE POWER SUPPLY

VFD VARIABLE FREQUENCY DRIVE

TEMPERATURE CONTROL VALVE

TEMPERATURE TRANSMITTER

BCP BOILER CONTROL PANEL

FS FLOW SWITCH

BMS BUILDING MANAGEMENT SYSTEM

CP CONTROL PANEL

A AQUASTAT

GCP GENERATOR CONTROL PANEL

CCP CHILLER CONTROL PANEL

EF EXHAUST FAN

FOCP FUEL OIL CONTROL PANEL

IMH IMMERSION HEATER

PUMP

COIL - PREHEATING

DAMPER - FIRE / SMOKE

C

PANIC BUTTON

UNDERFLOORTEMPERATURESENSOR

C

C

C

P

C

R

C

H

PI PRESSURE INDICATOR

TSD TOUCH SCREEN DISPLAY

XXYY

VARIABLE FRQUENCYDRIVE

MOTOR STARTER

VFD

HUMIDIFIER

PANEL(SEE ABBREVIATIONS)

XXX

THERMOWELL

AVERAGING ELEMENT

ACTUATOR - MOTOR

ACTUATOR - PISTON

VALVE - 2 WAY

VALVE - 3 WAY

MANUAL SWITCH

HORN / STROBE

STROBE

LOCAL HARD WIREDCONNECTION

XX - DEVICE TYPEBMS DEVICE

YY - DEVICE NUMBER

XX - DEVICE TYPENON-BMS DEVICE

YY - DEVICE NUMBER

ACTUATOR -DIAPHRAGM

M

ECC ENGINEERING CONTROL CENTER

TS TEMPERATURE SENSOR

ATU AIR TERMINAL UNIT

T ROOM THERMOSTAT

CV CONTROL VALVE

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:46:

51 P

M

CONTROL SYMBOLS,ABBREVIATIONS, AND NOTES

MH0.1.2TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

MECHANICAL SHEET INDEXSHEET DRAWING TITLE

MH4.1.1 HVAC SECTIONSMH0.1.1 TITLE PAGE, SYMBOLS, ABBREVIATIONS, AND NOTESMH0.1.2 CONTROL SYMBOLS, ABBREVIATIONS, AND NOTESMH0.2.1 HVAC SCHEDULESMH2.0.0 HVAC PLAN PRESSURIZATIONMH2.1.2 HVAC PLAN - LEVEL 2-4MH2.1.5 HVAC PLAN - ROOFMH2.1.1 HVAC PLAN - LEVEL 1MP2.3.1 HVAC PIPING PLAN - LEVEL 1MH5.1.1 HVAC CONTROLS DIAGRAMMH5.1.2 HVAC CONTROLS DIAGRAMMH5.1.3 HVAC CONTROLS DIAGRAMMH6.1.1 HVAC DETAILSMH6.1.2 HVAC DETAILSMH6.1.3 HVAC DETAILS

GENERAL NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

EXACT LOCATIONS OF ALL CEILING DIFFUSERS, REGISTERS AND GRILLES DETAILED ON THE ARCHITECTURAL REFLECTIVE CEILING PLAN, ANDARCHITECTURAL ROOM ELEVATIONS.

THE LOCATION OF ALL ROOF OPENINGS SHALL BE AS INDICATED ON THE MECHANICAL, STRUCTURAL AND ARCHITECTURAL DRAWINGS. COORDINATEEXACT SIZES OF OPENINGS REQUIRED.

ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. PROVIDE ALL FITTINGS,TRANSITIONS, DAMPERS, VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

ALL DUCTWORK SHALL BE CONSTRUCTED, ERECTED, AND TESTED IN ACCORDANCE WITH THE MOST RESTRICTIVE OF LOCAL REGULATIONS,PROCEDURES DETAILED IN THE ASHRAE HANDBOOK OF FUNDAMENTALS, OR THE APPLICABLE STANDARDS ADOPTED BY THE SHEET METAL AND AIRCONDITIONING CONTRACTORS NATIONAL ASSOCIATION.

DUCTWORK SHALL BE INSULATED OR LINED PER SPECIFICATIONS OR AS NOTED ON DRAWINGS. ALL DUCT JOINTS AND SEAMS SHALL BE SEALED PERSPECIFICATIONS.

DUCT AND PLENUM SIZES INDICATED ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS. WHERE DUCTWORK AND PLENUMS ARE INTERNALLY LINED,THEIR SIZES SHALL BE ADJUSTED TO PROVIDE THE INSIDE CLEAR DIMENSIONS INDICATED ON THE DRAWINGS.

MANUAL DAMPERS SHALL BE PROVIDED IN ALL DUCT BRANCHES AND IN ALL BRANCHES TO INDIVIDUAL DIFFUSERS, GRILLES AND REGISTERS.

ALL EQUIPMENT, DUCTS, PIPING, AND OTHER DEVICES AND MATERIALS INSTALLED OUTSIDE OF THE BUILDING OR OTHERWISE EXPOSED TO THEWEATHER SHALL BE COMPLETELY WEATHERPROOFED.

PROVIDE AN INSULATED SHEET METAL DRAIN PAN BELOW ALL CEILING HUNG FAN COIL UNITS. DRAIN PAN SHALL BE 4" DEEP AND SHALL EXTEND 6"BEYOND THE EDGE OF THE FAN COIL. PROVIDE TRAP AND DRAIN PIPING.

INSTALL DUCT MOUNTED SMOKE DETECTORS PER CODE REQUIREMENT..

PROVIDE METAL COVER PLATES FOR ALL PIPES LOCATED AT FLOOR LEVEL TO PREVENT PIPE DAMAGE. PLATES SHALL NOT BE DAMAGED BY NORMALMAINTENANCE TRAFFIC.

Page 5: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

DIFFUSER, REGISTER, GRILLE SCHEDULETYPE FUNCTION FACE SIZE FACE TYPE NOTESCD-1 SUPPLY AIR 24" x 24" SQUARE PANEL 1, 2, 4, 5, 9CD-2 SUPPLY AIR 4'-0" LONG (4) 3/4" SLOT DIFFUSER 1, 2, 3, 6, 9CD-3 SUPPLY AIR 4'-0" LONG (4) 3/4" SIDE WALL SLOT DIFFUSER 1, 2, 3, 6, 9CD-4 SUPPLY AIR 12" x 12" SQUARE PANEL 1, 2, 4, 5, 9

RG-1 RETURN AIR 24" x 24" SQUARE PANEL 1, 2, 4, 5, 9RG-2 RETURN AIR 4'-0" LONG (4) 3/4" SLOT DIFFUSER 1, 2, 3, 6, 9RG-3 RETURN AIR 4'-0" LONG (4) 3/4" SIDE WALL SLOT DIFFUSER 1, 2, 3, 6, 9RG-4 RETURN AIR 12" x 12" SQUARE PANEL 1, 2, 4, 5, 9

EG-1 EXHAUST AIR 24" x 24" SQUARE PANEL 1, 2, 4, 5, 9EG-2 EXHAUST AIR 12" x 12" SQUARE PANEL 1, 2, 4, 5, 8, 9EG-3 EXHAUST AIR 8" x 8" DUCT MOUNTED GRILLE 2, 4, 7, 9

NOTES:1. REFER TO ARCHITECTURAL CEILING PLANS FOR LOCATION OF CEILING DIFFUSERS AND REGISTERS.

2. ALL BRANCH DUCTWORK TO INDIVIDUAL DIFFUSERS AND REGISTERS SHALL BE PROVIDED WITH VOLUME DAMPERS,

PROVIDE CEILING ACCESS PANELS FOR DAMPERS LOCATED ABOVE HARD CEILINGS.

3. ALUMINUM CONSTRUCTION.

4. STEEL CONSTRUCTION.

5. 4-WAY BLOW UNLESS NOTED OTHERWISE.

6. PROVIDE FACTORY PLENUM BOX.

7. EXHAUST GRILLES SHALL BE HARD DUCT CONNECTED.

8. PROVIDE DAMPER REMOTE OPERATOR TO ALL DAMPERS ABOVE HARD CEILINGS.

9. PROVIDE NECK SIZED TO ACCOMMODATE BRANCH DUCT SIZE SPECIFIED, UNLESS SHOWN OTHERWISE. REFER TO TABLE BELOW FOR NECK SIZE.

DIFFUSER/GRILLE BRANCH DUCT SIZES (CD-1, CD-4, RG-1, EG-1, EG-2, RG-4)

MAX CFM NECK/BRANCH DUCT SIZES

0 - 180 CFM 8" DIA.

185 - 280 CFM 10" DIA. `

285 - 400 CFM 12" DIA.

405 - 500 CFM 14" DIA.

505 - 700 CFM 16" DIA.

705-1200 CFM 18 x 18

1205-1600 CFM 22 x 22

> 1600 CFM SEE DRAWINGS

LINEAR DIFFUSER PLENUM NECK SIZES (CD-2, CD-3, RG-2, RG-3)

MAX CFM NECK/BRANCH DUCT SIZES

0 - 160 CFM 8" DIA.

165 - 250 CFM 10" DIA.

250 - 350 CFM 12" DIA.

350 - 500 CFM 14" DIA.> 500 CFM SEE DRAWINGS

ROOM VENTILATION AND PRESSURIZATION SUMMARY SCHEDULEROOM CMC CMC DESIGN DESIGN

ROOM ROOM CMC AREA DESIGNATION (TABLE 4-A) ROOM CEILING ROOMPRESS. MIN MIN MINIMUM MAXIMUM

NO. NAME OCCUPANCY CATEGORY (TALBE 4-1) AREA HEIGHT VOLUME CODE VENT VENT VENT VENT(FT2) (FT) (FT3) (NR/N/P) (ACH) (CFM) (CFM) (CFM)

A1-148 CONFERENCE ADMINISTRATIVE 240 9 2160 NR 4.0 144 146 460A1-147 OFFICE ADMINISTRATIVE 117 9 1053 NR 4.0 70 76 360A1-145 OFFICE ADMINISTRATIVE 117 9 1053 NR 4.0 70 76 360A1-143 SHARED MENTAL HEALTH OFFICE ADMINISTRATIVE 120 9 1080 NR 4.0 72 76 390A1-141 SHARED SOCIAL WORK OFFICE ADMINISTRATIVE 186 9 1674 NR 4.0 112 116 550

A1-140B SUB-WAITING WAITING AREA 337 9 3033 NR 12.0 607 854 860A1-140D VESTIBULE PATIENT AREA CORRIDOR 106 9 954 NR 2.0 32 117 710A1-140 WAITING WAITING AREA 1033 9 9297 NR 12.0 1,859 2,593 2,590

A1-140A RECEPTION WAITING AREA 165 9 1485 NR 12.0 297 423 420A1-142 ELIGIBILITY/COPY ADMINISTRATIVE 115 9 1035 NR 10.0 173 183 180A1-144 OFFICE ADMINISTRATIVE 115 9 1035 NR 4.0 69 76 90A1-146 SHARED OFFICE ADMINISTRATIVE 210 9 1890 NR 4.0 126 136 150A1-149 OFFICE ADMINISTRATIVE 117 9 1053 NR 4.0 70 76 350A1-151 OFFICE ADMINISTRATIVE 138 9 1242 NR 4.0 83 85 750A1-150 TOILET M/W TOILET ROOM 51 9 459 N 10.0 77 84 80A1-152 TOILET M/W TOILET ROOM 51 9 459 N 10.0 77 84 80

A1-C002 CORRIDOR PATIENT AREA CORRIDOR 415 9 3735 NR 2.0 125 131 130A1-203 EXAM 1 TREATMENT AND EXAMINATION ROOMS 149 9 1341 6.0 134 141 140

AIR TERMINAL UNIT, SINGLE DUCT SCHEDULEUNIT NO. AHU NO.

SERVEDCFM UNIT INLET

SIZE(INCHES)

HOT WATER HEATING COIL

MIN MAX ENT AIR TEMP(degF) GPM ROWS APD CONTROL

VALVE

BRANCHPIPE SIZE

(IN)SB-V-10 1 230 710 10 58 0.6 1 0.02 2-WAY 0.75SB-V-11 1 165 550 8 58 0.5 1 0.02 2-WAY 0.75SB-V-12 1 145 390 8 58 0.3 1 0.01 2-WAY 0.75SB-V-13 1 325 1,080 12 58 0.9 1 0.02 2-WAY 0.75SB-V-14 1 230 750 10 58 0.6 1 0.02 2-WAY 0.75SB-V-15 1 145 460 8 58 0.3 1 0.01 3-WAY 0.75SB-C-4 1 1,160 1,160 12 58 3.1 1 0.16 3-WAY 0.75SB-C-5 1 1,390 1,390 14 58 4.1 1 0.11 2-WAY 0.75SB-C-6 1 1,360 1,360 14 58 4.0 1 0.11 2-WAY 0.75SB-C-8 1 650 650 10 58 1.9 1 0.10 2-WAY 0.75RB-V-10 1 230 710 10RB-V-11 1 165 550 8RB-V-12 1 145 390 8RB-V-13 1 325 1,080 12RB-V-14 1 230 750 10RB-V-15 1 145 460 8RB-C-4 1 1,680 1,680 14RB-C-5 1 960 960 12RB-C-6 1 1,300 1,300 14RB-C-7 1 320 320 8RB-C-8 1 550 550 8

NOTE:1. BRANCH DUCT CONNECTED TO TERMINAL UNIT TO BE SIZED SIMILAR TO UNIT INLET SIZE WITHIN 10 FEET LENGTH.

BEYOND 10 FEET (WHEN NOT SPECIFIED), THE BRANCH DUCT SHOULD BE NEXT LARGER SIZE.2. BRANCH PIPE SIZE CONNECTED TO TERMINAL UNIT TO BE SIZED SIMILAR TO CONNECTION SIZE, UNLESS OTHERWISE

SPECIFIED.

HEATING(CFM)

HEATING CAPACITY(BTUH)8937 2306641 1655800 14513154 3258937 2305795 14530042 1,16039500 1,39039050 1,36018522 650

AIR HANDLING UNIT SCHEDULE (1/3)

SUPPLY FAN (AHU-1S) RETURN/ EXHAUST FAN (AHU-1R)

MOTOR DATA MOTOR DATAOA CFM TOTAL EXTERNAL TOTAL CFM TOTAL EXTERNAL TOTAL

AREA DESIGN DESIGN PER SP. SP OPER FAN FAN TOTAL DESIGN PER SP. SP OPER. FAN FAN TOTALITEM MANUF. MODEL # LOCATION SERVED CFM CFM TYPE QTY FAN IN. W.G. IN W.G. RPM BHP BHP HP HP RPM VOLT PH HZ CFM TYPE FAN QTY IN. W.G. IN W.G. RPM BHP BHP HP HP RPM VOLT PH HZ

AHU-1 (S/R) ALLIANCE AIR 4SV-22.5 ROOF EMERGENCY DEPARTMENT 10,000 10,000 FAN WALL 4 2,500 4.00 2.50 3136 3.22 12.88 5.0 20.0 1800 460 3 60 10,000 PLUG 2,500 4 4.00 2.50 3703 2.67 10.68 3.0 12.0 3600 460 3 60

AIR HANDLING UNIT SCHEDULE (3/3)UNIT SOUND DATA VIBRATION ISOLATION

UNIT SUPPLY SOUND POWER (dB re 10^12W) (AHU-1S) UNIT EXHAUST OUTLET SOUND POWER (dB re 10^12W) (AHU-1R) UNIT CASING RADIATED SOUND POWER, SUPPLY(dB re 10^12W) (AHU-1S) UNIT CASING RADIATED SOUND POWER, EXHAUST (dB re 10^12W) (AHU-1R)ISOLATOR

TYPEAREA 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k DEFL'NITEM MANUF. MODEL # LOCATION SERVED (IN)

AHU-1 (S/R) ALLIANCE AIR 4SV-22.5 ROOF EMERGENCY DEPARTMENT 79 80 85 88 76 77 77 73 75 71 64 64 59 59 62 60 75 73 69 66 52 57 59 58 74 70 56 56 50 43 44 39 SS 1

NOTES:1. PROVIDE PRE-FILTERS AND FINAL FILTERS.2. PROVIDE VFD FOR EACH FAN.3. AREA SMOKE DETECTORS HARDWIRED INTERLOCK TO AHU FANS AND TO FIRE ALARM CONTROL PANEL.4. ROUTE AHU CONDENSATE TO NEAREST ROOF EQUIPMENT DRAIN.

AIR HANDLING UNIT SCHEDULE (2/3)

COOLING COIL DATA (AHU-1S) HEATING COIL DATA (AHU-1S)

AIRSIDE WATERSIDE AIRSIDE STEAMTOTAL SENSIBLE AIR ENTERING LVG ENTERING LEAVING MIN. ENTERING LVG STEAM PSIGCAP. CAP. AREA ROWS/ FPM PD DB WB DB WB FLOW WATER PD CAP. AREA ROWS/ FPM PD DB DB ENT ENT CVMBH MBH SQ FT QTY IN WG DEG F DEG F DEG F DEG F DEG F DEG F GPM FT MBH SQ FT QTY IN WG DEG F DEG F CV COIL LBS/HR

497 450 22.5 6/2 445 0.51 93 68 52 52 44 55 87 4.8 430 22.5 1/2 445 0.035 31 71 30 15 228

MCA(A)

MOCP(A)

33 40

MCA(A)

MOCP(A)

21 25

5. PROVIDE SINGLE POINT OF CONNECTION FOR EACH SUPPLY AIR AND EXHASUT/RETURN AIR UNIT.

WEIGHT(LBS)

AHU-1SUNIT

13500 8000

6. PROVIDE SPACE OR SLOT FOR ADDING CARBON FILTER IN THE FUTURE.

OADESIGN

CFMMIN

5,500

7. PROVIDE PRE-HEATING COIL AIR BY-PASS.

AHU-1RUNIT

FAN SCHEDULEFAN NO. MANUFACTURER & MODEL LOCATION AREA SERVED FAN

CFMDELIVERED

CFMLEAKAGE

CFM TSP(IN)

FANTYPE DISCHARGE

WHEELRPM

MOTORVFD(Y/N)

NOTESTYPE DIA (IN) BHP HP VOLT/PHASE

EF-1 GREENHECK SWB-206 ROOF ISOLATION SUITE 500 380 20 2 UTILITY UPBLAST CENTRIFUGAL 11.38 3210 0.67 0.75 460/3 NEF-2 GREENHECK SWB-206 ROOF ISOLATION SUITE 500 380 20 2 UTILITY UPBLAST CENTRIFUGAL 11.38 3210 0.67 0.75 460/3 N

NOTES:1. PROVIDE MOTOR HOUSING AND ADJUSTABLE DRIVE.2. PROVIDE WITH TEFC MOTOR.3. FANS IN EMERGENCY POWER.4. CONTRACTOR TO INSTALL BACK DRAFT DAMPER.5. PROVIDE SEISMIC SNUBBERS. SEISMIC SNUBBERS SHALL BE ADJUSTED AFTER FANS ARE OPERATED AND ADJUSTMENT OF SPRINGS HAS ACCOMMODATED LATERAL MOVEMENT AND THRUST.6. FANS ARE IN RUN AND STAND-BY FAN ARRANGEMENT.7. NEGATIVE ISOLATION ROOM EXHAUST SHALL BE LABELLED IN ACCORDANCE WITH UMC - "NEGATIVE-PRESSURE ISOLATION ROOMS - EXHAUST SYSTEMS". FOR CONTAINMENT APPLICATION, PROVIDE WEATHER PROOF LABELS ON DUCTS, PLENUMS AND DISCHARGE STACK. EXHAUST DUCT SYSTEM SERVING NEGATIVE ISOLATION ROOM SHALL BE CONTINUOUSLY WELDED.

8. PROVIDE INTERFACE CONTACTS/CONTROLS.9. ALL EXHAUST STALLS SHALL BE SELF-DRAIN TYPE, PROVIDE SCROLL DRAINS ON ALL FANS.10. PROVIDE FACTORY FURNISHED SUPPORT BASE WITH FIELD INSTALLED MOUNTING BRACKETS.11. EXHAUST FAN DISCHARGE SHALL BE MINIMUM 25 FEET AWAY FROM ANY AIR INTAKE INTO THE BUILDING AND 15 FEET ABOVE ROOF LEVEL.

AIR FILTER SCHEDULESYSTEM FILTER MANUFACTURER

RATEDEFF %

MAX SP DROPHOUSING TYPEINITIAL FINAL

EF-1 PRE-FILTER CAMFILL - FARR MERV 9 0.1 0.65 12" RIGIDBAG FILTER 99.97% 0.35 1 BAG-IN, BAG-OUT

NOTES:1. HOUSING PROVIDED BY FILTER MANUFACTURER.2. PROVIDE TEMPORARY CONSTRUCTION FILTERS, 2 SETS EACH. CHANGE AS REQUIRED.3. NUMBER AND SIZE AS REQUIRED BY UNIT MANUFACTURER.

NOTES

PRE-FILTERBAG FILTERPRE-FILTER

FILTERFINAL FILTER

EF-2

AHU-1S

CAMFILL - FARRCAMFILL - FARRCAMFILL - FARRCAMFILL - FARRCAMFILL - FARRCAMFILL - FARR

MERV 999.97%MERV 9MERV 9

95%

0.1.350.10.10.5

0.651

0.650.65

1

12" RIGIDBAG-IN, BAG-OUT

12" RIGID12" RIGID12" RIGID

1, 2, 31, 2, 31, 2, 31, 2, 31, 2, 31, 2, 31, 2, 3

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:46:

53 P

M

HVAC SCHEDULES

MH0.2.1TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Page 6: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

SARAEXHPRESS

110140

0( - )

SARAEXHPRESS

710710

0( = )

SARAEXHPRESS

550550

0( = )

SARAEXHPRESS

390390

0( = )

SARAEXHPRESS

360360

0( = )

SARAEXHPRESS

360360

0( = )

SARAEXHPRESS

350350

0( = )

SARAEXHPRESS

750750

0( = )

SARAEXHPRESS

180180

0( = )

SARAEXHPRESS

90900

( = )

SARAEXHPRESS

150150

0( = )

SARAEXHPRESS

60-90( - )

SARAEXHPRESS

60-

90( - )

SARAEXHPRESS

90060

( + )

SARAEXHPRESS

25902590

0( = )

SARAEXHPRESS

460460

0( = )

SARAEXHPRESS

3000

380( - )

CONS

TRUC

TIO

N ST

AGIN

G A

REA

SARAEXHPRESS

0080( - )

N.I.C. N.I.C.

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:46:

57 P

M

HVAC PLAN PRESSURIZATION

MH2.0.0TY ATJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 HVAC Plan Pressurization

Page 7: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

10 0

10 0

25 0

14 x1 0

825 0

18 x1 2

8

12

60

25 0

( E ) 1 6 - 1 0 7

21 0

8

610

( E )16 x14

680

1214

x106

80

23 0

( E ) 1 6 - 1 0 6

(E)1

0x12

70

6

8

6 80 11 0

8

8

11 0

( E ) 1 6 - 1 0 4

12

108

11 0

16 x1 4

6

18 0

12

8

(E)1

6-11

2

10x1

0 8

( E ) 1 6 - 1 0 0

8

10

6

10

( E ) 1 6 - 1 1 412 x1 2

18 0

10

11 0

21 0

(E)1

5-10

7

(E)1

5-10

5

(E)1

6-10

5

(E)1

5-10

8(E

)15-

109

16x1

2

13 0

8

8

10

10 0

12 0

12 0

14

(E)1

6x12

10

30 0

CTE

14 0

14 0

10

35 0

12 0

18 x1 4

11 0 8

35 0

28 0

28 0

23 0 8

23 0

10

14x1

0

58 5

13 0

62 516 x1 2

13 08x6

(E)

(E)

(E)

(E)

( E)14 x10

(E)1

6x8

(E)8

x8

10x1

014

x12

( E )34 x12

(E)1

6x12

(E)1

5-11

3

(E)1

5-11

2

(E)1

5-11

0

(E)1

5-10

0

12

( E)8x10

( E)8x10

15 0

10

8

11 0

11 0

812 x1 0

58 0

80

80

6

8

11 0

11 0

39 0

18 0

50

8

6

12 0

10 0

10 0

80

12

16x1

2

(E )DUCT UP TO( E ) E F / 7 9

8x8

8x88x8

6x6

8

10

8x8

13 06x6

10 06x6

6x6

6x6

( E) 8x8

906x6

906x6

6

6

8

8

6

6

18x1

4

8x8

8x8

8x8

8x8

6x6

6x6

6x6( E ) 1 5 - 1 1 7

12 x1 2

8x8

8

18 08x8

6x6

8x86x6

6x6

8x8

8

8x8

8x8

6x68x8

6x6

6

10 06x6

6

6x6

6x6

8x8

6x6

28 08x8

6x6

6x6

6

8x8

8x8

10

20 x1 4 16 x1 4

28X1

8

1214

30U.C.

FSD

34 08x8

1 5 - 1 1 2

UP

10

8

1 5 - 1 1 3

1 5 - 1 1 0

12x1

2

6x6

1 6 - 1 0 412 06x6

1 6 - 1 0 0

( E)18 x14

1 6 - 1 1 2

T S - 61 6 - 1 2 0

6x6

21 08x8

1 6 - 1 0 5

1 5 - 1 0 8

34 08x8

8x8

1 5 - 1 0 98x6

16 08x8

16 08x8

8x8

8

14 x1 0

6x6 10

8x8

6x6

8x8

51 010 x1 0

14 x1 0

8x8

42x20

1 6 - 1 1 9

1 6 - 1 1 5

8

8x8

8x8

8x8

8

10 x1 0

CVV

1

CVV

2

(E)1

0x10

26x1

4

8

51 010 x1 0

506x6

506x6

30U.C.

21 08x8

10

8

16 06x6

108x8

1 5 - 1 0 7

10

8 6

8

8

10

34 x1 8

10x 8

34 x1 8 30 x1 8 28 x1 6

16x1

2

( E )36 x20( E)44 x20

8x6

( E ) 1 6 - 1 0 8

28 x1 624 x1 424 x1 216 x1 0

1 5 - 1 0 5

44 x2 2

8

FSD

FSD

1 6 - 1 0 6

8

8

10

8

FSD

FSD

FSD

FSD

FSD

FSD

8

FSD's

FSD

stacked

FSD10

FSD

FSD

T

T

T

T

T

T

T

T

T

TTT T

TT

T

T

T

S

S

VDVD

VD

VDVD

VD

FSD

FSD

FSD FSD FSD

FSD

FSD

FSD

FSD

FSD

FSD

FSD

FSD

FSD

FSD

VD

VDVD

VD

VD

FSD

FSD

VD

VD

VD VD

VD

FSD

H

F

G

E

12345678

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

26' - 0" 26' - 0" 26' - 0" 26' - 0" 26' - 0"26' - 0"

(E) ADMINELEGIBILITY

A1-100

WORKINGPOINT CORNEROF EXISTINGBLDG 100

I

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09

J

J.2

26' -

0"

26' -

0"

6' -

0"26

' - 0

"26

' - 0

"26

' - 0

"

(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

N 36' - 10 1/8"E 384' - 6 9/32"

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

CONS

TRUC

TIO

N ST

AGIN

G A

REA

52/84

11/36

14/36

SC 1-5

30

55

31/96

4/36

26/36

SC 1-5:9/48

MAX

IMUM

TRA

VEL

DIST

ANCE

WIT

HIN

A SU

ITE

TOHO

RIZO

NTAL

EXI

T =

45'-8

"

AMBULANCEROUTE

EXITDOOR #4

EXITDOOR #3

EXITDOOR #1

EXITDOOR #5

LIMITS OF CONSTRUCTION.

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

SERVICEELEVATORSUSED TO HAULDEBRISOFF SITE FROMUPPER FLOORS ANDROOF.

2.08

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

9/48

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

MAXIMUM TRAVEL DISTANCEWITHIN A SUITE TO HORIZONTALEXIT = 83'-7"

H

F

G

E

12345678

3MH4.1.1

1MH4.1.1

I

J

J.2

SB-C44

RB-C44

RB-V99

SB-V99

RG-1(140)

CD-1(140)

14"øSA

24"x12"RA

16"x12"RA

SB-C55

RB-C55

SB-C66

RB-C66

SB-V1010

RB-V1010

10"øSA10"øRA

SB-C77

RB-C77

SB-C88

RB-C88

SB-V1111

RB-V1111

18"x12"SA

18"x12"SA

34"x1

4"RA

34"x1

4"SA

34"x14"RA

32"x12"SA

12"øSA20"x12"SA

14"øSA

16"x14"SA

SB-V1212

RB-V1212

SB-V1313

RB-V1313

SB-V1414

RB-V1414

SB-V1515

RB-V1515

16"x12"SA

8"øE

A

T

T

T T

T

T

T T TT

T

T

RG- 1(375)

RG- 1(375)

CD- 1(375)

CD- 1(375)

CD- 1(460)

RG- 1(460)

CD- 1(360)

RG- 1(360)

CD- 1(360)

RG- 1(360)

CD- 1(360)

RG- 1(360)

RG- 1(390)

CD- 1(390)

RG- 1(550)

CD- 1(550)

CD- 1(65)

CD- 1(180)

RG- 1(180) RG- 1

(90)

CD- 1(90)

RG- 1(150) CD- 1

(150)

RG- 1(130)

CD- 1(50)

CD- 1(50)

EG- 1(80)

EG- 1(80)

CD- 1(65)

RG-3240

(TYP 9)

CD-3290

(TYP 4)

CD-3290

(TYP 3) (TYP 2)

CD-2290

(TYP 2)

RG-2355

(TYP 2)

CD-2355

(TYP 2)

CD-3260

(TYP 5)

CD-3260

(TYP 5)

RG- 1(160)

RG- 1(160)

CD- 1(160)

CD- 1(160)

CD-2(160)(TYP 4)

RG-2(110)(TYP 4)

CD- 1(50)

EG- 1(80)

CD-1(300)

CD-1(100)

RG-1(130)

CD-1(100)

RG-1(130)

8"øSA

10"øSA

10"ø

RA 8"øR

A

12"øRA

8"øR

A

8"øRA

8"øSA

8"øRA

CD-1(110)

CD-1(120)

CD-1(100)

CD-1(100)

RG-1(200)

RG-1(130)

CD-1(170)

RG-1(200)

CD-1(130)

CD-1(120)

CD-1(80)

RG-1(160)

CD-1(290)

CD-1(290)

CD-2(90)

RG-1(130)

RG-1(120)

RG-1(100)

RG-1(140)

RG-1(110)

EG-2(90)

CD-1(170)

CD-1(170)

RG-1(320)

CD-1(140)

CD-2(160)

CD-1(100)

RG-1(130)

CD-1(100)

RG-2(90)

CD-1(115)

CD-1(115)

RG-1(200)

RG-4(130)

RG-2(170)CD-2

(160)RG-2(170)

CD-2(160)

RG-2(170)

CD-2(160)

RG-2(170)

CD-2(160)

RG-2(90)

RG-18(90)

RG-2(90)

CD-2(160)

CD-22(160)

RG-24(90)

CD-2(160)

CD-2(270)

RG-2(270)

CD-2(270)

RG-2(270)

CD-2(160)

RG-5(160)

CD-51(90)

CD-1(190)

CD-4(60)

CD-5(330)

CD-17(330)

SB-V66

SB-C11

SB-V33

SB-V22

SB-C22

SB-V44

RB-V44RB-C

22

RB-V33

RB-V22

RB-V66

SB-V88

RB-C33

RB-V77

SB-V77

RB-V55

SB-V55

RB-C11

SB-C33

RB-V88

SB-C99

SB-V11 RB-V

11

RG-1(200)

CONS

TRUC

TIO

N ST

AGIN

G A

REA14"øEA

8"x8"EA

(LOW LEVELEXHAUSTGRILLES)(TYP.2)

TOILETEXHAUSTGRILLE

14"ø

EA

8"x8"EA

EG-1(80)

RG-2(240)

CONNECT TONEAREST (E) TOILETEXHAUST SYSTEM

1

40"x2

6"RA

40"x2

6"SA

34"x14"RA

34"x14"SA

34"x1

4"SA

34"x1

4"RA

N.I.C.

N.I.C.

N.I.C.

EG-3(150)

3

16"x12"RA

14"RA

14"RA

16"RA

18"x12"RA

12"x12"SA

12"øRA

10"øRA

12"øSA

10"øSA

8"øSA

16"x12"RA

32"x12"RA

4

2

(TYP 2)

1

DUCT RISERS UPTHROUGH ROOF

CO2

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:47:

15 P

M

HVAC PLAN - LEVEL 1

MH2.1.1TY ATJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Phase 3 - Level 1 HVAC PlaN

TEST AND BALANCE ALL NEW AIR OUTLETS TO REGULATE AIRFLOW (CFM)

INSTALL NEW DUCTWORK WITH APPROPRIATE DUCTSUPPORT AND HANGER WITH ALL REQUIRED ACCESSORIES.

PROVIDE STAINLESS STEEL EXHAUST AIR DUCT FORNEGATIVE ISOLATION EXHAUST SYSTEM

1 14X4 EAD TO LOW LEVEL EXHAUST GRILLES (12X8), MIN3", MAX 4" ABOVE FINISHED FLOOR, (TYP 2)

ANTE ROOM SHALL HAVE THE SAME AIRFLOW ASEXISTING. REBALANCE AIRFLOW TO CONFIRM.

REMOVE (E) EXHAUST DUCTWORK INCLUDING (E)GRILLE AND ASSOCIATED (E) ACCESSORIES. CAPDUCTWORK WHERE SHOWN.

REMOVE (E) CEILING DIFFUSERS AND (E) RETURNGRILLES TO COORDINATE WITH (N) INSTALLATION OFSUPPLY DIFFUSERS AND CEILING GRILLES AS SHOWN.

2

3

1.

2.

3.

4

Page 8: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

15-205

15-21115-21015-20715-206

15-204

15-224

15-225

15-226

15-228

15-229

D

15-2

0915

-208

RA2.50

DDD

D

D

D

A2.51

DRH5.16

15-227

R

R

R

D 24x14 22x12

12x8

20x1422x14

26x14

26x16 24x14

12x8

10x1020x14

32x16 28x16

10x8

8x6

14x1216x12

12x8

20x16

12x1

012

x8

10"–

12x8

16x12

14x1

0

R

D

D

16x12

RH5.14

RH5.15

2

10x8

8x6L

A2.43A

15x3%%143

18x6L12x6L

c

a

b

A2.42

A2.44

10x8

8x6

8x8

10x8

10x8 10x8

8x8

8x6

10x8

10x8

8x6

10x68x6

8x6

12x1010x6

30x18 FB,44x18 TA

10"–10x10

10x8L

8x6L

8x88x6

8"–3

16x12

8x6

8x6

10x8

7

2

77

A2.43B

8"–

8 TYP.

0 SF

0 SF

0 SF

30 SF

89 SF

168 SF

211 SF 211 SF

78 SF

69 SF

78 SF

212 SF

68 SF

116 SF 113 SF 114 SF 114 SF

68 SF

243 SF

27 SF

39 SF

63 SF

128 SF

113 SF

93 SF

90 SF

123 SF

VD

VD

15-327

RH3.16

A3.67

D

A3.68

15-3

0815

-309

15-329

15-32815-326

15-325

15-324

15-304 15-305

15-307 15-310 15-311

15-306

D

R

D

R R

D

R

RRR

10x8

24x1226x12

24x14

10x10

10"–

20x12

14x1

0

10x8

12x1

0

22x14

20x18

28x16

10x8

30x16

14x1

0

16x1220x16

10"–

20x16

16x1010x8

18x14

26x16

16x1

2

10x10

D

D

D

R

D

10x8 10x8

8x6

10x8

8x8

8x6 8x6

10x88x6L10x8L

12x6L

14x4L

8x6L

8x6L

8x6 8x6

8x6

10x10

10x8L 8x6

8x6

8x6

8x6 10x6

a

b

c

8x6L

10x8L

18x6L

RH3.15

2

A3.62

A3.60

A3.61A

8x6L

A3.66

52x18 TA,44x18 FB

10x6

10x10

16x14

12x10

10x10

38"–

2

6

66

A3.61B

7 , TYP.

