Transformer Protection Final

72
5/20/2018 TransformerProtectionFinal-slidepdf.com http://slidepdf.com/reader/full/transformer-protection-final 1/72  9/12/2014 1

Transcript of Transformer Protection Final

  • 5/20/2018 Transformer Protection Final

    1/72

    9/12/2014 1

  • 5/20/2018 Transformer Protection Final

    2/72

    PROTECTION EQUIPMENTThe definitions that follow are generally used in relation to power

    system protection:

    1. Protection System: a complete arrangement of protection

    equipment and other devices required to achieve a specified

    function based on a protection principal (IEC 60255-20)

    2. Protection Equipment: a collection of protection devices (relays,

    fuses, etc.). Excluded are devices such as CTs, CBs, Contactors, etc.

    3. Protection Scheme: a collection of protection equipment providing adefined function and including all equipment required to make the

    scheme work (i.e. relays, CTs, CBs, batteries, etc.)

    Relays may be classified according to the technology used:

    a.electromechanicalb. static

    c. digital

    d. numerical

  • 5/20/2018 Transformer Protection Final

    3/72

    Faults on the Transformer

    Transformer faults are generally classified into five

    categories:

    winding and terminal faults

    core faults

    Tank and transformer accessory faults

    Onload tap changer faults

    Abnormal operating conditions

    Sustained or uncleared external faults

    3

  • 5/20/2018 Transformer Protection Final

    4/72

    TRANSFORMER PROTECTIONOVERVIEW

    Fault Type Protection Used

    Primary winding Phase-phase fault Differential; Overcurrent

    Primary winding Phase-earth fault Differential; Overcurrent

    Secondary winding Phase-phase fault Differential Secondary winding

    Phase-earth fault Differential; Restricted Earth Fault

    Interturn Fault Differential, Buchholz

    Core Fault Differential, Buchholz

    MainTank EarthFault Differential, Buchholz; Overfluxing Overfluxing

    Overheating Thermal

    4

  • 5/20/2018 Transformer Protection Final

    5/72

    NORMS OF PROTECTION FOR EHV CLASS POWERTRANSFORMERS

    Voltage ratio &

    capacity

    HV Side LV SIDE COMMON RELAYS

    132/33/11 KV

    66/11 KV T/F BELOW 8

    MVA CAPACITY

    3 O/C AND

    1 E/F RELAY

    2O/C AND

    1E/F RELAY

    DIFFERENTIAL, REF, OT,WT, BUCHHOLZ FOR

    MAIN

    132/33/11 KV

    66/11 KV T/F UP TO25/31.5/50 MVA

    CAPACITY

    3 O/C AND

    1 E/F RELAY

    2O/C AND

    1E/F RELAY

    DIFFERENTIAL WITH HIGH SET, REF, OT,WT

    FOR HV AND LV WINDING, BUCHHOLZ FORMAIN AND OLTC,PRV FOR MAIN AND OLTC,

    MOLG

    220/132 KV 50/100

    MVA

    220/66 KV 50/100

    MVA CAPACITY T/F

    3 O/C AND

    1 E/F

    RELAY(DIR)

    2O/C AND

    1E/F RELAY

    DIFFERENTIAL WITH HIGH SET, REF, OT,WT

    FOR HV AND LV WINDING, BUCHHOLZ FOR

    MAIN AND OLTC,PRV FOR MAIN AND OLTC,

    OVERFLUX AND OVERLOAD ALARM, MOLG

    400/220 KV T/F 315

    MVA AND ABOVE

    3 O/C

    DIR.AND

    1E/F DIR.

    3 O/C

    DIR.AND 1E/F

    DIR.

    DIFFERENTIAL WITH HIGH SET, REF, OT,WT

    FOR HV AND LV WINDING, BUCHHOLZ FOR

    MAIN AND OLTC,PRV FOR MAIN AND OLTC,

    OVERFLUX AND OVERLOAD ALARM, MOLG

  • 5/20/2018 Transformer Protection Final

    6/72

    ANSI NUMBERS OF RELAYS AND THEIR FUNCTIONNAME OF RELAY ANSI

    NUMBER

    PURPOSE OF THE RELAY

    O/C AND E/F

    RELAYIDMTL( NON

    DIRECTIONAL)

    IDMTL(

    DIRECTIONAL)

    DEFINITE TIME

    RELAY OR

    INSTANTANEOUS

    RELAY

    51 RNB67 CX/NX

    50 RNB

    These relays are used for protection of transmission lines/transformers. 3 O/C relays are

    used on HV side of the T/F and 2O/C and 1 E/F relays are used on LV side of the T/F andfeeder panels.

    IDMTL: A relay in which the time delay varies inversely with the characteristic quantity up

    to a certain value, after which the time delay becomes substantially independent.

    INSTANTANEOUS: A relay which operates and resets with no intentional time delay. They

    are used for faults close to the source when the fault current is very high.

    DIFFERENTIAL

    RELAY

    87L(

    LINE)

    87T( T/F)

    87G(

    GEN.)

