Total System Efficiency when Specifying VFD’s for Sustainable Buildings John Conboy Director of Sales & Marketing – Drives MENA

Transcript of Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System...

Page 1: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

Total System Efficiency when Specifying VFD’s for Sustainable BuildingsJohn ConboyDirector of Sales & Marketing – Drives MENA

Page 2: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The Facts

Page 3: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

3 | Danfoss Drives | Energy Efficiency

20%of the world’s energy consumptionis electrical energy

50%of electrical energy is used byelectric motors

100%of electric motors are oversized

75%of electric motors are used on Variable Torque load

50%reduction of energy consumption for a 20% reduction of flow

20%of electric motors use a VFD for control

Page 4: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

4 | Danfoss Drives | Energy Efficiency

8%of global electricity consumption by 2040

AC drives have the potential to save

Page 5: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The Science

Page 6: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

6 | Danfoss Drives | Energy Efficiency

The Affinity Law

100

70

00 70 100

Flow

, %

Speed, %

N2 N1

Q1

Q2

100

49

00 70 100

Pre

ssu

re, %

Speed, %

N2 N1

P1

P2

100

34

00 70 100

Pow

er, %

Speed, %

N2 N1

HP1

HP2

Affinity Laws of Centrifugal Loads:

FLOW is a proportional to motor speed

PRESSURE is proportional to the motor speed squared

POWER is proportional to the motor speed cubed

N = Speed

Q = Flow

P = Pressure

HP = Horsepower

Q2

Q1

N2

N1=

P2

P1

N2

N1=

2HP2

HP1

N2

N1=

3

Page 7: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

7 | Danfoss Drives | Energy Efficiency

Pump control methods

Source of images: https://www.linkedin.com/pulse/comparison-different-flow-control-methods-pumps-mircea-tomescu/

Flow Control Methods

Page 8: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

8 | Danfoss Drives | Energy Efficiency

Fan control methods Flow Control Methods

Outlet Damper Inlet Box Damper Variable Inlet Vane Variable Frequency Drive

% Design Flow%

Des

ign

KW

120

100

80

60

40

20

040 50 60 70 80 9030 100

Page 9: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

9 | Danfoss Drives | Energy Efficiency

Why do we do this?

Page 10: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The Standards

Page 11: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

11 | Danfoss Drives | Energy Efficiency

Definitions according to IEC61800-9

Extended Product

Motor System

Power Drive System (PDS)

Motor Starter(Contactor, Softstarter,…)

Trans-mission

Driven Equipment

Load-machine

Mains & cabling

Complete Drive Module (CDM)

Often named as VSD (Variable Speed Drive)

Feedingsection

Aux-ilaries

BasicDrive

Module (BDM)

Page 12: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

12 | Danfoss Drives | Energy Efficiency

Ecodesign from around the world

• Ecodesign is an approach to designing products with special consideration for the environmental impacts of the product during its whole lifecycle – it includes but is not limited to energy efficiency

• Around the world, various countries implement eco-design policies for motor systems

• The requirements are called MEPS (Minimum Efficiency Performance Standard)

Page 13: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

13 | Danfoss Drives | Energy Efficiency

Classification of motors and drives

IEC/EN 60034-30-1

• Fixed speed motors (DOL)• Classes IE1 – IE4

IEC/EN 60034-30-2

• Variable speed operation• Classes IE1 – IE5

IEC/EN 61800-9-2

• Complete Drive Module (CDM)• Classes IE0 – IE2

IEC/EN 61800-9-2

• Power Drive System (PDS)• Classes IES0 – IES2

Motor

Drive

Drive + motor

Page 14: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

14 | Danfoss Drives | Energy Efficiency

Part load losses

• Part load losses are defined in the nominal point and in 7 additional part load points for:

• CDM (drive)• PDS (drive + motor)

• Note that the nominal point for drives is 90% of nominal load and 100% for systems

• Part load losses can be determined in any point by interpolating between the 8 standardized points

Relative torque [%]

0%0% 100%

100%

50%

25%

50%

Relative speed [%]

CDM

PDS

Relative torque producing current [%]

0%0% 90%

100%

50%

25%

50%

Relative motorstator frequency

[%]

Arbitrary load point

Page 15: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

15 | Danfoss Drives | Energy Efficiency

Extended product approach

• The extended product approach combines the losses or efficiency of the motor system with the losses/efficiency of the driven system (pump, fan, conveyor, etc.)