20x18

10x6

FSD

VD

(E) C. UTILA2-122

(E) MEDA2-120A

S. UTILA2-150

(N) MECHSHAFT

H

F

G

E

34

3MH4.1.1

1MH4.1.1

I

CD-4(120)

CD-1(100)

RG-1(80)

1 2

14"øEAN.I.C.

2

40"x26"RA 40"x26"SA

H

F

G

E

34

3MH4.1.1

1MH4.1.1

I

CD-1(100)

8"øSA

8"øSA

CD-4(120)

CD-4(130)

CD-1(100)

RG-1(80)

1 2

8"øSA

8"øSA

12"x12"EA

14"Ø EAFROM BELOWTO ROOF

14"Ø EA TOABOVE

40"x26 RA

40"x26 SA

N.I.C.3

3 3

40"x26"RA40"x26"SA

(E) MEDA4-120A

32 SF

HACA4-150

46 SF

STFA4-152

(E) CLEANUTILITYA4-126

(N) MECH.SHAFT

H

F

G

E

34

3MH4.1.1

1MH4.1.1

I

40"x26" SA UP

FSD

FSD

1 2

14Ø" EA UP

N.I.C.

40"x26" RA UP

40"x26"RA40"x26"SA

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:47:

21 P

M

HVAC PLAN - LEVEL 2-4

MH2.1.2TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Phase 1 - Partial Level 2 HVAC Plan 1/8" = 1'-0"2 Phase 1 - Partial Level 3 HVAC Plan

1/8" = 1'-0"3 Phase 1 - Partial Level 4 HVAC Plan

1 PROVIDE MINIMUM 6 INCHES CLEARANCE BETWEENDUCTS.

2 PROVIDE MINIMUM 6 INCHES CLEARANCE AT SHAFTAROUND DUCT.

3 PROVIDE DUCT WRAP TO DUCTWORK THAT EXITS THERATED SHAFT.

1. TEST AND BALANCE ALL NEW AIR OUTLETS TO REGULATE AIR FLOW(CFM)

2. INSTALL NEW DUCTWORK WITH APPROPRIATE DUCT SUPPORT ANDHANGER WITH ALL REQUIRED ACCESSORIES.

Page 9: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

EF41EF79

2" VTR

4" VTR

H

F

G

E

12345678

I

EF1

EF1

EF1

EF2

EF2

EF2

DISCHARGE 10'-0"ABOVE ROOF FLOOR

FILTER HOUSING

6" CONCRETE PAD

OUTSIDE AIR

EXHAUST / RETURN UNIT

SUPPLY UNIT

AHU1R

AHU1R

AHU1R

AHU1S

AHU1S

AHU1S

40"x26" RA

40"x26" BYPASS

EXHAUST AIR

40"x26" SA

40"x26"

40"x26"SA

40"x2

6" 40"x2

6"RA

2-1/2" STEAM (MPS/MPR)PIPES FROM LEVEL 4,TAPPED AT (E) STEAMLINES SERVING AHU-15

3-1/2" CHWS/CHWR PIPESFROM LEVEL 4, TAPPEDAT (E) CHW PIPESSERVING AHU-15

CONDENSATE DRAIN LINE TONEAREST EQUIPMENT DRAIN,PIPE SIZE TO MATCHEQUIPMENT CONNECTION SIZE.

2-1/2" STEAMSUPPLY/RETURN

3-1/2" CHWS/CHWR

14"øEA

14"øEA

RA DUCT FROMBELOW

SA DUCT FROMBELOW

EA DUCT FROMBELOW

FILTER HOUSING

H

678

I

PIPES UPTO ROOF

POINT OF CONNECTIONTO EXISTING STEAMLINES SERVING AHU-15

POINT OF CONNECT TO EXISTINGCHILLED WATER LINESSERVING AHU-15

(E) HHW S/R

(E) MPS S/R

(N) 2-1/2" STEAM (MPS/MPR)PIPES TO AHU-1S ON ROOF

(N) 3-1/2" CHWS/CHWR PIPESTO AHU-1S ON ROOF

(E) 6" SCHS/R

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:47:

24 P

M

HVAC PLAN - ROOF

MH2.1.5Checker AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 HVAC - ROOF pLAN

1/8" = 1'-0"2 LEVEL 4 PIPING PLAN - AREA D

Page 10: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

Level 10' - 0"

LEVEL 10' - 0"

LEVEL 216' - 0"

LEVEL 332' - 0"

LEVEL 448' - 0"

(N) ROOF LEVEL14' - 0"

ROOF LEVEL64' - 0"

HG

Existing Level 2 (For ReferenceOnly)

16' - 0"

Existing Level 3 (For ReferenceOnly)

32' - 0"

Existing Level 4 (For ReferenceOnly)

48' - 0"

Existing Roof (For ReferenceOnly)

64' - 0"

1MH4.1.1

(N) ROOF LEVEL14' - 0"

26"x40"RA26"x40"SA

14"øEA

FSDFSD

DUCT WRAP WHEREDUCTS ARE OUT OFSHAFT (TYP)

40"x26"

TO EF-1 AND EF-2

Level 10' - 0"

LEVEL 10' - 0"

LEVEL 216' - 0"

LEVEL 332' - 0"

LEVEL 448' - 0"

(N) ROOF LEVEL14' - 0"

ROOF LEVEL64' - 0"

345

Existing Level 2 (For ReferenceOnly)

16' - 0"

Existing Level 3 (For ReferenceOnly)

32' - 0"

Existing Level 4 (For ReferenceOnly)

48' - 0"

Existing Roof (For ReferenceOnly)

64' - 0"

3MH4.1.1

ISOLATIONEXHAUST FAN

6" CONCRETE PAD

12"x12"EA

EF1

EF1

EF1

14"ø

EA

8"øSA

26"x40"

AHU1R1R

26"x40"SA

8"øSA

AHU1S1S

(N) ROOF LEVEL14' - 0"

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

35 P

M

HVAC SECTIONS

MH4.1.1Checker AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/4" = 1'-0"3 SHAFT SECTION - EAST / WEST 1/4" = 1'-0"1 SHAFT SECTION - NORTH / SOUTH

Page 11: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

ISOLATION ROOMS

DCP DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

-VAV TERMINAL UNITS --SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

AHU-1 ISOLATION EXHAUST CONTROL

DCP

DCP

710-HEX-1/710-HEX-2

DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

-CAV TERMINAL UNITS-SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

-EXHAUST FANS

1

E ETHERNET BY OWNER

DDC CONTROLS ARCHITECTURE - VA BLDG 100NOTE: NEW SYSTEM TO BE DIRECTLY INTEGRATED(MONITORED CONTROLLED, ALARMED, COMMANED,GRAPHICALLY DISPLAYED) AT EXISITING SIEMENS SERVERS.

UPS

E

UPS

E

UPS

E

UPS

E

E

SERVER

DCP

DCP

EXISTING SIEMENSAPOGEE SERVER (E) SIEMENS

BAS APOGEEWORKSTATION

EXISTING SIEMENSAPOGEE SERVER

EXISTING SIEMENSAPOGEE SERVER

EXISTING SIEMENSAPOGEE SERVER

(E) SIEMENSBAS APOGEE

WORKSTATION

(E) SIEMENSBAS APOGEE

WORKSTATION

(E) SIEMENSBAS APOGEE

WORKSTATION

SIEMENSNETWORKMANAGER

DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

-VAV TERMINAL UNITS --SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

-VAV TERMINAL UNITS-SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

DCP

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

-VAV TERMINAL UNITS-SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

DCP DEDICATED UNIT CONTROLLERS,QUANTITY AND TYPE AS REQUIRED.

-VAV TERMINAL UNITS --SUPPY/EXHAUST-TRACKING PAIRS-SPECIALTY ROOMS

TEMPERATURE CONTROL PANEL,LOCATED IN ELECTRICAL ROOM

SERVER

SERVER

SERVER

ROOF

4TH FLR

3RD FLR

2ND FLR

1ST FLR

ROOF

4TH FLR

3RD FLR

2ND FLR

1ST FLR

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

37 P

M

HVAC CONTROLS DIAGRAM

MH5.1.1TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Page 12: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

FLOWSENSOR

SB-V

SENSORFLOW

RA

AIAI

AIR FLOWFULLY MODUL

RA

AI AI

TS

SA

AIR FLOW FULLY MODUL SUPPLY TEMP

AI

UNIT SCHEDULESEE TERMINAL2 OR 3-WAY VALVE

AO

FULLYMODUL.

HHWS

HHWR

CH

HHW VALVE

SA

RB-V

THE TERMINAL UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING OPERATOR.OCCUPANCY MOTION SENSOR(S) SHALL INDICATE ZONE OCCUPIED OR UNOCCUPIED MODE.

THE TERMINAL UNIT CONTROLLER SHALL SENSE ZONE TEMPERATURE AND MODULATE THE REHEAT VALVE TO MAINTAIN THE ZONETEMPERATURE SETPOINT OF [73]°F.

WHEN THE ROOM IS UNOCCUPIED, THE TERMINAL UNIT CONTROLLER SHALL MODULATE THE TERMINAL UNIT ACTUATOR TO ITS MINIMUM AIRFLOW SETTING(ADJUSTABLE).THE RETURN VARIABLE BOX SHALL TRACK THE SUPPLY CV BOX TO MAINTAIN CONSTANT DIFFERENTIAL AIRFLOW WITHIN THE ROOM.THE ROOM TEMPERATURE SETPOINT CONTROLLER SHALL BE INTERLOCKED TO LOCK OUT THE AIR HANDLER SUPPLY AIR TEMPERATURE RESET FUNCTION WHEN THEROOM TEMPERATURE SETPOINT IS BELOW [68]°F.

SEQUENCE OF OPERATION:

SEE PLANS FORSENSOR LOCATIONS

T

TYPICAL

ZONE TEMP

AI

CO2

AI

SEE PLANS FORSENSOR LOCATIONS

CO2 SENSOR

DURING OCCUPIED MODE, A PROPORTIONAL ONLY (P-ONLY) LOOP SHALL MAINTAIN CO2 CONCENTRATION AT 1000 PPM; RESET 0% AT 800 PPM AND 100% AT 1000 PPM OF CO2.THE LOOP OUTPUT FROM 0-50% SHALL RESET THE AIRFLOW FROM "MIN AIRFLOW" TO "DESIGN COOLING AIRFLOW" LINEARLY. LOOP OUTPUT FROM 50% TO 100% SHALL BEIGNORED.

CONFERENCE ROOM ONLY

FULLY MODULAIR FLOW

AIAI

SB-CSENSOR

FLOW

HHW VALVE

HC

HHWR

HHWS

MODUL.FULLY

AO

2 OR 3-WAY VALVESEE TERMINAL UNITSCHEDULE

AI

SUPPLY TEMP

SAOA

TS

SEE PLANS FORSENSOR LOCATIONS

T

TYPICAL

ZONE TEMP

AI

THE CV BOX UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING OPERATOR.

THE CV BOX CONTROLLER SHALL SENSE ZONE TEMPERATURE, MAINTAIN THEBOX CFM SETPOINT (ADJUSTABLE) AND MODULATE THE REHEAT VALVE TOMAINTAIN THE ZONE TEMPERATURE SETPOINT OF [73]°F. AS THE ZONE TEMPERATUREFALLS BELOW THE SETPOINT, THE HOT WATER REHEAT VALVE SHALL MODULATE OPEN.

SEQUENCE OF OPERATION:

SARA RB-CSENSOR

FLOW

FULLY MODULATIONAIR FLOW

AIAI

THE CV BOX UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING OPERATOR.THE CV BOX CONTROLLER SHALL MAINTAIN THE BOX AIRFLOW SETPOINT (ADJUSTABLE).

SEQUENCE OF OPERATION:

AI AI

AIR FLOW FULLY MODUL

FLOWSENSOR

SB-C

AI

ZONE TEMP

TYPICAL

T

SENSOR LOCATIONSSEE PLANS FOR

TS

EA SA

SUPPLY TEMP

AI

THE CV BOX UNITS SHALL OPERATE AS SCHEDULED BY THE BUILDING OPERATOR.

THE CV BOX CONTROLLER SHALL SENSE ZONE TEMPERATURE AND MAINTAINTHE BOX AIRFLOW SETPOINT (ADJUSTABLE).

SEQUENCE OF OPERATION:

DUCT (REF. ONLY)

SDFSD SDOR AREADETECTOR(S)

TO/FROMFACP

NOTE: FA PANEL SHALL MONITOR FSDPOSITIONS.

TO/FROM FIREALARM PANELBY DIV. 26

M

M

EA

DS

MS

DI

ALARM ALARM

MS

DS

EF

EFEA

ES BY

AFMS

x

AI

AIR FLOW(AF-EF )

SPACEREFERENCE

CONTROLLED SPACE

CORRIDOR

MONITORED/

ISOLATION ROOM ANTE ROOM

PT-1

PT-2

STATUS/SWITCH

(RAM)

REMOTE

EMERGENCY CIRCUIT120 V AC POWER

NURSE STATION

~

~

MONITORACCESS

TO RAM

120 V AC POWEREMERGENCY CIRCUIT

~

DO

STARTSTOP/ STOP/

START

DODIDIDODI

OPEN/

DO

DAMPERPOS

DAMPERPOS

~

~

DIV. 26ES BYDIV. 26

CURRENT

FAULTSTATUS/SWITCHCURRENT

FAULT

CLOSEOPEN/CLOSE

A ROOM PRESSURIZATION MONITORING SYSTEM SHALL MONITOR THE DIFFERENTIAL PRESSURE BETWEEN THE ISOLATION ROOM AND ANTEROOM AND THE DIFFERENTIAL PRESSURE BETWEEN THEISOLATION ROOM AND THE CORRIDOR.

PER CODE:

AN ALARM SYSTEM SHALL CONSIST OF A DISPLAY MONITOR LOCATED ON THE CORRIDOR WALL NEAR THE DOOR TO THE ISOLATION ROOM AND VISUAL AND AUDIBLE ALARMS THAT ANNUNCIATE ATTHE ISOLATION ROOM ROOM AND AT A NURSES' STATION OR OTHER SUITABLE LOCATION THAT WILL PROVIDE SUITABLE SURVEILLANCE. THE ALARM SHALL ANNUNCIATE UPON A SIGNIFICANT DROPFROM DESIGN SUPPLY AIR FLOW TO THE ROOM (WHICH WOULD INDICATE AHU SUPPLY FAN FAILURE), A SIGNIFICANT DROP FROM DESIGN EXHAUST AIR FLOW FROM THE ROOM (WHICH WOULDINDICATE EXHAUST FAN FAILURE) AND WHEN A MINIMUM PRESSURE DIFFERENTIAL OF 0.001 INCH OF WATER IS NOT BEING MAINTAINED BETWEEN THE ANTEROOM AND ISOLATION ROOM ANDBETWEEN THE CORRIDOR AND ISOLATION ROOM.

PROVIDE LOCAL TRANSMITTERS WHERE REQUIRED TO CONFORM TO THE ABOVE REQUIREMENTS.

THE BAS SHALL MONITOR ALL ALARM CONDITIONS AND REPORT AND PRINT ANY ALARM CONDITION.

AN ADJUSTABLE TIME DELAY SHALL ALLOW FOR ROUTINE OPENING OF DOORS.

THE FOLLOWING POINTS SHALL BE MONITORED AND VIEWED AT THE OPERATOR WORKSTATION(S):

ROOM PRESSURE RELAY STATUS ROOM PRESSURE SETPOINT ROOM STATUS (NORMAL, WARNING, ALARMS) SUPPLY AIR FLOW RATE STATUS (NORMAL, ALARMS) FAN STATUS (NORMAL, ALARMS) EXHAUST AIR FLOW RATE STATUS (NORMAL, ALARMS) EXHAUST FAN STATUS (NORMAL, ALARMS)

THE ENABLE SIGNAL FOR THE DUTY EXHAUST FAN SERVING THE ISOLATION ROOM SHALL BE DERIVED FROM A FIXED TIME PROGRAM INITIALLY SET UP FOR 24 HOUR OPERATION.

THE DUTY EXHAUST FAN SHALL BE ROTATED EVERY [7] DAYS OR IN EVENT OF FAILURE. NORMAL ROTATION SHALL OCCUR AT MIDNIGHT ON [SUNDAY].

THE MOTORIZED DAMPER ASSOCIATED WITH THE DUTY FAN SHALL BE PROVED OPEN PRIOR TO DUTY FAN SWITCHOVER, ONCE THE DUTY FAN IS IN OPERATION, THE DAMPER ASSOCIATED WITH

THE STANDBY FAN SHALL CLOSE. A DAMPER MISMATCH ALARM SHALL BE RAISED AT THE BAS IF EITHER DUTY OR STANDBY DAMPER FAILS TO OPERATE ACCORDING TO THE ABOVE SEQUENCE.

FAILURE SHALL BE DETECTED BY MISMATCH BETWEEN THE DUTY FAN ENABLE SIGNAL AND THE FAN STATUS. ON FAILURE, THE BACK UP DUTY FAN SHALL START, AN ALARM SHALL BE

GENERATED AT THE OPERATOR TERMINAL, AND THE FAILED FAN SHALL NOT RE-ENTER NORMAL CONTROL UNTIL RESET BY A COMMAND FROM THE OPERATOR.

SA & EAFLOW ANDSF & EFSTATUSFROM BAS

DPT

DPT

AI

DIRTYFILTER ALARM

AI

DIRTYFILTER ALARM

SEQUENCE OF OPERATION:

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

39 P

M

HVAC CONTROLS DIAGRAM

MH5.1.2TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

12" = 1'-0"1 TYPICAL VARIABLE SUPPLY TERMINAL UNIT WITH REHEAT (SB-V/RB-V)

12" = 1'-0"2 TYPICAL CONSTANT SUPPLY TERMINAL UNIT WITH REHEAT (SB-C)

12" = 1'-0"3 TYPICAL CONSTANT RETURN TERMINAL UNIT (RB-C)

12" = 1'-0"4 TYPICAL CONSTANT SUPPLY BOX COOLING ONLY (SB-C)

12" = 1'-0"5 TYPICAL COMBINATION FIRE-SMOKE DAMPER

12" = 1'-0"6 AIRBORNE INFECTION ISOLATION ROOM (NEGATIVE PRESSURE)

Page 13: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

GENERAL NOTES:1. ALL DELAYS MUST BE VERIFIED AND TWEAKED BY THE (BUILDING

AUTOMATION SYSTEM) BAS CONTRACTOR BASED ON ACTUAL MOTOR DRIVESAND ACTUATORS RESPONSE TIME.

2. PROVIDE HARD-WIRE INTERLOCK FOR SUPPLY & EXHAUST FAN SHUTDOWN INA SMOKE ALARM CONDITION. CONTRACTOR ALSO TO PROVIDE CONNECTIONTO BUILDING DUCT MOUNTED SMOKE DETECTOR PER DIRECTION OF THEOWNER'S REPRESENTATIVE.

3. LOCATE AND INSTALL THE DUCT STATIC PRESSURE SENSOR APPROXIMATELY2/3 DOWNSTREAM OF THE SUPPLY FAN IN THE MAIN SUPPLY AIR DUCT PRIORTO ANY MAJOR DUCTWORK BRANCHES PER FLOOR.

4. PROVIDE HARD-WIRED RS-485 SECONDARY LAN CONNECTION AND PROGRAMI/O POINTS OR HARD-WIRED I/O POINTS DIRECTLY TO EMS DDC.

5. VFD POINTS ARE TO BE HARD-WIRED DIRECTLY TO THE DDC BAS I/O PANEL ASWELL AS PROVIDED VIA THE RS-485 SECONDARY LAN CONNECTION.

AVERAGINGAVERAGING

TO FIRE ALARM PANEL

ES BY DIV. 26

TSTS

OA SA

CHWS

CHWR

CC

CURRENT SWITCHSTATUS/FAULT

AHU MFR.AFMS BYAHU MFR.

ES BY DIV. 26

HS

CO2

AVERAGING

AI AI

RETURN AIR

HARDWIREDINTERLOCKSTO AHU FAN

TS SP

DUCT STATIC(ESP-ALM)

EXHAUSTAIR TEMP

(EA-T)

VFD

AIR FLOW(AFM-E)

N2(EF-N2)

PROVIDEOPEN

PROTOCOLGATEWAY

ALARM(EF-A2)

STOP/START(EF-S)

SPEEDCONTROL

(EF-C)

RUN STATUS(EF-A1)

AIAIAI DIDOAO

CHWOFF-COIL

WATER TEMP

AOAI AI

FULLYMODUL.

CHWOFF-COIL

WATER TEMP

EXHAUST AIR

HARDWIREDINTERLOCKSTO AHU FANS

DUCTSMOKE

DETECTORBY DIV. 26

SD

DUCT STATICCOORDINATE

LOCATION WITHTESTING ANDBALANCING

AGENT, MIN (2)AT REMOTELOCATIONS

HARDWIREDINTERLOCKSTO AHU FAN

SP

DUCT DISCHARGE STATIC

DUCT HIGH STATIC ALARM

AI AI AI

DIRTY FILTERALARM

SUPPLY AIRTEMP

TS

AI

CS

DPT

FINAL FILTER

3-WAYVALVE

LOW LIMIT TEMP ALARMSETPOINT ADJ. AT DEVICE

HEAT RECOVERY AIR TEMP

ON -COILAIR TEMP

AIR FLOWPROVIDE OPENPROTOCOL

GATEWAY N2

ALARMSTART/STOPSPEEDCONTROL

RUNSTATUS

DIDOAO

AI AI AI AI

TS TS

AI

CURRENT SWITCHSTATUS/FAULT

CS

VFD

AFMS BYAHU MFR.

AI

DIRTY FILTERALARM

DPT

PREFILTER

AIAI

TS

TEMPERATURE ANDHUMIDITY SENSORSLOCATED IN ROOFTOPAHU CABINETS AT OAINTAKE SHADED FROMHEAT SOURCES.

OUTSIDE AIRHUMIDITY

OUTSIDE AIRTEMP

OUTSIDE AIRCO2

AI

AIR QUALITYMONITORING:

AI

DIRTY FILTERALARM

FINALFILTER

DPT

CH

3-WAYVALVE

AO

TSTS

HHWOFF-COIL

WATER TEMPAI AI HHW

OFF-COILWATER TEMP

FULLYMODUL.

HHWS

HHWR

M

M

M

AODI DI

OA DAMPER(MODULATING)

AODI

RA DAMPER(MODULATING)

DI

AODI

EA DAMPER(MODULATING)

DI

A. START/STOP1. WHEN THE AIR HANDLER IS OFF (STOPPED/DISABLED FOR ANY REASON) THE FOLLOWING OCCURS:

a. THE OUTSIDE AIR DAMPER IS COMMANDED CLOSED.b. THE MINIMUM OUTSIDE AIR (MOA) DAMPER IS COMMANDED CLOSED.

c. THE EXAUST AIR DAMPER IS COMMANDED CLOSED.d. THE RETURN AIR DAMPER IS COMMANDED OPEN.

c. THE COOLING/HEATING COIL CONTROLL VALVES ARE COMMANDED CLOSED.

d. SUPPLY FANS ARE COMMANDED TO STOP.e. RETURN FANS ARE COMMANDED TO STOP.

B. ENABLE/DISABLE1. THE AIR HANDLER IS ENABLE BASED ON A TIME/DAY PROGRAMMABLE SCHEDULE.2. THE AIR HANDLER STARTS ONE HOUR BEFORE SCHEDULED PROGRAMMED OCCUPANCY.

C. START-UP1. WHEN THE AIR HANDLER IS ENABLED AUTOMATICALLY BY THE TIME/DAY SCHEDULE OR MANUALLY BY THE OPERATOR, THE FOLLOWING OCCURS;

a. THE MOA DAMPER OPENS AND OPEN STATUS CONFIRMED BY DAMPER END SWITCH.b. THE RETURN AIR DAMPER IS CONFIRMED OPEN BY DAMPER END SWITCH.c. THE SUPPLY FAN IS COMMANDED TO START.d. THE SUPPLY FAN SPEEDS UP TO PROGRAMMED MINIMUM SPEED (15 HZ).d. THE SUPPLY FAN STATUS IS CONFIRMED BY THE CURRENT SWITCH.d. ONCE SUPPLY FAN STATUS IS CONFIRMED, THE RETURN FAN IS COMMANDED ON.e. THE RETURN FAN SPEEDS UP TO PROGRAMMED MINIMUM SPEED (15HZ).f. RETURN FAN STATUS IS CONFIRMED BY THE CURRENT SWITCH.g. SUPPLY FAN SPEED CONTROL LOOP IS ENABLED.h. RETURN FAN SPEED CONTROL LOOP IS ENABLED.i. TEMPERATURE CONTROL LOOP IS ENABLED.j. TMPERATURE AND PRESURE ALARMS ARE ENABLED AFTER {15 MINUTES}.

SEQUENCE OF OPERATION:D. SUPPLY FAN (SF) SPEED CONTROL

1. SUPPLY FAN SPEED RAMPS UP TO MAINTAIN THE SUPPLY DUCT PRESSURE SET POINT.2. THE SUPPLY DUCT PRESSURE SET POINT IN 0.6" (ADJ). BALANCER TO ADJUST PRESSURE SET POINT DURING BALANCING AT THE MINIMUM REQUIRED TO MAINTAIN DESIGN AIRFLOWS.3. THE SUPPLY DUCT PRESSURE SET POINT SHALL BE RE-SET UP/DOWN IN INREMENTS OF {0.05}" SUCH THAT ONLY ONE (1) TERMINAL UNIT BOX DAMPER POSITION MAINTAINED BEYOND {90}% FULLY OPEN. USE "TRIM AND RESPOND" LOGIC.

E. RETURN FAN (RF) SPEED CONTROL1. THE RETURN FAN SPEED MODULATES TO MAINTAIN A RETURN AIR VOLUME EQUAL TO THE SUPPLY AIR VOLUME {MINUS ANY EXHASUT AIR VOLUME FROM TOILETS, ETC. SERVED BY THE SYSTEM}.

F. MINIMUM OUTSIDE AIR (MOA) VOLUME CONTROL1. IN MINIMUM OUTSIDE AIR MODE (AS OPPOSED TO ECONOMIZER MODE), THE RETURN AND EXHAUST AIR DAMPERS MODULATE TO MAINTAIN THE MOA SET POINT (SEE ROOM VENTILATION SCHEDULE FOR VOLUME) MEASURED BY T THE MOA FLOW MEASURING STATION.

G. MINIMUM OUTSIDE AIR SETPOINT1. THE MINIMUM OUTSIDE AIR SET POINT IS RESET UPWARDS BASED ON THE CO2 CONCENTRATION IN DEMAND-CONTROLLED ZONES. SEE AHU SCHEDULE FOR MINIMUM OA SETPOINTS.2. A ZONE IS IN ALARM WHEN CO2 CONCENTRATION LEVEL EXCEEDS 1000 PPM.3. IF ANY BOX IS IN ALARM, RESET MINIMUM OA SETPOINT TO HIGHEER OA SETPOINT AS SCHEDULED.

H. SUPPLY AIR TEMPERATURE CONTROL1. THE COOLING COIL CONTROL VALVE MODULATES TO MAINTAIN THE SUPPLY AIR TEMPERATURE (SAT) SET POINT OF {55 F}.

I. DEW POINT CONTROL1. DDC SYSTEM SHALL CALCULATE SUPPLY AIR DEW POINT USING SUPPLY AIR TEMPERATURE AND HUMIDITY SENSORS.2. IF CALCUALTED SPACE DEW POINT IS EQUAL TO OR EXCEEDS 57 F, THE DDC SYSTEM SHALL OVERRIDE SUPPLY AIR TEMPERATURE CONTROL AND OPEN COOLING VALVE TO DEPRESS SUPLY AIR TEMPERATURE UNTIL THE SUPPLY AIR DEW POINT IS EQUAL TO 50 F.

AFMS

AI

AIR FLOW MEASURINGSTATION (PER FAN)

AFMS

AI

AIR FLOWMEASURING

STATION

AFMS

AI

AIR FLOW MEASURINGSTATION (PER FAN)

TO FIRE ALARM PANELHARDWIREDINTERLOCKSTO AHU FANS

DUCTSMOKE

DETECTORBY DIV. 26

SD

M

AO DIDI

MINIMUMOUTSIDE AIR

DAMPER

MIN OA

J. ECONOMIZER CONTROL1. WHEN OUTSIDE AIR IS EQUAL OR HIGHER THAN THE SUPPLY AIR TEMPERATURE (SAT), SETPOINT BUT LOWER THAN {72 F}.

a. MINIMUM OUTSIDE AIR DAMPER IS FULLY OPEN.b. OUTSIDE AIR AND EXHAUST AIR DAMPERS ARE FULLY OPEN.c. RETURN AIR DAMPER IS FULLY CLOSED.d. COOLING COIL CONTROL VALVE MODULATES TO MAINTAIN SAT

SETPOINT.e. PRE-HEAT COIL CONTROL VALVE IS CLOSED.

2. WHEN OUTSIDE AIR IS LOWER THAN THE SAT SETPOINT.a. MINIMUM OUTSIDE AIR DAMPER IS FULLY OPEN.b. OUTSIDE AIR, EXHAUST AIR AND RETURN AIR DAMPERS MODULATE TO MAINTAIN SAT SETPOINT.c. IF SAT SETPOINT IS NOT BEING MET FROM MODULATION OF DAMPERS MENTIONED ABOVE, PRE-HEAT COIL CONTROL VALVE MODULATES TO MAINTAIN SAT SETPOINT.d. COOLING COIL CONTROL VALVE IS CLOSED.

3. WHEN OUTSIDE AIR IS HIGHER THAN {72 F}.a. MINIMUM OUTSIDE AIR DAMPER IS FULLY OPEN.b. OUTSIDE AIR DAMPER IS FULLY CLOSED.c. RETURN AIR AND EXHAUST AIR DAMPERS MODULATE TO MAINTAIN THE MOA SETPOINT.d. COOLING COIL CONTROL VALVE MOUDULATES TO MAINTAIN THE SAT SETPOINT.e. PRE-HEAT COIL CONTROL VALVE IS CLOSED.

K. FAILURE1. IF THE SUPPLY AIR FAN IS COMMANDED ON AND POSITIVE STATUS IS NOT RECEIVED FROM THE CURRENT SWITCH AFTER {30 SECONDS}, THE START- UP IS ABORTED.2. IF THE RETURN AIR FAN IS COMMANDED ON AND POSITIVE STATUS IS NOT RECEIVED FROM THE CURRENT SWITH AFTER {30 SECONDS{, THE START-UP IS ABORTED.3. IF THE SUPPLY DUCT PRESSURE INCREASES BEYOND (4"), THE HIGH STATIC PRESSURE SWITCH INSTALLED IN THE SUPPLY DUCT WILL CAUSE THE SUPPLY AND RETURN FAN TO STOP. THE SWITCH REQUIRES A MANUAL RESET TO ALLOW THE FANS TO RESTART.

COOLINGCOIL

PRE-HEATCOIL

4. IF THE RETURN DUCT PRESSURE DECREASES BEYOND (-2"), THE LOW STATIC PRESSURE SWITCH INSTALLED IN THE SUPPLY DUCT WILL CAUSE THE SUPPLY AND RETURN FAN TO STOP. THE SWITCH REQUIRES A MANUAL REST TO ALLOW THE FANS TO RESTART.

L. ALARMS1. CRITICAL ALARMS ARE GENERATED AT THE OPERATOR WORKSTATION WHEN:

a. THE HIGH DUCT STATIC PRESSURE SWITCH IS TRIGGERED.b. THE LOW DUCT STATIC PRESSEUR SWITCH IS TRIGGERED.c. IF THE SUPPLY AIR FAN IS COMMANDED ON AND POSITIVE STATUS IS NOT RECEIVED FROM THE CURRENT SWITCH AFTER {30 SECONDS}.d. IF THE RETURN AIR FAN IS COMMANDED ON AND POSITIVE STATUS IS NOT RECEIVED FROM THE CURRENT SWITCH AFTER {30 SECONDS}.e. MOA DAMPER IS COMMANDED FULLY OPEN AND POSITIVE STATUS IS NOT RECEIVED FROM THE OPEN END SWITCH AFTER {30 SECONDS}.f. MOA SAMPER IS COMMANDED FULLY CLOSED AND POSITIVE STATUS IS NOT RECEVIED FROM THE CLOSED END SWITCH AFTER {30 SECONDS}.g. OA DAMPER IS COMMANDED FULLY OPEN AND POSITIVE STATUS IS NOT RECEIVED FROM THE OPEN END SWITCH AFTER {30 SECONDS}.h. OA DAMPER IS COMMANDED FULLY CLOSED AND POSITIVE STATUS IS NOT RECEIVED FROM THE CLOSED END SWITCH AFTER {30 SECONDS}.i. SA DAMPER IS COMMANDED FULLY OPEN AND POSITIVE STATUS IS NOT RECEIVED FROM THE OPEN END SWITCH AFTER {30 SECONDS}.j. SA DAMPER IS COMMANDED FULLY CLOSED AND POSITIVE STATUS IS NOT RECEIVED FROM THE CLOSED END SWITCH AFTER {30 SECONDS}.k. RA DAMPER IS COMMANDED FULLY OPEN AND POSITIVE STATUS IS NOT RECEIVED FROM THE OPEN END SWITCH AFTER {30 SECONDS}.l. RA DAMPER IS COMMANDED FULLY CLOSED AND POSITIVE STATUS IS NOT RECEIVED FROM THE CLOSED END SWITCH AFTER {30 SECONDS}.m. EA DAMPER IS COMMANDED FULLY OPEN AND POSITIVE STATUS IS NOT RECEIVED FROM THE OPEN END SWITCH AFTER {30 SECONDS}.n. EA DAMPER IS COMMANDED FULLY CLOSED AND POSITIVE STATUS IS NOT RECEIVED FROM THE CLOSED END SWITCH AFTER {30 SECONDS}.o. SUPPLY AIR TEMPERATURE RISES ABOVE {60 F} FOR {5 CONSECUTIVE MINUTES}.

2. MAINTENANCE ALARMS ARE GENERATED AT THE OPERATOR WORKSTATION WHEN:

a. THE PRE-FILTERS PRESSURE DROP REACHES {0.5"}.b. THE FINAL FILTER PRESSURE DROP REACHES {0.8"}.c. DIFFERENCE BETWEEN SUPPLY AIR VOLUME AND RETURN AIR

VOLUME IS HIGHER THAN 5,000 CFM (ADJ) FOR {5 CONSECUTIVE MINUTES}.

d. DIFFERENCE BETWEEN SUPPLY AIR VOLUME AND RETURN AIR VOLUME IS LOWER THAN 4,000 CFM (ADJ) FOR {5 CONSECUTIVE MINUTES}.

e. SUPPLY AIR TEMPERATURE DROPS BELOW 50 F (ADJ) FOR {5 CONSECUTIVE MINUTES}.

f. ALARM STATE IS RECEIVED FROM THE SUPPLY FAN VFD.g. ALARM STATE IS RECEIVED FROM THE RETURN FAN VFD.h. IN MINIMUM OUTSIDE AIR MODE, THE MOA VOLUME DROPS BELOW

4,500 CFM (ADJ) FOR {5 CONSECUTIVE MINUTES}.i. IN MINIMUM OUTSIDE AIR MODE, THE MOA VOLUME RISES ABOVE 6,000

CFM (ADJ) FOR {5 CONSECUTIVE MINUTES}.M. COORDINATION OF AIR HANDLING UNIT SEQUENCES: ENSURE THAT PRE-

HEAT COIL, MIXED AIR, HEATING COIL, AND COOLING-COIL CONTROLS HAVECOMMON INPUTS AND DO NOT OVERLAP IN FUNCTION.

N. SMOKE DETECTORS SHALL BE MOUNTED IN BOTH SUPPLY AND RETURN AIRDUCTS. AIR HANDLER TO STOP OPERATION UPON DETECTION OF SMOKE. THEENGINEERING CONTROL CENTER SHALL BE PROGRAMMED TO PRINT AN ALARMMESSAGE ON THE SYSTEM ALARM PRINTER INDICATING THE TIME OF ALARMAND IDENTIFICATION OF THE SYSTEM STOPPED. SMOKE DAMPERS WITH ENDSWITCHES IN THE SUPPLY AND RETURN AIR DUCTS SHALL CLOSE UPONDETECTION OF SMOKE. END SWITHCES MOUNTED ON SMOKE DAMPERS SHALLPROVE THE DAMPERS OPEN PRIOR TO FAN RESTART. AIR HANDLING UNIT SHALLBE ALLOWED TO RESTART ONLY WHEN THE ALARM IS RESET MANUALLY.