    Differential protection is a very reliable method of protecting generators, transformers,

    buses, and transmission lines from the effects of internal faults. These relays compares the

    two quantities generally current.

    RESTRICTED

    EARTH FAULT

    64 REF is provided on the transformer where the winding is Y connected. It takes care of earth

    fault in a restricted zone which includes T/F winding, LA CT/NCT and their auxiliary wiring.The relay is fed through 3 no. T/F CT(REF core) and concerned NCT.

    NON DIRECTIONAL

    E/F

    64N During balanced conditions, current through the neutral is 0. If there is an unbalanced fault

    (one phase or two phase to ground fault) the current through neutral is no longer zero.

    Presence of current in the neutral indicates that there is a fault present. Ground current

    relays can be set to quite low values to detect this current and operate.

  • 5/20/2018 Transformer Protection Final

    7/72

    NEUTRAL

    DISPLACEMENT

    RELAY

    64N Failure of capacitor unit in a bank will cause the voltage to rise on the

    remaining units in the series group which contains the failed unit. Any

    additional fail of the unit will cause the voltage to rise still higher which can

    damage the healthy unit. To avoid such damage NDR is used which is fed

    through open delta connection of the RVT.

    DC SUPERVISION

    RELAY

    80

    ABCD

    It makes a continuous supervision of DC supply in the C&R panel, and in case of

    its operation initiates alarm contacts to the AC buzzer.

    VOLTAGE

    SELECTION RELAY

    75AB

    C

    Provided on 66/132/220 KV panels where double bus arrangement exist. It

    selects the bus PT supply to which the feeder is connected through auxiliary

    contacts of isolator and feeds to various protection schemes, metering etc.

    MASTER

    RELAY/TRIPPING

    RELAY

    86 It is used to extend tripping command to the circuit breaker and operates

    whenever receive command from other protection relays, also acts as blocking

    relay for breaker operation. Used for extending inter tripping commands.

    BUS BAR

    DIFFERENTIAL

    RELAY

    87M

    87B

    87C

    Used to isolate the faulty bus by tripping all the circuits connected to the faulty

    bus in case of any fault on that bus through high speed tripping relay:96

    TRIP CIRCUIT

    SUPERVISION RELAY

    95AB

    C

    The trip circuit extends beyond the relay enclosure and passes through more

    components, such as fuses, links, relay contacts, auxiliary switch contacts

    and so on, and in some cases through a considerable amount of circuit wiring

    with intermediate terminal boards. The no. of TCSR depends upon the no. of

    tripping coils used in the breaker.

    UNDER VOLTAGE

    RELAY

    27 Under voltage and over voltage relays initiate switching of capacitor banks or

    stepping of up or down of a tap changer, in case voltage exceeds or falls below

    the preset values. Generally these relays are used on capacitor bank panels.

    Over voltage relays are used to trip the circuit breaker in case the voltageexceeds the preset limit value generally 110% of the normal value. Over

    OVER VOLTAGE

    RELAY

    59

  • 5/20/2018 Transformer Protection Final

    8/72

    OVER CURRENT

    ALARM

    51L It is a relay that initiates in case the current exceeds the preset values.

    Generally used on 220 KV line and T/F C&R panels.

    FUSE FAILURE RELAY 97 Operates on failure of PT/VT fuse/fuses. Monitor the fuses on the

    secondary side of 11 kV metering PT. The failure of any of secondary fuse

    on the 11 kV PT is accompanied by visual & audio indication.

    ALARMCANCELLATION

    74 Accepts the alarm initiated by another relays.

    AC/DC CHANGE OVER 30X Without flag relay used for change over of AC and DC supply. It is provided

    on all the panels. The indications are normally connected to AC supply and

    in case of its failure the relay operates and the indications automatically

    get connected to DC supply.

    UNDER FREQUENCY 81 Operates when the frequency falls/exceeds below/above preset values.

    DISTANCE

    PROTECTION

    MAIN-1

    MAIN-II

    21

    21P

    21Q

    Impedance relays are used whenever over current relays does not provide

    adequate protection. They function even if the short circuit current is

    relatively low. The speed of operation is independent of current

    magnitude. Measures the apparent impedance between the relay and the

    short-circuit. The apparent impedance is measured by computing the ratio

    between voltage and current at the relay. These relays, which are almostalways directional, are typically employed on transmission lines where

    impedance is both predictable and constant.

    BUS BAR PROTN. TRIP

    RELAY

    96.1,

    96.2

    Used to isolate the faulty bus by tripping all the circuit breakers connected

    to the faulty bus.

    OVER FLUX RELAY 99 Generally installed on 220 KV C&R Panels of 220/132/66 KV T/F and

    operates if the V/f exceeds a preset value, to avoid saturation of magneticcircuits, and to avoid excessive core/iron losses in the T/F. generally its

  • 5/20/2018 Transformer Protection Final

    9/72

    POLE DISCREPANCY

    RELAY

    62 It is provided on 220 KV and above circuit breakers to ensure that

    all the poles of the CB close/open simultaneously. In case one or

    two fail to open/close then this relay operates and trips the pole

    which remain closed.

