Trouble Shooting BlueCool

download Trouble Shooting BlueCool

of 56

Transcript of Trouble Shooting BlueCool

  • 7/29/2019 Trouble Shooting BlueCool

    1/56

    Luft-Heizgerte

    Marine Air ConditioningSystemsFresh-Air Units

    03/2003

    OperationSettingsTrouble Shooting

    BlueCool Classic

    BlueCool Premium

  • 7/29/2019 Trouble Shooting BlueCool

    2/56

  • 7/29/2019 Trouble Shooting BlueCool

    3/56

    Improper installation or repair of Webasto heating and cooling systems can cause fire or theleakage of deadly carbon monoxide leading to serious injury or death.

    To install and repair Webasto heating and cooling systems you need to have completed aWebasto training course and have the appropriate technical documentation, special tools andspecial equipment.

    Only genuine Webasto parts may be used. See also Webasto air and water heaters accessoriescatalogue.

    NEVER try to install or repair Webasto heating or cooling systems if you have not completed aWebasto training course, you do not have the necessary technical skills and you do not havethe technical documentation, tools and equipment available to ensure that you can completethe installation and repair work properly.

    ALWAYS carefully follow Webasto installation and repair instructions and heed all WARNINGS.

    Webasto rejects any liability for problems and damage caused by the system being installed byuntrained personnel.

  • 7/29/2019 Trouble Shooting BlueCool

    4/56

    CONTENTS

    CONTENTS

    1 Digital Control Panel operation and settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    1.1 Operating and programming level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61.2 Entering programming menu level 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

    1.3 Entering programming menu level 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

    2 Programming Premium Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

    2.1 Programming level 2, Premium Card TECC 4.25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82.2 Programming level 3 at 29 C, Premium Card TECC 4.25 . . . . . . . . . . . . . . . . . . . . . . . . . .92.3 Programming level 3 at 15 C, Premium Card TECC 4.25 . . . . . . . . . . . . . . . . . . . . . . . . .10

    3 Programming Classic Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

    3.1 Programming level 2, Classic Card TCC 5.25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113.2 Programming level 3 at 29 C, Classic Card TCC 5.25 . . . . . . . . . . . . . . . . . . . . . . . . . . . .113.3 Programming level 3 at 15 C, Classic Card TCC 5.25 . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

    4 Programming Cabin Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

    4.1 Cabin Card 6.25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134.2 CAB V3 Card MTH2/PLANA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

    5 Programming Fresh-Air. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

    5.1 Digital Display Fresh-Air Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155.2 Start-up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155.3 Cycle Determination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165.4 Blower Speed Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165.5 Access Code. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .165.6 Visual Error Codes - Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

    5.7 Programming Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175.8 Cabin Card 6.25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195.9 CAB V3 Card MTH2/PLANA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

    6 Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

    6.1 Failure codes and trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216.2 Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24

    7 Controller Cards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    7.1 Classic / Select . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .257.2 Premium . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    7.3 Air handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

  • 7/29/2019 Trouble Shooting BlueCool

    5/56

    CONTENTS

    8 Electrical diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    8.1 Classic / Select TCC V3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 278.2 Classic / Select TCC V3 WB200 Pump Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288.3 Classic / Select, multiple units at one pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298.4 Select, blower speed controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308.5 Premium TECC V3, 1 and 2 compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    8.6 Premium TECC V3, add-on 3 and 4 compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 328.7 Premium, compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338.8 Premium TECC V3 with external heater. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348.9 Premium TECC V3 with calorifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358.10 Premium TECC V2, 1 compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368.11 Premium TECC V2, add-on 3 and 4 compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378.12 Premium, MTH mechanical thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 388.13 Premium, CAB V3 controller card + MTH2 thermostat + 3-way valve. . . . . . . . . . . . . . . . . 398.14 Premium, CAB V3 controller card + Plana thermostat + 3-way valve . . . . . . . . . . . . . . . . . 408.15 Premium, CAB V3 controller card + Digital Display Panel + 3-way valve . . . . . . . . . . . . . . . 418.16 Premium, Silent 5-speed for Compact and Slimline air handlers. . . . . . . . . . . . . . . . . . . . . 428.17 Premium, convert Danfoss into Lizhan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    8.18 Fresh-Air units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    9 Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    10 Blowers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    11 BlueCool Unit Performance Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

  • 7/29/2019 Trouble Shooting BlueCool

    6/56

    Digital Control Panel operation and settings

    6

    1 Digital Control Panel operation and settings

    1.1 Operating and programming level 1

    Highervalues

    Chiller Control

    Cool

    Auto

    Heat

    Read-out

    Blower speed Lower valuesSet-up / programming

    Cool cycle

    mode

    Automaticmode

    Heat cyclemode

    On / Off

    Highervalues(Sun)

    Read-out(0)

    Lower values(Snow flake)

    Blower speedFunction(F)

    Cool cycle

    mode

    Automaticoperation

    Heat cyclemode

    On / Off

    ON Push 1x, display will show ON. During first start-up display will also flash thecurrent frequency (50H = 50 Hz).After INIT, finally the room temperature will appear. Air-blower or chilledwater pump (Premium only) will start.Depending on controller setting unit will start in cooling or heating mode. Incase error codes appear, see trouble shooting.

    OFF Push 1x, unit and display will automatically shut-off when running.

    MEMO(NENO) Push 1x, to memorise new settings during programming.

    RETURN Push 1x, display will return to room temperature when programming.

    FUNCTION Push 1x, shows b.. for blower setting.Push 2x, shows E.. or H.. for coil or water temperature.

    Push 3x, shows CODE, enter code for access programming level 2.(Default=64) Classic/Select only

    Change b.. or enter CODE by pushing up or down key.

    NEXT LINE Push 1x, for next line and memorise new setting.

    DOWN Push 1x will show actual setpoint, again to lower setpoint.

    BLOWER SPEED Shows actual blower speed setting, bA automatic control or b1-b5 manual,adjustable by up or down.

    UP Push 1x will show actual setpoint, again to raise setpoint.

    During operation failure codes might appear on the display (see troubleshooting), when these are solved,controller will restart within 60 seconds.When the same failure occurs 6 times within 30 minutes the unit will stop completely without restart, LEDswill flash in the display until cause is solved. The counter is reset after 5 minutes of compressor operation.Failure code A01 has a time delay of approximately 40 seconds to avoid cut-out during start-up.

  • 7/29/2019 Trouble Shooting BlueCool

    7/56

    Digital Control Panel operation and settings

    7

    1.2 Entering programming menu level 2

    When security CODE is activated, push FUNCTION when unit is in operation till CODE appears in the display.

    Set security CODE by pushing UP or DOWN and confirm with FUNCTION (Default = 64).

    In case security CODE is not activated you will have direct access.

    Scroll through settings by pushing FUNCTION, values can be set by UP or DOWN keys and confirmed by FUNCTION fornext line.

    To leave this menu push ON/OFF, MEMO will be shown shortly and new settings will be memorised.

    1.3 Entering programming menu level 3

    Set setpoint temperature on 15 C or 29 C and switch off the controller.

    Push UP and DOWN simultaneously till display lights up.

    Set security CODE when activated by pushing UP or DOWN and confirm with FUNCTION (Default = 64).

    Scroll through settings by pushing FUNCTION, values can be set by UP or DOWN keys and confirmed by FUNCTION fornext line.

    To leave this menu push ON/OFF, MEMO will be shown shortly and new settings will be memorised.

  • 7/29/2019 Trouble Shooting BlueCool

    8/56

    Programming Premium Unit

    8

    2 Programming Premium Unit

    2.1 Programming level 2, Premium Card TECC 4.25

    Display Setting Default Min Max Unit

    b Selection of blower speed A 0 A

    H Water temperature

    F Selection of function mode 3 1 5

    Cool Only F1

    Heat Only F2

    Automatic cooling/heating with reverse cycle F3 C5 use

    Automatic cooling/heating with external heater F4

    Heat Only with external heater F5U Reading of voltage supply 0 Volt

    1C Choice compressor 1 ON/OFF 1 0 1

    2C Choice compressor 2 ON/OFF 1 0 1

    3C Choice compressor 3 ON/OFF 1 0 1

    4C Choice compressor 4 ON/OFF 1 0 1

    P Priority order for compressors 1-4 123

    L Time delay between compressor starts 1-4 9 1 9 seconds

    1L Switch off temperature delay for compressor 1 0 0 55 1/10

    2L Switch off temperature delay for compressor 2 0 0 55 1/10

    3L Switch off temperature delay for compressor 3 0 0 55 1/10

    4L Switch off temperature delay for compressor 4 0 0 55 1/10

    d Dehumidification cycle when system turned off (0 = non ac-tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per24h)

    0 0 3

    t Time to display table F 1 1 12 20 sec.