M

DI

SMOKEDAMPER

DI

M

DI

SMOKEDAMPER

DIDO

DORE

GIST

ERED

PROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

40 P

M

HVAC CONTROLS DIAGRAM

MH5.1.3Checker AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NTS1 AIR HANDLING UNIT (AHU) CONTROL DIAGRAM

Page 14: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

SHOWN ON PLANSROUND ELBOW WHENSHOWN. PROVIDESQUARE ELBOW

PLAN VIEW

PLAN VIEW

AIR SPLIT TYPE DUCT TAKE-OFF

BRANCH DUCT TAKE-OFF

BRANCH DUCTSUPPLY REGISTER OR

TURNING VANES

WHEN SHOWN ON PLANSPROVIDE VOLUME DAMPER

DIMENSIONSEE PLAN FOR SPLIT

DUCTMAIN SUPPLY

W

WHERE SHOWN ON PLANS.PROVIDE VOLUME DAMPER

BRANCH DUCT

1/4 4" MIN.

SCREW, MARK POSITIONOR LINKAGE W/ SETADJUSTABLE METAL ROD

CFM NOTED ON PLANSCLOSED POSITION TOADJUSTABLE FROM FULLYVOLUME EXTRACTOR;

SUPPLY REGISTER TAKE-OFFPLAN VIEW

MAIN SUPPLY DUCT

TOP REGISTER (TR)

MAIN SUPPLY DUCT

ALL SHORT RADIUS ELBOWS SHALL

SMACNA. FASTENED AS RECOMMENDED BY CONSTRUCTED, SUPPORTED AND HAVE VANES. VANES SHALL BE

ELBOWS FOR SUPPLY DUCTS ONLY. PLANS MAY BE MADE SHORT RADIUS

2. STANDARD RADIUS ELBOWS SHOWN ON

ELBOWS SHALL BE MADE ROUND.1. THE INTERIOR SURFACE OF ALL RADIUS

NOTES:

STANDARD RADIUS ELBOW

SHORT RADIUS ELBOW WITH ONE VANE

SHORT RADIUS ELBOW WITH TWO VANES

W

W

W

R

W

R1/3W

2/3W

R

1/6W

1/3W1/2W

GREATER THAN W.R SHALL EQUAL OR BE

GREATER THAN W.R SHALL EQUAL OR BE

GREATER THAN ›W.R SHALL EQUAL OR BE

VANED NOT VANED

W2

W1

3

3

W1

W2W2

W1

NOTES:

1. ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

2. WHEN W1 DOES NOT EQUAL W2 VANE SHALL SINGLE BLADE VANE TYPE REGARDLESS OF W DIMENSION.

3. ALL SINGLE VANES SHALL HAVE A 2 INCH RADIUS, 1 1/2 INCH MAXIMUM SPACE BETWEEN VANES AND A 3/4 INCH TRAILING EDGE.

4. WHEN W1 EQUALS W2 AND W1 IS GREATER THAN 20 INCHES VANES SHALL BE DOUBLE VANE TYPE.

5. VANED ELBOWS SHALL NOT BE USED IN RETURN OR EXHAUST DUCTS UNLESS OTHERWISENOTED ON THE PLANS FOR SPECIFIC ELBOWS.

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.NOTE:

AIR FLOW

EQUIPMENT , ie. HEATING COIL

EQUIPMENT IN DUCT

PLAN OR SIDE VIEW

PLAN OR SIDE VIEW

30° MAX.

30° MAX.

20° MAX.

20° MAX.

15° MAX.

15° MAX.

RADIUS OR SQUARE ELBOW

CEILING

VOLUME DAMPERUSE 45 DEGREE ENTRY,BELLMOUTH OR SPIN-INPER SMACNA STANDARD

AIR DUCT

(MAY BE ON SIDE OR BOTTOM OF DUCT)SEE CEILING INLET OROUTLET PLENUM DETAIL

HEIGHT AS REQUIREDTO ACCOMODATE DUCT

FLEXIBLE DUCT (WHEN USED) SHALL NOT EXCEED 5'-0".

CONNECTOR.TO ACCOMODATESQUARE. SIZE AS REQUIREDRECTANGULAR OR

STRUCTURE PER 'SMACNA'SUSPEND FROM ABOVE

GYP. BD. CEILING T-BAR CEILING

FOR TYPE & SIZESEE SCHEDULE FOR

1.

PLENUM BOX SHALL BE

DUCT, REFER TO DIFFUSER, REGISTER,GRILLE SCHEDULE FOR DUCT SIZE

NOTES:

GUIDELINES

ROUND, SQUARE ORRECTANGULAR DUCTCONNECTOR BETWEENCEILING INLET OR OUTLET& PLENUM BOX.

OBD WHERE APPLICABLE

CEILING INLET/OUTLET

CONNECTOR.

SEE NOTE 1

WHERE SHOWN ON PLANS.PROVIDE VOLUME DAMPER

PLAN VIEW

WBRANCH DUCT

1/4W 4" MIN.

RETURN DUCTMAIN EXHAUST OR

45°

FLANGED

ROUND

DUCT

ON 12" CENTERSSHEET METAL SCREWS

CENTERSRIVET ON 4"

1"1/2"

MATERIAL TAUT.INSTALLED. 6" NOMINAL WITH1 1/2" MIN. TO 3" MAX.

1/2"

AS SPECIFIEDMATERIALFLEXIBLE

1" x 1/8" DRAW BAND

ON FAN SIDECONNECTION

WASHER

IRON1" x 1/8" BAND

BOLT ON 4" CENTERS

FLANGED

RECTANGULAR

SLIP1 1/2" POCKET

DUCT

DUCTWORKSPECIFIED FORSHEET METAL AS

WITH MATERIAL TAUT.INSTALLED. 6" NOMINAL1 1/2" MIN. TO 3" MAX.

DUCTWORKSPECIFED FORSHEET METAL AS

ON FAN SIDECONNECTION

WASHER

AS SPECIFIEDFLEXIBLE MATERIALIRON

1" x 1/8" BAND

BOLT ON 4" CENTERS

1" FLANGE & HEM

POSITION OF BOLTALTERNATE

5/16" FLANGE

AND FAN ROOM FLOORS SHALL BE PROVIDED WITH A 3" HIGH CONCRETE CURBAROUND OPENING FOR DUCT.

1. ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS

NOTES:

MEDIUM PRESSURE DUCT

LOW PRESSURE DUCT

FLOOR

DUCT RISER - SEE PROJECTPLANS FOR SIZE

SEAL HOLE AFTER DUCTINSTALLATION WITH FIRE-PROOFING MATERIAL

SIDES OF DUCTON BOTH LONG DIMENSION2" x 2" x 1/4" ANGLE - INSTALL

DUCT RISER

HOLE IN STRUCTURAL FLOOR

SUPPORT POINTTRANSVERSE JOINT AT RISERARRANGE RISER TO REINFORCE

DUCT RISER

HOLE IN STRUCTURAL FLOOR

USE 2" x 2" x 1/8" ANGLE.OF DUCT. FOR DUCTS OVER 60"ON BOTH LONG DIMENSION SIDES1 1/2" x 1 1/2" x 1/8" ANGLE - INSTALL

ON CENTERSHEET METAL SCREWS 4"

PROOFING MATERIALINSTALLATION WITH FIRE-SEAL HOLE AFTER DUCT

FLOOR

DUCTEXTEND ANGLE 3" BEYOND

PLANS FOR SIZEDUCT RISER - SEE PROJECT

2. SIMILAR FOR DUCT RISER SUPPORTS IN SHAFT EXCEPT ANGLE SHALL REST ONINTERMEDIATE FRAMING MEMBERS (TUBE STEEL) IN SHAFT OR BUTT WELD TO STRUCTURALSTEEL AND OR INTERMEDIATE FRAMING MEMBERS. EXCEPT THE ANGLE IRONSIZES SHALL BE 2x2x1/4, (2 1/2 x 2 1/2 x 1/4 FOR DUCTS OVER 60") ON LOW PRESSUREAND 2 1/2 x 2 1/2 x 1/4 FOR MEDIUM PRESSURE.

IF REQUIRED FOR HEIGHT.OTHERWISE REMOVE

DRAIN FITTING

WEATHER COVER FORMOTOR AND DRIVES

VIBRATION ISOLATION2"STATIC DEFLECTION (TYP)

LEVEL SLEEPERS ORPLATFORM - BY GENERALCONTRACTOR

TOP

OF

DIS

CH

ARG

E E

XTEN

SIO

N T

O B

E AT

TO

P O

F P

ARAP

ET

LINEAR SLOT DIFFUSER/REGISTER

DUCT PLENUMINSULATED

HEIGHT TO SUITDUCT INLET

DUCT, SEE PLANS FORSIZE. PROVIDE TRANSITIONAS REQUIRED TO MATCHMFRS. STD. PLENUMCONNECTION COLLAR.

DETERMINE PLENUM SIZE BASED ON LENGTH AND NUMBEROF SLOTS SCHEDULED AND INLET SIZE SHOWN ON PLANS.

NOTE:

WASHER

ANGLE

5/8"

5/8"

1/2"

4x4x1/2x1'-4" LONG

4x4x1/2x1'-4" LONG

3x3x1/4x1'-4" LONG

4x4x12 GA

4x4x12 GA

3x3x16 GA

5x3x1/4"

4x4x1/4"

4x4x12 GA

96"

84"

UP TO 60"

OR INSERTCONCRETE ANCHOR

ANGLE CLIPALL OTHERSVERTICAL

BRACING ANGLES

DIMENSIONMAX. DUCT

BOTH SIDESLONGITUDINAL ANGLE

MAX.7'-0"

ANGLEDIAGONAL

11

DUCT SIZE DUCTWITH CUT3/8" BOLTS

ANGLESHORIZONTAL

VERTICAL

BENT PLATE OF EQUAL THICKNESS MAY BE SUBSTITUTED FOR LONGITUDINAL ANGLECLIP TO FACILITATE ANCHORAGE TO SLAB TROUGHS. PROVIDE EQUAL NUMBER OFANCHOR BOLTS TO THAT SHOWN.

PROVIDE MINIMUM EMBEDMENT OF 1 1/2" ABOVE TOP OF METAL DECK FOR ALL ANCHOR BOLTS.

ANGLE CLIP, ORIENT TO DECK SPAN.FIELD DRILL HOLES IN ANGLE CLIP FORANCHOR BOLTS TO SET IN DECK TROUGHANCHOR

BOLT, TYP.

CONCRETE FILLMETAL DECK WITH

1

2 3

2

3

REQUIRED FOR DUCT OVER 6 S.F. IF HANGING LOWER THAN 12" FROM STRUCTURE ABOVE.1

NOTES :

MAX.5'-0"

2

1

28" TO 50" DIAMETER

W/WASHER, TYP.1/2" BOLT

BRACETRANSVERSE

ANGLES2x2x16 GA

2"x12 GA STRAP

BRACELONGITUDINAL2x2x16 GA

11

BENT PLATE OF EQUAL THICKNESS MAY BE SUBSTITUTED FOR LONGITUDINAL ANGLECLIP TO FACILITATE ANCHORAGE TO SLAB TROUGHS. PROVIDE EQUAL NUMBER OFANCHOR BOLTS TO THAT SHOWN.PROVIDE MINIMUM EMBEDMENT OF 1 1/2" ABOVE TOP OF METAL DECK FOR ALL ANCHOR BOLTS.**

*

ANCHOR BOLTS TO SET IN DECK TROUGHFIELD DRILL HOLES IN ANGLE CLIP FOR3x3x1/4" ANGLE CLIP, ORIENT TO DECK SPAN.

1/2" ANCHORBOLT, TYP.

CONCRETE FILLMETAL DECK WITH

*

**

VIBRATIONISOLATIONASSEMBLY

CONCRETE HOUSEKEEPINGPAD. SEE STRUCTURALDRAWINGS FOR PAD DETAILING

DECK

ANCHOR OR EXPANSION(TYP.)

SNUBBER ASSEMBLY

EQUIPMENT BASE

NOTES:DETAIL FOR REFERENCE ONLY.1.

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

43 P

M

HVAC DETAILS

MH6.1.1TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. ANCHORAGE AND RESTRAINTS SHOWN IN DETAILS FOR BOTHSEISMIC AND GRAVITY SUPPORT ARE FOR REFERENCE ONLY. THEDESIGN AND DETAILING OF ALL ANCHORAGE AND SEISMIC RESTRAINTOF MECHANICAL COMPONENTS IS TO BE PROVIDED BY THECONTRACTOR IN ACCORDANCE WITH SPECIFICATION SECTION.

NTS1 SUPPLY DUCT TAKE-OFFS DETAIL

NTS2 RADIUS ELBOW DETAIL

NTS3 SQUARE ELBOW DETAIL

NTS5 DUCT TRANSFORMATION DETAIL

NTS6 CEILING INLET AND OUTLET BRANCH DUCT

NTS7 CEILING INLET OR OUTLET DETAIL

NTS4 EXHAUST-RETURN BRANCH DUCT DETAIL

NTS9 FLEXIBLE DUCT CONNECTION DETAIL

NTS10 DUCT RISER SUPPORT THRU FLOOR DETAIL

NTS11 UPBLAST UTILITY FAN

NTS12 TERMINAL UNIT DETAIL

NTS13 SEISMIC BRACING FOR RECTANGULAR DUCTS DETAIL

NTS14 SEISMIC BRACING FOR ROUND DUCTS DETAIL

NTS8 PAD MOUNTED EQUIPMENT W/BASE DETAIL

Page 15: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

FOR UNIT INLET DUCT CONNECTION.FLEXIBLE DUCT CONNECTION OF 3'-0" MAXIMUM LENGTH MAY BE PROVIDED

NOTES

1

TRANSITION FROM UNIT CONNECTION

DUCT SIZE SHOWNON AIR TERMINAL UNITSCHEDULE

S/A

E/AORR/A

AIR FLOW

UNIT HEATINGCOIL SECTION AS SCHEDULED

SOUND ATTENUATOR

HWH/HWHR PIPE (AS APPLICABLE)

AIR FLOW

SUPPLY BOX

RETURN BOX (RB)

S/A

1

1

2

TO DUCT SIZE SHOWN ON PLANS

DUCT SIZE AS NOTEDON PLANS

NOTED ON PLANSDUCT SIZE AS

PROVIDE SOUND ATTENUATOR AT TERMINAL UNIT.2

TO DUCT SIZE SHOWN ON PLANSTRANSITION FROM UNIT CONNECTION

R/AORE/A

DUCT SIZE SHOWNON AIR TERMINAL UNITSCHEDULE

HEATING COIL

UNION, TYP.

TEST PLUG

SCREWHEAD VENT

REDUCER, IF REQUIRED

HWHR

HWH1.

SWINGJOINT, TYP.

NOTES:

COILS IN EQUIPMENTLOOSE COILS IN DUCTWORK AND HTGTYP. FOR AIR TERMINAL UNIT COILS,

CONNECT COIL(S) TO PROVIDETEMPERATURE COUNTER FLOWBETWEEN AIR & WATER.

2.

HANGER ROD3/8" MIN. DIA.

WASHERSNUTS &

INSERTS, TYP.3/8" MIN. DIA.

FLOOR SLAB

FOR PIPES UNDER 2" IN SIZEUSE 1 1/2" x1 1/2" x 1/4" ANGLE.ALL PIPES 2" AND LARGERUSE 3"x3"x1/4" ANGLE.

TURNBUCKLE

3/8" MIN. DIA. ANCHORBOLTS OR INSERTS

3/8" MIN. DIA.HANGER ROD

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

-

32

24

-

30

20

-

28

18

-

27

16

-

25

14

-

23

12

-

22

10

16

19

8

14

17

6

13

16

5

12

14

4

10

12

3

9

11

21/2

8

10

2

8

9

11/2

7

7

11/41

7

65 FT

7 FT

THRU 3/4"

TUBING

PIPE

NOM. SIZE

MAXIMUM PIPE/TUBING SUPPORT SPACING, FEET

SIDE VIEW

TO 1000 LB. UNIFORM LOADTRAPEZE HANGER FOR UP

TYPE 43 IN SPECIFICATIONSADJUSTABLE ROLLER HANGER

TYPE 1 IN SPECIFICATIONSADJUSTABLE CLEVIS HANGER

1" MAX. ANGLECHANNEL OR 2"x2"x1/4"1 5/8" 12 GAGE

ALL PIPING (8" MIN.)SHIELD & INSERT FORPROVIDE INSULATION

BAND

ON EACH CHANNELWITH 36" MAX. SPACING1/2" DIA. HANGER RODS

SADDLE

WELD

INSULATION

HANGER ROD

INSULATION SHIELD AT HANGER

BLOCKS UNDER INSULATION SHIELDSTRENGTH INSULATION INSERTPROVIDE HIGH COMPRESSIVE

TEMPERATURE PIPE)TYPE IS REQUIRED FOR LOWINSULATION (VAPOR BARRIER

HANGER ROD

ACCESSIBLE LOCATION

2. IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN.1. VENT ALL HIGH POINTS AS INDICATED ABOVE.NOTES:

PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.2. WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR1. DRAIN ALL LOW POINTS AS INDICATED ABOVE.NOTES:

DRAIN VALVE CONNECTION

AIR VENTELEVATION

WELDED PIPING

ELEVATION

THREADED PIPING

ELEVATION

CIRCULATING WATER PIPING

REDUCER

4" NIPPLE GATE VALVE, (EASILY ACCESSIBLE)

COPPER TUBING, EXTEND TO

CAP NUT

THREAD, PROVIDE HOSEADAPTER TO 3/4" HOSE

3/4" GATE VALVE

REDUCER, IF REQUIRED

TYPICAL WATER PIPING

PIPE SUPPORT

PIPE SUPPORT

PIPE

INSULATION

PIPE GUIDE

'W'

PIPE SIZE

1" TO 6"

8" TO 16"

DIMEN. 'W'

6"

8"

MAX. MOVEMENT

+/- 4"

+/- 6"

DIMENSION TABLE

GENERAL

NO BRACING AS SHOWN ON DETAILS OR CALLED FOR IN SPECIFICATIONSIS REQUIRED IF THE TOP OF THE DUCT OR PIPE IS SUSPENDED 12" INCHES

WALLS, INCLUDING DRYWALL PARTITIONS MAY REPLACE REQUIRED TRANSVERSE ORVERTICAL BRACING FOR DUCTWORK ATTACHMENT TO WALL STUD IS REQUIRED.

ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES INCLUDED INFEDERAL SPECIFICATION WW-H-171 (MSS SP-58) OR BE BOLTED/WELDEDAS APPROVED BY THE RESIDENT ENGINEER. BRACES SHALL BE CONNECTEDTO THE HANGERS/SUPPORTS FOR DUCTS.

SEE THE SPECIFICATIONS FOR REQUIRED STRENGTH OF BRACING.

LATERAL SEISMIC FORCE SHALL BE CONSIDERED TO ACT CONCURRENTLYWITH THE LOAD. THE SLENDERNESS RATIO (1/R) OF BRACESSHALL NOT EXCEED 200, WHERE (L) IS THE LENGTH OF THE BRACEAND (R) IS THE LEAST RADIUS OF GYRATION, BOTH IN INCHES.

SWAY BRACING METHODS SHOWN IN LATEST EDITION OF NFPA 13 (SPRINKLERPIPING) MAY BE USED IN LIEU OF DETAILS SHOWN ON THE DRAWINGS FORPIPING AND DUCTWORK.

DUCTWORK

BRACE ALL RECTANGULAR DUCTS OF 6 SQ. FT. CROSS SECTIONAL AREA AND LARGER.BRACE ALL ROUND/OVAL DUCTS 28 INCHED IN DIAMETER AND LARGER. USE AIRCRAFT

TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 30 FOOT INTERVALS,MAXIMUM. LONGITUDINAL BRACING SHALL OCCUR AT 60 FOOT INTERVALS MAXIMUM.

PIPING

USE AIRCRAFT TYPE CABLE (SLACK) TO RESTRAIN MOVEMENT OF ALL NON BRACED PIPES.

DO NOT FASTEN ONE RIGID PIPING SYSTEM TO TWO DISSIMILAR PARTSOF THE BUILDING THAT MAY RESPOND IN DIFFERENT MODE DURINGAN EARTHQUAKE; FOR EXAMPLE, A WALL OR A ROOF.

DO NOT USE BRANCH LINES TO BRACE MAIN LINES.

EQUIPMENT

REFER TO SPECIFICATIONS SECTION 15200.

SEISMIC JOINT

PROVIDE FLEXIBLE CONNECTORS FOR ALL PIPES AND CONDUITSACROSS SEISMIC JOINTS.

6.

1.

2.

3.

4.

5.

7.

8.

9.

11.

12.

13.

14.

AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THERISER AT A POINT OR POINTS ABOVE THE CENTER OF GRAVITY OF THE RISER

10.

OR LESS FROM THE SUPPORTING STRUCTURAL MEMBER.

TYPE CABLE (SLACK) TO RESTRAIN MOVEMENT OF ALL NON BRACED DUCTS.

PIPE OR OTHER OBSTRUCTIONS.WALL, SUPPORT COLUMN, DUCTS,

UPSTREAM DUCT DOWNSTREAM DUCT

NOTES :

BEFORE INSTALLING THE FILTERSCONSTRUCTION DUST, ETC.,CLEANED TO REMOVESYSTEM SHOULD BEOF THE HOUSING(S), THEFOLLOWING INSTALLATION

WITH SEALANT.OR BY RIVETING AND SEALINGGASKETING AND BOLTING,THE DUCTWORK BY WELDING,PERMANTLY CONNECTED TOTHE HOUSING SHOULD BE

CONNECTING DUCT WORK.IS CORRECT PRIOR TOAND DIRECTION OF AIR FLOWHOUSING ACCESS DOOR(S)BE SURE POSITION OF

3.

2.

1.

(3'-0" MIN.)SUPPLIERAS REQUIRED BY

PLAN VIEW

ACCESS DOOR:

DUCT CONNECTION:

OF HEPA FILTERLOCATED ON UPSTREAM SIDEPREFILTER (WHEN SCEDULED):

AIR

FLOW

CEARANCE FORFILTER CHANGEOUT

HEPA FILTER

DUCT TRANSITION

SEE PLANS FOR DUCT SIZE

REFER TO DETAIL 2/MH6.1.3FOR EXACT DIMENSIONS,4.

INSULATE ANCHOR AS INDICATED FOR COLD PIPINGNOTE:

PLATE3/8" BASE

WELD,

1/2" U-BOLT

INSULATIONPIPE &

INSULATION THICKNESSSUIT PIPE DIA. AND3/8" PLATE, CUT TO

INSULATIONPIPE &

STRUCTURE

OR ANGLESSTRUCTURAL CHANNEL

MIN. SIZE 5/8"2 AT EACH PLATE.ANCHOR BOLTS,

TYP.

CEILING

PIPE

PIPE STANCHION SADDLE

STEEL U-BOLT

WELDS

GALVANIZED PIPE

NOTES:CONTRACTOR TO DESIGN AND SUPPLY SUPPORT SYSTEM.

COMPLETE SUPPORT ASSEMBLY HOT-DIPPED GALVANIZED AFTER FABRICATION NO SCREWS INTODUCTWORK ALLOWED. 2 COAT EPOXY PAINT.

COLD GALVANIZED ALL WELDED JOINTS.

PROVIDE PIPE ROLLERS, VIBRATION ISOLATION AND/OR EXPANSION DEVICES WHERE SPECIFIED OROTHERWISE REQUIRED FOR EXPANSION AND VIBRATION CONTROL.

1.

2.

3.

4.

EXPANSION ANCHORSAS REQUIRED BYCONTRACTOR DESIGN

DECK

18"M

IN.

NOTES:CONTRACTOR TO DESIGN AND SUPPLY SUPPORT SYSTEM.COMPLETE SUPPORT ASSEMBLY HOT-DIPPED GALVANIZED AFTERFABRICATION NO SCREWS INTO DUCTWORK ALLOWED. 2 COAT EPOXY PAINT.

1.2.

FASTENER PERSMACNA STANDARD(TYP)

DUCT STRAP PERSMACNA STANDARD

DUCTWORK

STRUCTURALSUPPORT

DECK

18"M

IN.

NOTES:CONTRACTOR TO DESIGN AND SUPPLY SUPPORT SYSTEM.COMPLETE SUPPORT ASSEMBLY HOT-DIPPED GALVANIZED AFTERFABRICATION NO SCREWS INTO DUCTWORK ALLOWED. 2 COAT EPOXY PAINT.

1.2.

FASTENER PERSMACNA STANDARD(TYP)

DUCT STRAP PERSMACNA STANDARD(TYP)DUCTWORK

(TYP)

STRUCTURALSUPPORT

16"

1" (25) MIN. TYPICALOVERLAP ON ALL SIDESOF DAMPER

1/4" (6) MIN.

DUCT/SLEEVE CONNECTION

CAULKING MATERIAL(MAY BE ON EITHER SIDEOF DAMPER FRAME)

DAMPER

SLEEVE

6" MAXIMUMMAXIMUM

ACTUATOR(LOCATION MAY VARY)

FIRESTATOR SP-100

MOUNTING ANGLES(PFMA, FAST ORCONVENTIONALANGLES,MAY BE INSTALLEDON EITHER SIDE OFTHE PARTITION)

OVER-CENTER LINK

AUXILIARYOPERATINGJACKSHAFT

CSFM LISTINGS: 3225-245:102 3230-245:110

EXTEND DUCTINSULATION AND/ORLAGGING TO WALL ASREQUIRED PERSPECIFICATIONSECTION 23 07 13

PRIMARY STRUCTURAL ORAUXILIARY FRAMING AS REQUIRED

SEISMIC RESTRAINT PERSPECIFICATION SECITION 13 05 41 OFTHE SPECIFICAITON

PIPING SUPPORT ANGLES

PIPE CLAPS

INSULATION

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

46 P

M

HVAC DETAILS

MH6.1.2TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. ANCHORAGE AND RESTRAINTS SHOWN IN DETAILS FOR BOTHSEISMIC AND GRAVITY SUPPORT ARE FOR REFERENCE ONLY. THEDESIGN AND DETAILING OF ALL ANCHORAGE AND SEISMIC RESTRAINTOF MECHANICAL COMPONENTS IS TO BE PROVIDED BY THECONTRACTOR IN ACCORDANCE WITH SPECIFICATION SECTION.

NTS2 TERMINAL UNIT DETAIL

NTS11 REHEAT COIL BRANCH PIPING FROM MAINNTS3 METHOD OF SECURING HANGER RODS DETAIL

NTS12 PIPE HANGERS DETAIL

NTS14 AIR VENT AND DRAIN VALVE CONNECTION DETAIL

NTS13 ALIGNMENT GUIDE DETAIL

NTS1 NOTES FOR SEISMIC BRACING FOR DUCTS

NTS10 SELF CONTAINED HEPA FILTER DETAIL

NTS9 TERMINAL UNIT DETAIL

NTS4 DUCT & PIPE SUPPORT FOOT DETAIL

NTS5 DUCTWORK - ROOF TOP DETAIL

NTS6 STACKED DUCTWORK - ROOF TOP DETAIL

NTS8 FIRE SMOKE DAMPER DETAIL

NTS7 PIPING SUPPORT DETAIL

Page 16: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

9 18

42Wx30H Plain Opening18

24Wx60H Access Door w/ Window17

2In. Prefilter Bank16

(2) 49Wx 33H Cooling Coil(s)15

24Wx60H Access Door w/ Window14

24Wx60H Access Door w/ Window13

(2) 49Wx 33H Heating Coil(s)12

24Wx60H Access Door w/ Window11

36 in. Sound Traps10

Fan & Motor Assy.9

16W x 23H VFD enc.8

24Wx60H Access Door w/ Window7

24Wx60H Access Door w/ Window6

36 in. Sound Traps5

2In. Prefilter w/ 12In. Final Filters4

(1) 18Wx72H Damper3

24Wx60H Access Door w/ Window2

(1) 44Wx66H Louver w/ (1) 30Wx66H Damper1

76

10

64

395

301652301330386030381636

6

182T-184T

182T-184T

182T-184T

182T-184T

17

1615

1413

12

11

10

8

76

54

3

21S D S D SD D S DS D S

7

11

10

9

8

7

6

5

4

3

2

1

76

10

64

2426

363870243830

70

3

18

23

143T-145T

143T-145T

143T-145T

143T-145T

1110

9

8

6

54

3

2

1

24Wx60H Access Door w/ Window

18Wx70H Plain Opening

36 in. Sound Traps

18Wx60H Access Door w/ Window

24Wx60H Access Door

16W x 23H VFD enc.

Fan & Motor Assy.

36 in. Sound Traps

24Wx60H Access Door w/ Window

(1) 20Wx72H Damper

(1) 30Wx60H Louver w/ (1) 30Wx60H Damper

NOTES:DETAIL FOR REFERENCE ONLY.

SEE ARCHITECTURAL DRAWINGS FOR ROOF CURB AND FLASHING REQUIREMENTS

1.

2.

ROOFING

FIRESTOPPING

ROOF CURB ANDFLASHING, SEE ARCH.DRAWINGS (TYP)

DUCT WRAP

DUCT

TRANSITION ASREQUIRED

CONCRETE SLABON METAL DECK

T

GLV NC

LCCR

CONDENSATE

GATE VALVE

3/4" STEAM TRAPTEST VALVE (NC)

GROUND JOINTUNION (TYP.) AS REQUIRED

ROUTING, FITTINGS,

LCSTEAM

0-500 F

GATE VALVE

STEAMCONNECT TO STEAM PIPEOR STEAM POWERED EQUIP.AS REQUIRED BY APPLICATION

DIRT LEG.SEE REQUIREMENTS

USE SCHEDULE 80 PIPE FOR ALLDRIP TRAP PIPING EXPOSED TOSTEAM MAIN PRESSURE(ABOVE 100 PSI).

MIN. 1.5 TIMES PIPE

LESS THAN 8"DIAMETER BUT NOT

8" MIN.

3/4" COPPERDRAIN

STEAM MAIN

AV

SPECIFIEDAIR VENT

SPECIFIEDISOLATIONVALVE

ROOF

PLAN

ELEVATION

PLAN

ELEVATION

NOTE:QUANTITY EACH SIDE AND EACH END.6'-0" MAX. SPACING ON SIDES OF UNIT,MAX. 1'-0" FROM END OF AHU

1.

ANCHOR SCHEDULEAHU

BOLTSENDSIDE

371

AHU CURB

SPACER

APPROX. 8x8x1HOLD DOWN GI PLATE

AHU BASE

3/4" DIA. ANCHOR BOLT

AHU

6" MIN.

4-3/4" MIN.EMBEDMENT

38"

-76"

-

-

24" M

AX

15"

FLOW

PLAN

ACCESS VIEW

18"

-

- 9"

NOTES:ONE (1) FILTER SYSTEM REQUIRED. UNIT SHOWN AS RIGHTHAND ACCESS.

INITIAL FILTERS SUPPLIED BY CAMFIL.

INITIAL CHANGE OUT BAGS SUPPLIED BY CAMFIL.

INLET/OUTLET DUCT CONNECTION FLANGES SHALL BE AMINIMUM OF 1-1/2" WIDE.

APPROX. SHIPPING WEIGHT: 500 LBS. (WITHOUT FILTERS)

A MINIMUM OF FOUR (4) FEET OF CLEARANCE IN FROM OFACCESS DOOR IS RECOMMENDED FOR FILTER CHANGEOUT.

DIRECTION OF ACCESS MUST BE SPECIFIED FORINSTALLATION. TO DETERMINE DIRECTION OF ACCESS,IMAGINE THAT YOU ARE STANDING ON THE UPSTREAM ENDOF THE HOUSING SO THAT THE AIR FLOW WOULD STRIKEYOUR BACK. IF THE DOOR IS ON THE RIGHT AS SHOWN,THEN THE UNIT IS RIGHT HAND ACCESS. IF THE DOOR IS ONTHE LEFT, THEN THE UNIT IS A LEFT HAND UNIT

USE ONE RIGHT HAND ACCESS AND ONE LEFT HANDACCESS AS SHOWN ON MECHANICAL ROOF PLAN.

1.

2.

3.

4.

5.

6.

7.

8.

HOUSING INFORMATION:DAMPER MODEL:

CF-BTFB-8-M-SS

PREFILTER/HEPA HOUSING:CF-1/2x1/2-212P-3GB-SS (REDUNDANT)PREFILTER SIZE: 12"x12"x2" NOM.QTY. PER SYSTEM = 2BAG: 42CX72/3GSTRAP: 54"HEPA FILTER SIZE = 12"x12"x11-1/2"QTY. PER SYSTEM = 2BAG: 56CX96/3GSTRAP: 75"

STATIC PRESSURE TAPS 1/4"NPT SST HALF COUPLINGWITH BRASS PLUG, (3) REQ'D

DIMENSIONS DOES NOT INCLUDE 1/4" FLANGE GASKET

TEST PORT 3/8" NPT SSTHALF COUPLING WITHBRASS PLUG, (3) REQ'D

-

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

48 P

M

HVAC DETAILS

MH6.1.3Checker AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NTS5 DUCT PENETRATION THROUGH ROOF

NTS1 STEAM DISTRIBUTION AND CONDENSATE RETURN DETAIL

NTS3 STEAM THERMOSTATIC AIR VENT

AS NOTED6 AIR HANDLING UNIT SUPPLY SECTION (AHU-1S)AS NOTED7 AIR HANDLING UNIT EXHAUST/RETURN SECTION

AS NOTED4 AHU ANCHORAGE DETAIL

AS NOTED2 EXHAUST FAN (EF-1 AND EF-2) FILTER HOUSING

Page 17: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

SEE

SHEE

T H2

.1.2

D

REFE

RENC

E LI

NE

15-110

15-118

15-108

15-109

16-117

15-1

07

15-105

15-1

12

15-113

15-111

16-114

16-120T

15-108 15-109T

16-114T

16-120T

16-117 T

15-107T

16-105T

15-110T

15-100

15-113

16-118T15-111

T16-125

T

15-118

HRS HRS HRRHRRHWH HWH

HWH

HWH HWHR

HWHR

HWHRHWHR

1“"

2"

1"

Ž"

1"2" 2"

1"

1"2"

EL1.3

EL1.4HP7 HP8

EL1.5

MOMENT GUIDE, TYP.

PIPE ANCHOR, TYP.

3"

1“"

1"

2"

2"

HP7, 8

2"

EMD

1" MPS (59) FA

1" MPR FA1" MPR FA

DN TO HW534 EMD

1" MPR FB

MPR

MPR

ST1.1

ST1.2

1"

T

TTS-6

TS-6T

TTS-6

DCP, SEE H5.2.8

T15-112

2"

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

SB-C77

SB-C55

SB-C44

SB-C66

SB-V99

SB-V1010

SB-C88

SB-V1515

SB-V1414

SB-V1313SB-V

1212SB-V

1111

1-1/2"HHW1-1/2"HHWR

1"HHW1"HHWR

1"HHW1"HHWR

CONS

TRUC

TIO

N ST

AGIN

G A

REA

LIMITS OF CONSTRUCTION.

1"HHW1"HHWR

1/2"HHW1/2"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

3/4"HHW3/4"HHWR

N.I.C.

N.I.C.

N.I.C.

REGI

STER

EDPROFESSIONAL

ENGINEER

STATE OF CALIFORNIA

RAS

MECHAN I CAL

M31875

D WANI.

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 4

:48:

56 P

M

HVAC PIPING PLAN - LEVEL 1

MP2.3.1TY NTJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Phase 3 - Level 1 HVAC Piping Plan

1. TEST AND BALANCE ALL NEW REHEAT COILS TO REGULATE WATERFLOW (GPM)

2. INSTALL NEW PIPESS WITH APPROPRIATE PIPE SUPPORT ANDHANGER WITH ALL REQUIRED ACCESSORIES.

Page 18: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

H

F

G

E

12345678

I

J

J.2

AS

4

4

4

4 44

CONS

TRUC

TIO

N ST

AGIN

G A

REA

AS

3

AS

AS

AS

1 2

LEGENDNON-HATCHED AREAS - LIGHT HAZARD,AUTOMATIC SPRINKLER DESIGN 155°F QUICK RESPONSE,k-5.6 OR k-8.0 HEADS.