    LBB RELAY 50 LBB It operates in case any breaker fail to trip on fault then all the

    other breakers connected to this bus will get the trip commandthrough this relay.

    AUXILLIARY RELAY 30 AX These relays are used to extend tripping commands such as

    BT/OTT/WTT/PRVT etc to the master/tripping relay.

    AUTO RECLOSER 152X A scheme of delay auto reclose will be provided to return circuits

    to service after transient line faults.

    VOLTAGE

    UNBALANCE RELAY

    60 Operates whenever unbalance in the voltage of all the three

    phases exceeds a preset value.

    BUCHHOLZ RELAY 63A

    63T

    These relays are sensitive to the generation of gases inside the

    main tank OLTC tank due to incipient faults.

    PRV RELAY This relay is installed on the transformer main tank and OLTC tank

    to safe guard the power transformer due to sudden high pressureof gases developed.

    CTD This is relay installed in the breaker and causes tripping of the

    breaker in case of DC fails or voltage level goes below preset value.

    ANTI PUMPING

    RELAY

    94 Used to avoid successive closing tripping closing and so on like

    pumping action of the breaker during fault condition for avoidingdamage to the coil, breaker and other equipment.

  • 5/20/2018 Transformer Protection Final

    10/72

    Fault in Power Transformer

    External factors Fault in down stream

    Lightning/ Switching

    Magnetic inrush

    Internal factors Insulation failure

    Atmospheric conditions

    Partial discharges

    Carona

    Fault in Tap changer

    10

  • 5/20/2018 Transformer Protection Final

    11/72

    Transformer protections are provided:

    a. Against effects of faults in the system to which the transformer is

    connected.b. Against effects of faults arising in the transformer.

    Protections against faults in the system:

    a. Short Circuits

    b. High Voltage, high frequency disturbance

    c. Pure Earth Faults

    11

  • 5/20/2018 Transformer Protection Final

    12/72

    Internal faults:

    Incipient Faults Poor joints/connection

    Core faults

    Coolant failure(logged oilflow) results in gas liberation.

    Bad load sharing betweenT/Fs.

    Initially, such faults are of

    minor nature but slowlymight develop into majorfaults. Such faults are nottraceable at the windingterminals by unbalance in

    voltage or current.

    Heavy faults Multi phase & Phase to

    earth faults.

    Short circuiting between

    turns in HV & LV windings

    9/12/2014 12

  • 5/20/2018 Transformer Protection Final

    13/72

    Name plate details Make

    Sr No

    Frequency Capacity

    Voltage

    Current

    Phase

    % Impedence

    Insulation Levels

    Drawing No.

    P O No.

    Vector group

    Types of Cooling

    Quantity of Oil

    Weight of Copper

    Weight of Core

    YOM 13

  • 5/20/2018 Transformer Protection Final

    14/72

    Principles of Protection System

    Principles used are:

    1. Overheating/Temperature and pressure

    2. Over Current

    3. Un-restricted earth faults

    4. Restricted earth-faults

    5. Percentage bias differential protection

    6. Gas detection due to incipient faults

    7. Low oil level

    8 Pressure relief (high overload/arcing)

    9. Over fluxing, Under frequency10. Tank earth current detection

    11. Lightning/Over Voltage Surges

    12. Tap changer problems

    14

  • 5/20/2018 Transformer Protection Final

    15/72

    Transformer Protection

    Percentage bias differential protection

    High impedance circulating current protection

    (Restricted earth fault protection)

    Over fluxing protection

    Back up O/C & E/F

    Over load alarm

    Protection & monitors built into transformer

    (Buchholz relay , OSR relay , Winding & Oil

    temperature indicators ,Pressure relief deviceand Oil level indicator)

  • 5/20/2018 Transformer Protection Final

    16/72

    Percentage Differential Protection

    This Scheme is used for Protection of T/F against internal short circuits.

    It is not capable of detecting incipient faults.

    The relay settings for T/F protection are kept higher than that foralternators.

    The typical values for T/F may be 40 % for operating coil & 10 % forrestraining coil respectively.

    Because a T/F is provided with OLTC. The CT ratio cannot be changedwith varying T/F ratio of T/F. so, for taps other than nominal, an out ofbalance current flows through the operating coil of the relay duringload and external fault condition.

    When a T/f is on no-load, there is no-load current in the relay. So, itssetting should be greater than no-load current.

    To supply the matching current in the operating winding of the relay,the CTs which are on the star side of the T/F are connected in delta &vice versa.

    16

  • 5/20/2018 Transformer Protection Final

    17/72

    Percentage Differential Protection for Star-deltaconnected Transformer

    17

  • 5/20/2018 Transformer Protection Final

    18/72

    Restricted Earth fault Protection

    REF protection is used to supplement the differential protection,

    particularly where star neutral of the T/F is grounded through a

    neutral grounding resistor to limit the earth fault current. REF

    protection provides increased coverage to star winding against earth

    faults.

