Generator & Transformer Protection

27
Welcome to presentation Welcome to presentation on on GENERATOR & TRANSFORMER GENERATOR & TRANSFORMER PROTECTION PROTECTION ELECTRICAL MAINTENANCE DEPARTMENT ELECTRICAL MAINTENANCE DEPARTMENT BY BY K JACOB K JACOB JOSE JOSE

description

PPT FOR 500MW GT PROTECTION

Transcript of Generator & Transformer Protection

Page 1: Generator & Transformer Protection

Welcome to presentationWelcome to presentationonon

GENERATOR & TRANSFORMER GENERATOR & TRANSFORMER PROTECTIONPROTECTION

ELECTRICAL MAINTENANCE DEPARTMENTELECTRICAL MAINTENANCE DEPARTMENT

BYBY

K JACOB K JACOB JOSEJOSE

Page 2: Generator & Transformer Protection

CLASSES OF PROTECTIONCLASSES OF PROTECTION

•CLASS A1CLASS A1

•CLASS A2CLASS A2

•CLASS BCLASS B

•CLASS CCLASS C

Page 3: Generator & Transformer Protection

GROUPS OF PROTECTIONGROUPS OF PROTECTION

• Group-1 – Group-1 – DC source 1 from 1/2 FA DC source 1 from 1/2 FA section-1section-1

• Group-2 – Group-2 – DC source 2 from 1/2 FA DC source 2 from 1/2 FA section-2section-2

• In case of any In case of any DC supply failureDC supply failure in GRP in GRP inform Electrical Maintenance inform Electrical Maintenance immediatelyimmediately

Page 4: Generator & Transformer Protection

CLASS A1CLASS A1

CAUSES OF CLASS A1CAUSES OF CLASS A1

1. GT & UT PROTECTIONS1. GT & UT PROTECTIONS

2. GENERATOR BACKUP PROTECTION2. GENERATOR BACKUP PROTECTION

3. OTHER BACKUP PROTECTIONS3. OTHER BACKUP PROTECTIONS

Page 5: Generator & Transformer Protection

CLASS A1 – CAUSES – CLASS A1 – CAUSES – TRANSFORMER PROTECTIONSTRANSFORMER PROTECTIONS

TRANSFORMER PROTECTIONS-MECHANICALTRANSFORMER PROTECTIONS-MECHANICAL

• PRVPRV• BUCHHOLZ RELAYBUCHHOLZ RELAY• SUDDEN PRESSURE RELAYSUDDEN PRESSURE RELAY• FIRE PROTECTIONFIRE PROTECTION• UT OLTC SUDDEN PRESSURE RELAYUT OLTC SUDDEN PRESSURE RELAY

Note: UT A/B WTI/OTI will trip the Note: UT A/B WTI/OTI will trip the corresponding incomer from the transformer corresponding incomer from the transformer and change over to Standby Trf.and change over to Standby Trf.

Page 6: Generator & Transformer Protection

CLASS A1 – CAUSES – CLASS A1 – CAUSES – TRANSFORMER PROTECTIONSTRANSFORMER PROTECTIONS

TRANSFORMER PROTECTIONS-ELECTRICALTRANSFORMER PROTECTIONS-ELECTRICAL

• DIFFERENTIAL PROTECTION(GT/UT) – 87GT/87UTDIFFERENTIAL PROTECTION(GT/UT) – 87GT/87UT• GT HV WINDING + O/H LINE DIFFERENTIAL-87HVGT HV WINDING + O/H LINE DIFFERENTIAL-87HV• RESTRICTED EARTH FAULT (UT’s only)87NUT A/BRESTRICTED EARTH FAULT (UT’s only)87NUT A/B• STANDBY EARTH FAULT (GT only)-51NGTSTANDBY EARTH FAULT (GT only)-51NGT• OVERCURRENT PROTECTION (UT’s only)-51UT A/BOVERCURRENT PROTECTION (UT’s only)-51UT A/B• BACKUP EARTH FAULT (UT’s only)-51 NUT A/BBACKUP EARTH FAULT (UT’s only)-51 NUT A/B• GT OVERFLUXING – 99GTGT OVERFLUXING – 99GT• EARTH FAULT BEYOND GCB – 64GTEARTH FAULT BEYOND GCB – 64GT• GT + O/H LINE DIFFERENTIAL – 87TLGT + O/H LINE DIFFERENTIAL – 87TL

Page 7: Generator & Transformer Protection

CLASS A1 – CAUSES – BACKUP CLASS A1 – CAUSES – BACKUP PROTECTIONS FOR PROTECTIONS FOR GENERATORGENERATOR BACKUP PROTECTIONS FOR BACKUP PROTECTIONS FOR