HATCHED AREAS - ORDINARY HAZARD GROUP 1,AUTOMATIC SPRINKLER DESIGN 155°F TO 200°F QUICK RESPONSE,k-5.6 OR k-8.0 HEADS.

HATCHED AREAS - ORDINARY HAZARD GROUP 2,AUTOMATIC SPRINKLER DESIGN 155°F QUICK RESPONSE,k-5.6 OR k-8.0 HEADS.

EXISTING, NO WORK

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

33 P

M

FIRE PROTECTION PLAN - LEVEL 1

FX2.0.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Fire Protection Plan

1. AUTOMATIC SPRINKLER SYSTEM DESIGN, ENGINEERING ANDINSTALLATION AS INDICATED ON THIS PLAN SHALL COMPLY WITHNFPA 13, 2013 EDITION, VA DESIGN STANDARDS, VA FIREPROTECTION DESIGN MANUAL.

AUTOMATIC SPRINKLER DESIGN SHALL BE AS NOTED BY HATCHEDAND NON-HATCH AREAS AND SPECIFICATIONS.

ALL PIPING PENETRATIONS THROUGH FIRE RATED ASSEMBLIESSHALL BE SEALED WITH AN APPROVED MATERIAL EQUAL TO THERATING OF SUCH ASSEMBLY.

FIRE PROTECTION DESIGN-BUILD CONTRACTORIS SHALLTEMPORARILY RELOCATE SPRINKLER HEADS AND OTHERPROTECTIVE SYSTEMS IN ORDER TO PROVIDE FULL COVERAGEDURING CONSTRUCTION WHILE CEILING ARE REMOVED AS PART OFTHE WORK COORDINATION REQUIREMENT.

2.

3.

4.

EXISTING CONTROL VALVE FOR EXISTING 3" MAIN.

PROVIDE A NEW FLOOR CONTROL VALVE FROM FIRE WATERMAIN.

PROVIDE NEW SPRINKLER SYSTEM

FIRE PROTECTION DESIGN-BUILD CONTRACTOR TO COORDINATEWITH ARCHITECTURAL DRAWINGS AND MECHANICALCONTRACTORS, PROVIDE SIDEWALL, CONCEALED SPRINKLERSFOR THESE AREA, IF APPLICABLE.

1

2

3

4

Page 19: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

PRESSURE REDUCING VALVE

CHECK VALVE

VALVE IN VERTICAL

COCK VALVE

COLD WATER PIPING

HOT WATER PIPING

HOT WATER RETURN PIPING

SHUT-OFF VALVE

GAS PIPING

DESCRIPTIONSYMBOL

SYMBOLS

CURB VALVE

MIXING VALVE

PIPE DROP, RISE OR DOWN

PIPE CONNECTION, TOP

PIPE CONNECTION, BOTTOM

"P" TRAP

CLEANOUT

CLEANOUT DECK PLATE

CAPPED OUTLET

PIPE UP

VENT THROUGH ROOF

FLOOR DRAIN, AREA DRAIN

YARD HYDRANT

HOSE BIBB

WALL HYDRANT

VACUUM BREAKER ASSEMBLY

THERMOMETER

PRESSURE GAUGE W/VALVE

BACKFLOW PREVENTER

FLOOR, AREA DRAIN (RISER)

ROOF DRAIN (RISER)

WATER HAMMER ARRESTOR

FRESH AIR INLET (FAI)

METER

WATER FILTER

PUMP

DIRECTION OF FLOW

PIPE BREAK

BALANCING VALVE ASSEMBLY

STORM DRAINAGE PIPING BELOW GRADE

STORM DRAINAGE PIPING

VENT PIPING

SANITARY PIPING ABOVE GRADE

SANITARY PIPING BELOW GRADE

RISER DESIGNATION

LEADER DESIGNATION

EQUIPMENT DESIGNATION

CONCENTRIC REDUCER

EXPANSION LOOP

FLEXIBLE CONNECTION

EXPANSION JOINT

AQUASTAT

HOUSE TRAP

BACKWATER VALVE

OS & Y VALVE IN VERTICAL

OS & Y VALVE

T & P RELIEF VALVE

AUTOMATIC AIR VENT VALVE

MOTOR VALVE

GAS PRESSURE REGULATOR

DIAPHRAGM VALVE

BALANCING VALVE

SYMBOL

EXISTING PIPING TO BE ABANDONED

ACID VENT PIPING

ACID WASTE PIPING

EJECTOR PUMP DISCHARGE PIPING

SUMP PUMP DISCHARGE PIPING

DESCRIPTION

ELECTRIC HEAT TRACING

CONDENSATE DRAIN PIPING

STRAINER Y-TYPE

STANDPIPE

FRESH AIR INLET

GREASE WASTE PIPING

INDIRECT WASTE PIPING

EXISTING PIPING TO BE REMOVED

GRAY WATER PIPING

TANK FILL PIPING

TEPID WATER PIPING

VACUUM PIPING

ROOF DRAIN, OVERFLOW DRAIN

SYMBOLS

SOLENOID VALVE

ANGLE VALVE

FLOOR SINK

BASKET STRAINER

WC

UON

MH

NC

NO

EJ

CA

WATER CLOSET

UNLESS OTHERWISE NOTED

NORMALLY OPEN

NORMALLY CLOSED

MANHOLE

EXPANSION JOINT

COMPRESSED AIR

DIMENSIONDIM

EWC ELECTRIC WATER COOLER

GAL GALLON

GPM GALLON PER MINUTE

INDIRECT WASTEIW

DFU DRAINAGE FIXTURE UNIT

VTR

VLV

TYP

V

TD

RPZ

S

ST

REDUCED PRESSURE ZONE

G

PRV

RD

MIN

LG

HB

GH

GD

DIA

FAI

F.F.

FD

EA

COWP

DET

CW

CO

CLG

BFP

SYMBOL

ARCH

DESCRIPTION

ABBREVIATIONS

MINIMUM

LOW PRESSURE GAS

HOSE BIBB

GROUND HYDRANT

GUTTER DRAIN

GAS PIPING

CEILING

FINISH FLOOR

FLOOR DRAIN

FRESH AIR INLET

EACH

DIAMETER

DETAIL

DOMESTIC COLD WATER

CLEANOUT WALL PLATE

CLEANOUT

BACKFLOW PREVENTER

ARCHITECTURAL

PRESSURE REDUCING VALVE

ROOF DRAIN

SANITARY WASTE

STORM DRAINAGE

TRENCH DRAIN

TYPICAL

VENT

VALVE

VENT THROUGH ROOF

AD AREA DRAIN

BLDG BUILDING

CONN

CONT

CONNECTION

CONTINUATION

DN DOWN

DWG

DSN

DRAWING

DOWNSPOUT NOZZLE

EQ

EL

EQUAL

ELEVATION

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FL FLOOR

HWR

HW

DOMESTIC HOT WATER RETURN

DOMESTIC HOT WATER

MECH MECHANICAL

VIF VERIFY IN FIELD

W/O WITHOUT

WH WALL HYDRANT

WHA WATER HAMMER ARRESTOR

YH YARD HYDRANT

FS FLOOR SINK

NTS NOT TO SCALE

OD OVERFLOW DRAIN

I.E. INVERT ELEVATION

W WASTE

W/ WITH

SF SQUARE FEET

VAC

TW

TF

SPD

IW

GW

FAI

EPD

CD

AW

AV

G

ST

ST

S

S

BFP

M

F

M

S

EJ

VB

POINT OF DISCONNECTION FOR EXISTING WORK

POINT OF CONNECTION NEW PIPE TO EXISTING

WATERTIGHT PIPE SLEEVE, BEAM PENETRATION

DCV DOUBLE CHECK VALVE

MAX MAXIMUM

MG MEDIUM PRESSURE GAS

GRW

NON-POTABLE WATER PIPINGNP

OWERFLOW DRAINAGE PIPINGOD

OXYGEN PIPINGO2

NITROGEN PIPINGN2

CARBON DIOXIDE PIPINGCO2

TP TRAP PRIMER

TRAP PRIMER PIPINGTP

CODP CLEANOUT DECK PLATE

FCO FLOOR CLEANOUT

WCO WALL CLEANOUT

TP TRAP PRIMER

ST#

*#

P#

BALL VALVE

TMV THERMOSTATIC MIXING VALVE

CSS CLINICAL SERVICE SINK

DR DRAIN

PLUMBING GENERAL NOTES:THE ENTIRE DESIGN AND INSTALLATION OF THE PLUMBING SYSTEMS SHALL COMPLY WITH CURRENT VA'S PLUMBING DESIGN MANUAL AND INTERNATIONALPLUMBING CODE 2012 EDITION.

ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO ALL APPLICABLE LOCAL CODES AND REGULATIONS.

DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW DRAWINGS IN LAYING OUT WORK ANDCHECK DRAWINGS OF OTHER TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND SPACECONDITIONS AT ALL TIMES.

COORDINATE PLUMBING SYSTEMS WITH WORK OF ALL OTHER TRADES PRIOR TO ANY FABRICATION OR INSTALLATION. PROVIDE ALL FITTINGS, OFFSETS, ANDTRANSITIONS AS REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

PLATFORMS, PITS, AND FLASHINGS FOR PLUMBING EQUIPMENT SHALL BE AS INDICATED ON THE STRUCTURAL AND ARCHITECTURAL PLANS, UNLESS NOTEDOTHERWISE. COORDINATE EXACT SIZES OF REQUIRED OPENINGS AND SUPPORTS FOR FURNISHED EQUIPMENT.

ALL EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND APPLICABLE CODES.PROVIDE ALL FITTINGS, TRANSITIONS, VALVES, AND OTHER DEVICES REQUIRED FOR A COMPLETE WORKABLE INSTALLATION.

MAINTENANCE LABEL SHALL BE AFFIXED TO ALL PLUMBING EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED TO OWNER.

THE CONTRACTOR SHALL VISIT THE JOB SITE TO DETERMINE EXISTING CONDITIONS, BECOME FULLY FAMILIAR WITH EXISTING SPRINKLER INSTALLATION,COMPARE SAME WITH DRAWINGS AND SPECIFICATIONS AND SATISFY HIMSELF OF ALL CONDITIONS PRIOR TO SUBMISSION OF A BID PROPOSAL. SUBMISSIONOF A COST PROPOSAL (BID) WILL BE JUDGED AS EVIDENCE THAT SITE EXAMINATION HAS BEEN MADE. CLAIMS FOR EXTRA COSTS FOR LABOR, EQUIPMENT,OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD SUCH EXAMINATION BEEN MADE WILL NOT BERECOGNIZED.

EXISTING PLUMBING PIPING SYSTEMS SHOWN ON THESE DRAWINGS ARE BASED ON INFORMATION TAKEN FROM EXISTING DESIGN DRAWINGS AND SURVEYOF ACCESSIBLE LOCATIONS AND ARE INDICATIVE ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING SYSTEMS, EXACTLOCATION AND SERVICE CONDITIONS. DISCREPANCIES BETWEEN THE INTENT OF THESE DRAWINGS AND THAT WHICH EXISTS IN THE FIELD SHALL BEBROUGHT TO THE ATTENTION OF THE CONSTRUCTION MANAGER PRIOR TO START OF WORK.

CONTRACTOR SHALL REFER TO ALL THE ARCHITECTURAL DRAWINGS FOR PLUMBING RELATED WORK.

CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS INCLUDING BUT NOT LIMITED TO ENTERING MANHOLES, USE OF WATERFROM LOW PRESSURE HYDRANTS, DEMOLITION AND NEW WORK, ETC. PRIOR TO COMMENCE OF WORK.

CONTRACTOR SHALL MAINTAIN THE EXISTING SANITARY AND STORM WATER SYSTEM IN OPERATION AT ALL TIMES.

PROVIDE INSULATION FOR DOMESTIC COLD WATER, HOT WATER AND HOT WATER RETURN PER SPECIFICATION 220711 IN NEW SCOPE.

PROVIDE WRITTEN NOTICE TO THE OWNER AT LEAST ONE WEEK PRIOR TO SHUT DOWN ANY EXISTING SERVICES.

PLUMBING DEMOLITION NOTES:1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

DEMOLITION PLANS ARE PROVIDED TO SHOW GENERAL CONCENTRATION OF DEMOLITION WORK. ADDITIONAL DEMOLITION WORK MAY BE NECESSARY INAREAS WHERE NO DEMOLITION WORK IS INDICATED. ITEMS TO REMAIN AND POINTS OF DISCONNECTIONS/CONNECTIONS ARE SHOWN ON NEW PLANS.

CONTRACTOR SHALL REMOVE ANY PLUMBING FIXTURES LOCATED IN AREAS TO BE DEMOLISHED.

CONTRACTOR SHALL REMOVE ANY EXISTING PIPING IN CONFLICT WITH THE ERECTION OF NEW WALLS AND RELOCATE TO MAINTAIN SERVICE.

EACH BIDDER PRIOR TO BID SHALL VISIT THE SITE TO EXAMINE EXISTING CONDITIONS AND BECOME INFORMED OF THE EXTENT AND CHARACTER OF WORKREQUIRED. NO ADDITIONAL COMPENSATION WILL BE APPROVED DUE TO FIELD CONDITIONS.

EXACT SIZES AND LOCATIONS OF ALL EXISTING PIPING SHALL BE VERIFIED IN FIELD.

ALL EXISTING PIPING TO REMAIN SHALL BE PROTECTED FROM DAMAGE DURING DEMOLITION. ANY DAMAGES INCURRED SHALL BE REPAIRED OR REPLACEDAT NO COST BY THIS CONTRACTOR.

ALL COSTS RESULTING FROM TEMPORARY SHUTDOWNS OF SERVICES SHALL BE BORN BY THIS CONTRACTOR.

SCOPE OF DEMOLITION WORK IN EQUIPMENT ROOMS: REMOVE EXISTING FIRE PUMP, JOCKEY PUMP, FIRE PUMP CONTROLLER, SEWAGE EJECTORS, WATERHEATERS, DOMESTIC WATER PUMPS, AIR COMPRESSORS AND ALL ASSOCIATED ACCESSORIES. DISPOSE EQUIPMENT AS DIRECTED BY OWNER.

CONTRACTOR SHALL MAINTAIN FULL SERVICE TO EXISTING AREAS THAT ARE TO REMAIN. CONTRACTOR SHALL VISIT THE PREMISES TO ASCERTAIN EXISTINGCONDITIONS AND AREAS TO REMAIN IN SERVICE.

PLUMBING DEMOLITION SHALL BE PROVIDED ON SECTION-BY-SECTION BASIS IN FULL COORDINATION WITH NEW PHASING WORK AND PHASING PLANS.COORDINATE ALL DEMO AND NEW WORK TO MINIMIZE EXISTING SYSTEMS DOWN TIME.

REFER TO ARCHITECTURAL AND PHASING DRAWINGS FOR MORE INFORMATION REGARDING ALL AREAS AFFECTED BY NEW CONSTRUCTION, PHASING WORKDESCRIPTION AND CONTRACT LIMIT LINES.

DEMOLITION WORK, NEW WORK AND CONNECTIONS TO EXISTING SHALL BE PROVIDED WITH MINIMUM INTERFERING WITH THE OPERATION OF THE FACILITY.PLUMBING SERVICE SHUTDOWNS OR INTERFERENCE WITH THE ACTIVE AREAS SHALL NOT BE PERMITTED WITHOUT PERMISSION OF THE OWNER.NOTIFICATION OF THE OWNER IN ADVANCE IN WRITING IS REQUIRED PRIOR TO ANY SHUTDOWN. MAKE TEMPORARY CONNECTIONS IF NECESSARY TO INSURECONTINUOUS OPERATION.

IN THE PROCESS OF DEMOLITION, THE CONTRACTOR SHALL EXERCISE EXTREME CAUTION TO PREVENT DAMAGE TO ARCHITECTURAL SURFACES ANDMATERIALS INCLUDING WALLS, FLOORS CEILINGS, WINDOWS, DOORS, MOLDINGS, STRUCTURAL MEMBERS, ETC. THE COST TO REPAIR OR REPLACE ANYMATERIAL DEEMED BY THE ARCHITECT TO HAVE BEEN UNDULY DAMAGED BY THIS CONTRACTOR DURING DEMOLITION OR CONSTRUCTION SHALL BE PAID BYTHIS CONTRACTOR AT NOT ADDITIONAL COST TO THE OWNER.

ALL PLUMBING WORK IN ADJOINING AREAS WHICH IS REQUIRED TO FUNCTION BUT IS AFFECTED BY DEMOLITION AND/OR PHASING WORK SHALL BERECONNECTED AND RESTORED TO ITS PRESENT FUNCTION AS PART OF NEW PLUMBING SYSTEM OF THE BUILDING.

EXISTING WATER AND GAS SERVICES SHALL BE REMOVED AND CAPPED AT THE BUILDING WALL AS SHOWN ON THE DRAWINGS.

PROVIDE MED GAS ALARM CONNECTIONS TO EXISTING BUILDING CONTROL SYSTEM.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

34 P

M

PLUMBING SYMBOLS,ABBREVIATIONS, AND NOTES

PL0.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

PLUMBING SHEET INDEXSHEET DRAWING TITLE

FX2.0.1 FIRE PROTECTION PLAN - LEVEL 1PL0.1.1 PLUMBING SYMBOLS, ABBREVIATIONS, AND NOTESPL0.1.2 PLUMBING SCHEDULESPL1.0.0 PLUMBING SITE PLANPD2.1.1 PLUMBING DEMOLITION PLAN - LEVEL 1PL2.1.1 PLUMBING PLAN - LEVEL 1PL2.3.2 PLUMBING PLAN - ROOF LEVELPL4.01 PLUMBING DOMESTIC WATER RISER DIAGRAMPL4.02 PLUMBING SANITARY WASTE AND VENT RISER DIAGRAMPL4.03 PLUMBING STORM DRAIN RISER DIAGRAMPL5.1.1 PLUMBING DETAILSDGD3.1.1 MEDICAL GAS DEMOLITION PLAN - LEVEL 1DG3.1.1 MEDICAL GAS PLAN - LEVEL 1DG4.01 MEDICAL GAS RISER DIAGRAM

Page 20: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

THE GENERAL LAYOUT OF THE CW, HW, TW, SS, & V PIPING SHOWN ON THE DRAWING INDICATES BRANCH RUNOUTS THAT TERMINATE AT INDIVIDUAL OR GROUP OF PLUMBINGFIXTURES AND EQUIPMENT. THE PIPING SHALL BE CONSIDERED CONTINUOUS AND FINALLY CONNECTED TO THE PLUMBING FIXTURE(S) AND EQUIPMENT. PROVIDE SERVICE SUPPLYSTOPS AT EACH PLUMBING FIXTURE(S) AND EQUIPMENT.

ALL FAUCET FIXTURES, OTHER THAN THOSE FOR PUBLIC LAVATORIES SHALL BE FITTED WITH AN APPROVED FLOW CONTROL DEVICE ALLOWING A MAXIMUM FLOW RATE OF 2.20 GPM.ALL PUBLIC LAVATORY FAUCETS SHALL BE FITTED WITH AN APPROVED FLOW CONTROL DEVICE ALLOWING A MAXIMUM OF 0.5 GPM. ALL SHOWER HEADS SHALL BE FITTED WITH ANAPPROVED FLOW CONTROL DEVICE ALLOWING A MAXIMUM OF 2.50 GPM.

ALL WATER CLOSETS SHALL USE A MAXIMUM OF 1.28 GALLONS PER FLUSH AND ALL URINALS SHALL USE A MAXIMUM OF 0.5 GALLON PER FLUSH.

PROVIDE WATER HAMMER ARRESTERS WITH 6" LONG BRASS NIPPLES FOR ALL FLUSH VALVES AND INSTALL PER MANUFACTURER'S RECOMMENDATIONS. PROVIDE ACCESS PANELSWHERE REQUIRED. PROVIDE 18" HIGH AIR CHAMBERS AT ALL OTHER FIXTURES.

INSULATE ALL LAVATORY AND SINK TRAPS AND HOT AND COLD WATER SUPPLIES PER ADA REQUIREMENTS.

PROVIDE TRAP PRIMER.

NOTES:

APPLIES TO ALL PLUMBING FIXTURESSS/ST

DESCRIPTIONFIXTURE

TAG

PLUMBING FIXTURE SCHEDULE

REMARKS

1

ROUGH-IN

V CW HW TW

P112

P414

WALL HUNG - SENSOR OPERATED, ECO-POWERED WITH BATTERY BACKUP FLUSH VALVE, HEAVY DUTY CARRIER, LOAD RATING TO BE 500 LBS. - ADA COMPLIANCE.1.28 GPF. TOTO CT708EV, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.4"WATER CLOSET 2" 1" - -

WALL HUNG - SENSOR OPERATED, HARD WIRED, THERMOSTATIC MIXING VALVE, GOOSENECK, NON-AERATOR SPOUT, 0.5 GPM FLOWWITH CHICAGO ELECTRONIC DC FUACET 116.103.AB.1, TOTO LT402 SELF-RIMMING LAVATORY- ADA COMPLIANCE, OR APPROVED EQUAL, SEESPECIFICATION FOR DETAILS.

2"LAVATORY 1-1/2" 1/2" 1/2" -

1 2 3 4

5

1

2

3

4

5

6

FD J.R. SMITH 2005, PROVIDE TRAP PRIMER AND CHROME PLATED GRATE, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.2"FLOOR DRAIN 1-1/2" - - - 6

P-801 1/4 TURN, NON-FREEZE WALL HYDRANT WITH INTEGRAL VACUUM BREAKER, MODEL NUMBER 5509QT BY J.R. SMITH. NO LEAD TYPE, OR APPROVEDEQUAL, SEE SPECIFICATION FOR DETAILS.-WALL HYDRANT - 3/4" - -

RPBP-1 WATTS 3/4" REDUCED PRESSURE BACKFLOW PREVENTER., MODEL NUMBER 995QT WITH STRAINER. NO LEAD TYPE,OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.-REDUCED PRESSURE BACKFLOW

PREVENTER - 3/4" - -

RD-1 ROOF DRAIN WITH ADJUSTABLE EXTENSION, MODEL NUMBER 1015 BY J.R. SMITH, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.4"ROOF DRAIN - - - -

OFD-1 OVERFLOW DRAIN WITH ADJUSTABLE EXTENSION, MODEL NUMBER 1074 BY J.R. SMITH, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.4"OVERFLOW DRAIN - - - -

DSN-1 OVERFLOW DOWNSPOUT NOZZLE MODEL NUMBER 1770 BY J.R. SMITH, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.4"OVERFLOW DOWNSPOUT NOZZLE - - - -

TP-1 PR-500 BY PPP INC. PRESSURE DROP ACTIVATED TRAP PRIMER, TO BE USED WITH WATER CLOSETS. FOLLOW MANUFACTURER'SRECOMMENDATION FOR INSTALLATION. PROVIDE ACCESS PANEL IN WALL, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.-TRAP PRIMER - 1/2" - -

TP-2 PRIME-PRO1-500 BY PPP INC. FLOW ACTIVATED TRAP PRIMER, TO BE USED WITH LAVATORY OR SINK FAUCETS. FOLLOW MANUFACTURER'SRECOMMENDATION FOR INSTALLATION. PROVIDE ACCESS PANEL IN WALL, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.-TRAP PRIMER - 1/2" - -

P530 2"SINK 1-1/2" 1/2" 1/2" -WALL HUNG, VITREOUS CHINA, COMRADE BY AMERICAN STANDARD WITH ANTI-LIGATURE FAUCET, HARD WIRED, SENSOR OPERATED THERMOSTATIC MIXINGVALVE, NON-AERATOR SPOUT 1.5 GPM FLOW, LAV SHIELD PROTECTIVE ANTI-LIGATURE, LAV ENCLOSURE BY TRUEBRO, BSP LIGATURE RESISTANT SENSORFAUCET, AMERICAN STANDARD COMRADEWALL-HUNG LAVATORY, OR APPROVED EQUAL, SEE SPECIFICATION FOR DETAILS.

MEDICAL GAS OUTLET ROUGH-IN SCHEDULE

TAG O2 REMARKSDESCRIPTION

MGO-1 HEADWALL FOR HW02 TRIAGE EXAM ROOM A1-203.

MA MV N2O N2 WAGD

- --(1) 1/2" (1) 1/2" (2) 3/4"

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

8/20

16 1

:57:

01 P

M

PLUMBING SCHEDULES

PL0.1.2GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Page 21: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

DN

H

F

G

E

12345678

I

J

J.2

6"S (343 FU)IE=95.29'

8"ST (14,530 SQ. FT.)IE=96.25'

4"S (110 FU)IE=96.63'

4"S (13 FU)IE=96.00'

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

36 P

M

PLUMBING SITE PLAN

PL1.0.0GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1" = 10'-0"1 Plumbing Site Plan

Page 22: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

SR

OLRL

OL RL

OL

RL

SS

SS

SS

SS

SSSS

SSSS

TP

TP

DIR

DI

G LA CO2

LV

OLRL

CD

CDCD

CD

RLOL

2"

2" 2"

2" SR (D) FA

S=1% 3"

4"

4"

4"

4"

4"

WCO

2"

4"

4"

3"

2"

2"

4"

2" 6"

4"

4"

6"

4"

4"

3"

4"

4" SS (100 FU)IE 94.50'

4"

2"

4"

2"

2"

4"

6"

8" RL (14,650 )IE 95.50'

8" OL (14,650 )IE 95.50'

6" SS (462.5 FU)IE 94.00'

6"

4"

4"

2"

2"

2"

6" OL (7,03 )IE 94.00'

6" RL (7,03 )IE 94.00'

6" SSIE 94.50'(333 FU)

2"

4"

4"

4"

4"SS

4"

4(E)"

4"

2"

2"

4"

2"

4" 2"

2"

TO 3"SS

2"

2"4"

2"

1/2"

2"

4"

2"

2"

1"2"

3"21/2"

2"1/2"

2" VR

1/2" CW (D) TO TP

4" HUB DRAIN FOR FSSYSTEM DRAIN.

3/4"

11/4"2"11/4"21/2"3"

11/4"

11/2"1"

3/4"

11/4"21/2"

3"

P-114

2"

2"

2" V (R) FB

2"

2"

WCO

WCO

2" V (R) TA

1"

3/4"

WCO

2" W (D) FA (TB)

2"

11/2"

1"

3/4" 1/2"

" CW (D)

1/2"

11/2"

3/4"

11/2" V (R) TA

11/2"

3/4"11/4"

3/4"

11/4"

(TYP)

2"

34 "

2"112"1"

2"

2"

114 "

3"

CORR

P-801

34"2" VR, TA

2" VR, TA

2" VR, TA

2"

34"

2"

34"

112"

112"

34"

1"

1-1/4"

2" VR, TA

34 "

P609

1"

3"2-1/2"1-1/4"

FCO

3/4"1-1/4"

FCO

2"

1"1-1/2"

2"

2"

2"

2"

2"

1/2"

3/4"

2"

1"

2"

2"

3"VR,

8"RL/OL

3/4"

2"

2"114 "

TA

3"VR, TA2"

2"

2"

FCO

FCO (TYP)

FCO

(E)2"VR

FCO

2"

3/4"

P112

P418

P701

P701

3/4"

2"P112

P415

2"FD

2"FDP520

1-1/4"1"

P418

P420P414

P104

1/2"

2" P420

1/2"

P420

P420

P420

1/2"

P418

P418

P418

P418

WCOP418

P420

P418P418P418

WCO2"

2"

P418

P112P1122"FD 2"FD

P418

P418

P420

P505

P415

P418

P112

P112

P418

2"FS

2"

1-1/4"

2"FD

2"FD

3/4"

3/4"

P708

3/4"

P418

FCO

P507

WCO

2"

WCO

3"

4(E)" CO

(E) 2"VR

3/4"3/4"

11/4"

34"

P701P104

2"FD

P418

FCO2"FD2"

DI1A

CH1A

G1A

2"

3"VR

P418 P418FCO

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) ADMINELEGIBILITY

A1-100

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) PSYCHEVAL

A1-136

(E) ERRECEPTION

A1-120

(E) AE WORKROOMA1-119

(E) 3 ERISOLATION

ROOMA1-206

(E) MAINELEC.

SEV1.1

(E) 2 EREXAM RM

A1-204

(E) NURSESTATIONA1-220

(E) ERWAITINGA1-125

(E) TOILETA1-127

(E) TOILETA1-129

(E) 8 ENTROOMA1-201

(E) 9 EREXAM RM

A1-205

(E) 10 EREXAM RM

A1-211(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E) SOILEDUTILITYA1-226

(E) ER MEDROOMA1-224

(E) TOILETA1-322

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E) EDOU 2A1-325B

(E) EDOU 3A1-325C

(E) EDOU 4A1-325D

(E) 1 EREXAM RM

A1-202

(E)CORRIDOR

A1-C13

(E) ERTRIAGEA1-209

(E) ERTRIAGEA1-207

(E) TOILETA1-416A

(E) WOMEN'SLOCKERA1-416(E) MEN'S

LOCKERA1-418

(E) TOILETA1-418A (E) STAFF

LOUNGEA1-410

(E) HACA1-414

(E) ANTEROOMA1-208

(E) 7 EREXAM RM

A1-218

(E) 6 EREXAM RM

A1-216

(E) 5PROCEDURE

ROOMA1-418D

(E) 4 ERCODE ROOM

A1-212

(E)PHYSICIAN

WORKROOMA1-210

(E)CONFERENCE

A1-211

(E)STORAGE

A1-340(E) TOILET

A1-334

(E) TOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUEQUIPMENT

ROOMA1-330

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

A1-TC1T-1.6

(E) SIGNALS-1.6 (E) EDOU

MED ROOMA1-325G

(E) SOCIALWORKERA1-331

(E) OFFICEA1-235

(E) NURSEOFFICEA1-245

(E) EDOU 6A1-325F

(E) EDOU 5A1-325E

(E) EMS HACA1-324

(E) NURSESTATIONA1-225

(E) EDOUSOILEDUTILITYA1-328

(E)CONFERENCE

A1-333

(E) STAFFTOILETROOMA1-403

(E)PHYSICIAN

CALL ROOMA1-402

(E)PROGRAMSUPPORT

ASSTA1-401

(E) STAFFLOUNGEA1-421

H

F

G

E

12345678

I

J

J.2

7

77

CONS

TRUC

TIO

N ST

AGIN

G A

REA

4

3

12

3

2

5

5 3

N.I.C.

N.I.C. N.I.C.

8

9

10

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

34 P

M

PLUMBING DEMOLITION PLAN - LEVEL1

PD2.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Plumbing Plan Demo

CUT AND CAP.

CUT AND PLUG.

PIPING SHALL BE REMOVE/DEMOLISH.

PIPING AND PLUMBING FIXTURE SHALL BE REMOVED. PLUGWASTE PIPE BELOW FINISH FLOOR

DO NOT DISCONNECT HW UNTIL REROUTING HW HAS BEENINSTALLED AND INSPECTED.

PLUG WATER WITH GAS TIGHT COVERS.

PLUG COVER.

CUT AND CAP AS CLOSE AS POSSIBLE TO THE MAIN.

REMOVE P-801 AND ASSOCIATED PIPING BACK TO MAIN.

SITE VERIFY THIS WATER LINE. IF IT'S SERVING ACTIVE PLUMBINGFIXTURE, REPORT BACK TO PROJECT PLUMBING ENGINEER; IF ITIS NOT SERVING ANY ACTIVE PLUMBING FIXTURE / EQUIPMENT;CUT AND PLUG BACK TO THIS POINT (TO BE CONNECTED TO THENEW P-801), AND REMOVE THE NOT-IN-USED PIPING.

1

2

3

4

5

6

7

8

9

10

Page 23: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

SR

OLRL

OL RL

OL

RL

SS

SS

SS

SS

SSSS

SSSS

TP

TP

DIR

DI

G LA CO2

LV

OLRL

CD

CDCD

CD

RLOL

2"

2" 2"

2" SR (D) FA

S=1% 3"

4"

4"

4"

4"

4"

WCO

2"

4"

4"

3"

2"

2"

4"

2" 6"

4"

4"

6"

4"

4"

4"

4" SS (100 FU)IE 94.50'

4"

2"

4"

2"

2"

4"

6"

8" RL (14,650 )IE 95.50'

8" OL (14,650 )IE 95.50'

6" SS (462.5 FU)IE 94.00'

6"

4"

4"

2"

2"

2"

6" OL (7,03 )IE 94.00'

6" RL (7,03 )IE 94.00'

6" SSIE 94.50'(333 FU)

2"

4"

4"

4"

4"SS

4"

4(E)"

4"

2"

2"

4"

2"

4" 2"

2"

TO 3"SS

2"

2"4"

2"

1/2"

2"

4"

2"

2"

1"2"

3"21/2"

2"1/2"

2" VR

1/2" CW (D) TO TP

4" HUB DRAIN FOR FSSYSTEM DRAIN.

3/4"

11/4"2"11/4"21/2"3"

11/4"

11/2"1"

3/4"

11/4"21/2"

3"

P-114

2"

2"

2" V (R) FB

2"

2"

WCO

WCO

2" V (R) TA

1"

3/4"

WCO

2" W (D) FA (TB)

2"

11/2"

1"

3/4" 1/2"

" CW (D)

1/2"

11/2"

3/4"

11/2" V (R) TA

11/2"

3/4"11/4"

3/4"

11/4"

(TYP)

3"VR

2"

34 "

2"112"1"

2"

2"

114 "

3"

CORR

2" VR, TA

2" VR, TA

2" VR, TA

2"

34"

2"

34"

112"

112"

34"

1"

1-1/4"

2" VR, TA

34 "

P609

1"

3"2-1/2"1-1/4"

FCO

3/4"1-1/4"

FCO

2"

1"1-1/2"

2"

2"

2"

2"

2"

1/2"

3/4"

2"

1"

2"

2"

3"VR,

8"RL/OL

3/4"

2"

2"114 "

TA

3"VR, TA2"

2"

2"

FCO

FCO (TYP)

FCO

(E)2"VR

FCO

2"

3/4"

P112

P418

P701

P701

3/4"

2"P112

P415

2"FD

2"FDP520

1-1/4"1"

P418

P420P414

P104

1/2"

2" P420

1/2"

P420

P420

P420

1/2"

P418

P418

P418

P418

WCOP418

P420

P418P418P418

WCO2"

2"

P418

P112P1122"FD 2"FD

P418

P418

P420

P505

P415

P418

P112

P112

P418

2"FS

2"

1-1/4"

2"FD

2"FD

3/4"

3/4"

P708

3/4"

P418

FCO

P507

WCO

2"

WCO

3"

4(E)" CO

(E) 2"VR

3/4"3/4"

11/4"

34"

P701P104

2"FD

P418

FCO2"FD2"

DI1A

CH1A

G1A

3"

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

4" 12

S

4"

12

6"

8" TP

TP

2

6"SIE=95.29'

8"STIE=96.25'

4"SIE=96.63'

4"SIE=96.00'

12

12

P4143

1

1-1/2"

1" 6

FCO2"FD

3

P414

TPV

TPV

2"FD

1/2"

WCO

FCO

1

P112

P112

WCO

2

1/2"

SST

FCO

S

9

4"

4"

4"

4"

6"

ODST

8

7

7

8

7 8

ODST

11810

DSN-1

P-801

3/4"

OD

ST

OD

SST

FCO1

P530

1-1/2"

2"

1/2"

7

6"

6"6"8"

CONS

TRUC

TIO

N ST

AGIN

G A

REA

1-1/2"

1"

1"

4

5

N.I.C.

N.I.C. N.I.C.

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

38 P

M

PLUMBING PLAN - LEVEL 1

PL2.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. PROVIDE HW AS CLOSE AS POSSIBLE TO FIXTURES (NO MORE THAN 5FEET OF DEAD LEG) PER VA STANDARD.

PROVIDE WATER HAMMER ARRESTOR (WHA) FOR ALL LINES WITHQUICK CLOSING VALVES (FLUSH VALVES AND SENSOR OPERATEDFAUCETS.)