    It is provided between the main CT and corresponding NCT.

    It is an instantaneous relay.

    The relay used in REF protection is of high impedance type to make

    scheme stable for external faults.

    18

  • 5/20/2018 Transformer Protection Final

    19/72

    Restricted Earth fault Protection

    9/12/2014 19

  • 5/20/2018 Transformer Protection Final

    20/72

    Over fluxing protection

    This condition arises during abnormal operating conditions:

    Heavy voltage fluctuations at lower frequency conditions.

    This condition is experienced by the T/F during heavy power

    swings, cascade tripping of generator sets & HT line in the

    Grid, interstate system separation conditions & due to AVR

    malfunctioning during start-up or shutting down in case of

    Generator Transformer.

  • 5/20/2018 Transformer Protection Final

    21/72

    Over fluxing protection

    It works on the principal of Voltage/Frequency

    Acc to EMF eqn, V1=4.4 f m N1 OR

    m = k V1/f

    Usually 10 % of over fluxing can be allowed without damage.

    If V1/f exceeds 1.1, overfluxing protection operates.

    Over fluxing does not require high speed tripping & hence

    instantaneous operation is undesirable when momentary

    disturbances occur, but the T/F should be isolated in one or two

    minutes if the over fluxing persists.

  • 5/20/2018 Transformer Protection Final

    22/72

    9/12/2014 22

  • 5/20/2018 Transformer Protection Final

    23/72

    V/fVn/fn

    1.1 1.2 1.25 1.3 1.4

    Duration ofwithstand

    limit (minutes)

    Cont. 2 1 0.5 0

  • 5/20/2018 Transformer Protection Final

    24/72

    MAGNETIC INRUSH

    The phenomenon of magnetizing inrush is a transient

    condition, which occurs primarily when a transformer isenergized.

    It is not a fault condition and therefore does not necessitatethe operation of protection, which on the contrary must

    remain stable during the inrush transient, which is a majorfactor that is to be taken care of in the design of transformerprotection.

    Magnetising inrush wave has the following harmonics1. 2nd harmonic63 %2. 3rd harmonic27 %3. 4th harmonic5%4. 5th harmonic4%

  • 5/20/2018 Transformer Protection Final

    25/72

    O/C & E/F Protection

    IDMT O/C elements on delta and star side, primarily serve as

    back up protection against downstream short circuits and aretime co-ordinated with downstream O/C protections.

    The high set instantaneous O/C elements are provided to detectsevere terminal short circuits and quickly isolate the transformer.

    The relay is connected in high impedence mode with a seriesstabilizing resistor.

  • 5/20/2018 Transformer Protection Final

    26/72

    O/C & E/F Protection

    26

  • 5/20/2018 Transformer Protection Final

    27/72

    Overheating Protection

    Protection is based on measurement of winding temperature which is

    measured by thermal image technique. Thermal sensing element is placed in small pockets located near the

    top T/F tank in the hot oil.

    A CT is employed on LV side to supply current to local heater.

    Winding temperature high alarm/trip is provided through mercuryswitches in the winding temperature indicators.

    By thermo-meters, mercury switches heat sensing silicon resistanceare also used for sensing the temperature rise.

    The max safe overloading is that which does not overheat the winding.

    Temperature of 55 deg C above ambient of 50 deg C is generallyprovided for tripping.

    27

  • 5/20/2018 Transformer Protection Final

    28/72

    Thermal Over heating

    Winding Temperature

    Sensors in 2 places

    Over loads/other abnormalconditions cause higher temp.

    Used to switch on fans

    Alarms and trips above setvalues.

    Oil Temperature sensors

    Switch on fans

    Alarm/Trip are the threefunctions associated with.

    28

  • 5/20/2018 Transformer Protection Final

    29/72

    29

    Winding Temperature alarm & Trippings

    The Transformer is provided with a W.T.I which contains a Liquid

    which expands itself when heated along with Tr.Oil, kept in aPocket & heated by WTI C.T Currents. Change of Volume activatesa Temperature Indicator suitably calibrated. These Indicators arecompensated for atmospheric Temperature Changes.

    Normally it has 04 Contacts

    Contact-1 : Fan Start ( ex. 60C)

    Contact-2 : Pump Start ( ex. 70C)

    Contact-3 : WTI Alarm ( ex. 85C)

    Contact-4 : WTI Trip ( ex. 90C)

  • 5/20/2018 Transformer Protection Final

    30/72

    Oil Temperature alarm & Trippings

    The Transformer is provided with a O.T.I which containsa Liquid which expands itself when heated along withTransformer Oil & Change of Volume activates aTemperature Indicator suitably calibrated. These

    Indicators are compensated for atmosphericTemperature Changes.