    S Choice of chilled water temperature sensor outlet or inlet 1 0 2

    c Temperature difference between compressor starts 15 0 99 1/10

    E Max temperature difference between chilled water outlet andinlet

    80 10 99 1/10

  • 7/29/2019 Trouble Shooting BlueCool

    9/56

    Programming Premium Unit

    9

    2.2 Programming level 3 at 29 C, Premium Card TECC 4.25

    Display Setting Default Min Max Unit

    0 Lower cut-out value in cool mode for chilled water tempera-ture outlet

    4 0 15

    1 Cut-in value in cool mode for chilled water temperature outlet 7 2 18

    2 Higher cut-out value in heat mode for chilled water tempera-ture outlet

    40 30 49

    3 Cut-in value in heat mode for chilled water temperature outlet 37 27 52

    4 Calibration chilled water temperature 0 -55 55 1/10

    5 Time for display standby 15 5 99 minutes

    6 Calibration of chilled water temperature inlet 0 -55 55 1/10

    7 Calibration of air temperature 0 -55 55 1/10

    8 Calibration of voltage under 50 Hz 0 -30 50

    9 Select function of relais 0 0 3

    Operating as staging relay 0

    Controlling 3 way valve air handler by TECC card 1

    Alarm indication 2

    Cycle indication 3 For C5 use

    A Calibration of voltage under 60 Hz -10 -30 50

    b Program Version 4.2*

    c Lower cut-out value in cool mode for chilled water tempera-

    ture inlet

    6 0 15

    d Cut-in value in cool mode for chilled water temperature inlet 9 2 18

    E Higher cut-out value in heat mode for chilled water tempera-ture inlet

    40 30 49

    F Cut-in value in heat mode for chilled water temperature inlet 37 27 52

  • 7/29/2019 Trouble Shooting BlueCool

    10/56

    Programming Premium Unit

    10

    2.3 Programming level 3 at 15 C, Premium Card TECC 4.25

    Display Setting Default Min Max Unit

    0 Cut-out value for low voltage 195 160 210 Volt

    1 Remote control activated/deactivated 0 0 1

    2 Choice of small relay setting indicating heat/cool cycle

    0 = C1 + T1 closed at heat cycle (F4, F5).C1 + R1 closed at cool cycle (F1, F3, F4).C1 + R1 closed at system block.00 Chiller1 = For fault messages, system block (A01, A02, A09 etc.)C1 + R1 closed, no faults.C1 + T1 closed, system block/ failures.

    0 0 1

    0 for C5

    3 Choice of thermostatic regulation or permanent ventilation 0 0 1

    4 Choice of internal/external air temperature sensor 0 0 1

    5 Choice of temperature reading in C or F 0 0 1

    6 Calibration of blower speed 5 70 1 70

    7 Calibration of blower speed 4 40 1 70

    8 Calibration of blower speed 3 35 1 70

    9 Calibration of blower speed 2 29 1 70

    A Calibration of blower speed 1 23 1 70

    b Access code for programming levels 0 0 99

    C Duration of heat cycle in dehumidification mode 1 1 99 minutes

    D Duration of cool cycle in dehumidification mode 1 1 99 minutes

    E Delay before first start 1 1 20 seconds

  • 7/29/2019 Trouble Shooting BlueCool

    11/56

    Programming Classic Unit

    11

    3 Programming Classic Unit

    3.1 Programming level 2, Classic Card TCC 5.25

    3.2 Programming level 3 at 29 C, Classic Card TCC 5.25

    Display Setting Default Min Max Unit

    b Selection of blower speed A 0 A

    F Selection of function mode 3 1 5

    U Reading of voltage supply 0 Volt

    1C Choice compressor 1 ON/OFF 1 0 1

    d Dehumidification cycle when system turned off (0 = non ac-tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per24h)

    0 0 3

    t Time to display table F 5 1 5 20 sec.

    Display Setting Default Min Max Unit

    0 Lower cut-out value in cool mode for evaporator temperature 0 -4 15

    1 Cut-in value in cool mode for evaporator temperature 7 2 18

    2 Higher cut-out value in heat mode for evaporator temperature 45 30 50

    3 Cut-in value in heat mode for evaporator temperature 38 27 47

    4 Calibration evaporator temperature 0 -55 55 1/10

    5 Time for display standby 15 5 99 minutes

    6 Time delay for first compressor start 1 1 20 seconds

    7 Calibration of air temperature 0 -55 55 1/10

    8 Calibration of voltage under 50 Hz 0 -30 50

    9 Time delay for compressor restart after end of cycle cut-out 2 1 99 minutes

    A Calibration of voltage under 60 Hz 0 -30 50

    B Program version v5.2*

    C Mode choice for pump exit 0 0 1D Minimum voltage for pump exit 12 12 18 Volt

    E Maximum voltage for pump exit 18 12 18 Volt

    F Mode choice for water valve exit 1 0 1

  • 7/29/2019 Trouble Shooting BlueCool

    12/56

    Programming Classic Unit

    12

    3.3 Programming level 3 at 15 C, Classic Card TCC 5.25

    Display Setting Default Min Max Unit

    0 Cut-out value for low voltage 195 160 210 Volt

    1 Remote control activated/deactivated 0 0 1

    2 Choice of blower type0 = blower speed regulated1 = blower speed uninterrupted

    1 0 1

    3 Choice of thermostatic regulation or permanent ventilation 1 0 1

    4 Choice of internal/external air temperature sensor 0 0 1

    5 Choice of temperature reading in C or F0 = C, 1 = F

    0 0 1

    6 Calibration of blower speed 5 70 1 70

    7 Calibration of blower speed 4 40 1 70

    8 Calibration of blower speed 3 35 1 70

    9 Calibration of blower speed 2 29 1 70

    A Calibration of blower speed 1 23 1 70

    b Access code for programming levels 64 0 99

    C Duration of heat cycle in dehumidification mode 1 1 99 minutes

    D Duration of cool cycle in dehumidification mode 1 1 99 minutes

  • 7/29/2019 Trouble Shooting BlueCool

    13/56

    Programming Cabin Controls

    13

    4 Programming Cabin Controls

    4.1 Cabin Card 6.25

    4.1.1 Setting

    4.1.2 Programming level 3 at 29 C, Cabin Card 6.25

    4.1.3 Programming level 3 at 15 C, Cabin Card 6.25

    Display Setting Default Min Max Unit

    b Selection of blower speed A 0 A

    H Water temperature

    F Selection of function mode 1 1 3

    d Dehumidification cycle when system turned off (0 = non ac-tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per24h)

    0 0 3

    t Time to display table F 1 1 5 20 sec.

    Display Setting Default Min Max Unit

    4 Calibration chilled water temperature 0 -55 55 1/10

    5 Time for display standby 15 5 99 seconds

    6 Time delay for first start 5 1 20

    7 Calibration of air temperature 0 -55 55 1/10

    b Program version v6.2*

    Display Setting Default Min Max Unit

    1 Remote control activated/deactivated 0 0 1

    2 Choice of blower type 1 0 2

    3 Choice of thermostatic regulation or permanent ventilation 0 0 1

    4 Choice of internal/external air temperature sensor 0 0 1

    5 Choice of temperature reading in C or F0 = C, 1 = F

    0 0 1

    6 Calibration of blower speed 5 70 1 70

    7 Calibration of blower speed 4 40 1 70

    8 Calibration of blower speed 3 35 1 70

    9 Calibration of blower speed 2 29 1 70

    A Calibration of blower speed 1 23 1 70

    b Access code for programming levels 0 0 99C Duration of heat cycle in dehumidification mode 1 1 99 minutes

    D Duration of cool cycle in dehumidification mode 1 1 99 minutes

  • 7/29/2019 Trouble Shooting BlueCool

    14/56

    Programming Cabin Controls

    14

    4.2 CAB V3 Card MTH2/PLANA

    Version CAB 9.03

    Display Setting Default Air Handler

    SP Speed Position selector switch SP...(0/1/2/3)

    tF 00 = blower off 01

    1 Setting fan speed level 1 (low) 23

    2 Setting fan speed level 2 35

    3 Setting fan speed level 3 (high) 70

  • 7/29/2019 Trouble Shooting BlueCool

    15/56

    Programming Fresh-Air

    15

    5 Programming Fresh-Air

    The Fresh-Air controller cards allows the end-user to precise-ly control the fresh-air temperature introduced into the dif-ferent volumes of the vessel. It also allows humidity control.

