VACAVILLE CLASSROOM BUILDING (ANNEX ... Classroom Bldg...A3.00 EXTERIOR ELEVATIONS A3.01-ALTROOF...

83
DATE: DESCRIPTION: NO: DATE: PROJECT NO: PERMIT APPLICATION NO.: SCALE: ISSUE/REVISION: KEY PLAN: CA ARCHITECTS 475 Gate Five Road, Suite 107 Sausalito, CA 94965 T 415.331.7655 F 415.331.7656 STAMP OWNER: ARCHITECT: SHEET LEGEND: PROJECT: CONSULTANT TEAM: Solano Community College District 2000 North Village Parkway Vacaville, CA 95688 Vacaville Classroom Building (Annex) Renovation Project 04/25/2017 ISSUE FOR DD 100% 06/06/2017 ISSUE FOR CD 50% 06/30/2017 ISSUE FOR CD 60% 07/20/2017 ISSUE FOR CD 100% 10/18/2017 DSA BACKCHECK A0.00 COVER SHEET INDEX VACAVILLE CLASSROOM BUILDING (ANNEX) RENOVATION PROJECT SOLANO COMMUNITY COLLEGE DISTRICT 2000 NORTH VILLAGE PARKWAY, VACAVILLE, CA 95688 PROJECT NO: APPLICATION NO: SUBMITTAL GENERAL DRAWINGS A0.00 COVER SHEET, INDEX ARCHITECTURE DRAWINGS A0.01 LOCAL FIRE AUTHORITY PLAN A0.10 ACCESS PLAN A0.20 ACCESSIBILITY - ADA DETAILS A0.30 EGRESS PLAN D1.01 EXISTING/DEMO ROOF PLAN D1.01-ALT EXISTING/DEMO ROOF PLAN D2.00 EXISTING/DEMO FLOOR PLAN D2.01 EXISTING TOILET ROOMS & DRINKING FOUNTAINS D3.00 EXISTING/DEMO ELEVATIONS D5.00 DEMO/EXITING INTERIOR ELEVATIONS D5.01 DEMO/EXISTING INTERIOR RESTROOM ELEVATIONS D6.00 EXISTING/DEMO RCP A1.00 SITE PLAN A1.01 ROOF PLAN A1.01-ALT ROOF PLAN A2.00 FLOOR PLAN A2.01 TOILET ROOMS & DRINKING FOUNTAINS A3.00 EXTERIOR ELEVATIONS A3.01-ALT ROOF PARAPET ELEVATIONS A5.01 INTERIOR ELEVATIONS A6.00 REFLECTED CEILING PLAN A8.00 EXTERIOR DETAILS A8.01 EXTERIOR DETAILS A8.02 EXTERIOR DETAILS A8.03 EXTERIOR DETAILS A8.04 EXTERIOR DETAILS A9.00 INTERIOR DETAILS A9.01 INTERIOR DETAILS A9.02 INTERIOR DETAILS A9.03 INTERIOR DETAILS GENERAL NOTE: TOPOGRAPHIC: INFORMATION WAS PROVIDED BY SCCD TO CA ARCHITECTS FOR USE AS EXISTING CONDITIONS FOR THIS PROJECT 1. CONTRACT DOCUMENTS ARE COMPLEMENTARY, THE CONTRACTOR SHALL, BEFORE STARTING EACH PORTION OF THE WORK, CAREFULLY STUDY AND COMPARE THE VARIOUS CONTRACT DOCUMENTS RELATIVE TO THAT PORTION OF THE WORK, AS WELL AS THE INFORMATION FURNISHED BY THE OWNER, SHALL TAKE FIELD MEASUREMENTS OF ANY EXISTING CONDITIONS RELATED TO THAT PORTION OF THE WORK, AND SHALL OBSERVE ANY CONDITIONS AT THE SITE AFFECTING IT. THESE OBLIGATIONS ARE FOR THE PURPOSE OF FACILITATING COORDINATION AND CONSTRUCTION BY THE CONTRACTOR AND ARE NOT FOR THE PURPOSE OF DISCOVERING ERRORS, OMISSIONS, OR INCONSISTENCIES IN THE &2175$&7 '2&80(176 +2:(9(5 THE CONTRACTOR SHALL PROMPTLY REPORT TO THE ARCHITECT ANY ERRORS, INCONSISTENCIES OR OMISSIONS DISCOVERED BY OR MADE KNOWN TO THE CONTRACTOR AS A REQUEST FOR INFORMATION IN SUCH FORM AS THE ARCHITECT MAY REQUIRE. 2. DEMO, CUTTING AND PATCHING SHALL BE PERFORMED AS NECESSARY FOR THE PERFORMANCE AND INSTALLATION OF WORK SHOWN AND SHALL MEET THE STANDARD OF CARE FOR EACH OF THE DISCIPLINES REQUIRED TO PERFORM THE WORK. 3. UNOBSTRUCTED ACCESS TO EXISTING EXITS AND ANY EMERGENCY LIGHTING SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. ALL EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES SHALL BE MAINTAINED FOR THE DURATION OF THE WORK OF THE PROJECT. 4. ALL WORK PERFORMED UNDER THESE DOCUMENTS SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES AND REQUIREMENTS. ALL NEW WORK SHALL NOT DIMINISH ANY EXISTING CONDITIONS WITH RESPECT TO THEIR ADHERENCE TO APPLICABLE CODES AND REQUIREMENTS (TYP.). THIS SHALL INCLUDE INSPECTIONS AND SUPERVISION OF WORK BY A LICENSED INSPECTOR OF RECORD (IOR) IN ACCORDANCE WITH DSA. 5. THESE DOCUMENTS ARE TO REFLECT GENERAL INTENT OF THE ARCHITECTURAL SCOPE OF WORK. THE INFORMATION SHOWN IN THESE DOCUMENT SHOW PURPOSE AND INTENT AND ARE NOT COMPLETE IN EVERY DETAIL. THE CONTRACTOR SHALL COMPLY WITH THEIR INTENT AND MEANING, TAKEN AS A WHOLE, AND SHALL NOT AVAIL ITSELF OF ANY MANIFEST ERROR, OMISSION, AND DISCREPANCY OF AMBIGUITY WHICH APPEAR IN THE DOCUMENTS. 6. CONTRACTOR SHALL ENGAGE USA TO VERIFY AND LOCATE ANY (E) UTILITIES WITHIN AREA OF SCOPE OF WORK PRIOR TO COMMENCENT OF DEMO WORK. CIVIL DRAWINGS C1 SITE PLAN C2 ACCESSIBLE DETAILS C3 ENLARGED PLANS C4 ENLARGED PLANS C5 PARTIAL SURVEY TBD X X X X 07/20/2017 11/30/2017 C-23410 Joshua Cohn ³'(6,*1 352)(66,21$/ ,1 *(1(5$/ 5(63216,%/( &+$5*( STATEMENT: THE POT IDENTIFIED IN THESE CONSTRUCTION DOCUMENTS IS COMPLIANT WITH THE CURRENT APPLICABLE CALIFORNIA BUILDING CODE ACCESSIBILITY PROVISIONS FOR PATH OF TRAVEL REQUIREMENTS FOR ALTERATIONS, ADDITIONS AND STRUCTURAL REPAIRS. AS PART OF THE DESIGN OF THIS PROJECT, THE POT WAS EXAMINED AND ANY ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WERE DETERMINED TO BE NONCOMPLIANT 1) HAVE BEEN IDENTIFIED AND 2) THE CORRECTIVE WORK NECESSARY TO BRING THEM INTO COMPLIANCE HAS BEEN ,1&/8'(' :,7+,1 7+( 6&23( 2) 7+,6 352-(&7¶6 :25. 7+528*+ DETAILS, DRAWINGS AND SPECIFICATIONS INCORPORATED INTO THESE CONSTRUCTION DOCUMENTS. ANY NONCOMPLIANT ELEMENTS, COMPONENTS OR PORTIONS OF THE POT THAT WILL NOT BE CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD LIMITATIONS OR A FINDING OF UNREASONABLE HARDSHIP ARE SO INDICATED IN THESE CONSTRUCTION DOCUMENTS. DURING CONSTRUCTION, IF POT ITEMS WITHIN THE SCOPE OF THE PROJECT REPRESENTED AS CODE COMPLIANT ARE FOUND TO BE NONCONFORMING BEYOND REASONABLE CONSTRUCTION TOLERANCES, THEY SHALL BE BROUGHT INTO COMPLIANCE WITH THE CBC AS A PART OF THIS PROJECT BY MEANS OF A CONSTRUCTION &+$1*( '2&80(17´ SEE C1, C2, C3, C4 FOR PATH OF TRAVEL REQUIREMENTS. PROJECT WILL REQUIRE INSPECTOR (IOR) CLASS 1 CGS DISTRICT NAME LUCKY LOFTON EXECUTIVE BOND MANAGER SOLANO COMMUNITY COLLEGE DISTRICT ADDRESS 4000 SUISUN VALLEY ROAD ADDRESS FAIRFIELD CA 94534 PHONE 707-863-7855 PHONE 707-646-7703 PM NAME KITCHELL CEM - PAM KINZIE ADDRESS 360 CAMPUS LANE, SUITE 203 ADDRESS FAIRFIELD, CA 94534 PHONE 707-864-7189 EMAIL [email protected] ARCHITECT NAME CA ARCHITECT ADDRESS 475 GATE FIVE ROAD, SUITE 107 ADDRESS SAUSALITO, CA 94965 PHONE 415-331-7655 PHONE 415-609-7177 EMAIL [email protected] CIVIL NAME FOULK CIVIL ENGINEERING, Inc. ADDRESS 4777 MANGLES BOULEVARD ADDRESS FAIRFIELD, CA 94534 PHONE 707-864-0784 PHONE 707-864-0793 EMAIL [email protected] ELECTRICAL NAME C&N ENGINEERS, INC. ADDRESS 319 SUTTER STREET, SUITE 202 ADDRESS SAN FRNACISCO, CA 94108 PHONE 415-982-1828 FAX 415-772-8005 EMAIL [email protected] MP DRAWINGS M0.1 MECHANICAL NOTES, SYMBOL, LEGEND AND SCHEDULE M0.2 MECHANICAL TITLE 24 M0.3 HVAC LOAD CALCULATION M2.1 MECHANICAL DEMO FLOOR PLAN M2.1D MECHANICAL FLOOR PLAN DEMO M2.2 MECHANICAL ROOF PLAN M2.2D MECHANICAL DEMO ROOF PLAN M4.1 MECHANICAL SCHEDULE M6.1 MECHANICAL DETAILS M6.2 MECHANICAL DETAILS P0.1 PLUMBING NOTES, SYMBOL, LEGEND AND SCHEDULE P2.1 PLUMBING DEMO FLOOR PLAN P2.1D PLUMBING FLOOR PLAN DEMO P2.2D PLUMBING DEMO ROOF PLAN P4.1 ENLARGED PLUMBING FLOOR PLAN P6.1 PLUMBING DETAILS MEP NAME EXCEL ENGINEERS ADDRESS 825 ORANGE AVE ADDRESS SUNNYVALE, CA 94087 PHONE 408-230-9164 FAX 408-749-9989 EMAIL [email protected] STRUCTURAL NAME TENNEBAUM-MANHEIM ENGINEERS ADDRESS 414 MASON STREET, SUITE 605 ADDRESS SAN FRNACISCO, CA 94102 PHONE 415-772-9891 EMAIL [email protected] SCOPE OF WORK IS BASED ON DSA APPROVED 02-REH-10012 (9/15/2015). REH SHALL FORM A PART OF THE REVIEW DOCUMENTS AND HAS BEEN UPDATED TO INCLUDE ADDITIONAL TESTING DATA. THE EXISTING BUILDING IS A ONE-STORY, 16,400 SF BUILDING AND 5,112 SF EXTERIOR COVERED WALKWAY FOR A TOTAL OF: 21,512SF, FULLY SPRINKLED. SCOPE OF WORK SHALL BE FOR THE FOR THE REHABILITATION OF THE (E) BUILDING FOR COMPLIANCE TO THE 2016 CALIFORNIA BUILDING STANDARDS CODE (CBC) AS OUTLINED IN THE REH. STRUCTURAL DRAWINGS S0.1 GENERAL NOTES S0.2 GENERAL NOTES & ABBREVIATIONS S1.0 TYPICAL DETAILS S2.1 1ST FLOOR AND FOUNDATION PLAN S2.2 ROOF FRAMING PLAN S3.1 WALL ELEVATIONS S3.2 WALL ELEVATIONS S4.1 SECTIONS & DETAILS S4.2 SECTIONS & DETAILS S4.3 SECTIONS & DETAILS EXISTING BUILDING TYPE: III-B PROPOSED BUILDING TYPE: V-B (SEE A0.03 EGRESS PLAN) EXISTING OCCUPANCY: B/A-3 PROPOSED OCCUPANCY: B/A-3 (SEE A0.03) EXISTING BUILDING IS CURRENTLY UNOCCUPIED AND SHALL REMAIN UNOCCUPIED UNTIL BUILDING IS CERTIFIED BY DSA. ELECTRICAL DRAWINGS E0.10 GENERAL NOTES, ABBREV. & LEGENDS E0.11 ELECTRICAL SPECIFICATIONS E0.30 ENERGY COMPLIANCE FORMS E0.40 ENERGY COMPLIANCE FORMS E0.50 ENERGY COMPLIANCE FORMS E0.60 ENERGY COMPLIANCE FORMS E1.00 POWER PLAN E1.01 POWER PLAN AT ROOF E2.00 LIGHTING PLAN E2.10 WIRING DIAGRAMS FIRE ALARM FA1.01 FIRE ALARM LEGEND, NOTES, & MOUNTING HEIGHT DETAILS FA2.00 FIRE ALARM FLOOR PLAN FA3.00 FIRE ALARM DEVICE DETAILS FA4.00 FIRE ALARM CALCULATIONS AND RISER DIAGRAM FA 5.00 FIRE STOP DETAILS FIRE ALARM NAME HCI SYSTEMS INC. ADDRESS 1419 N. MARKET BLVD. ADDRESS SACRAMENTO, CA 95834 PHONE 916-419-6900 EMAIL [email protected] FIRE PROTECTION NAME ZARI CONSULTING GROUP, INC. ADDRESS 755 BAYWOOD DRIVE, 2ND FLOOR ADDRESS PETALUMA, CA 95834 PHONE 925-381-2322 EMAIL [email protected] FIRE PROTECTION FP1-0 FIRE PROTECTION SYSTEM COVER SHEET FP1-1 FIRE PROTECTION SYSTEM SITE PLAN FP 2-0 FIRE PROTECTION SYSTEM SITE PLAN FP-3-0 FIRE PROTECTION SYSTEM SITE PLAN ABV. - Above ADD. - Addition ADJ. - Adjust A.F.F. - Above Finished Floor ALT. - Alternate APP'D. - Approved ARCH. - Architect, ASPH. - Asphalt BLDG. - Building BM. - Beam B.O. - Bottom of B.U.R./BUR - Built up Roof C.B. - Catch Basin C.D. - Construction document C.L. - Center Line CL. - Closet CLG. - Ceiling C.O. - Clean Out COL. - Column CONT. - Continuous CONTR. - Contractor CONC. - Concrete DBL. - Double DEMO. - Demolition DIA. - Diameter DIM. - Dimension DN. - Down DR. - Door EA. - Each E.F. - Exhaust fan ELEV. - Elevation ELECT. - Electric, electrical EQ. - Equal (E) - Existing EXT. - Exterior F.A. - Fire alarm F.D. - Floor drain F.E. - Fire extinguisher FIN. - Finish FLR. - Floor GA. - Gauge GALV. - Galvanized G.C. - General Contractor G.F.C.I. - Ground Fault Circuit Interrupt G.F.I. - Ground Fault Interrupt GL. - Glass GWB Gypsum Wall Board H.B. - Hose bib HDW. - Hardware HGT. - Height H.V.A.C. - Heating, Venting and Air Conditioning INV. - Invert INSUL. - Insulation INT. - Interior JCT. - Junction JST. - Joist LIN. - Linear LT. - Light LTG. - Lighting MTL. - Metal MAX. - Maximum MECH. - Mechanical MFR - Manufacturer's MIN. - Minimum MTL. - Metal (steel) (N) - New N.T.S. - Not to scale O.C. - On center OPNG. - Opening PTD. - Painted PART. - Partition PL - Property Line PLAM - Plastic laminate PLYWD. - Plywood P.S.F. - Pounds per square foot P.S.I. - Pounds per square inch RAD. - Radius R.D. - Roof drain R.O. - Rough Opening REF. - Reference REINF. - Reinforced RET. - Return REV. - Revision RM. - Room RMV. - Remove SED - See Electrical Docs SHT'G. - Sheathing SIM. - Similar SMD - See Mechanical Docs SPD - See Plumbing Docs SPECS. - Specifications SSD - See Structural Docs ST. - Square feet SI. - Square inches STD. - Standard STL. - Steel S.Y. - Square yard SYS. - System T.O. - Top of THR. - Threaded TYP. - Typical UNF. - Unfinished V.B. - Vapor barrier V.I.F. - Verify in field VCT. - Vinyl composition tile WP. - Weatherproof WD. - Wood FLOOD MAP INFO: FEMA MAP #06095C0164E AC_______ FLS _____ SS ____ DATE: ________________________ IDENTIFICATION STAMP DIVISION OF THE STATE ARCHITECT JCC GBC GBC PVL FILE: 48-C1 02-116082 10/31/2017