    Normally it has 02 Contacts

    Contact-1 : OTI Alarm : 85 deg

    Contact-2 : OTI Trip : 90 deg

  • 5/20/2018 Transformer Protection Final

    31/72

    INFRARED TEMPERATUREMEASUREMENTS

    A thermo vision apparatus with resolution better than 0.1 degreeC is used for checking of the temperature distribution on atransformer enclosure (tank and cover) and external auxiliaries

    Temperature rise above ambient Recommendation

    0-10 deg C Little probability of any damage

    11-39 deg C Inspect for damage in next Mtc. S/D 40-75 deg . Check for probable damage at anearliest possible opportunity

    Above 76 deg C Critical problem, take S/D forimmediate repairs

  • 5/20/2018 Transformer Protection Final

    32/72

    LATEST DIAGNOSTIC TECHNIQUES

    Frequency Response Analysis (FRA)

    PD measurement and acoustic localisation offaults

    Furan analysis in oil (HPLC chromatography)

    On-line dissipation factor monitoring of

    H.V. bushings

    Polarisation spectrum or Recovery Voltage(RVM) measurement

  • 5/20/2018 Transformer Protection Final

    33/72

    FREQUENCY RESPONSE ANALYSIS

    Mechanical movement of winding mayoccur during transportation shocks or SC

    forces or shrinkage due to ageing and mayresult in dielectric failure of transformer

    Such winding displacement may not bedetected by DGA, winding resistance or C

    &Tan measurementTechniques available to detect suchchanges are FRA or Vibration Measurement

  • 5/20/2018 Transformer Protection Final

    34/72

    FRA primarily used for detection of

    deformation/movements of winding

    FRA is also carried out periodically for detection

    of deformation of smaller magnitude, when

    transformer experiences several short circuit

    forces

    Helps in monitoring health and condition

    assessment of transformers

    FRA SIGNIFICANCE

  • 5/20/2018 Transformer Protection Final

    35/72

    PRINCIPLE OF FRA

    Both the applied impulse signal and the correspondingwinding responses are recorded using a high performancedigitizer and the results transformed into frequencydomain by Fast Fourier Transform calculation, a response

    function is obtained which is dependent almost entirely onthe test object and is independent of applied signal andtest circuit. The changes in the test object can be moreclearly and consistently identified. The technique used forFRA analysis is a sweep frequency technique which issuitable for site use and has a superior signal to noiseperformance at high frequencies.

  • 5/20/2018 Transformer Protection Final

    36/72

    FRA TEST SET-UP

  • 5/20/2018 Transformer Protection Final

    37/72

    ADVANTAGES OF FRA

    FRA detects winding movement, which cannot be

    ascertained by any other commonly known test

    FRA test is sensitive and very repeatable FRA is very powerful and effective tool and capable

    of detecting a range of transformer faults, it is

    nevertheless primarily a mechanical condition

    assessment test and must be used in conjunctionwith other diagnostic tests if a complete picture of

    the condition of the transformer is to be obtained.

  • 5/20/2018 Transformer Protection Final

    38/72

    REASONS FOR TRANSFORMER OILDETERIORATIONPHYSICAL CONTAMINATION DUE TO MOISTURE ENTRY, FIBERS IN

    INSULATION TAPE AND VARNISH IN THE PARMA WOOD, PRESSBOARDASSEMBLY.

    CHEMICAL REACTION DUE TO OXIDATION OF HYDROCARBON ALONG WITH

    VARIATION IN LOAD CONDITION AND TEMPERATURE OF THE OIL FORMS

    ACIDS AND SLUDGE .

    ELECTRICAL STRESS DUE TO ELECTRICAL FAULTS LIKE PARTIAL DISCHARGE,

    ARCING, SPARKING INSIDE THE TRANSFORMER.

    THERMAL STRESS DUE TO LOOSE CONTACTS IN WINDING LEADS, CORE

    CLAMPING ETC.

    AGEING OF TRANSFORMER OIL.

    POOR QUALITY OF TRANSFORMER OIL

    OIL QUALITY INDEX SYSTEM

  • 5/20/2018 Transformer Protection Final

    39/72

    OIL QUALITY INDEX SYSTEMGOOD OILS NN

    IFT

    -0.00 To -0.10

    -30.0 To -45.0

    Pale Yellow

    MIN: 300-1500

    Excellent

    PROPOSITION

    OILS

    NN

    IFT

    -0.05 To -.10

    -27.1 To -29.9

    Yellow

    MIN : 271-600

    GOOD

    MARGINAL OILS NN

    IFT

    -0.11 To -0.10

    -24.0 To 27.0

    Bright Yellow

    MIN : 160-318

    A drop in IFT signal

    the beginning of

    sludge in solution.

    BAD OILS NNIFT

    -0.16 To -0.40-18.0 To -23.0

    AMBERMIN : 45-159

    Oil is not providingproper cooling &

    winding protection

    V. BAD OILS NN

    IFT

    -0.41 To -0.65

    -14.0 To -17.9

    BROWN

    MIN : 22-24

    Sludge has already

    been deposited in &

    on T/F parts inalmost 100 % of

    these units.

    Insulation damaged

    & reduced cooling

    efficiency with high

    operating tempcharacteristics.