    Basically the end-user sets a differential between the outsideair temperature and the air temperature he wants to intro-duce into the vessel. There is also a ceiling limit which canbe programmed separetly to avoid that the freshair temper-ature becomes too cold and uncomfortable during night op-eration when outside temperatures drops too low.

    5.1 Digital Display Fresh-Air Control

    The Fresh-Air Control display will give the following imme-

    diate read-outs :

    1) Normal Read-out: Air-out temperature after treatment.

    Push key to obtain (examples):

    2) 2b 3 = Extraction Blower setting3) 1b 3 = Fresh-Air blower setting4) H 9.6 = chilled water temp. read-out5) E 35.2 = outside air temp. read-out6) U232 = AC voltage input reading

    5.2 Start-up Procedures

    When starting up the Fresh-Air control the Fresh-air blowerswill operate at the lowest possible speed setting to drawdown the air-out temperature as quickly as possible to thereference set-point and to eliminate accumulated moisturein the air-ducting.

    After the start-up period the Fresh-Air blower speed will re-sume operation at the speed setting as initially pro-grammed.

    Speed setting of the Fresh-Air and Extraction Air blowerscan be different so as to obtain the desired over-pressure inthe vessel.

    The key also gives access to such parameters as: reheat 1/2 on/off time delay between Fresh-Air Blower start and Extraction

    Blower start-up differential between Reheat 1/2 cut-in and reference set-point.

    See also page 2 - Programming procedures.

    Highervalues(Sun)

    Read-out(0)

    Lower values(Snow flake)

    Blower speedFunction(F)

    Cool cyclemode

    Automaticoperation

    Heat cycle

    mode

    On / Off

  • 7/29/2019 Trouble Shooting BlueCool

    16/56

    Programming Fresh-Air

    16

    5.3 Cycle Determination

    Here-above drawings explain the operating window withthe associated setpoints and reheat differentials.

    The choice between heat cycle and cool cycle is done auto-matically by the controller card depending on the chilled

    water temperature as recorded by the controller card. Theswitching temperature is determines by the programminglines 3 and 4 (snow key).Factory settings are as following:Lower ceiling : 18 CHigher ceiling : 20 C

    This means that below 18 C chilled water temperature thefresh-air controller considers that cool cycle operation is re-quired; above 20 C the controller switches to heat cycle op-eration. Between 18 C and 20 C the controllers suspendscontrolling activity and waits to see which cycle is definitelyadopted.

    5.4 Blower Speed Regulation

    As already explained blower speed can be set in a differen-tial way between the Fresh-Air blowers (1b) and the Extrac-tion Blowers (2b).

    In addition the Fresh-Air blowers can be set manually on afixed speed without any reference to the chilled water tem-perature and/or outside/inside air temperatures or start-up

    procedure. This choice can be made in programming mode(sun key - line 9).

    5.5 Access Code

    The end-user can deny access to all program settings by in-troducing an access code (see page 8 - code ). Blowerspeed and setpoints always remain accessible.

    Once an access code is validated, the digital panel will show if the end-user tries to access other functions thenblower speed or set-point. To gain full access push the sunkey to reach the code number as programmed and push the key again to gain access to full program settings.

    5.6 Visual Error Codes - Digital Display

    The following malfunctions will be displayed directly on thedigital display by a code and will be followed by a system

    halt.Whenever any of these codes appear the system is stoppedfor approx. 60 seconds and then a re-start is attempted.

    If for more than 30 minutes the same malfunction occurs,the system will be stopped completely and the error-codewill become steady.

    No more re-starts will be attempted and the user will haveto re-set the system by pushing the ON/OFF switch or bytemporarily cutting out the AC supply to the system.

    35C24C22C20C

    5C 24C22C21.5C

    Reference Setpoint

    Example of operating window setting - Fresh-Air Control - Cool Cycle

    Reheat 2 cuts in at 20 - cuts out at 22Cooling Coil 3 way valve cuts out at 20and cuts in again at 22

    Reheat 1 cuts in at 22 - cuts out at 24

    Reference Setpoint Ceiling Limit = 20 - i.e. reference setpoint will always be 20 C or higher

    Outside air temperature

    Differential = 16 C - Prog. Line 0 - Sun Key

    Outside air temperature

    Differential = 18 C - Prog. Line 2 - Sun Key

    Reference Setpoint Ceiling Limit = 24 - i.e. reference setpoint will always be 24 C or lower

    Reference Setpoint

    Reheat 1 cuts out at 24 - cuts in at 22Heating Coil 3 way valve cuts out at 24and cuts in again at 22

    Reheat 2 cuts out at 22 - cuts in at 21.5

    Example of operating window setting - Fresh-Air Control - Heat Cycle

  • 7/29/2019 Trouble Shooting BlueCool

    17/56

    Programming Fresh-Air

    17

    List of error-codes and nature of malfunction:

    Code :

    Persistent low voltage (voltage below 185 V) for more than5 seconds.

    - absent or defective external air sensor

    - absent or defective treated air sensor

    - absent or defective chilled water sensor

    Code A02 :

    Check the straps on HP/BP connectors

    5.7 Programming Parameters

    Three levels of programming parameters are available to theend user:

    A) through (Func tion) key

    2b 3 = Extraction blower(s) - 5 manual speeds can be pro-grammed - last setting is memorized.

    1b 3 = Fresh-Air blowers - 5 manual speeds can be pro-grammed - last setting is memorized.

    1r01 = reheat N 1 activated.

    1r00 = reheat N1 on standby.

    2r01 = reheat N 2 activated.

    2r00 = reheat N 2 on standby.

    L 09 = time delay between 1b (Fresh-air blower) and 2b (Ex-traction blowers) in seconds.

    1L2.0 = temperature differential reheat N 1 operation asmeasured from reference setpoint (2.0 C).

    2L2.5 = temperature differential reheat N 2 operation asmeasured from reference setpoint (2.5 C).

    d 0 = number of dehumidifying cycles per 24 Hours (if suchcycle is programmed in absence - see programming by snowkey).

    t 1 = number of minutes before display switches back to air-out temperature read-out after the key is used.

    B) Programming through Sun Key

    To enter this programming mode, first switch off Display byon/off key, then push Sun Key for 3 seconds. You will nowenter Sun Key programming mode as following:

    0 16 = temperature differential in C for cool cycle opera-tion. Max = 25 C - mini = 5 C.

    1 20 = max lower ceiling of reference setpoint cool cycle.Mini = 10 - max = 30 C.

    2 18 = temperature differential in C for heat cycle opera-tion. Max = 35 C - mini = 10 C.

    3 24 = max. higher ceiling for reference setpoint heat cycle.Mini = 10 - max. = 35 C.

    4 0.0 = temp. read out calibration chilled water sensor(from -9.9 to +9.9 C).

    5 15 = number of minutes before the Digital Display switch-es into sleep mode. Max. = 99 minutes.

    6 0.0 = outside air temperature sensor calibration.

    7 0.0 = air-out (after treatment) temperature calibration.

    8 00 = AC voltage reading calibration 50 Hz.

    9 01 = choice between normal procedure Fresh-Air blower

    operation of manual fixed speed.0 = manual speed regardless of all operating procedures.

    a 00 = AC voltage reading calibration - 60 Hz

  • 7/29/2019 Trouble Shooting BlueCool

    18/56

    Programming Fresh-Air

    18

    C) Programming through Snow Key

    To enter this programming mode, first switch off Display byon/off key, then push Snow Key for 3 seconds. You will nowenter Snow Key programming mode as following:

    0185 = AC voltage low safety cut-out (185 V)

    1 0 = infrared remote control disabled.

    1 1 = infrared remote control enabled.

    2 1 = type of blower used:0 = standard centrifugal1 = cross-flow

    3 18 = lower ceiling switch-over window between cool andheat cycle (18)

    4 20 = higher ceiling switch-over window between cool andheat cycle (20)

    5 00 = Temperature read-out in Celsius or Fahrenheit0 = Celsius1 = Fahrenheit

    6 70 = calibration blower speed N 5

    7 40 = calibration blower speed N 4

    8 29 = calibration blower speed N 3

    9 29 = calibration blower speed N 2

    a 23 = calibration blower speed N 1

    b 64 = programming access code-locked00 = no access code required01 to 99 = access code required

    c 01 = duration of dehumidifying heat cycle in minutes

    d 01 = duration of dehumidifying cool cycle in minutes.