GENERATORGENERATOR

• GENERATOR LBB (For GCB) – 50GLBBGENERATOR LBB (For GCB) – 50GLBB

• GENERATOR BACKUP IMPEDANCE – GENERATOR BACKUP IMPEDANCE – 21G21G

• DEAD MACHINE RELAY – 50GDMDEAD MACHINE RELAY – 50GDM

Page 8: Generator & Transformer Protection

CLASS A1 – CAUSES – OTHER CLASS A1 – CAUSES – OTHER BACKUP PROTECTIONSBACKUP PROTECTIONS

• SWITCHYARD TEE DIFFERENTIAL – SWITCHYARD TEE DIFFERENTIAL – 87TTIGX/87TT2GX87TTIGX/87TT2GX

• 400 KV BREAKER LBB – X52Z400 KV BREAKER LBB – X52Z (8-52/9-52/13-52/14-52)(8-52/9-52/13-52/14-52)

• 400KV BREAKER POLE DISCREPENCY -400KV BREAKER POLE DISCREPENCY -X52PDXX52PDX

(8-52/9-52/13-52/14-52) – DEFEATED(8-52/9-52/13-52/14-52) – DEFEATED

Page 9: Generator & Transformer Protection

CLASS A1 - ACTIONSCLASS A1 - ACTIONS

CLASS A1 CAUSES TRIPPING OFCLASS A1 CAUSES TRIPPING OF

• BOTH 400KV BREAKERS OF THE UNITBOTH 400KV BREAKERS OF THE UNIT

• GCBGCB

• FIELD BREAKERFIELD BREAKER

• STEAM TURBINESTEAM TURBINE

• UNIT TRANSFORMER INCOMERS – BA/BBUNIT TRANSFORMER INCOMERS – BA/BB

Page 10: Generator & Transformer Protection

CLASS A2 - CAUSESCLASS A2 - CAUSES

GENERATOR PROTECTIONSGENERATOR PROTECTIONS

• DIFFERENTIAL – 87G1/87G2DIFFERENTIAL – 87G1/87G2

• OVERVOLTAGE – 59G1OVERVOLTAGE – 59G1

• 95% EARTH FAULT -64G195% EARTH FAULT -64G1

• INTERTURN FAULT – 64GITINTERTURN FAULT – 64GIT

• OVERFLUXING – 99GOVERFLUXING – 99G

• NEGATIVE PHASE SEQUENCE – 46GNEGATIVE PHASE SEQUENCE – 46G

• LOW FORWARD POWER – 30sec – 37G1/2LOW FORWARD POWER – 30sec – 37G1/2

.. Contd... Contd.

Page 11: Generator & Transformer Protection

CLASS A2 - CAUSESCLASS A2 - CAUSES

GENERATOR PROTECTIONSGENERATOR PROTECTIONS

• POLE SLIPPING – 98GPOLE SLIPPING – 98G

• FIELD FAILURE – 40 G1/2FIELD FAILURE – 40 G1/2

..contd...contd.

Page 12: Generator & Transformer Protection

CLASS A2 - CAUSESCLASS A2 - CAUSES

SIEMENS MULTIFUNCTION RELAY – SIEMENS MULTIFUNCTION RELAY – 96G96G

• 100% STATOR EARTH FAULT100% STATOR EARTH FAULT

• ROTOR EARTH FAULTROTOR EARTH FAULT

• OVER VOLTAGEOVER VOLTAGE

Page 13: Generator & Transformer Protection

CLASS A2 - ACTIONSCLASS A2 - ACTIONS

CLASS A2 CAUSES TRIPPING OF CLASS A2 CAUSES TRIPPING OF

• GCBGCB

• FIELD BREAKERFIELD BREAKER

• STEAM TURBINESTEAM TURBINE

• UT INCOMER (if both 400kV breakers UT INCOMER (if both 400kV breakers are in tripped condition)are in tripped condition)

Page 14: Generator & Transformer Protection

CLASS B PROTECTIONCLASS B PROTECTION CLASS B – GENERATOR TRIP FROM TURBINE CLASS B – GENERATOR TRIP FROM TURBINE

TRIPTRIP

THIS IS ACHIEVED THROUGH LOW THIS IS ACHIEVED THROUGH LOW FORWARD POWER RELAY – 2 SEC DELAY- FORWARD POWER RELAY – 2 SEC DELAY- 37 G1/237 G1/2

NEED FOR CLASS B TRIPNEED FOR CLASS B TRIP

PROTECTION OF TURBINE FROM PROTECTION OF TURBINE FROM OVERHEATINGOVERHEATING

Page 15: Generator & Transformer Protection

CLASS B - ACTIONSCLASS B - ACTIONS

CLASS B CAUSES TRIPPING OF THE CLASS B CAUSES TRIPPING OF THE FOLLOWINGFOLLOWING

• GCBGCB• FIELD BREAKERFIELD BREAKER

(i.e. GT & UT will still be in charged (i.e. GT & UT will still be in charged condition from 400kV side – GRID)condition from 400kV side – GRID)

Page 16: Generator & Transformer Protection

CLASS C PROTECTION - CLASS C PROTECTION - CAUSESCAUSES

CLASS C IS CAUSED ONLY BY – CLASS C IS CAUSED ONLY BY –

UNDERFREQUENCY- UNDERFREQUENCY- 81G/96G81G/96G

(GRID COLLAPSE)(GRID COLLAPSE)

Presently connected to Class B at 45Hz.Presently connected to Class B at 45Hz.