Transcript of VACAVILLE CLASSROOM BUILDING (ANNEX ... Classroom Bldg...A3.00 EXTERIOR ELEVATIONS A3.01-ALTROOF...

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A0.00

    COVER SHEETINDEX

    VACAVILLE CLASSROOM BUILDING (ANNEX) RENOVATION PROJECTSOLANO COMMUNITY COLLEGE DISTRICT

    2000 NORTH VILLAGE PARKWAY, VACAVILLE, CA 95688PROJECT NO:

    APPLICATION NO:SUBMITTAL

    GENERAL DRAWINGS

    A0.00 COVER SHEET, INDEX

    ARCHITECTURE DRAWINGS

    A0.01 LOCAL FIRE AUTHORITY PLAN

    A0.10 ACCESS PLAN

    A0.20 ACCESSIBILITY - ADA DETAILS

    A0.30 EGRESS PLAN

    D1.01 EXISTING/DEMO ROOF PLAN

    D1.01-ALT EXISTING/DEMO ROOF PLAN

    D2.00 EXISTING/DEMO FLOOR PLAN

    D2.01 EXISTING TOILET ROOMS & DRINKING FOUNTAINS

    D3.00 EXISTING/DEMO ELEVATIONS

    D5.00 DEMO/EXITING INTERIOR ELEVATIONS

    D5.01 DEMO/EXISTING INTERIOR RESTROOM ELEVATIONS

    D6.00 EXISTING/DEMO RCP

    A1.00 SITE PLAN

    A1.01 ROOF PLAN

    A1.01-ALT ROOF PLAN

    A2.00 FLOOR PLAN

    A2.01 TOILET ROOMS & DRINKING FOUNTAINS

    A3.00 EXTERIOR ELEVATIONS

    A3.01-ALT ROOF PARAPET ELEVATIONS

    A5.01 INTERIOR ELEVATIONS

    A6.00 REFLECTED CEILING PLAN

    A8.00 EXTERIOR DETAILS

    A8.01 EXTERIOR DETAILS

    A8.02 EXTERIOR DETAILS

    A8.03 EXTERIOR DETAILS

    A8.04 EXTERIOR DETAILS

    A9.00 INTERIOR DETAILS

    A9.01 INTERIOR DETAILS

    A9.02 INTERIOR DETAILS

    A9.03 INTERIOR DETAILS

    GENERAL NOTE:

    TOPOGRAPHIC: INFORMATION WAS PROVIDED BY SCCD TO CA

    ARCHITECTS FOR USE AS EXISTING CONDITIONS FOR THIS PROJECT

    1. CONTRACT DOCUMENTS ARE COMPLEMENTARY, THE CONTRACTOR

    SHALL, BEFORE STARTING EACH PORTION OF THE WORK, CAREFULLY

    STUDY AND COMPARE THE VARIOUS CONTRACT DOCUMENTS RELATIVE TO

    THAT PORTION OF THE WORK, AS WELL AS THE INFORMATION FURNISHED

    BY THE OWNER, SHALL TAKE FIELD MEASUREMENTS OF ANY EXISTING

    CONDITIONS RELATED TO THAT PORTION OF THE WORK, AND SHALL

    OBSERVE ANY CONDITIONS AT THE SITE AFFECTING IT. THESE OBLIGATIONS

    ARE FOR THE PURPOSE OF FACILITATING COORDINATION AND

    CONSTRUCTION BY THE CONTRACTOR AND ARE NOT FOR THE PURPOSE OF

    DISCOVERING ERRORS, OMISSIONS, OR INCONSISTENCIES IN THE

    THE CONTRACTOR SHALL PROMPTLY

    REPORT TO THE ARCHITECT ANY ERRORS, INCONSISTENCIES OR

    OMISSIONS DISCOVERED BY OR MADE KNOWN TO THE CONTRACTOR AS A

    REQUEST FOR INFORMATION IN SUCH FORM AS THE ARCHITECT MAY

    REQUIRE.

    2. DEMO, CUTTING AND PATCHING SHALL BE PERFORMED AS NECESSARY

    FOR THE PERFORMANCE AND INSTALLATION OF WORK SHOWN AND SHALL

    MEET THE STANDARD OF CARE FOR EACH OF THE DISCIPLINES REQUIRED

    TO PERFORM THE WORK.

    3. UNOBSTRUCTED ACCESS TO EXISTING EXITS AND ANY EMERGENCY

    LIGHTING SHALL BE MAINTAINED THROUGHOUT CONSTRUCTION. ALL EXITS,

    EXIT LIGHTING, FIRE PROTECTIVE DEVICES SHALL BE MAINTAINED FOR THE

    DURATION OF THE WORK OF THE PROJECT.

    4. ALL WORK PERFORMED UNDER THESE DOCUMENTS SHALL BE IN

    ACCORDANCE WITH ALL APPLICABLE CODES AND REQUIREMENTS. ALL NEW

    WORK SHALL NOT DIMINISH ANY EXISTING CONDITIONS WITH RESPECT TO

    THEIR ADHERENCE TO APPLICABLE CODES AND REQUIREMENTS (TYP.).

    THIS SHALL INCLUDE INSPECTIONS AND SUPERVISION OF WORK BY A

    LICENSED INSPECTOR OF RECORD (IOR) IN ACCORDANCE WITH DSA.

    5. THESE DOCUMENTS ARE TO REFLECT GENERAL INTENT OF THE

    ARCHITECTURAL SCOPE OF WORK. THE INFORMATION SHOWN IN THESE

    DOCUMENT SHOW PURPOSE AND INTENT AND ARE NOT COMPLETE IN

    EVERY DETAIL. THE CONTRACTOR SHALL COMPLY WITH THEIR INTENT AND

    MEANING, TAKEN AS A WHOLE, AND SHALL NOT AVAIL ITSELF OF ANY

    MANIFEST ERROR, OMISSION, AND DISCREPANCY OF AMBIGUITY WHICH

    APPEAR IN THE DOCUMENTS.

    6. CONTRACTOR SHALL ENGAGE USA TO VERIFY AND LOCATE ANY (E)

    UTILITIES WITHIN AREA OF SCOPE OF WORK PRIOR TO COMMENCENT OF

    DEMO WORK.

    CIVIL DRAWINGS

    C1 SITE PLAN

    C2 ACCESSIBLE DETAILS

    C3 ENLARGED PLANS

    C4 ENLARGED PLANS

    C5 PARTIAL SURVEY

    TBD

    X

    X

    X

    X

    07/20/2017

    11/30/2017C-23410

    Joshua Cohn

    STATEMENT: THE POT IDENTIFIED IN THESE CONSTRUCTION

    DOCUMENTS IS COMPLIANT WITH THE CURRENT APPLICABLE

    CALIFORNIA BUILDING CODE ACCESSIBILITY PROVISIONS FOR PATH OF

    TRAVEL REQUIREMENTS FOR ALTERATIONS, ADDITIONS AND

    STRUCTURAL REPAIRS. AS PART OF THE DESIGN OF THIS PROJECT,

    THE POT WAS EXAMINED AND ANY ELEMENTS, COMPONENTS OR

    PORTIONS OF THE POT THAT WERE DETERMINED TO BE

    NONCOMPLIANT 1) HAVE BEEN IDENTIFIED AND 2) THE CORRECTIVE

    WORK NECESSARY TO BRING THEM INTO COMPLIANCE HAS BEEN

    DETAILS, DRAWINGS AND SPECIFICATIONS INCORPORATED INTO

    THESE CONSTRUCTION DOCUMENTS. ANY NONCOMPLIANT ELEMENTS,

    COMPONENTS OR PORTIONS OF THE POT THAT WILL NOT BE

    CORRECTED BY THIS PROJECT BASED ON VALUATION THRESHOLD

    LIMITATIONS OR A FINDING OF UNREASONABLE HARDSHIP ARE SO

    INDICATED IN THESE CONSTRUCTION DOCUMENTS. DURING

    CONSTRUCTION, IF POT ITEMS WITHIN THE SCOPE OF THE PROJECT

    REPRESENTED AS CODE COMPLIANT ARE FOUND TO BE

    NONCONFORMING BEYOND REASONABLE CONSTRUCTION

    TOLERANCES, THEY SHALL BE BROUGHT INTO COMPLIANCE WITH THE

    CBC AS A PART OF THIS PROJECT BY MEANS OF A CONSTRUCTION

    SEE C1, C2, C3, C4 FOR PATH OF TRAVEL REQUIREMENTS.