  • 7/29/2019 Trouble Shooting BlueCool

    19/56

    Programming Fresh-Air

    19

    5.8 Cabin Card 6.25

    5.8.1 Setting

    5.8.2 Programming level 3 at 29 C, Cabin Card 6.25

    5.8.3 Programming level 3 at 15 C, Cabin Card 6.25

    Display Setting Default Min Max Unit

    b Selection of blower speed A 0 A

    H Water temperature

    F Selection of function mode 1 1 3

    d Dehumidification cycle when system turned off (0 = non ac-tive; 1 = 1 cycle per 24h; 2 = 2 cycles per 24h ; 3 = 3 cycles per24h)

    0 0 3

    t Time to display table F 1 1 5 20 sec.

    Display Setting Default Min Max Unit

    4 Calibration chilled water temperature 0 -55 55 1/10

    5 Time for display standby 15 5 99 seconds

    6 Time delay for first start 5 1 20

    7 Calibration of air temperature 0 -55 55 1/10

    b Program version v6.2*

    Display Setting Default Min Max Unit

    1 Remote control activated/deactivated 0 0 1

    2 Choice of blower type 1 0 2

    3 Choice of thermostatic regulation or permanent ventilation 0 0 1

    4 Choice of internal/external air temperature sensor 0 0 1

    5 Choice of temperature reading in C or F0 = C, 1 = F

    0 0 1

    6 Calibration of blower speed 5 70 1 70

    7 Calibration of blower speed 4 40 1 70

    8 Calibration of blower speed 3 35 1 70

    9 Calibration of blower speed 2 29 1 70

    A Calibration of blower speed 1 23 1 70

    b Access code for programming levels 0 0 99

    C Duration of heat cycle in dehumidification mode 1 1 99 minutes

    D Duration of cool cycle in dehumidification mode 1 1 99 minutes

  • 7/29/2019 Trouble Shooting BlueCool

    20/56

    Programming Fresh-Air

    20

    5.9 CAB V3 Card MTH2/PLANA

    Version CAB 9.03

    Display Setting Default Air Handler

    SP Speed Position selector switch SP...(0/1/2/3)

    tF 00 = blower off 01

    1 Setting fan speed level 1 (low) 23

    2 Setting fan speed level 2 35

    3 Setting fan speed level 3 (high) 70

  • 7/29/2019 Trouble Shooting BlueCool

    21/56

    Trouble Shooting

    21

    6 Trouble Shooting

    6.1 Failure codes and trouble shooting

    Failurecode

    Description Possible cause Solution

    AAA Low Voltage Low voltage cut-out. Power supply wasover 5 sec lower than controller setting.Probably caused by long length powersupply cable or overload.

    Check setting, default 195 V.Don't set below 195 V to avoid damagesto the compressor or to expire warranty.Improve power supply.

    A01 Low pressure cut-outcompressor 1(Classic > 20.000 BTU)15 - 35 PSI /1 - 2.4 bar

    Defective pressure sensor or open/shortcircuit.

    Check wiring or replace pressure sensoron Schrader valve.

    COOLING MODE:- Insufficient evaporator water flow

    (Premium) or air flow (Classic).

    - Air lock in water circuit (Premium) orbroken circulation pump.

    Check water or air flow.T evaporator in/out minimum 4K.Bleed Premium water system; check

    pump operation.

    HEATING MODE:- Insufficient seawater flow or seawater

    to cold.- Blocked sea-water strainer or not

    primed.

    Check discharge water volume.V= 8 l/min(or > 30,000 BTU V= 18 l/min).T in/out minimum 4K.When T seawater < 4 C: preheatingnecessary.Clean strainer and bleed seawater circuit.

    Lack of refrigerant. Refrigerant leak check.

    A02 High pressure cut-out

    compressor 1350 - 250 PSI /24 - 17.24 bar

    Defective pressure sensor or open/short

    circuit.

    Check sensor and wiring. Replace sensor

    on Schrader if necessary.

    COOLING MODE:- Insufficient seawater cooling or

    defective circulation pump.- Blocked seawater strainer or not

    primed.

    Check discharge water volume.V= 8 l/min(or > 30,000 BTU V= 18 l/min).Clean strainer and bleed sea-water circuit.

    HEATING MODE:- Insufficient evaporator water flow

    (Premium) or air flow (Classic).- Air lock in chilled water circuit

    (Premium) or broken circulation pump.

    Check water or air-flow.T evaporator in/out minimum 4K.Bleed chilled water system or check pompoperation.

    A03 Low pressure cut-outcompressor 2(Premium only)

    See A01 See A01

    A04 High pressure cut-outcompressor 2(Premium only)

    See A02 See A02

    A05 Low pressure cut-outcompressor 3(Premium only)

    See A01 See A01

    A06 High pressure cut-outcompressor 3(Premium only)

    See A02 See A02

  • 7/29/2019 Trouble Shooting BlueCool

    22/56

    Trouble Shooting

    22

    A07 Low pressure cut-outcompressor 4(Premium only)

    See A01 See A01

    A08 High pressure cut-outcompressor 4(Premium only)

    See A02 See A02

    A09 Cabin temperaturesensor failure(internal and external)

    Broken internal or external temperaturesensor, open/short circuit, not present orprogrammed wrong.

    Replace sensor or controller.In case of external sensor try to reprogramto internal sensor first to determinefailure.

    A10 Evaporator temperaturesensor failure.

    Defective water temperature sensor(Premium), evaporator sensor (Classic) oropen/short circuit.

    Check wiring or replace sensor.Water infiltration (condense) can cause aread-out derivation or erratic functioningbefore an error code occurred.

    CA11 All compressors manuallyoff.

    Compressor(s) programmed not active incontroller setting.

    Check settings. At least one compressorshould be programmed active.C01=ON C00=OFF

    bA11 Fan standby. Blower operation from TECC card orcabin controller impossible.Discharge temperature higher than setpoint on cooling or lower on heating.

    Run compressor/unit for a certain time toreach required discharge temperature.Blower fan will start and blinking errorcode bA11 will disappear automatically.

    tA11 Tlow (in cool mode,deicing) or Thigh (in heatmode) limit exceeded.

    Compressor stopped to defrost or to cooldown in heat mode.

    Compressor exceeded limits. Automaticrestart, no complete system halt.Code visible in the display insteadof evaporator coil temperature.

    Press key (5) to read out evaporatorcoil temperature or code (F key -line E).Check controller settings to be set default(29 C line 0, 1, 2 and 3).

    EA11 T between chilled waterIN/OUT above limit(Premium only).

    Insufficient evaporator water flow. Check controller settings, see 29 Csettings line F.Check water flow, T evaporator in/outminimum 4K.Bleed water system or check pumpoperation.

    init Initialization procedure orsystem block.

    Setting DIP switches not according to thenumber of compressors.

    Check setting DIP switches.

    Defective wiring,open/short circuit.

    Check control panel controller cable andconnections.Replace defective cable, panel orcontroller card.

    n/a No output on printboard. Defective fuse or open/short circuit onspecific circuit.

    Repair or replace fuse,open/short circuit or replace printboard.

    Printboard damaged by high voltage (forPremium RT1 burnt)

    Replace printboard.

    Broken electronic relay (TRIAC) Replace defective TRIAC or printboard

    (operation of TRIAC can easily be testedwith a 40 W light bulb).

    Failurecode

    Description Possible cause Solution

  • 7/29/2019 Trouble Shooting BlueCool

    23/56

    Trouble Shooting

    23

    n/a Compressor not running. Broken compressor or open/short circuitcompressor wiring.

    Repair wiring or replace defectivecompressor.

    Compressor overload or broken Overload

    Protector (OLP) on top of the compressor.

    Wait a certain time to cool down or

    replace defective OLP.

    Compressor settings incorrect. Check settings, at least one compressorshould be programmed active.C01=ON C00=OFF

    n/a Seawater pump(s)running directly afterpower up controller.

    Wiring pump 1 (seawater) mixed-up withpump 2 (chilled water).

    Check wiring.

    n/a Compressor starts orstops continuously.

    Lack of chilled water. Check for leaks in water system.

    n/a No or insufficient cooling

    or heating performance.

    Bad air flow or water flow,

    filthy or blocked circulation.

    Ensure air or water flow

    (see A01 and/or A02).Lack of refrigerant. Lack of refrigerant mostly recognized by a

    low static pressure before start-up andnon-fluctuating LP associated with a lowHP pressure reading.Check for refrigerant leaks, repair ifnecessary and charge required amount ofrefrigerant.