Page 17: Generator & Transformer Protection

CLASS C PROTECTION - CLASS C PROTECTION - ACTIONSACTIONS

CLASS C CAUSES TRIPPING OFCLASS C CAUSES TRIPPING OF

• BOTH 400KV BREAKERSBOTH 400KV BREAKERS

(i.e. Unit will come on house load)(i.e. Unit will come on house load)

Page 18: Generator & Transformer Protection

ACTIONS IF CLASS A1 TRIP ACTIONS IF CLASS A1 TRIP OCCURSOCCURS

THE FOLLOWING ACTIONS ARE THE FOLLOWING ACTIONS ARE NECESSARYNECESSARY

• Restore unit supply if auto changeover Restore unit supply if auto changeover from standby trf. does not take placefrom standby trf. does not take place

• Ensure DG set availabilityEnsure DG set availability

• Inform Electrical MaintenanceInform Electrical Maintenance

Page 19: Generator & Transformer Protection

ACTIONS IF CLASS A2 ACTIONS IF CLASS A2 OCCURSOCCURS

THE FOLLOWING ACTIONS ARE THE FOLLOWING ACTIONS ARE NECESSAYNECESSAY

• Ensure unit supplies are healthyEnsure unit supplies are healthy

• Inform Electrical MaintenanceInform Electrical Maintenance

Page 20: Generator & Transformer Protection

CLASS A2 – LOW FORWARD CLASS A2 – LOW FORWARD RELAYRELAY

THE FOLLOWING SEQUENCE OF THE FOLLOWING SEQUENCE OF EVENTS OCCURSEVENTS OCCURS

• CLASS A2 TRIP – TRIP TO STEAM CLASS A2 TRIP – TRIP TO STEAM TURBINETURBINE

• AFTER TRUBINE TRIP – CLASS BAFTER TRUBINE TRIP – CLASS B

Page 21: Generator & Transformer Protection

CLASS A2 – LOW FORWARD CLASS A2 – LOW FORWARD RELAYRELAY

RESTARTINGRESTARTINGTHE FOLLOWING SEQUENCE OF EVENTS THE FOLLOWING SEQUENCE OF EVENTS

MUST BE FOLLOWEDMUST BE FOLLOWED

• RESET BOTH CLASS A2 TRIP RELAYSRESET BOTH CLASS A2 TRIP RELAYS• RESET STEAM TURBINE TRIPRESET STEAM TURBINE TRIP• RESET BOTH CLASS B TRIP RELAYSRESET BOTH CLASS B TRIP RELAYS• SYNCHRONISE USNIG GCBSYNCHRONISE USNIG GCB

Note: Reset trip relays only when Note: Reset trip relays only when starting to rollstarting to roll

Page 22: Generator & Transformer Protection

CLASS B TRIP - RESTARTINGCLASS B TRIP - RESTARTING

THE FOLLOWING SEQUENCE OF ACTIONS THE FOLLOWING SEQUENCE OF ACTIONS MUST BE FOLLOWEDMUST BE FOLLOWED

• RESET STEAM TURBINE RESET STEAM TURBINE • RESET BOTH CLASS B TRIP RELAYSRESET BOTH CLASS B TRIP RELAYS• SYNCHRONISE UNING GCBSYNCHRONISE UNING GCB

Note: Reset trip relays only when Note: Reset trip relays only when starting to rollstarting to roll

Page 23: Generator & Transformer Protection

CLASS C TRIP - ACTIONSCLASS C TRIP - ACTIONS

• Ensure unit has come on HOUSE Ensure unit has come on HOUSE LOAD and stabilizedLOAD and stabilized

• Ensure availability of DG setEnsure availability of DG set

• Inform Electrical MaintenanceInform Electrical Maintenance

Page 24: Generator & Transformer Protection

CLASS C - RESTARTINGCLASS C - RESTARTING

THE FOLLOWING SEQUENCE OF THE FOLLOWING SEQUENCE OF ACTIONS MUST BE FOLLOWEDACTIONS MUST BE FOLLOWED

• Energise 400KV switchyardEnergise 400KV switchyard

• After getting concurrence from After getting concurrence from SRLDC synchronise the unit using SRLDC synchronise the unit using 400KV breakers 400KV breakers

Page 25: Generator & Transformer Protection

STARTUP/TRIPPING RELAY-STARTUP/TRIPPING RELAY-RESETTINGRESETTING

• Just before rolling only, reset the trip Just before rolling only, reset the trip relaysrelays

• After excitation, in case any of the After excitation, in case any of the fuse fail relays/50GDM flag has fallen fuse fail relays/50GDM flag has fallen reset themreset them

• After synchronisation, see that no After synchronisation, see that no relays have acted. relays have acted.

• If the Low forward power relay LED If the Low forward power relay LED has come, it should be reset.has come, it should be reset.

Page 26: Generator & Transformer Protection

THANKYOUTHANKYOU

Page 27: Generator & Transformer Protection

QUESTIONS QUESTIONS

PLEASEPLEASE