    PROJECT WILL REQUIRE INSPECTOR (IOR) CLASS 1

    CGS

    DISTRICT NAME LUCKY LOFTON

    EXECUTIVE BOND MANAGER

    SOLANO COMMUNITY COLLEGE DISTRICT

    ADDRESS 4000 SUISUN VALLEY ROAD

    ADDRESS FAIRFIELD CA 94534

    PHONE 707-863-7855

    PHONE 707-646-7703

    PM NAME KITCHELL CEM - PAM KINZIE

    ADDRESS 360 CAMPUS LANE, SUITE 203

    ADDRESS FAIRFIELD, CA 94534

    PHONE 707-864-7189

    EMAIL [email protected]

    ARCHITECT NAME CA ARCHITECT

    ADDRESS 475 GATE FIVE ROAD, SUITE 107

    ADDRESS SAUSALITO, CA 94965

    PHONE 415-331-7655

    PHONE 415-609-7177

    EMAIL [email protected]

    CIVIL NAME FOULK CIVIL ENGINEERING, Inc.

    ADDRESS 4777 MANGLES BOULEVARD

    ADDRESS FAIRFIELD, CA 94534

    PHONE 707-864-0784

    PHONE 707-864-0793

    EMAIL [email protected]

    ELECTRICAL NAME C&N ENGINEERS, INC.

    ADDRESS 319 SUTTER STREET, SUITE 202

    ADDRESS SAN FRNACISCO, CA 94108

    PHONE 415-982-1828

    FAX 415-772-8005

    EMAIL [email protected]

    MP DRAWINGS

    M0.1 MECHANICAL NOTES, SYMBOL, LEGEND AND SCHEDULE

    M0.2 MECHANICAL TITLE 24

    M0.3 HVAC LOAD CALCULATION

    M2.1 MECHANICAL DEMO FLOOR PLAN

    M2.1D MECHANICAL FLOOR PLAN DEMO

    M2.2 MECHANICAL ROOF PLAN

    M2.2D MECHANICAL DEMO ROOF PLAN

    M4.1 MECHANICAL SCHEDULE

    M6.1 MECHANICAL DETAILS

    M6.2 MECHANICAL DETAILS

    P0.1 PLUMBING NOTES, SYMBOL, LEGEND AND SCHEDULE

    P2.1 PLUMBING DEMO FLOOR PLAN

    P2.1D PLUMBING FLOOR PLAN DEMO

    P2.2D PLUMBING DEMO ROOF PLAN

    P4.1 ENLARGED PLUMBING FLOOR PLAN

    P6.1 PLUMBING DETAILS

    MEP NAME EXCEL ENGINEERS

    ADDRESS 825 ORANGE AVE

    ADDRESS SUNNYVALE, CA 94087

    PHONE 408-230-9164

    FAX 408-749-9989

    EMAIL [email protected]

    STRUCTURAL NAME TENNEBAUM-MANHEIM ENGINEERS

    ADDRESS 414 MASON STREET, SUITE 605

    ADDRESS SAN FRNACISCO, CA 94102

    PHONE 415-772-9891

    EMAIL [email protected]

    SCOPE OF WORK IS BASED ON DSA APPROVED 02-REH-10012

    (9/15/2015). REH SHALL FORM A PART OF THE REVIEW DOCUMENTS

    AND HAS BEEN UPDATED TO INCLUDE ADDITIONAL TESTING DATA.

    THE EXISTING BUILDING IS A ONE-STORY, 16,400 SF BUILDING AND

    5,112 SF EXTERIOR COVERED WALKWAY FOR A TOTAL OF: 21,512SF,

    FULLY SPRINKLED. SCOPE OF WORK SHALL BE FOR THE FOR THE

    REHABILITATION OF THE (E) BUILDING FOR COMPLIANCE TO THE

    2016 CALIFORNIA BUILDING STANDARDS CODE (CBC) AS OUTLINED

    IN THE REH.

    STRUCTURAL DRAWINGS

    S0.1 GENERAL NOTES

    S0.2 GENERAL NOTES & ABBREVIATIONS

    S1.0 TYPICAL DETAILS

    S2.1 1ST FLOOR AND FOUNDATION PLAN

    S2.2 ROOF FRAMING PLAN

    S3.1 WALL ELEVATIONS

    S3.2 WALL ELEVATIONS

    S4.1 SECTIONS & DETAILS

    S4.2 SECTIONS & DETAILS

    S4.3 SECTIONS & DETAILS

    EXISTING BUILDING TYPE: III-B

    PROPOSED BUILDING TYPE: V-B (SEE A0.03 EGRESS PLAN)

    EXISTING OCCUPANCY: B/A-3

    PROPOSED OCCUPANCY: B/A-3 (SEE A0.03)

    EXISTING BUILDING IS CURRENTLY UNOCCUPIED AND SHALL

    REMAIN UNOCCUPIED UNTIL BUILDING IS CERTIFIED BY DSA.

    ELECTRICAL DRAWINGS

    E0.10 GENERAL NOTES, ABBREV. & LEGENDS

    E0.11 ELECTRICAL SPECIFICATIONS

    E0.30 ENERGY COMPLIANCE FORMS

    E0.40 ENERGY COMPLIANCE FORMS

    E0.50 ENERGY COMPLIANCE FORMS

    E0.60 ENERGY COMPLIANCE FORMS

    E1.00 POWER PLAN

    E1.01 POWER PLAN AT ROOF

    E2.00 LIGHTING PLAN

    E2.10 WIRING DIAGRAMS

    FIRE ALARM

    FA1.01 FIRE ALARM LEGEND, NOTES,

    & MOUNTING HEIGHT DETAILS

    FA2.00 FIRE ALARM FLOOR PLAN

    FA3.00 FIRE ALARM DEVICE DETAILS

    FA4.00 FIRE ALARM CALCULATIONS AND RISER DIAGRAM

    FA 5.00 FIRE STOP DETAILS

    FIRE ALARM NAME HCI SYSTEMS INC.

    ADDRESS 1419 N. MARKET BLVD.

    ADDRESS SACRAMENTO, CA 95834

    PHONE 916-419-6900

    EMAIL [email protected]

    FIRE

    PROTECTION NAME ZARI CONSULTING GROUP, INC.

    ADDRESS 755 BAYWOOD DRIVE, 2ND FLOOR

    ADDRESS PETALUMA, CA 95834

    PHONE 925-381-2322

    EMAIL [email protected]

    FIRE PROTECTION

    FP1-0 FIRE PROTECTION SYSTEM COVER SHEET

    FP1-1 FIRE PROTECTION SYSTEM SITE PLAN

    FP 2-0 FIRE PROTECTION SYSTEM SITE PLAN

    FP-3-0 FIRE PROTECTION SYSTEM SITE PLAN

    ABV. - Above

    ADD. - Addition

    ADJ. - Adjust

    A.F.F. - Above Finished Floor

    ALT. - Alternate

    APP'D. - Approved

    ARCH. - Architect,

    ASPH. - Asphalt

    BLDG. - Building

    BM. - Beam

    B.O. - Bottom of

    B.U.R./BUR - Built up Roof

    C.B. - Catch Basin

    C.D. - Construction document

    C.L. - Center Line

    CL. - Closet

    CLG. - Ceiling

    C.O. - Clean Out

    COL. - Column

    CONT. - Continuous

    CONTR. - Contractor

    CONC. - Concrete

    DBL. - Double

    DEMO. - Demolition

    DIA. - Diameter

    DIM. - Dimension

    DN. - Down

    DR. - Door

    EA. - Each

    E.F. - Exhaust fan

    ELEV. - Elevation

    ELECT. - Electric, electrical

    EQ. - Equal

    (E) - Existing

    EXT. - Exterior

    F.A. - Fire alarm

    F.D. - Floor drain

    F.E. - Fire extinguisher

    FIN. - Finish

    FLR. - Floor

    GA. - Gauge

    GALV. - Galvanized

    G.C. - General Contractor

    G.F.C.I. - Ground Fault Circuit Interrupt

    G.F.I. - Ground Fault Interrupt

    GL. - Glass

    GWB Gypsum Wall Board

    H.B. - Hose bib

    HDW. - Hardware

    HGT. - Height

    H.V.A.C. - Heating, Venting and Air

    Conditioning

    INV. - Invert

    INSUL. - Insulation

    INT. - Interior

    JCT. - Junction

    JST. - Joist

    LIN. - Linear

    LT. - Light

    LTG. - Lighting

    MTL. - Metal

    MAX. - Maximum

    MECH. - Mechanical

    MFR - Manufacturer's

    MIN. - Minimum

    MTL. - Metal (steel)

    (N) - New

    N.T.S. - Not to scale

    O.C. - On center

    OPNG. - Opening

    PTD. - Painted

    PART. - Partition

    PL - Property Line

    PLAM - Plastic laminate

    PLYWD. - Plywood

    P.S.F. - Pounds per square foot

    P.S.I. - Pounds per square inch

    RAD. - Radius

    R.D. - Roof drain

    R.O. - Rough Opening

    REF. - Reference

    REINF. - Reinforced

    RET. - Return

    REV. - Revision

    RM. - Room

    RMV. - Remove

    SED - See Electrical Docs

    SHT'G. - Sheathing

    SIM. - Similar

    SMD - See Mechanical Docs

    SPD - See Plumbing Docs

    SPECS. - Specifications

    SSD - See Structural Docs

    ST. - Square feet

    SI. - Square inches

    STD. - Standard

    STL. - Steel

    S.Y. - Square yard

    SYS. - System

    T.O. - Top of

    THR. - Threaded

    TYP. - Typical

    UNF. - Unfinished

    V.B. - Vapor barrier

    V.I.F. - Verify in field

    VCT. - Vinyl composition tile

    WP. - Weatherproof

    WD. - Wood

    FLOOD MAP INFO: FEMA MAP #06095C0164E

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • See General Note onC1 for POTcompliance (typ)

    48"

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • Side flare shall be 10% max at all ramps (typ)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • PLANTER

    PLANTER

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    ACCESS PLAN

    BUILDING PLAN - ACCESS

    SCALE: 1/16" = 1' - 0"10

    A0.10

    1 ACCESSIBLE STALLS WITH LEVELLOADING

    SHEET NOTES:

    2

    ACCESSIBLE PATH OF TRAVELSEE CIVIL DRAWINGS, SEE C.1FOR SITE DEVELOPMENTREQUIREMENTS

    3 SEE A1.00 SITE PLAN FORPARKING STALL RATIOS

    4 LISTENING DEVICE

    AS1.00

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • 04 WHEELCHAIR TURNING REQUIREMENTSIN AN ACCESSIBLE ROUTE

    05 DOORWAY REQUIREMENTS

    10 SIGN LOCATION AND INSTALLATION - WOMEN'S TOILET ROOM

    07 TABLE A - ADULT DIM 02 ACCESSIBLE PARKING SPACE

    SLOPE SHALL NOT EXCEED

    1:10 (MAX) PER

    11B-406.2.2 (V.I.F.)

    OUTLINE OF

    (E) RAMP

    INSTALL NEW DETECTABLE WARNINGS AT EXISTING CURB

    RAMP AND SHALL EXTEND THE FULL WIDTH OF THE RAMP PER

    11B-705.1.2.2. ONLT APPROVED DSA-AC DETECTABLE WARNING

    PRODUCTS SHALL BE INSTALLED PER 11B-705.1.1.1 AND

    11B-705.1.1.2

    01 ACCESSIBLE CURB CUT - VIF

    03 THRESHOLD REQUIREMENT @ENTRY (TYP)

    WHERE INDICATED:

    ACCESS AISLE

    PAINTED STRIPING WITH BLUE BOARDER

    AROUND ACCESS AISLE WITH WHITE

    DIAGONAL STRIPES AT 36"O.C. MAX

    PAINTED STRIPING WITH BLUE BOARDER

    AROUND ACCESS AISLE WITH WHITE

    DIAGONAL STRIPES AT 36"O.C. MAX

    PER 11B-705.1.1.3.1 DETECTABLE WARNING

    SURFACES SHALL BE YELLOW AND

    APPROXIMATE FS 33538 OF FEDERAL

    STANDARD 595C

    WHITE LETTERING 12" MIN HEIGHT

    PER 11B-703.7.2.6.2 WOMEN'S TOILET AND BATHING

    FACILITIES. A CIRCLE,

    1

    4

    INCH THICK AND 12 INCHES IN

    DIAMETER, SHALL BE LOCATED AT ENTRANCES TO

    WOMEN'S TOILET FACILITIES. THE CIRCLE SYMBOL

    SHALL CONTRAST WITH THE DOOR, EITHER LIGHT ON

    DARK BACKGROUND OR DARK ON LIGHT

    BACKGROUND.