    Oil lock. Operate the unit in heat cycle.Intervention by a refrigerant specialistmight be necessary.Technical Memo available.

    Blocked refrigerant circuit.(Drier, capillary or expansion valve).

    To be determined by a refrigerantspecialist.Technical Memo available.

    Bad compressor. To be determined by a refrigerantspecialist.

    n/a Pumps runningcontinuously.

    When additional relays are used tooperate pumps a small leaking currentfrom the printboard may operate the relaycontinuously.

    Remove R56 + C24 and/or R57 + C27from the printboard.

    n/a Inaccurate temperature

    read-out of room /ambient temperature,water temperature(premium) or evaporatortemperature (classic).

    Temperature sensor not installed on the

    right position, interference byenvironment or read-out deviation.

    Check for interference by direct sunlight,

    heat radiation from components near tothe sensor.Calibrate sensor.Replace defective sensor.

    n/a Blower not running. Defective fuse or open/short circuit onspecific circuit.

    Repair or replace fuse, open/short circuitor replace print board.

    Check fan by testing with direct currenton fan.Replace fan if still not running.

    Check if blower setting is not at B0.

    Put blower setting to B1 - BA.

    Failurecode

    Description Possible cause Solution

  • 7/29/2019 Trouble Shooting BlueCool

    24/56

    Trouble Shooting

    24

    6.2 Capacitors

    6.2.1 Run capacitor

    A run capacitor is installed to offset the magnetic field in thestator windings of a electric motor. When the run capacitorfails, the rotor will block on LRA (locked rotor amperage)and refuses to start running. Start attempts will result in cut-out by overload protection, repeated failed start-ups and ig-nored overload cut-outs will eventually lead to motor fail-ures instead of a simple capacitor replacement.

    6.2.2 Start capacitor

    A start capacitor is installed to offset the wave signal fre-

    quency during start-up. Capacitor failures will lock the rotoron LRA (locked rotor amperage) and refuses to start runninga electric motor. Start attempts will result in cut-out by over-load protection, repeated failed starts and ingnored verloadcut-outs will eventually lead to complete motor failures in-stead of a simple capacitor replacement. Start capacitor fail-ures will most likely cause excessive voltage drops on start-up and/or when running.

    6.2.3 Trouble shooting capacitors

    Broken capacitors will cause a rotor blockage on LRA,allowing a rotor only to turn slowly or cause excessivevoltage drops.

    1) When there is a presumption of a broken run capacitorfirst disable one of the wires of the start capacitor whenapplied.

    2) Try to start the motor/compressor again, if there is still aLRA blockage replace the run capacitor.

    3) If the motor/compressor attempts to start after a

    capacitor replacement and runs apparently normal,check the running amps to see if there are no damagesto the motor windings. When the amp read-out is fareabove normal, the windings are damaged and themotor or compressor should be replaced.

    4) Re-connect the start capacitor and test again to see ifstart-up and running is normal.Faulty start capacitors will give excessive voltage dropson start-up and/or when running. Replace startcapacitor if necessary.

    6.2.4 Trouble shooting controller cards

    The AC-output of a controller card is done through elec-tronic relays also called TRIACS mounted against an heat-sink for cooling.All TRIACS are protected by slow fuses except the maincompressor outlets COMP1 and COMP2. TRIAC failures cancause electrical problems.

    a) a TRIAC remains open, no active current on the AC out-let connector.

    b) a TRIAC remains closed, continuously AC outputpresent on the connector.

    When there is a presumption of a TRIAC failure first checkthe protective fuses to be OK. TRIAC failures are more likelyas a OPTO-COUPLER failure (I.e. the electronic device thatinterfaces the micro-processor with the power Triac). OPTO-COUPLER failures are more wise to return to the factory forrepair and testing.

    Replacing a TRIAC BTA26 can be done easily by unweldingand replaced at low cost, therefore to be available on stock.

    To test the AC output of a TRIAC on a outlet connector isimportant to test this with a electronic ballast such as a

    40 Watt light-bulb for example.An electronic volt/multi-meter is not adequate to test be-cause a TRIAC is generally allowed to leak current to deceivea electronic meter.Only when necessary a complete controller card can be re-placed. Before replacing a card make sure that the amper-age draw on the AC-output is in relation to the operationconditions shown as I [A] in the tabel with capacitors.

    Use only slow-blow fuses as replacement for all controllers!

  • 7/29/2019 Trouble Shooting BlueCool

    25/56

    Controller Cards

    25

    7 Controller Cards

    7.1 Classic / Select

    7.2 Premium

    CPAC - TCCController V2

    < 2004

    CPAC - TCCController V3

    2004 >

    Fuses V2 series

    Fuses V3 series:F1 Print board 315 mAF2 Pump 3.15 AF3 Valve 3.15 AF4 Fan 3.15 A

    Dipswitch settings V2 series

    WBCL000828

    Chiller - TECCController V2

    < 2006

    Chiller - TECCController V3.1

    2006 >

    Fuses V2 series

    Fuses V3 series:F1 Print board 315 mAF2 Fan 6.3 AF3 Valve 3.15 A

    F4 Pump 1 SW 3.15 AF5 Pump 2 CW 3.15 A

    Dipswitch settings V2 series

    WBCL000864

    1 and 2 com-pressors

    3 and 4 com-pressors

  • 7/29/2019 Trouble Shooting BlueCool

    26/56

    Controller Cards

    26

    7.3 Air handler

    Air handler - CABController V2

    < 2005

    Fuses V3 models:F1 Print board 315 mAF2 Fan 6.3 A

    Air handler - CABController V3.1

    2005 - 2006

    Air handler - CABController V3.2

    2006 >

    WBCL000860

  • 7/29/2019 Trouble Shooting BlueCool

    27/56

    Electrical diagrams

    27

    8 Electrical diagrams

    8.1 Classic / Select TCC V3

    brbl

    br

    bl

    brbl

    sw

    wssw

    swrt g

    rge

    blbrswgn

    blws

    Fuses:

    F1print315mA

    (115V630mA)

    F2fan3.1

    5A

    F3valve3.1

    5A

    F4pump1SW

    3.1

    5A

    Cablecolours

    bl

    br

    ge

    gn

    gr

    rt sw

    ws

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    4-wayrev.valve

    Blower

    Seawaterpump

    115/230VAC

    switchboard

    Pressureswitches

    LPonlyfor16,0

    00BTU

    andmore

    Runcapacitor

    Startcapacitor

    (onlyfor16,0

    00BTU

    andmore)

    Capacitorand

    resistorpump*)

    Display

    Externalairtemp.

    sensor

    Evaporatortemp.

    sensor

    compfan valve pump

    Capacitorand

    resistorpump*)

    *)Incasearelayisused,

    the

    controllershouldbewithout

    relatedcapacitorandresistor

  • 7/29/2019 Trouble Shooting BlueCool

    28/56

    Electrical diagrams

    28

    8.2 Classic / Select TCC V3 WB200 Pump Kit

    bl

    br

    IMPORTANT

    ForproperoperationTCCcontroller

    settingsatsetpoint29C,

    line

    mustbesetat01

    Seawaterpump

    TCCpumpoutlet

    Cablecolours

    bl

    br

    blue

    brown

    Display

    compfan valve pump

    Externalairtemp.

    sensor

    Evaporatortemp.

    sensor

    FUSE/VOLTAGESETT

    ING:

  • 7/29/2019 Trouble Shooting BlueCool

    29/56

    Electrical diagrams

    29

    8.3 Classic / Select, multiple units at one pump

    IMPORTANT

    TheTCCcontrollercardofeachunitshouldbewithoutcapacitorand

    resistorattherelatedoutput.

    Removeifnecessary!

    Commonseawater

    pump

    TCCpumpoutletunit1

    115/230VACswitchboard

    TCCpumpoutletunit2

    TCCpumpoutletunit3

    TCCpumpoutletunit4

  • 7/29/2019 Trouble Shooting BlueCool

    30/56

    Electrical diagrams

    30

    8.4 Select, blower speed controller

    Blowerspeedcontroller

    cardmountedingrille

    base

    1

    15/230VACsupplyfromsplitairunitselectricalbox

    Blowe

    relectrical

    termin

    als

    Splitair

    blower

    module

    GND

  • 7/29/2019 Trouble Shooting BlueCool

    31/56

    Electrical diagrams

    31

    8.5 Premium TECC V3, 1 and 2 compressors

    SW

    WS

    SWRT

    SWRT G

    EGE

    Fuses:

    F1PCB31

    5mA(115V630mA)

    F2fan6.3

    A

    F3valve3.1

    5A

    F4pump1SW

    3.1

    5A

    F5pump2CW

    3.1

    5A

    Cablecolours

    bl

    br

    ge

    gn

    gr

    rt swws

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    RelayComp.