PROVIDE 2" FLOOR DRAIN FOR ALL TOILET ROOMS, PROVIDE TRAPPRIMER CONNECTION TO ALL FLOOR DRAINS.

PROVIDE POINT OF USE TMV FOR ALL LAVATORIES/HAND WASHSINKS.

PROVIDE FIRE RATED SLEEVE FOR PIPING PENETRATING FIRE RATEDWALL.

INVERT ELEVATION SHOWN HERE ARE = (E)IE + SLOPE + 2.7',EXISTING INVERT ELEVATION PER AS BUILT DRAWINGS MAY NOT BEACCURATE. PLUMBING CONTRACTOR TO VERIFY ALL SITECONDITIONS INCLUDING INVERT ELEVATIONS ON SITE PRIOR TOINSTALLATION.

2.

3.

4.

5.

6.

1/8" = 1'-0"1 Level 1 Plumbing Plan

1/2"CW, 1/2"HW AND 1-1/2"V DOWN, AND 2"S FROM BELOWFLOOR.

2"V DOWN.

1-1/4"CW AND 2"V DOWN, AND 4"S FROM BELOW FLOOR.

3"V UP THROUGH ROOF.

NEW 1-1/2" CW TAP TO THE NEAREST CW BRANCH (2" ORLARGER). IF THERE IS NO 2" BRANCH AVAILABLE, TAP TO THECW MAIN WITH SHUTOFF VALVE.

REROUTE 1"HW MAIN, KEEP EXISTING HW MAIN RUNNING UNTILTHE NEW BRANCHES HAVE BEEN COMPLETED, INSPECTED,FLUSHED, DISINFECTED AND ACCEPTED BY THE OWNER'SREPRESENTATIVE.

4"ST UP TO ROOF DRAIN.

4"OD TO OVERFLOW DRAIN.

6"ST DOWN BELOW FLOOR.

6"OD DOWN.

4"ST DOWN BELOW FLOOR.

FOR CONTINUATION SEE PL1.0.0.

1

2

3

4

5

9

7

6

10

11

8

12

Page 24: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

DN

UP

DN

106 SF

(E) MEDA2-120A

159 SF

S. UTILA2-150

137 SF

(E) C. UTILA2-122

H

F

G

E

12345678

I

J

J.2

4"OFD-14"RD-14"OFD-14"RD-1

4"OFD-14"RD-1

4"RD-1

4"OFD-1

(2,600 SQ.FT.)

(2,200 SQ.FT.) (2,400 SQ.FT.)

(300 SQ.FT.)

3"VTR

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

40 P

M

PLUMBING PLAN - ROOF LEVEL

PL2.3.2GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Roof Level Plumbing Plan

Page 25: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

LEVEL 01

LEVEL 02

(E) CW

1-1/2"1/2"

1"

(E) HW(E) CW

(E) HW

TP-1

TP

WHA A1

-150

P112

A1-1

50P4

14

A1-1

52P5

20 WHA

TP-1

TP

WHA A1

-150

P112

1-1/2" (22.25 WSFU)

(E) CW(E) HW

(E) CW(E) HW

1/2"1/2"

A1-2

03P5

30 WHA

(E) CW(E) HW

1/2" (0.75 WSFU)1/2" (0.75 WSFU)1-1/4" (10.0 WSFU)

1-1/4" (10.0 WSFU)1/2" (1.5 WSFU)1/2" (1.5 WSFU)

(E) CW(E) HW

1-1/2" (21.5 WSFU)

1/2" (1.5 WSFU)1/2" (1.5 WSFU)

(E) CW(E) HW

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

40 P

M

PLUMBING DOMESTIC WATER RISERDIAGRAM

PL4.01GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NO SCALE1 Plumbing Domestic Water Riser Diagram

Page 26: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

LEVEL 01

LEVEL 02

3"

A1-1

52P4

14

FCO

A1-1

522"

FD

4"

(E) 4"S

4" (10.0 DFU)

4"S FORCONTINUATION SEECIVIL DRAWINGS4"S

A1-2

03P5

30

1-1/2"

FCO

2"

(E) S

(E) 2"V

1-1/2"

A1-1

50P1

12

A1-1

52P1

12

FCO

A1-1

502"

FD

A1-1

50P4

14

2"2"2"

TP

WCO

WCO

2"

2"

TP2" (2.0 DFU)

4" (5.0 DFU)

4" (5.0 DFU)

2" (4.0 DFU)

2" (1.0 DFU)

4" (14.0 DFU)4" (15.0 DFU)

4" (5.0 DFU)

2" (1.0 DFU)

4" (20.0 DFU)

3"VTR

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

40 P

M

PLUMBING SANITARY WASTE ANDVENT RISER DIAGRAM

PL4.02GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NO SCALE1 Plumbing Sanitary Waste and Vent Riser Diagram

Page 27: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

LEVEL 01

LEVEL 02/R00F

8"ST (14,530 SQ.FT.)FOR CONTINUATIONSEE CIVIL DRAWINGSST

4"RD-1 4"OFD-1

(E) 6"ST

LEVEL 01 SUB-ROOF

4"RD-1 4"OFD-1 4"RD-1 4"OFD-1

4"

4"

4" (4,600 SQ.FT.)

4" (4,600 SQ.FT.)

6"

STOD

OD

STOD

STOD

ST

OD

6"6"

ST

ST

STST

8" (14,230 SQ.FT.)

OD

4"RD-1 4"OFD-1

ST

6" (7,200 SQ.FT.) 4" (300 SQ.FT.)

4"

6" (7,500 SQ.FT.)

ODOD

ST

NOTE:

1. RAINFALL RATE: 1.5"/HR, 100 YEAR EVENT.

(2,600 SQ.FT.)

(E) (7,030 SQ.FT.)

(2,200 SQ.FT.)

6" (7,200 SQ.FT.)

(2,400 SQ.FT.)

(300 SQ.FT.)

DSN-1,DAYLIGHT TOEXTERIOR

(E) 6"OD FROMLEVEL 02

6"

DSN-1,DAYLIGHT TOEXTERIOR

OD(E) OD6"

REROUTED 6"OD

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

41 P

M

PLUMBING STORM DRAIN RISERDIAGRAM

PL4.03Checker LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NO SCALE1 Plumbing Storm Drain Riser Diagram

Page 28: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

000

1

HRIN HRDIAM, IN

1 OR 23/16 TO 3/8123 OR 41/4 TO 1/26

1 OR 20 TO 1-1/2#401 OR 20 TO 1/44

3 OR 43 OR 41/4 TO 1/20+, 1 OR 21 OR 20 TO 3/161

T RATING,F RATING,ANNULAR SPACE,MAX PIPE OR CONDUIT

(FORMERLY SYSTEM NO. 147)

SYSTEM NO. W-L-1001

SECTION A-A

A

A

F-RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2AND 3)T RATINGS - 0, 1, 2, 3 AND 4 HR (SEE ITEM 3)L RATING AT AMBIENT - LESS THAN 1 CFM/SQFTL RATING AT 400 F - LESS THAN 1 CFM/SQ FT

2

3 3

1A

1B

1. WALL ASSEMBLY - THE 1, 2, 3, OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUDWALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNERDESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNSIN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWINGCONSTRUCTION FEATURES:

A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 H FIRERATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OFNOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC WITH NOM 2 BY 4 IN. LUMBER END PLATESAND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. WIDE BY 1-3/8 IN. DEEPCHANNELS SPACED MAX 24 IN. OC.

B. WALLBOARD, GYPSUM* - NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE ORTAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OFLAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THEINDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY.MAX DIAM OF OPENING IS 13-1/2 IN.

2. PIPE OR CONDUIT - NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER)STEEL PIPE, NOM 12 IN. DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CASTIRON PRESSURE PIPE NOM 6 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLICTUBING, NOM 6 IN. DIAM (OR SMALLER) TYPE L OR (OR HEAVIER) COPPER TUBING ORNOM 1 IN. DIAM (OR SMALLER) FLEXIBLE STEEL CONDUIT. WHEN COPPER PIPE ISUSED, MAX F RATING OF FIRESTOP SYSTEM (ITEM 3) IS 2 H. STEEL PIPES ORCONDUITS LARGER THAN NOM 4 IN. DIAM MAY ONLY BE USED IN WALLSCONSTRUCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT ISPERMITTED IN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEARCENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUPPORTED ON BOTH SIDESOF WALL ASSEMBLY.

3. FILL, VOID OR CAVITY MATERIAL* - CAULK - CAULK FILL MATERIAL INSTALLED TOCOMPLETELY FILL ANNULAR SPACE BETWEEN PIPE OR CONDUIT AND GYPSUMWALLBOARD AND WITH A MIN 1/4 IN. DIAM BEAD OF CAULK APPLIED TO PERIMETEROF PIPE OR CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLEDSYMMETRICALLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OFTHE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING OF THEWALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN ON THE FOLLOWING TABLE.THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPEOR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALLASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:

+WHEN COPPER PIPE IS USED, T RATING IS 0 H. #0 TO 1-1/2 IN. ANNULAR SPACE APPLIESONLY WHEN TYPE CP-25 WB+ CAULK IS USED AND ONLY WHEN THE MIN THICKNESS OFTHE GYPSUM WALLBOARD IS 5/8 IN. FOR 1 HR RATED WALLS AND 1-1/4IN. FOR 2 HRRATED WALLS. MINNESOTA MINING & MFG. CO. - CP 25WB+.*BEARING THE UL CLASSIFICATION MARKING

2"HIGH DAMFOR OVERFLOWOR INTERNAL DAM

GRAVEL BALLAST

STEEL DECK

NO-HUB OUTLET

BEARING PLATE

DOMEREFER TOARCHITECTURALDWGS. FOR ROOFCONSTRUCTION

UNDERDECK CLAMP

GRAVEL BALLAST

STEEL DECK

NO-HUBOUTLET

BEARING PLATE

DOMEREFER TOARCHITECTURALDWGS. FOR ROOFCONSTRUCTION

UNDERDECK CLAMP

TRISOLATOR PIPE SLEEVE:SERIES100 FOR STEEL PIPE OR SERIES500 FOR COPPER

KEEP PIPE CLEAR OFSTRUCTURE, OTHER PIPES,AND OTHER TRADES

FASTEN CLAMP TOSTRUCTURE (TYP.)

WOOD BLOCK INSERT1.

NOTE

PIPING

SEE STRUCTURAL DRAWINGS FORHANGER ROD CONNECTION TOSTRUCTURE.

GALVANIZED INSULATIONPROTECTION SHIELD ATEACH HANGER

INSULATION -SEE SPECS

ADJUSTABLECLEVIS HANGER

HANGER RODSIZE (SEE SPECs.)

FIRE CAULKING SEALANT (SEE SPEC.)

PIPE SLEEVE

TERMINATE SLEEVEFLUSH WITH FINISHEDWALL SURFACES

PIPE ANDINSULATION TO BECENTERED INSLEEVE - DO NOTSUPPORT PIPEFROM SLEEVE

FINISHED ESCUTCHEONPLATE FLUSH AGAINST WALL &OF SIZE TO COMPLETELY COVEROPENING

FINISHEDWALLSURFACE

PIPE CLAMPS

INSULATION

SUPPORT ANGLES OR CHANNELS

NOTE: PROVIDE"SLACK" BRAIDEDCABLE RESTRAINTSCAPABLE OF BEARINGTHE ENTIRESUSPENDED LOAD.

VIBRATION ISOLATOR MASONINDUSTRIES TYPE 30N (1" MIN.STATIC DEFLECTION)

PRIMARY STRUCTURAL ORAUXILARYFRAMING AS REQUIRED

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

41 P

M

PLUMBING DETAILS

PL5.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NTS7 PENETRATION FIRE STOP

NTS2 OVERFLOW DRAIN DETAILNTS1 ROOF DRAIN DETAIL

NTS5 ATTACHEMENT OF PLUMBING PIPES GREATER THAN 1"-4"ø

NTS3 PIPE HANGER AND INSULATION DETAIL

NTS6 PIPE SLEEVE THROUGH INTERIOR FIRE WALL

NTS4 TRAPEZE PIPING OR EQUIPMENT SUPPORT

Page 29: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

MA MVO2NO

MV MANOO2

MAMVO2

MA

MV

O2

MA

MV O2

MAMVO2

MAMVO2

MA

02 MV

MA

MV 02

MA02MV

MA

O2

MV

MAMVO2

MAMVO2

2"

3/4"

OTHERWISE

34"2"

3/4"MV1/2"MA1/2"O2

3/4"MV1/2"MA1/2"O2

1/2"

3/4"

1"

1"3/4"

1-1/2"3/4"

3/4"MV1/2"MA1/2"O2

(TYP OF 5)

3/4" 3/4"

1"1"

3/4"1/2"

1/2"

(TYP OF 3)

(TYP 3)

3/4"

2"

1/2"

1-1/2"

3/4"3/4"

1"

3/4"

3/4"

1"1-1/2"

1-1/2"3/4"

LOCKEDVALVES

MGA

MGV

3/4"

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) ADMINELEGIBILITY

A1-100

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) PSYCHEVAL

A1-136

(E) ERRECEPTION

A1-120

(E) AE WORKROOMA1-119

(E) 3 ERISOLATION

ROOMA1-206

(E) MAINELEC.

SEV1.1

(E) 2 EREXAM RM

A1-204

(E) NURSESTATIONA1-220

(E) ERWAITINGA1-125

(E) TOILETA1-127

(E) TOILETA1-129

(E) 8 ENTROOMA1-201

(E) 9 EREXAM RM

A1-205

(E) 10 EREXAM RM

A1-211(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E) SOILEDUTILITYA1-226

(E) ER MEDROOMA1-224

(E) TOILETA1-322

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E) EDOU 2A1-325B

(E) EDOU 3A1-325C

(E) EDOU 4A1-325D

(E) 1 EREXAM RM

A1-202

(E)CORRIDOR

A1-C13

(E) ERTRIAGEA1-209

(E) ERTRIAGEA1-207

(E) TOILETA1-416A

(E) WOMEN'SLOCKERA1-416(E) MEN'S

LOCKERA1-418

(E) TOILETA1-418A (E) STAFF

LOUNGEA1-410

(E) HACA1-414

(E) ANTEROOMA1-208

(E) 7 EREXAM RM

A1-218

(E) 6 EREXAM RM

A1-216

(E) 5PROCEDURE

ROOMA1-418D

(E) 4 ERCODE ROOM

A1-212

(E)PHYSICIAN

WORKROOMA1-210

(E)CONFERENCE

A1-211

(E)STORAGE

A1-340(E) TOILET

A1-334

(E) TOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUEQUIPMENT

ROOMA1-330

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

A1-TC1T-1.6

(E) SIGNALS-1.6 (E) EDOU

MED ROOMA1-325G

(E) SOCIALWORKERA1-331

(E) OFFICEA1-235

(E) NURSEOFFICEA1-245

(E) EDOU 6A1-325F

(E) EDOU 5A1-325E

(E) EMS HACA1-324

(E) NURSESTATIONA1-225

(E) EDOUSOILEDUTILITYA1-328

(E)CONFERENCE

A1-333

(E) STAFFTOILETROOMA1-403

(E)PHYSICIAN

CALL ROOMA1-402

(E)PROGRAMSUPPORT

ASSTA1-401

(E) STAFFLOUNGEA1-421

H

F

G

E

12345678

I

J

J.2

CONS

TRUC

TIO

N ST

AGIN

G A

REA

1 1

1

1

3 3

3

3

22

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

32 P

M

MEDICAL GAS DEMOLITION PLAN -LEVEL 1

DGD3.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Med Gas Plan Demo

CUT AND CAP.

REMOVE HEADWALL MEDICAL GAS OUTLET.

PIPING SHALL BE REMOVE/DEMOLISH.

1

2

3

Page 30: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

MA MVO2NO

MV MANOO2

MAMVO2

MA

MV

O2

MA

MV O2

MAMVO2

MAMVO2

MA

02 MV

MA

MV 02

MA02MV

MA

O2

MV

MAMVO2

MAMVO2

2"

3/4"

OTHERWISE

34"2"

3/4"MV1/2"MA1/2"O2

3/4"MV1/2"MA1/2"O2

1/2"

3/4"

1"

1"3/4"

1-1/2"3/4"

3/4"MV1/2"MA1/2"O2

(TYP OF 5)

3/4" 3/4"

1"1"

3/4"1/2"

1/2"

(TYP OF 3)

(TYP 3)

3/4"

2"

1/2"

1-1/2"

3/4"3/4"

1"

3/4"

3/4"

1"1-1/2"

1-1/2"3/4"

LOCKEDVALVES

MGA

MGV

3/4"

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

CONS

TRUC

TIO

N ST

AGIN

G A

REA

MGO-1

3/4"

1/2"

2

1

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

31 P

M

MEDICAL GAS PLAN - LEVEL 1

DG3.1.1GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Med Gas Plan

3/4"MV, 1/2"MA AND 1/2"O2 TO MGO-1.

MGO-1, MEDICAL GAS OUTLET.

1

2

1. PROVIDE FIRE RATED SLEEVE FOR PIPING PENETRATING FIRE RATEDWALL.

Page 31: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

LEVEL 01

LEVEL 02

A1-203MGO-1

(E) MA(E) O2

(E) MV

1/2"

MVMA

O2

3/4"

1/2"

1/2"

3/4"

(E) MA(E) O2

(E) MV

(E) MA(E) O2

(E) MV

M31228

M E CH A N I C A

LS TATE OF CAL I FORN

I A

MATTHE

WJ . W I LL I AM

SONREGISTERE

DPROF

ESS I ONAL

ENGI NEE R

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/1

8/20

16 5

:23:

31 P

M

MEDICAL GAS RISER DIAGRAM

DG4.01GJ LEJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NO SCALE1 Medical Gas Riser Diagram

Page 32: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

TYPICAL LIGHTING FIXTURE WITH SHADED AREAINDICATES ON CRITICAL OR LIFE SAFETY CIRCUIT

LIGHTINGDESCRIPTIONSYMBOL

CEILING/WALL EXIT LIGHT AND OUTLET BOX,LED TYPE, SELF CONTAINED, WITH BATTERY PACK:- SHADED AREA INDICATES ILLUMINATED FACE(S)- ARROW INDICATES DIRECTION

EMERGENCY UNIT EQUIPMENT, 90 MINUTEBATTERY PACK, CHARGER AND TEST SWITCH.

NOTE: SEE LIGHT FIXTURE SCHEDULE AND SPECIFICATIONSFOR COMPLETE FIXTURE DESCRIPTION.

DESCRIPTIONSYMBOL

WIRING DEVICES

LINE VOLTAGE SWITCH- LOWER CASE LETTER DENOTES SWITCHING ZONES- 'T' DENOTES SWITCH TYPE:MC - MOMENTARY CONTACTD - DIMMERWP - WEATHER PROOF

LOW VOLTAGE SWITCH

OCCUPANCY SENSOR, CEILING MOUNTED

ABBREVIATIONSDESCRIPTIONSYMBOL

LC

A, AMP AMPERE

AMPS INTERRUPTING CAPACITYAIC

AC ALTERNATING CURRENT

ABOVE FINISHED FLOORAFF

ATC AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCHATS

BAS BUILDING AUTOMATION SYSTEM

BUILDING MANAGEMENT SYSTEMBMS

BFG BELOW FINISHED GRADEC, CDT CONDUIT

CIRCUIT BREAKERCB

CABINET HEIGHTCHCKT CIRCUIT

CONDUIT ONLYC.O., CO

CONFIG. CONFIGURATION

CENTERLINE

CONVENIENCECONV

CM CONSTRUCTION MANAGER

DIGITAL DATA CONTROLDDC

DWG DRAWING

ELECTRICAL CONTRACTORE.C.

ELEC ELECTRICAL

EMERGENCYEM

EMT ELECTRICAL METALLIC TUBING

ELECTRICALLY OPERATED 'ON-OFF'E.O.

EQUALEQ

EWC ELECTRIC WATER COOLER

FIRE ALARMFAFAI FURNISH AND INSTALL

FS FIRE SHUTTER/DOOR

FULL LOAD AMPSFLA

FSD FIRE SMOKE DAMPER

GROUNDG, GND

GEN GENERATOR

GROUND FAULT CIRCUIT INTERRUPTERGFCI

HC HUNG CEILING

HIGH INTENSITY DISCHARGEHID

HAND-OFF-AUTOMATICHOA

HORSE POWERHP

INSTALLED BY ELECTRICAL CONTRACTORIBEC

FURNISHED BY OTHERSFBO

ISOLATED GROUNDIGJB,J JUNCTION BOX

KILO VOLT- AMPEREKVA

KW KILO WATT

KILO WATT HOURKWH

LC

LCP

LOCK & COVER

LIGHTING CONTROL PANEL

POWERDESCRIPTIONSYMBOL

SAFETY DISCONNECT SWITCH, 3 POLE UONA: 30A UNFUSED AF: 30A FUSEDB: 60A UNFUSED BF: 60A FUSEDC: 100A UNFUSED CF: 100A FUSEDD: 200A UNFUSED DF: 200A FUSEDE: 400A UNFUSED EF: 400A FUSED- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

TRANSFORMER, SEE SCHEDULE FOR RATING

RELAY - NUMERAL DENOTES NUMBER OF POLES

SURFACE MOUNTED PANELBOARD

FLOOR MOUNTED DISTRIBUTION/SWITCHBOARD

CONDUIT AND WIRE HOMERUN. CONTINUOUS RUN TOMCC, PANELBOARD, SWITCHBOARD OR EQUIPMENTCABINET.

CONDUIT AND WIRE RUN IN WALL OR CEILING SPACE,OR RUN EXPOSED IN UNFINISHED SPACE.

FUSED DISCONNECT SWITCH- NUMERICAL DENOTES TRIP SIZE- '4x' DENOTES NEMA ENCLOSURE IF INDICATED

AUTOMATIC TRANSFER SWITCH, SEE RISERDIAGRAM FOR RATING

FLUSH MOUNTED PANELBOARD

PULLBOX

RR 6

ATS

4x AF

J

J

J

PB

T4

a,b

Ta,b

XP - EXPLOSION PROOF

O

OCCUPANCY SENSOR, WALL MOUNTEDO

PHOTOCELL CONTROLLER, CEILING MOUNTED

PHOTOCELL CONTROLLER, WALL MOUNTED

LIGHTING CONTACTOR

TIME CLOCK

PUSH BUTTON

REMOTE CONTROL SWITCHRC

TC

LC

SIMPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

QUAD RECEPTACLE WALL MOUNTED, +18" AFF, UON

SPECIAL RECEPTACLE WALL MOUNTED, +18" AFF, UON

SIMPLEX RECEPTACLE CEILING MOUNTED

DUPLEX RECEPTACLE CEILING MOUNTED

QUAD RECEPTACLE CEILING MOUNTED

SPECIAL RECEPTACLE CEILING MOUNTED

SIMPLEX RECEPTACLE FLUSH FLOOR MOUNTED

DUPLEX RECEPTACLE FLUSH FLOOR MOUNTED

QUAD RECEPTACLE FLUSH FLOOR MOUNTED

SPECIAL RECEPTACLE FLUSH FLOOR MOUNTED

JUNCTION BOX RECESSED WALL MOUNTED

JUNCTION BOX RECESSED CEILING MOUNTED

JUNCTION BOX RECESSED FLUSH FLOOR MOUNTED

MISCELLANEOUSDESCRIPTIONSYMBOL

FEEDER SIZE, SEE FEEDER SCHEDULE

REFERENCE NOTE

DETAIL REFERENCE:- DETAIL DESIGNATION- SHEET NUMBER REFERENCE

EQUIPMENT REFERENCE. COORDINATE EQUIPMENTWITH MECHANICAL/PLUMBING TRADES. SEEMECHANICAL/PLUMBING DRAWINGS FOR LOCATIONS.

EF1

#

P380D

DUPLEX RECEPTACLE WALL MOUNTED, +18" AFF, UON

X

LETTER DESIGNATION ON RECEPTACLES:A = ARC FAULT CIRCUIT INTERRUPTERIG = ISOLATED GROUNDWP = WEATHER PROOF WITH 'GFCI'S = SAFETYCT = ABOVE COUNTERCR = CRITICALEQ = EQUIPMENTLS = LIFE SAFETY+X" = INDICATES MOUNTING HEIGHT

CONDUIT AND WIRE RUN EXPOSED ON WALL ORCEILING IN FINISHED SPACE.

CONDUIT AND WIRE RUN CONCEALED IN SLAB, UNDERSLAB OR UNDERGROUND

MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS MOUNTEDAGAINST AN ADJACENT WALL OR OTHERWISEREMOTE FROM THE MOTOR. SEE MOTOR EQUIPMENTSCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROLEQUIPMENT, QUANTITY OF MOTORS CONNECTED TOCONTROLLER, AND OTHER DETAILS. CONDUCTORSIZE BETWEEN CONTROLLER AND MOTOR SHALLMATCH THE UPSTREAM OF THE CONTROLLER UNLESSNOTED OTHERWISE ON THE SCHEDULE.

MOTOR CONTROL EQUIPMENT AND CONNECTION TOCONTROLLED MOTOR(S). CONTROLLER IS EITHERINTEGRAL TO THE EQUIPMENT OR MOUNTED DIRECTLYONTO THE EQUIPMENT. SEE MOTOR EQUIPMENTSCHEDULE(S) FOR CIRCUITING, TYPE OF CONTROLEQUIPMENT, QUANTITY OF MOTORS CONNECTED TOCONTROLLER, AND OTHER DETAILS. CONDUCTOR SIZEBETWEEN CONTROLLER AND MOTOR SHALL MATCHTHE UPSTREAM OF THE CONTROLLER UNLESS NOTEDOTHERWISE ON THE SCHEDULE.

CB4x 225

+X"

ACCESS FLOOR BOX WITH OUTLETS AS SPECIFIED

POKE THROUGH FLOOR BOX WITH OUTLETS ASSPECIFIED

CONDUIT TURNING UP

CONDUIT TURNING DOWN

CONDUIT CAPPED

ARC FAULT CIRCUIT INTERRUPTERAFCI

RACEWAYS

FLEXIBLE CONNECTION

CONDUIT AND WIRE, HASH MARKS INDICATE NUMBEROF WIRES. # HASH MARKS INDICATES 3#12+3#10NIN 3/4" CONDUIT UON.

P

P

E-3A

LVR LOW VOLTAGE RELAY

MOTOR CONTROL CENTERMCC

MOTOR CONTROL PANELMCP

MER MECHANICAL EQUIPMENT ROOM

MANUFACTURERMFRR

MIN MINIMUM

MAIN LUGS ONLYMLO

MSB MAIN SWITCHBOARD

MOUNTEDMTD

N NEWNOT APPLICABLENA, N/A

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

N.C. NORMALLY CLOSEDNOT IN CONTRACTNIC

# NUMBER

NORMALLY OPENN.O.

NTS NOT TO SCALE

ON CENTEROC

POLESP

PB PULL BOX

POWER FACTOR CORRECTIONPFC

PH, ø PHASEPANELPNL

PVC POLYVINYL CHLORIDE

POWERPWR

RC REHEAT COIL

RECEPTACLERECPT, REC

RM ROOM

SIGNAGESGSHT SHEET

SPECIFICATIONSSPEC

SPDT SINGLE POLE DOUBLE THROW

SINGLE POLE SINGLE THROW

SWITCH

SPST

SW

SWBD

SWGR

SWITCHBOARD

SWITCHGEAR

TIME CLOCKTC

TYP TYPICAL

UNDERGROUNDUG

UON, U.O.N. UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLYUPSUNF UNFUSED

VOLTV

VA VOLT-AMPERES

VACUUM PRESSURE IMPREGNATIONVPI

VAPOR TIGHTVT

W WATT

WEATHER PROOFWP

XFMR TRANSFORMER

SURGE SUPPRESSIONSS

XP EXPLOSION PROOF

NEMA

DESCRIPTIONSYMBOL

LTG LIGHTING

LOW VOLTAGELV

DESCRIPTIONSYMBOL

PANELBOARD, SEE PANEL SCHEDULE FOR RATING.

MOLDED CASE CIRCUIT BREAKER:- 'TEXT' DENOTES CB ACCESSORIES

LOW VOLTAGE DRAW OUT CIRCUIT BREAKER:

MEDIUM VOLTAGE DRAW OUT CIRCUIT BREAKER

ST, ET. GFP, EO, LSI TRIP FUNCTIONS- NUMERICAL DENOTES TRIP SIZE

- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

WITH INTEGRAL TRIP UNIT

LOW VOLTAGE FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES

ST, GFR, EO, LO, LOCK OUT PROVISIONS- NUMERICAL DENOTES FUSE SIZE

MEDIUM VOLTAGE DRAWOUT FUSE/SWITCH UNIT- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES FUSE SIZE

ENCLOSED CIRCUIT BREAKER- 'TEXT' DENOTES CB ACCESSORIES- NUMERICAL DENOTES TRIP SIZE

ENCLOSED SAFETY DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

INTERMEDIATE CLASS MOV SURGE ARRESTER- NUMERICAL DENOTES ARRESTER RATING

FEEDER

BUSWAY

PANEL

BW

GFPTRIP

LSITRIP

STTRIP

STTRIP

GFP

FUSE

52

GFP

FUSE

SA12KV

AUTOMATIC TRANSFER SWITCH

GENERATOR

UTILITY METER

DIGITAL MULTIFUNCTION METER WITHCURRENT/POTENTIAL TRANSFORMER AS REQUIRED

MOTOR

AUTOMATIC TRANSFER SWITCHW/BYPASS ISOLATION

KEY INTERLOCK

RELAY NUMERICAL INDICATES TYPE

CURRENT TRANSFORMER:- '200/5' DENOTES CT RATIO IF INDICATED

POTENTIAL TRANSFORMER:- NUMERICAL DENOTES QUANTITY OF FUSES

INVERTER

RECTIFIER

BATTERY

TRANSFORMER WITH PRIMARY ANDSECONDARY CONNECTIONSAS INDICATED ON RISER DIAGRAM.

M

A

1

51

200/5

KI

N E

L

M VA

G

M

ATS-#CONNAMPS

ATS-#CONNAMPS

DIGITAL ENERGY METERM

GROUND CONNECTION

ENCLOSED FUSED DISCONNECT SWITCH- 'TEXT' DENOTES FUSE ACCESSORIES- NUMERICAL DENOTES SWITCH SIZE

SINGLE LINE DIAGRAMDESCRIPTIONSYMBOL

EXISTINGE

EXISTING TO BE REMOVEDER

DUPLEX RECEPTACLE WALL MOUNTED, GROUND FAULTCIRCUIT INTERRUPTER TYPE, +18" AFF, UON

TYPICAL LIGHTING FIXTURE WITH SHADED AREAINDICATES ON CRITICAL OR LIFE SAFETY CIRCUIT

VFD VARIABLE FREQUENCY DRIVE ANDDISCONNECT SWITCH

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

52 P

M

SYMBOLS, ABBREVIATIONS, ANDGENERAL NOTES

ES0.1.0RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

ELECTRICAL SHEET INDEXSHEET DRAWING TITLE

ES0.1.0 SYMBOLS, ABBREVIATIONS, AND GENERAL NOTESEDL2.1.1 LIGHTING DEMOLITION PLAN - LEVEL 1EDP2.1.1 POWER DEMOLITION PLAN - LEVEL 1EL2.1.1 LIGHTING PLAN - LEVEL 1EP2.1.1 POWER PLAN - LEVEL 1EP2.1.5 POWER PLAN - ROOF LEVELEP5.0.0 ELECTRICAL SINGLE LINE DIAGRAMEP5.0.1 ELECTRICAL SINGLE LINE DIAGRAMEP6.2.1 PANELBOARD SCHEDULESEP6.2.2 PANELBOARD SCHEDULESEP7.2.1 ELECTRICAL DETAILSEP7.2.2 ELECTRICAL DETAILS

LIGHTING FIXTURE SCHEDULETYPE DESCRIPTION LUMENS WATTS WATTS VOLTS

L1 RECESSED 2'x4' LED LUMINAIRE - HIGH OUTPUT 4248 39 W 277L1B RECESSED 2'x4' LED LUMINAIRE - LOW OUTPUT 3342 31 W 277L2 RECESSED 2'x2' LED LUMINAIRE - HIGH OUTPUT 3565 35 W 277

L2A RECESSED 2'x2' LED LUMINAIRE - LOW OUTPUT 2197 20 W 277L3 RECESSED 6" SLOT LED LUMINAIRE - 6'-0" 2461 45 W 277

L3B RECESSED 6" SLOT LED LUMINAIRE - 4'-0" 2461 45 W 277L4B SURFACE 6" DECORATIVE LED LUMINAIRE - REGRESSED LENS 1861 46 W 277L5 LED DOWNLIGHT - RECESSED INTERIOR 939 16 W 277L6 WALL MOUNTED LED LUMINAIRE 2152 19 W 277L8 LED DOWNLIGHT - WET LOCATION 1490 24 W 277L9 LED FLEX TUBE LUMINAIRE - LINEAR WET LOCATION 168 lm/ft. 3 W 3.2 W / FT 277

L10 LED LUMINAIRE - RECESSED LINEAR 483 lm/ft. 4 W 3.75 W / FT 277

(E) LIGHTING CONTROL PANEL LCP16ARELAY

NO. DESCRIPTIONBRANCH CIRCUIT CONTROL

LevelPANEL CIRCUIT ON OFF OVERRIDE

16A-1 NH16A 12 $ Level 116A-2 NH16A 14 $ Level 116A-3 NH16A 26 $ Level 116A-4 NH16A 24 $ Level 1

Page 33: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

J

J

J

(E) ERWAITINGA1-125

(E) ERRECEPTION

A1-120

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) ADMINELEGIBILITY

A1-100

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) ADMINELEGIBILITY

A1-100

(E) AE WORKROOMA1-119

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) NURSESTATIONA1-220

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E)CONFERENCE

A1-211

(E) 3 ERISOLATION

ROOMA1-206

(E) CLEANUTILITYA1-228

(E) SOILEDUTILITYA1-226

(E) ER MEDROOMA1-224

(E) TOILETA1-322

(E) MAINELEC.

SEV1.1

(E) EDOU 4A1-325D

(E) EDOU 3A1-325C

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) 7 EREXAM RM

A1-218

(E) 6 EREXAM RM

A1-216

(E) 5PROCEDURE

ROOMA1-418D

(E)STORAGE

A1-340(E) TOILET

A1-334

(E) TOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUEQUIPMENT

ROOMA1-330

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

A1-TC1T-1.6

(E) SIGNALS-1.6

(E) EDOUSOILEDUTILITYA1-328

(E) EMS HACA1-324

(E) NURSESTATIONA1-225

(E) EDOUMED ROOM

A1-325G(E) EDOU 6

A1-325F(E) EDOU 5

A1-325E

(E) NURSEOFFICEA1-245

(E) OFFICEA1-235

(E) SOCIALWORKERA1-331

(E) STAFFTOILETROOMA1-403

(E)PHYSICIAN

CALL ROOMA1-402

(E)PROGRAMSUPPORT

ASSTA1-401

(E)CONFERENCE

A1-333

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) TOILETA1-416A

(E) TOILETA1-418A

(E) MEN'SLOCKERA1-418

(E) ANTEROOMA1-208 (E)

PHYSICIANWORKROOMA1-210 (E) 4 ER

CODE ROOMA1-212

H

F

G

E

12345678

I

J

J.2

(ER)

(ER) (ER)

(ER)

(ER) (ER)

(ER) (ER)

1

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

32 P

M

LIGHTING DEMOLITION PLAN - LEVEL1

EDL2.1.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Lighting Plan Demo

1 DEMOLISH AND REMOVE ALL ELECTRICAL LIGHTINGDEVICES, FIXTURES, CONDUITS, WIRING, JUNCTIONBOXES, ETC. COMPLETE BACK TO SOURCE ENCLOSEDWITHIN THE DASHED LINES.

Page 34: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

J JJ J JJ

J J

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) ADMINELEGIBILITY

A1-100

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) PSYCHEVAL

A1-136

(E) ERRECEPTION

A1-120

(E) AE WORKROOMA1-119

(E) 3 ERISOLATION

ROOMA1-206

(E) MAINELEC.