    EXTREMELY

    BAD OIL

    NN

    IFT

    -0.66 To -1.50

    -9.0 To -13.9

    BARK BROWN

    MIN 6-21

    NN

    (NeutralizationNo.)

    IFT (Inter

    Facialtension)

    MIN : Myers Index No. = IFT/NN

  • 5/20/2018 Transformer Protection Final

    40/72

    FACTORS THAT DETERIORATES THEMATERIALS

    Moisture

    Oxygen

    Temperature

    40

    EFFECT OF THE ABOVE FACTORS

  • 5/20/2018 Transformer Protection Final

    41/72

    EFFECT OF THE ABOVE FACTORS

    Moisture: Absorbed from Atmospheric air during breathing. Reduces the BDV Oxygen

    41

    Oxygen : O2from atmospheric air while breathing and which

    is present in oil react with cellulose in presence ofcopper as catalyst form organic acid which

    dissolves in oil to form sludge. Restrict oil circulation

    Reduces heat transfer leading to increases thetemperature

  • 5/20/2018 Transformer Protection Final

    42/72

    EFFECT OF THE ABOVE FACTORScont.

    - Temperature :

    Cellulose free sugar glucose, H2O, CO, CO2+ Celluloseof reduced chain length.

    Reduces the BDV

    Deteriorate the cellulous insulation.

    Reduces Tensile strength

    The various types of cooling methods used for power transformer

  • 5/20/2018 Transformer Protection Final

    43/72

    The various types of cooling methods used for power transformerare given below (IS 2026: 1962)

    CoolingCooling method Oil circulation Winding temperature rise limit

    ON Natural Air-natural 550C

    ONAF Natural Air-blast/Forced 550C

    OFAN Forced Air-natural 600C

    OFAF Forced Air-natural 600C

    OFW Forced Water(Forced) 650C

    Top oil temperature measured by thermometer for all types of cooling is 400c

    (Ambient temperature)

    RECOMMENDED LIMITS OF T/F OILS

  • 5/20/2018 Transformer Protection Final

    44/72

    RECOMMENDED LIMITS OF T/F OILS

    NAME OF

    CHARATERISTICS

    UNUSED MINERAL OIL IN-SERVICE T/F OIL

    CATEGORY

    OF POWER

    T/F

    RECOMMEND

    ED LIMITS (AS

    per IS: 1866-2000)

    CATEGORY OF

    POWER T/F

    RECOMMENDED

    LIMITS (AS per IS:

    1866-2000)

    ELECTRIC

    BREAKDOWN(KV)

    BELOW 72.5

    KV

    72.5 KV To

    170 KV

    Above 170 KV

    40 KV (Min)

    50 KV (Min)

    60 KV (Min)

    Up to 72.5 KV

    72.5 KV To 170

    KV

    Above 170 KV

    30 KV (Min)

    40 KV (Min)

    50 KV (Min)

    Specific Resistance at

    90C

    All Voltages 6X10*12 Ohm-

    Cm (Min)

    All Voltages 0.1X10*12 Ohm-Cm

    (Min)

    WATER CONTENT BELOW 72.5

    KV

    72.5 KV To

    170 KVAbove 170 KV

    20 ppm (max)

    15 ppm (max)

    10 ppm (max)

    BELOW 72.5 KV

    72.5 KV To 170

    KV

    Above 170 KV

    No free moist at room

    temp

    40 ppm

    20 ppm

    DIELECTRIC

    DISSIPITATION

    FACTOR at 90C

    UP to 170 KV

    Above 170 KV

    0.015 (Max)

    0.010 (max)

    UP to 170 KV

    Above 170 KV

    1.0 (Max)

    0.2 (max)

    NEUTRALIZATION All Voltages 0.03 mg KOH/g All Voltages 0.3 mg KOH/g

  • 5/20/2018 Transformer Protection Final

    45/72

    9/12/2014 45

    DISSOLVED GAS ANALYSIS

    The inflammable gases dissolved in the transformer oil are

    mainly hydrocarbon gases (methane CH4, Ethane C2H6, Ethylene

    C2H4, Acetylene C2H2, Propane, Hydrogen, Carbon Monoxide and

    carbon dioxide). With the help of dissolved gas analysis equipment

    the concentration of these gases in PPM can be known and can becross checked with the IS standard. Also with the help of Rogers

    ratio method, the type of probable incipient fault can be judged and

    corrective action can be taken in advance to prevent failure of the

    transformer.

  • 5/20/2018 Transformer Protection Final

    46/72

    Buchholz relay

    Incipient faultGas accumulation is slow-top floatalarm.

    Heavy fault insideDecomposition high- heavy surge-bottom floattrip.

    Simulate condition 50-100 ms

    Normal time 200 ms.

    Fault below the oil levels only detected.