    WHITE LETTERING 12" MIN HEIGHT

    36" x 36" PAINTED ACCESSIBLE

    SIGN, WHITE W/ BLUE

    BACKGROUND

    96" @ VAN ACCESSIBLE SPACE

    ACCESSIBLE PARKING SIGN

    WALK OR PLANTING

    36" x 36" PAINTED ACCESSIBLE

    SIGN, WHITE W/ BLUE

    BACKGROUND

    ACCESS PARKING

    SIGN - SEE 07/SIGN B

    WALK OR PLANTING

    WALK OR PLANTING

    11 SIGN LOCATION AND INSTALLATION - MEN'S TOILET ROOM

    PER 11B-703.7.2.6.1 MEN'S TOILET AND BATHING

    FACILITIES. AN EQUILATERAL TRIANGLE,

    1

    4

    INCH

    THICK AND 12 INCHES LONG AND A VERTEX

    POINTING UPWARD, SHALL BE LOCATED AT

    ENTRANCES TO WOMEN'S TOILET FACILITIES. THE

    TRIANGLE SYMBOL SHALL CONTRAST WITH THE

    DOOR, EITHER LIGHT ON DARK BACKGROUND OR

    DARK ON LIGHT BACKGROUND.

    12 SIGN LOCATION AND INSTALLATION

    09 BATHROOM CLEARANCES

    "PASSENGER LOADING

    ZONE ONLY"

    "ADA PARKING ONLY"

    70 SQ. INCH ACCESSIBILITY

    SIGN PER SEC. 11B-502.6

    SIGNAGE SHALL INCLUDE

    "MINIMUM FINE $250"

    SEE SIGN A / SIGN B FOR DETAILS

    SIGN A:

    30

    "

    7'-0

    "

    TO

    B

    OT

    TO

    M O

    F S

    IG

    N

    12'-0"

    RAINTIGHT

    CAP

    VAN SIGNAGE

    CONCRETE FOUNDATION

    NO. 4 RE-BAR 8" LONG

    WELDED TO BOTTOM OF

    SLEEVE OR DRILLED INTO

    SLEEVE

    COMPACTED EARTH

    2" GALV. STEEL POST

    SET IN 2-1/2" GALV.

    STEEL SLEEVE

    4"

    1" S

    LO

    PE

    T

    YP

    REFLECTORIZED "ADA PARKING

    ONLY" 70 SQ. INCH

    ACCESSIBILITY SIGN PER SEC.

    11B-502.6 SIGNAGE SHALL

    INCLUDE "MINIMUM FINE $250"

    SIGNS (N.T.S.) SECURETO

    POST WITH 3/8" GALV. STEEL

    BOLTS, NUTS, AND WASHERS.

    08 ACCESSIBLE SIGNAGE @ PARKING

    "Unauthorized vehicles parked in designated accessible

    spaces not displaying distinguishing placards or special

    license plates issued for persons with disabilities will be

    be reclaimed at: Violators Subject to Tow Solano

    Community College Police Dept."

    ADDITIONAL SIGNAGE:

    SINGLE ACCOMMODATION TOILET FACILITYACCESSIBLE WATER CLOSET COMPARTMENT

    WITHIN A MULTIPLE-ACCOMODATION TOILET FACILITY

    TOILET STALL - SIDE ENTRY

    MULTIPLE ACCOMODATION TOILET ROOM

    A0.20

    ADA - ACCESS

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    17"-

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • A0.30

    EGRESS PLAN

    EGRESS PLAN

    SCALE: 3/32" = 1' - 0"10

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    1. PER TABLE 803.11CBC 2016, INTERIORFINISHES FOR WALL AND CEILING, INROOMS AND ENCLOSED SPACES SHALL BECLASS "C" OR BETTER AND CLASS "B" INCORRIDORS AND EXIT ENCLOSURES INFULLY SPRINKLED SPACES. CRITERIA FORFLAME SPREAD INDEX SHALL COMPLY WITHSEC 803 AND TABLE 803.9 (TYP).

    2. NON-RESILIENT FLOOR FINISHES SHALL OFCLASS I OR CLASS II IN ACCORDANCE WITHNFPA 253 (TYP) AND SHALL COMPLY WITHTHE REQUIREMENTS IN SECTION 804

    GENERAL NOTE:

    3. SEE DSA APPROVED 02-REH-10012(09/15/2015) FOR CHANGE OF BUILDINGCLASSIFICATION TO TYPE V-B.

    1. FIRE EXTINGUISHERS (FE) PROVIDED SHALL BE INCOMPLIANCE WITH CFC SECTION 906. CLASSIFICATION SHALLBE IN ACCORDANCE WITH CCR TITLE 19, DIV 1, SECT 565.1(A):LIGHT HAZARD (FOR CLASSROOMS), SEE A2.00 FORLOCATIONS.

    2. FE SHALL BE INSPECTED PER SEC 574.1 ON A MONTHLY BASISUNLESS OTHERWISE DETERMINED BY THE GOVERNING FIREAUTHORITY. FE SHALL REMAIN FULLY CHARGED AND KEPT INTHEIR DESIGNATED PLACES AT ALL TIMES.

    3. PER TITLE 19, DIV.1, SEC.568, TABLE 2, FE SHALL BE RATED AS2-A (MIN) AND SHALL BE PROVIDED WITH A MAXIMUM FLOORAREA PER FE AT 3000SF. TOTAL AREA = 16,400/3000 = 6 FE MIN.MAXIMUM TRAVEL DISTANCE FROM ANY POINT IN THEBUILDING SHALL NOT EXCEED 75' MIN. (TYP)

    GENERAL NOTES FOR FIRE EXTINGUISHER (FE): :

    1 ADJUST (E) DOOR OPENERS AT ACCESSIBLE ENTRIES (2 TOTAL).

    SHEET NOTES:

    2REINSTALL (E) METAL COILING DOOR ASSEMBLY AND (E)LOWER PLAM COUNTER FOR ACCESS COMPLIANCE.

    3 CONFORM (N) CONC WITH EXISTING (SSD), PATCH IN(N)WALL/CEILING FRAMING, GWB (PREP/TAPE/PAINT),TRIM TO MATCH EXISTING. WHERE WORK OCCURS ATDOORS ,REINSTALL (E) DOORS W/ NEW FRAMING TOMATCH. NEW CARPET TILES SHALL BE REPLACED IN WHOLESQUARES ONLY (TYP).

    4 REMOVE (E) SHORING ONLY AFTER SEOR CONFIRMS INWRITING WITH CONTRACTOR

    GENERAL EGRESS DOOR COMPLIANCE (PER CBC SEC. 1010.1.9):

    1. DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BYCHAPTER 11A OR 11B OF THE CALIFORNIA BUILDING CODE SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING ORTWISTING OF THE WRIST TO OPERATE.

    2. DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING DEVICES SHALL BE INSTALLED 34 INCHES (864 MM)MINIMUM AND 48 INCHES (1219 MM) MAXIMUM ABOVE THE FINISHED FLOOR.

    3. MANUALLY OPERATED FLUSH BOLTS OR SURFACE BOLTS ARE NOT PERMITTED.

    4. THE UNLATCHING OF ANY DOOR OR LEAF SHALL NOT REQUIRE MORE THAN ONE OPERATION. DOORS SERVING ROOMSOR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OCCUPANCY, ASSEMBLY AREA NOT CLASSIFIED ASAN ASSEMBLY OCCUPANCY, E, OCCUPANCIES SHALL NOT BE PROVIDED WITH A LATCH OR LOCK OTHER THAN PANICHARDWARE OR FIRE EXIT HARDWARE.

    5. PER 1010.1.10.1 WHERE PANIC OR FIRE EXIT HARDWARE IS INSTALLED, IT SHALL COMPLY WITH THE FOLLOWING: PANICHARDWARE SHALL BE LISTED IN ACCORDANCE WITH UL 305,FIRE EXIT HARDWARE SHALL BE LISTED IN ACCORDANCE WITH UL 10C AND UL 305, THE ACTUATING PORTION OF THERELEASING DEVICE SHALL EXTEND NOT LESS THAN ONE-HALF OF THE DOOR LEAF WIDTH, AND THE MAXIMUM UNLATCHINGFORCE SHALL NOT EXCEED 15 POUNDS (67 N).

    RISER ROOM SIGNAGE:

    1. PROVIDE EXTERIOR SIGN INDICATING"RISER ROOM IN ROOM 108"

    2. PROVIDE INTERIOR SIGN IN ROOM 108NEAR RISER ROOM DOOR INDICATING "RISER ROOM"

    PROVIDE COMPLIANT SIGNAGE FOR ASSEMBLY SPACE AT RMS 106 &120THAT NOTES MAXIMUM OCCUPANCY (BASED ON LOAD CALCULATIONSON THIS PAGE

    6. ALL EXITS DOORS SHALL HAVE COMPLIANT PANIC HARDWARE, VIF (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    D1.01

    EXISTING/DEMO

    ROOF PLAN

    EXISTING ROOF PLAN

    SCALE: 1/8" = 1' - 0"10

    1 REMOVE (E) BUILT-UP ROOF(BUR), IN AREAS SHOWN,COORDINATE WITHSTRUCTURAL DRAWINGS FORLOCATIONS (TYP).CONTRACTOR SHALL MOVEAND/OR CAP ALL UTILITIESTO ALLOW FOR WORK TO BEADEQUATELY PERFORMED(TYP).

    3 REMOVE (E) ROOFDRAINS/OVERFLOW (TYP) - SPD

    4 DEMO EXTERIOR ROOF ASSHOWN FOR NEW ACCESSHATCH , COORINDATE WITHLOCATION FOR NEW ACCESSLADDER BELOW (TYP).

    SHEET NOTES:

    5 DEMO TO PROVIDE FOR (N)EXHAUST FAN - SMD.

    6 REMOVE (E) LADDER AND ALLRELATED ATTACHMENTS REQ'DTO PREPARE TO (N) ROOF

    CONTRACTOR SHALL REMOVEAREAS OF THE ROOF ASINDICATED IN PREPARATION FOR(N) ROOF. COORDINATE WORKON ROOF WITH STRUCTURAL,MECHANICAL, ELECTRICAL ANDfa DOCUMENTS AS REQ'D FOR THEWORK TO BE PERFORMED (TYP).

    2 REMOVE (E) CONCRETE ROOFTILES AND PREPARE ROOFSUBSTRATE FOR INSTALLATIONOF (N) METAL STANDING SEAMROOF (TYP.)

    7 DASHED LINES INDICATEAPPROXIMATE AREAS OF (E)CRICKETS, EQUIPMENT ANDSUPPORT PLATFORMS THAT WILLREQUIRE ACCESS TOSHEATHING BELOW FORSTRUCTURAL WORK (SSD),CONTRACTOR SHALL PROVIDEACCESS AS REQ'D AND TEMPCAP AND RELOCATEEQUIPMENT WHILE WORK ISBEING PERFORMED (TYP).

    GENERAL ROOF DEMO NOTE:

    8REMOVE (E) EXISTING FAN TOREINSTALLION

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • D1.01 ALT

    EXISTING/DEMO

    ROOF PLAN

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    EXISTING ROOF PLAN

    SCALE: 1/8" = 1' - 0"10

    1 REMOVE (E) BUILT-UP ROOF(BUR) AS INDICATED. SEEDETAILS FOR EXTENT OFREMOVAL AT EQUIPMENTPADS AND PARAPET (TYP).

    3 REMOVE (E) ROOFDRAINS/OVERFLOW (TYP) - SPD

    4 DEMO FOR EXTERIOR ROOFACCESS HATCH,COORDINATE WITH INSTALLOF ACCESS LADDER BELOW.

    SHEET NOTES:

    5 DEMO TO PROVIDE FOR (N)EXHAUST FAN.

    7 DASHED LINES INDICATEAPPROXIMATE AREAS OF (E)CRICKETS, EQUIPMENT ANDSUPPORT PLATFORMS THATWILL REQUIRE ACCESS TOSHEATHING BELOW FORSTRUCTURAL WORK (SSD),CONTRACTOR SHALL PROVIDEACCESS AS REQ'D AND TEMPCAP AND RELOCATEEQUIPMENT WHILE WORK ISBEING PERFORMED (TYP).

    GENERAL ROOF DEMO NOTE:

    CONTRACTOR SHALL REMOVEAREAS OF THE ROOF ASINDICATED IN PREPARATION FOR(N) ROOF. COORDINATE WORKON ROOF WITH STRUCTURAL,MECHANICAL, ELECTRICAL ANDfa DOCUMENTS AS REQ'D FOR THEWORK TO BE PERFORMED (TYP).

    2 REMOVE (E) CONCRETETILES, COPING, FLASHINGAND ACCESSORIES ASREQ'D AND PREPARESUBSTRATE FORINSTALLATION OF (N) METALSEAM ROOF (TYP.)

    6 REMOVE (E) LADDER AND ALLRELATED ATTACHMENTS TOPREPARE TO (N) ROOF

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • B C D E F

    2

    3

    4

    A

    G

    1

    B C D E F

    2

    3

    4

    A

    G

    1

    C

    C.2

    D.8

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    D2.00

    EXISTING / DEMO

    FLOOR PLAN

    EXISTING / DEMO FLOOR PLAN

    SCALE: 1/8" = 1' - 0"10

    SHEET NOTES:

    2 REMOVE (E) METAL COILING DOOR ASSEMBLY AND (E)COUNTERS, STORE FOR REASSEMBLY - SEE INTERIOR DETAILS (TYP)

    3

    REMOVE PORTIONS OF (E)WALL/FRAMING, CARPET AND ALLRELATED ACCESSORIES AS REQ'D TO ALLOW FOR STRUCTURALWORK (TYP).