SEV1.1

(E) 2 EREXAM RM

A1-204

(E) NURSESTATIONA1-220

(E) ERWAITINGA1-125

(E) TOILETA1-127

(E) TOILETA1-129

(E) 8 ENTROOMA1-201

(E) 9 EREXAM RM

A1-205

(E) 10 EREXAM RM

A1-211(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E) SOILEDUTILITYA1-226

(E) ER MEDROOMA1-224

(E) TOILETA1-322

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

(E) EDOU 2A1-325B

(E) EDOU 3A1-325C

(E) EDOU 4A1-325D

(E) 1 EREXAM RM

A1-202

(E)CORRIDOR

A1-C13

(E) ERTRIAGEA1-209

(E) ERTRIAGEA1-207

N 35' - 3 1/2"E 384' - 7 25/32"

(E) TOILETA1-416A

(E) WOMEN'SLOCKERA1-416(E) MEN'S

LOCKERA1-418

(E) TOILETA1-418A (E) STAFF

LOUNGEA1-410

(E) HACA1-414

(E) ANTEROOMA1-208

(E) 7 EREXAM RM

A1-218

(E) 6 EREXAM RM

A1-216

(E) 5PROCEDURE

ROOMA1-418D

(E) 4 ERCODE ROOM

A1-212

(E)PHYSICIAN

WORKROOMA1-210

(E)CONFERENCE

A1-211

(E)STORAGE

A1-340(E) TOILET

A1-334

(E) TOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUEQUIPMENT

ROOMA1-330

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

A1-TC1T-1.6

(E) SIGNALS-1.6 (E) EDOU

MED ROOMA1-325G

(E) SOCIALWORKERA1-331

(E) OFFICEA1-235

(E) NURSEOFFICEA1-245

(E) EDOU 6A1-325F

(E) EDOU 5A1-325E

(E) EMS HACA1-324

(E) NURSESTATIONA1-225

(E) EDOUSOILEDUTILITYA1-328

(E)CONFERENCE

A1-333

(E) STAFFTOILETROOMA1-403

(E)PHYSICIAN

CALL ROOMA1-402

(E)PROGRAMSUPPORT

ASSTA1-401

(E) STAFFLOUNGEA1-421

H

F

G

E

12345678

I

J

J.2

(ER)(ER)

(ER)(ER)(ER)(ER)(ER)

(ER)

(ER)(ER)(ER)

(ER)(ER)(ER)(ER)(ER)

(ER)

(ER)

(ER)

1

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

34 P

M

POWER DEMOLITION PLAN - LEVEL 1

EDP2.1.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Power Plan Demo

1 DEMOLISH AND REMOVE ALL ELECTRICAL RECEPTACLES,CONDUITS, WIRING, JUNCTION BOXES, ETC. COMPLETEBACK TO SOURCE ENCLOSED WITHIN THE DASHED LINES.

Page 35: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

J

J

J J

J JJJ

J

JJ J J J J

J J

JDDD

POO O OO

O

OO

OO O O O O OO

P P P P P P

O O

OP

P

O

D

J

J

J

J

JJ

J J

J

J J J

FF

F

F

F

FF

J

J

J

J

J

J

J

J

J

J

J

J J

J

J J

O

(E) MAINELEC.

SEV1.1

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09

(E)CORRIDOR

A1-C10

(E)CONFERENCE

A1-422(E)

PHYSICIANCALL ROOM

A1-402

??

(E)CONFERENCE

A1-140

(E) NURSESTATIONA1-220

(E) TOILETA1-322

(E) CLEANUTILITYA1-228

(E) SOILEDUTILITYA1-226

(E) ER MEDROOMA1-224

(E)CORRIDOR

A1-C03

(E) EDOU 4A1-325D

(E) EDOU 3A1-325C

(E) EDOU 2A1-325B(E) EDOU 1

A1-325A

(E) 12 EREXAM RM

A1-221

(E) 11 EREXAM RM

A1-215

(E) STAFFLOUNGEA1-410

(E) TOILETA1-416A

(E) TOILETA1-418A

(E) MEN'SLOCKERA1-418

(E) WOMEN'SLOCKERA1-416

(E) HACA1-414

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151OFFICE

A1-149OFFICEA1-147

OFFICEA1-145

OFFICEA1-143

OFFICEA1-141

CORRIDORA1-C002

CORRIDORA1-C003

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

OFFICEA1-146

OFFICEA1-144

COPYA1-142

RECEPTIONA1-140A

(E) ASSTNURSE

MANAGERA1-323

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E)ELECTRICAL

ROOME-1.6

(E)TEL/DATA

T-1.6

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324 ALCOVE

A1-326

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245(E) EDOU

STORAGEA1-330

(E) LOCKERROOMA1-332

(E) STAFFTOILETA1-334

(E) STAFFTOILETA1-332A

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208(E) 3 ER

EXAM RMA1-206

(E) 2 EREXAM RM

A1-204

(E) 1 EREXAM RM

A1-202

TRIAGEEXAMA1-203

(E) 8 ENTROOMA1-201

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E)CORRIDOR

A1-C02

(E) OFFICEA1-134

(E) PSYCHEVAL

A1-136

(E) ER SDCA1-132

(E) ER SDCA1-130

(E) ADMINELEGIBILITY

A1-100

(E) ERRECEPTION

A1-120

(E) ERWAITINGA1-125

(E) AE WORKROOMA1-119

(E) ELECTE-1.4

(E)TEL/DATA

T-1.4

(E) AE MASSUPV

OFFICEA1-100A

(E) AEDECEDENT

AFFAIRSA1-106

(E)CORRIDOR

A1-C13

STAXISTORAGEA1-140B

WAITINGA1-140

(E) TOILETA1-129

(E) TOILETA1-127

H

F

G

E

12345678

I

J

J.2

L1 1 a

L1 1 a

L2 22 f

L222 a

L222 b

L2 22 c L1B 22 d L1B 22 e

L6 22 f

L6 22 g

L2 20 a L2 20 a

L220 b

L2 20 b

L2 20 c L2 20 c

L2A 20 h

L2A 20 g

L2A

20 hL2 20 fL2 18 eL2 18 d

L2

18 c

L1B 18 a L1B 18 b

L1B 18 a L1B 18 b

L5

12LCP - 16A-1

L516 c

L516 c

f

abc

a b

L222 c

L1B22 e

L1B22 d

d ec

a

g

f

a bc d e f g h

L218 c

L218 e

L220 f

L218 d

L2A20 g

a b

c

d

m

L5

L512LCP - 16A-1

L5

L5

12LCP - 16A-1

L512

LCP - 16A-1

L5

12LCP - 16A-1

L5L5

L8

L8

L8

L8

L5L3B24LCP - 16A-4

L3B24LCP - 16A-4

L3B24LCP - 16A-4

L3B L3B

L524LCP - 16A-4

L524

LCP - 16A-4

L5

L5

L5

L3

16 a

L3

16 b

L3

16 a

L3

16 b

L3

16 b

L3 L3

16 b

L3

L3

16 a

L3

16 b

L3

16 a

L3 16 b

L3

L316 d

L316 d

L316 d

22 f

22 g

L5

L5

L5

L9 L9 L9

D

D D DD D

D DD D D D

D

1

16 m 16 mL4BL4B

L9

L9

14LCP - 16A-2

14LCP - 16A-2

14 LCP - 16A-2

L10

L10

L10

2

L10

14LCP - 16A-2

L10

3

L222 a

L222 b

NH16A - 18,20,22

L8 L8

NH16A - 16

L2 22 f

L222 f

NH16A - 12,14

NH16A - 24

26LCP - 16A-3

26LCP - 16A-3

26LCP - 16A-3

26LCP - 16A-3

26LCP - 16A-3 NH16A - 26

SH16A - 5

SH16A - 7

CH16A - 1

5

5

5

5

5

5

5 5

5 5

5 5

7

777

14 LCP - 16A-2

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

38 P

M

LIGHTING PLAN - LEVEL 1

EL2.1.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Lighting Plan

1 FOR FLEX LIGHTING ACCESS PANEL, 277V.2 OVERRIDE SWITCH.3 FOR RECEPTION DESK TASK LIGHTING ON 120V POWER.

REFER TO ARCHITECTURAL DRAWINGS FOR EXACTLOCATION, MOUNTING HEIGHTS AND DETAILS.

Page 36: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

JJ

JJ JJ

JJ

J

J

J

J

J

J

J JJ

JJ

J

JJ

J

J

J

J

JJ

J

J

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

N 36' - 10 1/8"E 384' - 6 9/32"

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

CR

N CR

CR

CRCR

CT

CT CTCT

CR

40

CR

14

14

614

25

CT

1 1

3

1

37 33

35

35

20 20

242424

2020

2424

20

22

21

19 21

19

21

13

13

1513

15

13 15 13

19

21

1923

31

17

17 17

29

27

31

CL16A - 27,29,31

LS

LSCL16A - 20,22,24

CT17

LS

LS

1

2

3

4

311

11

NL16C - 11

1

5

56

7

8

219

1011

1011

11

10 11

1011

912

13

14

15

1611

11

(1)ELECTRICAL PORT FOR CABINET AND (1)ELECTRICAL PORT FOR MONITOR

16

(TYP. OF 2)

(TYP. OF 2)

NL16C - 1,3,5

2

25

CL16A - 6,14,40

NL16C - 9,25

1

CT

25

25

23

23SL16A - 23,25

NL16C - 13,15,17

NL16C - 19,21,23

CL16A - 33,35,3743

48

NL16C - 47,48

4847

4644

44

43

45 45

45

4748

NL16C - 43,45

47

43

44

46

NL16C - 44,46

49

50 NL16C - 50

49

NL16C - 49

17

17

17REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

42 P

M

POWER PLAN - LEVEL 1

EP2.1.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Level 1 Power Plan

FOR ALL SPECIAL HEIGHT RECEPTACLES REFER TO ARCHITECTURALELEVATION DETAILS.

RECEPTACLES IN PUBLIC AREAS SHALL BE TAMPER RESISTANT.

1.

2.

1 FOR PHYSIOLOGICAL PATIENT MONITOR, 120V, ITEM#MO13.

2 PROVIDE CONNECTION TO PATIENT HEADWALLASSEMBLY.

3 FOR AUTO DOOR, 120V.4 FOR COUNTERTOP PRINTER, 120V, ITEM #PR03X.5 FOR #ET01. REFER TO ARCHITECTURAL DRAWINGS FOR

MOUNTING HEIGHTS.6 FOR PATIENT LIFT #LI06.7 FOR DIAGNOSTIC SET WALL TRANSFORMER & SPECULA

HOLDER #DI01.8 FOR TV PANEL #TV32. REFER TO ARCHITECTURAL

DRAWINGS FOR MOUNTING HEIGHTS.9 FOR RECEPTION DESK TASK LIGHTING ON 120V POWER.

REFER TO ARCHITECTURAL DRAWINGS FOR EXACTLOCATION, MOUNTING HEIGHTS AND DETAILS.

10 PROVIDE AN EMPTY J-BOX FOR THE CARD READERKEYPAD.

11 PROVIDE A 1/2"C FOR LV WIRING BETWEEN THEACCESS PANEL AND THE CARD READER KEYPAD. ALLCONDUIT RUNS SHALL BE CONCEALED.

12 FOR PUMP,IV INFUSION, DUAL W/MOBILE STAND #PU1013 FOR COMPUTER WORKSTATION ON MOBILE STAND

#CO94X14 FOR EKG MACHINE, 120V, 5A, ITEM #EK01X.15 FOR I-STAT STATION, 120V. #ISO2,2A,2B16 FOR MONITOR POWER SUPPLY #MO73X17 HARDWIRE CONNECTION TO FAUCETS SENSORS.

1 Addendum #1 09/01/152 Addendum #2 09/08/15

Page 37: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

EF41EF79

2" VTR

4" VTR

J

J

H

F

G

E

12345678

I

J

J.2

EF1

EF1

EF1

EF2

EF2

EF2

6" CONCRETE PAD

OUTSIDE AIR

EXHAUST AND RETURN UNIT(DESIGN BUILT)

SUPPLY UNIT(DESIGN BUILT)

AHU1

AHU1

AHU1

AHU1

AHU1

AHU1

EXHAUST AIR

3#10, 1#10G, 3/4"C

3#8, 1#10G, 3/4"C

1

1

3#12, 1#12G, 3/4"C

2

2

QHD51A - 32,34,36

QHD51A - 38,40,423#12, 1#12G, 3/4"C

QHD51A - 29,31,33

QHD51A - 35,37,39

PANEL QHD51A(LOCATED BELOW ON LEVEL 1 INELECTRICAL CLOSET E-51,REFER TO SHEET EP7.2.2)

VFD

VFD

3

3

QL16A - 5

5

QL16A - 2424

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

42 P

M

POWER PLAN - ROOF LEVEL

EP2.1.5Checker AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 POWER PLAN SEQUENCE 1- ROOF LEVEL

1 PROVIDE A NEW 40A, 480V, 3PH BREAKER FOR AHU-1SUPPLY UNIT AND A NEW 25A, 480V, 3PH BREAKER FORAHU-1 EXHAUST/RETURN UNIT. NEW BREAKER TOMATCH THE EXISTING ELECTRICAL BOARD. EXTENDNEW WIRING AND CONDUITS FROM THE LOCATION OFTHE EXISTING PANEL TO THE NEW AHU.

2 PROVIDE A NEW 15A, 480V, 3PH BREAKER FOREXHAUST FAN. EXTEND NEW WIRING AND CONUITSFROM THE LOCATION OF EXISTING PANEL TO EXHAUSTFAN.

3 FOR AIR HANDLER UNIT INTEGRATED LIGHTS ANDRECEPTACLES.

Page 38: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

DMM

GFR

ST

DMM

GFR

ST

NHV1001BNHV1001A

1

NUMBERED SHEET NOTES

NORMAL POWER ONE-LINE DIAGRAM - ELECTRICAL SERVICE 1

4000 AMP, 277/480 VAC, 3 PHASE, 4 WIRE BUS

SWITCHBOARD NHS1001A

42,000 RMS SYM AIC

TOCATS1001A SATS1001A

1

TO TOQATS1001A

CRITICAL BRANCH

LIFE SAFETY BRANCH

EQUIPMENT SYSTEMS

8004

7004 2254 8004 6003

E5.3.0

SPACE

BW

800 AMPNBW1A

J

BW

CABLE TAP BOX

---AT

QATS1001CTO

CT'S

1

J

10004

J

5004

TOQATS1001D

6003

ELECTRICAL RISER E-1 ELECTRICAL RISER E-2

ELECTRICAL RISER E-6

800AF3P

ROOF

BW

ST

GFRCT'SCT'S GFR

STST

GFRCT'S

ST

GFRCT'SCT'S GFR

ST

CT'S GFR

STST

GFRCT'SCT'S GFR

ST

2

NH01APANEL

NBS01A

3P60AS60AF

604

3 PHASE

CABLE TAP BOX

NTX11A2253

112.5 KVA

2254

4004225AF400AS3P

NBS11A

PANELNH11A

3P

225AF400AS

NBS11B

NH12APANEL

NBS12A

3P60AS60AF

4004

604

112.5 KVA

2253NTX12A

3P

NBS12B

400AS225AF

604

300460AF60AS3P

NBS22A

PANELNH22ANH21A

PANEL

NBS21A

3P60AS60AF 4004

604

NTX31A1503

75 KVA

604

300460AF60AS3P

NBS31A

PANELNH31A NH32A

PANEL

NBS32A

3P60AS60AF

3004

604

75 KVA

1503NTX32A

3P

150AF200AS

NBS31B

3P

NBS32B

150AS150AF

604

6004

60AF60AS3P

NBS42A

PANELNH42A

PANELNL41ANH41A

PANEL

NBS41A

3P60AS60AF

4004

604

NTX16A75 KVA

704

300470AF100AS3P

NBS16A

PANELNH16A

3P

150AF150AS

NBS16B

CABLE TAP BOX

NH26APANEL

NBS26A

3P60AS60AF

604

3P

NTX36A1503

75 KVA

604

300460AF60AS3P

NBS36A

PANELNH36A

150AF200AS

NBS36B

NH46APANEL

NBS46A

3P60AS60AF

3004

604

42,000 RMS SYM AIC

SWITCHBOARD NHS1001B

4000 AMP, 277/480 VAC, 3 PHASE, 4 WIRE BUS

1504

150AF150AS3P

NBS02A

PANELNH02A

BW

EQUIPMENT SYSTEMS

EQUIPMENT SYSTEMS

4

1

E6.2.0 E6.2.0

2

4

4

E6.2.0E6.2.0

1

ST

GFRCT'S

4003

CT'S GFR

ST

8003

CT'S GFR

ST

GENERATORBUILDING 103

(LOADING DOCK)

PROCESSORINFECTIOUS WASTE

400AS3P

SEE SITE DRAWINGES5.2.0 FOR CONTINUATION

UNIT SUBSTATION 1001A

3P

75 KVA

1503NTX26A

200AS150AFNBS26B

3004

NTX46A1503

75 KVA

3P200AS150AFNBS46B

200AS3P

NTX22A1503

75 KVA

150AFNBS22B

400AS3P

NTX42A3003

150 KVA

300AFNBS42B

200AS3P

75 KVA

1503NTX21A

NBS21B150AF

400AS3P

112.5 KVA

2253NTX41A

NBS41B225AF

3P

45 KVA

1003NTX01A

100AS

NBS01B100AF

3P

NTX02A3003

150 KVA

400AS300AFNBS02B

WITH GROUND

ST

GFRCT'S

ROOF

TOQATS1001B

EQUIPMENT SYSTEM

5003

1754

8003

EQUIPMENT SYSTEMS

QATS1001ETO

COOLING TOWER YARD

CT'S

1

1E5.2.0 NOT TO SCALE

NL31APANEL

PANELNL21A

NL11APANEL

PANELNL01A NL02A

PANEL

PANELNL12A

NL22APANELPANEL

NL22B

PANELNL32A

PANELNL42A NL46A

PANEL

PANELNL36A

NL26APANEL

PANELNL16A

5

CMTS16A1503

MOTORCONTROLCENTERNMCC00A

COOLING

F

F

F

F

F

F

F

F

F

F

F

F

F

F

2253

NBS22C225AF400AS3P

NTX22B112.5 KVA

3004

BW

F

F

F

F

F

F

F

F

F

F

F

F

F

F

2

EATS1031A

SEE DRAWING103-E5.1.0

3 4 5 66 7 8 9 2

SHO38

12 4 5 6 87

1

NTX1001A

7

DMM DMM DMM DMM DMM DMM

6

8

3

CT'S GFR

ST

6004

TOCATS1001B

BUS

6

CRITICAL BRANCH

DMM DMM DMM DMMDMM DMM DMM

3P800AF---AT

SPACE

NLX42APANEL

NLX42BPANEL

604(TYPICALFOR 2)

NLX41APANEL PANEL

NLX41B NLX41CPANEL

NLX41DPANEL

NLX41EPANEL

NLX41FPANEL PANEL

NLX41LPANELNLX41K

PANELNLX41J

PANELNLX41INLX41H

PANELPANELNLX41G NLX41M

PANELNLX41NPANEL

604

(TYPICALFOR 14)

DRAWOUT, ADJUSTABLE TRIP, MOLDED CASE MAIN BREAKER AND COMPARTMENT PER SPECIFICA-

GROUP MOUNTED, ADJUSTABLE TRIP, MOLDED CASE FEEDER BREAKER PER SPECIFICATION

PROVIDE BUSSED SPACE AND MOUNTING HARDWARE FOR FUTURE FEEDER BREAKER TO MATCHNEW BREAKERS.

PROVIDE BUS BAR EXTENSION FOR FUTURE SECTION.

PROVIDE TRANSFORMER WITH COOLING FANS AND ASSOCIATED CONTROLS.

TYPE I SWITCHBOARD PER SECTION 16462.

REFER TO DRAWING 103-E5.1.0 FOR FEEDER SIZE.

2

3

4

5

6

7

8

4 WIRE

200AT400AF3P

3 32 2 2 2 2 9 102

(AA80°/AA100°/FA100°)12470-277/480 VAC3 PHASE, 4 WIRE

2000/2250/3000 KVA 2000/2250/3000 KVA

3 PHASE, 4 WIRE12470-277/480 VAC(AA80°/AA100°/FA100°)

NTX1001B

ROOF

2 2

NHD51A NMCC51A NMCC52A

1003 1003

2

EXTEND CRITICAL FEEDER FROM MANUAL TRANSFER SWITCH CMTS16A (SEE DRAWING E5.2.0)TO BUSWAY SWITCH CBS16C, (SEE DRAWING E5.3.0).

E8.4.0

-

4 WIRE3 PHASE

NBW2A1000 AMP

-

E8.4.0 E8.4.0

-

600 AMPNBW6A

3 PHASE4 WIRE

11

UNIT SUBSTATION 1001B

ES5.2.0 FOR CONTINUATIONSEE SITE DRAWING

CT'S

800AT800AF

3P

1000AT1200AF

3P

500AT800AF

3P

400AT400AF

3P

800AT800AF

3P

500AT800AF

3P

500AT800AF

3P

400AT400AF

3P

700AT800AF

3P

600AT800AF

3P

225AT250AF

3P

2

7

800AT800AF

3P

800AT800AF

3P

600AT800AF

3P

2 2 2

DMM

GFR

ST

2600AT800AF

3P

2 9 3 10

3P400AF400AT

DMM

CT'S GFR

ST

4004

F

6004

TOWER

YARD

DMM

ST

GFRCT'S

6003 8003

CT'S GFR

ST

DMM

3P800AF600AT

2 11

NHD53A

1003

NMCC53A

4 WIRE3 PHASE,400 AMP,

BW

F

F

NL14APANEL

NBS24B

200AS150AF

150AF200AS

NBS14B

3P

NTX14A1503

75 KVA

604

300460AF60AS3P

NBS14A

PANELNH14A

CABLE TAP BOX

J

NBW4A

F

F

F

F

F

F

PANELNL24A

NL34APANEL

PANELNL44ANH44A

PANEL

NBS44A

3P60AS60AF

3004

604

75 KVA

1504NTX44A

3P

NBS44B

200AS150AF

100AF100AS

NBS34B

3P

NTX34A1003

45 KVA

604

175460AF60AS3P

NBS34A

PANELNH34A

3P

NH24APANEL

NBS24A

3P60AS60AF

3004

604

75 KVA

1503NTX24A

ELECTRICAL RISER E-4

-

E8.4.0

SECTION 16462.

TION SECTION 16462.

2003

60KVAR KVAR

80

2003

FILTER

10

3P800AF600AT

DMM

CT'S GFR

ST

60032

300KVAR KVAR

300

2 6003

ST

GFRCT'S

DMM

600AT800AF

3P

1010

9

10 10 10 10 10 10 10 10 10 10 10 10 10

3P800AF600AT

DMM

CT'S GFR

ST

60032

300KVARKVAR

300

2 6003

ST

GFRCT'S

DMM

600AT800AF

3P

9

PROVIDE LOCAL POWER DISTRIBUTION METERING EQUIPMENT PER SECTION 16430, 2.2,METERING.

9

PROVIDE PMDAS REMOTE MONITORING PER SECTION 16430, 2.2, METERING.10

GFR

ST

DMM

2253

PANELNH16B

PANELNL16B

(E) (E) (E)PANELNL16B

(E)

PANELNL16C

(N)

AREA OF WORK

AREA OF WORK

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

43 P

M

ELECTRICAL SINGLE LINE DIAGRAM

EP5.0.0RP AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. CONTRACTOR SHALL INSPECT AND FIELD VERIFY ALL EXISTING SWITCHBOARDS AND PANELBOARDS, IN SCOPE OF WORK, TO CONFIRM SPARE BREAKER AND SPACE AVAILABILTY.

Page 39: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

SPACE SPACE

ESSENTIAL POWER ONE-LINE DIAGRAM - ELECTRICAL SERVICE 1

NUMBERED SHEET NOTES

300AT400AF

3P

2

---AT400AF

3P

800AT800AF

3P

BY-PASSMANUAL

BY-PASSMANUAL

3000AT4000AF

3P

SPACE

600 AMP

QATS1001D

MANUALBY-PASS

600 AMP

QATS1001C

MANUALBY-PASS

800 AMP

QATS1001A

225 AMP

SATS1001A

CRITICAL BRANCH DISTRIBUTIONBOARD CHD1001A

700AT800AF

3P

NORMAL FEED FROMNHS1001B-7NHS1001B-5

NORMAL FEED FROM

BY-PASSMANUAL

CATS1001A

800 AMP

4000 AMP BUS, 277/480 VAC, 3 PHASE, 4 WIRE

ATS/ESSENTIAL DISTRIBUTION BOARD EHD1001A

NORMAL FEED FROMNHS1001B-8

NORMAL FEED FROMNHS1001B-4NHS1001B-2

NORMAL FEED FROM

SWITCHBOARD EHS1031AENGINE GENERATOR PARALLELING

800 AMP BUS, 277/480 VAC, 3 PHASE 4 WIRE

6003

CBS36A

3P60AS60AF

1003

1754

604

3P

CBS36B

100AS100AF

PANELCL36ACH36A

PANEL

45 KVACTX36A

604

PANELCH46A CL46A

PANEL

175460AF60AS3P

CBS46ACBS42A

3P60AS60AF

604

PANELCL42ACH42A

PANEL

604

604

60AF60AS3P

CBS41A

604

PANELCH41A CL41A

PANEL

3004

3P

CBS31B

400AS225AF

PANELCL31ACH31A

PANEL

CBS31A

3P60AS60AF

4004

604

112.5 KVA

2253CTX31A

1503

1504

CTX32A75 KVA

150AF200AS3P

CBS32A

PANELCH32A CL32A

PANEL

150AF200AS

CBS32B

3P

3P

CBS16B

100AS100AF

PANELCL16ACH16A

PANEL

CBS16A

3P60AS60AF

175445 KVACTX16A

604

1003

604

175460AF60AS3P

CBS26A

PANELCH26A CL26A

PANELPANELCL22ACH22A

PANEL

CBS22A

3P60AS60AF

1754

604604

600460AF60AS3P

CBS21A

PANELCH21A CL21A

PANEL

4004

J

BOXCABLE TAP

604

60AF60AS3P

CBS12A

PANELCH12A CL12A

PANELPANELCL11ACH11A

PANEL

CBS11A

3P400AS400AF

4004

CABLE TAPBOX

604

400460AF60AS3P

CBS01A

PANELCH01A CL01A

PANEL

4W400A,3P,CBW-2A

BW

BW

J

4004

4W400A,3P,CBW-6A

BW

BW

J

BW

BW

BOXCABLE TAP

CBW-1A800A,3P,4W

7004

PANELCL02ACH02A

PANEL

CBS02A

3P60AS60AF 1754

604

8004

3P250AF100AT

3504 4004 1004

PANELQL01AQH01A

PANEL

PANELQH11A QL11A

PANEL

PANELQL21AQH21A

PANEL

PANELQL31AQH31A

PANEL

PANELQL41AQH41A

PANEL PANELQH42A QL42A

PANEL

PANELQH32A QL32A

PANEL

PANELQH22A QL22A

PANEL

PANELQL12AQH12A

PANEL PANELQH16A QL16A

PANEL

PANELQL26AQH26A

PANEL

PANELQL36AQH36A

PANEL

PANELQL46AQH46A

PANEL

30 KVASTX26A

503

PANELSH46A SL46A

PANEL

PANELSH36A SL36A

PANEL

PANELSH26A SL26A

PANEL

PANELSL16ASH16A

PANELPANELSH12A SL12A

PANEL

PANELSL22ASH22A

PANEL

PANELSL32ASH32A

PANEL

PANELSL42ASH42A

PANELPANELSH41A SL41A

PANEL

PANELSH31A SL31A

PANEL

PANELSH21A SL21A

PANEL

PANELSL11ASH11A

PANEL

PANELSH01A SL01A

PANEL

10041004

6041004

1004

30 KVASTX21A

2254

503

1004

EQUIPMENT SYSTEMS DISTRIBUTIONBOARD QHD1001ALIFE SAFETY BRANCH DISTRIBUTIONBOARD SHD1001A

800 AMP BUS, 277/480 VAC, 3 PHASE 4 WIRE

QMCC51ACENTERMOTOR CONTROL

PANELSL02ASH02A

PANEL

1004 604

PANELQH02A QL02A

PANEL

SPACE

ELECTRICAL RISER E-1 ELECTRICAL RISER E-2 ELECTRICAL RISER E-6

ELECTRICAL RISERE-1

ELECTRICAL RISERE-2

ELECTRICAL RISERE-6 E-6

ELECTRICAL RISERE-2

ELECTRICAL RISERE-1

ELECTRICAL RISER

28,000 RMS SYM AIC

---400AF

3P

70047004 22542254 8004 8004 6003

3003 6003

1004

30 KVASTX22A

503

10043504

2253

3504

2253

QTX32A112.5 KVA

6041004

503

QTX31A30 KVA

503

QTX36A30 KVA

40043504

10041004 604

6041004 1004 604 6041004

1004 60460410041004 604

10043504 4004

30044004 604

1004 1004

3003CTX21A150 KVA

300AF400AS

CBS21B

3P

1003

CBS22B

100AS100AF

45 KVACTX22A

1003CTX26A

3P

100AF100AS

CBS26B

1003CTX46A

3P

100AF100AS

CBS46B

2253

3P

CBS01B225AF400AS

CTX01A112.5 KVA

3P

1003

100AS

CBS02B100AF

CTX02A45 KVA

5003NHS1001A-12NORMAL FEED FROM

QATS1001B

600 AMP

BY-PASSMANUAL

PANELQHD51A

DIST.

2003

42,000 RMS SYM AIC42,000 RMS SYM AIC

45 KVA

45 KVA

8003

8003

NORMAL FEED FROMNHS1001B-6

800 AMP

QATS1001E

MANUALBY-PASS

800AT800AF

3P

8003

CONTROLMOTOR

PANELDIST.

QMCC00A

CENTERQHD00A

2253

DMM

NOT TO SCALEE5.3.01

1503

4

3P200AS

CBS16C150AF

1004

COOLING TOWER YARD

1254

604

5

5

5 6

5

5

5 5

5 5 5

55

5

1004 1004

604 604

55

5

5

5 5

5

6 5

5

5 5

5

6

1004

1004

4004 1004

1004 6044004 1004

5

5

5

5

BW

BW

6004

6004

NORMAL FEED FROMNHS1001B-3

600 AMP

CATS1001B

MANUALBY-PASS

6004

DMM DMM DMM DMM

DMM DMM DMM

F

F

F

F CL00APANEL

1004

LOCATED INCOOLINGTOWER YARD

DMM DMM DMM

11

DMM

PANELCLX01A

2254

F

F

F

F

F

F

F

F

F

F

F

F

F F

F

F

F

F

F

F

F

SPACE SPACEDMM DMM DMM SPACE DMM DMM

1503

5 5

5

5

5

5

5

5

656565

5 5

PANELQLX42A

3004

55

QTX41A112.5 KVA

4004

QL41BPANEL

112.5 KVAQTX41B

4004 2253

DIST.

QHD51BPANEL

ELEVATORSELEVATORS

PANELQHD54A

DIST.

5

DIST.

QHD51CPANEL

12531003

CONTROLMOTOR

QMCC52A

CENTER

QHX02APANEL

8

7

6

5

4

3

2

1

PER SET) IN 4" CONDUITS CONTAINED IN DUCT BANK AS SHOWN ON DRAWING 100-ES3.1.1.PROVIDE 3000 AMP, 3 PHASE 4 WIRE FEEDER ( 8 SETS OF #500MCM WITH 1 # 400MCM

TYPE I SWITCHBOARD PER SECTION 16462.

FLOOR PANELS. SEE PANEL SCHEDULES FOR SUB FEED BREAKER SIZES.PROVIDE THIS PANEL WITH SIDE GUTTER FOR EXTENSION OF SUB FEEDERS TO ADJACENT

E8.4.2. FEEDER TAP TO MATCH AMPACITY OF PANEL MAIN CIRCUIT BREAKER AS SHOWN ONPROVIDE THIS PANEL WITH SIDE GUTTER FEEDER TAP AS SHOWN IN DETAIL 7, DRAWING

TO BUSWAY SWITCH CBS16C (SEE DRAWING E5.3.0).EXTEND CRITICAL FEEDER FROM MANUAL TRANSFER SWITCH CMTS16A (SEE DRAWING E5.2.0)BREAKERS.PROVIDE BUSSED SPACE AND MOUNTING HARDWARE FOR FUTURE BREAKER TO MATCH NEW

GROUP MOUNTED, ADJUSTABLE TRIP, MOLDED CASE FEEDER BREAKER PER SPECIFICATION

1022 9

6 -AT400AF

3P

5 322 4150AT250AF

3P

2 3400AT400AF

3P

7

3P400AF - AT

23

3P400AF350AT

12

55

55

DIST.

QHD53BPANEL

3003

3 6 - AT400AF

3P

225 AMP BUS, 277/480 VAC, 3 PHASE 4 WIRE 36,000 RMS SYM AIC

837362

7

11

8

3P250AF100AT

52

3P400AF - AT

432 3100AT250AF

3P

3 2 - AT400AF

3P

2100AT250AF

3P

1

2 54232

7

2 2

7

5

3P400AF - AT

33

- AT400AF

3P

43

3P400AF - AT

32

400AT400AF

3P

2

400AF400AT

2

3P

1

3P

ELEVATORS

5

THE PANEL SCHEDULE DRAWINGS.

CONTROLMOTOR

QMCC1001A

CENTER

303

DMM

DRAWOUT, ADJUSTABLE TRIP MOLDED CASE MAIN CIRCUIT BREAKER ANDCOMPARTMENT PER SPECIFICATION SECTION 16462.

2003 3003

80 KVARFILTER

100 KVARFILTER

SECTION 16462.

PROVIDE LOCAL POWER DISTRIBUTION METERING EQUIPMENT PER SECTION 16430, 2.1 ANDPMDAS REMOTE MONITORING PER SECTION 16430, 2.2 METERING.

9

PROVIDE PMDAS REMOTE MONITORING PER SECTION 16430, 2.2 METERING.10

10 10 10

10 10 10 10 10 10 10 10 10SPACE

10 10

10

10 10 10

PANELCL16B

(E)PANELCL16B

(E)

AREA OF WORK

AREA OF WORK

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

44 P

M

ELECTRICAL SINGLE LINE DIAGRAM

EP5.0.1RP AuthorJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. CONTRACTOR SHALL INSPECT AND FIELD VERIFY ALL EXISTING SWITCHBOARDS AND PANELBOARDS, IN SCOPE OF WORK, TO CONFIRM SPARE BREAKER AND SPACE AVAILABILTY.