    1

    Blower

    115/230VAC

    switchboard

    Pressureswitches

    Display

    Externalairtem

    p.

    sensor

    Chilledwatert

    emp.

    sensor

    fan valve pump2

    C

    apacitorand

    r

    esistorpump2*)

    *)Incasearelayisused,

    thecontroller

    shouldbewithoutrelatedcapacitorand

    resistor

    Capac

    itorand

    resisto

    rpump1*)

    pump1

    fanNvalveN

    pump1N

    pump2N

    Notused

    4-wayrev.valve

    RelayComp.

    2

    4-wayrev.valve

    Seawaterpump

    Chilledw

    aterpump

  • 7/29/2019 Trouble Shooting BlueCool

    32/56

    Electrical diagrams

    32

    8.6 Premium TECC V3, add-on 3 and 4 compressors

    GE

    GE

    GE

    GE

    RT

    SW

    RT

    SW

    F

    usesTECCV3:

    F1PCB315mA(115V630mA)

    F2fan6.3

    A

    F3valve3.1

    5A

    F4pump1SW

    3.1

    5A

    F5pump2CW

    3.1

    5A

    F

    uses4compadd-on:

    F1Comp.

    43.1

    5A

    F2Comp.

    33.1

    5A

    Cablecolours

    bl

    br

    ge

    gn

    gr

    rt swws

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    RelayComp.

    3

    115/230VAC

    switchboard

    Pressureswitches

    Display

    Externalairtemp.

    sensor

    Chilledwatertemp.

    sensor

    valve

    valveN

    Notused

    4-wayrev.valve1

    RelayComp.

    4

    4-wayrev.valve2

    4-wayrev.valve3

    4-wayrev.valve4

    4comp.a

    dd-on

  • 7/29/2019 Trouble Shooting BlueCool

    33/56

    Electrical diagrams

    33

    8.7 Premium, compressors

    SW

    SW

    Compre

    ssor115/230V1PH

    Compre

    ssor115/230V1PH

    Compre

    ssor208/400V3PH

    ACSwitchBoard

    ACSwitchBoard

    TECCCompOutlet

    MainAC

    TE

    CCCompOutlet

    MainAC

    TE

    CCCompOutlet

    StartCapacitor

    RunCapacitor

    Cablecolours

    bl

    br

    sw

    blue

    brown

    black

  • 7/29/2019 Trouble Shooting BlueCool

    34/56

    Electrical diagrams

    34

    8.8 Premium TECC V3 with external heater

    Fuses:

    F1PCB315mA(115V630mA)

    F2fan6.3A

    F3valve3.15A

    F4pump1

    SW

    3.1

    5A

    F5pump2

    CW

    3.1

    5A

    Cablecolours

    bl

    br

    gr

    or

    blue

    brown

    grey

    orange

    115/230VAC

    switchboard

    Display

    Externalairtemp.

    sensor

    Chilledwatertemp.

    sensor

    fan valve pump2pump1

    fanNvalveN

    pump1N

    pump2N

    Notused

    Externalheate

    r

    control

    Danfoss3-wayvalve

    230Vcool/ext.h

    eater

    IMPORTANT

    ForexternalheateroperationsetTECC

    controlleratF-04,

    setpoint15

    C2-00and

    29C9-03

    .

  • 7/29/2019 Trouble Shooting BlueCool

    35/56

    Electrical diagrams

    35

    8.9 Premium TECC V3 with calorifier

    SWRT

    SWRT

    GR

    GE

    GR

    GE

    WS

    SW

    Fuses:

    F1PCB315mA(11

    5V630mA)

    F2fan6.3

    A

    F3valve3.1

    5A

    F4pump1SW

    3.1

    5A

    F5pump2CW

    3.1

    5A

    Cable

    colours

    bl

    br

    ge

    gn

    gr

    rt swws

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    R

    elayComp.

    1

    Blower

    ACswitchboard

    P

    ressureswitches

    Display

    Externalairtemp.

    sensor

    Chilledwatertemp.

    sensor

    fan valve pump2

    Capacitorand

    resistorpump2*)

    *)Incasearelayisused,

    thecontrollershould

    bewithoutrelatedcapacitorandresistor

    Capacitorand

    resistorpump1*)

    pump1

    fanNvalveN

    pump1N

    pump2N

    Notused

    4-wayrev.valve

    RelayComp.

    2

    4-wayrev.valve

    Seawaterpump

    Chilledwaterpump

    **)IMPORTANT

    IncaseacalorifierisusedsetTECC

    controlleratsetpoint15C

    2-00

    Clixon/

    Thermostat

    Heater

    element

    Calorifier**

    )

  • 7/29/2019 Trouble Shooting BlueCool

    36/56

    Electrical diagrams

    36

    8.10 Premium TECC V2, 1 compressor

  • 7/29/2019 Trouble Shooting BlueCool

    37/56

    Electrical diagrams

    37

    8.11 Premium TECC V2, add-on 3 and 4 compressors

  • 7/29/2019 Trouble Shooting BlueCool

    38/56

    Electrical diagrams

    38

    8.12 Premium, MTH mechanical thermostat

    SW

    115/230VAC

    SwitchBoard

    MTHThermostat

    Blower

    Cablecolours

    bl

    br

    gn

    sw

    blue

    brown

    green

    black

  • 7/29/2019 Trouble Shooting BlueCool

    39/56

    Electrical diagrams

    39

    8.13 Premium, CAB V3 controller card + MTH2 thermostat + 3-way valve

    SW

    SW

    Fuses:

    F1PCB315mA

    F2fan3.1

    5A

    Cablecolour

    s

    bl

    br

    ge

    gn

    gr

    rt swws

    or

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    orange

    Blower

    230VAC

    switchboard

    Display(program

    only!)

    Notused

    Speedselections

    witch

    CABV33-speed

    Thermostat

    3-wayva

    lve

    230V

    Fan

    Danfoss3-way

    valve230V

  • 7/29/2019 Trouble Shooting BlueCool

    40/56

    Electrical diagrams

    40

    8.14 Premium, CAB V3 controller card + Plana thermostat + 3-way valve

    SW

    SW

    Fuses:

    F1PCB315mA

    F2fan3.1

    5A

    Cablecolours

    bl

    br

    ge

    gn

    gr

    rt swws

    or

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    orange

    Blower

    230VAC

    switchboard

    Display(program

    only!)

    Notused

    Speedselectionswitch

    CABV33-speed

    Thermostat

    3-wayvalve

    230V

    Fan

    Danfoss3-way

    valve230V

  • 7/29/2019 Trouble Shooting BlueCool

    41/56

    Electrical diagrams

    41

    8.15 Premium, CAB V3 controller card + Digital Display Panel + 3-way valve

    SW

    SW

    Fuses:

    F1PCB315mA(115V

    630mA)

    F2fan3.1

    5A

    Cablecolours

    bl

    br

    ge

    gn

    gr

    rt swws

    or

    blue

    brown

    yellow

    green

    grey

    red

    black

    white

    orange

    Blower

    115

    /230VAC

    swi

    tchboard

    Display

    Externalairtemp.sensor

    Chilledwatertemp.

    sensor

    CABV3Digital

    H

    eaterelement

    3-wayvalve

    (230Vo

    nly)

    Fan

    Danfoss3-wayvalve

    (230Vonly)

    Valve H

    eat

  • 7/29/2019 Trouble Shooting BlueCool

    42/56

    Electrical diagrams

    42

    8.16 Premium, Silent 5-speed for Compact and Slimline air handlers

    Below diagram is OK for index A silent 5-speed controlsFor an index B you must set code 2 at15 C to

    Very important:WBCL000373A can only pilot the A version silencers and are not fowards compatible.WBCL000373B can only pilot the B version silencers and are not backwards compatible.