    Gas Detection

  • 5/20/2018 Transformer Protection Final

    47/72

    a. Buchholz relay protection

    b. Pressure relief valves / switches (for heavy internal faults)

    Buchholz Protection

    This is for two types of faults inside the transformer.

    a. For incipient faults because of

    1. Core bolt insulation failure

    2. Short circuit in laminations

    3. Local over heating because of clogging of oil

    4. Excess ingress of air in oil system

    5. Loss of oil due to heavy leakage

    6. Uneven load sharing between two transformers in parallel

    causing overheating due to circulating current.

    47

    These generate gases causing operation of upper float and

    energises the alarm circuits.

  • 5/20/2018 Transformer Protection Final

    48/72

    Why DGA

    9/12/2014 48

    1. DIRECTLY DETECTS THE GASES EVOLVED DUETO DECOMPOSITION OF OIL, INSULATING

    MATERIALS LIKE PAPER, PRESS BOARD ETC.

    2. EFFECTIVE AND POWERFUL DIAGNOSTIC TOOLFOR MONITORING THE DEVELOPING INCIPIENT

    FAULT.

    3. DETECTION OF FAULT FROM THE

    INTERPRETATION OF THE TEST RESULTS GIVESEARLY WARNING OF ANY DEVELOPING FAULT.

    4. THE KEY GAS INDICATES THE TYPE OF FAULT

    DEVELOPING INSIDE THE TRANSFORMER.

  • 5/20/2018 Transformer Protection Final

    49/72

    ADVANTAGES OF DGA MONITORING

    49

    DGA MONITORING MINIMISES OUTAGE OF EQUIPMENT.

    DGA HELPS IN REDUCING THE REPAIR COST.

    DGA HELPS TO IMPROVE LIFE SPAN OF THE EQUIPMENT.

    DGA IMPROVES THE OPERATING CONDITION OF THE EQUIPME

    DGA IMPROVES THE PLANT EFFICIENCY.

  • 5/20/2018 Transformer Protection Final

    50/72

    GASES LIBERATED DURING OILDECOMPOSITION

    1. METHANE CH4

    2. ETHANE C2H

    6

    3. ETHYLENE C2H4

    4. ACETYLENE C2H25. CARBON MONOXIDE CO

    6. CARBONDIOXIDE CO2

    7. HYDROGEN H2

    8. OXYGEN O29. NITROGEN N2

  • 5/20/2018 Transformer Protection Final

    51/72

    TEMPERATURES AT WHICH GASES EVOLVE

    METHANE (CH4) > 1200C

    HYDROGEN (H2) > 1500C

    ETHANE (C2H6) > 2500C

    ETHYLENE (C2H4) > 3500C

    ACETYLENE (C2H2) > 7000C

  • 5/20/2018 Transformer Protection Final

    52/72

  • 5/20/2018 Transformer Protection Final

    53/72

    FAULTS ASSOCIATED WITH DIFFERENT GAS

    OIL OVERHEATING : C2H4, C2H6, CH4

    TRACES OF ACETYLENE WITH SMALL QUANTITY OF

    HYDROGEN

    OVERHEATED CELLULOSE : C02 & CO

    LARGE QUANTITY OF CO2AND CO EVOLVED FROM

    OVERHEATED CELLULOSE.

    CH4AND C2H4FORMS IF FAULT INVOLVES OIL

    IMPREGNATED STRUCTURE

  • 5/20/2018 Transformer Protection Final

    54/72

  • 5/20/2018 Transformer Protection Final

    55/72SAMPLING OF OIL - PROCEDURE

  • 5/20/2018 Transformer Protection Final

    56/72

    THE CONTAINER FOR SAMPLING SHALL BE STAINLESS STEEL OR GLASS

    SAMPLING BOTTLE WITH STOP VALVES ON BOTH ENDS.

    THE COLOUR OF THE BOTTLE SHALL BE BROWN PREFERABLY.

    FREQUENCY OF SAMPLING FOR DGA

    FOR NEW TRANSFORMER :

    FIRST SAMPLE: : BEFORE ENERGIZING NEW T/F,

    SECOND SAMPLE : AFTER ONE MONTH OF SERVICE

    THIRD SAMPLE : ONCE IN A YEAR IF NO ABNORMALITY.

    FOR REPAIRED TRANSFORMER :

    FIRST SAMPLE : BEFORE ENERGIZING REPAIRED T/F

    SECOND SAMPLE : AFTER THREE MONTHS AND

    THIRD SAMPLE : ONWARDS ONCE IN A YEAR IF NO

    ABNORMALITY.

  • 5/20/2018 Transformer Protection Final

    57/72

    CODES & STANDARDS FOR DGA

    IS 943 1979

    IS 10593 1983IEC 599 1978

    FOR OIL SAMPLINGIS: 9497

  • 5/20/2018 Transformer Protection Final

    58/72

  • 5/20/2018 Transformer Protection Final

    59/72

  • 5/20/2018 Transformer Protection Final

    60/72

    DISSOLVED GAS ANALYSIS

    Brief Overview of Various Interpretation Technique for DGA Data

    Individual Fault Gases Acceptable Norms

    Total Dissolved Combustible Gas (TDCG) limits

    IEC 599 Method

    IEEE Standard C: 57.104/1995Key Gas Method

    Ratio Methods

    Trend Analysis

    INTERPRETATION OF DGA RESULTS:

  • 5/20/2018 Transformer Protection Final

    61/72

    INTERPRETATION OF DGA RESULTS:

    KEY GAS METHODS: The permissible concentration of Dissolved Gases As perIEEE.