Page 40: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

45 P

M

PANELBOARD SCHEDULES

EP6.2.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Notes:

Total Est. Demand: 1Total Conn.: 1

Total Est. Demand: 714 VATotal Conn. Load: 572 VA

Lighting 572 VA 125.00% 714 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 1 0 1Total Load: 223 VA 0 VA 347 VA

41 0 0 -- -- SPACE 4239

EXISTING 0 20 0 -- -- SPACE 40

37 SPACE -- -- 0 0 -- -- SPACE 3835 SPACE -- -- 0 0 -- -- SPACE 3633 SPACE -- -- 0 0 -- -- SPACE 3431 SPACE -- -- 0 0 -- -- SPACE 3229 SPACE -- -- 0 0 -- -- SPACE 3027 SPACE -- -- 0 0 -- -- SPACE 2825 SPACE -- -- 0 0 -- -- SPACE 2623 EXISTING 20 1 0 0 -- -- SPACE 2421 SPACE -- -- 0 0 -- -- SPACE 2219 SPACE -- -- 0 0 -- -- SPACE 2017 SPACE -- -- 0 0 -- -- SPACE 1815 SPACE -- -- 0 0 -- -- SPACE 1613 SPACE -- -- 0 0 -- -- SPACE 1411 SPACE -- -- 0 0 -- -- SPACE 129 SPACE -- -- 0 0 -- -- SPACE 107 Lighting 20 1 183 0 -- -- SPACE 85 Lighting 20 1 347 0 1 20 SPARE 63 EXISTING 20 1 0 0 1 20 SPARE 41 Lighting 20 1 40 0 1 20 EXISTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: (E) CONFERENCE A1-422 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: SH16A

Notes:

Total Est. Demand: 6Total Conn.: 6

Total Est. Demand: 2000 VATotal Conn. Load: 2000 VA

Power 2000 VA 100.00% 2000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 10 0 10Total Load: 1000 VA 0 VA 1000 VA

41 0 0 -- -- SPACE 4239

SPARE 0 20 0 -- -- SPACE 40

37 SPACE -- -- 0 0 -- -- SPACE 3835 SPACE -- -- 0 0 -- -- SPACE 3633 SPACE -- -- 0 0 -- -- SPACE 3431 SPACE -- -- 0 0 -- -- SPACE 3229 SPACE -- -- 0 0 -- -- SPACE 3027 SPACE -- -- 0 0 -- -- SPACE 2825 Power 20 1 1000 0 -- -- SPACE 2623 Power 20 1 1000 0 -- -- SPACE 2421 EXISTING 20 1 0 0 -- -- SPACE 2219 EXISTING 20 1 0 0 -- -- SPACE 2017 EXISTING 20 1 0 0 1 20 EXISTING 1815 EXISTING 20 1 0 0 -- -- SPACE 1613 EXISTING 20 1 0 0 -- -- SPACE 1411 SPARE 20 1 0 0 -- -- SPACE 129 SPARE 20 1 0 0 -- -- SPACE 107 EXISTING 20 1 0 0 1 20 SPARE 85 EXISTING 20 1 0 0 1 20 EXISTING 63 EXISTING 20 1 0 0 1 20 SPARE 41 EXISTING 20 1 0 0 1 20 SPARE 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: (E) CONFERENCE A1-422 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: SL16A

Notes:

Total Est. Demand: 0Total Conn.: 0

Total Est. Demand: 219 VATotal Conn. Load: 175 VA

Lighting 175 VA 125.00% 219 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 1 0 0Total Load: 175 VA 0 VA 0 VA

41 SPACE -- -- 0 0 -- -- SPACE 4239 SPACE -- -- 0 0 -- -- SPACE 4037 SPACE -- -- 0 0 -- -- SPACE 3835 SPACE -- -- 0 0 -- -- SPACE 3633 SPACE -- -- 0 0 -- -- SPACE 3431 SPACE -- -- 0 0 -- -- SPACE 3229 SPACE -- -- 0 0 -- -- SPACE 3027 SPACE -- -- 0 0 -- -- SPACE 2825 SPACE -- -- 0 0 -- -- SPACE 2623 SPACE -- -- 0 0 -- -- SPACE 2421 SPACE -- -- 0 0 -- -- SPACE 2219 SPACE -- -- 0 0 -- -- SPACE 2017 SPACE -- -- 0 0 -- -- SPACE 1815 SPACE -- -- 0 0 -- -- SPACE 1613 SPACE -- -- 0 0 -- -- SPACE 1411 SPACE -- -- 0 0 -- -- SPACE 129 SPACE -- -- 0 0 -- -- SPACE 107 SPACE -- -- 0 0 1 0 EXISTING 85 SPARE 20 1 0 0 1 0 EXISTING 63 SPARE 20 1 0 0 1 0 EXISTING 41 Lighting - A1-203 20 1 79 96 1 20 E-1.6 / T-1.6 LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: CH16A

Notes:

Total Est. Demand: 17Total Conn.: 17

Total Est. Demand: 6080 VAReceptacle 5580 VA 100.00% 5580 VA Total Conn. Load: 6080 VAPower 500 VA 100.00% 500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 23 9 22Total Load: 2520 VA 1080 VA 2480 VA

41 SPARE 0 1 0 0 1 0 SPARE 4239 SPARE 0 1 0 360 1 20 A1-205 RECEPTACLES 4037 Receptacle - A1 - 149/151 20 1 360 0 1 0 EXISTING 3835 Power - A1 - 149/151 20 1 720 0 1 0 EXISTING 3633 Receptacle - A1 - 149/151 20 1 360 0 1 0 EXISTING 3431 Receptacle - A1 - 144/146 20 1 540 0 1 0 EXISTING 3229 Receptacle - A1 - 144/146 20 1 360 0 1 0 EXISTING 3027 Receptacle - A1 - 144/146 20 1 180 0 1 0 EXISTING 2825 EXISTING 0 1 0 0 1 0 EXISTING 2623 EXISTING 0 1 0 900 1 20 Receptacle - A1 - 143/145/147/149 2421 EXISTING 0 1 0 180 1 20 Receptacle - A1 - 143/145/147/149 2219 EXISTING 0 1 0 900 1 20 Receptacle - A1 - 143/145/147/149 2017 EXISTING 0 1 0 0 1 0 EXISTING 1815 EXISTING 0 1 0 0 1 0 EXISTING 1613 EXISTING 0 1 0 720 1 20 A1-203 RECEPTACLES 1411 EXISTING 0 1 0 0 1 0 EXISTING 129 EXISTING 0 1 0 0 1 0 EXISTING 107 EXISTING 0 1 0 0 1 0 EXISTING 85 EXISTING 0 1 0 500 1 20 A1-203 STX16A 63 EXISTING 0 1 0 0 1 0 EXISTING 41 EXISTING 0 1 0 0 1 0 EXISTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 225Mounting: SURFACE Wires: 4 Mains Rating: 225

Supply From: Phases: 3 Mains Type: MCBLocation: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: CL16A

Notes:

Total Est. Demand: 47Total Conn.: 41

Total Est. Demand: 39239 VATotal Conn. Load: 34251 VA

Motor 34251 VA 114.56% 39239 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 41 41 41Total Load: 11417 VA 11417 VA 11417 VA

41 SPACE 0 1 0 443 4239 6651 443 4037 6651 443

3 15 EF-238

35AHU-1 SUPPLY UNIT 40 3

6651 443 3633 3880 443 3431 3880 443

3 15 EF-132

29AHU-1 EXHAUST/RETURN UNIT 25 3

3880 3027 2825 2623 2421 2219 0 1 20 EXISTING 2017 0 1 20 EXISTING 1815 EXISTING 20 1 0 0 1 20 EXISTING 1613 EXISTING 20 1 0 0 1 20 EXISTING 1411 EXISTING 20 1 0 0 1 20 EXISTING 129 EXISTING 20 1 0 0 1 20 EXISTING 107 EXISTING 20 1 0 0 1 20 EXISTING 85 EXISTING 20 1 0 0 1 20 EXISTING 63 EXISTING 20 1 0 0 1 20 EXISTING 41 EXISTING 20 1 0 0 1 20 EXISTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 800Mounting: SURFACE Wires: 4 Mains Rating: 800

Supply From: Phases: 3 Mains Type: MCBLocation: (E) CONFERENCE A1-422 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: QHD51A

Notes:

Total Est. Demand: 3Total Conn.: 3

Total Est. Demand: 1000 VATotal Conn. Load: 1000 VA

Power 1000 VA 100.00% 1000 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 0 0 8Total Load: 0 VA 0 VA 1000 VA

41 EXISTING 0 1 0 0 -- -- SPACE 4239 EXISTING 0 1 0 0 -- -- SPACE 4037 EXISTING 0 1 0 0 -- -- SPACE 3835 SPARE 0 1 0 0 -- -- SPACE 3633 SPARE 0 1 0 0 -- -- SPACE 3431 SPARE 0 1 0 0 -- -- SPACE 3229 SPARE 0 1 0 0 -- -- SPACE 3027 SPARE 0 1 0 0 -- -- SPACE 2825 SPARE 0 1 0 0 -- -- SPACE 2623 SPARE 0 1 0 500 1 20 AHU-1 (EXHAUST) LIGHTS AND RECEPT. 2421 SPARE 0 1 0 0 1 20 EXISTING 2219 SPARE 0 1 0 0 -- -- SPACE 2017 SPARE 0 1 0 0 -- -- SPACE 1815 SPARE 0 1 0 0 -- -- SPACE 1613 SPARE 20 1 0 0 -- -- SPACE 1411 SPARE 20 1 0 0 -- -- SPACE 129 SPARE 20 1 0 0 -- -- SPACE 107 SPARE 20 1 0 0 -- -- SPACE 85 AHU-1 (SUPPLY) LIGHTS AND RECEPT. 20 1 500 0 1 20 EXISTING 63 EXISTING 20 1 0 0 1 20 EXISTING 41 EXISTING 20 1 0 0 1 20 EXISTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: (E) CONFERENCE A1-422 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: QL16A

GENERAL NOTE:1. CONTRACTOR SHALL INSPECT AND FIELD VERIFY ALL EXISTING SWITCHBOARDS AND PANELBOARDS, IN SCOPE OF WORK, TO CONFIRM SPARE BREAKER AND SPACE AVAILABILTY.

Page 41: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

LOAD VERIFICATION

LOAD TO BE ADDED:

AMPS @ 480/277V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "CH16A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND(E) DEMAND LOAD PER AS-BUILT DWGS

LOAD JUSTIFICATION FOR (E) PANEL 'CH16A' - CRITICAL

(E) BUS RATING

____________

________________________

________________________

0.08KVA

12.55KVA15.1A

12A15A

____________ 100A

LOAD TO BE ADDED:

AMPS @ 208/120V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "CL16A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND(E) DEMAND LOAD PER AS-BUILT DWGS

LOAD JUSTIFICATION FOR (E) PANEL 'CL16A' - CRITICAL

(E) BUS RATING

____________

________________________

________________________

9.72KVA

62.86KVA174.5A

118A147.5A

____________ 225A

LOAD VERIFICATION

LOAD TO BE ADDED:

AMPS @ 480V/277V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "SH16A" IS SUFFICIENT FOR THE ADDED LOAD.

LOAD JUSTIFICATION FOR (E) PANEL 'SH16A' LIFE SAFETY

(E) BUS RATING

____________

________________________

1.2KVA

6.4KVA7.7A

____________ 100A

LOAD TO BE ADDED:

AMPS @ 480/277V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "NH16A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND

(E) DEMAND LOAD RECORDED FOR 30 DAYS

LOAD JUSTIFICATION FOR (E) PANEL 'NH16A' - NORMAL

(E) BUS RATING

____________

____________

____________

________________________

4.5KVA

10.4KVA12.5A

5.7A

7.125A

____________ 100A

LOAD VERIFICATION

LOAD TO BE ADDED:

AMPS @ 208V/120V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "SL16A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND(E) DEMAND LOAD PER AS-BUILT DWGS

LOAD JUSTIFICATION FOR (E) PANEL 'SL16A' - LIFE SAFETY

(E) BUS RATING

____________

________________________

________________________

1.00KVA

17.2KVA48A

36A45A

____________ 100A

LOAD TO BE ADDED:

AMPS @ 480V/277V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "QHD51A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND(E) DEMAND LOAD PER AS-BUILT DWGS

LOAD JUSTIFICATION FOR (E) PANEL 'QHD51A' - EQUIPMENT

(E) BUS RATING

____________

________________________

________________________

48KVA

528KVA635A

461A577A

____________ 800A

FROM 06/13/16 TO 07/13/16RECORDED MAX LOAD

LOAD TO BE ADDED:

AMPS @ 208V/120V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) XFMR "NTX16A" IS SUFFICIENT FOR THE ADDED LOAD.

MAX DEMAND = 1.25 x DEMAND

(E) DEMAND LOAD RECORDED FOR 30 DAYS

LOAD JUSTIFICATION FOR (E) XFMR 'NTX16A' - NORMAL

(E) XFMR RATING

____________

____________

____________

________________________

12.1KVA

39.65KVA110A

61.2A

76.5A

____________ 75KVA

LOAD VERIFICATION

LOAD TO BE ADDED:

AMPS @ 208V/120V, 3

(N) EST. MAX. DEMANDMAX. DEMAND + ADDED LOAD

THEREFORE THE (E) PANEL "QL16A" IS SUFFICIENT FOR THE ADDED LOAD.

LOAD JUSTIFICATION FOR (E) PANEL 'QL16A' - EQUIPMENT

(E) BUS RATING

____________

________________________

1.0KVA

5.2KVA14.4A

____________ 100A

FROM 06/13/16 TO 07/13/16RECORDED MAX LOAD

MAX DEMAND = 1.25 x DEMAND

(E) DEMAND LOAD RECORDED FOR 30 DAYS

____________

____________ 9.3A

11.6A

FROM 06/13/16 TO 07/13/16RECORDED MAX LOAD

MAX DEMAND = 1.25 x DEMAND

(E) DEMAND LOAD RECORDED FOR 30 DAYS

____________

____________ 5A

6.25A

FROM 06/13/16 TO 07/13/16RECORDED MAX LOAD

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

46 P

M

PANELBOARD SCHEDULES

EP6.2.2RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Notes:

Total Est. Demand: 3Total Conn.: 3

Total Est. Demand: 2763 VAOther 0 VA 0.00% 0 VA Total Conn. Load: 2211 VALighting 2211 VA 125.00% 2763 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 2 4 2Total Load: 420 VA 1213 VA 577 VA

41 SPARE 0 1 0 0 -- -- SPACE 4239 SPARE 0 1 0 0 -- -- SPACE 4037 0 0 -- -- SPACE 3835 0 0 -- -- SPACE 3633

EXISTING 0 30 0 -- -- SPACE 34

31 SPARE 0 1 0 0 -- -- SPACE 3229 SPARE 0 1 0 0 -- -- SPACE 3027 SPARE 0 1 0 0 -- -- SPACE 2825 SPARE 0 1 0 16 1 20 Lighting 2623 SPARE 0 1 0 167 1 20 Lighting 2421 SPARE 0 1 0 504 1 20 Lighting 2219 SPARE 0 1 0 356 1 20 Lighting 2017 SPARE 0 1 0 330 1 20 Lighting 1815 SPARE 0 1 0 710 1 20 Lighting 1613 SPARE 0 1 0 48 1 20 Lighting 1411 SPARE 0 1 0 80 1 20 Lighting 129 SPARE 0 1 0 0 1 0 EXISTING 107 SPARE 0 1 0 0 1 0 EXISTING 85 EXISTING 0 1 0 0 1 0 EXISTING 63 EXISTING 0 1 0 0 1 0 EXISTING 41 EXISTING 0 1 0 0 1 0 EXISTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: (E) ELECTRICAL ROOM E-1.6 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: NH16A

Notes:

Total Est. Demand: 38Total Conn.: 44

Total Est. Demand: 13600 VAReceptacle 14200 VA 85.21% 12100 VA Total Conn. Load: 15700 VAPower 1500 VA 100.00% 1500 VALoad Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:Total Amps: 61 32 41Total Load: 7140 VA 3780 VA 4780 VA

41 SPARE 0 1 0 0 1 0 SPARE 4239 SPARE 0 1 0 0 1 0 SPARE 4037 SPARE 0 1 0 0 1 0 SPARE 3835 SPARE 0 1 0 0 1 0 SPARE 3633 SPARE 0 1 0 0 1 0 SPARE 3431 SPARE 0 1 0 0 1 0 SPARE 3229 SPARE 0 1 0 0 1 0 SPARE 3027 SPARE 0 1 0 0 1 0 SPARE 2825 RECEPTACLE 20 1 360 0 1 0 SPARE 2623 A1-142 COPY MACHINE 20 1 1000 0 1 0 SPARE 2421 A1-140/142 20 1 1080 0 1 0 SPARE 2219 A1-140/142 20 1 1080 0 1 0 SPARE 2017 A1-C002/150/152 20 1 720 0 1 0 SPARE 1815 A1-140 20 1 1080 0 1 0 SPARE 1613 A1-140 20 1 1440 0 1 0 SPARE 1411 A1-140 20 1 720 0 1 0 SPARE 129 A1-203 IV INFUSION PUMP 20 1 180 0 1 0 SPARE 107 SPARE 0 1 0 0 1 0 SPARE 85 A1-203 PATIENT LIFT 20 1 0 0 1 0 SPARE 63 A1-203 HEADWALL 20 1 0 0 1 0 SPARE 41 A1-203 GP 20 1 1500 0 1 0 SPARE 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: TYPE 1 MCB Rating: 100Mounting: SURFACE Wires: 4 Mains Rating: 100

Supply From: Phases: 3 Mains Type: MCBLocation: (E) ELECTRICAL ROOM E-1.6 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: NL16C

GENERAL NOTE:1. CONTRACTOR SHALL INSPECT AND FIELD VERIFY ALL EXISTING SWITCHBOARDS AND PANELBOARDS, IN SCOPE OF WORK, TO CONFIRM SPARE BREAKER AND SPACE AVAILABILTY.

Page 42: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

1/2" BOLTS TO P1010 NUTS4 TOTAL MIN.

USE 2#10 SMS. EA. END16GAx3" CROSS STRAPPING;

3/4" NEOPRENE PAD

7'-0" TO TOPOF SLAB

SECTION A

FOR SUPPORTP1000 WITH 1/2" BOLTS

FORMERTRANS-

6" MAX.

SIM. TO SECTION ACROSS BRACE

HSS 6X4 COLUMN

SECTION B

CEILING

NON-STRUCTURAL

1/4

WALL

6"

B

4"

B

3/164 SIDES, (TYP)

HSS 4x4x1/4

NON-STRUCTURALWALL

1/4

B

4"

B3/4" M.B. TO ANGLE,

ADJUST LOCATION ( 6") IF NEEDED TO AVOID CONFLIC WITH STEEL FRAMING OVERHEAD.

CONFIRM FINAL LOCATION WITH ARCHITECT BEFORE STARTING WORK.

HEIGHT, WIDTH, OR DEPTH OF TRANSFORMER VARIES.

AFTER FABRICATION, GRIND ALL WELDS, PAINT WITH ONE COAT RED LEAD

SLOPE OF 1 TO 1 OR GREATER

3/4" M.B. TO ANGLE,(TYP OF 4)

DRY-TYPE

3/4" M.B.

3x3x3/8

TRANSFORMER

3/4" NEOPRENE PADS

A

A

3/8"x4"x4" PLATE WITH

SLOPE OF 1 TO 1 OR GREATER

PANELBOARD

CONDUIT

3/4" NEOPRENE PADS

TRANSFORMER

3x3x3/8

3/4" M.B.

DRY-TYPE

(TYP OF 4)

A

A

1.AND TWO COATS OF GRAY PAINT.

4.

3.

2.

-+

NOTES:

TRANSFORMER PHYSICAL DATA

30"H x 20"W x 14"D

DIMENSIONS

3/8"x4"x4" PLATE WITH

RATING

30KVA

WEIGHT

300#

DETAIL NOTES:

THE CAULK IS TO BE FORCED INTO THE ANNULAR SPACE TO THE MAXIMUMEXTENT POSSIBLE, FLUSH WITH THE EXTERIOR OF THE PENETRATIONSURFACE.

FINISH CAULKING WITH A 1/4" MINIMUM BEAD OF 3M CP 25N/S CAULK APPLIEDTO THE PERIMETER OF THE CONDUIT AT ITS EGRESS FROM THE WALL.

THE MAXIMUM ANNULAR SPACE IS NOT TO EXCEED 3/16".

INSTALL 3M FIRESTOP ON BOTH SIDES OF THE WALL.

THESE RECOMMENDATIONS ARE BASED ON THE PRODUCT PERFORMANCEPER ASTM E-814 FIRE TEST AND UL THROUGH PENETRATION FIRESTOPSYSTEM #WL1001 RATED UP TO 2 HOURS.

1/4" (6MM) MINIMUMDIAMETER BEAD OF 3MCP 25N/S CAULK

1 OR 2 HOUR FIRE RATEDGYPSUM BOARD WALL

CONDUIT UP TO 4"

STEELSTUD

1.

2.

3.

4.

5.

0CL

120V

N

H 1N 2

0

LC

PHOTOCELL, CONDUIT MOUNTINGWITH SWIVEL, IN TOUGH LEXANENCLOSURE, TORK #EPC-1

TO OTHER LCP'S

MECHANICALLY HELD MULTI-POLEREMOTE CONTROL LIGHTING CONTACTOR(TYPICAL)

NEMA 1 ENCLOSURE(SIZED AS REQUIRED)

EXT. LTG.PHOTO"ON"TIME "OFF"

SITE LTG.PHOTO "ON"PHOTO "OFF"

BYPASS SWITCH,MOMENTARY CONTACT,3 POSITION, CENTEROFF, MOUNT ON PANELCOVER (TYPICAL)

MOMENTARYCONTACTADAPTER(TYP. FOR 2)

ELECTRONICTIMESWITCH WITHBATTERY BACKUPAND TWO CIRCUITS,TORK NO. DGLC

OFF PULSEON PULSEOFF PULSEON PULSE

CLOCK

SECURE LIGHT FIXTURE SUPPORT WIRESTO MOUNTING TABS, IF LIGHT FIXTURENOT FURNISHED WITH MOUNTING TABS.PROVIDE 4-EYE BOLTS WITH ALLNECESSARY HARDWARE

#12 GA (MIN) LIGHT SUPPORT WIRE,4-PER 4-FOOT LENGHT OF LIGHTFIXTURE. SECURE TO BUILDINGSTRUCTURE SIMILAR TO CEILINGSUPPORT WIRES

#12 GA (MIN) LIGHT SUPPORTWIRE, 4-PER 4-FOOT LENGTHOF LIGHT FIXTURE. SECURE TOBUILDING STRUCTURE SIMILARTO CEILING SUPPORT WIRES

SECURE LIGHT FIXTURESUPPORT WIRES TO MOUNTINGTABS, IF LIGHT FIXTURE NOTFURNISHED WITH MOUNTINGTABS. PROVIDE 4-EYE BOLTSWITH ALL NECESSARYHARDWARE

TYPICAL CROSS "T" BAR

TYPICAL ACOUSTICALTILE CEILING

TYPICAL GYPSUMCEILING

TYPICAL RECESSEDLIGHT FIXTURE

TYPICAL RECESSEDLIGHT FIXTURE

TYPICAL FLEX CONDUIT WITH ALLNECESSARY FITTINGS TO JUNCTION BOX.PROVIDE #12 BRANCH CIRCUIT WIRESAND #12 GROUND WIRE BOND TO LIGHTFIXTURES

"T" BAR CLIP, ALL LIGHT FIXTURES (ORROWS) SHALL HAVE TWO CLIPS ATEACH END. PROVIDE 2#8-32 BOLTSWITH LARGE FLAT WASHERS AND NUTSBETWEEN LIGHT FIXTURES INCONTINUOUS ROW INSTALLATION

TYPICAL MAIN"T" RUNNER

PENDANTMOUNTEDLIGHT FIXTURE

"EYE" BOLT (TYP.)

TYPICAL FLEX CONDUITWITH ALL NECESSARYFITTINGS TO JUNCTIONBOX. PROVIDE #12BRANCH CIRCUIT WIRESAND #12 GROUND WIREBONDTO LIGHT FIXTURE

HILTI HKT 14 TIE WIREANCHOR WITH MIN. 1 1/8"MIN. EMBEDMENT (TYP.)

3/32" DIA. AIRCRAFTCABLE. 2 PER 4FOOTLENGTH OFLIGHTFIXTURE. SECURE TOBUILDING STRUCTURE

NICO PRESS AT END(TYPICAL)

LP-215 AMP

15 AMP

15 AMP

15 AMP

15 AMP

15 AMP

15 AMP

DIGITALCONTROLLER

RELAY LIGHTINGCONTACTORS(TYPICAL)

DIGITAL CONTROLLERAPPROX DIM= 10%%212"Wx4"Dx15"H

F44

F31

F31

F45

F45

F31

F31

F45

F37

STAIR #1CELLAR(LP-2 CKT 13)

STAIR #12ND FLOOR(LP-2 CKT 4)

STAIR #12ND FLOOR MEZZ(LP-2 CKT 4)

STAIR #12ND FLOOR ARCH LIGHTBOX(LP-2 CKT 2)

STAIR #12ND FLOOR MEZZARCH LIGHTBOX(LP-2 CKT 2)

STAIR #13RD FLOOR(LP-2 CKT 12)

EXTERIORLIGHTING(LP-2 CKT 5)

STAIR #11ST FLOOR(LP-2 CKT 15)

3M FIRE BARRIERCP 25 CAULK

FIRE RATED CONC.FLOOR SLAB

FIRE BARRIER

DAMMING MATERIAL(MINERAL WOOL ORCERAMIC FIBER)

CONDUIT

3M FIRE BARRIERCP 150 CAULK

FIRE RATED CONC.WALL

3M FIRE BARRIERFS-195 WRAP/STRIP ORMINIRAL WOOL ORCERAMIC FIBER

CONDUIT

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

48 P

M

ELECTRICAL DETAILS

EP7.2.1RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

NTS03 CONDUIT FIRE WALL PENETRATION DETAIL

NTS02 LIGHTING CONTROL PANEL DIAGRAM

NTS04 RECESSED LIGHT FIXTURE MOUNTING DETAIL

NTS05 PENDANT MOUNTED LIGHT FIXTURE DETAIL

NTS06 LIGHTING CONTROL DETAIL

NTS07 PENETRATION FIRESTOP FOR CONDUIT THRU FLOOR SLAB (SYSTEM CAJ1001)

NTS08 PENETRATION FIRESTOP FOR CONDUIT THRU FLOOR CONC (SYSTEM CAJ1017)

12" = 1'-0"01 WALL MOUNTED TRANSFORMER

Page 43: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

A

A

3

2

1A

1B

SECTION A-A

SYSTEM No. WL3047

PLAN

WALL ASSEMBLY - THE FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BECONTRCUTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 ORU400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALLINCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

CABLES - MAX 7/C NO. 12 AWG CABLES WITH POLYVINYL CHLORIDE JACKET AND INSULATION.AGGREGATE CROSS - SECTIONAL AREA OF TIGHTLY BUNDLED CABLE GROUP TO BE 33 PERECENTOF THE AGGREGATE CROSS-SECTIONAL AREA OF THE OPENING. CABLES TO BE RIGIDLYSUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.

FILL, VOID OR CAVITU MATERIAL* - SEALANT - MIN 1-1/4 IN. THICKNESS OF FILL MATERIAL APPLIEDWITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. SEALANT TO BE FORCED INTOINTERSTICES OF CABLE GROUP TO MAX EXTENT POSSIBLE.

STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNELSTUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACE 16 IN. OC. STEELSTUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC.

GYPSUM BOARD* - TWO LAYERS OF 5/8 IN. THICK GYPSUM WALLBOARD, AS SPECIFIED INTHE INDIVIDUAL WALL AND PARTITION DESIGN. MAX DIA OF OPENING IS 6 IN.

A.

B.

1.

2.

3.

A

A

TOTAL WEIGHT: 300 LBS. MAX.

SECTION A-AELEVATION

ARCHITECTURAL STUDSJ4 16 GA.

5.75"

48"

72" MAX.

20"

4" MAX (TYP)

METAL STUD(TYPICAL)

WALL MOUNTEDELECTRICALPANELBOARD

SELF-TAPPINGSHEET METALSCREWS ATEACH CORNER

16 GA ANGLECLIP (2"x2")

METAL STUD(TYPICAL)

ELECTRICALPANELBOARD

6" GA X 14 GATRACK TO SPANA MIN. OF 3STUDS TYP. ATTOP ANDBOTTOM

2-#14 TEKSSCREWS TYP.TOP ANDBOTTOM OFPANEL

4#10 SMSREQUIRED ATEACH CLIP

FINISHED FLOOR

(N) PANEL BL16C

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAUN

DAVID LANDMAN

E L E C T R I C A

L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd. 3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

FOR CONSTRUCTIONFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

Associate Architect:

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com11/2

9/20

16 2

:59:

49 P

M

ELECTRICAL DETAILS

EP7.2.2RP DSJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

12" = 1'-0"1 FIRE RATED WALL CABLE PENETRATION DETAIL

12" = 1'-0"2 ELECTRICAL PANEL ANCHORAGE DETAIL

12" = 1'-0"3 ELECTRICAL CLOSET E-16

12" = 1'-0"4 ELECTRICAL CLOSET E-51

NOTE:1. PROVIDE AND INSTALL NEW MATCHING RELAYS TO EXISTING LCP16A AS INDICATED ON SHEET ES0.1.0.

(SEE NOTE 1)

Page 44: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

DESCRIPTIONSYMBOL

TELECOMMUNICATIONSSYMBOLS LIST

TELECOMMUNICATIONSGENERAL NOTES

THE MINIMUM WORK OUTLET PATHWAY SHALL CONSIST OF ONE (1) 4-11/16 " SQUAREBACKBOX SERVED BY ONE (1) 1 1 /4" CONDUIT. THE BACKBOX SHALL HAVE A 2-GANGREDUCER COLLAR TO ACCEPT A DOUBLE GANG FACEPLATE.

PROVIDE A COMPLEMENT OF 4-PAIR UTP CATEGORY 6 CABLES FOR ALLTELECOMMUNICATION OUTLETS. QUANTITY OF CABLES TO MATCH THE NUMBER OF PORTSSHOWN FOR EACH OUTLET LOCATION.

ALL OUTLETS SHALL BE MOUNTED @ 18" AFF/OC, AND RECEIVE (1) 1-1/4 INCHESCONDUIT TO THE NEAREST CABLE TRAY, UON. BY NOTE OR SYSTEM IDENTIFIER.

SYSTEM IDENTIFICATION:

ANY OUTLET NOT LABELED SHALL RECEIVE (4) FOUR CATEGORY 6 4 PAIR UTP CABLES.

W = WALL PHONE, ONE (1) EACH CAT6 UTP CABLE IN A SINGLE GANG BACK BOX,MOUNTED @ +44" TO THE BOTTOM OF THE DEVICE BACK BOX.

WAP = LOCATIONS ARE SHOWN FOR COORDINATION PURPOSES. WAPS ARESHOWN IN APPROXIMATE LOCATIONS. THE GC TO INFORM AND COORDINATEREMOVAL OF EXISTING WAP DEVICES. EXISTING WAP DEVICES SHALL BERETURNED TO THE VA. THE VA (i.e. REGIONAL VA OIT) WILL BE RESPONSIBLEFOR INSTALLATION OF THE CABLING REINSTALLATION OF WAP CABLING ANDDEVICES. PRIOR OF REMOVAL.DAS = THE GC SHALL COORDINATE WITH VA REGARDING THE EXISTINGSPRINT SYSTEM. VA AND SPRINT TO BE RESPONSIBLE FOR REINSTALLATIONOF THE SYSTEM.

TV = TELEVISION. PROVIDE RG6 CABLE TO NEW SIGNAL ROOM. REFER TOARCHITECTURAL ELEVATION DRAWINGS FOR MOUNTING HEIGHTS.

# = NUMBER OF CAT6 UTP STATION CABLES

THIS SHEET ILLUSTRATES AND DEFINES TYPICAL GRAPHIC SYMBOLS, ANDSYSTEMS OF GRAPHICSYMBOLS WHICH MAY OCCUR ON THE TELECOMMUNICATIONS DRAWINGS. THEILLUSTRATION OF A SYMBOL OR SYSTEM OF SYMBOLS, ON THIS SHEET DOESNOT NECESSARILY INDICATE THAT THE BUILDING ITEM OF THE DESCRIBEDSYSTEM BY THE SYMBOL IS USED AS PART OF THIS PROJECT. REFER TO THEPLANS, ELEVATIONS, SECTIONS, SCHEDULES, DETAILS AND SPECIFICATIONSTO DETERMINE THE SCOPE OF WORK.

THE WORK, INCLUDING MATERIALS, METHODS, ASSEMBLIES, ETC., SHALLCOMPLY WITH THE MINIMUM REQUIREMENTS OF THE GOVERNING LAWS,ORDINANCES, AND REGULATIONS OF ALL FEDERAL, STATE, DISTRICT, ANDLOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT, AS WELL ASTHOSE GREATER REQUIREMENTS INDICATED BY THE CONTRACT DOCUMENTS.NO PART OF THE CONTRACT DOCUMENT MAY BE CONSTRUED TO REQUIRE ORPERMIT WORK CONTRARY TO A GOVERNING LAW, ORDINANCE, ORREGULATION.

THE WORK INCLUDES, BUT IS NOT LIMITED TO, THE ITEMS OUTLINED IN THESECONSTRUCTION DOCUMENTS AND AS INDICATED ON THE SHOP DRAWINGS, ASWELL AS ALL INCIDENTAL ITEMS REQUIRED TO PROVIDE COMPLETE ANDOPERATIONAL SYSTEMS. WHERE REFERENCE IS MADE TO A REQUIREMENTSTHAT EXCEEDS MINIMUM CODE/STANDARD REQUIREMENTS, THISCONSTRUCTION DOCUMENT REQUIREMENTS SHALL TAKE PRECEDENCE. THECONTRACTOR SHALL REPORT ANY WORK THAT IS IN APPARENT CONFLICTWITH APPLICABLE CODES.

THE TELECOMMUNICATIONS DRAWINGS ARE PART OF A LARGER SET OFDRAWINGS WHICH, WHEN COMPLETE, CONSISTS OF DRAWINGS LISTED BY THE"INDEX OF DRAWINGS". THE WORK DESCRIBED BY THE DRAWINGS OF ANY ONEDISCIPLINE MAY BE AFFECTED BY THE WORK AND REQUIREMENTSDESCRIBED ON DRAWINGS OF ANOTHER DISCIPLINE AND MAY REQUIREREFERENCE TO THE DRAWINGS OF ANOTHER DISCIPLINE. PARTIAL SETS OFDRAWINGS ARE INCOMPLETE AND SHOULD NOT BE DISTRIBUTED OR UTILIZEDBY THE CONTRACTOR. MANAGE, SUPERVISE, REVIEW, AND COORDINATE THEWORK OF SUB-CONTRACTORS, TRADES AND SUPPLIER WITH THEREQUIREMENTS OF THE CONTRACT DOCUMENTS BEFORE COMMENCINGCONSTRUCTION AND TO ASSURE THAT PARTIES ARE AWARE OFREQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR IN THECONTRACT DOCUMENTS, WHICH MAY AFFECT THE WORK OF THAT PARTY.

THESE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THETELECOMMUNICATIONS SPECIFICATION DOCUMENTS, ANY DISCREPANCYBETWEEN THE DRAWINGS AND THE SPECIFICATIONS SHALL BE REPORTED TOTHE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION FORRESOLUTION.

THE ARCHITECTURAL DRAWINGS ESTABLISH AND COORDINATE THE FINISHEDAPPEARANCE AND EXACT LOCATION OF EXPOSED ELEMENTS OF THE WORK OFTRADES, INCLUDING THAT WORK THAT IS ILLUSTRATED PRIMARILY OF THESEDRAWINGS. LOCATIONS SHOWN ON THESE DRAWINGS ARE DIAGRAMMATIC.REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONED LOCATIONS

COORDINATE EXACT MOUNTING LOCATIONS AND HEIGHTS OF ALL DEVICESMOUNTED TO BUILDING EXTERIORS WITH THE ARCHITECT. CONTRACTORSHALL MAKE EFFORT TO RESPECT THE SYMMETRIC OF THE STRUCTUREWHEN LOCATING EXTERIOR DEVICES. OBTAIN APPROVAL OF EXACT DEVICELOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.

CONTRACTOR SHALL NOT NOTCH, CUT OR BORE ANY STRUCTURAL MEMBERNOT SPECIFICALLY DETAILED ON THE APPROVED DRAWINGS WITHOUT PRIORWRITTEN APPROVAL FROM THE ARCHITECT AND STRUCTURAL ENGINEER.

ALL INSTALLATION WORK SHALL BE PERFORMED ACCORDING TO PUBLISHEDINDUSTRY GUIDELINES, RULES, AND REGULATIONS. IF CONFLICTS ORDISPUTES OCCUR VA STANDARDS HAVE PRECEDENCE; THEN OWNER POLICIESAND PROCEDURES; THEN STANDARDS SUCH AS TIA/EIA; THEM GUIDELINESFROM FIRMS SUCH AS BUILDING INDUSTRY CONSULTING SERVICESINTERNATIONAL (BICSI); THEN FINALLY, MANUFACTURER RECOMMENDATIONS.

WHERE REFERENCE IS MADE TO REQUIREMENT THAT EXCEEDS MINIMUMCODES/STANDARD REQUIREMENTS, THIS CONSTRUCTION DOCUMENTREQUIREMENT SHALL TAKE PRECEDENCE.