  • 7/29/2019 Trouble Shooting BlueCool

    43/56

    Electrical diagrams

    43

    8.17 Premium, convert Danfoss into Lizhan

  • 7/29/2019 Trouble Shooting BlueCool

    44/56

    Electrical diagrams

    44

    8.18 Fresh-Air units

    Fresh-Air V3 wiring

  • 7/29/2019 Trouble Shooting BlueCool

    45/56

    Electrical diagrams

    45

  • 7/29/2019 Trouble Shooting BlueCool

    46/56

    Electrical diagrams

    46

  • 7/29/2019 Trouble Shooting BlueCool

    47/56

    Compressors

    47

    9 Compressors

    Unitmodelw

    ithRotarycompressor

    C

    ompressortype

    Partnumber

    Each

    compressor

    Ca

    pacitors

    Volta

    ge

    Cablesize

    [mm

    2]

    I[A]

    Fuse

    [A]

    RU

    N

    Partnumber

    START

    Partnumber

    Classic5

    RM5460HNE

    WBCL002260

    230V

    1Ph

    2.5

    2.1

    8

    20

    uF

    WBCL000180

    n/a

    n/a

    Classic5

    RM460GQ84

    WBCL002268

    115V

    1Ph

    4.2

    16

    40

    uF

    WBCL000110

    n/a

    n/a

    Classic6,5

    RM465GQ84

    WBCL002269

    115V

    1Ph

    5.5

    16

    40

    uF

    WBCL000110

    n/a

    n/a

    Classic7

    LG-NK125P

    WBCL002261

    230V

    1Ph

    2.5

    2.8

    10

    25

    uF

    WBCL000181

    n/a

    n/a

    Classic9

    LG-NK164P

    WBCL002262

    230V

    1Ph

    2.5

    3.2

    12

    30

    uF

    WBCL000182

    n/a

    n/a

    Classic9

    LG-QK125C

    WBCL002270

    115V

    1Ph

    6.5

    20

    45

    uF

    WBCL000108

    n/a

    n/a

    Classic12

    LG-NK185P

    WBCL002263

    230V

    1Ph

    2.5

    4.4

    16

    35

    uF

    WBCL000109

    n/a

    n/a

    Classic12/Premium12Mono-24Twin

    LG-QK164C

    WBCL002271

    115V

    1Ph

    9

    25

    50

    uF

    WBCL000107

    DST5/HS600

    WBCL000001

    Premium12Mo

    no-24Twin

    LG-NK185P

    WBCL002263

    230V

    1Ph

    2.5

    4.4

    16

    35

    uF

    WBCL000109

    DST5/HS600

    WBCL000001

    Classic16/Premium16Mono-32Twin

    LG-NJ236P

    WBCL002264

    230V

    1Ph

    2.5

    5.6

    20

    30

    uF

    WBCL000182

    DST5/HS600

    WBCL000001

    Classic16/Prem

    ium16Mono-32Twin

    LG-QK191C

    WBCL002272

    115V

    1Ph

    11

    32

    60

    uF

    WBCL000184

    DST5/HS600

    WBCL000001

    Classic20/Prem

    ium20Mono-40Twin-60Tri

    LG-NJ282P

    WBCL002265

    230V

    1Ph

    2.5

    6.5

    20

    35

    uF

    WBCL000109

    DST5/HS600

    WBCL000001

    Classic24/Premium24Mono-50Twin-72Tri-100QtrLG-NP362P

    WBCL002266

    230V

    1Ph

    2.5

    7.5

    25

    45

    uF

    WBCL000108

    DST5/HS600

    WBCL000001

    Classic30/Premium30Mono-60Twin-90Tri-120QtrLG-NP407P

    WBCL002267

    230V

    1Ph

    4

    9

    25

    55

    uF

    WBCL000183

    DST5/HS600

    WBCL000001

  • 7/29/2019 Trouble Shooting BlueCool

    48/56

    Compressors

    48

    UnitmodelwithScrollcompressor

    Com

    pressortype

    Partnumber

    Eachcompressor

    Capacitors

    Voltage

    Cablesize

    [mm2]

    I[A]

    Fuse

    [A]

    RUN

    Partnumber

    START

    P

    artnumber

    Premium

    30Mono-60Twin

    LG-HQ028P

    WBCL009504

    230V1Ph

    4

    60uF

    WBCL009502

    DST5/HS600W

    BCL000001

    Premium

    30Mono-60Twin-90Tri-120Qtr

    Cop

    eland-ZR28

    WBCL009399

    230V1Ph

    4

    10

    32

    45uF

    WBCL000108

    DST5/HS600W

    BCL000001

    Premium

    36Mono-72Twin-108Tri

    LG-HQ034P

    WBCL009487

    230V1Ph

    4

    60uF

    WBCL009502

    DST6

    W

    BCL000027

    Premium

    36Mono-72Twin-108Tri-144Qtr

    Cop

    eland-ZR34

    WBCL009397

    230V1Ph

    4

    11.5

    32

    50uF

    WBCL000107

    DST6

    W

    BCL000027

    Premium

    42Mono-84Twin-126Tri

    LG-HQ040P

    WBCL009488

    230V1Ph

    4

    60uF

    WBCL009502

    DST6

    W

    BCL000027

    Premium

    42Mono-84Twin-126Tri-168Qtr

    Cop

    eland-ZR40

    WBCL009396

    230V1Ph

    4

    13.5

    40

    55uF

    WBCL000183

    DST6

    W

    BCL000027

    Premium

    48Mono-96Twin-144Tri

    LG-HR049P

    WBCL009489

    230V1Ph

    4

    60uF

    WBCL009502

    DST6

    W

    BCL000027

    Premium

    48Mono-96Twin-144Tri-192Qtr

    Cop

    eland-ZR48

    WBCL009401

    230V1Ph

    4

    15

    40

    60uF

    WBCL000184

    DST6

    W

    BCL000027

    Premium

    30Mono-60Twin

    LG-HQ028Y

    WBCL009492

    400V3Ph

    4

    Premium

    36Mono-72Twin-108Tri

    LG-HQ034Y

    WBCL009494

    400V3Ph

    4

    Premium

    42Mono-84Twin-126Tri

    LG-HQ040Y

    WBCL009496

    400V3Ph

    4

    Premium

    48Mono-96Twin-144Tri

    LG-HR049Y

    WBCL009498

    400V3Ph

    4

    Premium

    60Mono-180Tri-240Qtr

    LG-HR061Y

    WBCL002283

    400V3Ph

    4

    Premium

    216Tri-288Qtr

    LG-HR073Y

    WBCL009499

    400V3Ph

    4

    Premium

    252Tri-336Qtr

    LG-HR081Y

    WBCL009500

    400V3Ph

    4

    Premium

    384Qtr

    Cop

    eland-ZR90K3E

    WBCL009386

    400V3Ph

    4

    Cop

    eland-ZR94KCE

    WBCL009386B

    400V3Ph

    4

    Premium

    448Qtr

    Cop

    eland-ZR11M3E

    WBCL009389

    400V3Ph

    4

    Cop

    eland-ZR108M3E

    WBCL009389B

    400V3Ph

    4

    Premium

    504Qtr

    Cop

    eland-ZR12M3E

    WBCL009387

    400V3Ph

    4

    ???

    WBCL009387B

    400V3Ph

    4

    Premium

    572Qtr

    Cop

    eland-ZR16M3E

    WBCL009388

    400V3Ph

    4

    Cop

    eland-ZR144KCE

    WBCL009388B

    400V3Ph

    4

  • 7/29/2019 Trouble Shooting BlueCool

    49/56

    Blowers

    49

    10 Blowers

    Including capacitor, insulated

    Blowers230V

    Part

    number

    Capacitor

    Part

    number

    Unitmodel

    I[A]

    Fuse[A]

    Ecofit2GRE15120x62R

    WBC

    L007020

    2uF

    WBCL000017

    CPAC5/7-Compact45

    00/6000

    0.3

    5

    2

    Ecofit2GRE25140x59R

    WBC

    L007021

    2.5uF

    WBCL000009

    CPAC9-Compact9000

    0.5

    7

    3

    Ecofit2GRE35140x59R

    WBC

    L007022

    4uF

    WBCL000018

    CPAC12/24-Compact

    12000/24000

    0.6

    5

    3

    Ecofit2GRE45180x75R

    WBC

    L007023

    6uF

    WBCL000070

    CPAC16/20-Compact

    16000/20000

    0.8

    7

    4

    Ecofit2GRE45160x62R

    WBC

    L007025

    6uF

    WBCL000070

    CPAC30-Compact30000-FreshAir24

    0.8

    5

    4

    Ecofit2GRE65180x70R

    WBC

    L007024

    12uF

    WBCL007041

    Fresh-Air48-Special24

    1.2

    5

    6

    Blowers115V

    Partnumber

    Capacitor

    Partnumber

    Unitmodel

    I[A]

    Fuse[A]