    5

    DEMO PORTION OF THE CONCRETE SLAB, CARPET/VINYL FLOOR,WALL FRAMING AND ALL RELATED ACCESSORIES AS REQ'D TOADEQUATELY PERFORM THE STRUCTURAL WORK - SSD.

    6 DEMO (E) WALL AS REQ'D FOR WORK - SSD

    1 PROTECT ALL CARPET THAT WILL REMAIN IN DURING WORK.

    7 REMOVE (E) CEILING GRID AND (E) CEILING TILES AS NEEDED TOINSTALL NEW TRUSSES.

    4 OUTLINE OF EXISTING SHORING TO REMAIN UNTIL ROOF LOADSCAN BE ADEQUATELY SUPPORTED UNDER NEW TRUSS,COORDINATE SCHEDULE ACCORDINGLY WITH SEOR (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DD

    PLUMBING FIXTURE ANALYSIS - ADMIN

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    D2.01

    TOILET ROOMS 111 & 112 (EXISTING)

    SCALE: 1/2" = 1' - 0"

    10

    TOILET ROOMS 122 & 123 (EXISTING)

    SCALE: 1/2" = 1' - 0"

    01

    EXISTING DRINKING FOUNTAINS

    SCALE: 3/4" = 1' - 0"

    02

    DEMO PLANS EXISTING

    TOILET ROOMS &

    DRINKING FOUNTAINS

    1REMOVE (E) SINK AND CABINET, PREP WALL FORPAINTING AND NEW CARPET (WHOLE SQUARES ONLY)WHERE DAMAGEDS FOR NEW CABINET/SINK (TYP).

    SHEET NOTES:

    2 (E) TOILET ROOMS 111 & 112 - REMOVE ANDSALVAGE FOR REINSTALLATION TWO (2) EXISTINGTOILET FIXTURES, ADJACENT ACCESSORIES, GRABBARS AND CARRIERS. PREPARE WASTE LINES ANDWATER SUPPLY LINES TO ALLOW FOR 5' MIN STALLWIDTH. DEMO EXISTING WALL AND PREPARE FORRE-FRAMING.

    PLUMBING FIXTURE ANALYSIS

    SCALE: 1/2" = 1' - 0"

    12

    3 REMOVE AND SALVAGE ALL (3) DRINKINGFOUNTAINS. CAP POWER, WATER SUPPLY ANDWASTE LINE. DRINKING FOUNTAIN B & C TO BE KEPTFOR REINSTALLATION, DRINKING FOUNTAIN A TO BESALVAGED TO OWNER. DEMO (E) PARTITION OFTHE WALL REQUIRED TO ALLOW FOR (N) PLUMBINGAND ELECTRICAL AND BACKING (TYP.) - SEE02/D2.01

    REMOVE AND SALVAGE (E) GARBAGE DISPOSA FOROWNER

    6 DEMO (E) WALL- CONTRACTOR TO DETERMINE ACTUALSCOPE OF DEMIOLITION (TYP).

    7REMOVE PORTIONS OF (E) CARPET TILE, COVEBASE AND CEILING TILES AS REQ.'D TO PROVIDESUFFICIENT CLEARANCE FOR NEW WALL.REPLACE TILES IN WHOLE SQUARES ONLY (TYP).

    8 DEMO (E) TILE FLOOR AND CONCRETE SLABBELOW TO ALLOW FOR RE-LOCATED TOILET,SUPPLY AND WASTE LINE (SPD).OUTLINE OF DEMO AREA IS FOR REFERENCERONLY, CONTRACTOR SHALL DETERMINE ACTUALAREA OF DEMOLITIION (TYP).

    4 REMOVE (E) PARTITION DOOR AT WOMEN'SRESTROOM 112 AND SALVAGE FORREINSTALLATION TO ALLOW FOR IN-SWING.PROVIDE ALL HARDWARE NECCESSARY FORSCOPE (TYP)

    5

    9REMOVE (E) TOILETS AND ALL RELATED ACCESSORIESFOR REINSTALLATION. DEMO CONC SLAB/TILE/WALLAS REQ'D TO ALLOW FOR STRUCTURAL WORK (SSD),CAP ALL UTILITIES AND PROTECT LINES FORREINSTALLATION. OUTLINE FOR DEMO IS FOR REFERENCEONLY, CONTRACTOR SHALL DETERMINE EXTENT (TYP).

    DASHED OUTLINEOF PANEL ABOVE

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • BC

    E

    ABC

    DEF

    A

    G

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    D3.00

    EXISTING/DEMO

    ELEVATIONS

    EXISTING NORTH ELEVATIONS13SCALE: 1/8" = 1' - 0"

    EXISTING SOUTH ELEVATIONS12SCALE: 1/8" = 1' - 0"

    EXISTING WEST ELEVATIONS11SCALE: 1/8" = 1' - 0"

    EXISTING EAST ELEVATIONS10SCALE: 1/8" = 1' - 0"

    EXISTING COLORSTRIM AND PAINTED SURFACES(REFERENCE FROM A2.1 - SCCD

    SET APPROVED DATE 12-25-1995)

    - ROOF"LIFETILE" FLAT CONC. TILE 1220 OREQUAL- BUILDINGSTUCCO "LA HABRA STUCCO""PURE IVORY" (MAIN BUILDINGSTUCCO, STUCCO AT TEMP./PERM.SIGNAGE, DIRECTORIES, TRASHENCLOSURES, COLUMN BODIES)STUCCO TRIM "LA HABRA STUCCO""FRENCH VANILLA" (ACCENTSTUCCO, TRIM & COLUMN BASEVENEER)- WOODTRIM "DUNN-EDWARDS""RODEO TAN" OR EQUAL (ALLWOOD PAINTED TRIM)

    1 CORING HOLES AT (E)CONCRETE PANELS (TYP)-SSD

    SHEET NOTES:

    2 REMOVE (E) CONCRETETILES AND PREPARE FORINSTALLATION OF (N) METALSEAM ROOF (TYP.)

    3 PREPARE (E) WALL FOR NEWFLASHING, REMOVE CEMENTPLASTER AS REQ'D (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • B C D E F

    A

    G

    B C D E F

    A

    G

    B

    CDEF

    A

    B

    CDEF

    A

    G

    4 3 32

    1

    1 32

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    ISSUE FORREVIEW

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    D5.00

    DEMO/EXISTING

    ELEVATIONS

    EXISTING ELEVATIONS - A14SCALE: 1/8" = 1' - 0"

    EXISTING ELEVATIONS - C13SCALE: 1/8" = 1' - 0"

    EXISTING ELEVATIONS - C12SCALE: 1/8" = 1' - 0"

    EXISTING ELEVATIONS11SCALE: 1/8" = 1' - 0"

    EXISTING ELEVATIONS10SCALE: 1/8" = 1' - 0"

    1COORDINATE ALL (N) STRUCTURAL WORK FOR (N)REINFORCING (SSD). THIS WILL REQUIRE SELECTIVEDEMOLITION AS REQ'D TO PROVIDE APPROPRIATEACCESS. GC SHALL COORDINATE WORK WITHSUBCONTRACTORS TO ENSURE APPROPRIATE SCOPE OFDEMOLITION FOR ADEQUATE ACCESS FOR STRUCTURALWORK (TYP). AFTER STRUCTURAL WORK IS COMPLETE,SCOPE SHALL INCLUDE RE-FRAMING, (N) GWB TO PATCH,PREP AND PAINT TO MATCH (TYP).

    SHEET NOTES:

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    ISSUE FORREVIEW

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    D5.01

    DEMO/EXISTING

    ELEVATIONS

    EXISTING ELEVATIONS - WOMEN'S RESTROOM13

    EXISTING ELEVATIONS - DRINKING FOUNTAINS

    SCALE: 3/8" = 1' - 0"10

    EXISTING ELEVATIONS - MEN'S RESTROOM

    SCALE: 3/8" = 1' - 0"12

    SCALE: 3/8" = 1' - 0"

    SCALE: 3/8" = 1' - 0"11 EXISTING ELEVATIONS - ADMIN RESTROOM WOMEN

    SCALE: 3/8" = 1' - 0"05 EXISTING ELEVATIONS - ADMIN RESTROOMS MEN

    04 ANNEX COUNTERTOP/SINKSCALE: 3/8" = 1' - 0"

    1DEMOLISH (E) WALL, FRAMING, GWB, TILE, ETC. AND CAP (E) UTILITIES (IF FOUND)TO BE RE-LOCATED (TYP). COORDINATE CORRESPONDING DEMO @(E) FLOORS,CEILING, AND ALL ADJACENT SPACES THAT WILL BE EFFECTED BY THE DEMO (TYP).

    SHEET NOTES:

    2 REMOVE AND SALVAGE FOR REINSTALLATION (E) RESTROOM SIGNS.

    3 REMOVE AND SALVAGE FOR OWNER ONE (1) EXISTING DRINKING FOUNTAIN -SEE 02/A2.01.

    4 REMOVE AND SALVAGE FOR REINSTALLATION TWO (2) EXISTING DRINKINGFOUNTAINS - SEE 02/D2.01.

    5 REMOVE AND SALVAGE FOR REINSTALLATION ACCESSORIES.

    6 DEMO WALL AS REQ'D TO ALLOW FOR STRUCTURAL WORK AS SHOWN INDOCUMENTS, CONTRACTOR SHALL DETERMINE EXTENT OF DEMOLITION TOPERFORM WORK. THIS SHALL DETERMINE EXTENT OF NEW WORK AND SHALL BEINCLUDED CONTRACTOR'S SCOPE (TYP).

    GENERAL NOTE: REFER TO 07/A0.20 FOR ALL FIXTURE ANDACCESSORY MOUNTING HEIGHTS AND REQUIRMENTS (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    ISSUE FORREVIEW

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    D5.01

    DEMO/EXISTING

    ELEVATIONS

    EXISTING ELEVATIONS - WOMEN'S RESTROOM13

    EXISTING ELEVATIONS - DRINKING FOUNTAINS

    SCALE: 3/8" = 1' - 0"10

    EXISTING ELEVATIONS - MEN'S RESTROOM

    SCALE: 3/8" = 1' - 0"12

    SCALE: 3/8" = 1' - 0"

    SCALE: 3/8" = 1' - 0"11 EXISTING ELEVATIONS - ADMIN RESTROOM WOMEN

    SCALE: 3/8" = 1' - 0"05 EXISTING ELEVATIONS - ADMIN RESTROOMS MEN

    04 ANNEX COUNTERTOP/SINKSCALE: 3/8" = 1' - 0"

    1DEMOLISH (E) WALL, FRAMING, GWB, TILE, ETC. AND CAP (E) UTILITIES (IF FOUND)TO BE RE-LOCATED (TYP). COORDINATE CORRESPONDING DEMO @(E) FLOORS,CEILING, AND ALL ADJACENT SPACES THAT WILL BE EFFECTED BY THE DEMO (TYP).

    SHEET NOTES:

    2 REMOVE AND SALVAGE FOR REINSTALLATION (E) RESTROOM SIGNS.

    3 REMOVE AND SALVAGE FOR OWNER ONE (1) EXISTING DRINKING FOUNTAIN -SEE 02/A2.01.

    4 REMOVE AND SALVAGE FOR REINSTALLATION TWO (2) EXISTING DRINKINGFOUNTAINS - SEE 02/D2.01.

    5 REMOVE AND SALVAGE FOR REINSTALLATION ACCESSORIES.

    6 DEMO WALL AS REQ'D TO ALLOW FOR STRUCTURAL WORK AS SHOWN INDOCUMENTS, CONTRACTOR SHALL DETERMINE EXTENT OF DEMOLITION TOPERFORM WORK. THIS SHALL DETERMINE EXTENT OF NEW WORK AND SHALL BEINCLUDED CONTRACTOR'S SCOPE (TYP).