ALL NEW CONDUIT, CABLE TRAY AND EQUIPMENT ANCHORAGE SHALL BEDETAILED ON DRAWINGS AND SHALL CONFORM TO 2001CBC SECTION 1632AAND TABLE 16 A-0.

THE CONTRACTOR SHALL MAINTAIN A COPY OF THE SPECIFICATIONS ANDDRAWINGS AT THE JOB SITE. PRESENT THE SPECIFICATIONS AND DRAWINGSUPON REQUEST. MAINTAIN DAILY MARKUPS OF ACTUAL INSTALLATION TOACCURATELY RECORD FIELD CONDITIONS AND PRESENT FOR REVIEW UPONREQUEST.

REFER TO WRITTEN SPECIFICATIONS FOR PROJECT SCOPE, GENERALREQUIREMENTS, PRODUCT SPECIFICATIONS AND INSTALLATIONREQUIREMENTS. WHERE QUANTITY DIFFER, THE HIGHER OF EACH SHALLPREVAIL.

THE CONTRACTOR SHALL PROVIDE AND INSTALL NECESSARY EQUIPMENT ANDACCESSORIES FOR A FULLY FUNCTIONAL SYSTEM THAT MEETS INTENDEDWHETHER EXPRESSLY SPECIFIED OR NOT.

PROVIDE MATERIALS AND EQUIPMENT LISTED BY UNDERWRITERSLABORATORIES FOR THE PURPOSE USED AND BEARING THEIR LABEL.

PRIOR TO PERFORMING WORK, IMMEDIATELY NOTIFY THE OWNER, OWNER'SREPRESENTATIVE, IN WRITING OF OBSERVATIONS OR CONDITIONSDISCOVERED THAT WOULD PREVENT INSTALLATION ACCORDING TO DRAWINGSTO DRAWINGS AND SPECIFICATIONS.

PREPARE A SET OF MARKED UP PLANS TO WEEKLY CONSTRUCTION MEETINGFOR OWNER'S OR OWNER'S REPRESENTATIVE'S APPROVAL PRIOR TOPRODUCTION OF AS-BUILT DRAWINGS FOR RECORD DOCUMENTATION.

ALL MATERIALS IN THESE CONTRACT DOCUMENTS SHALL BE PROVIDED ANDINSTALLED UNLESS OTHERWISE NOTED.

INSTALL EQUIPMENT, DEVICES AND PATHWAYS, SUCH THAT CABLE TRAY,RUNWAY, CONDUITS, CABLE HANGERS, AND PULL BOXES, ETC. ADHERE TOSTATE AND LOCAL CODES AND REGULATORY REQUIREMENTS FOR SEISMICBRACING.

INSTALL CONDUIT PATHWAYS PER TIA/EIA-569-B AND BICSI (BUILDINGINDUSTRY CONSULTING SERVICES INTERNATIONAL) TDMM(TELECOMMUNICATIONS DISTRIBUTION METHODS MANUAL) LATEST EDITION.

CONDUIT ROUTING, WHERE SHOWN ON DRAWINGS, IS DIAGRAMMATIC INNATURE. FIELD DETERMINE CONDUIT ROUTES TO SUIT FIELD CONDITIONSWHILE CONFORMING TO SPECIFICATIONS. PREPARE SHOP DRAWINGS SHOWINGEXACT CONDUIT ROUTES, INDICATING PENETRATION TYPES. COORDINATEREQUIREMENTS WITH OTHER TRADES.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

TELECOMMUNICATIONSLEGEND NOTES

DESCRIPTIONSYMBOL

PATHWAYS AND MISC.SYMBOLS LIST

NURSE CALLSYMBOLS LIST

SYMBOL

NCCP NURSE CALL TERMINAL. CONTRACTOR TO COORDINATE FINAL LOCATION WITH OWNER.

NURSE CALL SYSTEM PULL STATION WALLMOUNTED OR ON PATIENT HEADWALL UNIT.REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR MOUNTINGHEIGHTS.

NURSE CALL SYSTEM DOME LIGHT, WALL MOUNTED(SEE ARCH. ELEVATORS FOR EXACT LOCATION)REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR MOUNTINGHEIGHTS.

NURSE CALL SYSTEM DOME LIGHT, CEILING MOUNT

PS

CB CODE BLUE MOUNTED ON HEAD WALL

ROUTE CONDUIT, CABLE TRAYS AND OTHER PATHWAYS PERPENDICULAR ORPARALLEL TO BUILDING LINES, IN GENERAL. ROUTE TELECOMMUNICATIONSCABLES NO LESS THAN 6 INCHES FROM ANY POWER SOURCE OR FLORESCENTLIGHTING FIXTURE AND NO LESS THAN 4 FEET FROM ANY TRANSFORMER ORMOTOR.

CONDUITS WITH A 2" INSIDE DIAMETER OR LESS WILL HAVE A BEND RADIUS OFLESS THAN 10 TIMES THE INSIDE DIAMETER.

CONDUIT RUNS SHALL NOT EXCEED 180 DEGREES OR TWO 90 DEGREE BENDSWITHOUT AN APPROPRIATE NEMA RATED PULL BOX OR/AND ADDITIONAL BENDOF UP TO 90 DEGREES, UNLESS LAST BEND IS WITHIN 12 INCHES OF THECONDUIT END.

WHEN ROUTING CONDUIT IN CONCRETE, MAINTAIN A GRADUATED BENDRADIUS TO MAINTAIN CONDUIT CAPACITY. THE USED OF 90-DEGREE "ELBOW"FITTING IS EXPRESSLY PROHIBITED UNLESS PRIOR AUTHORIZATION ISRECEIVED FROM OWNER, OR OWNER'S REPRESENTATIVE IN WRITING.

PROPERLY FIRE SEAL CONDUIT AND RACEWAY PENETRATIONS THROUGH FIRERATED WALLS AND FLOORS TO MAINTAIN THE FIRE SEPARATION RATING.PROVIDE FIRE SEALING ASSEMBLIES THAT ARE UL LISTED FOR THEAPPLICATION. COORDINATE REQUIREMENTS WITH LOCAL FIRE MARSHALLPRIOR TO INSTALLATION. DO NOT MIX PRODUCT BETWEEN MANUFACTUREDASSEMBLIES.

PROVIDE EXPANSION/DEFECTION FITTINGS FOR CONDUITS AT STRUCTURALEXPANSION JOINT CROSSINGS.

PROVIDE EXPANSION/DEFECTION FITTINGS FOR CONDUITS AT STRUCTURALEXPANSION JOINT CROSSINGS.

PROVIDE PLASTIC BUSHING ON EXPOSED END OF ALL CONDUIT AND SLEEVES,WHETHER VISIBLE OR NOT.

ALL SLEEVES SHALL BE FILED CLEAN, DEBARRED, CAPPED, LABELED ANDFURNISHED WITH A MEASURED PULL TAPE BY THE CONTRACTOR.

ALL CONDUIT STUBS ARE TO BE LOCATED PAST SOFFITS, HARD LID CEILINGAND INACCESSIBLE AREAS.

PROVIDE MINIMUM 1 INCH SIZE CONDUIT FOR HORIZONTAL DISTRIBUTION ANDTELECOMMUNICATIONS. CONSOLIDATION OF CONDUITS IS ALLOWED WHENEQUAL OR GREATER CONSOLIDATED AREA IS PROVIDED.

PROVIDE DEDICATED CONDUIT STUB PER TELECOMMUNICATIONS DEVICEBACK BOX. DASY-CHAINING DEVICE BOXES IS PROHIBITED UNLESSSPECIFICALLY NOTED ON FLOOR PLANS.

CONDULET ("LB", ETC) FITTINGS ARE EXPRESSLY PROHIBITED FORTELECOMMUNICATIONS SYSTEM PATHWAYS.

PROVIDE A PULL STRING IN EMPTY/UNUSED DISTRIBUTION CONDUITS ANDCONDUITS SERVING TELECOMMUNICATIONS DEVICES SUITABLE FOR A 200LBPULL TENSION MINIMUM.

PROVIDE DEDICATED SUPPORT (E.G. CLIPS & WIRES) FOR CABLE SUPPORTHANGERS (OR SIMILAR PATHWAY COMPONENTS) INTENDED FORTELECOMMUNICATIONS CABLES A MINIMUM OF EVERY 4 FEET.

DO NOT SHARE SUPPORT WITH OTHER TRADES/SYSTEM, OTHER THANSECURITY AND /OR AUDIO VISUAL.

PROVIDE TELECOMMUNICATION CONDUITS FOR CABLING ROUTED THROUGHNON-ACCESSIBLE SPACE (E.G. "HARD LID CEILING), UON. SIZE CONDUITS TOMAINTAIN A FILL CAPACITY OF NO MORE THAN 40% (INCLUDING A 50% SPARECAPACITY).

INSTALL TELECOMMUNICATIONS DEVICES AT HEIGHTS NOTED ON SYMBOLSLIST OR DEVICE SCHEDULE, UNLESS OTHERWISE SHOWN ON THE DRAWINGSOR STATED IN SPECIFICATIONS. MOUNTING HEIGHT ARE FROM FINISHEDFLOOR TO THE CENTERLINE OF THE DEVICE. REFER TO ARCHITECTURALELEVATION DRAWINGS FOR ADDITIONAL INFORMATION OR EXACT LOCATIONSWALL/CELING/FLOOR MOUNTED DEVICES. VERIFY HEIGHT ARE THE SAME ASACCOMPANYING POWER RECEPTACLES AND NOTIFY OWNER, OR OWNER'SREPRESENTATIVE OF ANY DISCREPANCY.

PROVIDE A 24" MINIMUM SEPARATION BETWEEN "BACK-TO-BACK"TELECOMMUNICATIONS, POWER OR SIGNAL DEVICES IN FRAMED WALLS.

CABLES SHALL ONLY SUPPORTED BY APPARATUS MEANT TO DO SO. DO NOTSUPPORT CABLES ON PLUMBING PIPES, ELECTRICAL CONDUITS ORMECHANICAL DUCTWORK. WHEN J-HOOKS CAN NOT BE ATTACHED TO THEWALL OR STRUCTURAL MEMBERS, PROVIDE NEW 12 GAUGE CEILING HANGERWIRES TO SUPPORT J-HOOKS, INDEPENDENT OF T-BAR HANGER WIRES ANDLIGHTING HANGER WIRES. DO NOT TIE CABLES TO OTHER STRUCTURES NOTINTENDED FOR THIS SPECIFIC USE. DO NOT TIE CABLES TO CABLE TRAY.

GROUP AND DRESS EXPOSED TELECOMMUNICATIONS CABLES USINGREUSABLE 1 /2 INCH HOOK AND LOOP TYPE CABLE WRAPS. PLASTIC ZIP TIEWRAPS ARE NOT ALLOWED.

ALL CABLING SHALL HAVE A 15 FOOT SERVICE LOOP AT THE DEVICE LOCATIONEND IN AN ACCESSIBLE AREA UNLESS OTHERWISE SPECIFIED.

COMPONENTS NOT RELATED TO THE SUPPORT OF THE TELECOMMUNICATIONSROOM(S) FUNCTION (E.G. PIPING, DUCTWORK, PNEUMATIC TUBING, ETC.)SHALL NOT BE INSTALLED IN, PASS THROUGH, OR ENTER THETELECOMMUNICATIONS ROOM.

COMPONENTS CONTAINING LIQUID MUST BE LOCATED OUTSIDE THETELECOMMUNICATION ROOM(S) WHEN POSSIBLE. WHEN NOT POSSIBLE,TUBING CONTAINING LIQUIDS MUST BE ENCLOSED WITH A SPLASH GUARD ANDMUST HAVE DRAINAGE THE PREVENTS THE BUILDUPS OF LIQUID WITHIN THETELECOMMUNICATIONS ROOMS.

ALL OUTLETS AND DEVICES SHALL BE FLUSH WITH THE WALL, FLOOR FINISHEDOR CEILING FINISHED UNLESS OTHERWISE NOTED.

ALL HORIZONTAL PATHWAYS SHALL BE ROUTED SUCH THAT THE TOTALHORIZONTAL END TO END CABLE LENGTHS SHALL NOT EXCEED 295 FEET. IFTHIS REQUIREMENT CANNOT BE MET NOTIFY THE OWNER OR OWNER'SREPRESENTATIVE PRIOR TO INSTALLATION.

WHEN PENETRATING THE SLAB, CONDUITS/SLEEVES SHALL BE TERMINATED 3INCHES ABOVE THE FINISHED SLAB/FLOOR.

ALL CONDUIT, SLEEVES, FLOOR BOXES, CONDUIT STUBS, CABLE TRAY,RACEWAYS, BACK BOXES AND PULL BOXES SHALL BE PROVIDED UNDER THEELECTRICAL SECTION AND ARE SHOWN INTHE TELECOMMUNICATIONS DRAWINGS FOR COORDINATION PURPOSES.

ANY POWER RECEPTACLES, SWITCHES AND ETC. SHOWN ON THESE DRAWINGSARE FOR INFORMATION ONLY. PLEASE REFER TO ELECTRICAL DRAWINGS FORACTUAL QUANTITIES, TYPES AND LOCATIONS.

ALL CABLE PATHWAYS SHALL BE CONCEALED IN WALLS AND FLOOR SPACESWHERE POSSIBLE UNLESS OTHERWISE NOTED.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

33.

34.

35.

36.

37.

38.

39.

40.

41.

42.

43.

44.

45.

46.

47.

48.

49.

50.

51.

DETAIL REFERENCE:# = DETAIL NUMBER; TXXX = DRAWING NUMBER

CABLE TRAY

LADDER RACK

INFLOOR CABLING DUCT

SLEEVE / CONDUIT END

CONDUIT OR SLEEVE GOING UP

CONDUIT OR SLEEVE GOING DOWN

CONDUIT GOING THROUGH

IN SLAB CONDUIT

TELECOM SPACES/ROOM OUTLINE

TELECOM ZONE SERVED BY EITHER TR OR ER/TR# = TR (OR ER/TR) NUMBER

PULL BOX

CONSOLIDATION POINT

TELECOMMUNICATIONS GROUNDING BUSBAR

CEILING MTD WIRELESS ACCESS POINT

FURNITURE FEED POINTPROVIDE 1½" CONDUIT TO EACH FURNITURE FEEDPOINT FROM NEAREST ZONED CABLE TRAY OR TR,UON. COORDINATE LOCATIONS WITH THEARCHITECT.

PB

TXXX#

WAP

T-ZONE TR-#

CP

FF

DESCRIPTIONSYMBOL

DESCRIPTION

TGB: TELECOM GROUNDING BUS BAR (RISER)

TMGB: TELECOM MAIN GROUNDING BUS BAR

GROUND

GEC: GROUND ELECTRODE CONDUCTOR

,

J-HOOK PATH DESIGNATOR - SUPPORT CABLE EVERY FIVEFOOT MINIMUM. CABLES SHALL ONLY BE SUPPORTED BYAPPARATUS MEANT TO DO SO. DO NOT SUPPORT CABLES ONPLUMBING PIPE, ELECTRICAL CONDUIT, OR MECHANICALDUCTWORK. USE MANUFACTURER'S RECOMMENDATIONS FORCABLE FILL PER J-HOOK. WHEN J-HOOK CAN NOT BE ATTACHEDTO THE ATTIC WALL OR ATTIC STRUCTURAL MEMBERS,PROVIDE NEW 12 GAUGE CEILING HANGER WIRES TO SUPPORTJ-HOOK, INDEPENDENT OF T-BAR HANGER WIRES AND LIGHTINGHANGER WIRES.

SLEEVES - 2" EMT CONDUIT UNLESS OTHERWISE NOTED. EXTEND SLEEVES PAST SOFFITS &HARD LID CEILINGS. FIELD CONDITIONS MAY VARY. SEE PATHWAY AND SLEEVES DETAILS.

STUB LEADER INDICATES WITH DIRECTION TO STUB DATA OUTLET RISER. GENERALLYSTUB TOWARD J-HOOK PATH OR CABLE TRAY SYSTEM. FIELD CONDITIONS MAY VARY.

STUB LEADER ROUTING UNDERFLOOR INDICATES WITH DIRECTION TO STUB DATAOUTLET RISER CONDUIT. GENERALLY STUB TOWARD J-HOOK PATH OR CABLE TRAYSYSTEM. FIELD CONDITIONS MAY VARY.

UNDERGROUND TELECOMMUNICATION CONDUIT DUCT BANK

FLEXIBLE METALLIC CONDUIT

LINEAR RING PATHWAY

"EZ-PATH" TYPE FIRESTOP DEVICE, NOTES INDICATES SIZE AND QUANTITY.

POWER POLE WITH SEPARATE POWER AND TELECOMMUNICATIONS FEEDS.

J

TT

J

NC NURSE CALL

WALL MOUNTED OUTLET

FLOOR MOUNTED OUTLET

CEILING MOUNTED OUTLET

RACEWAY/FURNITURE MOUNTED OUTLET

ABBREVIATIONS

DESCRIPTIONSYMBOL

ABBREVIATIONS

CONDUITC, COND

AFF

CATEGORY

CATV

CAT

CCTV

EF

DWG

FM

FO

ELEC

CABLE TELEVISION

KVA

LAN

KW

MIN

LV

MTD

MM

N/A

NO, #

NIC

GRD

EC

PVC

PWR

NTS

ACCESS POINTAP

DRAWING

ENTRANCE FACILITY

FURNITURE MOUNTED

CLOSED CIRCUIT TELEVISION

ELECTRICAL CONTRACTOR

KILO WATT

MINIMUM

LOW VOLTAGE

MOUNTED

NUMBER

NOT APPLICABLE

MULTI-MODE FIBER OPTIC CABLES

LOCAL AREA NETWORK

NOT IN CONTRACT

POWER

TYPICAL

UNDERGROUND

TYP

UG

POLYVINYL CHLORIDE

VOICE

UON

UPS

UTP

V

VA

WAN

UNINTERRUPTIBLE POWER SUPPLY

UNLESS OTHERWISE NOTED

UNSHIELDED TWISTED PAIR

WIDE AREA NETWORK

WLAN

NOT TO SCALE

PA PUBLIC ADDRESS

PB PULL BOX

POE POWER OVER ETHERNET

VOICE OVER IPVOIP

DAS

EMI

EMT

GEC

HVAC

HZ

IDC

IDF

PR

WP

DISTRIBUTED ANTENNA SYSTEM

ELECTRICAL

ELECTROMAGNETIC INTERFERENCE

FIBER OPTICS

ELECTRICAL METALLIC TUBING

GROUNDING ELECTRODE CONDUCTOR

HEATING,VENTILATION, AND AIR CONDITIONING

HERTZ

INSULATION DISPLACEMENT CONNECTORS

KILO VOLT- AMPERE

INTERMEDIATE DISTRIBUTION FRAME

PAIR

VOLT-AMPERES

WIRELESS LOCAL AREA NETWORK

WATERPROOF OUTLET

ABOVE FINISHED FLOOR

D DATA

GROUND

BFC BELOW FINISHED CEILING

ICT INFORMATION AND COMMUNICATIONS TECHNOLOGY

AFC ABOVE FINISHED CEILING

BFF BELOW FINISHED FLOOR

WALL PHONEW

NOC NETWORK OPERATION CENTER

DC DATA CENTER

N NETWORK

AV

DSB

NCD

DCD

PRD

CEL

PAG

FIR

PMR(S)

LIU

PP

CB

AUDIO VISUAL

CONSOLIDATION BOX

CELLULAR SERVICES

FIRST RESPONDERS

PAGING SERVICES

NETWORK CORE DISTRIBUTION

PRIVATE MOBILE RADIO (SYSTEM)

PATCH PANEL

PRODUCTION

DATA CENTER DISTRIBUTION

LIGHT GUIDE INTERCONNECTION UNIT

DATA STORAGE BACKUP

ADA AMERICAN WITH DISABILITIES ACT

WAP WIRELESS ACCESS POINT

TZ TELECOMMUNICATION ZONE

AC ABOVE COUNTER

E ELEVATOR MACHINE ROOM

C CAMERA (NON SECURITY)

P PROJECTOR

FUT FUTURE

CBN COMMON BONDING NETWORK

HH HAND HOLE

GE GROUNDING EQUALIZER

PO POWER OUTLET (LOCATION FOR INFORMATION ONLY)

OR OUTSIDE RATED

FS FUSION SPLICE

MPOE MINIMUM POINT OF ENTRY

CATEGORY 6 4PR UTP CABLECAT6

ER EQUIPMENT ROOM

CSR CAMPUS SERVER ROOM

CB CONSOLIDATION BOX

CH CITY HALL

UNDER FINISHED FLOORUCF

SEC

RM

RMU

SECURITY

ROOM

SWITCH

SPECIFICATIONS

TBD

SINGLE MODE FIBER OPTIC CABLES

RACK MOUNT UNIT

SM

SW

SPEC

TBB

TGB

TMGB

TO BE DETERMINED

TELECOMMUNICATIONS BONDING BACKBONE

TELECOMMUNICATIONS GROUNDING BUSBAR

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TD

TB

TEST AND DEVELOPMENT

RK RACK/CABINET

TV TELEVISION

RSD ROOM SCHEDULING DISPLAY

STATIONSSTA

SER SECURITY EQUIPMENT ROOM

SECURITY OPERATION CENTERSOC

TR TELECOM ROOM

RACK MOUNTED 110 200PR TERMINATION BLOCK WITH JUMPING SLOTS

DESCRIPTIONSYMBOL

SEE ARCHITECTURAL ELEVATION FOR OUTLET MOUNTING HEIGHT.

FF = FURNITURE FEED FOR FUTURE MODULAR FURNITURE.

CR CARD READERCAMERAS TO BE WIRED BACK TO EXISTING TELECOM CLOSET T-1.4.

CLOSED CIRCUIT TELEVISION CAMERA (FIXED) - WALL MOUNTED.CAMERAS TO BE WIRED BACK TO EXISTING TELECOM CLOSET T-1.4.

CLOSED CIRCUIT TELEVISION CAMERA (PTZ) - WALL MOUNTED.CAMERAS TO BE WIRED BACK TO EXISTING TELECOM CLOSET T-1.4.

M MONITOR. CONTRACTOR TO COORDINATE FINAL LOCATION WITH OWNER.NC = NURSE CALL. NURSE CALL HEADWALL ASSEMBLY INCLUDES:

- (2) CAT-6 CABLES TO TELECOM ROOM.- CODE BLUE- MONITOR (2 CAT-6 UTP CABLE).

COORDINATE HEADWALL ASSEMBLY TYPE WITH ARCHITECTURAL DRAWINGS.

M = MONITOR. PROVIDE (2) CAT-6 CABLES TO TELECOM ROOM. REFER TOARCHITECTURAL ELEVATION DRAWINGS FOR MOUNTING HEIGHTS.

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAU

N

DAVID LANDMAN

E L E C T R I C A L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/2/

2016

3:5

2:58

PM SYMBOLS, GENERAL NOTES &

ABBREVIATIONS

TS0.1.0TY BMJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

Page 45: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

DN

PSNCPSNCPSNC

PS

PS NC

PS

PS

TV

PSNC

TV

TV TV

TV TV

PS NC

TV TV

FF

FF

M

PSPS NC NC

(E) ADMINELEGIBILITY

A1-100

(E) ADMINELEGIBILITY

A1-100

(E) ELECTE-1.4

(E)TEL/DATA

T-1.4

(E) AE MASSUPV

OFFICEA1-100A

(E) ER SDCA1-132

(E) ER SDCA1-130

(E) AEDECEDENT

AFFAIRSA1-106

(E) OFFICEA1-134

(E) PSYCHEVAL

A1-136

(E) ERRECEPTION

A1-120

(E) AE WORKROOMA1-119

(E) 3 EREXAM RM

A1-206

(E) 2 EREXAM RM

A1-204

(E) 1 EREXAM RM

A1-202

(E) MAINELEC.

SEV1.1

(E) TOILETA1-129

(E) TOILETA1-127

(E) STAFFLOUNGEA1-421

(E)PHYSICIAN

CALL ROOMA1-402

(E) LOCKERROOMA1-332

(E) SOCIALWORKA1-331

(E) NURSEMGR.

OFFICEA1-245

??

(E) EDOU 4A1-325D

(E) ERWAITINGA1-125

ALCOVEA1-C10A

(E)CORRIDOR

A1-C09

(E)CORRIDOR

A1-C13

(E)CORRIDOR

A1-335

(E)CORRIDOR

A1-C02

(E) EXAMA1-214

CORRIDORA1-340

(E) STAFFTOILETA1-334

(E) STAFFTOILETA1-332A(E) EXAM

A1-214

(E) ANTEROOMA1-208

(E) ASSTNURSE

MANAGERA1-323

(E) EDOU 1A1-325A(E) 8 ENT

ROOMA1-201

(E)CONFERENCE

A1-422

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E)CONFERENCE

A1-140

(E) EXAMA1-212

??

(E) ANTEROOMA1-208

(E) ANTEROOMA1-208

(E)CONFERENCE

A1-422

??

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)CONFERENCE

A1-422

(E)CONFERENCE

A1-422

H

F

G

E

12345678

I

J

J.2

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAU

N

DAVID LANDMAN

E L E C T R I C A L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/2/

2016

3:5

2:53

PM TELECOM DEMOLITION PLAN - LEVEL

1

TD2.1.1TY BMJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1. ALL TELECOM CABLING SHALL BE DEMOLISHED WITHINSEQUENCED AREA.

2. CONTRACTOR TO DEMOLISH OLD CABLE TRAY IN SEQUENCEAREAS. CABLING THAT ROUTE IN DEMOLISHED CABLE TRAY THAT IS

NOT PART OF SEQUENCED AREA SHALL BE SUSPENDED USING J-HOOKS.

3. VA WILL BE RESPONSIBLE CONTACTING SPRINT FOR REMOVALAND RELOCATION OF EXISTING SYSTEM PRIOR TO EDDEMOLITION.

4. GC TO SCHEDULE WORK TO MINIMUM INTERRUPTION OFHOSPITAL ACTIVITY. WORK TO BE SCHEDULED BETWEEN 8:00AM

TO 4:30PM. ANY WORK OUTSIDE OF REGULAR HOURS REQUIRES VAPRIOR APPROVAL.

1/8" = 1'-0"1 Phase 3 - Level 1 Telecom Plan Demo

Page 46: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

UP

UP

DN

PSNC

WAP

PSNCPSNC

PS

WAP

WAP

WAP

WAP

CR

CR

WAP

PS NC

CRCR

CRNCPS

CR

PS

PS

TV

PSNC

TV

TV TV

TV TV

PS NC

TV TVTV

M

MM

FF

FF

M

PSPS NC NC

CR

CR

CR

CR

CR

CR

CR

CR

CR

CR

(E) ADMINELEGIBILITY

A1-100

(E) AE MASSUPV

OFFICEA1-100A

(E)TEL/DATA

T-1.4

(E) ELECTE-1.4

(E) AE WORKROOMA1-119

(E)CORRIDOR

A1-C02

(E) ERWAITINGA1-125

(E) 1 EREXAM RM

A1-202

(E) 2 EREXAM RM

A1-204

(E) 3 EREXAM RM

A1-206

(E) NURSESTATIONA1-220

(E) ER MEDROOMA1-224

(E) SOILEDUTILITYA1-226

(E) 8 ENTROOMA1-201

(E) 11 EREXAM RM

A1-215

(E) 12 EREXAM RM

A1-221

(E) CLEANUTILITYA1-228

(E)CORRIDOR

A1-C03

(E) AEDECEDENT

AFFAIRSA1-106

(E) MAINELEC.

SEV1.1

(E) TOILETA1-322

(E) TOILETA1-127

(E) TOILETA1-129

(E) ERRECEPTION

A1-120

(E) ADMINELEGIBILITY

A1-100

(E) STAFFLOUNGEA1-421

(E)CORRIDOR

A1-C09(E)CONFERENCE

A1-422

(E) PSYCHEVAL

A1-136

(E) OFFICEA1-134

(E) ER SDCA1-132

(E) ER SDCA1-130

(E)CORRIDOR

A1-C10

(E) ERTRIAGEA1-207

(E) ERTRIAGEA1-209

(E) EDOU 4A1-325D

(E) EDOU 2A1-325B

(E) EDOU 1A1-325A

(E) ASSTNURSE

MANAGERA1-323

N 36' - 10 1/8"E 384' - 6 9/32"

(E)CONFERENCE

A1-140

(E)PHYSICIAN

CALL ROOMA1-402

(E) EDOU 3A1-325C

(E) STAFFLOUNGEA1-410

(E) HACA1-414

(E) WOMEN'SLOCKERA1-416

(E) MEN'SLOCKERA1-418

(E) TOILETA1-418A

(E) TOILETA1-416A

(E)PROGRAMSUPPORT

A1-401

(E) STAFFTOILETROOMA1-403

(E) NURSESTATIONA1-225

(E) EDOU 5A1-325E

(E) EDOU 6A1-325F

(E) EDOUMEDS

A1-325G

(E) EDOUSOILED UTIL

A1-328

(E) HACA1-324

(E) STAFFTOILETA1-332A

(E) LOCKERROOMA1-332

(E) EDOUSTORAGE

A1-330

(E) SOCIALWORKA1-331

(E) CHEIFOFFICEA1-235

(E) NURSEMGR.

OFFICEA1-245

(E) STAFFTOILETA1-334

(E) EXAMA1-214

(E) EXAMA1-216

(E) EXAMA1-218

(E) EXAMA1-212

(E) WORKROOMA1-210

(E) ANTEROOMA1-208

TRIAGEEXAMA1-203

(E)TEL/DATA

T-1.6

(E)ELECTRICAL

ROOME-1.6

CORRIDORA1-340

OPENOFFICE /

CONFERENCEA1-149

OFFICEA1-151

OFFICEA1-149

OFFICEA1-147

OFFICEA1-145OFFICE

A1-141OFFICEA1-143

OFFICEA1-144

OFFICEA1-146

COPYA1-142

M. STAFFTOILETA1-150

W. STAFFTOILETA1-152

CORRIDORA1-C002

CORRIDORA1-C003

WAITINGA1-140

RECEPTIONA1-140A

VESTIBULEA1-140D

H

F

G

E

12345678

I

J

J.2

PB

PB

12" WIDE CABLE TRAY IN CEILING

1

(1)DATA PORT FOR CABINET AND (1)DATAPORT FOR MONITOR

(1)DATA PORT FOR CABINET AND (1)DATAPORT FOR MONITOR

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAU

N

DAVID LANDMAN

E L E C T R I C A L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/19

/201

6 12

:28:

44 P

M

TELECOM PLAN - LEVEL 1

TP2.1.1TY BMJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

1/8" = 1'-0"1 Phase 3 - Level 1 Telecom Plan

1. NURSE CALL AND TELECOM OUTLETS IN TRIAGE ROOMS TO BEINTEGRATED IN HEAD-WALL AND COORDINATED WITH HEAD- WALLDESIGN. NEW NURSE CALL DEVICES TO BE COORDINATE WITHEXISTING SYSTEM (EZCARE).

3. GC TO SCHEDULE WORK TO MIMIMUM INTERRUPTION OF HOSPITALACTIVITY. WORK TO BE SCHEDULED BETWEEN 8:00AM TO 4:30PM.ANY WORK OUTSIDE OF REGULAR HOURS REQUIRES VA PRIORAPPROVAL.

1 CARD ACCESS SYSTEM AND SECURITY CAMERAS TO BEWIRED BACK TO EXISTING TELECOM CLOSET T-1.4

1 Addendum #1 09/01/152 Addendum #2 09/08/15

Page 47: VV ITEM: VA SUPPLIED AND INSTALLED VC ITEM: VA SUPPLIED ...halbertco.com/wp-content/uploads/2017/05/Plans-2.pdf · 2. furniture is n.i.c., u.o.n. 3. see architectural rcp for ceiling

BASEMENT LEVEL

FIRST FLOOR

T0.1

T1.5

PB

SG1.5 FCC

PB

SG1.6 T1.6 SG

1.6 T1.6

PB

SECOND FLOOR

THIRD FLOOR

T2.5 SG2.5

SG2.6 T2.6

FOURTH FLOOR

FIFTH FLOOR/ROOF

T3.5 SG3.5

SG3.6 T3.6

T4.5 SG4.5

SG4.6 T4.6

(4)x4" CONDUIT (E)

(8)x4" CONDUIT (E) (4)x4" CONDUIT (E)(3)x2" CONDUIT (E)

REGISTERE

DPRO

FESSIONAL

ENGINE

STATE OF CALIFORNI

A

E17532 ERSHAU

N

DAVID LANDMAN

E L E C T R I C A L

Cwww.arup.comTel (415) 957 9445 Fax (415) 957 9096San Francisco, CA 94105560 Mission Street, Suite 700Arup North America Ltd.

GRAPHIC SCALE:

0'

1/16" = 1'-0"

16' 16' 32'8'

GRAPHIC SCALE:

0'

1/8" = 1'-0"

8' 8' 16'

GRAPHIC SCALE:

4' 0' 4' 8'

1/4" = 1'-0"

3801 Miranda Ave., Palo Alto CA

VA PALO ALTO HEALTH CARE SYSTEM

CONSTRUCTION DOCUMENTSFULLY SPRINKLERED

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office ofConstructionand FacilitiesManagement

Seals and Signatures

one e

ighth

inch =

one f

oot

168

40

B

A

C

D

E

F

three

inch

es =

one f

oot

6"1

06"

one a

nd on

e half

inch

es =

one f

oot

one i

nch =

one f

oot

20

6"6"

02

three

quart

ers i

nch =

one f

oot

one h

alf in

ch =

one f

oot

40

three

eigh

ths in

ch =

one f

oot

40

04

8on

e qua

rter in

ch =

one f

oot

VA FORM 08-6231

1 2 3 5 6 87 9

F

E

D

C

B

A

97 8654321

595 Market Street, 12th Floor San Francisco, CA 94105T 415.243.4170 F 415.243.4176

www.cannondesign.com

SHEET NOTES

KEYNOTES

Associate Architect:

TRUE NORTH

PROJ NORTH

Department ofVeterans Affairs

PRIN

TED

ON:

1629 Telegraph Avenue, Suite 500 Oakland, CA 94612Phone: 415-777-3737 Fax: 415-777-3476

www.dpsf.com9/2/

2016

3:5

2:56

PM TELECOM RISER DIAGRAM

TP5.2.1TY BMJune 20, 2016

100

640-369

EXPAND EMERGENCY DEPT. FACILITIES

12" = 1'-0"1 Riser Diagram - Existing

1. CONTRACTOR TO PROVIDE 12 STRAND SINGLEMODE FIBER AND25-PAIR COPPER RISER CABLING TO TELECOM ROOMS T1.6, T2.6, T3.6AND T4.6 FROM THE MPOE IN THE BASEMENT. FIBER SHALL TERMINATEIN A FIBER PANEL MOUNTED IN RACK ON LC CONNECTORS. 25-PAIRCOPPER FEEDER SHALL TERMINATED ON 110 BLOCKS MOUNTED ONWALL. EXISTING FIBER AND COPPER FEEDERS WILL BE DEMOED AFTERNEW TELECOM ROOM IS FULLY FUNCTIONAL AND CAPABLE TO

SUPPORT CUTOVER.

2. CONDUIT CONNECTIONS FROM THE BASEMENT PULL BOX TO THENEW TELECOM ROOM IS REQUIRED. EXISTING CONNECTION IN T1.6 ISLOCATED IN THE SLAB THEREFORE CAN NOT BE REUSED ANS SHALL BEABANDONED.

3. ELEVATOR MAYBE CONNECTED FROM EXISTING TELECOMROOM.CONTRACTOR SHALL PROVIDE CONTINUOUS CONNECTION TO THEELEVATOR DURING PROJECT.

4. GC TO SCHEDULE WORK TO MINIMUM INTERRUPTION OF HOSPITALACTIVITY. WORK TO BE SCHEDULED BETWEEN 8:00AM TO 4:30PM. ANYWORK OUTSIDE OF REGULAR HOURS REQUIRES VA PRIOR APPROVAL.

5. CONTRACTOR TO COORDINATE COMMUNICATION CUTOVER WITHTHE VA BEFORE PERFORMING WORK.

6. EXISTING SEISMIC METERING (RED CABLE) IN EXISTING TELECOMROOM WILL BE COORDINATED WITH VA BEFORE DEMOLISION OFTHIS ROOM.