• Based on the losses or efficiency of the extended product, the energy efficiency index (EEI) can be calculated for a given load-time duty profile

• Knowing the part load losses for the motor-drive system is essential for calculating the EEI, which is the ultimate purpose of the ecodesign standard

Page 16: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The products that will affect Total System Efficiency

The Motor

Page 17: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

17 | Danfoss Drives | Energy Efficiency

Comparison of efficienciesVentilation Unit with IE2, IE3 and IE4 motor

Page 18: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The products that will affect Total System Efficiency

The Fan

Page 19: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

19 | Danfoss Drives | Energy Efficiency

Comparison test – same installationAir Handling Unit, manufactured by Trubel Luft-und Klimatechnik GmbH

AHU w. Radial Fan (Plug Fan) AHU w. High Efficiency Axial Fan

Radial Fan (Plug fan)High Efficiency Axial Fan

Page 20: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

20 | Danfoss Drives | Energy Efficiency

Energy cost saving

Energy SavingHigh Efficiency Axial Fan vs. Radial Fan (Plug Fan)

Page 21: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The products that will affect Total System Efficiency

The DriveInstalled Efficiency

Heat lossHarmonics

Page 22: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

22 | Danfoss Drives | Energy Efficiency

Input:kW System

++

+ +

Installed or “wire to air” or “wire to water” efficiency is the trend:

Motor/AC drive CAPEX/OPEX split

Investment

Electricity

Harmonic mitigation

AC unit

Installed energy efficiency is important

Page 23: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

23 | Danfoss Drives | Energy Efficiency

110 kW 50 Hz, 4 pole motor:• IE 1 = 93,3 %• IE 2 = 94,5 %• IE 3 = 95,4 %

Energy efficiency difference for a 110 kW IE 2 vs IE 3 motor is 0,9 %, price ~15-20 % - 0,9 % efficiency gain seems important !

Which item of efficiency is most important?

Page 24: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

24 | Danfoss Drives | Energy Efficiency

There are many solutions:

• Low Harmonic Drive - AAF based

• Low Harmonic Drive – AFE based

• Central/Sep. solutions – AAF based

• Passive Harmonic solutions

Heatloss/efficiency difference between AAF vs AFE

0

10,000

20,000

30,000

40,000

50,000

AQUA AAF

NXC AFE

Heat loss W

PowerSize

Energy Efficiency harmonic mitigation

Page 25: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

25 | Danfoss Drives | Energy Efficiency

Additional benefits for AAF:

• AAF sleep mode saves energy

• If the AAF fails, the drive will continue

• The AAF creates lower boost voltage and less motor stress than the AFE

Power Heat Loss W AAF/AFE Size kW AAF AFE Difference conv. to efficiency

160 8.725 11.356 2.631 1,6%200 9.831 13.731 3.900 2,0%250 11.371 18.753 7.382 3,0%355 15.320 23.610 8.290 2,3%400 17.180 26.166 8.986 2,2%450 18.447 29.986 11.539 2,6%500 21.909 33.768 11.859 2,4%560 24.592 38.241 13.649 2,4%630 26.640 40.574 13.934 2,2%710 30.519 46.524 16.005 2,3%

Comparison of heat loss at <5% THD

Page 26: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

26 | Danfoss Drives | Energy Efficiency

Typically 0.4W of energy needed to remove 1W of heat.

The energy saving for a 160 kW drive will be about 15 % of investment made in standard AC drive

90%

160 kW AC drive standard: Heatloss 3770 W. AC saving ~ 3770 * 0,9 * 0,4 AC * 0,1 € * 0,6 load * 24 h * 365 d = 713 € ~ 15 % of AC drive purchase price

Intelligent heat managementPart of installed efficiency

90%Reduction in energy use

for air condition

Page 27: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

27 | Danfoss Drives | Energy Efficiency

0.0%

0.5%

1.0%

1.5%

2.0%

2.5%

3.0%

3.5%

160 200 250 355 400 450 500 560 630 710

conv. to eff.

AC Eff saving

0.0%

5.0%

10.0%

15.0%

20.0%

25.0%

30.0%

35.0%

40.0%

45.0%

160 200 250 355 400 450 500 560 630 710

Total

Heat loss AAF/AFE

AC saving

Efficiency % gain

Power size

Power size

Basis for calculations: LHD AC Drive, 0,1 €/kWh, 60 % load, 24/7 operation, 0,4 W AC/W removed

Options Efficiency gained

IE 2 to IE 3 motor 0,9 %

Backchannel cooling ~ 2,5 %

AAF vs AFE 1,6 – 3,0 %

Options Savings % of Inv.

Backchannel cooling 12 – 20 %

AAF vs AFE 7 – 23 %

Total 20 – 43 %

% Savings per year/Inv. in AC drive

Which item of efficiency is most important?

Page 28: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

The Summary

Page 29: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

29 | Danfoss Drives | Energy Efficiency

Summary

• Consider Energy Efficiency in all parts of your HVAC Systems

• Specify high efficient Drive and Motor Systems to meet IEC/EN 61800-9-2 Class IES2 and capability for more motor technologies with same drive (future proof)

• Specify highest efficiency fans, pumps and compressors

• Apply an Extended Product Approach and Specify Energy Efficiency Index• Utilize intelligent Heat Management e.g. Back-Channel Cooling.

• There are no regulations, which require THDi ≤ 5% at drive mains terminals.

• Apply IEEE-519 recommended limits at the PCC only and not to individual pieces of equipment.

• Do not use harmonics mitigation equipment, if it is not needed.

Page 30: Total System Efficiency when Specifying VFD’s for Sustainable … · 2019-12-29 · Total System Efficiency when Specifying VFD’s for Sustainable Buildings. John Conboy. Director

THANK YOUFOR ATTENDING THE PRESENTATION