    GENERAL NOTE: REFER TO 07/A0.20 FOR ALL FIXTURE ANDACCESSORY MOUNTING HEIGHTS AND REQUIRMENTS (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    D6.00

    EXISTING/ DEMO

    RCP

    EXISTING RCP

    SCALE: 1/8" = 1' - 0"10

    1 REMOVE EXISTING SUSPENDEDCEILING GRID, HANGERS ANDSUPPORTS.

    SHEET NOTES:

    2 OUTLINE OF WALLS FOR DEMO (TYP).

    3 DEMO (E) LIGHTING (TYP).

    4 LEAVE (E) GWB WHERE OCCURS- HALLWAYS, RESTROOMS 111 &112, RESTROOMS 122 & 123.

    GENERAL NOTES:1. DEMO ENTIRE EXISTINGSUSPENDED CEILING GRID, HANGERSAND SUPPORTS. SALVAGE EXISTINGTILES AND CEILING TILE INSULATIONFOR RE-USE (TYP). EXISTING GWBCEILING SHALL REMAIN IN PLACEUNLESS OTHERWISE INDICATED.EXISTING LIGHT FIXTURES SHALL BEREMOVED FOR SALVAGE BYGC.LOCATION OF NEW SUSPENDEDCEILING SHA;LL REPLICATE EXISTINGFOR ORIENTATION AND LOCATION(TYP)2. SEE SHEET A9.03 FOR ADD'L REQ'TS(TYP)

    5 REMOVE (E) GWB, FIXTURESAND EQUIPMENT TO ALLOWWORK AS OUTLINED ON S2.1

    5

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    AS1.00

    SITE PLAN

    SITE PLAN

    SCALE: 1/32" = 1' - 0"10

    2 SITE CONDITIONS AT DRIVEWAYBASED ON INFORMATIONPROVIDED BY SCCD

    1 SEE CIVIL DRAWINGS FORSITE ACCESS COMPLIANCEWORK

    3 PARKING AS INDICATEDEQUALS 289 STALLS

    SHEET NOTES:

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A1.01

    ROOF PLAN

    PROPOSED ROOF PLAN

    SCALE: 1/8" = 1' - 0"10

    1INSTALL (N) STANDING SEAM METAL ROOF OVER PROPERLY PREPARED SUBSTRATE PERMANF'RS RECOMMENDATIONS, REMOVE (E) COPING AND PREP/INSTALL FOR NEWCOPING/FLASHING AS REQ'D, SEE 01/A8.01 & 04/A8.02 FOR ADD'L DETAILS (TYP)

    SHEET NOTES:

    2 COORDINATE STRUCTURAL/MEP WORK, PROPERLY PATCH PREPARED SUBSTRATE ASINDICATED WITH BUR, USE MATRIX 307 PRIMER FOR TIE IN TO EXISTING ROOF, NAIL # 75BASE TO (E) WOOD DECK (REPLACE DAMAGED SUBSTRATE AS REQ'D), MOP 2 PLIES OF PLY 6

    EACH SUBSEQUENT LAYER +6" OVER ALL SIDES (TYP), SEE DOCUEMENTS FOR ADD'L INFO.

    3 REINSTALL PARAPET PORTION OF (E) ROOF LADDER AS REQ'D FOR USE, SEE GENNOTES AND INSTALL PER CCR TITLE 8, SEC 3277(TYP).

    4 SEE DETAILS FOR EXISTING ROOF AT T.O.EQUIPMENT PAD AND PARAPET TO TIE INTONEW BUR, REPLACE DAMAGED PARAPET SHEET/SHINGLES (TYP)

    5 REPLACE (E) ROOF DRAINS/OVERFLOW, SEE 11/A8.02 (TYP) - SPD

    6INSTALL (N) EXTERIOR ROOF ACCESS HATCH, COORDINATE WITH ACCESS LADDERBELOW.

    7DASHED LINES INDICATE PORTIONS OF CRICKETS AND EQUIPMENT PADS THATREQUIRE NEW WORK TO MATCH/CONFORM EXISTING TO ALLOW FOR PROPERDRAINAGE AND EQUIPMENT SUPPORT (TYP).

    8 REINSTALL/INSTALL (N) EXHAUST FAN, REINSTALLATION OF EQUIPMENT NOTINDICATED ON EXISTING PAD, USE 10/A8.03 U.O.N. - TYP - SMD

    GENERAL NOTES:

    ALL ROOFING ASSEMBLIES SHALL BE REQUIRED TO BE A CLASS "A"ROOF ASSEMBLY AND TESTED IN ACCORDANCE WITH ASTM 108 OR UL790 AND COMPLY WITH THE REQUIRMENTS IN CBC 1505 (TYP).

    FOR SHEET NOTE #3: BEFORE REATTACHING PARAPET PORTION OF (E)LADDER, CLEAN OUT (E) HOLES, USE WEDGE ANCHORS 1/2" DIA MIN,INSTALL PER S0.1 DETAILS FOR USE/LOAD (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • ROOF PLAN

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    PROPOSED ROOF PLAN - ADDITIVE ALTERNATE

    SCALE: 1/8" = 1' - 0"10

    1 INSTALL (N) STANDING SEAM METAL ROOFSHEET NOTES:

    2 REPLACE (E) BUILT-UP ROOF (BUR) WITH NEW BUR (TYP). INSTALL (N) BUROVER PROPERLY PREPARED SUBSTRATE (INC. CRICKET). NAIL # 75 BASE TOWOOD DECK, MOP 2 PLIES OF PLY 6 PLY SHEET WITH TYPE III ASPHALT,

    3 RE-INSTALL (E) ROOF ACCESS LADDER IF REQUIRED,RE-INSTALL PER TITLE 8, CCR SEC 3277(TYP).

    4SEE DETAILS FOR EXISTING ROOF AT T.O.EQUIPMENT PAD AND PARAPET TO TIEINTO NEW BUR, REPLACE DAMAGED PARAPET SHEET/SHINGLES (TYP)

    5REPLACE (E) ROOF DRAINS/OVERFLOW, SEE 11/A8.02 (TYP) - SPD

    6 INSTALL (N) EXTERIOR ROOF ACCESS HATCH, COORDINATE WITH ACCESSLADDER LOCATION BELOW.

    7DASHED LINES INDICATE PORTIONS OF CRICKETS AND EQUIPMENT PADSTHAT REQUIRE NEW WORK TO MATCH/CONFORM EXISTING TO ALLOW FORPROPER DRAINAGE AND EQUIPMENT SUPPORT (TYP).

    A1.01 ALT

    8REINSTALL/INSTALL (N) EXHAUST FAN, REINSTALLATION OFEQUIPMENT NOT INDICATED ON EXISTING PAD, USE 10/A8.03U.O.N. - TYP - SMD

    GENERAL NOTES:

    ALL ROOFING ASSEMBLIES SHALL BE REQUIRED TO BE A CLASS "A"ROOF ASSEMBLY AND TESTED IN ACCORDANCE WITH ASTM 108 OR UL790 AND COMPLY WITH THE REQUIRMENTS IN CBC 1505 (TYP).

    FOR SHEET NOTE #3: BEFORE REATTACHING PARAPET PORTION OF (E)LADDER, CLEAN OUT (E) HOLES, USE WEDGE ANCHORS 1/2" DIA MIN,INSTALL PER S0.1 DETAILS FOR USE/LOAD (TYP).

    USE (2) # 12 SSSCREWS PERCLIP (TYP)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • 2

    3

    4

    1

    2

    3

    4

    1

    B C D E F

    A

    G

    B C D E F

    A

    G

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A2.00

    FLOOR PLAN

    FLOOR PLAN

    SCALE: 1/8" = 1' - 0"10

    1 ADJUST (E) DOOR OPENERS AT ACCESSIBLE ENTRIES (2 TOTAL).

    SHEET NOTES:

    2REINSTALL (E) METAL COILING DOOR ASSEMBLY AND (E)LOWER PLAM COUNTER FOR ACCESS COMPLIANCE. SSDFOR MOUNTING DETAILS

    3 CONFORM (N) CONC WITH EXISTING (SSD), PATCH IN(N)WALL/CEILING FRAMING, GWB (PREP/TAPE/PAINT),TRIM TO MATCH EXISTING. WHERE WORK OCCURS ATDOORS ,REINSTALL (E) DOORS W/ NEW FRAMING TOMATCH. NEW CARPET TILES SHALL BE REPLACED IN WHOLESQUARES ONLY (TYP).

    4 REMOVE (E) SHORING ONLY AFTER SEOR CONFIRMS INWRITING WITH CONTRACTOR

    5 ADD NEW FRAMING/FURRING, CONFORM WITH EXISTINGWALLS, INSTALL NEW GWB (TAPE/PREP/PAINT) TO MATCHEXISTING - SSD . IF CARPET TILES ARE DAMAGED, REPLACE INWHOLE SQUARES ONLY (TYP.)

    REFER TO 07/A0.20 FOR ALL FIXTURE AND ACCESSORYMOUNTING HEIGHTS AND REQUIRMENTS (TYP).

    GENERAL NOTES:

    6PROVIDE SEMI-RECESSED FIRE EXTINGUISHER (FE) & FEC TOMATCH EXISTING CLASS A FE (TYP), MOUNT NO HIGHER THAN60" AFF FOR LESS THAN 40 LBS FE AND THE BOTTOM OF THE FENO LESS THAN 4" FROM THE FLOOR (TYP). PROVIDE 6 FE MIN .

    6

    6

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • D

    33

    DD

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A2.01

    TOILET ROOMS 111 & 112

    SCALE: 1/2" = 1' - 0"

    10

    TOILET ROOMS 122 & 123 - ADMIN AREA

    SCALE: 1/2" = 1' - 0"

    01

    EXISTING DRINKING FOUNTAINS

    SCALE: 3/4" = 1' - 0"

    02

    ENLARGED PLANS

    TOILET ROOMS &

    DRINKING FOUNTAINS

    1

    SHEET NOTES:

    INSTALL ACCESSIBLE SINK CABINET, ADA ACCESSIBLE COUNTER, SINK AND FAUCET (SPD, PREP AND PAINT WALL ANDBASEBOARD TRIM TO MATCH EXISTING (TYP).

    2 RE-SPACE AND RE-INSTALL (2) DRINKING FOUNTAINS B & C - SEE 02/D2.01 AND 02/A2.01, PROVIDE ALL NECESSARY BACKINGREQUIRED TO RE-HANG (E) DRINKING FOUNTAIN (TYP). RE-FRAME AND ADD (N) GWB TO MATCH (E), TAPE AND PAINT TO MATCH (TYP).

    3 PROVIDE (N) CONCRETE SLAB WITH WP. BELOW, DOWEL (SEE SSD) AND CONFORM TO ALLOW (N) TILE TO ALIGN WITHEXISTING ADJACENT FLOOR. NEW TILE/GROUNT TO MATCH (E) TYP.

    4 MOVE AND REINSTALL ALL ACCESSORIES/GRAB BARS, MIRRORS, PROVIDE ADEQUATE BACKING FOR ALL WALL MTD. WORK TYP. USEBACKING FOR MED. LOADS (MIN) 04/A9.01 WITH 3-#10 SCREWS MIN AT ENDS TO SUPPORT MIN LOAD OF 250LBS.

    6 REHANG (E) MIRRORS TO BE HEIGHT COMPLIANT SEE A5.01.

    5 REINSTALL TWO (2) EXISTING TOILETS (SPD), AND ALL ADJACENT ACCESSORIES, GRAB BARS, CARRIERS, WASTE LINES, WATER SUPPLYLINES TO NEW LOCATION AS SHOWN FOR ACCESS COMPLIANCE. INSTALL NEW WALL FRAMING/GWB, TILE WALL/FLOOR (TO MATCHEXISTING), PROVIDE BACKING AS REQ'D TO RE-ATTACH EXISTING ACCESSORIES AND GRAB-BARS (TYP.).

    7 MOVE TOTAL OF 5 (FIVE) ACCESSORIES TO BE COMPLIANT. - SEE A5.01

    8 PARTITION DOOR AT WOMEN RESTROOM 112 TO BE MOVED 4" DOWN TO PROVIDE 18" CLEAR SPACE AT OPENING,RE-HAND (E) DOOR TO ALLOW IN-SWING, PROVIDE DOOR HARDWARE TO ALLOW AS REQ'D.

    9 PROVIDE CARPET TILES AND BASE TRIM AS REQUIRED. REINSTALL ALL WALL ACCESSORIES AS REQ'D, PREP/PAINT (N)WALL/TRIM TO MATCH EXISTING. ONLY REPLACE CARPET TILES IN WHOLE SQUARES ONLY (TYP).

    10 INSTALL (N) ROOF ACCESS HATCH AT ROOM ABOVE 122, SEE 10/A8.03.

    PLENUM PLATFORM ABOVE BATHROOM

    SCALE: 3/4" = 1' - 0"

    03

    6

    6

    9

    9

    11 CONFORM NEW CONC SLAB WITH EXISTING, ADD DOWELS/WATERPROOFING AS REQ'D (SSD), PATCH IN AND WELDSEAMS AT NEW SHEET VINYL TO MATCH EXISTING AT FLOOR AND COVE BASE (TYP.) INSTALL NEW FRAMING GWB(COMPLIANT WITH TOILET ROOM) AND PATCH/PREP/PAINT TO MATCH EXISTING. REINSTALL ALL ACCESSORIES FORCOMPLIANCE FOR ACCESS (WITH BACKING) AND REINSTALL (E) TOILETS tYP.).