    Ecofit2GRE15120x62R

    WBC

    L007030

    6uF

    WBCL000070

    CPAC5/6.5-Compact4500/6000

    0.7

    3

    Ecofit2GRE25140x59R

    WBC

    L007031

    8uF

    WBCL000008

    CPAC9-Compact900

    0

    1.1

    5

    6

    Ecofit2GRE35140x59R

    WBC

    L007032

    18uF

    WBCL000012

    CPAC12/24-Compact

    12000/24000

    1.3

    6

    Ecofit2GRE45180x75R

    WBC

    L007033

    24uF

    WBCL000016

    CPAC16/20-Compact

    16000/20000

    1.7

    5

    8

  • 7/29/2019 Trouble Shooting BlueCool

    50/56

    BlueCool Unit Performance Report

    50

    11 BlueCool Unit Performance Report

    Unit type : ....................Serial number : ....................Refrigerant : R22 / R407

    Check before unit start-up:T ambient compressor : .................... CP discharge circuit I / II : .................... / .................... barT ambient outside : .................... C

    Check running in Cool cycle:Circuit I Circuit II

    U Compressor : .................... .................... VoltsI Compressor : .................... .................... AmpsFrequency : .................... .................... Hz

    1. T seawater inlet : .................... .................... C

    2. T seawater outlet : .................... .................... C3. Volume seawater : .................... ltr/min. (at unit or through-hull)

    Height seawater outlet : .................... m (above water level)Inside diameter suction line : .................... mmInside diam. outlet through-hull : .................... mmHeight seawater inlet : .................... m below water levelInside diameter discharge line : .................... mmInside diam. inlet through-hull : .................... mmPump total discharge head : .................... m

    Type / size strainer : ............................................................

    Number of strainers : .................... piecesMax.Strainer flow-rate : .................... ltr/min each

    4. T condenser inlet : .................... .................... C5. T condenser outlet : .................... .................... C

    6. T liquid : .................... .................... C

    7. T evaporator inlet : .................... .................... C8. T evaporator outlet : .................... .................... C

    9. T suction : .................... .................... C9a. T bulb expansion valve : .................... .................... C10. P suction : .................... .................... bar

    11. T discharge : .................... .................... C12. P discharge : .................... .................... bar

    13. T chilled water inlet : .................... .................... C14. T chilled water outlet : .................... .................... C

    Air handler(s) (Fan coil) I II III IV15. T blower air inlet : ............... C ............... C ............... C ............... C16. T blower air outlet : ............... C ............... C ............... C ............... C17. T water air handler inlet : ............... C ............... C ............... C ............... C

    18. T water air handler outlet : ............... C ............... C ............... C ............... C

    Gaugingsite

    indrawing

    Report date : ....................

  • 7/29/2019 Trouble Shooting BlueCool

    51/56

    BlueCool Unit Performance Report

    51

    Check running in Heat cycle:Circuit I Circuit II

    U Compressor : .................... .................... VoltsI Compressor : .................... .................... AmpsFrequency : .................... .................... Hz

    1. T seawater inlet : .................... .................... C2. T seawater outlet : .................... .................... C3. Volume seawater : .................... ltr/min. (at unit or through-hull)

    Height seawater outlet : .................... m (above water level)Inside diameter suction line : .................... mmInside diam. outlet through-hull : .................... mmHeight seawater inlet : .................... m below water levelInside diameter discharge line : .................... mmInside diam. inlet through-hull : .................... mmPump total discharge head : .................... m

    Type / size strainer : ............................................................Number of strainers : .................... piecesMax.Strainer flow-rate : .................... ltr/min each

    4. T condenser inlet : .................... .................... C5. T condenser outlet : .................... .................... C

    6. T liquid : .................... .................... C

    7. T evaporator inlet : .................... .................... C8. T evaporator outlet : .................... .................... C

    9. T suction : .................... .................... C9a. T bulb expansion valve : .................... .................... C10. P suction : .................... .................... bar

    11. T discharge : .................... .................... C12. P discharge : .................... .................... bar

    13. T chilled water inlet : .................... .................... C14. T chilled water outlet : .................... .................... C

    Air handler(s) (Fan coil) I II III IV15. T blower air inlet : ............... C ............... C ............... C ............... C

    16. T blower air outlet : ............... C ............... C ............... C ............... C17. T water air handler inlet : ............... C ............... C ............... C ............... C18. T water air handler outlet : ............... C ............... C ............... C ............... C

    Conclusion:................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................

    ..........................................................................................................................................................................................

    ..........................................................................................................................................................................................

    ..........................................................................................................................................................................................

    ..........................................................................................................................................................................................

    Gaugngste

    indrawing

  • 7/29/2019 Trouble Shooting BlueCool

    52/56

    BlueCool Unit Performance Report

    52

    Controller settings

    Main menuFunction Description AC AH 1 AH 2 AH 3 AH 4

    .. Room temperature

    .. Setpoint temperature

    b.. Fan speed

    H / E.. TemperatureF.. Cycle mode

    U.. Line current

    1C.. Compressor 1 on/off

    2C.. Compressor 2 on/off

    3C.. Compressor 3 on/off

    4C.. Compressor 4 on/off

    P.. Compressor sequence

    L.. Start delay compressors

    1L.. Temp. comp. 1 off

    2L.. Temp. comp. 2 off

    3L.. Temp. comp. 3 off

    4L.. Temp. comp. 4 offd Dehumidifying

    t Display time

    29 C menu0 Temp. low cut-out

    1 Temp. low cut-in

    2 Temp. high cut-out

    3 Temp. high cut-in

    4 Calibration H/E temp. sensor

    5 Time [min] to sleep mode

    6 Start delay unit

    7 Calibration room temp sensor

    8 Calibration AC 50 Hz

    9 Setting R2

    A Calibration AC 60 Hz

    b Software version

    c Pump 1 continuous/staged

    d Lower VDC pump 1

    E Higher VDC pump 1

    F

    15 C menu0 Low AC voltage cut-out

    1 Remote control

    2 Setting R1/Blower type

    3 Blower setting

    4 Internal / external room temp. sensor

    5 Fahrenheit or Celsius

    6 Setting fanspeed level 5

    7 Setting fanspeed level 4

    8 Setting fanspeed level 3

    9 Setting fanspeed level 2

    A Setting fanspeed level 1

    b Set security CODE

    c Dehumidifying time heating

    d Dehumidifying time cooling

  • 7/29/2019 Trouble Shooting BlueCool

    53/56

    BlueCool Unit Performance Report

    53

    Refrigeration cycle

    3

    2

    4

    1

    5

    6

    7

    14

    17.1

    17.2

    17.3

    15.2

    15.3

    15.1

    16.1

    16.2

    16.3

    18

    .3

    18.2

    18.1

    13

    8

    7

    Classic

    Premium

    15

    8

    16

    9

    10

    12

    9a1

    1

  • 7/29/2019 Trouble Shooting BlueCool

    54/56

    BlueCool Unit Performance Report

    54

    Gauging sites

    1. Temperature seawater inlet2. Temperature seawater outlet

    3. Flow seawater

    1 2

    3

    4-I

    4-II

    5-II

    5-I

    4. Temperature condenser inlet4-I : circuit I4-II : circuit II

    5. Temperature condenser outlet5-I : circuit I5-II : circuit II

    8-II

    6. Temperature liquid6-I : circuit I6-II : circuit II

    8. Temperature evaporator outlet8-I : circuit I8-II : circuit II

    6-II

    6-I

    8-I

  • 7/29/2019 Trouble Shooting BlueCool

    55/56

    BlueCool Unit Performance Report

    55

    For proper measurement of temperature at point 13 and 14, the tubular insulation has to be removedor pushed aside.

    6

    8

    10

    14

    7

    9a

    12

    6. Temperature liquid circuit II7. Temperature evaporator inlet circuit II8. Temperature evaporator outlet circuit II9a. Temperature bulb expansion valve circuit II

    10. Pressure suction circuit II12. Pressure discharge circuit II14. Temperature chilled water outlet circuit II

    9

    11

    9a

    12

    9. Temperature suction circuit I9a. Temperature bulb expansion valve circuit I11. Temperature discharge circuit I

    8-I. Temperature evaporator outletcircuit I

    13-I. Temperature chilled water inletcircuit I

    13-II. Temperature chilled water inletcircuit II14-I. Temperature chilled water outlet

    circuit I

    14-I

    9a

    8-I

    13-I

    13-II

  • 7/29/2019 Trouble Shooting BlueCool

    56/56

    0ErrorsandomissionsexceptedPrintedinTheNetherlandsWebastoAG,

    GCS2010