    All gas concentration are in ppm

    GAS LESS THAN 4 YRS

    in Service

    4-10 years in

    Service

    More than 10 years

    in service

    Hydrogen 100-150 200-300 200-300

    Methane 50-70 100-150 200-300

    Acetylene 20-30 30-50 100-150

    Ethylene 100-150 150-200 200-400

    Ethane 30-50 100-150 800-1000

    Carbon Monoxide 200-300 400-500 600-700

    Carbon Dioxide 3000-3500 4000-5000 9000-12000

    Recommendations if Values of the Fault Gases ExceedsPermissible Limits

  • 5/20/2018 Transformer Protection Final

    62/72

    Permissible Limits

    GAS Permissible

    Limits

    Value Obtained

    by DGA

    Recommendations Remarks

    A. TRANSFORMER under 4 Years of Service

    ETHANE C2H6 30-50 50-150 Monitoring > 150- View Seriously

    Ethylene C2H4 100-150 150-300 Monitoring > 300- View Seriously

    Acetylene C2H2 20-30 30-70 Monitoring > 70- Immediate

    inspectionB. TRANSFORMER Between 4-10 Years of Service

    ETHANE C2H6 100-150 150-500 Monitoring > 500- View Seriously

    Ethylene C2H4 150-200 200-400 Monitoring > 400- View Seriously

    Acetylene

    C2H2

    30-50 50-70 Monitoring > 70- Immediate

    inspection

    C. TRANSFORMER Above 10 Years of Service

    ETHANE C2H6 800-1500 Upto 800 Monitoring > 800- View Seriously

    Ethylene C2H4 200-400 400-600 Monitoring > 600- View Seriously

    Acetylene

    C2H2

    100-150 70-100 Monitoring > 100- Immediate

    inspection

    T f Di i U i T t l Di l d C b tibl G

  • 5/20/2018 Transformer Protection Final

    63/72

    Transformer Diagnosis Using Total Dissolved Combustible GasConcentrations.

    STATUS H2 CH4 C2H2 C2H4 C2H6 CO CO2 TDCG

    Condition

    1

    100 120 35 50 65 350 2500 720

    Condition

    2

    101-700 121-400 36-50 51-100 66-100 351-570 2500-

    4000

    721-

    1920

    Condition

    3

    701-1800 401-

    1000

    51-80 101-

    200

    101-

    150

    571-

    1400

    4001-

    10000

    1921-

    4630

    Condition

    4

    >1800 >1000 >80 >200 >150 >1400 >10000 > 4630

    Condition 1: Total dissolved combustible gas (TDCG) below this levelindicates the transformer is operating satisfactorily

  • 5/20/2018 Transformer Protection Final

    64/72

    indicates the transformer is operating satisfactorily.

    Condition 2: TDCG within this range indicates greater than normalcombustible gas level. Any individual combustible gas

    exceeding specified levels in table 4 should haveadditional investigation. A fault may be present. TakeDGA samples as recommended by HVPNL authorities.

    Condition 3: TDCG within this range indicates a high level ofdecomposition cellulose insulation and/or oil. Any

    individual combustible gas exceeding specified levels intable 4 should have additional investigation. A fault orfaults are probably present.

    Condition 4: TDCG within this range indicates excessivedecomposition of cellulose insulation and/or oil.Continued operation could result in failure of thetransformer.

    INTERPRETATION OF DGA RESULTS:

  • 5/20/2018 Transformer Protection Final

    65/72

    Rogers Ratio METHODS: The admissible gas concentration limits may can bemisleading. Sometimes faults can be detected with lesser concentrations.

    Code Range of

    Ratios

    C2H2/C2

    H4

    CH4/H

    2

    C2H4/C2

    H6

    3

    0

    1

    1

    2

    1

    0

    2

    2

    0

    0

    1

    2

    Case Fault Type Problem Found

    0 No Fault 0 0 0 Normal Aging

    1 Low EnergyPartial

    Discharge

    1 1 0 Electric discharge in bubbles, caused byinsulation voids or high moisture in oil.

    2 High Energy

    Partial

    Discharge

    1 1 0 Same as above

  • 5/20/2018 Transformer Protection Final

    66/72

    Case Fault Type C2H2

    /C2H

    4

    CH4/

    H2

    C2H4

    /C2H

    6

    Problem Found

    4 High Energy

    Discharges,

    arcing

    1 0 2 Discharges (arcing) with power; arcing B/D of

    oil between winding or coils, or between coils

    & ground, or OLTC arcing across the contacts

    during switching with the oil leaking into the

    main tank.

    5 Thermal fault