    DASHED OUTLINEOF PANEL ABOVE

    DASHED OUTLINEOF LEVEL LANDING

    DASHED OUTLINEOF LEVEL LANDING

    DASHED OUTLINEOF LEVEL LANDING

    DASHED OUTLINEOF LEVEL LANDING

    DASHED OUTLINEOF LEVEL LANDING

    DASHED OUTLINEOF LEVEL LANDING

    GEN NOTE:

    NO STUDENT ACCESS TO

    ATTIC OR ROOF ABOVE (TYP)

    GENERAL NOTE: REFER TO07/A0.20 FOR ALL FIXTUREAND ACCESSORY MOUNTINGHEIGHTS AND REQUIRMENTS(TYP).

    SEE S2.1 FOR FRAMING

    REQUIREMENTS FOR

    PLATFORM. TEMPORARILY

    REMOVE AND RE-INSTALL (E)

    EQUIPMENT IF REQ'D FOR

    NEW FRAMING AND

    SUPPORT (TYP)

    16"

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • BC

    E

    ABC

    DEF

    A

    G

    A3.00

    EXTERIOR

    ELEVATIONS

    EXISTING NORTH ELEVATIONS13

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    SCALE: 1/8" = 1' - 0"

    EXISTING SOUTH ELEVATIONS12SCALE: 1/8" = 1' - 0"

    EXISTING WEST ELEVATIONS11SCALE: 1/8" = 1' - 0"

    EXISTING EAST ELEVATIONS10SCALE: 1/8" = 1' - 0"

    1(N) BOLT CONNECTIONS ATCONCRETE PANEL - SEE 1/A8.04 -SSD

    SHEET NOTES:

    2NEW FLASHING/CEMENTPLASTER/WATERPROOFING ASREQ'D TO INSTALL NEW ROOF-SEE4/A8.01 (TYP.)

    3 WHERE METAL ROOF TERMINATESINTO (E) WALL, PROVIDEAPPROPRIATEFLASHING/COUNTERFLASHING ASREQ'D PER MFR'SRECOMMENDATIONS(TYP).

    GENERAL NOTES:

    ALL ROOFING ASSEMBLIES SHALLBE REQUIRED TO BE A CLASS "A"ROOF ASSEMBLY AND TESTED INACCORDANCE WITH ASTM 108 ORUL 790 AND COMPLY WITH THEREQUIRMENTS IN CBC 1505 (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A3.01ALT

    PARAPET ELEVATIONS

    EXISTING NORTH ROOF ELEVATIONS13SCALE: 1/4" = 1' - 0"

    EXISTING SOUTH ROOF ELEVATIONS12SCALE: 1/8" = 1' - 0"

    EXISTING WEST ROOF ELEVATIONS10SCALE: 1/8" = 1' - 0"

    EXISTING EAST ROOF ELEVATIONS11SCALE: 1/4" = 1' - 0"

    SCALE: 1/4" = 1' - 0"

    1

    SHEET NOTES:

    2

    (E) ROOF LADDERATTACHMENTS - REMOVEAND RE-INSTALL AS REQ'DTO RE-ROOF PARAPET, SEENOTE #3/A1.01

    REMOVE COPING AND PREP FORNEW METAL ROOF AS SHOWN. NEWCOPING AND RELATED FLASHING ISREQUIRED FOR NEW METAL ROOFAND SHALL BE INCLUDED IN BASEBID, SEE 01/A8.01FOR TYPICALSCOPE.

    3 REMOVE (E) ROOF DRAINSAND INSTALL NEW DRAINS -SPD (TYP.)

    3

    3

    3

    3

    3

    3

    4 EXISTING PARAPETWATERPROOFING TOREMAIN EXCPET IN AREAS ASNOTED. INSPECT AND PATCHAREAS OF EXISTING PARAPETTHAT APPEAR TO REQUIREREPAIR (TYP)

    4

    4

    4

    4

    4

    GENERAL NOTES:

    ALL ROOFING ASSEMBLIES SHALLBE REQUIRED TO BE A CLASS "A"ROOF ASSEMBLY AND TESTED INACCORDANCE WITH ASTM 108 ORUL 790 AND COMPLY WITH THEREQUIRMENTS IN CBC 1505 (TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • A5.01

    PROPOSED

    ELEVATIONS

    PROPOSED ELEVATIONS - WOMEN'S RESTROOM 11213

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    ISSUE FORREVIEW

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    PROPOSED ELEVATIONS - DRINKING FOUNTAINS

    SCALE: 3/8" = 1' - 0"10

    PROPOSED ELEVATIONS - MEN'S RESTROOM 111

    SCALE: 3/8" = 1' - 0"12

    SCALE: 3/8" = 1' - 0"

    SCALE: 3/8" = 1' - 0"11 PROPOSED ELEVATIONS - ADMIN UNISEX RESTROOM122

    SCALE: 3/8" = 1' - 0"05 PROPOSED ELEVATIONS - ADMIN UNISEX RESTROOM 123

    04 PROPOSED - ADMIN SINK 121SCALE: 3/8" = 1' - 0"

    1 PROVIDE (N) GWB/TILE (TO MATCH) EXISTING PAINT & TILE (TYP).

    SHEET NOTES:

    2 PROVIDE (N) BACKING IN WALLS SUFFICIENT TO RE-LOCATE (E)ACCESSORIES & GRAB BARS (TYP).

    3 ADJUST HEIGHT OF ACCESSORIES TO COMPLY WITH REQUIREDADA HEIGTHS.

    4 PROVIDE AND INSTALL (N) UNISEX RESTROOM SIGNS.

    5 NEW AREA OF WALL TO BE REBUILT, CONTRACTOR SHALL ACCOUNTFOR EXTENT OF SCOPE BASED ON DEMO SCOPE. CONTRACTORSHALL REPLACE/REINSTALL ANY DEVICES, FIXTURES ANDACCESSORIES ON BOTH SIDES OF THE WALLS. ALL FINISHES,MATERIALS AND COLORS SHALL MATCH EXISTING ON BOTHSSIDESOF THE WALLS (TYP).

    6 GENERAL NOTE: SEE 07/A0.20 FOR ADD'D ACCESSCOMPLIANCE INFORMATION AS REQ'D FOR SCOPE SHOWN(TYP)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A6.00

    REFLECTED

    CEILING PLAN

    RCP

    SCALE: 1/8" = 1' - 0"10

    1 GEN NOTE: SED FOR ADDITIONALINFORMATION FOR LIGHTING ANDCONTROLS (TYP).

    SHEET NOTES:

    2 WALL LOCATION WILL SHIFT,ADJUST NEW CEILING GRIDACCORDINGLY TO ALLOW FOREXISTING FP/FIXTURES (TYP)

    3 GEN. NOTE: REINSTALL SALVAGEDCEILING TILES AND INSULATIONTILES (ABOVE) IN NEW SUSPENDEDCEILING GRID (TYP).

    4 GEN. NOTE: REPLACEDAMAGED TILES ANDINSULATION TILES (ABOVE)WHERE DAMAGED (TYP).

    GEN. NOTE: WHERE GWBCEILING IS DISTURBED BY NEWSCOPE OF WORK, PATCH INNEW GWB, PREP/PAINT TOMATCH EXISTING (TYP).

    5

    1. RE-INSTALL ALL CEILINGMOUNTED PROJECTORS, SCREENS,ROUTERS AND SENSORS TOEXISTING LOCATIONS. PROVIDEPOWER & DATA CONNECTIONSFOR ALL REINSTALLED DEVICESAND RESTORE TO WORKINGORDER.lOCATIONS SHOWN ONPLAN MAY BE DIAGRAMMATIC,RE-INSTALL TO ORGINAL LOCATIONUON (TYP)

    ALL LIGHTWEIGHT MISCELLANEOUSDEVICES, SUCH AS STROBE LIGHTS,OCCUPANCY SENSORS,SPEAKERS, EXIT SIGNS, ETC., SHALLBE ATTACHED TO THE CEILINGGRID. IN ADDITION, DEVICESWEIGHING MORE THAN 10 LBS.SHALL HAVE A #12 GAGE SLACKSAFETY WIRE ANCHORED TO THESTRUCTURE. DEVICESWEIGHING MORE THAN 20 LBS.SHALL BE SUPPORTED FROM THESTRUCTURE ABOVE USING DETAILSPROVIDED BY THE REGISTEREDDESIGN PROFESSIONAL.

    2. SEE ELECTRICAL, MEP, FP AND FAFOR ADDITONAL DEVICES AS PARTOF PROJECT SCOPE (TYP).

    3. SEE A9.03 FOR ADD'L DETAILS(TYP)

    GENERAL NOTES:

    IN RM #122: NEW GWB,PROVIDE FOR REINSTALLATIONOF EXISTING FIXTURES ANDEQUIPMENT. TAPE, PREP ANDMATCH (E) FINISH AND PAINT.SEE S2.1 DOE SCOPE OF WORK

    6

    6

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A8.00EXT. DETAILS

    03 PARTIAL ELEVATION AT EXISTING ROOF/WALLSCALE: 3/4" =1'-0"

    02 PARTIAL ELEVATION AT STANDING METAL SEAM ROOF/WALLSCALE: 3/4" =1'-0"

    01 PARTIAL PLAN AT STANDING METAL SEAM ROOFSCALE: 3/4" =1'-0"

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A8.00EXT. DETAILS

    03 PARTIAL ELEVATION AT EXISTING ROOF/WALLSCALE: 3/4" =1'-0"

    02 PARTIAL ELEVATION AT STANDING METAL SEAM ROOF/WALLSCALE: 3/4" =1'-0"

    01 PARTIAL PLAN AT STANDING METAL SEAM ROOFSCALE: 3/4" =1'-0"

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • 1.

    REFER TO TECHNICAL INFORMATION SHEETS2.FOR FASCIA SIZES, ACCESSORIES, AND FINISHES

    3. WOOD NAILER MUST BE INSTALLED TO MEETAPPLICABLE BUILDING CODES OR 200 LBS PERLINEAR FOOT MINIMUM IN ANY GIVEN DIRECTION.

    AVAILABLE.

    REFER TO FIRESTONE WEBSITE FOR MOSTCURRENT INFORMATION.

    4. REFER TO THE FIRESTONE TECHNICAL DATABASEFOR FASTENER COMPATIBILITY WITH METAL.

    APPLICATION DETAILS ARE FOR ILLUSTRATIONPURPOSES ONLY AND MAY NOT BE APPROPRIATEFOR ALL BUILDING DESIGNS AND CONDITIONS.

    5.

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    04 FIXED HEAD WALLA8.01

    EXT.DETAILS

    01 FIXED HIGH EAVE03 METAL ROOF EAVE AT DRIP EDGE (TYP)SCALE: 3" = 1'-0"

    06 METAL ROOF EAVE AT GUTTER (TYP)SCALE: 3" = 1'-0"

    SCALE: 3" = 1'-0"

    SCALE: 3" = 1'-0"

    WHERE GUTTER TERMINATES INTO E)WALL, PROVIDE APPROPRIATE FLASHINGAND COUNTERFLASHING AS REQ'D PREMFR'S RECOMMENDATIONS (TYP).

    WHERE EAVE TERMINATES INTO E) WALL,PROVIDE APPROPRIATE FLASHING ANDCOUNTERFLASHING AS REQ'D PRE MFR'SRECOMMENDATIONS (TYP).

    #8 SS WOODSCREW @8"O.C., EMBED1-1/2" TYP

    #8 SS WOOD SCREW @8"O.C., EMBED 1-1/2" TYP

    #8 SS WOOD SCREW @

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • 1" M

    IN.

    SUBSTRATE SUBSTRAT

    E

    3" (76.2 mm) MIN.

    PREVAILINGWIND

    3

    "

    (

    7

    6

    .

    2

    m

    m

    )

    M

    I

    N

    .

    SUBSTRATESUBSTRATE

    04 MTL ROOF AT RAKE (TYP)

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A8.02EXT. DETAILS

    01 MTL ROOF AT VALLEY (TYP)SCALE: 3" = 1'-0"NTS

    10 MTL ROOF AT RIDGE (TYP)NTS

    11 ROOF DRAIN FLASHING AT BUR (TYP) - SPD (P2.2) FOR OVERFLOW 06 BUR ROOF PENETRATIONS (TYP)SCALE: 3" = 1'-0"NTS USE FOR TYPICAL ROOF PENETRATIONS U.O.N.

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • SLO

    PE

    STEP 1 STEP 2

    STEP 3 STEP 4

    S

    lo

    p

    e

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A8.03EXT. DETAILS

    04 ROOF/PARAPET CONNECTION (TYP)SCALE: 3" = 1'-0"

    SCALE: 6" = 1'-0"08 BUR AT EQUIPMENT SUPPORT (TYP)

    SCALE: 3" = 1'-0"11 TYPICAL BUR DETAILS AT CORNERS

    SCALE: 3" = 1'-0"12 TYPICAL BUR - PLY SEQUENCE

    07 COPING/ROOF AT LOWER ROOF /CONC WALL (TYP)SCALE: 3" = 1'-0"

    INSTALL PER MFR'S RECOMMENDATION

    INSTALL PER MFR'S RECOMMENDATION

    NTS03 ROOF HATCH ROOFING DIAGRAM

    TYPICAL BUR DETAILS AT CORNERS

    SCALE: 3" = 1'-0"10

    1`-1/2" MIN EMBED(TYP)

    #8 X 1-1/2" SSSCREW (TYP)

    #8" SS WOOD SCREW W/1-1/2"MIN EMBED @ 12" O.C. (TYP).

    TOE-NAIL ALL CRICKET SUPPORT WITH 10D @6" O.C. (TYP)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    SCALE: 1-1/2" = 1' - 0"10 ROOF HATCH SECTION A8.04

    EXT. DETAILS

    SCALE: 1-1/2" = 1' - 0"03 BOLLARD BASE DETAIL - SECTION - SCD

    (REFERENCE 2/E0.1 - FROM SCCD SET 8-28-1995)

    SCALE: 3" = 1' - 0"01 ANCHOR BOLT AT EXT WALL - SSD

    SCALE: 1-1/2" = 1' - 0"11 ROOF HATCH PLAN

    SCALE: NTS08 SAFETY POLE/LADDER AT HATCH (TYP)

    SEE 8 & 11 / A8.04 & 3/A8.03 FOR ADD'L REQUIREMENTS (TYP)

    SEE MNR'S RECOMMENDATIONS FOR ADDITIONALDETTAILS FOR FRAMING SUPPORT, FLASHING ANDCLEARANCES ADJACENT TO WALL/SCURBS TOENSURE APPROPRIATE WATERPROOFING (TYP).

    GENERAL HATCH AND LADDER REQUIREMENTS PER 2016 CMC AND CEC, & CCR DIV 8, SEC 3277 (TYP):

    1. PER CMC 904.10.3.3 ACCESS DOORS SHALL BE AT LEAST TWENTY-TWO (22) INCHES X TWENTY-FOUR (24)

    INCHES IN SIZE, SHALL OPEN EASILY AND SAFELY UNDER ALL CONDITIONS, ESPECIALLY SNOW, AND SHALL BE

    CONSTRUCTED SO AS TO PERMIT ACCESS FROM THE ROOF SIDE UNLESS DELIBERATELY LOCKED ON THE

    INSIDE. AT LEAST SIX (6) FEET OF CLEARANCE SHALL BE AVAILABLE BETWEEN THE ACCESS OPENING AND THE

    EDGE OF THE ROOF OR SIMILAR HAZARD (TYP).

    2. ALL RUNGS SHALL HAVE A MINIMUM DIAMETER OF 3/4 INCH FOR METAL LADDERS. THE DISTANCE BETWEEN

    THE TOP SURFACES OF RUNGS, CLEATS, AND STEPS SHALL NOT EXCEED 12 INCHES AND SHALL BE UNIFORM

    THROUGHOUT THE LENGTH OF THE LADDER EXCEPT THE VERTICAL DISTANCE OF THE FIRST RUNG FROM

    GROUND LEVEL MAY BE AS HIGH AS 14 INCHES. METAL LADDERS AND APPURTENANCES SHALL BE PAINTED OR

    OTHERWISE TREATED TO RESIST CORROSION AND RUSTING WHEN LOCATION DEMANDS.

    3. THE MINIMUM DESIGN LIVE LOAD SHALL BE A SINGLE CONCENTRATED LOAD OF 300 POUNDS.

    4. ALL HATCH COVERS SHALL OPEN A MINIMUM OF 60 DEGREES FROM THE HORIZONTAL. THE DISTANCE FROM

    THE CENTER LINE OF RUNGS OR CLEATS TO THE EDGE OF THE HATCH OPENING ON THE CLIMBING SIDE SHALL

    BE NOT LESS THAN 24 INCHES FOR OFFSET WELLS OR 30 INCHES FOR STRAIGHT WELLS.

    1/4" SS WOOD SCREW

    3" MIN EMBED (TYP)

    VARIES VIF

    2-1/2"x1/4" MTL STRAP@4'-0" O.C. OF LADDER LENGTH, USE 3/8"WEDGE ANCHOR SSD FOR EMBED. @ CONC.WALL. , USE 1/4" BOLT AT LADDER (TYP)

    2-1/2x1/4" MTLANGLE TO FASTEN LADDERTO (E) PLYWD SUBSTRATE,1/4" THRU BOLT TO LADDER,LAG ANGLE TO FLOOR (TYP)

    1/4" SS WOODSCREW W/ 3"EMBED. ATHOLES PROVIDED(TYP).

    1/4" SS WOOD SCREW @ 8" OC W/ 2-1/2" EMBED (TYP)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A9.00INTERIORDETAILS

    SCALE: 1-1/2" = 1' - 0"01 SECTION @ACCESSIBLE SINK & COUNTERTOP

    SCALE: 1-1/2" = 1' - 0"04 SECTION @ADMIN OFFICE COILING SHUTTER

    SCALE: 3/4" = 1' - 0"06 PARTIAL PLAN @ADMIN OFFICE COILING SHUTTER

    SCALE: 1-1/2" = 1' - 0"10 PARTIAL ELEVATION @ADMIN OFFICE COILING SHUTTER

    SCALE: 3" = 1' - 0"14 TYPICAL JAMB DETAIL AT COILING DOOR

    2"x1/8" CONT. MTL ANGLE TOATTACH CABINET BASE AT SIDESTO FLOOR, USE #8 WD SCREWSAT 8" AT WOOD SIDE (DO NOTPENETRATE OUTER FACE) AND3/16" CONC SCREWS AT 8" O.C.PREDRILLED HOLES (TYP).

    ATTACH WITH#8 SMSCREWSTHROUGHMED-DUTYBACKING PER4/A0.01 @8"O.C. (TYP)

    PROVIDE 2"x1/4" CONTMTL ANGLE SUPPORT@ EDGE (TYP), USE 1/4"LAG ANCHOR EA END (TYP)

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    SCALE: 3" = 1' - 0"10 NON - RATED WALL SECTION A9.01

    INTERIORDETAILS

    NTS07 BACKING PLATE LIGHT LOADS

    NTS04 BACKING PLATE - MOD LOADS

    NTS01 BACKING PLATE - HEAVY LOADS

    SCALE: 1/4"=1'-0"08 TYPICAL WALL FRAMING CONTRACT

    SCALE: 6"=1'-0"05 PARTIAL WALL SECTION

    SCALE: 3" = 1' - 0"12 WALL SECTION @ (N) WALL RESTROOMS 111&112

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A9.02INTERIORDETAILS

    SCALE: 3/4" = 1'-0"10 PARTIAL ELEVATION 07 PLAN VIEW

    SCALE: 3/4" = 1'-0"

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • NTS02 COMPRESSION STRUT DETAIL (TYP)

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA BACKCHECK

    A9.03INTERIORDETAILS

    NTS05 HANGER GRID DETAIL (TYP)

    NTS11 PERIMETER DETAILS (TYP.)

    NTS10 ACCEPTABLE DETAILS - WIRE CONNECTIONS TO WOOD FRAMING

    12 SUSPENDED CEILING - EXPANSION DETAILS (TYP.)NTS

    06 SUSPENDED CEILING - EXITWAYS DETAILS (TYP.)NTS

    1. CBC SECTION 1615A1.16 (1615.10.13*) REQUIRES THE DESIGNAND INSTALLATION TO BE IN COMPLIANCE WITH ASTM C635,C636, AND E580, SECTION 5, AS AMENDED BY 2010 CBCSECTION 1615A.1.16 (1615.10.13*).

    2. NOTE: AMENDMENTS IN CBC SECTION 1615A.1.16 (1615.10.13*)REPLACE ASCE 7, SECTION 13.5.6.

    3. THE REQUIREMENTS IN THIS IR APPLY TO FLAT AND LEVELCEILING SYSTEMS WHOSE TOTAL WEIGHT INCLUDING CEILINGMOUNTAED AIR TERMINALS, SERVICES AND LIGHT FIXTURES, DOESNOT EXCEED FOUR (4) PSF. HEAVY SYSTEMS, SYSTEMS THAT ARENOT FLAT AND LEVEL, AND THOSE SUPPORTING LATERAL LOADSFROM PARTITIONS ARE BEYOND THE SCOPE OF THIS IR ADN WILLREQUIRE SPECIAL DESIGN DETAILS.

    4. USE TYPE S-12, 1" LONG, SELF DRILLING/TAPPING SCREW,FASTEN AT STRUCTURE, APPROX 16" OC AT 2" STANDARD 2" X 2"WALL LEDGER ANGLE TO CONNECT CEILING ASSEMBLY TO TOWALL (TYP).

    GENERAL NOTES:

    NTS05A COMPRESSION STRUT SIZING CHART (TYP)

    USE TYPE S-12, 1" LONG, SELF DRILLING/TAPPING SCREW, FASTENAT STRUCTURE, APPROX 16" OC AT 2" STANDARD 2" X 2" WALLLEDGER ANGLE TO CONNECT CEILING ASSEMBLY TO TO WALL(TYP).

    USE TYPE S-12, 1" LONG, SELF DRILLING/TAPPING SCREW, FASTENAT STRUCTURE, APPROX 16" OC AT 2" STANDARD 2" X 2" WALLLEDGER ANGLE TO CONNECT CEILING ASSEMBLY TO TO WALL(TYP).

    AC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • BUILDING STANDARD QUAD / DUPLEX RECEPTACLE

    LIGHTING CONTROL PANEL

    BUILDING STANDARD CEILING/WALL

    WALL MOUNTED / CEILING

    SHEET NOTE TAG.

    DATA / VOICE OUTLET BOX AT 18" AFF TO CENTER OF BOX.

    DIMMING SWITCH AT 48" AFF TO TOP OF BOX

    SURFACE / FLUSH MTD. PANELBOARD.

    LIGHT SWITCH AND SWITCH LEG IDENTIFICATION AT

    SPLIT-WIRED DUPLEX RECEPTACLE

    GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE

    CEILING MOUNTED EXIT LIGHT

    RECEPTACLE ON DEDICATED CIRCUIT AT 18" AFF TO

    BUILDING STANDARD HORSEPOWER RATED SWITCH.

    CEILING MOUNTED RECEPTACLE.

    AT 18" AFF TO CENTER OF BOX, U.O.N

    LEVITON 1221-2W, 20A, 120/277V AT 48" AFF TO TOP OF BOX

    BUILDING STANDARD STROBE.

    FLOOR MOUNTED DATA / VOICE OUTLET BOX

    MOUNTED STROBE HORN.

    208 VOLT RECEPTACLE

    TELEPHONE CABINET

    EQ

    X

    EQUIPMENT TAG

    LOW LEVEL WALL MOUNTED EXIT LIGHT

    MOUNTED JUNCTION BOX.

    FLOOR MOUNTED RECEPTACLE.

    LEVITON T5825-W, 20A, 125V

    AT 18" AFF TO CENTER OF BOX.

    ENERGEBCY POWER OFF BUTTON

    WITH COVER

    EMON DMON WATT METER

    48"AFF TO TOP OF BOX

    CENTER OF BOX, U.O.N.

    CEILING HEAT DETECTOR

    240 VOLT RECEPTACLE

    LIGHTING DAYLIGHT SENSOR

    LIGHTING NETWORK BRIDGE

    LIGHTING ROOM/ZONE CONTROLLER

    OCCUPANCY SENSOR

    EMERGENCY LIGHT WITHBATTERY BACK UP

    GENERAL NOTES,

    ABBREV. & LEGEND

    E0.10

    NO SCALE

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA RESUBMIT

    DSA RESUB. SET

    ISSUE FORREVIEWAC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • ELECTRICAL SPECIFICATIONS

    ELECTRICAL

    SPECIFICATIONS

    E0.11

    NO SCALE

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA RESUBMIT

    DSA RESUB. SET

    ISSUE FORREVIEWAC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • ENERGY

    COMPLIANCE FORMS

    E0.30

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STAMP

    OWNER:

    ARCHITECT:

    SHEET LEGEND:

    PROJECT:

    CONSULTANT TEAM:

    Solano Community College District2000 North Village ParkwayVacaville, CA 95688

    Vacaville Classroom Building(Annex) Renovation Project

    04/25/2017 ISSUE FOR DD 100%

    06/06/2017 ISSUE FOR CD 50%

    06/30/2017 ISSUE FOR CD 60%

    07/20/2017 ISSUE FOR CD 100%

    10/18/2017 DSA RESUBMIT

    DSA RESUB. SET

    ISSUE FORREVIEWAC_______ FLS _____ SS ____

    DATE: ________________________

    IDENTIFICATION STAMPDIVISION OF THE STATE ARCHITECT

    JCC GBC GBC

    PVL

    FILE: 48-C1

    02-116082

    10/31/2017

  • ENERGY

    COMPLIANCE FORMS

    E0.40

    DATE: DESCRIPTION:NO:

    DATE:PROJECT NO:PERMIT APPLICATION NO.:

    SCALE:

    ISSUE/REVISION:

    KEY PLAN:

    CA ARCHITECTS475 Gate Five Road, Suite 107Sausalito, CA 94965T 415.331.7655F 415.331.7656

    STA